AG1-553 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:57
Cordova 345 kV
236.4 MW Capacity / 284.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-553 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar; Storage generating facility located in the ComEd zone — Rock Island County, Illinois. The installed facilities will have a total capability of 284.0 MW with 236.4 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-553 |
| Project Name | Cordova 345 kV |
| Developer Name | Fowl Solar, LLC |
| State | Illinois |
| County | Rock Island |
| Transmission Owner | ComEd |
| MFO | 284.0 MW |
| MWE | 284.0 MW |
| MWC | 236.4 MW |
| Fuel Type | Solar; Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-553 will interconnect on the ComEd transmission system by tying into the 345kV bus at TSS 940 Cordova Energy Center substation.
Summer Peak Analysis
The Queue Project was evaluated as a 284.0 MW (Capacity 236.4 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 183.54 % | 185.3 % | 1409.0 | B | 2610.93 | 29.36 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 183.54 % | 185.3 % | 1409.0 | B | 2610.89 | 29.36 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
Base Case | Single | AC | 137.96 % | 138.63 % | 1409.0 | A | 1953.32 | 16.18 | |
| CE |
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
924470 to 270883 ckt 1 |
COMED_P1-2_345-L18905__B-R-B-2
CONTINGENCY 'COMED_P1-2_345-L18905__B-R-B-2' TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Single | AC | 122.38 % | 123.99 % | 1568.0 | STE | 1944.16 | 23.73 | |
| CE |
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
924470 to 270883 ckt 1 |
COMED_P1-2_345-L18905__B-R-B-1
CONTINGENCY 'COMED_P1-2_345-L18905__B-R-B-1' TRIP BRANCH FROM BUS 962700 TO BUS 965553 CKT 1 /*AG1-119 TAP 345.0 - AG1-423 TP 345.0 END |
Single | AC | 120.36 % | 121.99 % | 1568.0 | STE | 1912.84 | 23.73 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 124.51 % | 126.33 % | 971.0 | STE | 1226.69 | 20.27 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 124.51 % | 126.33 % | 971.0 | STE | 1226.69 | 20.27 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545
CONTINGENCY 'EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545' OPEN BRANCH FROM BUS 249521 TO BUS 347340 CKT 1 /*08SUGCRK 345.0 - 7KANSAS 345.0 END |
Single | AC | 124.59 % | 125.75 % | 1466.0 | B | 1843.44 | 18.77 | |
| CE |
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
270694 to 924470 ckt 1 |
COMED_P1-2_345-L18905__B-R-B-2
CONTINGENCY 'COMED_P1-2_345-L18905__B-R-B-2' TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Single | AC | 116.54 % | 118.14 % | 1568.0 | STE | 1852.45 | 23.73 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P1-2_345-L1202__B-S
CONTINGENCY 'COMED_P1-2_345-L1202__B-S' TRIP BRANCH FROM BUS 270716 TO BUS 930770 CKT 1 /*DRESDEN ; B 345.0 - AB1-122 TAP2 345.0 END |
Single | AC | 115.74 % | 117.09 % | 1568.0 | STE | 1835.9 | 20.71 | |
| CE |
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
270694 to 924470 ckt 1 |
COMED_P1-2_345-L18905__B-R-B-1
CONTINGENCY 'COMED_P1-2_345-L18905__B-R-B-1' TRIP BRANCH FROM BUS 962700 TO BUS 965553 CKT 1 /*AG1-119 TAP 345.0 - AG1-423 TP 345.0 END |
Single | AC | 114.53 % | 116.15 % | 1568.0 | STE | 1821.26 | 23.73 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B
CONTINGENCY 'EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B' OPEN BRANCH FROM BUS 990270 TO BUS 347340 CKT 1 /*J1263 TAP 345.0 - 7KANSAS 345.0 END |
Single | AC | 120.32 % | 121.4 % | 1466.0 | B | 1779.68 | 14.8 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 118.11 % | 119.95 % | 1399.0 | B | 1678.06 | 25.65 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 118.11 % | 119.94 % | 1399.0 | B | 1678.02 | 25.65 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
Base Case | Single | AC | 115.33 % | 116.57 % | 1334.0 | A | 1555.07 | 15.99 | |
| CE |
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
924470 to 270883 ckt 1 |
Base Case | Single | AC | 113.8 % | 115.32 % | 1201.0 | A | 1384.95 | 16.98 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
Base Case | Single | AC | 112.2 % | 113.9 % | 1201.0 | A | 1367.96 | 19.75 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P1-2_345-L9806__R-S
CONTINGENCY 'COMED_P1-2_345-L9806__R-S' TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1 /*NEVADA ; R 345.0 - GOODINGS ;2R 345.0 END |
Single | AC | 102.76 % | 104.18 % | 1568.0 | STE | 1633.51 | 21.35 | |
| CE |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line
957470 to 270730 ckt 1 |
Base Case | Single | AC | 107.9 % | 110.4 % | 1334.0 | A | 1472.7 | 41.26 | |
| CE/NIPS |
ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line
270886 to 255104 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 108.44 % | 110.07 % | 1091.0 | B | 1200.82 | 18.35 | |
| CE/NIPS |
17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line
255112 to 270886 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 108.44 % | 110.06 % | 1091.0 | B | 1200.81 | 18.35 | |
| CE/NIPS |
ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line
270886 to 255104 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 108.44 % | 110.06 % | 1091.0 | B | 1200.8 | 18.35 | |
| CE/NIPS |
17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line
255112 to 270886 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 108.44 % | 110.06 % | 1091.0 | B | 1200.79 | 18.35 | |
| AEP/CE |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line
270771 to 243229 ckt 1 |
EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A
CONTINGENCY 'EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A' OPEN BRANCH FROM BUS 255101 TO BUS 991245 CKT 1 /*17BURR_OAK 345.0 - J1684 TAP 345.0 END |
Single | AC | 108.82 % | 109.9 % | 971.0 | B | 1067.12 | 12.86 | |
| CE |
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
270694 to 924470 ckt 1 |
Base Case | Single | AC | 106.83 % | 108.33 % | 1201.0 | A | 1301.1 | 16.98 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 99.33 % | 100.91 % | 1483.0 | STE | 1496.55 | 26.02 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 99.32 % | 100.91 % | 1483.0 | STE | 1496.47 | 26.02 | |
| AEP/CE |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line
270771 to 243229 ckt 1 |
EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B
CONTINGENCY 'EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B' OPEN BRANCH FROM BUS 991245 TO BUS 990545 CKT 1 /*J1684 TAP 345.0 - J1333 TAP 345.0 END |
Single | AC | 105.56 % | 106.64 % | 971.0 | B | 1035.45 | 12.86 | |
| AEP |
05DUMONT-05SORENS 765.0 kV Ckt 1 line
243206 to 246999 ckt 1 |
AEP_P1-2_#709_546
CONTINGENCY 'AEP_P1-2_#709_546' OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 END |
Single | AC | 105.7 % | 106.36 % | 4142.0 | B | 4405.27 | 45.31 | |
| AEP |
05DUMONT-05SORENS 765.0 kV Ckt 1 line
243206 to 246999 ckt 1 |
AEP_P1-2_#9287_1679
CONTINGENCY 'AEP_P1-2_#9287_1679' OPEN BRANCH FROM BUS 243206 TO BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 END |
Single | AC | 103.85 % | 104.81 % | 4142.0 | B | 4341.06 | 45.61 | |
| CE |
AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line
965553 to 270916 ckt 1 |
COMED_P1-2_345-L97104__-R
CONTINGENCY 'COMED_P1-2_345-L97104__-R' TRIP BRANCH FROM BUS 924470 TO BUS 270883 CKT 1 /*GARDEN PR; R 345.0 - SILVER LK; R 345.0 END |
Single | AC | 101.06 % | 102.37 % | 2107.0 | STE | 2156.85 | 26.62 | |
| CE/MEC |
QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line
270866 to 636610 ckt 1 |
EXT_P12:345:MEC:CORDOVA:SUB 39
CONTINGENCY 'EXT_P12:345:MEC:CORDOVA:SUB 39' OPEN BRANCH FROM BUS 636600 TO BUS 636605 CKT 1 /*SB 39 3 345.0 - MECCORD3 345.0 END |
Single | AC | 99.8 % | 104.35 % | 1471.0 | B | 1534.94 | 68.46 | |
| CE |
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
270730 to 270812 ckt 1 |
Base Case | Single | AC | 102.34 % | 103.23 % | 1201.0 | A | 1239.8 | 12.99 | |
| CE |
AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line
965553 to 270916 ckt 1 |
COMED_P1-2_345-L15616__-R
CONTINGENCY 'COMED_P1-2_345-L15616__-R' TRIP BRANCH FROM BUS 270694 TO BUS 924470 CKT 1 /*CHERRY VA; B 345.0 - GARDEN PR; R 345.0 END |
Single | AC | 98.73 % | 100.03 % | 2107.0 | STE | 2107.66 | 26.62 | |
| CE |
AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line
965553 to 270916 ckt 1 |
Base Case | Single | AC | 101.0 % | 102.27 % | 1679.0 | A | 1717.08 | 21.43 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3128_05EUGENE 345_A2
CONTINGENCY 'AEP_P4_#3128_05EUGENE 345_A2' OPEN BRANCH FROM BUS 243221 TO BUS 249504 CKT 1 /*05EUGENE 345.0 - 08CAYSUB 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 171.37 % | 171.8 % | 1466.0 | B | 2518.53 | 22.71 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3130_05EUGENE 345_B2
CONTINGENCY 'AEP_P4_#3130_05EUGENE 345_B2' OPEN BRANCH FROM BUS 243221 TO BUS 247712 CKT 1 /*05EUGENE 345.0 - 05SULLIVAN 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 157.96 % | 158.28 % | 1466.0 | B | 2320.34 | 23.02 | |
| CE |
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
924470 to 270883 ckt 1 |
COMED_P4_144-45-BT6-8__
CONTINGENCY 'COMED_P4_144-45-BT6-8__' TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Breaker | AC | 146.28 % | 147.87 % | 1568.0 | STE | 2318.54 | 28.51 | |
| CE |
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
924470 to 270883 ckt 1 |
COMED_P4_144-45-BT6-7__
CONTINGENCY 'COMED_P4_144-45-BT6-7__' DISCONNECT BUS 275228 /*WAYNE ;1M 138.0 TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270900 CKT 1 /*WAYNE ; B 345.0 - TOLLWAY ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 END |
Breaker | AC | 146.28 % | 147.86 % | 1568.0 | STE | 2318.51 | 28.51 | |
| CE |
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
270694 to 924470 ckt 1 |
COMED_P4_144-45-BT6-8__
CONTINGENCY 'COMED_P4_144-45-BT6-8__' TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Breaker | AC | 136.78 % | 138.36 % | 1568.0 | STE | 2169.52 | 28.51 | |
| CE |
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
270694 to 924470 ckt 1 |
COMED_P4_144-45-BT6-7__
CONTINGENCY 'COMED_P4_144-45-BT6-7__' DISCONNECT BUS 275228 /*WAYNE ;1M 138.0 TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270900 CKT 1 /*WAYNE ; B 345.0 - TOLLWAY ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 END |
Breaker | AC | 136.78 % | 138.36 % | 1568.0 | STE | 2169.47 | 28.51 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_116-45-L11614_
CONTINGENCY 'COMED_P4_116-45-L11614_' DISCONNECT BUS 270769 /*GOODINGS ;2R 345.0 TRIP BRANCH FROM BUS 270667 TO BUS 270665 CKT 1 /*BLUE ISL ;RT 345.0 - BLUE ISL ; R 345.0 TRIP BRANCH FROM BUS 270667 TO BUS 270927 CKT 1 /*BLUE ISL ;RT 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 270769 TO BUS 270667 CKT 1 /*GOODINGS ;2R 345.0 - BLUE ISL ;RT 345.0 END |
Breaker | AC | 119.42 % | 120.33 % | 2083.0 | STE | 2506.46 | 21.82 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_116-45-TR82___
CONTINGENCY 'COMED_P4_116-45-TR82___' DISCONNECT BUS 270769 /*GOODINGS ;2R 345.0 TRIP BRANCH FROM BUS 270769 TO BUS 271565 TO BUS 275324 CKT 1 /*GOODINGS ;2R 345.0 - GOODINGS ; R 138.0 - GOODINGS ;2C 34.5 END |
Breaker | AC | 115.26 % | 116.17 % | 2083.0 | STE | 2419.8 | 21.81 | |
| CE |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line
957470 to 270730 ckt 1 |
COMED_P4_937-45-BT2-3__
CONTINGENCY 'COMED_P4_937-45-BT2-3__' REMOVE UNIT 1 FROM BUS 274760 /*LEE CO EC;1U 13.8 REMOVE UNIT 2 FROM BUS 274761 /*LEE CO EC;2U 13.8 REMOVE UNIT 3 FROM BUS 274762 /*LEE CO EC;3U 13.8 REMOVE UNIT 4 FROM BUS 274763 /*LEE CO EC;4U 13.8 REMOVE UNIT 5 FROM BUS 274764 /*LEE CO EC;5U 13.8 REMOVE UNIT 6 FROM BUS 274765 /*LEE CO EC;6U 13.8 REMOVE UNIT 7 FROM BUS 274766 /*LEE CO EC;7U 13.8 REMOVE UNIT 8 FROM BUS 274767 /*LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274760 TO BUS 274761 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;1U 13.8 - LEE CO EC;2U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274762 TO BUS 274763 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;3U 13.8 - LEE CO EC;4U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274764 TO BUS 274765 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;5U 13.8 - LEE CO EC;6U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274766 TO BUS 274767 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;7U 13.8 - LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 274759 CKT 1 /*LEE CO EC;BP 345.0 - LEE CO EC; 345.0 END |
Breaker | AC | 117.07 % | 120.85 % | 1837.0 | STE | 2219.93 | 67.38 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_116-45-L0303__
CONTINGENCY 'COMED_P4_116-45-L0303__' DISCONNECT BUS 270769 /*GOODINGS ;2R 345.0 REMOVE SWSHUNT FROM BUS 270827 /*NEVADA ; R 345.0 TRIP BRANCH FROM BUS 936290 TO BUS 270827 CKT 1 /*AD2-038 TAP 345.0 - NEVADA ; R 345.0 END |
Breaker | AC | 113.55 % | 114.45 % | 2083.0 | STE | 2384.01 | 21.81 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_112-45-BT4-5__
CONTINGENCY 'COMED_P4_112-45-BT4-5__' TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1 /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1 /*BLUE ISL ;BT 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1 /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0 TRIP BRANCH FROM BUS 270852 TO BUS 270704 CKT 1 /*PONTIAC ; B 345.0 - LORETTO ; B 345.0 END |
Breaker | AC | 112.01 % | 113.41 % | 2083.0 | STE | 2362.28 | 27.32 | |
| CE |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line
957470 to 270730 ckt 1 |
COMED_P4_006-45-BT3-8__
CONTINGENCY 'COMED_P4_006-45-BT3-8__' TRIP BRANCH FROM BUS 270678 TO BUS 270679 CKT 1 /*BYRON ; B 345.0 - BYRON ; R 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 END |
Breaker | AC | 114.62 % | 117.11 % | 1837.0 | STE | 2151.34 | 67.28 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_076-45-BT4-5__
CONTINGENCY 'COMED_P4_076-45-BT4-5__' TRIP BRANCH FROM BUS 270664 TO BUS 275162 CKT 1 /*BLUE ISL ; B 345.0 - BLUE ISL ;3M 138.0 TRIP BRANCH FROM BUS 270664 TO BUS 275181 CKT 1 /*BLUE ISL ; B 345.0 - BLUE ISL ;4M 138.0 TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1 /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1 /*BLUE ISL ;BT 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 270674 TO BUS 270664 CKT 1 /*BURNHAM ; B 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1 /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0 TRIP BRANCH FROM BUS 275162 TO BUS 271100 CKT 1 /*BLUE ISL ;3M 138.0 - BLUE ISL ; B 138.0 TRIP BRANCH FROM BUS 275181 TO BUS 271100 CKT 1 /*BLUE ISL ;4M 138.0 - BLUE ISL ; B 138.0 TRIP BRANCH FROM BUS 275262 TO BUS 275162 CKT 1 /*BLUE ISLA;3C 34.5 - BLUE ISL ;3M 138.0 TRIP BRANCH FROM BUS 275281 TO BUS 275181 CKT 1 /*BLUE ISLA;4C 34.5 - BLUE ISL ;4M 138.0 END |
Breaker | AC | 108.67 % | 109.8 % | 2083.0 | STE | 2287.12 | 27.02 | |
| CE |
PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer
275207 to 270630 ckt 1 |
COMED_P4_167-45-BT5-6__
CONTINGENCY 'COMED_P4_167-45-BT5-6__' TRIP BRANCH FROM BUS 270846 TO BUS 270847 CKT 1 /*PLANO ; B 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 270847 TO BUS 270733 CKT 1 /*PLANO ; R 345.0 - ELECT JCT;3R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1 /*PLANO ;4M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1 /*PLANO ;4M 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1 /*PLANO ;4M 345.0 - PLANO ;4C 33.0 END |
Breaker | AC | 117.63 % | 118.02 % | 1469.0 | STE | 1733.72 | 20.85 | |
| CE |
PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line
270846 to 275207 ckt 1 |
COMED_P4_167-45-BT5-6__
CONTINGENCY 'COMED_P4_167-45-BT5-6__' TRIP BRANCH FROM BUS 270846 TO BUS 270847 CKT 1 /*PLANO ; B 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 270847 TO BUS 270733 CKT 1 /*PLANO ; R 345.0 - ELECT JCT;3R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1 /*PLANO ;4M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1 /*PLANO ;4M 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1 /*PLANO ;4M 345.0 - PLANO ;4C 33.0 END |
Breaker | AC | 117.54 % | 117.94 % | 1469.0 | STE | 1732.56 | 20.85 | |
| CE |
PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer
275208 to 270630 ckt 1 |
COMED_P4_167-45-BT8-12_
CONTINGENCY 'COMED_P4_167-45-BT8-12_' TRIP BRANCH FROM BUS 270846 TO BUS 270730 CKT 1 /*PLANO ; B 345.0 - ELECT JCT; B 345.0 TRIP BRANCH FROM BUS 270846 TO BUS 272278 TO BUS 275354 CKT 1 /*PLANO ; B 345.0 - PLANO;1I 138.0 - PLANO;1C 34.5 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 1 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 2 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1 /*PLANO ;3M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1 /*PLANO ;3M 345.0 - PLANO ; B 345.0 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1 /*PLANO ;3M 345.0 - PLANO ;3C 33.0 END |
Breaker | AC | 115.66 % | 115.92 % | 1469.0 | STE | 1702.87 | 17.64 | |
| CE |
PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line
270847 to 275208 ckt 1 |
COMED_P4_167-45-BT8-12_
CONTINGENCY 'COMED_P4_167-45-BT8-12_' TRIP BRANCH FROM BUS 270846 TO BUS 270730 CKT 1 /*PLANO ; B 345.0 - ELECT JCT; B 345.0 TRIP BRANCH FROM BUS 270846 TO BUS 272278 TO BUS 275354 CKT 1 /*PLANO ; B 345.0 - PLANO;1I 138.0 - PLANO;1C 34.5 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 1 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 2 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1 /*PLANO ;3M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1 /*PLANO ;3M 345.0 - PLANO ; B 345.0 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1 /*PLANO ;3M 345.0 - PLANO ;3C 33.0 END |
Breaker | AC | 115.25 % | 115.51 % | 1469.0 | STE | 1696.78 | 17.64 | |
| CE |
AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line
965660 to 957470 ckt 1 |
COMED_P4_937-45-BT2-3__
CONTINGENCY 'COMED_P4_937-45-BT2-3__' REMOVE UNIT 1 FROM BUS 274760 /*LEE CO EC;1U 13.8 REMOVE UNIT 2 FROM BUS 274761 /*LEE CO EC;2U 13.8 REMOVE UNIT 3 FROM BUS 274762 /*LEE CO EC;3U 13.8 REMOVE UNIT 4 FROM BUS 274763 /*LEE CO EC;4U 13.8 REMOVE UNIT 5 FROM BUS 274764 /*LEE CO EC;5U 13.8 REMOVE UNIT 6 FROM BUS 274765 /*LEE CO EC;6U 13.8 REMOVE UNIT 7 FROM BUS 274766 /*LEE CO EC;7U 13.8 REMOVE UNIT 8 FROM BUS 274767 /*LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274760 TO BUS 274761 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;1U 13.8 - LEE CO EC;2U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274762 TO BUS 274763 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;3U 13.8 - LEE CO EC;4U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274764 TO BUS 274765 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;5U 13.8 - LEE CO EC;6U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274766 TO BUS 274767 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;7U 13.8 - LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 274759 CKT 1 /*LEE CO EC;BP 345.0 - LEE CO EC; 345.0 END |
Breaker | AC | 105.27 % | 108.99 % | 1837.0 | STE | 2002.22 | 67.38 | |
| CE |
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
270730 to 270812 ckt 1 |
COMED_P4_012-45-BT5-6__
CONTINGENCY 'COMED_P4_012-45-BT5-6__' TRIP BRANCH FROM BUS 270716 TO BUS 270736 CKT 1 /*DRESDEN ; B 345.0 - ELWOOD ; B 345.0 TRIP BRANCH FROM BUS 270736 TO BUS 270737 CKT 1 /*ELWOOD ; B 345.0 - ELWOOD ; R 345.0 TRIP BRANCH FROM BUS 274702 TO BUS 270716 CKT 1 /*KENDALL ;BU 345.0 - DRESDEN ; B 345.0 END |
Breaker | AC | 111.64 % | 112.64 % | 1568.0 | STE | 1766.13 | 18.45 | |
| CE |
AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line
965660 to 957470 ckt 1 |
COMED_P4_937-45-BT1-4__
CONTINGENCY 'COMED_P4_937-45-BT1-4__' REMOVE UNIT W1 FROM BUS 274857 /*BIG SKY ;U1 0.7 REMOVE UNIT W2 FROM BUS 274858 /*BIG SKY ;U2 0.7 TRIP BRANCH FROM BUS 271421 TO BUS 274450 CKT 1 /*EASY ROAD; B 138.0 - EASY ROAD;1 34.5 TRIP BRANCH FROM BUS 271421 TO BUS 274451 CKT 1 /*EASY ROAD; B 138.0 - EASY ROAD;2 34.5 TRIP BRANCH FROM BUS 272528 TO BUS 271421 CKT 1 /*S DIXON ; B 138.0 - EASY ROAD; B 138.0 TRIP BRANCH FROM BUS 274420 TO BUS 274857 CKT 1 /*EASY ROAD;1H 34.5 - BIG SKY ;U1 0.7 TRIP BRANCH FROM BUS 274421 TO BUS 274858 CKT 1 /*EASY ROAD;2H 34.5 - BIG SKY ;U2 0.7 TRIP BRANCH FROM BUS 274450 TO BUS 274420 CKT 1 /*EASY ROAD;1 34.5 - EASY ROAD;1H 34.5 TRIP BRANCH FROM BUS 274451 TO BUS 274421 CKT 1 /*EASY ROAD;2 34.5 - EASY ROAD;2H 34.5 TRIP BRANCH FROM BUS 274768 TO BUS 272528 CKT 1 /*LEE CO EC;BP 345.0 - S DIXON ; B 138.0 TRIP BRANCH FROM BUS 946150 TO BUS 274768 CKT 1 /*AF1-280 TAP 345.0 - LEE CO EC;BP 345.0 END |
Breaker | AC | 101.39 % | 105.11 % | 1837.0 | STE | 1930.81 | 67.39 | |
| CE |
AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line
965660 to 957470 ckt 1 |
COMED_P4_937-45-BT1-2__
CONTINGENCY 'COMED_P4_937-45-BT1-2__' TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 TRIP BRANCH FROM BUS 946150 TO BUS 274768 CKT 1 /*AF1-280 TAP 345.0 - LEE CO EC;BP 345.0 END |
Breaker | AC | 101.27 % | 104.98 % | 1837.0 | STE | 1928.56 | 67.39 | |
| CE |
AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line
965660 to 957470 ckt 1 |
COMED_P4_144-45-BT6-8__
CONTINGENCY 'COMED_P4_144-45-BT6-8__' TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Breaker | AC | 102.21 % | 104.73 % | 1837.0 | STE | 1923.81 | 54.4 | |
| CE |
AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line
965660 to 957470 ckt 1 |
COMED_P4_144-45-BT6-7__
CONTINGENCY 'COMED_P4_144-45-BT6-7__' DISCONNECT BUS 275228 /*WAYNE ;1M 138.0 TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270900 CKT 1 /*WAYNE ; B 345.0 - TOLLWAY ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 END |
Breaker | AC | 102.19 % | 104.7 % | 1837.0 | STE | 1923.29 | 54.4 | |
| CE |
NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer
270828 to 275204 ckt 1 |
COMED_P4_155-45-BT2-34_
CONTINGENCY 'COMED_P4_155-45-BT2-34_' TRIP BRANCH FROM BUS 270828 TO BUS 272094 TO BUS 275341 CKT 1 /*NELSON ; B 345.0 - NELSON ; B 138.0 - NELSON ;1C 34.5 TRIP BRANCH FROM BUS 270828 TO BUS 965660 CKT 1 /*NELSON ; B 345.0 - AG1-434 TAP 345.0 END |
Breaker | AC | 100.65 % | 103.12 % | 493.0 | STE | 508.36 | 14.33 | |
| CE |
NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line
270828 to 965660 ckt 1 |
COMED_P4_937-45-BT2-3__
CONTINGENCY 'COMED_P4_937-45-BT2-3__' REMOVE UNIT 1 FROM BUS 274760 /*LEE CO EC;1U 13.8 REMOVE UNIT 2 FROM BUS 274761 /*LEE CO EC;2U 13.8 REMOVE UNIT 3 FROM BUS 274762 /*LEE CO EC;3U 13.8 REMOVE UNIT 4 FROM BUS 274763 /*LEE CO EC;4U 13.8 REMOVE UNIT 5 FROM BUS 274764 /*LEE CO EC;5U 13.8 REMOVE UNIT 6 FROM BUS 274765 /*LEE CO EC;6U 13.8 REMOVE UNIT 7 FROM BUS 274766 /*LEE CO EC;7U 13.8 REMOVE UNIT 8 FROM BUS 274767 /*LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274760 TO BUS 274761 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;1U 13.8 - LEE CO EC;2U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274762 TO BUS 274763 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;3U 13.8 - LEE CO EC;4U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274764 TO BUS 274765 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;5U 13.8 - LEE CO EC;6U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274766 TO BUS 274767 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;7U 13.8 - LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 274759 CKT 1 /*LEE CO EC;BP 345.0 - LEE CO EC; 345.0 END |
Breaker | AC | 110.33 % | 114.48 % | 1656.0 | B | 1895.77 | 67.38 | |
| CE |
NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line
275204 to 272094 ckt 1 |
COMED_P4_155-45-BT2-34_
CONTINGENCY 'COMED_P4_155-45-BT2-34_' TRIP BRANCH FROM BUS 270828 TO BUS 272094 TO BUS 275341 CKT 1 /*NELSON ; B 345.0 - NELSON ; B 138.0 - NELSON ;1C 34.5 TRIP BRANCH FROM BUS 270828 TO BUS 965660 CKT 1 /*NELSON ; B 345.0 - AG1-434 TAP 345.0 END |
Breaker | AC | 99.01 % | 101.48 % | 493.0 | STE | 500.32 | 14.33 | |
| CE |
NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line
270828 to 965660 ckt 1 |
COMED_P4_144-45-BT6-8__
CONTINGENCY 'COMED_P4_144-45-BT6-8__' TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Breaker | AC | 107.72 % | 110.53 % | 1656.0 | B | 1830.31 | 54.4 | |
| CE |
CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line
274750 to 270728 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 100.01 % | 101.23 % | 1483.0 | STE | 1501.2 | 18.18 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P2-2_#286_05EUGENE 345_2
CONTINGENCY 'AEP_P2-2_#286_05EUGENE 345_2' OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Bus | AC | 158.08 % | 158.19 % | 1466.0 | B | 2318.99 | 23.0 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P2-2_116_GG-345R__2
CONTINGENCY 'COMED_P2-2_116_GG-345R__2' DISCONNECT BUS 270769 /*GOODINGS ;2R 345.0 END |
Bus | AC | 115.27 % | 116.17 % | 2083.0 | STE | 2419.85 | 21.81 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S' TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1 /*KATYDID ; B 345.0 - GOODINGS ;4B 345.0 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1 /*NEVADA ; R 345.0 - GOODINGS ;2R 345.0 END |
Tower | AC | 147.47 % | 148.96 % | 2033.0 | ALDR | 3028.32 | 28.43 | |
| AMIL/CE |
7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line
349662 to 930760 ckt 1 |
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S' TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1 /*KATYDID ; B 345.0 - GOODINGS ;4B 345.0 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1 /*NEVADA ; R 345.0 - GOODINGS ;2R 345.0 END |
Tower | AC | 164.25 % | 166.2 % | 1479.0 | B | 2458.04 | 28.43 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B
CONTINGENCY 'COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B' REMOVE SWSHUNT FROM BUS 270827 /*NEVADA ; R 345.0 TRIP BRANCH FROM BUS 270854 TO BUS 270790 CKT 1 /*POWERTON ; B 345.0 - KATYDID ; B 345.0 TRIP BRANCH FROM BUS 936290 TO BUS 270827 CKT 1 /*AD2-038 TAP 345.0 - NEVADA ; R 345.0 END |
Tower | AC | 135.64 % | 137.03 % | 2033.0 | ALDR | 2785.78 | 28.49 | |
| AMIL/CE |
7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line
349662 to 930760 ckt 1 |
COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B
CONTINGENCY 'COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B' REMOVE SWSHUNT FROM BUS 270827 /*NEVADA ; R 345.0 TRIP BRANCH FROM BUS 270854 TO BUS 270790 CKT 1 /*POWERTON ; B 345.0 - KATYDID ; B 345.0 TRIP BRANCH FROM BUS 936290 TO BUS 270827 CKT 1 /*AD2-038 TAP 345.0 - NEVADA ; R 345.0 END |
Tower | AC | 150.5 % | 152.6 % | 1479.0 | B | 2256.92 | 28.49 | |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 19.53 MW | 16.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 25.97 MW | 22.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 25.57 MW | 21.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 10.11 MW | 8.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 6.73 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 8.2 MW | 6.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 95.03 MW | 95.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 15.96 MW | 13.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 29.36 MW | 24.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 4.18 MW | 3.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 1.39 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965091 | AG1-374 C | Adder | 19.52 MW | 16.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 19.89 MW | 16.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 17.05 MW | 14.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 4.84 MW | 4.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 4.55 MW | 3.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 19.0 MW | 16.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 2.47 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 2.1 MW | 1.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.6 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 16.63 MW | 16.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 3.09 MW | 2.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 20.75 MW | 17.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 2.16 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 1.08 MW | 0.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 3.42 MW | 2.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 22.92 MW | 19.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 1.06 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 3.86 MW | 3.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 5.54 MW | 4.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 3.26 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 9.91 MW | 8.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.97 MW | 2.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 2.21 MW | 1.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 3.62 MW | 3.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 1.02 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 14.94 MW | 12.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 9.93 MW | 8.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 4.47 MW | 3.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 13.4 MW | 11.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 13.16 MW | 11.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 24.1 MW | 20.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 4.28 MW | 3.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 8.36 MW | 7.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 16.73 MW | 14.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 7.05 MW | 5.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 7.15 MW | 6.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 6.27 MW | 5.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 25.46 MW | 21.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 9.78 MW | 8.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 1.3 MW | 1.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 6.94 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 8.18 MW | 6.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 7.98 MW | 6.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 5.32 MW | 4.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 15.09 MW | 15.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274723 | RIVER EC ;12 | 80/20 | 5.49 MW | 5.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274724 | RIVER EC ;11 | 80/20 | 5.46 MW | 5.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | 80/20 | 7.55 MW | 7.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | 80/20 | 7.57 MW | 7.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274792 | SE CHICAG;9U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274793 | SE CHICAG;0U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274794 | SE CHICAG;1U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274795 | SE CHICAG;2U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274798 | UNIV PARK;1U | 80/20 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274799 | UNIV PARK;2U | 80/20 | 1.52 MW | 1.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274826 | FISK ;BP | 80/20 | 2.86 MW | 2.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274827 | FISK ;RP | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276164 | X3-005 C | 80/20 | 0.11 MW | 0.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276592 | O-012 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.68 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 42.84 MW | 36.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 34.06 MW | 28.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 80.68 MW | 68.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 86.94 MW | 73.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 3.1 MW | 2.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | Adder | 10.72 MW | 9.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 9.8 MW | 8.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 4.61 MW | 3.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 7.16 MW | 6.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 12.06 MW | 10.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 6.19 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 9.54 MW | 8.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 7.7 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 13.91 MW | 11.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 5.68 MW | 4.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 18.34 MW | 15.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 5.1 MW | 4.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 6.86 MW | 5.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 2.34 MW | 1.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 2.81 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 1.58 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | Adder | 1.65 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 25.1 MW | 21.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.28 MW | 0.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 22.18 MW | 18.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | Adder | 39.58 MW | 33.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.82 MW | 1.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 6.52 MW | 5.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 7.03 MW | 5.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 361.52 MW | 307.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 953871 | J847 | External Queue | 13.43 MW | 13.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 954751 | J351 | External Queue | 441.39 MW | 441.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 955741 | J1058 | External Queue | 24.2 MW | 24.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990541 | J1332 | External Queue | 26.68 MW | 26.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990646 | J1355 | External Queue | 43.02 MW | 43.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990661 | J1358 | External Queue | 15.6 MW | 15.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990761 | J1386 | External Queue | 13.07 MW | 13.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990976 | J1447 | External Queue | 28.98 MW | 28.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 991271 | J1724 | External Queue | 41.93 MW | 41.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 991331 | J1785 | External Queue | 13.63 MW | 13.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.77 MW | 1.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 101.19 MW | 101.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.78 MW | 26.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.57 MW | 0.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.99 MW | 4.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.62 MW | 15.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.62 MW | 0.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.01 MW | 2.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.38 MW | 4.38 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 19.53 MW | 16.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 25.97 MW | 22.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 25.57 MW | 21.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 10.11 MW | 8.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 6.73 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 8.2 MW | 6.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 95.03 MW | 95.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 15.96 MW | 13.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 29.36 MW | 24.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 4.18 MW | 3.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 1.39 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965091 | AG1-374 C | Adder | 19.52 MW | 16.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 19.89 MW | 16.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 17.05 MW | 14.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 4.84 MW | 4.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 4.55 MW | 3.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 19.0 MW | 16.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 2.47 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 2.1 MW | 1.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.6 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 16.63 MW | 16.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 3.09 MW | 2.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 20.75 MW | 17.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 2.16 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 1.08 MW | 0.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 3.42 MW | 2.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 22.92 MW | 19.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 1.06 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 3.86 MW | 3.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 5.54 MW | 4.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 3.26 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 9.91 MW | 8.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.97 MW | 2.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 2.21 MW | 1.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 3.62 MW | 3.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 1.02 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 14.94 MW | 12.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 9.93 MW | 8.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 4.47 MW | 3.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 13.4 MW | 11.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 13.16 MW | 11.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 24.1 MW | 20.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 4.28 MW | 3.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 8.36 MW | 7.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 16.73 MW | 14.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 7.05 MW | 5.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 7.15 MW | 6.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 6.27 MW | 5.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 25.46 MW | 21.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 9.78 MW | 8.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 1.3 MW | 1.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 6.94 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 8.18 MW | 6.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 7.98 MW | 6.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 5.32 MW | 4.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 15.09 MW | 15.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274723 | RIVER EC ;12 | 80/20 | 5.49 MW | 5.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274724 | RIVER EC ;11 | 80/20 | 5.46 MW | 5.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | 80/20 | 7.55 MW | 7.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | 80/20 | 7.57 MW | 7.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274792 | SE CHICAG;9U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274793 | SE CHICAG;0U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274794 | SE CHICAG;1U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274795 | SE CHICAG;2U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274798 | UNIV PARK;1U | 80/20 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274799 | UNIV PARK;2U | 80/20 | 1.52 MW | 1.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274826 | FISK ;BP | 80/20 | 2.86 MW | 2.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274827 | FISK ;RP | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276164 | X3-005 C | 80/20 | 0.11 MW | 0.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276592 | O-012 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.68 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 42.84 MW | 36.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 34.06 MW | 28.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 80.68 MW | 68.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 86.94 MW | 73.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 3.1 MW | 2.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | Adder | 10.72 MW | 9.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 9.8 MW | 8.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 4.61 MW | 3.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 7.16 MW | 6.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 12.06 MW | 10.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 6.19 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 9.54 MW | 8.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 7.7 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 13.91 MW | 11.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 5.68 MW | 4.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 18.34 MW | 15.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 5.1 MW | 4.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 6.86 MW | 5.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 2.34 MW | 1.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 2.81 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 1.58 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | Adder | 1.65 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 25.1 MW | 21.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.28 MW | 0.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 22.18 MW | 18.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | Adder | 39.58 MW | 33.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.82 MW | 1.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 6.52 MW | 5.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 7.03 MW | 5.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 361.52 MW | 307.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 953871 | J847 | External Queue | 13.43 MW | 13.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 954751 | J351 | External Queue | 441.39 MW | 441.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 955741 | J1058 | External Queue | 24.2 MW | 24.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990541 | J1332 | External Queue | 26.68 MW | 26.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990646 | J1355 | External Queue | 43.02 MW | 43.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990661 | J1358 | External Queue | 15.6 MW | 15.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990761 | J1386 | External Queue | 13.07 MW | 13.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990976 | J1447 | External Queue | 28.98 MW | 28.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 991271 | J1724 | External Queue | 41.93 MW | 41.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 991331 | J1785 | External Queue | 13.63 MW | 13.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.77 MW | 1.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 101.19 MW | 101.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.78 MW | 26.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.57 MW | 0.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.99 MW | 4.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.62 MW | 15.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.62 MW | 0.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.01 MW | 2.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.38 MW | 4.38 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 961651 | AG1-005 C O1 | Adder | 10.9 MW | 9.27 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 962691 | AG1-118 C O1 | Adder | 13.99 MW | 11.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 962701 | AG1-119 C | Adder | 13.97 MW | 11.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 962711 | AG1-120 C O1 | Adder | 5.49 MW | 4.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C O1 | Adder | 3.74 MW | 3.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 962781 | AG1-127 C | Adder | 4.42 MW | 3.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 964361 | AG1-298 O1 | 80/20 | 68.34 MW | 68.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 964581 | AG1-321 C O1 | Adder | 8.74 MW | 7.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | Adder | 16.18 MW | 13.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 965061 | AG1-371 | Adder | 2.28 MW | 1.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 965081 | AG1-373 | Adder | 0.76 MW | 0.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 965141 | AG1-379 C | Adder | 11.35 MW | 9.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 965551 | AG1-423 C O1 | Adder | 9.32 MW | 7.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C O1 | Adder | 2.64 MW | 2.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C O1 | Adder | 2.53 MW | 2.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | Adder | 10.48 MW | 8.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 966091 | AG1-478 C | Adder | 1.47 MW | 1.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 966431 | AG1-512 C | Adder | 1.25 MW | 1.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 966441 | AG1-513 C | Adder | 0.32 MW | 0.27 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 966651 | AG1-535 O1 | 80/20 | 12.35 MW | 12.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 272364 | ESS H440N ;R | Adder | 1.67 MW | 1.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 919581 | AA2-030 C | Adder | 11.39 MW | 9.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 926331 | AC1-110 1 | Adder | 1.21 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 926341 | AC1-110 2 | Adder | 1.21 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | Adder | 0.75 MW | 0.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 927451 | AC1-142A 1 | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 927461 | AC1-142A 2 | Adder | 2.89 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 933911 | AD1-013 C | Adder | 1.17 MW | 0.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 933931 | AD1-016 C | Adder | 0.6 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 934051 | AD1-031 C O1 | Adder | 1.9 MW | 1.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 934721 | AD1-100 C | Adder | 12.81 MW | 10.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 934971 | AD1-129 C | Adder | 0.58 MW | 0.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 936291 | AD2-038 C O1 | Adder | 2.24 MW | 1.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 936371 | AD2-047 C O1 | Adder | 3.44 MW | 2.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 936461 | AD2-060 | Adder | 2.02 MW | 1.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 936511 | AD2-066 C O1 | Adder | 5.66 MW | 4.81 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 937311 | AD2-172 C | Adder | 1.58 MW | 1.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 937401 | AD2-194 1 | Adder | 5.29 MW | 4.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 937411 | AD2-194 2 | Adder | 5.3 MW | 4.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | Adder | 1.22 MW | 1.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | Adder | 2.07 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | Adder | 0.6 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 942991 | AE2-321 C | Adder | 5.25 MW | 4.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 943121 | AE2-341 C | Adder | 7.84 MW | 6.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 943591 | AF1-030 C O1 | Adder | 5.21 MW | 4.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 943801 | AF1-048 C | Adder | 2.46 MW | 2.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 958481 | AF2-142 C | Adder | 7.88 MW | 6.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 958491 | AF2-143 C | Adder | 7.65 MW | 6.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 958911 | AF2-182 C | Adder | 13.22 MW | 11.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | Adder | 2.35 MW | 2.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 959081 | AF2-199 C | Adder | 4.56 MW | 3.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 959091 | AF2-200 C O1 | Adder | 9.11 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | Adder | 3.87 MW | 3.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 959341 | AF2-225 C | Adder | 3.95 MW | 3.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 959351 | AF2-226 C | Adder | 1.82 MW | 1.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 960281 | AF2-319 C | Adder | 1.82 MW | 1.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 960381 | AF2-329 | Adder | 3.29 MW | 2.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 960581 | AF2-349 C | Adder | 13.99 MW | 11.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 960591 | AF2-350 C O1 | Adder | 6.08 MW | 5.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 960601 | AF2-351 C O1 | Adder | 0.81 MW | 0.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 960721 | AF2-363 C O1 | Adder | 3.76 MW | 3.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 960751 | AF2-366 C | Adder | 4.41 MW | 3.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | Adder | 2.57 MW | 2.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 961501 | AF2-441 C O1 | 80/20 | 10.75 MW | 10.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274723 | RIVER EC ;12 | 80/20 | 4.1 MW | 4.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274724 | RIVER EC ;11 | 80/20 | 4.06 MW | 4.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274751 | CRETE EC ;1U | 80/20 | 1.54 MW | 1.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274752 | CRETE EC ;2U | 80/20 | 1.54 MW | 1.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274753 | CRETE EC ;3U | 80/20 | 1.54 MW | 1.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274754 | CRETE EC ;4U | 80/20 | 1.54 MW | 1.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274788 | SE CHICAG;5U | 80/20 | 5.66 MW | 5.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274789 | SE CHICAG;6U | 80/20 | 5.67 MW | 5.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274790 | SE CHICAG;7U | 80/20 | 5.75 MW | 5.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274791 | SE CHICAG;8U | 80/20 | 5.75 MW | 5.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274792 | SE CHICAG;9U | 80/20 | 5.72 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274793 | SE CHICAG;0U | 80/20 | 5.72 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274794 | SE CHICAG;1U | 80/20 | 5.72 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 274795 | SE CHICAG;2U | 80/20 | 5.72 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 276164 | X3-005 C | 80/20 | 0.07 MW | 0.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 276592 | O-012 C | 80/20 | 0.41 MW | 0.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 915011 | Y3-013 1 | Adder | 2.45 MW | 2.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 915021 | Y3-013 2 | Adder | 2.45 MW | 2.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 915031 | Y3-013 3 | Adder | 2.45 MW | 2.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | Adder | 0.93 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 930482 | AB1-089 CT | Adder | 23.46 MW | 19.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 930483 | AB1-089 ST | Adder | 18.65 MW | 15.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 930761 | AB1-122 CT1 | Adder | 44.3 MW | 37.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 930771 | AB1-122 CT2 | Adder | 50.08 MW | 42.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 933411 | AC2-154 C | Adder | 1.92 MW | 1.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 938511 | AE1-070 1 | Adder | 6.22 MW | 5.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 938521 | AE1-070 2 | Adder | 5.69 MW | 4.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C O1 | Adder | 5.46 MW | 4.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | Adder | 2.53 MW | 2.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 939051 | AE1-134 1 | Adder | 0.88 MW | 0.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 939061 | AE1-134 2 | Adder | 0.88 MW | 0.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | Adder | 4.17 MW | 3.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 939351 | AE1-166 C O1 | Adder | 6.91 MW | 5.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | Adder | 3.38 MW | 2.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 939741 | AE1-205 C O1 | Adder | 5.26 MW | 4.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 940501 | AE2-035 C | Adder | 1.58 MW | 1.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 941131 | AE2-107 C | Adder | 4.15 MW | 3.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 941551 | AE2-152 C O1 | Adder | 7.97 MW | 6.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | Adder | 3.13 MW | 2.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 946151 | AF1-280 C O1 | Adder | 10.06 MW | 8.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | Adder | 2.58 MW | 2.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | Adder | 2.8 MW | 2.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | Adder | 3.83 MW | 3.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 946661 | AF1-330 C | Adder | 1.29 MW | 1.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 946671 | AF1-331 | Adder | 1.52 MW | 1.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 957331 | AF2-027 C | Adder | 1.63 MW | 1.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 957371 | AF2-031 C O1 | 80/20 | 1.18 MW | 1.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 957401 | AF2-034 C | Adder | 0.96 MW | 0.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 957471 | AF2-041 C | Adder | 13.67 MW | 11.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | Adder | 0.16 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | Adder | 0.22 MW | 0.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 958011 | AF2-095 C O1 | Adder | 13.77 MW | 11.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 958021 | AF2-096 C | Adder | 23.24 MW | 19.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | Adder | 1.02 MW | 0.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 934101 | AD2-000 1 | Adder | 3.58 MW | 3.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 934111 | AD2-000 2 | Adder | 4.05 MW | 3.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 945351 | AF1-200 FTIR | Adder | 171.02 MW | 145.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 953871 | J847 | External Queue | 13.45 MW | 13.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 954751 | J351 | External Queue | 461.93 MW | 461.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 955741 | J1058 | External Queue | 23.51 MW | 23.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 990541 | J1332 | External Queue | 26.83 MW | 26.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 990546 | J1333 | External Queue | 16.82 MW | 16.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 990551 | J1334 | External Queue | 16.82 MW | 16.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 990556 | J1335 | External Queue | 14.03 MW | 14.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 990646 | J1355 | External Queue | 46.49 MW | 46.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 990661 | J1358 | External Queue | 16.35 MW | 16.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 990761 | J1386 | External Queue | 12.39 MW | 12.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 990976 | J1447 | External Queue | 28.74 MW | 28.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 991271 | J1724 | External Queue | 45.68 MW | 45.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 991331 | J1785 | External Queue | 15.71 MW | 15.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | 991336 | J1802 | External Queue | 12.69 MW | 12.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.46 MW | 0.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.78 MW | 0.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.15 MW | 0.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.24 MW | 0.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 63.06 MW | 63.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.77 MW | 15.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.3 MW | 0.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.88 MW | 2.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.69 MW | 8.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.75 MW | 0.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.28 MW | 0.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.21 MW | 1.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.44 MW | 2.44 MW |
| Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962691 | AG1-118 C O1 | 80/20 | 12.7 MW | 12.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962701 | AG1-119 C | 80/20 | 46.06 MW | 46.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962711 | AG1-120 C O1 | 80/20 | 11.09 MW | 11.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962781 | AG1-127 C | 80/20 | 5.18 MW | 5.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 966821 | AG1-553 C O1 | 80/20 | 23.73 MW | 23.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965551 | AG1-423 C O1 | 80/20 | 30.71 MW | 30.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965661 | AG1-434 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965931 | AG1-462 C O1 | 80/20 | 15.36 MW | 15.36 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 272364 | ESS H440N ;R | 80/20 | 2.14 MW | 2.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 295108 | WESTBROOK C | 80/20 | 0.12 MW | 0.12 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 295110 | SUBLETTE C | 80/20 | 0.07 MW | 0.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 919221 | AA1-146 | 80/20 | 3.41 MW | 3.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 919581 | AA2-030 C | 80/20 | 20.0 MW | 20.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 926431 | AC1-114 | 80/20 | 0.85 MW | 0.85 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 927511 | AC1-113 1 | 80/20 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 927521 | AC1-113 2 | 80/20 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 933911 | AD1-013 C | 80/20 | 1.49 MW | 1.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 933931 | AD1-016 C | 80/20 | 0.52 MW | 0.52 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 934971 | AD1-129 C | 80/20 | 1.33 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 937001 | AD2-134 C | 80/20 | 2.08 MW | 2.08 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 937311 | AD2-172 C | 80/20 | 4.49 MW | 4.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 942991 | AE2-321 C | 80/20 | 4.29 MW | 4.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 943801 | AF1-048 C | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 958911 | AF2-182 C | 80/20 | 29.28 MW | 29.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 958921 | AF2-183 C | 80/20 | 5.21 MW | 5.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 959101 | AF2-201 C O1 | 80/20 | 10.99 MW | 10.99 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 960581 | AF2-349 C | 80/20 | 89.45 MW | 89.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 960721 | AF2-363 C O1 | 80/20 | 7.71 MW | 7.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 960751 | AF2-366 C | 80/20 | 5.17 MW | 5.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961011 | AF2-392 C O1 | 80/20 | 4.58 MW | 4.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961021 | AF2-393 O1 | 80/20 | 7.8 MW | 7.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961031 | AF2-394 O1 | 80/20 | 5.2 MW | 5.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274656 | BYRON ;1U | 80/20 | 50.94 MW | 50.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274657 | BYRON ;2U | 80/20 | 49.83 MW | 49.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274662 | QUAD CITI;1U | 80/20 | 15.55 MW | 15.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274663 | QUAD CITI;2U | 80/20 | 15.59 MW | 15.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274699 | CORDOVA ;1C | 80/20 | 2.73 MW | 2.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274700 | CORDOVA ;2C | 80/20 | 2.73 MW | 2.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274701 | CORDOVA ;1S | 80/20 | 3.07 MW | 3.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274715 | NELSON EC;1C | 80/20 | 3.65 MW | 3.65 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274716 | NELSON EC;1S | 80/20 | 2.67 MW | 2.67 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274717 | NELSON EC;2C | 80/20 | 3.68 MW | 3.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274718 | NELSON EC;2S | 80/20 | 2.69 MW | 2.69 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274760 | LEE CO EC;1U | 80/20 | 2.58 MW | 2.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274761 | LEE CO EC;2U | 80/20 | 2.58 MW | 2.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274762 | LEE CO EC;3U | 80/20 | 2.58 MW | 2.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274763 | LEE CO EC;4U | 80/20 | 2.56 MW | 2.56 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274764 | LEE CO EC;5U | 80/20 | 2.59 MW | 2.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274765 | LEE CO EC;6U | 80/20 | 2.59 MW | 2.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274766 | LEE CO EC;7U | 80/20 | 2.55 MW | 2.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274767 | LEE CO EC;8U | 80/20 | 2.55 MW | 2.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274822 | ROCKFORD ;11 | 80/20 | 4.76 MW | 4.76 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274823 | ROCKFORD ;21 | 80/20 | 4.89 MW | 4.89 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274824 | ROCKFORD ;12 | 80/20 | 4.72 MW | 4.72 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274855 | GSG-6 ;RU | 80/20 | 0.36 MW | 0.36 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274856 | ECOGROVE ;U1 | 80/20 | 0.71 MW | 0.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274857 | BIG SKY ;U1 | 80/20 | 0.46 MW | 0.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274858 | BIG SKY ;U2 | 80/20 | 0.46 MW | 0.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276156 | O-029 C | 80/20 | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276157 | O-029 C | 80/20 | 0.22 MW | 0.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276158 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276162 | X1-087 | 80/20 | 0.35 MW | 0.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276590 | R-018 | 80/20 | 0.28 MW | 0.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293513 | O-009 C1 | 80/20 | 0.38 MW | 0.38 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293514 | O-009 C2 | 80/20 | 0.19 MW | 0.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293515 | O-009 C3 | 80/20 | 0.21 MW | 0.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 930482 | AB1-089 CT | 80/20 | 78.43 MW | 78.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 930483 | AB1-089 ST | 80/20 | 62.35 MW | 62.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932881 | AC2-115 1 | 80/20 | 0.85 MW | 0.85 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932891 | AC2-115 2 | 80/20 | 0.85 MW | 0.85 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932921 | AC2-116 | 80/20 | 0.3 MW | 0.3 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 938861 | AE1-114 C O1 | 80/20 | 6.14 MW | 6.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 939051 | AE1-134 1 | 80/20 | 1.55 MW | 1.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 939061 | AE1-134 2 | 80/20 | 1.55 MW | 1.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 940501 | AE2-035 C | 80/20 | 4.49 MW | 4.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 941131 | AE2-107 C | 80/20 | 4.58 MW | 4.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946151 | AF1-280 C O1 | 80/20 | 22.29 MW | 22.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946161 | AF1-281 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946321 | AF1-296 C O1 | 80/20 | 3.89 MW | 3.89 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946501 | AF1-314 C | 80/20 | 7.96 MW | 7.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946671 | AF1-331 | 80/20 | 1.94 MW | 1.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274872 | LEE DEKAL;1U | 80/20 | 0.58 MW | 0.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274850 | MENDOTA H;RU | 80/20 | 0.22 MW | 0.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 952431 | J760 | External Queue | 5.12 MW | 5.12 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953681 | J818 | External Queue | 13.14 MW | 13.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953901 | J850 | External Queue | 21.75 MW | 21.75 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953921 | J855 C | External Queue | 1.28 MW | 1.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954001 | J864 | External Queue | 4.23 MW | 4.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954061 | J870 | External Queue | 16.88 MW | 16.88 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954071 | J871 | External Queue | 8.44 MW | 8.44 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 955971 | J1084 | External Queue | 11.07 MW | 11.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990116 | J1214 | External Queue | 38.66 MW | 38.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990406 | J1304 | External Queue | 9.21 MW | 9.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990511 | J1326 | External Queue | 9.67 MW | 9.67 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990726 | J1377 | External Queue | 16.92 MW | 16.92 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 991201 | J1629 | External Queue | 13.05 MW | 13.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.55 MW | 0.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.34 MW | 0.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.43 MW | 47.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.53 MW | 9.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.02 MW | 0.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.5 MW | 2.5 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.71 MW | 9.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.01 MW | 1.01 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.49 MW | 0.49 MW |
| Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 962691 | AG1-118 C O1 | 80/20 | 12.7 MW | 12.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 962701 | AG1-119 C | 80/20 | 46.06 MW | 46.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 962711 | AG1-120 C O1 | 80/20 | 11.09 MW | 11.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 962781 | AG1-127 C | 80/20 | 5.18 MW | 5.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 966821 | AG1-553 C O1 | 80/20 | 23.73 MW | 23.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 965661 | AG1-434 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 965931 | AG1-462 C O1 | 80/20 | 15.36 MW | 15.36 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 272364 | ESS H440N ;R | 80/20 | 2.14 MW | 2.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 295108 | WESTBROOK C | 80/20 | 0.12 MW | 0.12 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 295110 | SUBLETTE C | 80/20 | 0.07 MW | 0.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 919221 | AA1-146 | 80/20 | 3.41 MW | 3.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 919581 | AA2-030 C | 80/20 | 20.0 MW | 20.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 926431 | AC1-114 | 80/20 | 0.85 MW | 0.85 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 927511 | AC1-113 1 | 80/20 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 927521 | AC1-113 2 | 80/20 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 933911 | AD1-013 C | 80/20 | 1.49 MW | 1.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 933931 | AD1-016 C | 80/20 | 0.52 MW | 0.52 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 934971 | AD1-129 C | 80/20 | 1.33 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 937001 | AD2-134 C | 80/20 | 2.08 MW | 2.08 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 937311 | AD2-172 C | 80/20 | 4.49 MW | 4.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 942991 | AE2-321 C | 80/20 | 4.29 MW | 4.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 943801 | AF1-048 C | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 958911 | AF2-182 C | 80/20 | 29.28 MW | 29.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 958921 | AF2-183 C | 80/20 | 5.21 MW | 5.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 959101 | AF2-201 C O1 | 80/20 | 10.99 MW | 10.99 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 960581 | AF2-349 C | 80/20 | 89.45 MW | 89.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 960721 | AF2-363 C O1 | 80/20 | 7.71 MW | 7.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 960751 | AF2-366 C | 80/20 | 5.17 MW | 5.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 961011 | AF2-392 C O1 | 80/20 | 4.58 MW | 4.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 961021 | AF2-393 O1 | 80/20 | 7.8 MW | 7.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 961031 | AF2-394 O1 | 80/20 | 5.2 MW | 5.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274656 | BYRON ;1U | 80/20 | 50.94 MW | 50.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274657 | BYRON ;2U | 80/20 | 49.83 MW | 49.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274662 | QUAD CITI;1U | 80/20 | 15.55 MW | 15.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274663 | QUAD CITI;2U | 80/20 | 15.59 MW | 15.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274699 | CORDOVA ;1C | 80/20 | 2.73 MW | 2.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274700 | CORDOVA ;2C | 80/20 | 2.73 MW | 2.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274701 | CORDOVA ;1S | 80/20 | 3.07 MW | 3.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274715 | NELSON EC;1C | 80/20 | 3.65 MW | 3.65 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274716 | NELSON EC;1S | 80/20 | 2.67 MW | 2.67 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274717 | NELSON EC;2C | 80/20 | 3.68 MW | 3.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274718 | NELSON EC;2S | 80/20 | 2.69 MW | 2.69 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274760 | LEE CO EC;1U | 80/20 | 2.58 MW | 2.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274761 | LEE CO EC;2U | 80/20 | 2.58 MW | 2.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274762 | LEE CO EC;3U | 80/20 | 2.58 MW | 2.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274763 | LEE CO EC;4U | 80/20 | 2.56 MW | 2.56 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274764 | LEE CO EC;5U | 80/20 | 2.59 MW | 2.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274765 | LEE CO EC;6U | 80/20 | 2.59 MW | 2.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274766 | LEE CO EC;7U | 80/20 | 2.55 MW | 2.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274767 | LEE CO EC;8U | 80/20 | 2.55 MW | 2.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274822 | ROCKFORD ;11 | 80/20 | 4.76 MW | 4.76 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274823 | ROCKFORD ;21 | 80/20 | 4.89 MW | 4.89 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274824 | ROCKFORD ;12 | 80/20 | 4.72 MW | 4.72 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274855 | GSG-6 ;RU | 80/20 | 0.36 MW | 0.36 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274856 | ECOGROVE ;U1 | 80/20 | 0.71 MW | 0.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274857 | BIG SKY ;U1 | 80/20 | 0.46 MW | 0.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274858 | BIG SKY ;U2 | 80/20 | 0.46 MW | 0.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 276156 | O-029 C | 80/20 | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 276157 | O-029 C | 80/20 | 0.22 MW | 0.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 276158 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 276162 | X1-087 | 80/20 | 0.35 MW | 0.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 276590 | R-018 | 80/20 | 0.28 MW | 0.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 293513 | O-009 C1 | 80/20 | 0.38 MW | 0.38 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 293514 | O-009 C2 | 80/20 | 0.19 MW | 0.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 293515 | O-009 C3 | 80/20 | 0.21 MW | 0.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 930482 | AB1-089 CT | 80/20 | 78.43 MW | 78.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 930483 | AB1-089 ST | 80/20 | 62.35 MW | 62.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 932881 | AC2-115 1 | 80/20 | 0.85 MW | 0.85 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 932891 | AC2-115 2 | 80/20 | 0.85 MW | 0.85 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 932921 | AC2-116 | 80/20 | 0.3 MW | 0.3 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 938861 | AE1-114 C O1 | 80/20 | 6.14 MW | 6.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 939051 | AE1-134 1 | 80/20 | 1.55 MW | 1.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 939061 | AE1-134 2 | 80/20 | 1.55 MW | 1.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 940501 | AE2-035 C | 80/20 | 4.49 MW | 4.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 941131 | AE2-107 C | 80/20 | 4.58 MW | 4.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 946151 | AF1-280 C O1 | 80/20 | 22.29 MW | 22.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 946161 | AF1-281 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 946321 | AF1-296 C O1 | 80/20 | 3.89 MW | 3.89 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 946501 | AF1-314 C | 80/20 | 7.96 MW | 7.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 946671 | AF1-331 | 80/20 | 1.94 MW | 1.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274872 | LEE DEKAL;1U | 80/20 | 0.58 MW | 0.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274850 | MENDOTA H;RU | 80/20 | 0.22 MW | 0.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 952431 | J760 | External Queue | 5.12 MW | 5.12 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 953681 | J818 | External Queue | 13.14 MW | 13.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 953901 | J850 | External Queue | 21.75 MW | 21.75 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 953921 | J855 C | External Queue | 1.28 MW | 1.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 954001 | J864 | External Queue | 4.23 MW | 4.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 954061 | J870 | External Queue | 16.88 MW | 16.88 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 954071 | J871 | External Queue | 8.44 MW | 8.44 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 955971 | J1084 | External Queue | 11.07 MW | 11.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 990116 | J1214 | External Queue | 38.66 MW | 38.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 990406 | J1304 | External Queue | 9.21 MW | 9.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 990511 | J1326 | External Queue | 9.67 MW | 9.67 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 990726 | J1377 | External Queue | 16.92 MW | 16.92 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 991201 | J1629 | External Queue | 13.05 MW | 13.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.55 MW | 0.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.34 MW | 0.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.43 MW | 47.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.53 MW | 9.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.02 MW | 0.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.5 MW | 2.5 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.71 MW | 9.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.01 MW | 1.01 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.49 MW | 0.49 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 13.52 MW | 11.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 17.81 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 4.66 MW | 3.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 5.71 MW | 4.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | Adder | 44.21 MW | 37.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 10.83 MW | 9.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 20.27 MW | 17.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 3.15 MW | 2.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 13.12 MW | 11.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 3.65 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | Adder | 6.98 MW | 5.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 14.38 MW | 12.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 0.95 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.36 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.74 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.48 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | 80/20 | 10.09 MW | 10.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 9.69 MW | 8.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 16.72 MW | 14.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 2.97 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 4.78 MW | 4.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 4.37 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 17.74 MW | 15.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 3.25 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 5.53 MW | 4.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 3.69 MW | 3.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | Adder | 7.13 MW | 6.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 22.57 MW | 22.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 22.07 MW | 22.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 21.01 MW | 21.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 21.1 MW | 21.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 9.6 MW | 9.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 9.59 MW | 9.59 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | Adder | 3.03 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | Adder | 3.04 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274792 | SE CHICAG;9U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274793 | SE CHICAG;0U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274794 | SE CHICAG;1U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274795 | SE CHICAG;2U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274802 | UNIV PARK;5U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274803 | UNIV PARK;6U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.37 MW | 0.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.16 MW | 0.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 29.81 MW | 25.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 23.7 MW | 20.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 56.16 MW | 47.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 60.43 MW | 51.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 4.19 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 6.37 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 9.65 MW | 8.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 3.79 MW | 3.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 12.72 MW | 10.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.28 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 4.75 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | Adder | 0.65 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 17.44 MW | 14.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.28 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 28.05 MW | 28.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.26 MW | 1.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274805 | UNIV PK N;1U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274806 | UNIV PK N;2U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274807 | UNIV PK N;3U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274808 | UNIV PK N;4U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274809 | UNIV PK N;5U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274810 | UNIV PK N;6U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274811 | UNIV PK N;7U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274812 | UNIV PK N;8U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274813 | UNIV PK N;9U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274814 | UNIV PK N;0U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274815 | UNIV PK N;XU | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274816 | UNIV PK N;YU | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 252.02 MW | 214.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.21 MW | 54.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 13.52 MW | 11.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 17.81 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 4.66 MW | 3.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 5.71 MW | 4.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | Adder | 44.21 MW | 37.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 10.83 MW | 9.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 20.27 MW | 17.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 3.15 MW | 2.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 13.12 MW | 11.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 3.65 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | Adder | 6.98 MW | 5.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 14.38 MW | 12.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 0.95 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.36 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.74 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.48 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | 80/20 | 10.09 MW | 10.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 9.69 MW | 8.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 16.72 MW | 14.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 2.97 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 4.78 MW | 4.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 4.37 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 17.74 MW | 15.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 3.25 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 5.53 MW | 4.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 3.69 MW | 3.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | Adder | 7.13 MW | 6.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 22.57 MW | 22.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 22.07 MW | 22.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 21.01 MW | 21.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 21.1 MW | 21.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 9.6 MW | 9.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 9.59 MW | 9.59 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | Adder | 3.03 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | Adder | 3.04 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274792 | SE CHICAG;9U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274793 | SE CHICAG;0U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274794 | SE CHICAG;1U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274795 | SE CHICAG;2U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274802 | UNIV PARK;5U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274803 | UNIV PARK;6U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.37 MW | 0.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.16 MW | 0.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 29.81 MW | 25.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 23.7 MW | 20.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 56.16 MW | 47.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 60.43 MW | 51.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 4.19 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 6.37 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 9.65 MW | 8.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 3.79 MW | 3.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 12.72 MW | 10.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.28 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 4.75 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | Adder | 0.65 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 17.44 MW | 14.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.28 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 28.05 MW | 28.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.26 MW | 1.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274805 | UNIV PK N;1U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274806 | UNIV PK N;2U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274807 | UNIV PK N;3U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274808 | UNIV PK N;4U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274809 | UNIV PK N;5U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274810 | UNIV PK N;6U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274811 | UNIV PK N;7U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274812 | UNIV PK N;8U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274813 | UNIV PK N;9U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274814 | UNIV PK N;0U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274815 | UNIV PK N;XU | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274816 | UNIV PK N;YU | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 252.02 MW | 214.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.21 MW | 54.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 961651 | AG1-005 C O1 | 80/20 | 11.76 MW | 11.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 962721 | AG1-121 C O1 | 80/20 | 4.07 MW | 4.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 963831 | AG1-236 C | 80/20 | 3.67 MW | 3.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 964581 | AG1-321 C O1 | 80/20 | 10.95 MW | 10.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 966821 | AG1-553 C O1 | 80/20 | 18.77 MW | 18.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965061 | AG1-371 | Adder | 1.93 MW | 1.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965081 | AG1-373 | Adder | 0.64 MW | 0.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965091 | AG1-374 C | 80/20 | 20.2 MW | 20.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965141 | AG1-379 C | Adder | 8.57 MW | 7.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965331 | AG1-398 | 80/20 | 1.01 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965341 | AG1-399 C | 80/20 | 6.67 MW | 6.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965351 | AG1-400 | 80/20 | 18.94 MW | 18.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965371 | AG1-402 | 80/20 | 18.94 MW | 18.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965391 | AG1-404 | 80/20 | 12.62 MW | 12.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965661 | AG1-434 C O1 | Adder | 2.33 MW | 1.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965671 | AG1-435 C O1 | 80/20 | 2.78 MW | 2.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965911 | AG1-460 C | 80/20 | 2.02 MW | 2.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965931 | AG1-462 C O1 | 80/20 | 12.14 MW | 12.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 272364 | ESS H440N ;R | Adder | 1.39 MW | 1.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 295110 | SUBLETTE C | 80/20 | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 919221 | AA1-146 | 80/20 | 1.92 MW | 1.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 919581 | AA2-030 C | 80/20 | 11.24 MW | 11.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 925771 | AC1-053 C | 80/20 | 3.67 MW | 3.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 926821 | AC1-168 C O1 | 80/20 | 0.76 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 927201 | AC1-214 C O1 | 80/20 | 0.26 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 933911 | AD1-013 C | Adder | 0.98 MW | 0.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 934051 | AD1-031 C O1 | 80/20 | 2.12 MW | 2.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 934971 | AD1-129 C | Adder | 0.47 MW | 0.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 935141 | AD1-148 | 80/20 | 5.36 MW | 5.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 936511 | AD2-066 C O1 | Adder | 4.53 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 936771 | AD2-100 C | 80/20 | 21.97 MW | 21.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 936971 | AD2-131 C | 80/20 | 1.45 MW | 1.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 937001 | AD2-134 C | Adder | 1.35 MW | 1.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 937311 | AD2-172 C | Adder | 1.4 MW | 1.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 942111 | AE2-223 C | 80/20 | 2.0 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 942421 | AE2-255 C O1 | Adder | 1.56 MW | 1.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 942481 | AE2-261 C | 80/20 | 30.19 MW | 30.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 945871 | AF1-252 O1 | 80/20 | 11.99 MW | 11.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 945881 | AF1-253 | 80/20 | 8.3 MW | 8.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 958911 | AF2-182 C | 80/20 | 12.57 MW | 12.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 958921 | AF2-183 C | 80/20 | 2.24 MW | 2.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 959081 | AF2-199 C | Adder | 3.86 MW | 3.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 959091 | AF2-200 C O1 | Adder | 7.73 MW | 6.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 959101 | AF2-201 C O1 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 959341 | AF2-225 C | 80/20 | 6.45 MW | 6.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 959611 | AF2-252 C | 80/20 | 2.24 MW | 2.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 960141 | AF2-305 | 80/20 | 1.27 MW | 1.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 960261 | AF2-317 | 80/20 | 2.32 MW | 2.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 960611 | AF2-352 C | 80/20 | 2.24 MW | 2.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 961011 | AF2-392 C O1 | 80/20 | 2.5 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 961021 | AF2-393 O1 | 80/20 | 4.26 MW | 4.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 961031 | AF2-394 O1 | 80/20 | 2.84 MW | 2.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274650 | KINCAID ;1U | 80/20 | 15.72 MW | 15.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274651 | KINCAID ;2U | 80/20 | 15.71 MW | 15.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274662 | QUAD CITI;1U | 80/20 | 12.34 MW | 12.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274663 | QUAD CITI;2U | 80/20 | 12.34 MW | 12.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274699 | CORDOVA ;1C | 80/20 | 2.17 MW | 2.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274700 | CORDOVA ;2C | 80/20 | 2.17 MW | 2.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274701 | CORDOVA ;1S | 80/20 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274715 | NELSON EC;1C | 80/20 | 2.05 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274716 | NELSON EC;1S | 80/20 | 1.5 MW | 1.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274717 | NELSON EC;2C | 80/20 | 2.07 MW | 2.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274718 | NELSON EC;2S | 80/20 | 1.51 MW | 1.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274760 | LEE CO EC;1U | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274761 | LEE CO EC;2U | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274762 | LEE CO EC;3U | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274764 | LEE CO EC;5U | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274765 | LEE CO EC;6U | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274848 | CAMPGROVE;RU | 80/20 | 0.36 MW | 0.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274849 | CRESCENT ;1U | 80/20 | 0.14 MW | 0.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274851 | PROVIDENC;RU | 80/20 | 0.14 MW | 0.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274853 | TWINGROVE;U1 | 80/20 | 0.67 MW | 0.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274854 | TWINGROVE;U2 | 80/20 | 0.68 MW | 0.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274863 | CAYUGA RI;1U | 80/20 | 0.3 MW | 0.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274864 | CAYUGA RI;2U | 80/20 | 0.3 MW | 0.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274877 | BISHOP HL;1U | 80/20 | 0.27 MW | 0.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274878 | BISHOP HL;2U | 80/20 | 0.27 MW | 0.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274880 | RADFORD R;1U | 80/20 | 1.08 MW | 1.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274889 | BRIGHTSTK;1U | 80/20 | 0.45 MW | 0.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 276156 | O-029 C | 80/20 | 0.14 MW | 0.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 276157 | O-029 C | 80/20 | 0.15 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 276158 | O-029 C | 80/20 | 0.27 MW | 0.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 293513 | O-009 C1 | 80/20 | 0.26 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 293514 | O-009 C2 | 80/20 | 0.13 MW | 0.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 293515 | O-009 C3 | 80/20 | 0.14 MW | 0.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 924041 | AB2-047 C O1 | 80/20 | 0.57 MW | 0.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 924261 | AB2-070 C O1 | 80/20 | 3.59 MW | 3.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 925581 | AC1-033 C | 80/20 | 1.04 MW | 1.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 930482 | AB1-089 CT | Adder | 19.56 MW | 16.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 930483 | AB1-089 ST | Adder | 15.55 MW | 13.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 930761 | AB1-122 CT1 | Adder | 38.62 MW | 32.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 938851 | AE1-113 C O1 | Adder | 4.12 MW | 3.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 938861 | AE1-114 C O1 | Adder | 2.32 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 939051 | AE1-134 1 | 80/20 | 0.87 MW | 0.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 939061 | AE1-134 2 | 80/20 | 0.87 MW | 0.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 939401 | AE1-172 C O1 | 80/20 | 3.23 MW | 3.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 939741 | AE1-205 C O1 | 80/20 | 8.6 MW | 8.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 940501 | AE2-035 C | Adder | 1.4 MW | 1.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 941731 | AE2-173 O1 | 80/20 | 5.12 MW | 5.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 944221 | AF1-090 C O1 | 80/20 | 6.76 MW | 6.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946151 | AF1-280 C O1 | 80/20 | 9.57 MW | 9.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946161 | AF1-281 C O1 | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946321 | AF1-296 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946501 | AF1-314 C | Adder | 2.47 MW | 2.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946541 | AF1-318 C O1 | 80/20 | 4.14 MW | 4.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946671 | AF1-331 | Adder | 1.27 MW | 1.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 957381 | AF2-032 C | 80/20 | 2.26 MW | 2.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 957471 | AF2-041 C | Adder | 11.59 MW | 9.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 957751 | AF2-069 C | 80/20 | 0.17 MW | 0.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 957761 | AF2-070 C | 80/20 | 0.24 MW | 0.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 958341 | AF2-128 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 934101 | AD2-000 1 | Adder | 3.12 MW | 2.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 944202 | AF1-088 FTWR | 80/20 | 245.28 MW | 245.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 952651 | J756 C | External Queue | 2.22 MW | 2.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 952871 | J757 C | External Queue | 4.04 MW | 4.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953371 | J808 | External Queue | 10.27 MW | 10.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953401 | J811 | External Queue | 19.51 MW | 19.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953431 | J853 | External Queue | 12.26 MW | 12.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953641 | J813 | External Queue | 43.35 MW | 43.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953651 | J815 | External Queue | 33.52 MW | 33.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953671 | J817 | External Queue | 11.46 MW | 11.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953741 | J826 C | External Queue | 1.11 MW | 1.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953881 | J848 C | External Queue | 5.53 MW | 5.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953951 | J859 | External Queue | 9.46 MW | 9.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 954411 | J912 | External Queue | 15.02 MW | 15.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 954681 | J949 C | External Queue | 38.76 MW | 38.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 954721 | J750 C | External Queue | 2.12 MW | 2.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 954821 | J955 | External Queue | 113.42 MW | 113.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 956151 | J1102 | External Queue | 5.29 MW | 5.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 956281 | J1115 C | External Queue | 2.59 MW | 2.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 956451 | J1139 | External Queue | 12.24 MW | 12.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 990056 | J1201 | External Queue | 7.49 MW | 7.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 990071 | J1204 | External Queue | 71.26 MW | 71.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 990271 | J1263 | External Queue | 121.58 MW | 121.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 990351 | J1289 C | External Queue | 2.11 MW | 2.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 990856 | J1408 | External Queue | 10.35 MW | 10.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 991191 | J1610 | External Queue | 9.56 MW | 9.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 991196 | J1626 | External Queue | 29.56 MW | 29.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 991236 | J1676 C | External Queue | 3.32 MW | 3.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 991266 | J1714 | External Queue | 19.71 MW | 19.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 991261 | J1713 C | External Queue | 3.18 MW | 3.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 4.33 MW | 4.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.63 MW | 1.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.23 MW | 15.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 68.22 MW | 68.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 67.57 MW | 67.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.59 MW | 0.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 1.7 MW | 1.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.02 MW | 13.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.72 MW | 1.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.21 MW | 15.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.47 MW | 1.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.97 MW | 7.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.01 MW | 2.01 MW |
| Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962691 | AG1-118 C O1 | 80/20 | 12.7 MW | 12.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962701 | AG1-119 C | 80/20 | 46.06 MW | 46.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962711 | AG1-120 C O1 | 80/20 | 11.09 MW | 11.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962781 | AG1-127 C | 80/20 | 5.18 MW | 5.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 966821 | AG1-553 C O1 | 80/20 | 23.73 MW | 23.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965551 | AG1-423 C O1 | 80/20 | 30.71 MW | 30.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965661 | AG1-434 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965931 | AG1-462 C O1 | 80/20 | 15.36 MW | 15.36 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 272364 | ESS H440N ;R | 80/20 | 2.14 MW | 2.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 295108 | WESTBROOK C | 80/20 | 0.12 MW | 0.12 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 295110 | SUBLETTE C | 80/20 | 0.07 MW | 0.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 919221 | AA1-146 | 80/20 | 3.41 MW | 3.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 919581 | AA2-030 C | 80/20 | 20.0 MW | 20.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 926431 | AC1-114 | 80/20 | 0.85 MW | 0.85 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 927511 | AC1-113 1 | 80/20 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 927521 | AC1-113 2 | 80/20 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 933911 | AD1-013 C | 80/20 | 1.49 MW | 1.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 933931 | AD1-016 C | 80/20 | 0.52 MW | 0.52 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 934971 | AD1-129 C | 80/20 | 1.33 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 937001 | AD2-134 C | 80/20 | 2.08 MW | 2.08 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 937311 | AD2-172 C | 80/20 | 4.49 MW | 4.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 942991 | AE2-321 C | 80/20 | 4.29 MW | 4.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 943801 | AF1-048 C | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 958911 | AF2-182 C | 80/20 | 29.28 MW | 29.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 958921 | AF2-183 C | 80/20 | 5.21 MW | 5.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 959101 | AF2-201 C O1 | 80/20 | 10.99 MW | 10.99 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 960721 | AF2-363 C O1 | 80/20 | 7.71 MW | 7.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 960751 | AF2-366 C | 80/20 | 5.17 MW | 5.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961011 | AF2-392 C O1 | 80/20 | 4.58 MW | 4.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961021 | AF2-393 O1 | 80/20 | 7.8 MW | 7.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961031 | AF2-394 O1 | 80/20 | 5.2 MW | 5.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274656 | BYRON ;1U | 80/20 | 50.94 MW | 50.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274657 | BYRON ;2U | 80/20 | 49.83 MW | 49.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274662 | QUAD CITI;1U | 80/20 | 15.55 MW | 15.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274663 | QUAD CITI;2U | 80/20 | 15.59 MW | 15.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274699 | CORDOVA ;1C | 80/20 | 2.73 MW | 2.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274700 | CORDOVA ;2C | 80/20 | 2.73 MW | 2.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274701 | CORDOVA ;1S | 80/20 | 3.07 MW | 3.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274715 | NELSON EC;1C | 80/20 | 3.65 MW | 3.65 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274716 | NELSON EC;1S | 80/20 | 2.67 MW | 2.67 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274717 | NELSON EC;2C | 80/20 | 3.68 MW | 3.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274718 | NELSON EC;2S | 80/20 | 2.69 MW | 2.69 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274760 | LEE CO EC;1U | 80/20 | 2.58 MW | 2.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274761 | LEE CO EC;2U | 80/20 | 2.58 MW | 2.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274762 | LEE CO EC;3U | 80/20 | 2.58 MW | 2.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274763 | LEE CO EC;4U | 80/20 | 2.56 MW | 2.56 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274764 | LEE CO EC;5U | 80/20 | 2.59 MW | 2.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274765 | LEE CO EC;6U | 80/20 | 2.59 MW | 2.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274766 | LEE CO EC;7U | 80/20 | 2.55 MW | 2.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274767 | LEE CO EC;8U | 80/20 | 2.55 MW | 2.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274822 | ROCKFORD ;11 | 80/20 | 4.76 MW | 4.76 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274823 | ROCKFORD ;21 | 80/20 | 4.89 MW | 4.89 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274824 | ROCKFORD ;12 | 80/20 | 4.72 MW | 4.72 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274855 | GSG-6 ;RU | 80/20 | 0.36 MW | 0.36 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274856 | ECOGROVE ;U1 | 80/20 | 0.71 MW | 0.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274857 | BIG SKY ;U1 | 80/20 | 0.46 MW | 0.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274858 | BIG SKY ;U2 | 80/20 | 0.46 MW | 0.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276156 | O-029 C | 80/20 | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276157 | O-029 C | 80/20 | 0.22 MW | 0.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276158 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276162 | X1-087 | 80/20 | 0.35 MW | 0.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276590 | R-018 | 80/20 | 0.28 MW | 0.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293513 | O-009 C1 | 80/20 | 0.38 MW | 0.38 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293514 | O-009 C2 | 80/20 | 0.19 MW | 0.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293515 | O-009 C3 | 80/20 | 0.21 MW | 0.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 930482 | AB1-089 CT | 80/20 | 78.43 MW | 78.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 930483 | AB1-089 ST | 80/20 | 62.35 MW | 62.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932881 | AC2-115 1 | 80/20 | 0.85 MW | 0.85 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932891 | AC2-115 2 | 80/20 | 0.85 MW | 0.85 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932921 | AC2-116 | 80/20 | 0.3 MW | 0.3 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 938861 | AE1-114 C O1 | 80/20 | 6.14 MW | 6.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 939051 | AE1-134 1 | 80/20 | 1.55 MW | 1.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 939061 | AE1-134 2 | 80/20 | 1.55 MW | 1.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 940501 | AE2-035 C | 80/20 | 4.49 MW | 4.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 941131 | AE2-107 C | 80/20 | 4.58 MW | 4.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946151 | AF1-280 C O1 | 80/20 | 22.29 MW | 22.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946161 | AF1-281 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946321 | AF1-296 C O1 | 80/20 | 3.89 MW | 3.89 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946501 | AF1-314 C | 80/20 | 7.96 MW | 7.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946671 | AF1-331 | 80/20 | 1.94 MW | 1.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274872 | LEE DEKAL;1U | 80/20 | 0.58 MW | 0.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274850 | MENDOTA H;RU | 80/20 | 0.22 MW | 0.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 952431 | J760 | External Queue | 5.12 MW | 5.12 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953681 | J818 | External Queue | 13.14 MW | 13.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953901 | J850 | External Queue | 21.75 MW | 21.75 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953921 | J855 C | External Queue | 1.28 MW | 1.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954001 | J864 | External Queue | 4.23 MW | 4.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954061 | J870 | External Queue | 16.88 MW | 16.88 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954071 | J871 | External Queue | 8.44 MW | 8.44 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 955971 | J1084 | External Queue | 11.07 MW | 11.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990116 | J1214 | External Queue | 38.66 MW | 38.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990406 | J1304 | External Queue | 9.21 MW | 9.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990511 | J1326 | External Queue | 9.67 MW | 9.67 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990726 | J1377 | External Queue | 16.92 MW | 16.92 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 991201 | J1629 | External Queue | 13.05 MW | 13.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.55 MW | 0.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.34 MW | 0.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.43 MW | 47.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.53 MW | 9.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.02 MW | 0.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.5 MW | 2.5 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.71 MW | 9.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.01 MW | 1.01 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.49 MW | 0.49 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 961651 | AG1-005 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 962721 | AG1-121 C O1 | 80/20 | 8.57 MW | 8.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 966821 | AG1-553 C O1 | 80/20 | 20.71 MW | 20.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 965141 | AG1-379 C | 80/20 | 59.32 MW | 59.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 965671 | AG1-435 C O1 | 80/20 | 6.0 MW | 6.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 965911 | AG1-460 C | 80/20 | 0.74 MW | 0.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 965931 | AG1-462 C O1 | 80/20 | 13.4 MW | 13.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 926821 | AC1-168 C O1 | 80/20 | 1.32 MW | 1.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 927201 | AC1-214 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 934051 | AD1-031 C O1 | 80/20 | 4.82 MW | 4.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 935141 | AD1-148 | 80/20 | 1.83 MW | 1.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 936291 | AD2-038 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 936771 | AD2-100 C | 80/20 | 7.61 MW | 7.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 936971 | AD2-131 C | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 942421 | AE2-255 C O1 | 80/20 | 10.81 MW | 10.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 942481 | AE2-261 C | 80/20 | 11.03 MW | 11.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 942651 | AE2-281 C O1 | 80/20 | 1.74 MW | 1.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 945871 | AF1-252 O1 | 80/20 | 3.57 MW | 3.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 945881 | AF1-253 | 80/20 | 2.47 MW | 2.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 958481 | AF2-142 C | 80/20 | 15.36 MW | 15.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 958491 | AF2-143 C | 80/20 | 22.36 MW | 22.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 959351 | AF2-226 C | 80/20 | 3.26 MW | 3.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 960261 | AF2-317 | 80/20 | 0.79 MW | 0.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 960281 | AF2-319 C | 80/20 | 3.26 MW | 3.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274650 | KINCAID ;1U | 80/20 | 5.86 MW | 5.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274651 | KINCAID ;2U | 80/20 | 5.87 MW | 5.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274662 | QUAD CITI;1U | 80/20 | 13.55 MW | 13.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274663 | QUAD CITI;2U | 80/20 | 13.51 MW | 13.51 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274677 | POWERTON ;5U | 80/20 | 56.64 MW | 56.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274678 | POWERTON ;6U | 80/20 | 56.78 MW | 56.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274699 | CORDOVA ;1C | 80/20 | 2.4 MW | 2.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274700 | CORDOVA ;2C | 80/20 | 2.4 MW | 2.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274701 | CORDOVA ;1S | 80/20 | 2.7 MW | 2.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274848 | CAMPGROVE;RU | 80/20 | 0.9 MW | 0.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274849 | CRESCENT ;1U | 80/20 | 0.27 MW | 0.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274851 | PROVIDENC;RU | 80/20 | 0.28 MW | 0.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274861 | TOP CROP ;1U | 80/20 | 0.51 MW | 0.51 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274862 | TOP CROP ;2U | 80/20 | 0.97 MW | 0.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274877 | BISHOP HL;1U | 80/20 | 0.61 MW | 0.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274878 | BISHOP HL;2U | 80/20 | 0.61 MW | 0.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274879 | MINONK ;1U | 80/20 | 2.95 MW | 2.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274891 | OTTER CRK;1U | 80/20 | 0.57 MW | 0.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 276156 | O-029 C | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 276157 | O-029 C | 80/20 | 0.17 MW | 0.17 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 276158 | O-029 C | 80/20 | 0.31 MW | 0.31 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 293513 | O-009 C1 | 80/20 | 0.29 MW | 0.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 293514 | O-009 C2 | 80/20 | 0.15 MW | 0.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 293515 | O-009 C3 | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 925581 | AC1-033 C | 80/20 | 2.35 MW | 2.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 930761 | AB1-122 CT1 | 80/20 | 379.71 MW | 379.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 930771 | AB1-122 CT2 | 80/20 | 248.59 MW | 248.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 938851 | AE1-113 C O1 | 80/20 | 28.54 MW | 28.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 939321 | AE1-163 C O1 | 80/20 | 12.18 MW | 12.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 944221 | AF1-090 C O1 | 80/20 | 2.01 MW | 2.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 946321 | AF1-296 C O1 | 80/20 | 3.0 MW | 3.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 946541 | AF1-318 C O1 | 80/20 | 7.12 MW | 7.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 957381 | AF2-032 C | 80/20 | 0.84 MW | 0.84 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 957751 | AF2-069 C | 80/20 | 0.35 MW | 0.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 957761 | AF2-070 C | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 958341 | AF2-128 C O1 | 80/20 | 1.81 MW | 1.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 934101 | AD2-000 1 | 80/20 | 30.71 MW | 30.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 934111 | AD2-000 2 | 80/20 | 20.1 MW | 20.1 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 951631 | J456 C | External Queue | 3.93 MW | 3.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 952651 | J756 C | External Queue | 3.6 MW | 3.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 952871 | J757 C | External Queue | 4.6 MW | 4.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 953201 | J715 C | External Queue | 1.47 MW | 1.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 953951 | J859 | External Queue | 23.64 MW | 23.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 954981 | J974 C | External Queue | 13.89 MW | 13.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 955711 | J1055 C | External Queue | 4.5 MW | 4.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 956151 | J1102 | External Queue | 6.35 MW | 6.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 956411 | J1131 | External Queue | 7.79 MW | 7.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 990051 | J1200 | External Queue | 2.98 MW | 2.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 990351 | J1289 C | External Queue | 4.41 MW | 4.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 990751 | J1383 | External Queue | 32.96 MW | 32.96 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 991091 | J1477 | External Queue | 3.89 MW | 3.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 991216 | J1653 | External Queue | 31.41 MW | 31.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 991276 | J1725 C | External Queue | 3.27 MW | 3.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 991301 | J1755 C | External Queue | 3.13 MW | 3.13 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.88 MW | 0.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.32 MW | 11.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 32.69 MW | 32.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 34.95 MW | 34.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.57 MW | 6.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.38 MW | 0.38 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.06 MW | 13.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.13 MW | 0.13 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.75 MW | 3.75 MW |
| Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 962691 | AG1-118 C O1 | 80/20 | 12.7 MW | 12.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 962701 | AG1-119 C | 80/20 | 46.06 MW | 46.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 962711 | AG1-120 C O1 | 80/20 | 11.09 MW | 11.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 962781 | AG1-127 C | 80/20 | 5.18 MW | 5.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 966821 | AG1-553 C O1 | 80/20 | 23.73 MW | 23.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 965661 | AG1-434 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 965931 | AG1-462 C O1 | 80/20 | 15.36 MW | 15.36 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 272364 | ESS H440N ;R | 80/20 | 2.14 MW | 2.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 295108 | WESTBROOK C | 80/20 | 0.12 MW | 0.12 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 295110 | SUBLETTE C | 80/20 | 0.07 MW | 0.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 919221 | AA1-146 | 80/20 | 3.41 MW | 3.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 919581 | AA2-030 C | 80/20 | 20.0 MW | 20.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 926431 | AC1-114 | 80/20 | 0.85 MW | 0.85 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 927511 | AC1-113 1 | 80/20 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 927521 | AC1-113 2 | 80/20 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 933911 | AD1-013 C | 80/20 | 1.49 MW | 1.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 933931 | AD1-016 C | 80/20 | 0.52 MW | 0.52 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 934971 | AD1-129 C | 80/20 | 1.33 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 937001 | AD2-134 C | 80/20 | 2.08 MW | 2.08 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 937311 | AD2-172 C | 80/20 | 4.49 MW | 4.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 942991 | AE2-321 C | 80/20 | 4.29 MW | 4.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 943801 | AF1-048 C | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 958911 | AF2-182 C | 80/20 | 29.28 MW | 29.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 958921 | AF2-183 C | 80/20 | 5.21 MW | 5.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 959101 | AF2-201 C O1 | 80/20 | 10.99 MW | 10.99 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 960721 | AF2-363 C O1 | 80/20 | 7.71 MW | 7.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 960751 | AF2-366 C | 80/20 | 5.17 MW | 5.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 961011 | AF2-392 C O1 | 80/20 | 4.58 MW | 4.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 961021 | AF2-393 O1 | 80/20 | 7.8 MW | 7.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 961031 | AF2-394 O1 | 80/20 | 5.2 MW | 5.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274656 | BYRON ;1U | 80/20 | 50.94 MW | 50.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274657 | BYRON ;2U | 80/20 | 49.83 MW | 49.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274662 | QUAD CITI;1U | 80/20 | 15.55 MW | 15.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274663 | QUAD CITI;2U | 80/20 | 15.59 MW | 15.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274699 | CORDOVA ;1C | 80/20 | 2.73 MW | 2.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274700 | CORDOVA ;2C | 80/20 | 2.73 MW | 2.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274701 | CORDOVA ;1S | 80/20 | 3.07 MW | 3.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274715 | NELSON EC;1C | 80/20 | 3.65 MW | 3.65 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274716 | NELSON EC;1S | 80/20 | 2.67 MW | 2.67 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274717 | NELSON EC;2C | 80/20 | 3.68 MW | 3.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274718 | NELSON EC;2S | 80/20 | 2.69 MW | 2.69 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274760 | LEE CO EC;1U | 80/20 | 2.58 MW | 2.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274761 | LEE CO EC;2U | 80/20 | 2.58 MW | 2.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274762 | LEE CO EC;3U | 80/20 | 2.58 MW | 2.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274763 | LEE CO EC;4U | 80/20 | 2.56 MW | 2.56 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274764 | LEE CO EC;5U | 80/20 | 2.59 MW | 2.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274765 | LEE CO EC;6U | 80/20 | 2.59 MW | 2.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274766 | LEE CO EC;7U | 80/20 | 2.55 MW | 2.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274767 | LEE CO EC;8U | 80/20 | 2.55 MW | 2.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274822 | ROCKFORD ;11 | 80/20 | 4.76 MW | 4.76 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274823 | ROCKFORD ;21 | 80/20 | 4.89 MW | 4.89 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274824 | ROCKFORD ;12 | 80/20 | 4.72 MW | 4.72 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274855 | GSG-6 ;RU | 80/20 | 0.36 MW | 0.36 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274856 | ECOGROVE ;U1 | 80/20 | 0.71 MW | 0.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274857 | BIG SKY ;U1 | 80/20 | 0.46 MW | 0.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274858 | BIG SKY ;U2 | 80/20 | 0.46 MW | 0.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 276156 | O-029 C | 80/20 | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 276157 | O-029 C | 80/20 | 0.22 MW | 0.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 276158 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 276162 | X1-087 | 80/20 | 0.35 MW | 0.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 276590 | R-018 | 80/20 | 0.28 MW | 0.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 293513 | O-009 C1 | 80/20 | 0.38 MW | 0.38 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 293514 | O-009 C2 | 80/20 | 0.19 MW | 0.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 293515 | O-009 C3 | 80/20 | 0.21 MW | 0.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 930482 | AB1-089 CT | 80/20 | 78.43 MW | 78.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 930483 | AB1-089 ST | 80/20 | 62.35 MW | 62.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 932881 | AC2-115 1 | 80/20 | 0.85 MW | 0.85 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 932891 | AC2-115 2 | 80/20 | 0.85 MW | 0.85 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 932921 | AC2-116 | 80/20 | 0.3 MW | 0.3 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 938861 | AE1-114 C O1 | 80/20 | 6.14 MW | 6.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 939051 | AE1-134 1 | 80/20 | 1.55 MW | 1.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 939061 | AE1-134 2 | 80/20 | 1.55 MW | 1.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 940501 | AE2-035 C | 80/20 | 4.49 MW | 4.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 941131 | AE2-107 C | 80/20 | 4.58 MW | 4.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 946151 | AF1-280 C O1 | 80/20 | 22.29 MW | 22.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 946161 | AF1-281 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 946321 | AF1-296 C O1 | 80/20 | 3.89 MW | 3.89 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 946501 | AF1-314 C | 80/20 | 7.96 MW | 7.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 946671 | AF1-331 | 80/20 | 1.94 MW | 1.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274872 | LEE DEKAL;1U | 80/20 | 0.58 MW | 0.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 274850 | MENDOTA H;RU | 80/20 | 0.22 MW | 0.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 952431 | J760 | External Queue | 5.12 MW | 5.12 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 953681 | J818 | External Queue | 13.14 MW | 13.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 953901 | J850 | External Queue | 21.75 MW | 21.75 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 953921 | J855 C | External Queue | 1.28 MW | 1.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 954001 | J864 | External Queue | 4.23 MW | 4.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 954061 | J870 | External Queue | 16.88 MW | 16.88 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 954071 | J871 | External Queue | 8.44 MW | 8.44 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 955971 | J1084 | External Queue | 11.07 MW | 11.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 990116 | J1214 | External Queue | 38.66 MW | 38.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 990406 | J1304 | External Queue | 9.21 MW | 9.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 990511 | J1326 | External Queue | 9.67 MW | 9.67 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 990726 | J1377 | External Queue | 16.92 MW | 16.92 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | 991201 | J1629 | External Queue | 13.05 MW | 13.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.55 MW | 0.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.34 MW | 0.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.43 MW | 47.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.53 MW | 9.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.02 MW | 0.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.5 MW | 2.5 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.71 MW | 9.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.01 MW | 1.01 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.49 MW | 0.49 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 961651 | AG1-005 C O1 | 80/20 | 8.06 MW | 8.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 962721 | AG1-121 C O1 | 80/20 | 2.87 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 963831 | AG1-236 C | 80/20 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 964581 | AG1-321 C O1 | 80/20 | 6.96 MW | 6.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 966821 | AG1-553 C O1 | 80/20 | 14.8 MW | 14.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 965091 | AG1-374 C | 80/20 | 12.9 MW | 12.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 965331 | AG1-398 | 80/20 | 0.66 MW | 0.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 965341 | AG1-399 C | 80/20 | 4.29 MW | 4.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 965351 | AG1-400 | 80/20 | 12.18 MW | 12.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 965371 | AG1-402 | 80/20 | 12.18 MW | 12.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 965391 | AG1-404 | 80/20 | 8.12 MW | 8.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 965671 | AG1-435 C O1 | 80/20 | 1.97 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 965911 | AG1-460 C | 80/20 | 1.48 MW | 1.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 965931 | AG1-462 C O1 | 80/20 | 9.58 MW | 9.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 295110 | SUBLETTE C | 80/20 | 0.03 MW | 0.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 919221 | AA1-146 | 80/20 | 1.46 MW | 1.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 919581 | AA2-030 C | 80/20 | 8.56 MW | 8.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 925771 | AC1-053 C | 80/20 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 926821 | AC1-168 C O1 | Adder | 0.52 MW | 0.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 927201 | AC1-214 C O1 | 80/20 | 0.18 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 934051 | AD1-031 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 935141 | AD1-148 | 80/20 | 3.68 MW | 3.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 936771 | AD2-100 C | 80/20 | 16.32 MW | 16.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 936971 | AD2-131 C | 80/20 | 1.07 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 942111 | AE2-223 C | 80/20 | 1.24 MW | 1.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 942481 | AE2-261 C | 80/20 | 22.16 MW | 22.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 945871 | AF1-252 O1 | 80/20 | 9.19 MW | 9.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 945881 | AF1-253 | 80/20 | 6.36 MW | 6.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 958911 | AF2-182 C | 80/20 | 9.5 MW | 9.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 958921 | AF2-183 C | 80/20 | 1.69 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 959341 | AF2-225 C | 80/20 | 4.0 MW | 4.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 959611 | AF2-252 C | 80/20 | 1.43 MW | 1.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 960141 | AF2-305 | 80/20 | 0.83 MW | 0.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 960261 | AF2-317 | 80/20 | 1.59 MW | 1.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 960611 | AF2-352 C | 80/20 | 1.43 MW | 1.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 961011 | AF2-392 C O1 | 80/20 | 1.89 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 961021 | AF2-393 O1 | 80/20 | 3.22 MW | 3.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 961031 | AF2-394 O1 | 80/20 | 2.15 MW | 2.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274650 | KINCAID ;1U | 80/20 | 11.48 MW | 11.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274651 | KINCAID ;2U | 80/20 | 11.48 MW | 11.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274662 | QUAD CITI;1U | 80/20 | 9.74 MW | 9.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274663 | QUAD CITI;2U | 80/20 | 9.73 MW | 9.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274699 | CORDOVA ;1C | 80/20 | 1.71 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274700 | CORDOVA ;2C | 80/20 | 1.71 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274701 | CORDOVA ;1S | 80/20 | 1.92 MW | 1.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274715 | NELSON EC;1C | 80/20 | 1.56 MW | 1.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274716 | NELSON EC;1S | 80/20 | 1.14 MW | 1.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274717 | NELSON EC;2C | 80/20 | 1.57 MW | 1.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274718 | NELSON EC;2S | 80/20 | 1.15 MW | 1.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274760 | LEE CO EC;1U | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274761 | LEE CO EC;2U | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274762 | LEE CO EC;3U | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274764 | LEE CO EC;5U | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274765 | LEE CO EC;6U | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274848 | CAMPGROVE;RU | 80/20 | 0.26 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274849 | CRESCENT ;1U | 80/20 | 0.1 MW | 0.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274851 | PROVIDENC;RU | 80/20 | 0.1 MW | 0.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274853 | TWINGROVE;U1 | 80/20 | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274854 | TWINGROVE;U2 | 80/20 | 0.44 MW | 0.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274877 | BISHOP HL;1U | 80/20 | 0.2 MW | 0.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274878 | BISHOP HL;2U | 80/20 | 0.2 MW | 0.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274880 | RADFORD R;1U | 80/20 | 0.69 MW | 0.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 274889 | BRIGHTSTK;1U | 80/20 | 0.28 MW | 0.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 276156 | O-029 C | 80/20 | 0.1 MW | 0.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 276157 | O-029 C | 80/20 | 0.11 MW | 0.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 276158 | O-029 C | 80/20 | 0.2 MW | 0.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 293513 | O-009 C1 | 80/20 | 0.19 MW | 0.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 293514 | O-009 C2 | 80/20 | 0.1 MW | 0.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 293515 | O-009 C3 | 80/20 | 0.11 MW | 0.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 924041 | AB2-047 C O1 | 80/20 | 0.35 MW | 0.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 924261 | AB2-070 C O1 | 80/20 | 2.36 MW | 2.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 925581 | AC1-033 C | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 938861 | AE1-114 C O1 | Adder | 1.73 MW | 1.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 939051 | AE1-134 1 | 80/20 | 0.67 MW | 0.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 939061 | AE1-134 2 | 80/20 | 0.67 MW | 0.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 939741 | AE1-205 C O1 | 80/20 | 5.34 MW | 5.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 941731 | AE2-173 O1 | 80/20 | 3.18 MW | 3.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 944221 | AF1-090 C O1 | 80/20 | 5.18 MW | 5.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 946151 | AF1-280 C O1 | 80/20 | 7.23 MW | 7.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 946161 | AF1-281 C O1 | 80/20 | 0.16 MW | 0.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 946321 | AF1-296 C O1 | 80/20 | 2.29 MW | 2.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 946541 | AF1-318 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 957381 | AF2-032 C | 80/20 | 1.65 MW | 1.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 958341 | AF2-128 C O1 | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 944202 | AF1-088 FTWR | 80/20 | 206.95 MW | 206.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 952871 | J757 C | External Queue | 2.71 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 953371 | J808 | External Queue | 11.71 MW | 11.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 953401 | J811 | External Queue | 20.5 MW | 20.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 953431 | J853 | External Queue | 15.54 MW | 15.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 953611 | J800 | External Queue | 14.26 MW | 14.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 953641 | J813 | External Queue | 50.84 MW | 50.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 953651 | J815 | External Queue | 25.3 MW | 25.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 953671 | J817 | External Queue | 12.09 MW | 12.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 953881 | J848 C | External Queue | 3.98 MW | 3.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 954411 | J912 | External Queue | 11.97 MW | 11.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 954721 | J750 C | External Queue | 1.27 MW | 1.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 954821 | J955 | External Queue | 73.66 MW | 73.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 990056 | J1201 | External Queue | 7.3 MW | 7.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 990071 | J1204 | External Queue | 92.1 MW | 92.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 990271 | J1263 | External Queue | 188.83 MW | 188.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 990856 | J1408 | External Queue | 6.87 MW | 6.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 952791 | J753 | External Queue | 5.09 MW | 5.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 954641 | J944 | External Queue | 10.28 MW | 10.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 991191 | J1610 | External Queue | 6.01 MW | 6.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 991196 | J1626 | External Queue | 31.06 MW | 31.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 991266 | J1714 | External Queue | 20.71 MW | 20.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | 991261 | J1713 C | External Queue | 1.33 MW | 1.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.57 MW | 0.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.88 MW | 2.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.88 MW | 1.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 20.04 MW | 20.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 55.31 MW | 55.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 71.22 MW | 71.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.88 MW | 0.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.9 MW | 0.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.68 MW | 13.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.63 MW | 1.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.4 MW | 13.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.26 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.01 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.86 MW | 8.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:138-345:AMIL::CASEYWEST:KANSAS:4525-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.5 MW | 1.5 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 17.02 MW | 14.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 22.84 MW | 19.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 22.56 MW | 19.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 8.9 MW | 7.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 5.89 MW | 5.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 13.52 MW | 11.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 25.65 MW | 21.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 3.69 MW | 3.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 17.85 MW | 15.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 4.27 MW | 3.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 3.98 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 16.6 MW | 14.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 2.03 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.52 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 2.71 MW | 2.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 18.22 MW | 15.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 1.2 MW | 1.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927091 | AC1-204 GEN1 | 80/20 | 13.07 MW | 13.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927093 | AC1-204 GEN2 | 80/20 | 13.1 MW | 13.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.9 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.98 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 3.28 MW | 2.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 2.41 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 8.63 MW | 7.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 8.25 MW | 7.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | 80/20 | 8.27 MW | 8.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.84 MW | 1.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 3.25 MW | 2.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.87 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 8.45 MW | 7.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 13.09 MW | 11.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 8.71 MW | 7.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 3.95 MW | 3.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 11.16 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 11.17 MW | 9.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 21.18 MW | 18.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 3.76 MW | 3.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 7.38 MW | 6.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 14.75 MW | 12.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 6.2 MW | 5.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 5.95 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 5.49 MW | 4.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 22.47 MW | 19.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 6.11 MW | 5.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 7.19 MW | 6.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 4.11 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 7.0 MW | 5.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 4.67 MW | 3.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 29.37 MW | 29.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 28.57 MW | 28.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 26.96 MW | 26.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 27.07 MW | 27.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 12.28 MW | 12.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 12.29 MW | 12.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274687 | WILL CNTY;4U | 80/20 | 12.33 MW | 12.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274704 | KENDALL ;1C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274705 | KENDALL ;1S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274706 | KENDALL ;2C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274707 | KENDALL ;2S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274728 | ELWOOD EC;5P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274730 | ELWOOD EC;6P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274732 | ELWOOD EC;7P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274733 | ELWOOD EC;3P | 80/20 | 3.51 MW | 3.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274734 | ELWOOD EC;8P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274736 | ELWOOD EC;9P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274751 | CRETE EC ;1U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274752 | CRETE EC ;2U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274753 | CRETE EC ;3U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274754 | CRETE EC ;4U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.47 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.47 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 37.77 MW | 32.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 30.03 MW | 25.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 70.93 MW | 60.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 78.7 MW | 66.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 2.29 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | 80/20 | 9.71 MW | 9.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 8.87 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 4.06 MW | 3.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 6.08 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 10.51 MW | 8.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 5.21 MW | 4.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 7.93 MW | 6.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 6.76 MW | 5.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 4.72 MW | 4.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 16.12 MW | 13.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 4.49 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 5.98 MW | 5.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 1.52 MW | 1.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 22.13 MW | 18.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.25 MW | 0.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 16.36 MW | 13.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 40.19 MW | 40.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.59 MW | 1.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 317.97 MW | 270.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.33 MW | 2.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.01 MW | 62.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 18.89 MW | 18.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.78 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.41 MW | 13.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.79 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.87 MW | 3.87 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 17.02 MW | 14.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 22.84 MW | 19.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 22.56 MW | 19.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 8.9 MW | 7.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 5.89 MW | 5.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 13.52 MW | 11.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 25.65 MW | 21.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 3.69 MW | 3.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 17.85 MW | 15.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 4.27 MW | 3.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 3.98 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 16.6 MW | 14.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 2.03 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.52 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 2.71 MW | 2.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 18.22 MW | 15.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 1.2 MW | 1.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927091 | AC1-204 GEN1 | 80/20 | 13.07 MW | 13.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927093 | AC1-204 GEN2 | 80/20 | 13.1 MW | 13.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.9 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.98 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 3.28 MW | 2.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 2.41 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 8.63 MW | 7.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 8.25 MW | 7.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | 80/20 | 8.27 MW | 8.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.84 MW | 1.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 3.25 MW | 2.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.87 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 8.45 MW | 7.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 13.09 MW | 11.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 8.71 MW | 7.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 3.95 MW | 3.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 11.16 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 11.17 MW | 9.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 21.18 MW | 18.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 3.76 MW | 3.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 7.38 MW | 6.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 14.75 MW | 12.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 6.2 MW | 5.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 5.95 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 5.49 MW | 4.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 22.47 MW | 19.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 6.11 MW | 5.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 7.19 MW | 6.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 4.11 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 7.0 MW | 5.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 4.67 MW | 3.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 29.37 MW | 29.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 28.57 MW | 28.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 26.96 MW | 26.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 27.07 MW | 27.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 12.28 MW | 12.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 12.29 MW | 12.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274687 | WILL CNTY;4U | 80/20 | 12.33 MW | 12.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274704 | KENDALL ;1C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274705 | KENDALL ;1S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274706 | KENDALL ;2C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274707 | KENDALL ;2S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274728 | ELWOOD EC;5P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274730 | ELWOOD EC;6P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274732 | ELWOOD EC;7P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274733 | ELWOOD EC;3P | 80/20 | 3.51 MW | 3.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274734 | ELWOOD EC;8P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274736 | ELWOOD EC;9P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274751 | CRETE EC ;1U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274752 | CRETE EC ;2U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274753 | CRETE EC ;3U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274754 | CRETE EC ;4U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.47 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.47 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 37.77 MW | 32.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 30.03 MW | 25.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 70.93 MW | 60.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 78.7 MW | 66.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 2.29 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | 80/20 | 9.71 MW | 9.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 8.87 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 4.06 MW | 3.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 6.08 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 10.51 MW | 8.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 5.21 MW | 4.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 7.93 MW | 6.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 6.76 MW | 5.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 4.72 MW | 4.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 16.12 MW | 13.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 4.49 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 5.98 MW | 5.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 1.52 MW | 1.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 22.13 MW | 18.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.25 MW | 0.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 16.36 MW | 13.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 40.19 MW | 40.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.59 MW | 1.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 317.97 MW | 270.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.33 MW | 2.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.01 MW | 62.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 18.89 MW | 18.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.78 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.41 MW | 13.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.79 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.87 MW | 3.87 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961651 | AG1-005 C O1 | 80/20 | 9.86 MW | 9.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 963831 | AG1-236 C | 80/20 | 3.04 MW | 3.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 964581 | AG1-321 C O1 | 80/20 | 9.09 MW | 9.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 15.99 MW | 15.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965091 | AG1-374 C | 80/20 | 16.71 MW | 16.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965331 | AG1-398 | 80/20 | 0.84 MW | 0.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965341 | AG1-399 C | 80/20 | 5.51 MW | 5.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965351 | AG1-400 | 80/20 | 15.65 MW | 15.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965371 | AG1-402 | 80/20 | 15.65 MW | 15.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965391 | AG1-404 | 80/20 | 10.43 MW | 10.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C O1 | 80/20 | 2.34 MW | 2.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965911 | AG1-460 C | 80/20 | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | 80/20 | 10.35 MW | 10.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.03 MW | 0.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 1.63 MW | 1.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 919581 | AA2-030 C | 80/20 | 9.55 MW | 9.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 925771 | AC1-053 C | 80/20 | 3.04 MW | 3.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 0.64 MW | 0.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 934051 | AD1-031 C O1 | 80/20 | 1.78 MW | 1.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 935141 | AD1-148 | 80/20 | 4.45 MW | 4.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 936771 | AD2-100 C | 80/20 | 18.31 MW | 18.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 936971 | AD2-131 C | 80/20 | 1.21 MW | 1.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 937311 | AD2-172 C | Adder | 1.19 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 1.65 MW | 1.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 942481 | AE2-261 C | 80/20 | 25.14 MW | 25.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 10.01 MW | 10.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 | 80/20 | 6.93 MW | 6.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 958911 | AF2-182 C | 80/20 | 10.68 MW | 10.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 1.9 MW | 1.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | Adder | 2.9 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 959341 | AF2-225 C | 80/20 | 5.33 MW | 5.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 1.86 MW | 1.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 960141 | AF2-305 | 80/20 | 1.05 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 960261 | AF2-317 | 80/20 | 1.92 MW | 1.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 1.86 MW | 1.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 2.12 MW | 2.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 3.62 MW | 3.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 2.41 MW | 2.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274650 | KINCAID ;1U | 80/20 | 13.09 MW | 13.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274651 | KINCAID ;2U | 80/20 | 13.08 MW | 13.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274662 | QUAD CITI;1U | 80/20 | 10.51 MW | 10.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274663 | QUAD CITI;2U | 80/20 | 10.51 MW | 10.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274699 | CORDOVA ;1C | 80/20 | 1.84 MW | 1.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274700 | CORDOVA ;2C | 80/20 | 1.84 MW | 1.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274701 | CORDOVA ;1S | 80/20 | 2.07 MW | 2.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274715 | NELSON EC;1C | 80/20 | 1.74 MW | 1.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274716 | NELSON EC;1S | 80/20 | 1.27 MW | 1.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274717 | NELSON EC;2C | 80/20 | 1.76 MW | 1.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274718 | NELSON EC;2S | 80/20 | 1.28 MW | 1.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274760 | LEE CO EC;1U | 80/20 | 0.85 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274761 | LEE CO EC;2U | 80/20 | 0.85 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274762 | LEE CO EC;3U | 80/20 | 0.85 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274764 | LEE CO EC;5U | 80/20 | 0.85 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274765 | LEE CO EC;6U | 80/20 | 0.85 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.3 MW | 0.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.11 MW | 0.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.12 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 0.55 MW | 0.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 0.57 MW | 0.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 0.25 MW | 0.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 0.25 MW | 0.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.23 MW | 0.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.23 MW | 0.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274880 | RADFORD R;1U | 80/20 | 0.89 MW | 0.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 0.38 MW | 0.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.12 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.13 MW | 0.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.23 MW | 0.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.22 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.11 MW | 0.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.12 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 0.47 MW | 0.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 924261 | AB2-070 C O1 | 80/20 | 2.97 MW | 2.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 0.88 MW | 0.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 930761 | AB1-122 CT1 | Adder | 32.47 MW | 27.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | Adder | 1.97 MW | 1.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939051 | AE1-134 1 | 80/20 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939061 | AE1-134 2 | 80/20 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939741 | AE1-205 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 940501 | AE2-035 C | Adder | 1.19 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 4.23 MW | 4.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 5.64 MW | 5.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946151 | AF1-280 C O1 | 80/20 | 8.13 MW | 8.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.18 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 2.48 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | Adder | 2.1 MW | 1.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 3.48 MW | 3.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 957381 | AF2-032 C | 80/20 | 1.88 MW | 1.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 0.92 MW | 0.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 934101 | AD2-000 1 | Adder | 2.63 MW | 2.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 944202 | AF1-088 FTWR | 80/20 | 256.43 MW | 256.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 952871 | J757 C | External Queue | 3.17 MW | 3.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953371 | J808 | External Queue | 8.84 MW | 8.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953401 | J811 | External Queue | 16.63 MW | 16.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953431 | J853 | External Queue | 10.98 MW | 10.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953641 | J813 | External Queue | 38.0 MW | 38.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953651 | J815 | External Queue | 26.98 MW | 26.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953671 | J817 | External Queue | 9.65 MW | 9.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953881 | J848 C | External Queue | 4.42 MW | 4.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 954411 | J912 | External Queue | 12.2 MW | 12.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 954681 | J949 C | External Queue | 27.62 MW | 27.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 954721 | J750 C | External Queue | 1.64 MW | 1.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 954821 | J955 | External Queue | 89.27 MW | 89.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 956151 | J1102 | External Queue | 4.0 MW | 4.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 956281 | J1115 C | External Queue | 1.95 MW | 1.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 956451 | J1139 | External Queue | 8.69 MW | 8.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990056 | J1201 | External Queue | 6.29 MW | 6.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990071 | J1204 | External Queue | 63.47 MW | 63.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990271 | J1263 | External Queue | 98.78 MW | 98.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990856 | J1408 | External Queue | 8.15 MW | 8.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 991191 | J1610 | External Queue | 7.47 MW | 7.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 991196 | J1626 | External Queue | 25.2 MW | 25.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 991266 | J1714 | External Queue | 16.8 MW | 16.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 991261 | J1713 C | External Queue | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.96 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.53 MW | 1.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.51 MW | 14.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 59.93 MW | 59.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 63.08 MW | 63.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.58 MW | 0.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 11.66 MW | 11.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.44 MW | 1.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.12 MW | 13.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.05 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.31 MW | 7.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.71 MW | 1.71 MW |
| Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 962691 | AG1-118 C O1 | 80/20 | 10.48 MW | 10.48 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 962701 | AG1-119 C | 80/20 | 15.68 MW | 15.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 962711 | AG1-120 C O1 | 80/20 | 9.0 MW | 9.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 962781 | AG1-127 C | 80/20 | 4.24 MW | 4.24 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 16.98 MW | 16.98 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 965551 | AG1-423 C O1 | 80/20 | 10.31 MW | 10.31 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C O1 | 80/20 | 1.96 MW | 1.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | 80/20 | 10.99 MW | 10.99 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 272364 | ESS H440N ;R | 80/20 | 1.67 MW | 1.67 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.09 MW | 0.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.06 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 2.43 MW | 2.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 919581 | AA2-030 C | 80/20 | 14.27 MW | 14.27 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 926431 | AC1-114 | 80/20 | 0.68 MW | 0.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 927511 | AC1-113 1 | 80/20 | 0.34 MW | 0.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 927521 | AC1-113 2 | 80/20 | 0.34 MW | 0.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 933911 | AD1-013 C | 80/20 | 1.17 MW | 1.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.01 MW | 0.01 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 934971 | AD1-129 C | 80/20 | 1.04 MW | 1.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 1.62 MW | 1.62 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 937311 | AD2-172 C | 80/20 | 3.49 MW | 3.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 958911 | AF2-182 C | 80/20 | 20.64 MW | 20.64 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 3.67 MW | 3.67 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 8.54 MW | 8.54 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 960581 | AF2-349 C | 80/20 | 82.67 MW | 82.67 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 960721 | AF2-363 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 960751 | AF2-366 C | 80/20 | 4.22 MW | 4.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 3.35 MW | 3.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 5.72 MW | 5.72 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 3.81 MW | 3.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274656 | BYRON ;1U | 80/20 | 35.35 MW | 35.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274657 | BYRON ;2U | 80/20 | 34.66 MW | 34.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274662 | QUAD CITI;1U | 80/20 | 11.13 MW | 11.13 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274663 | QUAD CITI;2U | 80/20 | 11.16 MW | 11.16 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274699 | CORDOVA ;1C | 80/20 | 1.95 MW | 1.95 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274700 | CORDOVA ;2C | 80/20 | 1.95 MW | 1.95 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274701 | CORDOVA ;1S | 80/20 | 2.2 MW | 2.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274715 | NELSON EC;1C | 80/20 | 2.6 MW | 2.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274716 | NELSON EC;1S | 80/20 | 1.9 MW | 1.9 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274717 | NELSON EC;2C | 80/20 | 2.63 MW | 2.63 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274718 | NELSON EC;2S | 80/20 | 1.92 MW | 1.92 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274760 | LEE CO EC;1U | 80/20 | 1.81 MW | 1.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274761 | LEE CO EC;2U | 80/20 | 1.81 MW | 1.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274762 | LEE CO EC;3U | 80/20 | 1.81 MW | 1.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274763 | LEE CO EC;4U | 80/20 | 1.79 MW | 1.79 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274764 | LEE CO EC;5U | 80/20 | 1.82 MW | 1.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274765 | LEE CO EC;6U | 80/20 | 1.82 MW | 1.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274766 | LEE CO EC;7U | 80/20 | 1.79 MW | 1.79 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274767 | LEE CO EC;8U | 80/20 | 1.79 MW | 1.79 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274822 | ROCKFORD ;11 | 80/20 | 3.79 MW | 3.79 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274823 | ROCKFORD ;21 | 80/20 | 3.89 MW | 3.89 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274824 | ROCKFORD ;12 | 80/20 | 3.76 MW | 3.76 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 0.28 MW | 0.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 0.32 MW | 0.32 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 0.32 MW | 0.32 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.15 MW | 0.15 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.16 MW | 0.16 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.29 MW | 0.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 276162 | X1-087 | 80/20 | 0.28 MW | 0.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 276590 | R-018 | 80/20 | 0.22 MW | 0.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.27 MW | 0.27 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.14 MW | 0.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.15 MW | 0.15 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 930482 | AB1-089 CT | 80/20 | 43.61 MW | 43.61 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 930483 | AB1-089 ST | 80/20 | 34.67 MW | 34.67 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 932881 | AC2-115 1 | 80/20 | 0.68 MW | 0.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 932891 | AC2-115 2 | 80/20 | 0.68 MW | 0.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 932921 | AC2-116 | 80/20 | 0.24 MW | 0.24 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 4.71 MW | 4.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 939051 | AE1-134 1 | 80/20 | 1.11 MW | 1.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 939061 | AE1-134 2 | 80/20 | 1.11 MW | 1.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 940501 | AE2-035 C | 80/20 | 3.49 MW | 3.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 941131 | AE2-107 C | 80/20 | 3.67 MW | 3.67 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 946151 | AF1-280 C O1 | 80/20 | 15.71 MW | 15.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.34 MW | 0.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 2.8 MW | 2.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 6.18 MW | 6.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 946671 | AF1-331 | 80/20 | 1.52 MW | 1.52 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 0.46 MW | 0.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.17 MW | 0.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 952431 | J760 | External Queue | 3.89 MW | 3.89 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 953681 | J818 | External Queue | 9.65 MW | 9.65 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 953901 | J850 | External Queue | 15.89 MW | 15.89 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 953921 | J855 C | External Queue | 0.94 MW | 0.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 954001 | J864 | External Queue | 3.12 MW | 3.12 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 954061 | J870 | External Queue | 12.45 MW | 12.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 954071 | J871 | External Queue | 6.23 MW | 6.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 955971 | J1084 | External Queue | 7.99 MW | 7.99 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 990116 | J1214 | External Queue | 29.06 MW | 29.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 990406 | J1304 | External Queue | 6.94 MW | 6.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 990511 | J1326 | External Queue | 7.26 MW | 7.26 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | 990726 | J1377 | External Queue | 12.85 MW | 12.85 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.04 MW | 0.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.38 MW | 0.38 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.15 MW | 0.15 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.34 MW | 0.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 33.02 MW | 33.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.9 MW | 6.9 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.06 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.8 MW | 1.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.96 MW | 6.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.73 MW | 0.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.16 MW | 0.16 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 961651 | AG1-005 C O1 | 80/20 | 18.46 MW | 18.46 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C O1 | 80/20 | 8.03 MW | 8.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 19.75 MW | 19.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965141 | AG1-379 C | 80/20 | 26.97 MW | 26.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C O1 | 80/20 | 5.62 MW | 5.62 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965911 | AG1-460 C | 80/20 | 0.66 MW | 0.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | 80/20 | 12.78 MW | 12.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 1.25 MW | 1.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 934051 | AD1-031 C O1 | 80/20 | 4.5 MW | 4.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 936291 | AD2-038 C O1 | 80/20 | 5.59 MW | 5.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 936771 | AD2-100 C | 80/20 | 6.76 MW | 6.76 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 936971 | AD2-131 C | 80/20 | 0.45 MW | 0.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | 80/20 | 4.91 MW | 4.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 942481 | AE2-261 C | 80/20 | 9.79 MW | 9.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | 80/20 | 1.48 MW | 1.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 3.18 MW | 3.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 | 80/20 | 2.2 MW | 2.2 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 958481 | AF2-142 C | 80/20 | 13.06 MW | 13.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 958491 | AF2-143 C | 80/20 | 19.05 MW | 19.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 959351 | AF2-226 C | 80/20 | 2.79 MW | 2.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 960281 | AF2-319 C | 80/20 | 2.79 MW | 2.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274650 | KINCAID ;1U | 80/20 | 5.2 MW | 5.2 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274651 | KINCAID ;2U | 80/20 | 5.21 MW | 5.21 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274662 | QUAD CITI;1U | 80/20 | 12.92 MW | 12.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274663 | QUAD CITI;2U | 80/20 | 12.88 MW | 12.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274677 | POWERTON ;5U | 80/20 | 48.16 MW | 48.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274678 | POWERTON ;6U | 80/20 | 48.42 MW | 48.42 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274699 | CORDOVA ;1C | 80/20 | 2.29 MW | 2.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274700 | CORDOVA ;2C | 80/20 | 2.29 MW | 2.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274701 | CORDOVA ;1S | 80/20 | 2.57 MW | 2.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.84 MW | 0.84 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.26 MW | 0.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.27 MW | 0.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274861 | TOP CROP ;1U | 80/20 | 0.44 MW | 0.44 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274862 | TOP CROP ;2U | 80/20 | 0.83 MW | 0.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.57 MW | 0.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.57 MW | 0.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274879 | MINONK ;1U | 80/20 | 1.34 MW | 1.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274891 | OTTER CRK;1U | 80/20 | 0.48 MW | 0.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.15 MW | 0.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.3 MW | 0.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.28 MW | 0.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 2.19 MW | 2.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 930761 | AB1-122 CT1 | 80/20 | 367.02 MW | 367.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C O1 | 80/20 | 12.97 MW | 12.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | 80/20 | 10.37 MW | 10.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 2.87 MW | 2.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 6.75 MW | 6.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 957381 | AF2-032 C | 80/20 | 0.75 MW | 0.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.47 MW | 0.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 1.72 MW | 1.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 934101 | AD2-000 1 | 80/20 | 29.68 MW | 29.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 951511 | J530 C | External Queue | 3.3 MW | 3.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 951631 | J456 C | External Queue | 3.6 MW | 3.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 951821 | J541 C | External Queue | 4.19 MW | 4.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 952651 | J756 C | External Queue | 3.25 MW | 3.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 952871 | J757 C | External Queue | 4.15 MW | 4.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 953201 | J715 C | External Queue | 1.4 MW | 1.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 953951 | J859 | External Queue | 21.59 MW | 21.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 954721 | J750 C | External Queue | 1.45 MW | 1.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 954981 | J974 C | External Queue | 12.78 MW | 12.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 955711 | J1055 C | External Queue | 4.11 MW | 4.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 956151 | J1102 | External Queue | 5.67 MW | 5.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 956411 | J1131 | External Queue | 7.32 MW | 7.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 990051 | J1200 | External Queue | 2.79 MW | 2.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 990351 | J1289 C | External Queue | 4.02 MW | 4.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 990751 | J1383 | External Queue | 30.22 MW | 30.22 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991091 | J1477 | External Queue | 3.66 MW | 3.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991216 | J1653 | External Queue | 28.71 MW | 28.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991276 | J1725 C | External Queue | 2.99 MW | 2.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991301 | J1755 C | External Queue | 2.92 MW | 2.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.8 MW | 0.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 10.23 MW | 10.23 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 32.25 MW | 32.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 31.99 MW | 31.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.51 MW | 0.51 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.05 MW | 6.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.3 MW | 0.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 12.29 MW | 12.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.44 MW | 3.44 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 961651 | AG1-005 C O1 | 80/20 | 19.98 MW | 19.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 962721 | AG1-121 C O1 | 80/20 | 8.65 MW | 8.65 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 966821 | AG1-553 C O1 | 80/20 | 21.35 MW | 21.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 965141 | AG1-379 C | 80/20 | 30.92 MW | 30.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 965671 | AG1-435 C O1 | 80/20 | 6.05 MW | 6.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 965911 | AG1-460 C | 80/20 | 0.73 MW | 0.73 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 965931 | AG1-462 C O1 | 80/20 | 13.82 MW | 13.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 295110 | SUBLETTE C | 80/20 | 0.03 MW | 0.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 919221 | AA1-146 | 80/20 | 1.42 MW | 1.42 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 919581 | AA2-030 C | 80/20 | 8.34 MW | 8.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 926821 | AC1-168 C O1 | 80/20 | 1.35 MW | 1.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 927201 | AC1-214 C O1 | 80/20 | 0.53 MW | 0.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 934051 | AD1-031 C O1 | 80/20 | 4.84 MW | 4.84 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 936291 | AD2-038 C O1 | 80/20 | 11.08 MW | 11.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 936771 | AD2-100 C | 80/20 | 7.52 MW | 7.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 936971 | AD2-131 C | 80/20 | 0.49 MW | 0.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 942421 | AE2-255 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 942481 | AE2-261 C | 80/20 | 10.9 MW | 10.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 942651 | AE2-281 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 945871 | AF1-252 O1 | 80/20 | 3.53 MW | 3.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 945881 | AF1-253 | 80/20 | 2.44 MW | 2.44 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 958481 | AF2-142 C | 80/20 | 37.77 MW | 37.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 958491 | AF2-143 C | 80/20 | 37.77 MW | 37.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 959351 | AF2-226 C | 80/20 | 3.16 MW | 3.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 960281 | AF2-319 C | 80/20 | 3.16 MW | 3.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 961011 | AF2-392 C O1 | 80/20 | 1.91 MW | 1.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 961021 | AF2-393 O1 | 80/20 | 3.25 MW | 3.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 961031 | AF2-394 O1 | 80/20 | 2.16 MW | 2.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274650 | KINCAID ;1U | 80/20 | 5.79 MW | 5.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274651 | KINCAID ;2U | 80/20 | 5.8 MW | 5.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274662 | QUAD CITI;1U | 80/20 | 13.97 MW | 13.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274663 | QUAD CITI;2U | 80/20 | 13.93 MW | 13.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274677 | POWERTON ;5U | 80/20 | 54.7 MW | 54.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274678 | POWERTON ;6U | 80/20 | 54.99 MW | 54.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274699 | CORDOVA ;1C | 80/20 | 2.47 MW | 2.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274700 | CORDOVA ;2C | 80/20 | 2.47 MW | 2.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274701 | CORDOVA ;1S | 80/20 | 2.78 MW | 2.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274715 | NELSON EC;1C | 80/20 | 1.52 MW | 1.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274716 | NELSON EC;1S | 80/20 | 1.11 MW | 1.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274717 | NELSON EC;2C | 80/20 | 1.53 MW | 1.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274718 | NELSON EC;2S | 80/20 | 1.12 MW | 1.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274848 | CAMPGROVE;RU | 80/20 | 0.9 MW | 0.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274849 | CRESCENT ;1U | 80/20 | 0.28 MW | 0.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274851 | PROVIDENC;RU | 80/20 | 0.28 MW | 0.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274861 | TOP CROP ;1U | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274862 | TOP CROP ;2U | 80/20 | 0.95 MW | 0.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274877 | BISHOP HL;1U | 80/20 | 0.61 MW | 0.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274878 | BISHOP HL;2U | 80/20 | 0.61 MW | 0.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274879 | MINONK ;1U | 80/20 | 1.53 MW | 1.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 274891 | OTTER CRK;1U | 80/20 | 1.39 MW | 1.39 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 276156 | O-029 C | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 276157 | O-029 C | 80/20 | 0.18 MW | 0.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 276158 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 276173 | Z2-081 | 80/20 | 0.12 MW | 0.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 293513 | O-009 C1 | 80/20 | 0.3 MW | 0.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 293514 | O-009 C2 | 80/20 | 0.15 MW | 0.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 293515 | O-009 C3 | 80/20 | 0.17 MW | 0.17 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 925581 | AC1-033 C | 80/20 | 2.36 MW | 2.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 930761 | AB1-122 CT1 | 80/20 | 378.37 MW | 378.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 938851 | AE1-113 C O1 | 80/20 | 14.87 MW | 14.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 939051 | AE1-134 1 | 80/20 | 0.65 MW | 0.65 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 939061 | AE1-134 2 | 80/20 | 0.65 MW | 0.65 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 939321 | AE1-163 C O1 | 80/20 | 20.57 MW | 20.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 944221 | AF1-090 C O1 | 80/20 | 1.99 MW | 1.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 946321 | AF1-296 C O1 | 80/20 | 3.11 MW | 3.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 946541 | AF1-318 C O1 | 80/20 | 7.3 MW | 7.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 957381 | AF2-032 C | 80/20 | 0.83 MW | 0.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 957751 | AF2-069 C | 80/20 | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 957761 | AF2-070 C | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 958341 | AF2-128 C O1 | 80/20 | 1.86 MW | 1.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 934101 | AD2-000 1 | 80/20 | 30.6 MW | 30.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 951631 | J456 C | External Queue | 3.87 MW | 3.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 952651 | J756 C | External Queue | 3.53 MW | 3.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 952871 | J757 C | External Queue | 4.51 MW | 4.51 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 953201 | J715 C | External Queue | 1.52 MW | 1.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 953951 | J859 | External Queue | 23.25 MW | 23.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 954981 | J974 C | External Queue | 13.67 MW | 13.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 955711 | J1055 C | External Queue | 4.42 MW | 4.42 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 956151 | J1102 | External Queue | 6.2 MW | 6.2 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 956411 | J1131 | External Queue | 7.9 MW | 7.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 990051 | J1200 | External Queue | 3.01 MW | 3.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 990351 | J1289 C | External Queue | 4.34 MW | 4.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 990751 | J1383 | External Queue | 32.44 MW | 32.44 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 991091 | J1477 | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 991216 | J1653 | External Queue | 30.89 MW | 30.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 991276 | J1725 C | External Queue | 3.21 MW | 3.21 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | 991301 | J1755 C | External Queue | 3.15 MW | 3.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.35 MW | 0.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.86 MW | 0.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 10.77 MW | 10.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 34.51 MW | 34.51 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 34.63 MW | 34.63 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.53 MW | 0.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.53 MW | 6.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.35 MW | 0.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.28 MW | 13.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9806__R-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.7 MW | 3.7 MW |
| Details for AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 41.26 MW | 41.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 965061 | AG1-371 | 80/20 | 16.27 MW | 16.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 965081 | AG1-373 | 80/20 | 5.42 MW | 5.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C O1 | 80/20 | 16.45 MW | 16.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | 80/20 | 26.71 MW | 26.71 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 272364 | ESS H440N ;R | 80/20 | 1.75 MW | 1.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.1 MW | 0.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.1 MW | 0.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 6.46 MW | 6.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 919581 | AA2-030 C | 80/20 | 37.96 MW | 37.96 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 926431 | AC1-114 | 80/20 | 0.27 MW | 0.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 927511 | AC1-113 1 | 80/20 | 0.13 MW | 0.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 927521 | AC1-113 2 | 80/20 | 0.13 MW | 0.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 933911 | AD1-013 C | 80/20 | 1.22 MW | 1.22 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 934051 | AD1-031 C O1 | 80/20 | 2.11 MW | 2.11 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.01 MW | 0.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 1.74 MW | 1.74 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 937311 | AD2-172 C | 80/20 | 2.29 MW | 2.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 958911 | AF2-182 C | 80/20 | 36.36 MW | 36.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 6.46 MW | 6.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 959081 | AF2-199 C | 80/20 | 32.54 MW | 32.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 959091 | AF2-200 C O1 | 80/20 | 65.08 MW | 65.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 5.62 MW | 5.62 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 7.07 MW | 7.07 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 12.04 MW | 12.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 8.03 MW | 8.03 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274656 | BYRON ;1U | 80/20 | 19.25 MW | 19.25 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274657 | BYRON ;2U | 80/20 | 18.75 MW | 18.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274662 | QUAD CITI;1U | 80/20 | 26.95 MW | 26.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274663 | QUAD CITI;2U | 80/20 | 27.03 MW | 27.03 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274699 | CORDOVA ;1C | 80/20 | 4.75 MW | 4.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274700 | CORDOVA ;2C | 80/20 | 4.75 MW | 4.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274701 | CORDOVA ;1S | 80/20 | 5.34 MW | 5.34 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274715 | NELSON EC;1C | 80/20 | 6.93 MW | 6.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274716 | NELSON EC;1S | 80/20 | 5.06 MW | 5.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274717 | NELSON EC;2C | 80/20 | 6.99 MW | 6.99 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274718 | NELSON EC;2S | 80/20 | 5.1 MW | 5.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274760 | LEE CO EC;1U | 80/20 | 2.67 MW | 2.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274761 | LEE CO EC;2U | 80/20 | 2.67 MW | 2.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274762 | LEE CO EC;3U | 80/20 | 2.67 MW | 2.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274763 | LEE CO EC;4U | 80/20 | 2.64 MW | 2.64 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274764 | LEE CO EC;5U | 80/20 | 2.67 MW | 2.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274765 | LEE CO EC;6U | 80/20 | 2.67 MW | 2.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274766 | LEE CO EC;7U | 80/20 | 2.63 MW | 2.63 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274767 | LEE CO EC;8U | 80/20 | 2.63 MW | 2.63 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274822 | ROCKFORD ;11 | 80/20 | 1.49 MW | 1.49 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274823 | ROCKFORD ;21 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274824 | ROCKFORD ;12 | 80/20 | 1.48 MW | 1.48 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 0.3 MW | 0.3 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 0.36 MW | 0.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 0.48 MW | 0.48 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 0.48 MW | 0.48 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.27 MW | 0.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.27 MW | 0.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.34 MW | 0.34 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.36 MW | 0.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.67 MW | 0.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 276162 | X1-087 | 80/20 | 0.18 MW | 0.18 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 276590 | R-018 | 80/20 | 0.08 MW | 0.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.62 MW | 0.62 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.32 MW | 0.32 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.35 MW | 0.35 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 1.05 MW | 1.05 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 930482 | AB1-089 CT | Adder | 23.3 MW | 19.8 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 930483 | AB1-089 ST | Adder | 18.52 MW | 15.74 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 932881 | AC2-115 1 | 80/20 | 0.27 MW | 0.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 932891 | AC2-115 2 | 80/20 | 0.27 MW | 0.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 932921 | AC2-116 | 80/20 | 0.09 MW | 0.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 4.79 MW | 4.79 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 939051 | AE1-134 1 | 80/20 | 2.95 MW | 2.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 939061 | AE1-134 2 | 80/20 | 2.95 MW | 2.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 940501 | AE2-035 C | 80/20 | 2.29 MW | 2.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 946151 | AF1-280 C O1 | 80/20 | 27.67 MW | 27.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.61 MW | 0.61 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 4.06 MW | 4.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 946671 | AF1-331 | 80/20 | 1.58 MW | 1.58 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 957471 | AF2-041 C | 80/20 | 97.62 MW | 97.62 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.18 MW | 0.18 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 951381 | J504 | External Queue | 3.81 MW | 3.81 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 951421 | J514 | External Queue | 2.28 MW | 2.28 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 955971 | J1084 | External Queue | 21.02 MW | 21.02 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 956411 | J1131 | External Queue | 11.0 MW | 11.0 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 991091 | J1477 | External Queue | 5.5 MW | 5.5 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.08 MW | 0.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.22 MW | 0.22 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.39 MW | 0.39 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.46 MW | 3.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 50.61 MW | 50.61 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.83 MW | 15.83 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.12 MW | 0.12 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.85 MW | 3.85 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.23 MW | 0.23 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.35 MW | 13.35 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.19 MW | 0.19 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.09 MW | 0.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.79 MW | 1.79 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.67 MW | 0.67 MW |
| Details for ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 12.18 MW | 10.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 16.33 MW | 13.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 16.12 MW | 13.7 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 4.21 MW | 3.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 5.16 MW | 4.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | Adder | 35.6 MW | 30.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 9.74 MW | 8.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 18.35 MW | 15.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965091 | AG1-374 C | Adder | 11.68 MW | 9.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 10.75 MW | 9.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 2.84 MW | 2.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 11.88 MW | 10.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 1.16 MW | 0.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 13.03 MW | 11.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 0.85 MW | 0.72 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927091 | AC1-204 GEN1 | 80/20 | 9.28 MW | 9.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927093 | AC1-204 GEN2 | 80/20 | 9.29 MW | 9.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 3.17 MW | 3.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 3.17 MW | 3.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.13 MW | 1.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 1.82 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 1.81 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | 80/20 | 5.87 MW | 5.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.33 MW | 1.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 9.37 MW | 7.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 6.23 MW | 5.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 15.14 MW | 12.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 2.69 MW | 2.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 4.43 MW | 3.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 4.3 MW | 3.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | Adder | 1.3 MW | 1.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 16.05 MW | 13.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | Adder | 1.3 MW | 1.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 4.36 MW | 3.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 2.94 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 5.01 MW | 4.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 3.34 MW | 2.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | Adder | 6.11 MW | 5.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 20.63 MW | 20.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 20.08 MW | 20.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 19.08 MW | 19.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 19.16 MW | 19.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 8.73 MW | 8.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 8.73 MW | 8.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274687 | WILL CNTY;4U | 80/20 | 8.78 MW | 8.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274704 | KENDALL ;1C | 80/20 | 3.09 MW | 3.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274705 | KENDALL ;1S | 80/20 | 2.07 MW | 2.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274706 | KENDALL ;2C | 80/20 | 3.09 MW | 3.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274707 | KENDALL ;2S | 80/20 | 2.07 MW | 2.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274728 | ELWOOD EC;5P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274730 | ELWOOD EC;6P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274732 | ELWOOD EC;7P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274734 | ELWOOD EC;8P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274735 | ELWOOD EC;4P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274736 | ELWOOD EC;9P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274751 | CRETE EC ;1U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274752 | CRETE EC ;2U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274753 | CRETE EC ;3U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274754 | CRETE EC ;4U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | Adder | 2.5 MW | 2.12 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | Adder | 2.5 MW | 2.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | Adder | 2.54 MW | 2.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | Adder | 2.54 MW | 2.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.33 MW | 0.33 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 0.62 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.05 MW | 0.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 26.99 MW | 22.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 50.7 MW | 43.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 55.88 MW | 47.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | 80/20 | 6.89 MW | 6.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 2.9 MW | 2.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.01 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.01 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 3.77 MW | 3.2 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 5.73 MW | 4.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 1.81 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 3.41 MW | 2.9 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 11.52 MW | 9.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.25 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 2.93 MW | 2.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 3.21 MW | 2.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 4.28 MW | 3.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 1.76 MW | 1.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | Adder | 0.54 MW | 0.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 1.07 MW | 1.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 15.81 MW | 13.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 27.74 MW | 27.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.14 MW | 0.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 227.54 MW | 193.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 955741 | J1058 | External Queue | 33.49 MW | 33.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.55 MW | 1.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.95 MW | 47.95 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 12.18 MW | 10.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 16.33 MW | 13.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 16.12 MW | 13.7 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 4.21 MW | 3.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 5.16 MW | 4.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | Adder | 35.6 MW | 30.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 9.74 MW | 8.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 18.35 MW | 15.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965091 | AG1-374 C | Adder | 11.68 MW | 9.93 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 10.75 MW | 9.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 2.84 MW | 2.42 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 11.88 MW | 10.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 1.16 MW | 0.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 13.03 MW | 11.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 0.85 MW | 0.72 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927091 | AC1-204 GEN1 | 80/20 | 9.28 MW | 9.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927093 | AC1-204 GEN2 | 80/20 | 9.29 MW | 9.29 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 3.17 MW | 3.17 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 3.17 MW | 3.17 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.13 MW | 1.81 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 1.82 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 1.81 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | 80/20 | 5.87 MW | 5.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.33 MW | 1.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 9.37 MW | 7.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 6.23 MW | 5.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 15.14 MW | 12.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 2.69 MW | 2.29 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 4.43 MW | 3.77 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 4.3 MW | 3.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | Adder | 1.3 MW | 1.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 16.05 MW | 13.64 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | Adder | 1.3 MW | 1.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 4.36 MW | 3.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 2.94 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 5.01 MW | 4.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 3.34 MW | 2.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | Adder | 6.11 MW | 5.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 20.63 MW | 20.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 20.08 MW | 20.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 19.08 MW | 19.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 19.16 MW | 19.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 8.73 MW | 8.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 8.73 MW | 8.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274687 | WILL CNTY;4U | 80/20 | 8.78 MW | 8.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274704 | KENDALL ;1C | 80/20 | 3.09 MW | 3.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274705 | KENDALL ;1S | 80/20 | 2.07 MW | 2.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274706 | KENDALL ;2C | 80/20 | 3.09 MW | 3.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274707 | KENDALL ;2S | 80/20 | 2.07 MW | 2.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274728 | ELWOOD EC;5P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274730 | ELWOOD EC;6P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274732 | ELWOOD EC;7P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274734 | ELWOOD EC;8P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274735 | ELWOOD EC;4P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274736 | ELWOOD EC;9P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274751 | CRETE EC ;1U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274752 | CRETE EC ;2U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274753 | CRETE EC ;3U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274754 | CRETE EC ;4U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | Adder | 2.5 MW | 2.12 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | Adder | 2.5 MW | 2.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | Adder | 2.54 MW | 2.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | Adder | 2.54 MW | 2.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.33 MW | 0.33 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 0.62 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.05 MW | 0.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 26.99 MW | 22.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 50.7 MW | 43.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 55.88 MW | 47.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | 80/20 | 6.89 MW | 6.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 2.9 MW | 2.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.01 MW | 0.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.01 MW | 0.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 3.77 MW | 3.2 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 5.73 MW | 4.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 1.81 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 3.41 MW | 2.9 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 11.52 MW | 9.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.25 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 2.93 MW | 2.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 3.21 MW | 2.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 4.28 MW | 3.64 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 1.76 MW | 1.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | Adder | 0.54 MW | 0.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 1.07 MW | 1.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 15.81 MW | 13.44 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 27.74 MW | 27.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.14 MW | 0.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 227.54 MW | 193.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 955741 | J1058 | External Queue | 33.49 MW | 33.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.55 MW | 1.55 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.95 MW | 47.95 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 12.18 MW | 10.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 16.33 MW | 13.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 16.12 MW | 13.7 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 4.21 MW | 3.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 5.16 MW | 4.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | Adder | 35.6 MW | 30.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 9.74 MW | 8.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 18.35 MW | 15.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965091 | AG1-374 C | Adder | 11.68 MW | 9.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 10.75 MW | 9.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 2.84 MW | 2.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 11.88 MW | 10.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 1.16 MW | 0.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 13.03 MW | 11.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 0.85 MW | 0.72 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927091 | AC1-204 GEN1 | 80/20 | 9.28 MW | 9.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927093 | AC1-204 GEN2 | 80/20 | 9.29 MW | 9.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 3.17 MW | 3.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 3.17 MW | 3.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.13 MW | 1.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 1.82 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 1.81 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | 80/20 | 5.87 MW | 5.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.33 MW | 1.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 9.37 MW | 7.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 6.23 MW | 5.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 15.14 MW | 12.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 2.69 MW | 2.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 4.43 MW | 3.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 4.3 MW | 3.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | Adder | 1.3 MW | 1.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 16.05 MW | 13.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | Adder | 1.3 MW | 1.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 4.36 MW | 3.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 2.94 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 5.01 MW | 4.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 3.34 MW | 2.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | Adder | 6.11 MW | 5.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 20.63 MW | 20.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 20.08 MW | 20.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 19.08 MW | 19.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 19.16 MW | 19.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 8.73 MW | 8.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 8.73 MW | 8.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274687 | WILL CNTY;4U | 80/20 | 8.78 MW | 8.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274704 | KENDALL ;1C | 80/20 | 3.09 MW | 3.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274705 | KENDALL ;1S | 80/20 | 2.07 MW | 2.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274706 | KENDALL ;2C | 80/20 | 3.09 MW | 3.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274707 | KENDALL ;2S | 80/20 | 2.07 MW | 2.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274728 | ELWOOD EC;5P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274730 | ELWOOD EC;6P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274732 | ELWOOD EC;7P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274734 | ELWOOD EC;8P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274735 | ELWOOD EC;4P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274736 | ELWOOD EC;9P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274751 | CRETE EC ;1U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274752 | CRETE EC ;2U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274753 | CRETE EC ;3U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274754 | CRETE EC ;4U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | Adder | 2.5 MW | 2.12 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | Adder | 2.5 MW | 2.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | Adder | 2.54 MW | 2.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | Adder | 2.54 MW | 2.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.33 MW | 0.33 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 0.62 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.05 MW | 0.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 26.99 MW | 22.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 50.7 MW | 43.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 55.88 MW | 47.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | 80/20 | 6.89 MW | 6.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 2.9 MW | 2.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.01 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.01 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 3.77 MW | 3.2 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 5.73 MW | 4.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 1.81 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 3.41 MW | 2.9 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 11.52 MW | 9.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.25 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 2.93 MW | 2.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 3.21 MW | 2.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 4.28 MW | 3.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 1.76 MW | 1.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | Adder | 0.54 MW | 0.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 1.07 MW | 1.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 15.81 MW | 13.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 27.74 MW | 27.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.14 MW | 0.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 227.54 MW | 193.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 955741 | J1058 | External Queue | 33.49 MW | 33.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.55 MW | 1.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.95 MW | 47.95 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 12.18 MW | 10.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 16.33 MW | 13.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 16.12 MW | 13.7 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 4.21 MW | 3.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 5.16 MW | 4.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | Adder | 35.6 MW | 30.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 9.74 MW | 8.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 18.35 MW | 15.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965091 | AG1-374 C | Adder | 11.68 MW | 9.93 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 10.75 MW | 9.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 2.84 MW | 2.42 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 11.88 MW | 10.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 1.16 MW | 0.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 13.03 MW | 11.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 0.85 MW | 0.72 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927091 | AC1-204 GEN1 | 80/20 | 9.28 MW | 9.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927093 | AC1-204 GEN2 | 80/20 | 9.29 MW | 9.29 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 3.17 MW | 3.17 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 3.17 MW | 3.17 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.13 MW | 1.81 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 1.82 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 1.81 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | 80/20 | 5.87 MW | 5.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.33 MW | 1.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 9.37 MW | 7.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 6.23 MW | 5.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 15.14 MW | 12.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 2.69 MW | 2.29 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 4.43 MW | 3.77 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 4.3 MW | 3.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | Adder | 1.3 MW | 1.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 16.05 MW | 13.64 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | Adder | 1.3 MW | 1.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 4.36 MW | 3.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 2.94 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 5.01 MW | 4.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 3.34 MW | 2.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | Adder | 6.11 MW | 5.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 20.63 MW | 20.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 20.08 MW | 20.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 19.08 MW | 19.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 19.16 MW | 19.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 8.73 MW | 8.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 8.73 MW | 8.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274687 | WILL CNTY;4U | 80/20 | 8.78 MW | 8.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274704 | KENDALL ;1C | 80/20 | 3.09 MW | 3.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274705 | KENDALL ;1S | 80/20 | 2.07 MW | 2.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274706 | KENDALL ;2C | 80/20 | 3.09 MW | 3.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274707 | KENDALL ;2S | 80/20 | 2.07 MW | 2.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274728 | ELWOOD EC;5P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274730 | ELWOOD EC;6P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274732 | ELWOOD EC;7P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274734 | ELWOOD EC;8P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274735 | ELWOOD EC;4P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274736 | ELWOOD EC;9P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274751 | CRETE EC ;1U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274752 | CRETE EC ;2U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274753 | CRETE EC ;3U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274754 | CRETE EC ;4U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | Adder | 2.5 MW | 2.12 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | Adder | 2.5 MW | 2.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | Adder | 2.54 MW | 2.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | Adder | 2.54 MW | 2.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.33 MW | 0.33 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 0.62 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.05 MW | 0.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 26.99 MW | 22.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 50.7 MW | 43.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 55.88 MW | 47.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | 80/20 | 6.89 MW | 6.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 2.9 MW | 2.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.01 MW | 0.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.01 MW | 0.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 3.77 MW | 3.2 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 5.73 MW | 4.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 1.81 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 3.41 MW | 2.9 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 11.52 MW | 9.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.25 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 2.93 MW | 2.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 3.21 MW | 2.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 4.28 MW | 3.64 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 1.76 MW | 1.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | Adder | 0.54 MW | 0.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 1.07 MW | 1.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 15.81 MW | 13.44 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 27.74 MW | 27.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.14 MW | 0.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 227.54 MW | 193.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 955741 | J1058 | External Queue | 33.49 MW | 33.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.55 MW | 1.55 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.95 MW | 47.95 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 961651 | AG1-005 C O1 | Adder | 8.61 MW | 7.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 962691 | AG1-118 C O1 | Adder | 11.34 MW | 9.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 962701 | AG1-119 C | Adder | 11.29 MW | 9.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 962711 | AG1-120 C O1 | Adder | 4.44 MW | 3.77 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 962721 | AG1-121 C O1 | Adder | 2.96 MW | 2.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 962781 | AG1-127 C | Adder | 3.58 MW | 3.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 964361 | AG1-298 O1 | 80/20 | 45.09 MW | 45.09 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 964581 | AG1-321 C O1 | Adder | 6.8 MW | 5.78 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 966821 | AG1-553 C O1 | Adder | 12.86 MW | 10.93 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 965061 | AG1-371 | Adder | 1.84 MW | 1.56 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 965081 | AG1-373 | Adder | 0.61 MW | 0.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 965141 | AG1-379 C | Adder | 9.15 MW | 7.77 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 965551 | AG1-423 C O1 | Adder | 7.53 MW | 6.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 965661 | AG1-434 C O1 | Adder | 2.13 MW | 1.81 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 965671 | AG1-435 C O1 | Adder | 2.0 MW | 1.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 965931 | AG1-462 C O1 | Adder | 8.32 MW | 7.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 966091 | AG1-478 C | Adder | 1.14 MW | 0.97 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 966431 | AG1-512 C | Adder | 0.81 MW | 0.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 966441 | AG1-513 C | Adder | 0.26 MW | 0.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 966651 | AG1-535 O1 | 80/20 | 7.84 MW | 7.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 272364 | ESS H440N ;R | Adder | 1.35 MW | 1.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 919581 | AA2-030 C | Adder | 9.12 MW | 7.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 926331 | AC1-110 1 | Adder | 0.98 MW | 0.83 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 926341 | AC1-110 2 | Adder | 0.98 MW | 0.83 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 926821 | AC1-168 C O1 | Adder | 0.6 MW | 0.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 927451 | AC1-142A 1 | Adder | 2.33 MW | 1.98 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 927461 | AC1-142A 2 | Adder | 2.33 MW | 1.98 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 933911 | AD1-013 C | Adder | 0.95 MW | 0.8 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 933931 | AD1-016 C | Adder | 0.48 MW | 0.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 934051 | AD1-031 C O1 | Adder | 1.5 MW | 1.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 934721 | AD1-100 C | Adder | 10.23 MW | 8.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 934971 | AD1-129 C | Adder | 0.47 MW | 0.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 936291 | AD2-038 C O1 | Adder | 1.76 MW | 1.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 936371 | AD2-047 C O1 | Adder | 2.56 MW | 2.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 936461 | AD2-060 | Adder | 1.51 MW | 1.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 936511 | AD2-066 C O1 | Adder | 4.49 MW | 3.81 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 937001 | AD2-134 C | Adder | 1.3 MW | 1.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 937311 | AD2-172 C | Adder | 1.27 MW | 1.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 937401 | AD2-194 1 | Adder | 4.28 MW | 3.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 937411 | AD2-194 2 | Adder | 4.29 MW | 3.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 942421 | AE2-255 C O1 | Adder | 1.67 MW | 1.42 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 942651 | AE2-281 C O1 | Adder | 0.47 MW | 0.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 942991 | AE2-321 C | Adder | 4.24 MW | 3.61 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 943121 | AE2-341 C | Adder | 6.4 MW | 5.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 943591 | AF1-030 C O1 | Adder | 4.26 MW | 3.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 943801 | AF1-048 C | Adder | 1.98 MW | 1.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 945501 | AF1-215 C O1 | Adder | -10.08 MW | -8.57 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 958481 | AF2-142 C | Adder | 6.1 MW | 5.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 958491 | AF2-143 C | Adder | 5.98 MW | 5.09 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 958911 | AF2-182 C | Adder | 10.61 MW | 9.02 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 958921 | AF2-183 C | Adder | 1.89 MW | 1.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 959081 | AF2-199 C | Adder | 3.68 MW | 3.13 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 959091 | AF2-200 C O1 | Adder | 7.36 MW | 6.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 959101 | AF2-201 C O1 | Adder | 3.11 MW | 2.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 959351 | AF2-226 C | Adder | 1.52 MW | 1.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 960281 | AF2-319 C | Adder | 1.52 MW | 1.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 960381 | AF2-329 | Adder | 2.68 MW | 2.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 960581 | AF2-349 C | Adder | 11.29 MW | 9.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 960591 | AF2-350 C O1 | Adder | 4.52 MW | 3.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 960601 | AF2-351 C O1 | Adder | 0.6 MW | 0.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 960721 | AF2-363 C O1 | Adder | 3.04 MW | 2.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 960751 | AF2-366 C | Adder | 3.57 MW | 3.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 961011 | AF2-392 C O1 | Adder | 2.06 MW | 1.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 961021 | AF2-393 O1 | Adder | 3.51 MW | 2.98 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 961031 | AF2-394 O1 | Adder | 2.34 MW | 1.99 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 961501 | AF2-441 C O1 | 80/20 | 6.88 MW | 6.88 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274723 | RIVER EC ;12 | 80/20 | 2.59 MW | 2.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274724 | RIVER EC ;11 | 80/20 | 2.49 MW | 2.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274751 | CRETE EC ;1U | 80/20 | 2.24 MW | 2.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274752 | CRETE EC ;2U | 80/20 | 2.24 MW | 2.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274753 | CRETE EC ;3U | 80/20 | 2.24 MW | 2.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274754 | CRETE EC ;4U | 80/20 | 2.24 MW | 2.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274788 | SE CHICAG;5U | 80/20 | 3.45 MW | 3.45 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274789 | SE CHICAG;6U | 80/20 | 3.46 MW | 3.46 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274790 | SE CHICAG;7U | 80/20 | 3.5 MW | 3.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274791 | SE CHICAG;8U | 80/20 | 3.5 MW | 3.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274792 | SE CHICAG;9U | 80/20 | 3.6 MW | 3.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274793 | SE CHICAG;0U | 80/20 | 3.6 MW | 3.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274794 | SE CHICAG;1U | 80/20 | 3.6 MW | 3.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 274795 | SE CHICAG;2U | 80/20 | 3.6 MW | 3.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 276164 | X3-005 C | 80/20 | 0.05 MW | 0.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 276592 | O-012 C | 80/20 | 0.28 MW | 0.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 915011 | Y3-013 1 | Adder | 1.98 MW | 1.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 915021 | Y3-013 2 | Adder | 1.98 MW | 1.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 915031 | Y3-013 3 | Adder | 1.98 MW | 1.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 925581 | AC1-033 C | Adder | 0.74 MW | 0.63 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 930482 | AB1-089 CT | Adder | 18.92 MW | 16.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 930483 | AB1-089 ST | Adder | 15.04 MW | 12.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 930761 | AB1-122 CT1 | Adder | 35.57 MW | 30.23 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 930771 | AB1-122 CT2 | Adder | 40.58 MW | 34.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 933411 | AC2-154 C | Adder | 1.43 MW | 1.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 938511 | AE1-070 1 | Adder | 5.04 MW | 4.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 938521 | AE1-070 2 | Adder | 4.6 MW | 3.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 938851 | AE1-113 C O1 | Adder | 4.4 MW | 3.74 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 938861 | AE1-114 C O1 | Adder | 2.03 MW | 1.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 939051 | AE1-134 1 | Adder | 0.71 MW | 0.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 939061 | AE1-134 2 | Adder | 0.71 MW | 0.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 939321 | AE1-163 C O1 | Adder | 3.26 MW | 2.77 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 939351 | AE1-166 C O1 | Adder | 5.53 MW | 4.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 939401 | AE1-172 C O1 | Adder | 2.66 MW | 2.26 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 940501 | AE2-035 C | Adder | 1.27 MW | 1.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 941131 | AE2-107 C | Adder | 3.36 MW | 2.86 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 941551 | AE2-152 C O1 | Adder | 6.38 MW | 5.42 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 946151 | AF1-280 C O1 | Adder | 8.07 MW | 6.86 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 946161 | AF1-281 C O1 | Adder | 0.18 MW | 0.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 946321 | AF1-296 C O1 | Adder | 2.05 MW | 1.74 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 946501 | AF1-314 C | Adder | 2.25 MW | 1.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 946541 | AF1-318 C O1 | Adder | 3.02 MW | 2.57 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 946661 | AF1-330 C | Adder | 1.04 MW | 0.88 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 946671 | AF1-331 | Adder | 1.23 MW | 1.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 957331 | AF2-027 C | Adder | 1.32 MW | 1.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 957371 | AF2-031 C O1 | 80/20 | 0.72 MW | 0.72 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 957401 | AF2-034 C | Adder | 0.78 MW | 0.67 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 957471 | AF2-041 C | Adder | 11.04 MW | 9.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 957751 | AF2-069 C | Adder | 0.12 MW | 0.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 957761 | AF2-070 C | Adder | 0.18 MW | 0.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 958011 | AF2-095 C O1 | Adder | 10.25 MW | 8.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 958021 | AF2-096 C | Adder | 19.75 MW | 16.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 958341 | AF2-128 C O1 | Adder | 0.8 MW | 0.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 934101 | AD2-000 1 | Adder | 2.88 MW | 2.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 934111 | AD2-000 2 | Adder | 3.28 MW | 2.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 945351 | AF1-200 FTIR | Adder | 143.89 MW | 122.31 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 953871 | J847 | External Queue | 12.12 MW | 12.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 955741 | J1058 | External Queue | 36.76 MW | 36.76 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 990541 | J1332 | External Queue | 30.8 MW | 30.8 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 990546 | J1333 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 990551 | J1334 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 990556 | J1335 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 990561 | J1336 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 990576 | J1339 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 990581 | J1340 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 990761 | J1386 | External Queue | 17.46 MW | 17.46 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 990976 | J1447 | External Queue | 52.4 MW | 52.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | 991246 | J1684 | External Queue | 31.68 MW | 31.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.41 MW | 0.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.17 MW | 1.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.1 MW | 0.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 40.47 MW | 40.47 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.2 MW | 9.2 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.28 MW | 0.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.73 MW | 6.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.57 MW | 0.57 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.64 MW | 0.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.96 MW | 1.96 MW |
| Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 962691 | AG1-118 C O1 | 80/20 | 10.48 MW | 10.48 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 962701 | AG1-119 C | 80/20 | 15.68 MW | 15.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 962711 | AG1-120 C O1 | 80/20 | 9.0 MW | 9.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 962781 | AG1-127 C | 80/20 | 4.24 MW | 4.24 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 16.98 MW | 16.98 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 965551 | AG1-423 C O1 | 80/20 | 10.31 MW | 10.31 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C O1 | 80/20 | 1.96 MW | 1.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | 80/20 | 10.99 MW | 10.99 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 272364 | ESS H440N ;R | 80/20 | 1.67 MW | 1.67 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.09 MW | 0.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.06 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 2.43 MW | 2.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 919581 | AA2-030 C | 80/20 | 14.27 MW | 14.27 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 926431 | AC1-114 | 80/20 | 0.68 MW | 0.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 927511 | AC1-113 1 | 80/20 | 0.34 MW | 0.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 927521 | AC1-113 2 | 80/20 | 0.34 MW | 0.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 933911 | AD1-013 C | 80/20 | 1.17 MW | 1.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.01 MW | 0.01 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 934971 | AD1-129 C | 80/20 | 1.04 MW | 1.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 1.62 MW | 1.62 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 937311 | AD2-172 C | 80/20 | 3.49 MW | 3.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 958911 | AF2-182 C | 80/20 | 20.64 MW | 20.64 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 3.67 MW | 3.67 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 8.54 MW | 8.54 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 960721 | AF2-363 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 960751 | AF2-366 C | 80/20 | 4.22 MW | 4.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 3.35 MW | 3.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 5.72 MW | 5.72 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 3.81 MW | 3.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274656 | BYRON ;1U | 80/20 | 35.35 MW | 35.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274657 | BYRON ;2U | 80/20 | 34.66 MW | 34.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274662 | QUAD CITI;1U | 80/20 | 11.13 MW | 11.13 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274663 | QUAD CITI;2U | 80/20 | 11.16 MW | 11.16 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274699 | CORDOVA ;1C | 80/20 | 1.95 MW | 1.95 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274700 | CORDOVA ;2C | 80/20 | 1.95 MW | 1.95 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274701 | CORDOVA ;1S | 80/20 | 2.2 MW | 2.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274715 | NELSON EC;1C | 80/20 | 2.6 MW | 2.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274716 | NELSON EC;1S | 80/20 | 1.9 MW | 1.9 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274717 | NELSON EC;2C | 80/20 | 2.63 MW | 2.63 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274718 | NELSON EC;2S | 80/20 | 1.92 MW | 1.92 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274760 | LEE CO EC;1U | 80/20 | 1.81 MW | 1.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274761 | LEE CO EC;2U | 80/20 | 1.81 MW | 1.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274762 | LEE CO EC;3U | 80/20 | 1.81 MW | 1.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274763 | LEE CO EC;4U | 80/20 | 1.79 MW | 1.79 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274764 | LEE CO EC;5U | 80/20 | 1.82 MW | 1.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274765 | LEE CO EC;6U | 80/20 | 1.82 MW | 1.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274766 | LEE CO EC;7U | 80/20 | 1.79 MW | 1.79 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274767 | LEE CO EC;8U | 80/20 | 1.79 MW | 1.79 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274822 | ROCKFORD ;11 | 80/20 | 3.79 MW | 3.79 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274823 | ROCKFORD ;21 | 80/20 | 3.89 MW | 3.89 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274824 | ROCKFORD ;12 | 80/20 | 3.76 MW | 3.76 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 0.28 MW | 0.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 0.32 MW | 0.32 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 0.32 MW | 0.32 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.15 MW | 0.15 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.16 MW | 0.16 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.29 MW | 0.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 276162 | X1-087 | 80/20 | 0.28 MW | 0.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 276590 | R-018 | 80/20 | 0.22 MW | 0.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.27 MW | 0.27 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.14 MW | 0.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.15 MW | 0.15 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 930482 | AB1-089 CT | 80/20 | 43.61 MW | 43.61 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 930483 | AB1-089 ST | 80/20 | 34.67 MW | 34.67 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 932881 | AC2-115 1 | 80/20 | 0.68 MW | 0.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 932891 | AC2-115 2 | 80/20 | 0.68 MW | 0.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 932921 | AC2-116 | 80/20 | 0.24 MW | 0.24 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 4.71 MW | 4.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 939051 | AE1-134 1 | 80/20 | 1.11 MW | 1.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 939061 | AE1-134 2 | 80/20 | 1.11 MW | 1.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 940501 | AE2-035 C | 80/20 | 3.49 MW | 3.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 941131 | AE2-107 C | 80/20 | 3.67 MW | 3.67 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 946151 | AF1-280 C O1 | 80/20 | 15.71 MW | 15.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.34 MW | 0.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 2.8 MW | 2.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 6.18 MW | 6.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 946671 | AF1-331 | 80/20 | 1.52 MW | 1.52 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 0.46 MW | 0.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.17 MW | 0.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 952431 | J760 | External Queue | 3.89 MW | 3.89 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 953681 | J818 | External Queue | 9.65 MW | 9.65 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 953901 | J850 | External Queue | 15.89 MW | 15.89 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 953921 | J855 C | External Queue | 0.94 MW | 0.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 954001 | J864 | External Queue | 3.12 MW | 3.12 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 954061 | J870 | External Queue | 12.45 MW | 12.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 954071 | J871 | External Queue | 6.23 MW | 6.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 955971 | J1084 | External Queue | 7.99 MW | 7.99 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 990116 | J1214 | External Queue | 29.06 MW | 29.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 990406 | J1304 | External Queue | 6.94 MW | 6.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 990511 | J1326 | External Queue | 7.26 MW | 7.26 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | 990726 | J1377 | External Queue | 12.85 MW | 12.85 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.04 MW | 0.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.38 MW | 0.38 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.15 MW | 0.15 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.34 MW | 0.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 33.02 MW | 33.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.9 MW | 6.9 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.06 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.8 MW | 1.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.96 MW | 6.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.73 MW | 0.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.16 MW | 0.16 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 17.26 MW | 14.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 23.12 MW | 19.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 22.84 MW | 19.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 9.01 MW | 7.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 5.97 MW | 5.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 7.3 MW | 6.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 13.71 MW | 11.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 26.02 MW | 22.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 3.74 MW | 3.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 1.24 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 18.06 MW | 15.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 15.24 MW | 12.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 4.32 MW | 3.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 4.03 MW | 3.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 16.84 MW | 14.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 2.05 MW | 1.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 1.68 MW | 1.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.53 MW | 0.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 2.75 MW | 2.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 18.46 MW | 15.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.99 MW | 1.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.99 MW | 1.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 1.21 MW | 1.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927091 | AC1-204 GEN1 | 80/20 | 13.22 MW | 13.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927093 | AC1-204 GEN2 | 80/20 | 13.24 MW | 13.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 4.5 MW | 4.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 4.51 MW | 4.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.92 MW | 1.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.97 MW | 0.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 3.02 MW | 2.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 19.88 MW | 19.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 3.32 MW | 2.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 4.14 MW | 3.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 2.44 MW | 2.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 8.74 MW | 7.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.65 MW | 2.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.57 MW | 2.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | 80/20 | 8.35 MW | 8.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | 80/20 | 8.36 MW | 8.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.87 MW | 1.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 3.29 MW | 2.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.88 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 8.55 MW | 7.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 13.25 MW | 11.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 8.81 MW | 7.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 4.0 MW | 3.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 11.3 MW | 9.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 11.31 MW | 9.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 21.46 MW | 18.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 3.82 MW | 3.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 7.47 MW | 6.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 14.94 MW | 12.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 6.28 MW | 5.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 6.05 MW | 5.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 5.56 MW | 4.72 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 22.75 MW | 19.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 7.31 MW | 6.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.97 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 6.18 MW | 5.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 7.28 MW | 6.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 4.16 MW | 3.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 7.1 MW | 6.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 4.73 MW | 4.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 29.69 MW | 29.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 28.88 MW | 28.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 25.8 MW | 25.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 27.26 MW | 27.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 27.37 MW | 27.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 12.42 MW | 12.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 12.43 MW | 12.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274687 | WILL CNTY;4U | 80/20 | 12.46 MW | 12.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274704 | KENDALL ;1C | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274705 | KENDALL ;1S | 80/20 | 2.95 MW | 2.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274706 | KENDALL ;2C | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274707 | KENDALL ;2S | 80/20 | 2.95 MW | 2.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274728 | ELWOOD EC;5P | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274729 | ELWOOD EC;1P | 80/20 | 3.55 MW | 3.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274730 | ELWOOD EC;6P | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274731 | ELWOOD EC;2P | 80/20 | 3.55 MW | 3.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274732 | ELWOOD EC;7P | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274733 | ELWOOD EC;3P | 80/20 | 3.55 MW | 3.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274734 | ELWOOD EC;8P | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274735 | ELWOOD EC;4P | 80/20 | 3.55 MW | 3.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274736 | ELWOOD EC;9P | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 0.64 MW | 0.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.48 MW | 0.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 0.91 MW | 0.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.24 MW | 0.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276159 | W4-082 | 80/20 | 0.13 MW | 0.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.49 MW | 1.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 38.24 MW | 32.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 30.41 MW | 25.84 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 71.82 MW | 61.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | 80/20 | 79.59 MW | 79.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 2.32 MW | 1.97 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | 80/20 | 9.82 MW | 9.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | 80/20 | 8.97 MW | 8.97 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 8.69 MW | 7.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 4.11 MW | 3.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.44 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.44 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 6.16 MW | 5.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | 80/20 | 10.63 MW | 10.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 5.28 MW | 4.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 8.06 MW | 6.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.57 MW | 2.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 6.85 MW | 5.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | 80/20 | 12.27 MW | 12.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 4.8 MW | 4.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 16.33 MW | 13.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.36 MW | 0.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 4.15 MW | 3.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 4.55 MW | 3.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 6.07 MW | 5.16 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 2.09 MW | 1.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 2.5 MW | 2.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.62 MW | 2.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 1.54 MW | 1.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 22.41 MW | 19.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.25 MW | 0.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.35 MW | 0.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 16.57 MW | 14.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 40.58 MW | 40.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.61 MW | 1.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 5.81 MW | 4.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | 80/20 | 6.44 MW | 6.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 273.44 MW | 273.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.74 MW | 0.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.06 MW | 2.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.26 MW | 0.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 64.19 MW | 64.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 20.29 MW | 20.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.18 MW | 0.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.05 MW | 4.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.66 MW | 13.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.09 MW | 1.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.92 MW | 3.92 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 17.26 MW | 14.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 23.12 MW | 19.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 22.84 MW | 19.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 9.01 MW | 7.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 5.97 MW | 5.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 7.3 MW | 6.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 13.71 MW | 11.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 26.02 MW | 22.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 3.74 MW | 3.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 1.24 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 18.06 MW | 15.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 15.24 MW | 12.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 4.32 MW | 3.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 4.03 MW | 3.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 16.84 MW | 14.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 2.05 MW | 1.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 1.68 MW | 1.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.53 MW | 0.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 2.75 MW | 2.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 18.46 MW | 15.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.99 MW | 1.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.99 MW | 1.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 1.21 MW | 1.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927091 | AC1-204 GEN1 | 80/20 | 13.22 MW | 13.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927093 | AC1-204 GEN2 | 80/20 | 13.24 MW | 13.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 4.5 MW | 4.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 4.51 MW | 4.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.92 MW | 1.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.97 MW | 0.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 3.02 MW | 2.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 19.88 MW | 19.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 3.32 MW | 2.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 4.14 MW | 3.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 2.44 MW | 2.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 8.74 MW | 7.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.65 MW | 2.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.57 MW | 2.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | 80/20 | 8.35 MW | 8.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | 80/20 | 8.36 MW | 8.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.87 MW | 1.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 3.29 MW | 2.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.88 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 8.55 MW | 7.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 13.25 MW | 11.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 8.81 MW | 7.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 4.0 MW | 3.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 11.3 MW | 9.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 11.31 MW | 9.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 21.46 MW | 18.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 3.82 MW | 3.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 7.47 MW | 6.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 14.94 MW | 12.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 6.28 MW | 5.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 6.05 MW | 5.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 5.56 MW | 4.72 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 22.75 MW | 19.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 7.31 MW | 6.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.97 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 6.18 MW | 5.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 7.28 MW | 6.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 4.16 MW | 3.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 7.1 MW | 6.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 4.73 MW | 4.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 29.69 MW | 29.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 28.88 MW | 28.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 25.8 MW | 25.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 27.26 MW | 27.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 27.37 MW | 27.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 12.42 MW | 12.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 12.43 MW | 12.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274687 | WILL CNTY;4U | 80/20 | 12.46 MW | 12.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274704 | KENDALL ;1C | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274705 | KENDALL ;1S | 80/20 | 2.95 MW | 2.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274706 | KENDALL ;2C | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274707 | KENDALL ;2S | 80/20 | 2.95 MW | 2.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274728 | ELWOOD EC;5P | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274729 | ELWOOD EC;1P | 80/20 | 3.55 MW | 3.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274730 | ELWOOD EC;6P | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274731 | ELWOOD EC;2P | 80/20 | 3.55 MW | 3.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274732 | ELWOOD EC;7P | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274733 | ELWOOD EC;3P | 80/20 | 3.55 MW | 3.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274734 | ELWOOD EC;8P | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274735 | ELWOOD EC;4P | 80/20 | 3.55 MW | 3.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274736 | ELWOOD EC;9P | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 0.64 MW | 0.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.48 MW | 0.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 0.91 MW | 0.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.24 MW | 0.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276159 | W4-082 | 80/20 | 0.13 MW | 0.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.49 MW | 1.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 38.24 MW | 32.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 30.41 MW | 25.84 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 71.82 MW | 61.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | 80/20 | 79.59 MW | 79.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 2.32 MW | 1.97 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | 80/20 | 9.82 MW | 9.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | 80/20 | 8.97 MW | 8.97 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 8.69 MW | 7.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 4.11 MW | 3.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.44 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.44 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 6.16 MW | 5.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | 80/20 | 10.63 MW | 10.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 5.28 MW | 4.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 8.06 MW | 6.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.57 MW | 2.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 6.85 MW | 5.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | 80/20 | 12.27 MW | 12.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 4.8 MW | 4.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 16.33 MW | 13.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.36 MW | 0.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 4.15 MW | 3.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 4.55 MW | 3.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 6.07 MW | 5.16 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 2.09 MW | 1.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 2.5 MW | 2.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.62 MW | 2.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 1.54 MW | 1.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 22.41 MW | 19.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.25 MW | 0.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.35 MW | 0.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 16.57 MW | 14.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 40.58 MW | 40.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.61 MW | 1.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 5.81 MW | 4.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | 80/20 | 6.44 MW | 6.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 273.44 MW | 273.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.74 MW | 0.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.06 MW | 2.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.26 MW | 0.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 64.19 MW | 64.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 20.29 MW | 20.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.18 MW | 0.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.05 MW | 4.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.66 MW | 13.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.09 MW | 1.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.92 MW | 3.92 MW |
| Details for GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 961651 | AG1-005 C O1 | Adder | 8.61 MW | 7.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 962691 | AG1-118 C O1 | Adder | 11.34 MW | 9.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 962701 | AG1-119 C | Adder | 11.29 MW | 9.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 962711 | AG1-120 C O1 | Adder | 4.44 MW | 3.77 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 962721 | AG1-121 C O1 | Adder | 2.96 MW | 2.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 962781 | AG1-127 C | Adder | 3.58 MW | 3.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 964361 | AG1-298 O1 | 80/20 | 45.09 MW | 45.09 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 964581 | AG1-321 C O1 | Adder | 6.8 MW | 5.78 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 966821 | AG1-553 C O1 | Adder | 12.86 MW | 10.93 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 965061 | AG1-371 | Adder | 1.84 MW | 1.56 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 965081 | AG1-373 | Adder | 0.61 MW | 0.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 965141 | AG1-379 C | Adder | 9.15 MW | 7.77 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 965551 | AG1-423 C O1 | Adder | 7.53 MW | 6.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 965661 | AG1-434 C O1 | Adder | 2.13 MW | 1.81 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 965671 | AG1-435 C O1 | Adder | 2.0 MW | 1.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 965931 | AG1-462 C O1 | Adder | 8.32 MW | 7.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 966091 | AG1-478 C | Adder | 1.14 MW | 0.97 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 966431 | AG1-512 C | Adder | 0.81 MW | 0.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 966441 | AG1-513 C | Adder | 0.26 MW | 0.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 966651 | AG1-535 O1 | 80/20 | 7.84 MW | 7.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 272364 | ESS H440N ;R | Adder | 1.35 MW | 1.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 919581 | AA2-030 C | Adder | 9.12 MW | 7.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 926331 | AC1-110 1 | Adder | 0.98 MW | 0.83 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 926341 | AC1-110 2 | Adder | 0.98 MW | 0.83 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 926821 | AC1-168 C O1 | Adder | 0.6 MW | 0.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 927451 | AC1-142A 1 | Adder | 2.33 MW | 1.98 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 927461 | AC1-142A 2 | Adder | 2.33 MW | 1.98 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 933911 | AD1-013 C | Adder | 0.95 MW | 0.8 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 933931 | AD1-016 C | Adder | 0.48 MW | 0.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 934051 | AD1-031 C O1 | Adder | 1.5 MW | 1.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 934721 | AD1-100 C | Adder | 10.23 MW | 8.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 934971 | AD1-129 C | Adder | 0.47 MW | 0.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 936291 | AD2-038 C O1 | Adder | 1.76 MW | 1.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 936371 | AD2-047 C O1 | Adder | 2.56 MW | 2.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 936461 | AD2-060 | Adder | 1.51 MW | 1.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 936511 | AD2-066 C O1 | Adder | 4.49 MW | 3.81 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 937001 | AD2-134 C | Adder | 1.3 MW | 1.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 937311 | AD2-172 C | Adder | 1.27 MW | 1.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 937401 | AD2-194 1 | Adder | 4.28 MW | 3.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 937411 | AD2-194 2 | Adder | 4.29 MW | 3.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 942421 | AE2-255 C O1 | Adder | 1.67 MW | 1.42 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 942651 | AE2-281 C O1 | Adder | 0.47 MW | 0.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 942991 | AE2-321 C | Adder | 4.24 MW | 3.61 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 943121 | AE2-341 C | Adder | 6.4 MW | 5.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 943591 | AF1-030 C O1 | Adder | 4.26 MW | 3.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 943801 | AF1-048 C | Adder | 1.98 MW | 1.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 945501 | AF1-215 C O1 | Adder | -10.08 MW | -8.57 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 958481 | AF2-142 C | Adder | 6.1 MW | 5.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 958491 | AF2-143 C | Adder | 5.98 MW | 5.09 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 958911 | AF2-182 C | Adder | 10.61 MW | 9.02 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 958921 | AF2-183 C | Adder | 1.89 MW | 1.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 959081 | AF2-199 C | Adder | 3.68 MW | 3.13 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 959091 | AF2-200 C O1 | Adder | 7.36 MW | 6.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 959101 | AF2-201 C O1 | Adder | 3.11 MW | 2.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 959351 | AF2-226 C | Adder | 1.52 MW | 1.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 960281 | AF2-319 C | Adder | 1.52 MW | 1.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 960381 | AF2-329 | Adder | 2.68 MW | 2.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 960581 | AF2-349 C | Adder | 11.29 MW | 9.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 960591 | AF2-350 C O1 | Adder | 4.52 MW | 3.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 960601 | AF2-351 C O1 | Adder | 0.6 MW | 0.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 960721 | AF2-363 C O1 | Adder | 3.04 MW | 2.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 960751 | AF2-366 C | Adder | 3.57 MW | 3.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 961011 | AF2-392 C O1 | Adder | 2.06 MW | 1.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 961021 | AF2-393 O1 | Adder | 3.51 MW | 2.98 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 961031 | AF2-394 O1 | Adder | 2.34 MW | 1.99 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 961501 | AF2-441 C O1 | 80/20 | 6.88 MW | 6.88 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274723 | RIVER EC ;12 | 80/20 | 2.59 MW | 2.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274724 | RIVER EC ;11 | 80/20 | 2.49 MW | 2.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274751 | CRETE EC ;1U | 80/20 | 2.24 MW | 2.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274752 | CRETE EC ;2U | 80/20 | 2.24 MW | 2.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274753 | CRETE EC ;3U | 80/20 | 2.24 MW | 2.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274754 | CRETE EC ;4U | 80/20 | 2.24 MW | 2.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274788 | SE CHICAG;5U | 80/20 | 3.45 MW | 3.45 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274789 | SE CHICAG;6U | 80/20 | 3.46 MW | 3.46 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274790 | SE CHICAG;7U | 80/20 | 3.5 MW | 3.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274791 | SE CHICAG;8U | 80/20 | 3.5 MW | 3.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274792 | SE CHICAG;9U | 80/20 | 3.6 MW | 3.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274793 | SE CHICAG;0U | 80/20 | 3.6 MW | 3.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274794 | SE CHICAG;1U | 80/20 | 3.6 MW | 3.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 274795 | SE CHICAG;2U | 80/20 | 3.6 MW | 3.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 276164 | X3-005 C | 80/20 | 0.05 MW | 0.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 276592 | O-012 C | 80/20 | 0.28 MW | 0.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 915011 | Y3-013 1 | Adder | 1.98 MW | 1.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 915021 | Y3-013 2 | Adder | 1.98 MW | 1.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 915031 | Y3-013 3 | Adder | 1.98 MW | 1.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 925581 | AC1-033 C | Adder | 0.74 MW | 0.63 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 930482 | AB1-089 CT | Adder | 18.92 MW | 16.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 930483 | AB1-089 ST | Adder | 15.04 MW | 12.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 930761 | AB1-122 CT1 | Adder | 35.57 MW | 30.23 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 930771 | AB1-122 CT2 | Adder | 40.58 MW | 34.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 933411 | AC2-154 C | Adder | 1.43 MW | 1.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 938511 | AE1-070 1 | Adder | 5.04 MW | 4.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 938521 | AE1-070 2 | Adder | 4.6 MW | 3.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 938851 | AE1-113 C O1 | Adder | 4.4 MW | 3.74 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 938861 | AE1-114 C O1 | Adder | 2.03 MW | 1.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 939051 | AE1-134 1 | Adder | 0.71 MW | 0.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 939061 | AE1-134 2 | Adder | 0.71 MW | 0.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 939321 | AE1-163 C O1 | Adder | 3.26 MW | 2.77 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 939351 | AE1-166 C O1 | Adder | 5.53 MW | 4.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 939401 | AE1-172 C O1 | Adder | 2.66 MW | 2.26 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 940501 | AE2-035 C | Adder | 1.27 MW | 1.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 941131 | AE2-107 C | Adder | 3.36 MW | 2.86 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 941551 | AE2-152 C O1 | Adder | 6.38 MW | 5.42 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 946151 | AF1-280 C O1 | Adder | 8.07 MW | 6.86 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 946161 | AF1-281 C O1 | Adder | 0.18 MW | 0.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 946321 | AF1-296 C O1 | Adder | 2.05 MW | 1.74 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 946501 | AF1-314 C | Adder | 2.25 MW | 1.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 946541 | AF1-318 C O1 | Adder | 3.02 MW | 2.57 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 946661 | AF1-330 C | Adder | 1.04 MW | 0.88 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 946671 | AF1-331 | Adder | 1.23 MW | 1.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 957331 | AF2-027 C | Adder | 1.32 MW | 1.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 957371 | AF2-031 C O1 | 80/20 | 0.72 MW | 0.72 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 957401 | AF2-034 C | Adder | 0.78 MW | 0.67 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 957471 | AF2-041 C | Adder | 11.04 MW | 9.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 957751 | AF2-069 C | Adder | 0.12 MW | 0.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 957761 | AF2-070 C | Adder | 0.18 MW | 0.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 958011 | AF2-095 C O1 | Adder | 10.25 MW | 8.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 958021 | AF2-096 C | Adder | 19.75 MW | 16.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 958341 | AF2-128 C O1 | Adder | 0.8 MW | 0.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 934101 | AD2-000 1 | Adder | 2.88 MW | 2.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 934111 | AD2-000 2 | Adder | 3.28 MW | 2.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 945351 | AF1-200 FTIR | Adder | 143.89 MW | 122.31 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 953871 | J847 | External Queue | 12.12 MW | 12.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 955741 | J1058 | External Queue | 36.76 MW | 36.76 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 990541 | J1332 | External Queue | 30.8 MW | 30.8 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 990546 | J1333 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 990551 | J1334 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 990556 | J1335 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 990561 | J1336 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 990576 | J1339 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 990581 | J1340 | External Queue | 31.62 MW | 31.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 990761 | J1386 | External Queue | 17.46 MW | 17.46 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | 990976 | J1447 | External Queue | 52.4 MW | 52.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.41 MW | 0.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.17 MW | 1.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.1 MW | 0.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 40.47 MW | 40.47 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.2 MW | 9.2 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.28 MW | 0.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.73 MW | 6.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.57 MW | 0.57 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.64 MW | 0.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o EXT_P12:345:NIPS:34513:17BURR_OAK:17SCHAHFER:1-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.96 MW | 1.96 MW |
| Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 961651 | AG1-005 C O1 | Adder | 30.05 MW | 25.54 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 962691 | AG1-118 C O1 | Adder | 38.33 MW | 32.58 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 962701 | AG1-119 C | Adder | 37.78 MW | 32.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 962711 | AG1-120 C O1 | Adder | 14.96 MW | 12.72 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 962721 | AG1-121 C O1 | Adder | 10.36 MW | 8.8 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 962781 | AG1-127 C | Adder | 12.12 MW | 10.3 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 964361 | AG1-298 O1 | Adder | 108.85 MW | 92.52 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 964401 | AG1-302 C O1 | Adder | 34.56 MW | 29.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 964581 | AG1-321 C O1 | Adder | 25.28 MW | 21.49 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 964861 | AG1-349 C O1 | Adder | 29.84 MW | 25.37 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 966821 | AG1-553 C O1 | Adder | 45.31 MW | 38.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 965061 | AG1-371 | Adder | 6.22 MW | 5.29 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 965081 | AG1-373 | Adder | 2.08 MW | 1.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 965141 | AG1-379 C | Adder | 28.97 MW | 24.63 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 965551 | AG1-423 C O1 | Adder | 25.19 MW | 21.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 965661 | AG1-434 C O1 | Adder | 7.24 MW | 6.15 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 965671 | AG1-435 C O1 | Adder | 7.0 MW | 5.95 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 965681 | AG1-436 C | Adder | 16.22 MW | 13.78 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 965791 | AG1-447 | Adder | 11.89 MW | 10.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 965931 | AG1-462 C O1 | Adder | 29.32 MW | 24.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 966091 | AG1-478 C | Adder | 3.44 MW | 2.93 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 966431 | AG1-512 C | Adder | 3.49 MW | 2.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 966441 | AG1-513 C | Adder | 0.87 MW | 0.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 966651 | AG1-535 O1 | Adder | 18.45 MW | 15.69 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 272364 | ESS H440N ;R | Adder | 4.6 MW | 3.91 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 919581 | AA2-030 C | Adder | 31.39 MW | 26.68 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 926331 | AC1-110 1 | Adder | 3.25 MW | 2.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 926341 | AC1-110 2 | Adder | 3.25 MW | 2.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 926821 | AC1-168 C O1 | Adder | 2.07 MW | 1.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 927451 | AC1-142A 1 | Adder | 6.97 MW | 5.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 927461 | AC1-142A 2 | Adder | 6.97 MW | 5.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 933911 | AD1-013 C | Adder | 3.22 MW | 2.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 933931 | AD1-016 C | Adder | 1.6 MW | 1.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 934051 | AD1-031 C O1 | Adder | 5.27 MW | 4.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 934721 | AD1-100 C | 80/20 | 32.94 MW | 32.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 934971 | AD1-129 C | Adder | 1.56 MW | 1.33 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 936291 | AD2-038 C O1 | Adder | 5.59 MW | 4.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 936371 | AD2-047 C O1 | 80/20 | 7.43 MW | 7.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 936461 | AD2-060 | 80/20 | 4.37 MW | 4.37 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 936511 | AD2-066 C O1 | Adder | 14.57 MW | 12.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 937001 | AD2-134 C | Adder | 4.42 MW | 3.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 937311 | AD2-172 C | Adder | 4.3 MW | 3.65 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 937401 | AD2-194 1 | Adder | 12.98 MW | 11.03 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 937411 | AD2-194 2 | Adder | 12.98 MW | 11.03 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 942111 | AE2-223 C | Adder | 3.71 MW | 3.15 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 942421 | AE2-255 C O1 | Adder | 5.28 MW | 4.49 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 942651 | AE2-281 C O1 | Adder | 1.48 MW | 1.26 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 942991 | AE2-321 C | Adder | 14.09 MW | 11.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 943121 | AE2-341 C | 80/20 | 22.0 MW | 22.0 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 943591 | AF1-030 C O1 | 80/20 | 14.63 MW | 14.63 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 943801 | AF1-048 C | Adder | 6.59 MW | 5.6 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 944931 | AF1-158 C O1 | Adder | 18.04 MW | 15.34 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 945501 | AF1-215 C O1 | Adder | 35.44 MW | 30.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 958481 | AF2-142 C | Adder | 19.23 MW | 16.34 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 958491 | AF2-143 C | Adder | 19.06 MW | 16.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 958911 | AF2-182 C | Adder | 36.28 MW | 30.84 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 958921 | AF2-183 C | Adder | 6.45 MW | 5.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 959001 | AF2-191 C O1 | Adder | 13.32 MW | 11.32 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 959081 | AF2-199 C | Adder | 12.45 MW | 10.58 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 959091 | AF2-200 C O1 | Adder | 24.9 MW | 21.16 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 959101 | AF2-201 C O1 | Adder | 10.52 MW | 8.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 959141 | AF2-205 C | Adder | 10.92 MW | 9.28 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 959341 | AF2-225 C | Adder | 11.97 MW | 10.18 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 959351 | AF2-226 C | Adder | 4.27 MW | 3.63 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 960281 | AF2-319 C | Adder | 4.27 MW | 3.63 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 960381 | AF2-329 | 80/20 | 9.23 MW | 9.23 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 960581 | AF2-349 C | Adder | 37.6 MW | 31.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 960591 | AF2-350 C O1 | 80/20 | 13.12 MW | 13.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 960601 | AF2-351 C O1 | 80/20 | 1.75 MW | 1.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 960681 | AF2-359 C | Adder | 16.22 MW | 13.78 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 960721 | AF2-363 C O1 | Adder | 10.27 MW | 8.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 960751 | AF2-366 C | Adder | 12.09 MW | 10.27 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 961011 | AF2-392 C O1 | Adder | 7.07 MW | 6.01 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 961021 | AF2-393 O1 | Adder | 12.05 MW | 10.24 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 961031 | AF2-394 O1 | Adder | 8.03 MW | 6.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 961501 | AF2-441 C O1 | Adder | 17.45 MW | 14.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 243441 | 05CKG2 | 80/20 | 56.12 MW | 56.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 244415 | 05OLIV SLR C | Adder | 0.51 MW | 0.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274654 | BRAIDWOOD;1U | 80/20 | 44.27 MW | 44.27 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274655 | BRAIDWOOD;2U | 80/20 | 43.18 MW | 43.18 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274660 | LASCO STA;1U | 80/20 | 42.79 MW | 42.79 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274661 | LASCO STA;2U | 80/20 | 42.97 MW | 42.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274708 | KENDALL ;3C | 80/20 | 6.93 MW | 6.93 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274709 | KENDALL ;3S | 80/20 | 4.58 MW | 4.58 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274710 | KENDALL ;4C | 80/20 | 6.85 MW | 6.85 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274711 | KENDALL ;4S | 80/20 | 4.58 MW | 4.58 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274770 | LINCOLN ;1U | 80/20 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274771 | LINCOLN ;2U | 80/20 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274772 | LINCOLN ;3U | 80/20 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274773 | LINCOLN ;4U | 80/20 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274774 | LINCOLN ;5U | 80/20 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274775 | LINCOLN ;6U | 80/20 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274776 | LINCOLN ;7U | 80/20 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274777 | LINCOLN ;8U | 80/20 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274788 | SE CHICAG;5U | Adder | 8.23 MW | 7.0 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274789 | SE CHICAG;6U | Adder | 8.25 MW | 7.01 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274790 | SE CHICAG;7U | Adder | 8.36 MW | 7.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274791 | SE CHICAG;8U | Adder | 8.36 MW | 7.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274792 | SE CHICAG;9U | Adder | 8.35 MW | 7.1 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274793 | SE CHICAG;0U | Adder | 8.35 MW | 7.1 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274794 | SE CHICAG;1U | Adder | 8.35 MW | 7.1 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274795 | SE CHICAG;2U | Adder | 8.35 MW | 7.1 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274847 | GR RIDGE ;BU | 80/20 | 1.02 MW | 1.02 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274871 | GR RIDGE ;2U | 80/20 | 0.38 MW | 0.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274887 | PILOT HIL;1U | 80/20 | 1.3 MW | 1.3 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274888 | KELLY CRK;1U | 80/20 | 1.3 MW | 1.3 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 276164 | X3-005 C | 80/20 | 0.13 MW | 0.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 915011 | Y3-013 1 | Adder | 6.37 MW | 5.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 915021 | Y3-013 2 | Adder | 6.37 MW | 5.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 915031 | Y3-013 3 | Adder | 6.37 MW | 5.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 925581 | AC1-033 C | Adder | 2.59 MW | 2.21 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 930482 | AB1-089 CT | Adder | 63.57 MW | 54.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 930483 | AB1-089 ST | Adder | 50.54 MW | 42.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 930761 | AB1-122 CT1 | Adder | 120.56 MW | 102.47 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 930771 | AB1-122 CT2 | Adder | 124.11 MW | 105.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 933281 | AC2-140 C | 80/20 | 1.86 MW | 1.86 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 933411 | AC2-154 C | 80/20 | 4.16 MW | 4.16 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 938511 | AE1-070 1 | Adder | 15.25 MW | 12.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 938521 | AE1-070 2 | Adder | 13.95 MW | 11.86 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 938851 | AE1-113 C O1 | Adder | 13.94 MW | 11.85 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 938861 | AE1-114 C O1 | Adder | 6.92 MW | 5.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 939051 | AE1-134 1 | Adder | 2.44 MW | 2.07 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 939061 | AE1-134 2 | Adder | 2.44 MW | 2.07 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 939321 | AE1-163 C O1 | Adder | 10.38 MW | 8.82 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 939351 | AE1-166 C O1 | 80/20 | 17.12 MW | 17.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 939401 | AE1-172 C O1 | Adder | 9.38 MW | 7.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 939741 | AE1-205 C O1 | Adder | 15.97 MW | 13.57 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 940501 | AE2-035 C | Adder | 4.3 MW | 3.65 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 941131 | AE2-107 C | Adder | 11.4 MW | 9.69 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 941551 | AE2-152 C O1 | 80/20 | 19.76 MW | 19.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 941731 | AE2-173 O1 | Adder | 9.5 MW | 8.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 946151 | AF1-280 C O1 | Adder | 27.61 MW | 23.47 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 946161 | AF1-281 C O1 | Adder | 0.6 MW | 0.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 946321 | AF1-296 C O1 | Adder | 7.2 MW | 6.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 946501 | AF1-314 C | Adder | 7.61 MW | 6.47 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 946541 | AF1-318 C O1 | Adder | 10.56 MW | 8.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 946661 | AF1-330 C | Adder | 3.45 MW | 2.93 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 946671 | AF1-331 | Adder | 4.18 MW | 3.55 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 957331 | AF2-027 C | Adder | 4.24 MW | 3.61 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 957371 | AF2-031 C O1 | Adder | 1.74 MW | 1.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 957401 | AF2-034 C | Adder | 2.34 MW | 1.99 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 957471 | AF2-041 C | Adder | 37.35 MW | 31.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 957751 | AF2-069 C | Adder | 0.44 MW | 0.37 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 957761 | AF2-070 C | Adder | 0.62 MW | 0.52 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 958011 | AF2-095 C O1 | 80/20 | 29.74 MW | 29.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 958021 | AF2-096 C | 80/20 | 55.95 MW | 55.95 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 958341 | AF2-128 C O1 | Adder | 2.8 MW | 2.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 958381 | AF2-132 C O1 | Adder | 34.56 MW | 29.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 958391 | AF2-133 C O1 | Adder | 34.11 MW | 28.99 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 958401 | AF2-134 C O1 | Adder | 11.81 MW | 10.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 934101 | AD2-000 1 | Adder | 9.75 MW | 8.29 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 934111 | AD2-000 2 | Adder | 10.04 MW | 8.53 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274805 | UNIV PK N;1U | 80/20 | 1.38 MW | 1.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274807 | UNIV PK N;3U | 80/20 | 1.39 MW | 1.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274808 | UNIV PK N;4U | 80/20 | 1.38 MW | 1.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274810 | UNIV PK N;6U | 80/20 | 1.38 MW | 1.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274811 | UNIV PK N;7U | 80/20 | 1.39 MW | 1.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274815 | UNIV PK N;XU | 80/20 | 1.38 MW | 1.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 274816 | UNIV PK N;YU | 80/20 | 1.39 MW | 1.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | 945351 | AF1-200 FTIR | 80/20 | 462.39 MW | 462.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.74 MW | 1.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.5 MW | 0.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.78 MW | 1.78 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 206.46 MW | 206.46 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 75.62 MW | 75.62 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.09 MW | 1.09 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 11.6 MW | 11.6 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.32 MW | 3.32 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 25.81 MW | 25.81 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.87 MW | 2.87 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.79 MW | 0.79 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.38 MW | 6.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#709_546 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 6.47 MW | 6.47 MW |
| Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 961651 | AG1-005 C O1 | Adder | 30.28 MW | 25.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 962601 | AG1-109 | Adder | 4.9 MW | 4.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 962691 | AG1-118 C O1 | Adder | 39.84 MW | 33.87 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 962701 | AG1-119 C | Adder | 39.11 MW | 33.24 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 962711 | AG1-120 C O1 | Adder | 15.5 MW | 13.18 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 962721 | AG1-121 C O1 | Adder | 10.45 MW | 8.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 962781 | AG1-127 C | Adder | 12.59 MW | 10.7 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 964361 | AG1-298 O1 | Adder | 113.99 MW | 96.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 964581 | AG1-321 C O1 | Adder | 25.19 MW | 21.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 966821 | AG1-553 C O1 | Adder | 45.61 MW | 38.77 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 965061 | AG1-371 | Adder | 6.42 MW | 5.46 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 965081 | AG1-373 | Adder | 2.14 MW | 1.82 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 965141 | AG1-379 C | Adder | 29.92 MW | 25.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 965551 | AG1-423 C O1 | Adder | 26.08 MW | 22.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 965661 | AG1-434 C O1 | Adder | 7.44 MW | 6.33 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 965671 | AG1-435 C O1 | Adder | 7.06 MW | 6.0 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 965681 | AG1-436 C | Adder | 16.94 MW | 14.4 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 965791 | AG1-447 | Adder | 12.42 MW | 10.56 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 965931 | AG1-462 C O1 | Adder | 29.52 MW | 25.09 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 966091 | AG1-478 C | Adder | 3.59 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 966431 | AG1-512 C | Adder | 3.66 MW | 3.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 966441 | AG1-513 C | Adder | 0.91 MW | 0.77 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 966651 | AG1-535 O1 | Adder | 19.32 MW | 16.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 272364 | ESS H440N ;R | Adder | 4.75 MW | 4.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 919581 | AA2-030 C | Adder | 32.01 MW | 27.21 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 926331 | AC1-110 1 | Adder | 3.39 MW | 2.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 926341 | AC1-110 2 | Adder | 3.39 MW | 2.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 926821 | AC1-168 C O1 | Adder | 2.1 MW | 1.79 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 927451 | AC1-142A 1 | Adder | 7.28 MW | 6.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 927461 | AC1-142A 2 | Adder | 7.28 MW | 6.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 933911 | AD1-013 C | Adder | 3.32 MW | 2.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 933931 | AD1-016 C | Adder | 1.65 MW | 1.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 934051 | AD1-031 C O1 | Adder | 5.3 MW | 4.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 934721 | AD1-100 C | 80/20 | 34.4 MW | 34.4 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 934971 | AD1-129 C | Adder | 1.62 MW | 1.37 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 936141 | AD2-020 C O1 | Adder | 12.14 MW | 10.32 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 936291 | AD2-038 C O1 | Adder | 5.78 MW | 4.91 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 936371 | AD2-047 C O1 | 80/20 | 7.78 MW | 7.78 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 936461 | AD2-060 | 80/20 | 4.58 MW | 4.58 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 936511 | AD2-066 C O1 | Adder | 14.97 MW | 12.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 936631 | AD2-079 C O1 | Adder | 2.21 MW | 1.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 937001 | AD2-134 C | Adder | 4.57 MW | 3.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 937311 | AD2-172 C | Adder | 4.42 MW | 3.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 937401 | AD2-194 1 | Adder | 13.52 MW | 11.49 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 937411 | AD2-194 2 | Adder | 13.52 MW | 11.49 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 942111 | AE2-223 C | Adder | 3.58 MW | 3.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 942421 | AE2-255 C O1 | Adder | 5.45 MW | 4.63 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 942651 | AE2-281 C O1 | Adder | 1.53 MW | 1.3 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 942991 | AE2-321 C | Adder | 14.6 MW | 12.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 943021 | AE2-325 C | Adder | 6.14 MW | 5.22 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 943121 | AE2-341 C | 80/20 | 23.05 MW | 23.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 943591 | AF1-030 C O1 | 80/20 | 15.33 MW | 15.33 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 943801 | AF1-048 C | Adder | 6.82 MW | 5.8 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 944161 | AF1-084 C | Adder | 10.68 MW | 9.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 944931 | AF1-158 C O1 | Adder | 19.14 MW | 16.27 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 944961 | AF1-161 C | Adder | 4.9 MW | 4.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 945111 | AF1-176 C O1 | Adder | 19.35 MW | 16.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 958481 | AF2-142 C | Adder | 19.94 MW | 16.95 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 958491 | AF2-143 C | Adder | 19.7 MW | 16.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 958911 | AF2-182 C | Adder | 37.1 MW | 31.54 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 958921 | AF2-183 C | Adder | 6.6 MW | 5.61 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 959001 | AF2-191 C O1 | Adder | 14.09 MW | 11.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 959081 | AF2-199 C | Adder | 12.84 MW | 10.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 959091 | AF2-200 C O1 | Adder | 25.68 MW | 21.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 959101 | AF2-201 C O1 | Adder | 10.81 MW | 9.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 959341 | AF2-225 C | Adder | 11.57 MW | 9.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 959351 | AF2-226 C | Adder | 4.42 MW | 3.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 960281 | AF2-319 C | Adder | 4.42 MW | 3.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 960381 | AF2-329 | 80/20 | 9.67 MW | 9.67 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 960581 | AF2-349 C | Adder | 38.88 MW | 33.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 960591 | AF2-350 C O1 | 80/20 | 13.72 MW | 13.72 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 960601 | AF2-351 C O1 | 80/20 | 1.83 MW | 1.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 960681 | AF2-359 C | Adder | 16.94 MW | 14.4 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 960721 | AF2-363 C O1 | Adder | 10.64 MW | 9.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 960751 | AF2-366 C | Adder | 12.55 MW | 10.67 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 960981 | AF2-389 C | Adder | 5.8 MW | 4.93 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 961011 | AF2-392 C O1 | Adder | 7.22 MW | 6.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 961021 | AF2-393 O1 | Adder | 12.3 MW | 10.46 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 961031 | AF2-394 O1 | Adder | 8.2 MW | 6.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 961051 | AF2-396 O1 | Adder | 38.08 MW | 32.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 961501 | AF2-441 C O1 | 80/20 | 18.29 MW | 18.29 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 243440 | 05CKG1 | 80/20 | 40.5 MW | 40.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 243441 | 05CKG2 | 80/20 | 64.35 MW | 64.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 244415 | 05OLIV SLR C | Adder | 0.54 MW | 0.46 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274654 | BRAIDWOOD;1U | 80/20 | 46.34 MW | 46.34 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274655 | BRAIDWOOD;2U | 80/20 | 45.2 MW | 45.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274660 | LASCO STA;1U | 80/20 | 44.97 MW | 44.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274661 | LASCO STA;2U | 80/20 | 45.16 MW | 45.16 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274708 | KENDALL ;3C | 80/20 | 7.27 MW | 7.27 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274709 | KENDALL ;3S | 80/20 | 4.81 MW | 4.81 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274710 | KENDALL ;4C | 80/20 | 7.19 MW | 7.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274711 | KENDALL ;4S | 80/20 | 4.81 MW | 4.81 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274770 | LINCOLN ;1U | 80/20 | 3.25 MW | 3.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274771 | LINCOLN ;2U | 80/20 | 3.25 MW | 3.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274772 | LINCOLN ;3U | 80/20 | 3.25 MW | 3.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274773 | LINCOLN ;4U | 80/20 | 3.25 MW | 3.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274774 | LINCOLN ;5U | 80/20 | 3.25 MW | 3.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274775 | LINCOLN ;6U | 80/20 | 3.25 MW | 3.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274776 | LINCOLN ;7U | 80/20 | 3.25 MW | 3.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274777 | LINCOLN ;8U | 80/20 | 3.25 MW | 3.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274788 | SE CHICAG;5U | Adder | 8.62 MW | 7.33 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274789 | SE CHICAG;6U | Adder | 8.64 MW | 7.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274790 | SE CHICAG;7U | Adder | 8.76 MW | 7.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274791 | SE CHICAG;8U | Adder | 8.76 MW | 7.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274792 | SE CHICAG;9U | Adder | 8.74 MW | 7.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274793 | SE CHICAG;0U | Adder | 8.74 MW | 7.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274794 | SE CHICAG;1U | Adder | 8.74 MW | 7.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274795 | SE CHICAG;2U | Adder | 8.74 MW | 7.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274887 | PILOT HIL;1U | 80/20 | 1.36 MW | 1.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274888 | KELLY CRK;1U | 80/20 | 1.36 MW | 1.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 276164 | X3-005 C | 80/20 | 0.13 MW | 0.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 915011 | Y3-013 1 | Adder | 6.62 MW | 5.62 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 915021 | Y3-013 2 | Adder | 6.62 MW | 5.62 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 915031 | Y3-013 3 | Adder | 6.62 MW | 5.62 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 925581 | AC1-033 C | Adder | 2.61 MW | 2.22 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 930482 | AB1-089 CT | Adder | 65.6 MW | 55.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 930483 | AB1-089 ST | Adder | 52.16 MW | 44.33 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 930761 | AB1-122 CT1 | Adder | 123.96 MW | 105.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 930771 | AB1-122 CT2 | Adder | 129.27 MW | 109.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 933281 | AC2-140 C | 80/20 | 2.13 MW | 2.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 933411 | AC2-154 C | 80/20 | 4.35 MW | 4.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 938511 | AE1-070 1 | Adder | 15.89 MW | 13.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 938521 | AE1-070 2 | Adder | 14.53 MW | 12.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 938851 | AE1-113 C O1 | Adder | 14.39 MW | 12.23 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 938861 | AE1-114 C O1 | Adder | 7.09 MW | 6.03 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 939051 | AE1-134 1 | Adder | 2.49 MW | 2.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 939061 | AE1-134 2 | Adder | 2.49 MW | 2.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 939321 | AE1-163 C O1 | Adder | 10.73 MW | 9.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 939351 | AE1-166 C O1 | 80/20 | 17.9 MW | 17.9 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 939395 | AE1-170 C | Adder | 12.66 MW | 10.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 939401 | AE1-172 C O1 | Adder | 9.57 MW | 8.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 939741 | AE1-205 C O1 | Adder | 15.43 MW | 13.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 940501 | AE2-035 C | Adder | 4.42 MW | 3.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 941131 | AE2-107 C | Adder | 11.82 MW | 10.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 941551 | AE2-152 C O1 | 80/20 | 20.66 MW | 20.66 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 941731 | AE2-173 O1 | Adder | 9.18 MW | 7.8 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 946151 | AF1-280 C O1 | Adder | 28.24 MW | 24.0 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 946161 | AF1-281 C O1 | Adder | 0.62 MW | 0.53 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 946321 | AF1-296 C O1 | Adder | 7.26 MW | 6.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 946501 | AF1-314 C | Adder | 7.82 MW | 6.65 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 946541 | AF1-318 C O1 | Adder | 10.64 MW | 9.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 946661 | AF1-330 C | Adder | 3.57 MW | 3.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 946671 | AF1-331 | Adder | 4.32 MW | 3.67 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 957331 | AF2-027 C | Adder | 4.41 MW | 3.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 957371 | AF2-031 C O1 | Adder | 1.82 MW | 1.55 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 957401 | AF2-034 C | Adder | 2.44 MW | 2.07 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 957471 | AF2-041 C | Adder | 38.53 MW | 32.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 957751 | AF2-069 C | Adder | 0.44 MW | 0.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 957761 | AF2-070 C | Adder | 0.62 MW | 0.53 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 957891 | AF2-083 C O1 | Adder | 19.29 MW | 16.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 958011 | AF2-095 C O1 | 80/20 | 31.11 MW | 31.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 958021 | AF2-096 C | 80/20 | 58.55 MW | 58.55 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 958341 | AF2-128 C O1 | Adder | 2.82 MW | 2.4 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 934101 | AD2-000 1 | Adder | 10.02 MW | 8.52 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 934111 | AD2-000 2 | Adder | 10.45 MW | 8.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274805 | UNIV PK N;1U | 80/20 | 1.44 MW | 1.44 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274807 | UNIV PK N;3U | 80/20 | 1.45 MW | 1.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274808 | UNIV PK N;4U | 80/20 | 1.45 MW | 1.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274810 | UNIV PK N;6U | 80/20 | 1.45 MW | 1.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274811 | UNIV PK N;7U | 80/20 | 1.45 MW | 1.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274815 | UNIV PK N;XU | 80/20 | 1.44 MW | 1.44 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 274816 | UNIV PK N;YU | 80/20 | 1.45 MW | 1.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | 945351 | AF1-200 FTIR | 80/20 | 490.16 MW | 490.16 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.96 MW | 1.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.67 MW | 0.67 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.91 MW | 0.91 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 208.56 MW | 208.56 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 53.87 MW | 53.87 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.31 MW | 1.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.8 MW | 8.8 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.32 MW | 0.32 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 24.86 MW | 24.86 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.75 MW | 2.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.32 MW | 0.32 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.93 MW | 3.93 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#9287_1679 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 6.67 MW | 6.67 MW |
| Details for AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 962701 | AG1-119 C | 80/20 | 101.34 MW | 101.34 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 962711 | AG1-120 C O1 | 80/20 | 9.4 MW | 9.4 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 962781 | AG1-127 C | Adder | 4.3 MW | 3.66 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 966821 | AG1-553 C O1 | 80/20 | 26.62 MW | 26.62 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 965551 | AG1-423 C O1 | 80/20 | 67.97 MW | 67.97 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 965661 | AG1-434 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 965931 | AG1-462 C O1 | 80/20 | 17.23 MW | 17.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 272364 | ESS H440N ;R | 80/20 | 1.99 MW | 1.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 295108 | WESTBROOK C | 80/20 | 0.11 MW | 0.11 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 295110 | SUBLETTE C | 80/20 | 0.08 MW | 0.08 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 919221 | AA1-146 | 80/20 | 3.85 MW | 3.85 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 919581 | AA2-030 C | 80/20 | 22.58 MW | 22.58 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 926431 | AC1-114 | 80/20 | 0.76 MW | 0.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 927511 | AC1-113 1 | 80/20 | 0.38 MW | 0.38 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 927521 | AC1-113 2 | 80/20 | 0.38 MW | 0.38 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 933911 | AD1-013 C | 80/20 | 1.39 MW | 1.39 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 933931 | AD1-016 C | 80/20 | 0.66 MW | 0.66 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 934971 | AD1-129 C | 80/20 | 1.24 MW | 1.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 937001 | AD2-134 C | 80/20 | 1.94 MW | 1.94 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 937311 | AD2-172 C | 80/20 | 4.25 MW | 4.25 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 942991 | AE2-321 C | 80/20 | 5.53 MW | 5.53 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 958911 | AF2-182 C | 80/20 | 33.76 MW | 33.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 958921 | AF2-183 C | 80/20 | 6.0 MW | 6.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 959101 | AF2-201 C O1 | 80/20 | 10.4 MW | 10.4 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 960581 | AF2-349 C | 80/20 | 46.8 MW | 46.8 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 960721 | AF2-363 C O1 | 80/20 | 6.54 MW | 6.54 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 960751 | AF2-366 C | Adder | 4.29 MW | 3.65 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 961011 | AF2-392 C O1 | 80/20 | 4.91 MW | 4.91 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 961021 | AF2-393 O1 | 80/20 | 8.38 MW | 8.38 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 961031 | AF2-394 O1 | 80/20 | 5.58 MW | 5.58 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274656 | BYRON ;1U | 80/20 | 60.35 MW | 60.35 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274657 | BYRON ;2U | 80/20 | 58.8 MW | 58.8 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274662 | QUAD CITI;1U | 80/20 | 17.44 MW | 17.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274663 | QUAD CITI;2U | 80/20 | 17.49 MW | 17.49 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274699 | CORDOVA ;1C | 80/20 | 3.06 MW | 3.06 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274700 | CORDOVA ;2C | 80/20 | 3.06 MW | 3.06 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274701 | CORDOVA ;1S | 80/20 | 3.44 MW | 3.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274715 | NELSON EC;1C | 80/20 | 4.12 MW | 4.12 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274716 | NELSON EC;1S | 80/20 | 3.01 MW | 3.01 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274717 | NELSON EC;2C | 80/20 | 4.16 MW | 4.16 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274718 | NELSON EC;2S | 80/20 | 3.04 MW | 3.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274760 | LEE CO EC;1U | 80/20 | 2.99 MW | 2.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274761 | LEE CO EC;2U | 80/20 | 2.99 MW | 2.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274762 | LEE CO EC;3U | 80/20 | 2.99 MW | 2.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274763 | LEE CO EC;4U | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274764 | LEE CO EC;5U | 80/20 | 3.0 MW | 3.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274765 | LEE CO EC;6U | 80/20 | 3.0 MW | 3.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274766 | LEE CO EC;7U | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274767 | LEE CO EC;8U | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274822 | ROCKFORD ;11 | 80/20 | 4.24 MW | 4.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274823 | ROCKFORD ;21 | 80/20 | 4.36 MW | 4.36 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274824 | ROCKFORD ;12 | 80/20 | 4.21 MW | 4.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274855 | GSG-6 ;RU | 80/20 | 0.34 MW | 0.34 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274856 | ECOGROVE ;U1 | 80/20 | 0.67 MW | 0.67 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274857 | BIG SKY ;U1 | 80/20 | 0.54 MW | 0.54 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274858 | BIG SKY ;U2 | 80/20 | 0.54 MW | 0.54 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 276156 | O-029 C | 80/20 | 0.22 MW | 0.22 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 276157 | O-029 C | 80/20 | 0.24 MW | 0.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 276158 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 276162 | X1-087 | 80/20 | 0.32 MW | 0.32 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 276590 | R-018 | 80/20 | 0.24 MW | 0.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 293513 | O-009 C1 | 80/20 | 0.41 MW | 0.41 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 293514 | O-009 C2 | 80/20 | 0.21 MW | 0.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 293515 | O-009 C3 | 80/20 | 0.23 MW | 0.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 930482 | AB1-089 CT | 80/20 | 123.96 MW | 123.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 930483 | AB1-089 ST | 80/20 | 98.56 MW | 98.56 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 932881 | AC2-115 1 | 80/20 | 0.76 MW | 0.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 932891 | AC2-115 2 | 80/20 | 0.76 MW | 0.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 932921 | AC2-116 | 80/20 | 0.27 MW | 0.27 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 938861 | AE1-114 C O1 | 80/20 | 6.0 MW | 6.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 939051 | AE1-134 1 | 80/20 | 1.75 MW | 1.75 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 939061 | AE1-134 2 | 80/20 | 1.75 MW | 1.75 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 940501 | AE2-035 C | 80/20 | 4.25 MW | 4.25 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 941131 | AE2-107 C | Adder | 4.0 MW | 3.4 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946151 | AF1-280 C O1 | 80/20 | 25.7 MW | 25.7 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946161 | AF1-281 C O1 | 80/20 | 0.56 MW | 0.56 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946321 | AF1-296 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946501 | AF1-314 C | 80/20 | 7.53 MW | 7.53 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946661 | AF1-330 C | Adder | 1.31 MW | 1.11 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946671 | AF1-331 | 80/20 | 1.8 MW | 1.8 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274850 | MENDOTA H;RU | 80/20 | 0.21 MW | 0.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 952431 | J760 | External Queue | 5.1 MW | 5.1 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 953681 | J818 | External Queue | 14.04 MW | 14.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 953901 | J850 | External Queue | 23.48 MW | 23.48 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 953921 | J855 C | External Queue | 1.36 MW | 1.36 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 954001 | J864 | External Queue | 4.48 MW | 4.48 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 954061 | J870 | External Queue | 17.88 MW | 17.88 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 954071 | J871 | External Queue | 8.94 MW | 8.94 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 955971 | J1084 | External Queue | 12.21 MW | 12.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 990116 | J1214 | External Queue | 39.41 MW | 39.41 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 990406 | J1304 | External Queue | 9.34 MW | 9.34 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 990511 | J1326 | External Queue | 9.85 MW | 9.85 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 990726 | J1377 | External Queue | 16.85 MW | 16.85 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 991201 | J1629 | External Queue | 14.55 MW | 14.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.09 MW | 0.09 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.67 MW | 0.67 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.22 MW | 0.22 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.11 MW | 0.11 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 55.88 MW | 55.88 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.46 MW | 10.46 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.12 MW | 0.12 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.76 MW | 2.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.89 MW | 10.89 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.23 MW | 0.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.09 MW | 1.09 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.11 MW | 1.11 MW |
| Details for QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 962691 | AG1-118 C O1 | Adder | 11.85 MW | 10.07 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 962701 | AG1-119 C | Adder | 13.26 MW | 11.27 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 962711 | AG1-120 C O1 | Adder | 5.26 MW | 4.47 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 962781 | AG1-127 C | Adder | 3.93 MW | 3.34 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 966821 | AG1-553 C O1 | 80/20 | 68.46 MW | 68.46 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 965061 | AG1-371 | 80/20 | 3.53 MW | 3.53 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 965081 | AG1-373 | 80/20 | 1.18 MW | 1.18 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 965551 | AG1-423 C O1 | Adder | 8.81 MW | 7.49 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 965661 | AG1-434 C O1 | 80/20 | 4.66 MW | 4.66 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 965931 | AG1-462 C O1 | 80/20 | 44.31 MW | 44.31 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 272364 | ESS H440N ;R | 80/20 | 2.01 MW | 2.01 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 295108 | WESTBROOK C | 80/20 | 0.11 MW | 0.11 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 295110 | SUBLETTE C | 80/20 | 0.07 MW | 0.07 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 919221 | AA1-146 | 80/20 | 4.72 MW | 4.72 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 919581 | AA2-030 C | 80/20 | 27.74 MW | 27.74 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 926431 | AC1-114 | 80/20 | 0.28 MW | 0.28 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 933911 | AD1-013 C | 80/20 | 1.4 MW | 1.4 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 933931 | AD1-016 C | Adder | 0.49 MW | 0.42 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 934971 | AD1-129 C | Adder | 0.56 MW | 0.47 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 937001 | AD2-134 C | 80/20 | 1.96 MW | 1.96 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 937311 | AD2-172 C | 80/20 | 2.04 MW | 2.04 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 942991 | AE2-321 C | Adder | 4.33 MW | 3.68 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 943801 | AF1-048 C | Adder | 2.02 MW | 1.72 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 958911 | AF2-182 C | 80/20 | 27.77 MW | 27.77 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 958921 | AF2-183 C | 80/20 | 4.94 MW | 4.94 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 959081 | AF2-199 C | 80/20 | 7.06 MW | 7.06 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 959091 | AF2-200 C O1 | 80/20 | 14.13 MW | 14.13 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 959101 | AF2-201 C O1 | 80/20 | 5.0 MW | 5.0 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 960581 | AF2-349 C | Adder | 12.94 MW | 11.0 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 960721 | AF2-363 C O1 | Adder | 3.62 MW | 3.08 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 960751 | AF2-366 C | Adder | 3.91 MW | 3.33 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 961011 | AF2-392 C O1 | 80/20 | 5.15 MW | 5.15 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 961021 | AF2-393 O1 | 80/20 | 8.78 MW | 8.78 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 961031 | AF2-394 O1 | 80/20 | 5.85 MW | 5.85 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274656 | BYRON ;1U | 80/20 | 18.9 MW | 18.9 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274657 | BYRON ;2U | 80/20 | 18.43 MW | 18.43 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274662 | QUAD CITI;1U | 80/20 | 45.88 MW | 45.88 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274663 | QUAD CITI;2U | 80/20 | 45.27 MW | 45.27 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274699 | CORDOVA ;1C | 80/20 | 7.9 MW | 7.9 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274700 | CORDOVA ;2C | 80/20 | 7.9 MW | 7.9 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274701 | CORDOVA ;1S | 80/20 | 8.89 MW | 8.89 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274715 | NELSON EC;1C | 80/20 | 5.06 MW | 5.06 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274716 | NELSON EC;1S | 80/20 | 3.69 MW | 3.69 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274717 | NELSON EC;2C | 80/20 | 5.1 MW | 5.1 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274718 | NELSON EC;2S | 80/20 | 3.73 MW | 3.73 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274760 | LEE CO EC;1U | 80/20 | 2.09 MW | 2.09 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274761 | LEE CO EC;2U | 80/20 | 2.09 MW | 2.09 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274762 | LEE CO EC;3U | 80/20 | 2.09 MW | 2.09 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274763 | LEE CO EC;4U | 80/20 | 2.07 MW | 2.07 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274764 | LEE CO EC;5U | 80/20 | 2.09 MW | 2.09 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274765 | LEE CO EC;6U | 80/20 | 2.09 MW | 2.09 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274766 | LEE CO EC;7U | 80/20 | 2.06 MW | 2.06 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274767 | LEE CO EC;8U | 80/20 | 2.06 MW | 2.06 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274822 | ROCKFORD ;11 | 80/20 | 1.58 MW | 1.58 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274823 | ROCKFORD ;21 | 80/20 | 1.62 MW | 1.62 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274855 | GSG-6 ;RU | 80/20 | 0.34 MW | 0.34 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274856 | ECOGROVE ;U1 | 80/20 | 0.32 MW | 0.32 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274857 | BIG SKY ;U1 | 80/20 | 0.37 MW | 0.37 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274858 | BIG SKY ;U2 | 80/20 | 0.37 MW | 0.37 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 276156 | O-029 C | 80/20 | 0.22 MW | 0.22 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 276157 | O-029 C | 80/20 | 0.24 MW | 0.24 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 276158 | O-029 C | 80/20 | 0.43 MW | 0.43 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 276162 | X1-087 | 80/20 | 0.17 MW | 0.17 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 293513 | O-009 C1 | 80/20 | 0.4 MW | 0.4 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 293514 | O-009 C2 | 80/20 | 0.2 MW | 0.2 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 293515 | O-009 C3 | 80/20 | 0.23 MW | 0.23 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 930482 | AB1-089 CT | 80/20 | 26.56 MW | 26.56 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 930483 | AB1-089 ST | 80/20 | 21.11 MW | 21.11 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 932921 | AC2-116 | 80/20 | 0.1 MW | 0.1 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 938861 | AE1-114 C O1 | 80/20 | 3.88 MW | 3.88 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 939051 | AE1-134 1 | 80/20 | 2.16 MW | 2.16 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 939061 | AE1-134 2 | 80/20 | 2.16 MW | 2.16 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 940501 | AE2-035 C | 80/20 | 2.04 MW | 2.04 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 941131 | AE2-107 C | Adder | 4.17 MW | 3.54 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 946151 | AF1-280 C O1 | 80/20 | 21.14 MW | 21.14 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 946161 | AF1-281 C O1 | 80/20 | 0.46 MW | 0.46 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 946321 | AF1-296 C O1 | Adder | 2.49 MW | 2.12 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 946501 | AF1-314 C | 80/20 | 3.62 MW | 3.62 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 946661 | AF1-330 C | Adder | 1.05 MW | 0.89 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 946671 | AF1-331 | 80/20 | 1.82 MW | 1.82 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 957471 | AF2-041 C | 80/20 | 21.19 MW | 21.19 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 274850 | MENDOTA H;RU | 80/20 | 0.21 MW | 0.21 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 952431 | J760 | External Queue | 2.7 MW | 2.7 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 953151 | J831 | External Queue | 2.24 MW | 2.24 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 953491 | J947 | External Queue | 11.72 MW | 11.72 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 953681 | J818 | External Queue | 10.3 MW | 10.3 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 953901 | J850 | External Queue | 19.01 MW | 19.01 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 953921 | J855 C | External Queue | 0.91 MW | 0.91 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 954001 | J864 | External Queue | 2.8 MW | 2.8 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 954061 | J870 | External Queue | 11.91 MW | 11.91 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 954071 | J871 | External Queue | 5.95 MW | 5.95 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 954141 | J878 | External Queue | 12.63 MW | 12.63 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 955971 | J1084 | External Queue | 42.86 MW | 42.86 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 990116 | J1214 | External Queue | 22.79 MW | 22.79 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 990406 | J1304 | External Queue | 5.52 MW | 5.52 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 990511 | J1326 | External Queue | 5.7 MW | 5.7 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 990726 | J1377 | External Queue | 8.8 MW | 8.8 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 991201 | J1629 | External Queue | 11.65 MW | 11.65 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | 991321 | J1778 | External Queue | 6.31 MW | 6.31 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 3.26 MW | 3.26 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.14 MW | 1.14 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.05 MW | 2.05 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.05 MW | 1.05 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.59 MW | 0.59 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.05 MW | 1.05 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 7.88 MW | 7.88 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.79 MW | 0.79 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.93 MW | 0.93 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.52 MW | 0.52 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 11.18 MW | 11.18 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.64 MW | 0.64 MW |
| QUAD 6-7-SUB 91 3 345.0 kV Ckt 1 line l/o EXT_P12:345:MEC:CORDOVA:SUB 39 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.04 MW | 1.04 MW |
| Details for ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 962691 | AG1-118 C O1 | 80/20 | 18.27 MW | 18.27 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 962701 | AG1-119 C | Adder | 11.87 MW | 10.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 962711 | AG1-120 C O1 | 80/20 | 5.51 MW | 5.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 962781 | AG1-127 C | 80/20 | 5.35 MW | 5.35 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | Adder | 12.99 MW | 11.04 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 965061 | AG1-371 | 80/20 | 4.31 MW | 4.31 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 965081 | AG1-373 | 80/20 | 1.44 MW | 1.44 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 965551 | AG1-423 C O1 | Adder | 7.93 MW | 6.74 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C O1 | 80/20 | 4.47 MW | 4.47 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | Adder | 8.41 MW | 7.15 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 966441 | AG1-513 C | Adder | 0.25 MW | 0.21 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 272364 | ESS H440N ;R | 80/20 | 1.92 MW | 1.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.1 MW | 0.1 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.04 MW | 0.04 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 2.07 MW | 2.07 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 919581 | AA2-030 C | 80/20 | 12.13 MW | 12.13 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 926331 | AC1-110 1 | 80/20 | 2.38 MW | 2.38 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 926341 | AC1-110 2 | 80/20 | 2.38 MW | 2.38 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 933911 | AD1-013 C | 80/20 | 1.34 MW | 1.34 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 1.84 MW | 1.84 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 937311 | AD2-172 C | Adder | 1.13 MW | 0.96 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 943121 | AE2-341 C | 80/20 | 9.29 MW | 9.29 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 943591 | AF1-030 C O1 | 80/20 | 6.18 MW | 6.18 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 958911 | AF2-182 C | 80/20 | 12.86 MW | 12.86 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 2.29 MW | 2.29 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 959081 | AF2-199 C | 80/20 | 8.61 MW | 8.61 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 959091 | AF2-200 C O1 | 80/20 | 17.22 MW | 17.22 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | Adder | 2.77 MW | 2.35 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 960381 | AF2-329 | 80/20 | 3.9 MW | 3.9 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 960721 | AF2-363 C O1 | 80/20 | 3.76 MW | 3.76 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 960751 | AF2-366 C | 80/20 | 5.33 MW | 5.33 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 2.54 MW | 2.54 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 4.32 MW | 4.32 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 2.88 MW | 2.88 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274715 | NELSON EC;1C | 80/20 | 2.21 MW | 2.21 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274716 | NELSON EC;1S | 80/20 | 1.62 MW | 1.62 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274717 | NELSON EC;2C | 80/20 | 2.23 MW | 2.23 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274718 | NELSON EC;2S | 80/20 | 1.63 MW | 1.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274738 | AURORA EC;3P | 80/20 | 4.11 MW | 4.11 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274740 | AURORA EC;4P | 80/20 | 4.11 MW | 4.11 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274760 | LEE CO EC;1U | 80/20 | 0.99 MW | 0.99 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274761 | LEE CO EC;2U | 80/20 | 0.99 MW | 0.99 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274762 | LEE CO EC;3U | 80/20 | 0.99 MW | 0.99 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274763 | LEE CO EC;4U | 80/20 | 0.99 MW | 0.99 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274764 | LEE CO EC;5U | 80/20 | 1.0 MW | 1.0 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274765 | LEE CO EC;6U | 80/20 | 1.0 MW | 1.0 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274766 | LEE CO EC;7U | 80/20 | 0.98 MW | 0.98 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274818 | ELGIN EC ;1P | 80/20 | 1.55 MW | 1.55 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274820 | ELGIN EC ;2P | 80/20 | 1.55 MW | 1.55 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 0.32 MW | 0.32 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 930482 | AB1-089 CT | Adder | 18.33 MW | 15.58 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 930483 | AB1-089 ST | Adder | 14.58 MW | 12.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | Adder | 2.07 MW | 1.76 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 939051 | AE1-134 1 | 80/20 | 0.94 MW | 0.94 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 939061 | AE1-134 2 | 80/20 | 0.94 MW | 0.94 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 940501 | AE2-035 C | Adder | 1.13 MW | 0.96 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 941131 | AE2-107 C | 80/20 | 5.0 MW | 5.0 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 946151 | AF1-280 C O1 | 80/20 | 9.79 MW | 9.79 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.21 MW | 0.21 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | Adder | 2.08 MW | 1.77 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | Adder | 2.0 MW | 1.7 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 946671 | AF1-331 | 80/20 | 1.75 MW | 1.75 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 957471 | AF2-041 C | 80/20 | 25.83 MW | 25.83 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 0.63 MW | 0.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.2 MW | 0.2 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 945351 | AF1-200 FTIR | 80/20 | 140.59 MW | 140.59 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.02 MW | 0.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.2 MW | 0.2 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.47 MW | 5.47 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 3.9 MW | 3.9 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.97 MW | 0.97 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.73 MW | 3.73 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.41 MW | 0.41 MW |
| Details for AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 962701 | AG1-119 C | 80/20 | 101.34 MW | 101.34 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 962711 | AG1-120 C O1 | 80/20 | 9.4 MW | 9.4 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 962781 | AG1-127 C | Adder | 4.3 MW | 3.66 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 966821 | AG1-553 C O1 | 80/20 | 26.62 MW | 26.62 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 965551 | AG1-423 C O1 | 80/20 | 67.97 MW | 67.97 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 965661 | AG1-434 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 965931 | AG1-462 C O1 | 80/20 | 17.23 MW | 17.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 272364 | ESS H440N ;R | 80/20 | 1.99 MW | 1.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 295108 | WESTBROOK C | 80/20 | 0.11 MW | 0.11 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 295110 | SUBLETTE C | 80/20 | 0.08 MW | 0.08 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 919221 | AA1-146 | 80/20 | 3.85 MW | 3.85 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 919581 | AA2-030 C | 80/20 | 22.58 MW | 22.58 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 926431 | AC1-114 | 80/20 | 0.76 MW | 0.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 927511 | AC1-113 1 | 80/20 | 0.38 MW | 0.38 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 927521 | AC1-113 2 | 80/20 | 0.38 MW | 0.38 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 933911 | AD1-013 C | 80/20 | 1.39 MW | 1.39 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 933931 | AD1-016 C | 80/20 | 0.66 MW | 0.66 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 934971 | AD1-129 C | 80/20 | 1.24 MW | 1.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 937001 | AD2-134 C | 80/20 | 1.94 MW | 1.94 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 937311 | AD2-172 C | 80/20 | 4.25 MW | 4.25 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 942991 | AE2-321 C | 80/20 | 5.53 MW | 5.53 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 958911 | AF2-182 C | 80/20 | 33.76 MW | 33.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 958921 | AF2-183 C | 80/20 | 6.0 MW | 6.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 959101 | AF2-201 C O1 | 80/20 | 10.4 MW | 10.4 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 960721 | AF2-363 C O1 | 80/20 | 6.54 MW | 6.54 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 960751 | AF2-366 C | Adder | 4.29 MW | 3.65 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 961011 | AF2-392 C O1 | 80/20 | 4.91 MW | 4.91 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 961021 | AF2-393 O1 | 80/20 | 8.38 MW | 8.38 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 961031 | AF2-394 O1 | 80/20 | 5.58 MW | 5.58 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274656 | BYRON ;1U | 80/20 | 60.35 MW | 60.35 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274657 | BYRON ;2U | 80/20 | 58.8 MW | 58.8 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274662 | QUAD CITI;1U | 80/20 | 17.44 MW | 17.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274663 | QUAD CITI;2U | 80/20 | 17.49 MW | 17.49 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274699 | CORDOVA ;1C | 80/20 | 3.06 MW | 3.06 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274700 | CORDOVA ;2C | 80/20 | 3.06 MW | 3.06 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274701 | CORDOVA ;1S | 80/20 | 3.44 MW | 3.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274715 | NELSON EC;1C | 80/20 | 4.12 MW | 4.12 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274716 | NELSON EC;1S | 80/20 | 3.01 MW | 3.01 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274717 | NELSON EC;2C | 80/20 | 4.16 MW | 4.16 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274718 | NELSON EC;2S | 80/20 | 3.04 MW | 3.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274760 | LEE CO EC;1U | 80/20 | 2.99 MW | 2.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274761 | LEE CO EC;2U | 80/20 | 2.99 MW | 2.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274762 | LEE CO EC;3U | 80/20 | 2.99 MW | 2.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274763 | LEE CO EC;4U | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274764 | LEE CO EC;5U | 80/20 | 3.0 MW | 3.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274765 | LEE CO EC;6U | 80/20 | 3.0 MW | 3.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274766 | LEE CO EC;7U | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274767 | LEE CO EC;8U | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274822 | ROCKFORD ;11 | 80/20 | 4.24 MW | 4.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274823 | ROCKFORD ;21 | 80/20 | 4.36 MW | 4.36 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274824 | ROCKFORD ;12 | 80/20 | 4.21 MW | 4.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274855 | GSG-6 ;RU | 80/20 | 0.34 MW | 0.34 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274856 | ECOGROVE ;U1 | 80/20 | 0.67 MW | 0.67 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274857 | BIG SKY ;U1 | 80/20 | 0.54 MW | 0.54 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274858 | BIG SKY ;U2 | 80/20 | 0.54 MW | 0.54 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 276156 | O-029 C | 80/20 | 0.22 MW | 0.22 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 276157 | O-029 C | 80/20 | 0.24 MW | 0.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 276158 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 276162 | X1-087 | 80/20 | 0.32 MW | 0.32 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 276590 | R-018 | 80/20 | 0.24 MW | 0.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 293513 | O-009 C1 | 80/20 | 0.41 MW | 0.41 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 293514 | O-009 C2 | 80/20 | 0.21 MW | 0.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 293515 | O-009 C3 | 80/20 | 0.23 MW | 0.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 930482 | AB1-089 CT | 80/20 | 123.96 MW | 123.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 930483 | AB1-089 ST | 80/20 | 98.56 MW | 98.56 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 932881 | AC2-115 1 | 80/20 | 0.76 MW | 0.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 932891 | AC2-115 2 | 80/20 | 0.76 MW | 0.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 932921 | AC2-116 | 80/20 | 0.27 MW | 0.27 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 938861 | AE1-114 C O1 | 80/20 | 6.0 MW | 6.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 939051 | AE1-134 1 | 80/20 | 1.75 MW | 1.75 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 939061 | AE1-134 2 | 80/20 | 1.75 MW | 1.75 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 940501 | AE2-035 C | 80/20 | 4.25 MW | 4.25 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 941131 | AE2-107 C | Adder | 4.0 MW | 3.4 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 946151 | AF1-280 C O1 | 80/20 | 25.7 MW | 25.7 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 946161 | AF1-281 C O1 | 80/20 | 0.56 MW | 0.56 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 946321 | AF1-296 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 946501 | AF1-314 C | 80/20 | 7.53 MW | 7.53 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 946661 | AF1-330 C | Adder | 1.31 MW | 1.11 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 946671 | AF1-331 | 80/20 | 1.8 MW | 1.8 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 274850 | MENDOTA H;RU | 80/20 | 0.21 MW | 0.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 952431 | J760 | External Queue | 5.1 MW | 5.1 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 953681 | J818 | External Queue | 14.04 MW | 14.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 953901 | J850 | External Queue | 23.48 MW | 23.48 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 953921 | J855 C | External Queue | 1.36 MW | 1.36 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 954001 | J864 | External Queue | 4.48 MW | 4.48 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 954061 | J870 | External Queue | 17.88 MW | 17.88 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 954071 | J871 | External Queue | 8.94 MW | 8.94 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 955971 | J1084 | External Queue | 12.21 MW | 12.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 990116 | J1214 | External Queue | 39.41 MW | 39.41 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 990406 | J1304 | External Queue | 9.34 MW | 9.34 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 990511 | J1326 | External Queue | 9.85 MW | 9.85 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 990726 | J1377 | External Queue | 16.85 MW | 16.85 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | 991201 | J1629 | External Queue | 14.55 MW | 14.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.09 MW | 0.09 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.67 MW | 0.67 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.22 MW | 0.22 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.11 MW | 0.11 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 55.88 MW | 55.88 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.46 MW | 10.46 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.12 MW | 0.12 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.76 MW | 2.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.89 MW | 10.89 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.23 MW | 0.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.09 MW | 1.09 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15616__-R | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.11 MW | 1.11 MW |
| Details for AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 962701 | AG1-119 C | 80/20 | 96.55 MW | 96.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 962711 | AG1-120 C O1 | 80/20 | 6.65 MW | 6.65 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 21.43 MW | 21.43 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 965551 | AG1-423 C O1 | 80/20 | 64.82 MW | 64.82 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C O1 | Adder | 2.36 MW | 2.01 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | 80/20 | 13.87 MW | 13.87 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 272364 | ESS H440N ;R | Adder | 1.48 MW | 1.25 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.06 MW | 0.06 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 3.1 MW | 3.1 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 919581 | AA2-030 C | 80/20 | 18.22 MW | 18.22 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 926431 | AC1-114 | 80/20 | 0.55 MW | 0.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 927511 | AC1-113 1 | 80/20 | 0.28 MW | 0.28 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 927521 | AC1-113 2 | 80/20 | 0.28 MW | 0.28 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 933911 | AD1-013 C | Adder | 1.03 MW | 0.87 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 933931 | AD1-016 C | 80/20 | 0.55 MW | 0.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 934971 | AD1-129 C | 80/20 | 0.92 MW | 0.92 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | Adder | 1.44 MW | 1.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 937311 | AD2-172 C | 80/20 | 3.18 MW | 3.18 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 942991 | AE2-321 C | 80/20 | 4.67 MW | 4.67 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 943801 | AF1-048 C | Adder | 2.18 MW | 1.86 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 958911 | AF2-182 C | 80/20 | 27.45 MW | 27.45 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 4.88 MW | 4.88 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 7.79 MW | 7.79 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 960581 | AF2-349 C | 80/20 | 21.53 MW | 21.53 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 960721 | AF2-363 C O1 | 80/20 | 4.63 MW | 4.63 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 3.89 MW | 3.89 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 6.63 MW | 6.63 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 4.42 MW | 4.42 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274656 | BYRON ;1U | 80/20 | 49.55 MW | 49.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274657 | BYRON ;2U | 80/20 | 48.21 MW | 48.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274662 | QUAD CITI;1U | 80/20 | 14.04 MW | 14.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274663 | QUAD CITI;2U | 80/20 | 14.08 MW | 14.08 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274699 | CORDOVA ;1C | 80/20 | 2.47 MW | 2.47 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274700 | CORDOVA ;2C | 80/20 | 2.47 MW | 2.47 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274701 | CORDOVA ;1S | 80/20 | 2.77 MW | 2.77 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274715 | NELSON EC;1C | 80/20 | 3.33 MW | 3.33 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274716 | NELSON EC;1S | 80/20 | 2.43 MW | 2.43 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274717 | NELSON EC;2C | 80/20 | 3.35 MW | 3.35 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274718 | NELSON EC;2S | 80/20 | 2.45 MW | 2.45 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274760 | LEE CO EC;1U | 80/20 | 2.44 MW | 2.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274761 | LEE CO EC;2U | 80/20 | 2.44 MW | 2.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274762 | LEE CO EC;3U | 80/20 | 2.44 MW | 2.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274763 | LEE CO EC;4U | 80/20 | 2.42 MW | 2.42 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274764 | LEE CO EC;5U | 80/20 | 2.45 MW | 2.45 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274765 | LEE CO EC;6U | 80/20 | 2.45 MW | 2.45 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274766 | LEE CO EC;7U | 80/20 | 2.41 MW | 2.41 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274767 | LEE CO EC;8U | 80/20 | 2.41 MW | 2.41 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274822 | ROCKFORD ;11 | 80/20 | 3.08 MW | 3.08 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274823 | ROCKFORD ;21 | 80/20 | 3.17 MW | 3.17 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274824 | ROCKFORD ;12 | 80/20 | 3.06 MW | 3.06 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 0.5 MW | 0.5 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 0.44 MW | 0.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 0.44 MW | 0.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.18 MW | 0.18 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.19 MW | 0.19 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.35 MW | 0.35 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 276162 | X1-087 | 80/20 | 0.23 MW | 0.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 276590 | R-018 | 80/20 | 0.18 MW | 0.18 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.33 MW | 0.33 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.17 MW | 0.17 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.18 MW | 0.18 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 930482 | AB1-089 CT | 80/20 | 110.64 MW | 110.64 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 930483 | AB1-089 ST | 80/20 | 87.96 MW | 87.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 932881 | AC2-115 1 | 80/20 | 0.55 MW | 0.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 932891 | AC2-115 2 | 80/20 | 0.55 MW | 0.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 932921 | AC2-116 | 80/20 | 0.19 MW | 0.19 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 4.57 MW | 4.57 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 939051 | AE1-134 1 | 80/20 | 1.42 MW | 1.42 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 939061 | AE1-134 2 | 80/20 | 1.42 MW | 1.42 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 940501 | AE2-035 C | 80/20 | 3.18 MW | 3.18 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946151 | AF1-280 C O1 | 80/20 | 20.89 MW | 20.89 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.46 MW | 0.46 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 3.46 MW | 3.46 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 5.63 MW | 5.63 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946661 | AF1-330 C | Adder | 1.12 MW | 0.95 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946671 | AF1-331 | Adder | 1.34 MW | 1.14 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 952431 | J760 | External Queue | 3.92 MW | 3.92 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 953681 | J818 | External Queue | 11.09 MW | 11.09 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 953901 | J850 | External Queue | 18.62 MW | 18.62 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 953921 | J855 C | External Queue | 1.07 MW | 1.07 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 954001 | J864 | External Queue | 3.52 MW | 3.52 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 954061 | J870 | External Queue | 14.08 MW | 14.08 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 954071 | J871 | External Queue | 7.04 MW | 7.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 955971 | J1084 | External Queue | 9.77 MW | 9.77 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 990116 | J1214 | External Queue | 30.53 MW | 30.53 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 990406 | J1304 | External Queue | 7.22 MW | 7.22 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 990511 | J1326 | External Queue | 7.63 MW | 7.63 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 990726 | J1377 | External Queue | 12.92 MW | 12.92 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 991201 | J1629 | External Queue | 11.69 MW | 11.69 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.08 MW | 0.08 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.55 MW | 0.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.17 MW | 0.17 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.0 MW | 0.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.79 MW | 45.79 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.35 MW | 8.35 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.1 MW | 0.1 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.03 MW | 0.03 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.21 MW | 2.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.76 MW | 8.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.87 MW | 0.87 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.06 MW | 1.06 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961651 | AG1-005 C O1 | Adder | 12.31 MW | 10.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961652 | AG1-005 E O1 | Adder | 8.21 MW | 6.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962721 | AG1-121 C O1 | Adder | 4.22 MW | 3.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962722 | AG1-121 E O1 | Adder | 19.72 MW | 16.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963831 | AG1-236 C | 50/50 | 3.97 MW | 3.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963832 | AG1-236 E | 50/50 | 26.57 MW | 26.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964581 | AG1-321 C O1 | Adder | 11.78 MW | 10.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964582 | AG1-321 E O1 | Adder | 6.86 MW | 5.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966821 | AG1-553 C O1 | Adder | 18.91 MW | 16.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966822 | AG1-553 E O1 | Adder | 3.81 MW | 3.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965091 | AG1-374 C | 50/50 | 21.96 MW | 21.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965092 | AG1-374 E | 50/50 | 14.64 MW | 14.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965331 | AG1-398 | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965341 | AG1-399 C | 50/50 | 7.26 MW | 7.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965342 | AG1-399 E | 50/50 | 33.99 MW | 33.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965351 | AG1-400 | 50/50 | 20.62 MW | 20.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965371 | AG1-402 | 50/50 | 20.62 MW | 20.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965391 | AG1-404 | 50/50 | 13.75 MW | 13.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965671 | AG1-435 C O1 | Adder | 2.87 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965672 | AG1-435 E O1 | Adder | 13.45 MW | 11.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965911 | AG1-460 C | 50/50 | 2.08 MW | 2.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965912 | AG1-460 E | 50/50 | 3.12 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965931 | AG1-462 C O1 | Adder | 12.24 MW | 10.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965932 | AG1-462 E O1 | Adder | 8.16 MW | 6.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290261 | S-027 E | 50/50 | 19.32 MW | 19.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290265 | S-028 E | 50/50 | 19.32 MW | 19.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 295111 | SUBLETTE E | Adder | 1.61 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 919581 | AA2-030 C | Adder | 11.31 MW | 9.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925771 | AC1-053 C | 50/50 | 3.97 MW | 3.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925772 | AC1-053 E | 50/50 | 26.57 MW | 26.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926821 | AC1-168 C O1 | Adder | 0.79 MW | 0.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926822 | AC1-168 E O1 | Adder | 5.29 MW | 4.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 927202 | AC1-214 E O1 | Adder | 4.96 MW | 4.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934051 | AD1-031 C O1 | Adder | 2.19 MW | 1.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934052 | AD1-031 E O1 | Adder | 3.57 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 935141 | AD1-148 | 50/50 | 5.71 MW | 5.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936771 | AD2-100 C | 50/50 | 22.42 MW | 22.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936772 | AD2-100 E | 50/50 | 14.95 MW | 14.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936971 | AD2-131 C | 50/50 | 1.48 MW | 1.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936972 | AD2-131 E | 50/50 | 7.42 MW | 7.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942111 | AE2-223 C | 50/50 | 2.2 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942112 | AE2-223 E | 50/50 | 14.74 MW | 14.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942481 | AE2-261 C | 50/50 | 31.04 MW | 31.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942482 | AE2-261 E | 50/50 | 20.7 MW | 20.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945871 | AF1-252 O1 | 50/50 | 11.99 MW | 11.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945881 | AF1-253 | 50/50 | 8.3 MW | 8.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946542 | AF1-318 E O1 | Adder | 20.29 MW | 17.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958911 | AF2-182 C | Adder | 12.64 MW | 10.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958912 | AF2-182 E | Adder | 8.43 MW | 7.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958921 | AF2-183 C | Adder | 2.25 MW | 1.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958922 | AF2-183 E | Adder | 3.37 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959341 | AF2-225 C | 50/50 | 7.12 MW | 7.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959342 | AF2-225 E | 50/50 | 9.83 MW | 9.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959611 | AF2-252 C | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959612 | AF2-252 E | 50/50 | 3.66 MW | 3.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960141 | AF2-305 | 50/50 | 1.38 MW | 1.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960261 | AF2-317 | 50/50 | 2.47 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960611 | AF2-352 C | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960612 | AF2-352 E | 50/50 | 3.66 MW | 3.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961011 | AF2-392 C O1 | Adder | 2.52 MW | 2.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961012 | AF2-392 E O1 | Adder | 11.79 MW | 10.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961021 | AF2-393 O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961031 | AF2-394 O1 | Adder | 2.86 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274650 | KINCAID ;1U | 50/50 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274651 | KINCAID ;2U | 50/50 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274853 | TWINGROVE;U1 | 50/50 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274854 | TWINGROVE;U2 | 50/50 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274859 | EASYR;U1 E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274860 | EASYR;U2 E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274880 | RADFORD R;1U | 50/50 | 1.17 MW | 1.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276615 | W2-048 GEN | 50/50 | 8.12 MW | 8.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276621 | X2-022 GEN | 50/50 | 29.13 MW | 29.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293516 | O-009 E1 | Adder | 6.11 MW | 5.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293517 | O-009 E2 | Adder | 3.11 MW | 2.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293518 | O-009 E3 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293715 | O-029 E | Adder | 6.54 MW | 5.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293716 | O-029 E | Adder | 3.58 MW | 3.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293717 | O-029 E | Adder | 3.29 MW | 2.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293771 | O-035 E | Adder | 4.86 MW | 4.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293777 | CAYUG;1U E | Adder | 10.16 MW | 8.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293778 | CAYUG;2U E | Adder | 10.16 MW | 8.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293798 | W4-005 E | 50/50 | 39.32 MW | 39.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294401 | BSHIL;1U E | Adder | 6.58 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294410 | BSHIL;2U E | Adder | 6.58 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 916211 | Z1-072 E | Adder | 3.68 MW | 3.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 917502 | Z2-087 E | 50/50 | 19.65 MW | 19.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924042 | AB2-047 E O1 | 50/50 | 24.56 MW | 24.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924261 | AB2-070 C O1 | 50/50 | 3.91 MW | 3.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924262 | AB2-070 E O1 | 50/50 | 23.69 MW | 23.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925581 | AC1-033 C | Adder | 1.08 MW | 0.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925582 | AC1-033 E | Adder | 7.21 MW | 6.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 930761 | AB1-122 CT1 | Adder | 39.4 MW | 33.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938861 | AE1-114 C O1 | Adder | 2.33 MW | 1.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938862 | AE1-114 E O1 | Adder | 7.94 MW | 6.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939051 | AE1-134 1 | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939061 | AE1-134 2 | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939401 | AE1-172 C O1 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939402 | AE1-172 E O1 | Adder | 16.04 MW | 13.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939741 | AE1-205 C O1 | 50/50 | 9.49 MW | 9.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939742 | AE1-205 E O1 | 50/50 | 13.1 MW | 13.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941731 | AE2-173 O1 | 50/50 | 5.65 MW | 5.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944221 | AF1-090 C O1 | 50/50 | 6.77 MW | 6.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944222 | AF1-090 E O1 | 50/50 | 31.68 MW | 31.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946151 | AF1-280 C O1 | Adder | 9.62 MW | 8.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946152 | AF1-280 E O1 | Adder | 4.42 MW | 3.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946161 | AF1-281 C O1 | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946162 | AF1-281 E O1 | Adder | 1.19 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946321 | AF1-296 C O1 | Adder | 2.94 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946322 | AF1-296 E O1 | Adder | 13.76 MW | 11.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946541 | AF1-318 C O1 | Adder | 4.33 MW | 3.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957381 | AF2-032 C | 50/50 | 2.33 MW | 2.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957382 | AF2-032 E | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957752 | AF2-069 E | Adder | 0.58 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957761 | AF2-070 C | Adder | 0.25 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957762 | AF2-070 E | Adder | 1.24 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958341 | AF2-128 C O1 | Adder | 1.15 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958342 | AF2-128 E O1 | Adder | 5.38 MW | 4.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990901 | L-005 E | Adder | 10.49 MW | 8.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934101 | AD2-000 1 | Adder | 3.19 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944202 | AF1-088 FTWR | 50/50 | 279.8 MW | 279.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942602 | AE2-276 BAT | 50/50 | 13.99 MW | 13.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941343 | AE2-130 BAT | 50/50 | 31.84 MW | 31.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953371 | J808 | External Queue | 2.59 MW | 2.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953401 | J811 | External Queue | 18.15 MW | 18.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953641 | J813 | External Queue | 40.39 MW | 40.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953651 | J815 | External Queue | 32.21 MW | 32.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953741 | J826 C | External Queue | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953742 | J826 E | External Queue | 9.11 MW | 9.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953881 | J848 C | External Queue | 5.26 MW | 5.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953882 | J848 E | External Queue | 28.46 MW | 28.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954411 | J912 | External Queue | 14.27 MW | 14.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954681 | J949 C | External Queue | 33.84 MW | 33.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954821 | J955 | External Queue | 112.27 MW | 112.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 955402 | J1022 E | External Queue | 16.19 MW | 16.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 956451 | J1139 | External Queue | 20.56 MW | 20.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990056 | J1201 | External Queue | 6.99 MW | 6.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990071 | J1204 | External Queue | 65.14 MW | 65.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990271 | J1263 | External Queue | 107.73 MW | 107.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990672 | J1360 E | External Queue | 35.45 MW | 35.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990856 | J1408 | External Queue | 10.19 MW | 10.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991196 | J1626 | External Queue | 27.49 MW | 27.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991266 | J1714 | External Queue | 18.33 MW | 18.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991261 | J1713 C | External Queue | 3.06 MW | 3.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991262 | J1713 E | External Queue | 16.55 MW | 16.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.68 MW | 2.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.77 MW | 1.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 16.49 MW | 16.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 68.32 MW | 68.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 74.8 MW | 74.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.65 MW | 0.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.26 MW | 13.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.53 MW | 1.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.26 MW | 15.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.79 MW | 4.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.99 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.32 MW | 8.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.01 MW | 2.01 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961651 | AG1-005 C O1 | Adder | 12.53 MW | 10.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961652 | AG1-005 E O1 | Adder | 8.35 MW | 7.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962721 | AG1-121 C O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962722 | AG1-121 E O1 | Adder | 20.08 MW | 17.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 963831 | AG1-236 C | 50/50 | 3.85 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 963832 | AG1-236 E | 50/50 | 25.74 MW | 25.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 964581 | AG1-321 C O1 | Adder | 11.86 MW | 10.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 964582 | AG1-321 E O1 | Adder | 6.91 MW | 5.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 966821 | AG1-553 C O1 | Adder | 19.16 MW | 16.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 966822 | AG1-553 E O1 | Adder | 3.86 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965091 | AG1-374 C | 50/50 | 21.61 MW | 21.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965092 | AG1-374 E | 50/50 | 14.4 MW | 14.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965331 | AG1-398 | 50/50 | 1.07 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965341 | AG1-399 C | 50/50 | 7.08 MW | 7.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965342 | AG1-399 E | 50/50 | 33.15 MW | 33.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965351 | AG1-400 | 50/50 | 20.12 MW | 20.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965371 | AG1-402 | 50/50 | 20.12 MW | 20.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965391 | AG1-404 | 50/50 | 13.41 MW | 13.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965671 | AG1-435 C O1 | Adder | 2.92 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965672 | AG1-435 E O1 | Adder | 13.68 MW | 11.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965911 | AG1-460 C | 50/50 | 2.0 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965912 | AG1-460 E | 50/50 | 3.0 MW | 3.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965931 | AG1-462 C O1 | Adder | 12.4 MW | 10.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965932 | AG1-462 E O1 | Adder | 8.27 MW | 7.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 290261 | S-027 E | 50/50 | 19.01 MW | 19.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 290265 | S-028 E | 50/50 | 19.01 MW | 19.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 295111 | SUBLETTE E | Adder | 1.66 MW | 1.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 919581 | AA2-030 C | Adder | 11.63 MW | 9.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925771 | AC1-053 C | 50/50 | 3.85 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925772 | AC1-053 E | 50/50 | 25.74 MW | 25.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 926821 | AC1-168 C O1 | Adder | 0.81 MW | 0.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 926822 | AC1-168 E O1 | Adder | 5.42 MW | 4.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 927202 | AC1-214 E O1 | Adder | 5.04 MW | 4.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934051 | AD1-031 C O1 | Adder | 2.22 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934052 | AD1-031 E O1 | Adder | 3.62 MW | 3.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 935141 | AD1-148 | 50/50 | 5.53 MW | 5.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936511 | AD2-066 C O1 | Adder | 4.85 MW | 4.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936512 | AD2-066 E O1 | Adder | 3.24 MW | 2.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936771 | AD2-100 C | 50/50 | 21.54 MW | 21.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936772 | AD2-100 E | 50/50 | 14.36 MW | 14.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936971 | AD2-131 C | 50/50 | 1.42 MW | 1.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936972 | AD2-131 E | 50/50 | 7.13 MW | 7.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 937311 | AD2-172 C | Adder | 1.46 MW | 1.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 937312 | AD2-172 E | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942111 | AE2-223 C | 50/50 | 2.18 MW | 2.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942112 | AE2-223 E | 50/50 | 14.59 MW | 14.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942481 | AE2-261 C | 50/50 | 29.87 MW | 29.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942482 | AE2-261 E | 50/50 | 19.91 MW | 19.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 945871 | AF1-252 O1 | 50/50 | 11.48 MW | 11.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 945881 | AF1-253 | 50/50 | 7.95 MW | 7.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946542 | AF1-318 E O1 | Adder | 20.64 MW | 17.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958911 | AF2-182 C | Adder | 13.04 MW | 11.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958912 | AF2-182 E | Adder | 8.69 MW | 7.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958921 | AF2-183 C | Adder | 2.32 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958922 | AF2-183 E | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959101 | AF2-201 C O1 | Adder | 3.57 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959102 | AF2-201 E O1 | Adder | 10.24 MW | 8.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959341 | AF2-225 C | 50/50 | 7.04 MW | 7.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959342 | AF2-225 E | 50/50 | 9.73 MW | 9.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959611 | AF2-252 C | 50/50 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959612 | AF2-252 E | 50/50 | 3.6 MW | 3.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960141 | AF2-305 | 50/50 | 1.34 MW | 1.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960261 | AF2-317 | 50/50 | 2.39 MW | 2.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960611 | AF2-352 C | 50/50 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960612 | AF2-352 E | 50/50 | 3.6 MW | 3.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961011 | AF2-392 C O1 | Adder | 2.59 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961012 | AF2-392 E O1 | Adder | 12.14 MW | 10.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961021 | AF2-393 O1 | Adder | 4.42 MW | 3.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961031 | AF2-394 O1 | Adder | 2.95 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274650 | KINCAID ;1U | 50/50 | 15.61 MW | 15.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274651 | KINCAID ;2U | 50/50 | 15.6 MW | 15.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274853 | TWINGROVE;U1 | 50/50 | 0.71 MW | 0.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274854 | TWINGROVE;U2 | 50/50 | 0.73 MW | 0.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274859 | EASYR;U1 E | Adder | 6.88 MW | 5.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274860 | EASYR;U2 E | Adder | 6.88 MW | 5.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274880 | RADFORD R;1U | 50/50 | 1.14 MW | 1.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.49 MW | 0.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 276615 | W2-048 GEN | 50/50 | 7.85 MW | 7.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 276621 | X2-022 GEN | 50/50 | 28.17 MW | 28.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293516 | O-009 E1 | Adder | 6.27 MW | 5.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293517 | O-009 E2 | Adder | 3.18 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293518 | O-009 E3 | Adder | 3.51 MW | 2.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293715 | O-029 E | Adder | 6.7 MW | 5.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293716 | O-029 E | Adder | 3.67 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293717 | O-029 E | Adder | 3.38 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293771 | O-035 E | Adder | 4.94 MW | 4.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293777 | CAYUG;1U E | Adder | 10.34 MW | 8.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293778 | CAYUG;2U E | Adder | 10.34 MW | 8.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293798 | W4-005 E | 50/50 | 38.12 MW | 38.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294401 | BSHIL;1U E | Adder | 6.68 MW | 5.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294410 | BSHIL;2U E | Adder | 6.68 MW | 5.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294763 | P-046 E | Adder | 5.55 MW | 4.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 916211 | Z1-072 E | Adder | 3.74 MW | 3.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 917502 | Z2-087 E | 50/50 | 19.45 MW | 19.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924042 | AB2-047 E O1 | 50/50 | 24.32 MW | 24.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924261 | AB2-070 C O1 | 50/50 | 3.79 MW | 3.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924262 | AB2-070 E O1 | 50/50 | 22.98 MW | 22.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925581 | AC1-033 C | Adder | 1.09 MW | 0.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925582 | AC1-033 E | Adder | 7.32 MW | 6.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 930761 | AB1-122 CT1 | Adder | 41.0 MW | 34.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 938861 | AE1-114 C O1 | Adder | 2.41 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 938862 | AE1-114 E O1 | Adder | 8.22 MW | 6.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939051 | AE1-134 1 | Adder | 0.9 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939061 | AE1-134 2 | Adder | 0.9 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939401 | AE1-172 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939402 | AE1-172 E O1 | Adder | 16.51 MW | 14.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939741 | AE1-205 C O1 | 50/50 | 9.39 MW | 9.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939742 | AE1-205 E O1 | 50/50 | 12.97 MW | 12.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 940501 | AE2-035 C | Adder | 1.46 MW | 1.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 940502 | AE2-035 E | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 941731 | AE2-173 O1 | 50/50 | 5.59 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944221 | AF1-090 C O1 | 50/50 | 6.48 MW | 6.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944222 | AF1-090 E O1 | 50/50 | 30.33 MW | 30.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946151 | AF1-280 C O1 | Adder | 9.92 MW | 8.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946152 | AF1-280 E O1 | Adder | 4.56 MW | 3.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946162 | AF1-281 E O1 | Adder | 1.23 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946321 | AF1-296 C O1 | Adder | 2.98 MW | 2.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946322 | AF1-296 E O1 | Adder | 13.97 MW | 11.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946501 | AF1-314 C | Adder | 2.58 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946502 | AF1-314 E | Adder | 12.12 MW | 10.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946541 | AF1-318 C O1 | Adder | 4.41 MW | 3.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957381 | AF2-032 C | 50/50 | 2.24 MW | 2.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957382 | AF2-032 E | 50/50 | 1.05 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957752 | AF2-069 E | Adder | 0.59 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957761 | AF2-070 C | Adder | 0.26 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957762 | AF2-070 E | Adder | 1.26 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958341 | AF2-128 C O1 | Adder | 1.17 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958342 | AF2-128 E O1 | Adder | 5.47 MW | 4.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990901 | L-005 E | Adder | 10.63 MW | 9.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934101 | AD2-000 1 | Adder | 3.32 MW | 2.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944202 | AF1-088 FTWR | 50/50 | 309.06 MW | 309.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942602 | AE2-276 BAT | 50/50 | 15.45 MW | 15.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 941343 | AE2-130 BAT | 50/50 | 34.8 MW | 34.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953401 | J811 | External Queue | 17.16 MW | 17.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953641 | J813 | External Queue | 37.62 MW | 37.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953651 | J815 | External Queue | 30.66 MW | 30.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953881 | J848 C | External Queue | 4.99 MW | 4.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953882 | J848 E | External Queue | 27.02 MW | 27.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954411 | J912 | External Queue | 13.54 MW | 13.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954681 | J949 C | External Queue | 31.51 MW | 31.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954821 | J955 | External Queue | 84.37 MW | 84.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 956451 | J1139 | External Queue | 19.36 MW | 19.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990056 | J1201 | External Queue | 6.62 MW | 6.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990071 | J1204 | External Queue | 61.78 MW | 61.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990271 | J1263 | External Queue | 101.39 MW | 101.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990672 | J1360 E | External Queue | 33.75 MW | 33.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991196 | J1626 | External Queue | 26.01 MW | 26.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991266 | J1714 | External Queue | 17.34 MW | 17.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991261 | J1713 C | External Queue | 2.9 MW | 2.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991262 | J1713 E | External Queue | 15.68 MW | 15.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.8 MW | 3.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.56 MW | 1.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.57 MW | 13.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 71.43 MW | 71.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 67.74 MW | 67.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.36 MW | 12.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.6 MW | 1.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.01 MW | 15.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.1 MW | 5.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.33 MW | 1.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.55 MW | 7.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.1 MW | 2.1 MW |
| Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960581 | AF2-349 C | 50/50 | 87.91 MW | 87.91 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960582 | AF2-349 E | 50/50 | 58.6 MW | 58.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274761 | LEE CO EC;2U | 50/50 | 2.56 MW | 2.56 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960581 | AF2-349 C | 50/50 | 87.91 MW | 87.91 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960582 | AF2-349 E | 50/50 | 58.6 MW | 58.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274761 | LEE CO EC;2U | 50/50 | 2.56 MW | 2.56 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274762 | LEE CO EC;3U | 50/50 | 2.56 MW | 2.56 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274762 | LEE CO EC;3U | 50/50 | 2.56 MW | 2.56 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961651 | AG1-005 C O1 | Adder | 11.21 MW | 9.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961652 | AG1-005 E O1 | Adder | 7.48 MW | 6.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962691 | AG1-118 C O1 | Adder | 13.13 MW | 11.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962692 | AG1-118 E O1 | Adder | 8.75 MW | 7.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962701 | AG1-119 C | Adder | 14.19 MW | 12.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962702 | AG1-119 E | Adder | 9.46 MW | 8.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962711 | AG1-120 C O1 | Adder | 5.33 MW | 4.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962712 | AG1-120 E O1 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962721 | AG1-121 C O1 | Adder | 4.06 MW | 3.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962722 | AG1-121 E O1 | Adder | 18.97 MW | 16.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962781 | AG1-127 C | Adder | 4.17 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962782 | AG1-127 E | Adder | 2.77 MW | 2.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 966821 | AG1-553 C O1 | Adder | 18.17 MW | 15.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 966822 | AG1-553 E O1 | Adder | 3.66 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965061 | AG1-371 | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965081 | AG1-373 | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965141 | AG1-379 C | Adder | 20.91 MW | 17.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965142 | AG1-379 E | Adder | 9.57 MW | 8.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965551 | AG1-423 C O1 | Adder | 9.46 MW | 8.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965552 | AG1-423 E O1 | Adder | 6.31 MW | 5.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965661 | AG1-434 C O1 | Adder | 2.81 MW | 2.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965662 | AG1-434 E O1 | Adder | 13.14 MW | 11.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965671 | AG1-435 C O1 | Adder | 2.81 MW | 2.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965672 | AG1-435 E O1 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965931 | AG1-462 C O1 | Adder | 11.76 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965932 | AG1-462 E O1 | Adder | 7.84 MW | 6.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 966441 | AG1-513 C | Adder | 0.3 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 966442 | AG1-513 E | Adder | 0.44 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 272364 | ESS H440N ;R | Adder | 1.63 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 290021 | O50 E | Adder | 24.38 MW | 20.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 290051 | GSG-6; E | Adder | 6.51 MW | 5.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 295109 | WESTBROOK E | Adder | 3.48 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 295111 | SUBLETTE E | Adder | 1.77 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 918052 | AA1-018 E OP | Adder | 18.15 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 919581 | AA2-030 C | Adder | 12.27 MW | 10.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 920272 | AA2-123 E | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 926331 | AC1-110 1 | Adder | 1.17 MW | 0.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 926341 | AC1-110 2 | Adder | 1.17 MW | 0.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 927091 | AC1-204 GEN1 | 50/50 | 19.31 MW | 19.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 927093 | AC1-204 GEN2 | 50/50 | 19.42 MW | 19.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 927202 | AC1-214 E O1 | Adder | 4.8 MW | 4.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 927451 | AC1-142A 1 | Adder | 3.67 MW | 3.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 927461 | AC1-142A 2 | Adder | 3.7 MW | 3.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 933911 | AD1-013 C | Adder | 1.14 MW | 0.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 933912 | AD1-013 E | Adder | 1.83 MW | 1.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 933931 | AD1-016 C | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 933932 | AD1-016 E | Adder | 0.98 MW | 0.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934051 | AD1-031 C O1 | Adder | 2.2 MW | 1.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934052 | AD1-031 E O1 | Adder | 3.58 MW | 3.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934432 | AD1-067 E | Adder | 0.34 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934971 | AD1-129 C | Adder | 0.59 MW | 0.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934972 | AD1-129 E | Adder | 0.39 MW | 0.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 936291 | AD2-038 C O1 | Adder | 3.71 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 936292 | AD2-038 E O1 | Adder | 17.39 MW | 14.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 936511 | AD2-066 C O1 | Adder | 6.33 MW | 5.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 936512 | AD2-066 E O1 | Adder | 4.22 MW | 3.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937001 | AD2-134 C | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937002 | AD2-134 E | Adder | 6.29 MW | 5.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937311 | AD2-172 C | Adder | 1.64 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937312 | AD2-172 E | Adder | 2.26 MW | 1.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937401 | AD2-194 1 | Adder | 12.19 MW | 10.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937411 | AD2-194 2 | 50/50 | 12.26 MW | 12.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942421 | AE2-255 C O1 | Adder | 3.81 MW | 3.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942422 | AE2-255 E O1 | Adder | 11.43 MW | 9.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942651 | AE2-281 C O1 | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942652 | AE2-281 E O1 | Adder | 6.05 MW | 5.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942991 | AE2-321 C | Adder | 5.3 MW | 4.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942992 | AE2-321 E | Adder | 2.61 MW | 2.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 943801 | AF1-048 C | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 943802 | AF1-048 E | Adder | 1.65 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946542 | AF1-318 E O1 | Adder | 18.68 MW | 15.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958481 | AF2-142 C | Adder | 12.52 MW | 10.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958482 | AF2-142 E | Adder | 8.35 MW | 7.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958491 | AF2-143 C | Adder | 12.66 MW | 10.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958492 | AF2-143 E | Adder | 8.44 MW | 7.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958911 | AF2-182 C | Adder | 14.08 MW | 11.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958912 | AF2-182 E | Adder | 9.39 MW | 7.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958921 | AF2-183 C | Adder | 2.5 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958922 | AF2-183 E | Adder | 3.75 MW | 3.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959081 | AF2-199 C | Adder | 4.81 MW | 4.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959082 | AF2-199 E | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959091 | AF2-200 C O1 | Adder | 9.63 MW | 8.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959092 | AF2-200 E O1 | Adder | 6.42 MW | 5.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959101 | AF2-201 C O1 | Adder | 4.01 MW | 3.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959102 | AF2-201 E O1 | Adder | 11.51 MW | 9.79 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959351 | AF2-226 C | 50/50 | 5.92 MW | 5.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959352 | AF2-226 E | 50/50 | 8.88 MW | 8.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960281 | AF2-319 C | 50/50 | 5.92 MW | 5.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960282 | AF2-319 E | 50/50 | 8.88 MW | 8.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960581 | AF2-349 C | Adder | 14.2 MW | 12.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960582 | AF2-349 E | Adder | 9.47 MW | 8.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960721 | AF2-363 C O1 | Adder | 3.66 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960722 | AF2-363 E O1 | Adder | 2.44 MW | 2.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960751 | AF2-366 C | Adder | 4.15 MW | 3.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960752 | AF2-366 E | Adder | 2.77 MW | 2.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961011 | AF2-392 C O1 | Adder | 2.74 MW | 2.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961012 | AF2-392 E O1 | Adder | 12.85 MW | 10.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961021 | AF2-393 O1 | Adder | 4.68 MW | 3.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961031 | AF2-394 O1 | Adder | 3.12 MW | 2.65 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274728 | ELWOOD EC;5P | 50/50 | 5.22 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274730 | ELWOOD EC;6P | 50/50 | 5.22 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274731 | ELWOOD EC;2P | 50/50 | 5.19 MW | 5.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274732 | ELWOOD EC;7P | 50/50 | 5.22 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274734 | ELWOOD EC;8P | 50/50 | 5.22 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274736 | ELWOOD EC;9P | 50/50 | 5.22 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274859 | EASYR;U1 E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274860 | EASYR;U2 E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274861 | TOP CROP ;1U | 50/50 | 0.93 MW | 0.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274862 | TOP CROP ;2U | 50/50 | 1.77 MW | 1.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 276170 | Z1-108 E | Adder | 1.6 MW | 1.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 276591 | L-013 2 | Adder | 2.24 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293516 | O-009 E1 | Adder | 6.49 MW | 5.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293517 | O-009 E2 | Adder | 3.3 MW | 2.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293518 | O-009 E3 | Adder | 3.63 MW | 3.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293644 | O22 E1 | 50/50 | 24.17 MW | 24.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293645 | O22 E2 | 50/50 | 46.91 MW | 46.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293715 | O-029 E | Adder | 6.94 MW | 5.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293716 | O-029 E | Adder | 3.8 MW | 3.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293717 | O-029 E | Adder | 3.5 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293771 | O-035 E | Adder | 4.71 MW | 4.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 294401 | BSHIL;1U E | Adder | 6.59 MW | 5.6 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 294410 | BSHIL;2U E | Adder | 6.59 MW | 5.6 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 294763 | P-046 E | Adder | 6.24 MW | 5.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 915011 | Y3-013 1 | Adder | 2.46 MW | 2.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 915021 | Y3-013 2 | Adder | 2.46 MW | 2.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 915031 | Y3-013 3 | Adder | 2.46 MW | 2.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 916211 | Z1-072 E | Adder | 3.56 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 916221 | Z1-073 E | Adder | 3.38 MW | 2.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 925581 | AC1-033 C | Adder | 1.08 MW | 0.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 925582 | AC1-033 E | Adder | 7.22 MW | 6.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 930482 | AB1-089 CT | Adder | 24.07 MW | 20.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 930483 | AB1-089 ST | Adder | 19.13 MW | 16.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 930761 | AB1-122 CT1 | Adder | 69.01 MW | 58.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 930771 | AB1-122 CT2 | Adder | 92.77 MW | 78.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938511 | AE1-070 1 | 50/50 | 14.41 MW | 14.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938521 | AE1-070 2 | Adder | 13.11 MW | 11.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938851 | AE1-113 C O1 | Adder | 10.06 MW | 8.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938852 | AE1-113 E O1 | Adder | 35.66 MW | 30.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938861 | AE1-114 C O1 | Adder | 2.65 MW | 2.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938862 | AE1-114 E O1 | Adder | 9.04 MW | 7.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 939051 | AE1-134 1 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 939061 | AE1-134 2 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 939321 | AE1-163 C O1 | Adder | 6.89 MW | 5.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 939322 | AE1-163 E O1 | Adder | 42.35 MW | 36.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 940501 | AE2-035 C | Adder | 1.64 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 940502 | AE2-035 E | Adder | 2.26 MW | 1.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 941131 | AE2-107 C | Adder | 3.95 MW | 3.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 941132 | AE2-107 E | Adder | 2.63 MW | 2.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946151 | AF1-280 C O1 | Adder | 10.72 MW | 9.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946152 | AF1-280 E O1 | Adder | 4.93 MW | 4.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946161 | AF1-281 C O1 | Adder | 0.23 MW | 0.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946162 | AF1-281 E O1 | Adder | 1.33 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946321 | AF1-296 C O1 | Adder | 2.86 MW | 2.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946322 | AF1-296 E O1 | Adder | 13.4 MW | 11.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946501 | AF1-314 C | Adder | 2.9 MW | 2.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946502 | AF1-314 E | Adder | 13.64 MW | 11.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946541 | AF1-318 C O1 | Adder | 3.99 MW | 3.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946661 | AF1-330 C | Adder | 1.3 MW | 1.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946662 | AF1-330 E | Adder | 0.28 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946671 | AF1-331 | Adder | 1.48 MW | 1.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957331 | AF2-027 C | Adder | 1.64 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957332 | AF2-027 E | Adder | 2.46 MW | 2.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957401 | AF2-034 C | Adder | 1.86 MW | 1.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957402 | AF2-034 E | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957471 | AF2-041 C | Adder | 14.44 MW | 12.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957472 | AF2-041 E | Adder | 7.22 MW | 6.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957752 | AF2-069 E | Adder | 0.56 MW | 0.48 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957762 | AF2-070 E | Adder | 1.2 MW | 1.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958341 | AF2-128 C O1 | Adder | 1.05 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958342 | AF2-128 E O1 | Adder | 4.9 MW | 4.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 990901 | L-005 E | Adder | 10.47 MW | 8.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934101 | AD2-000 1 | Adder | 5.58 MW | 4.74 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934111 | AD2-000 2 | Adder | 7.5 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 290108 | LEEDK;1U E | Adder | 14.61 MW | 12.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958023 | AF2-096 BAT | Adder | 8.68 MW | 7.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 964362 | AG1-298 BAT | Adder | 57.7 MW | 49.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 954981 | J974 C | External Queue | 3.04 MW | 3.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 954982 | J974 E | External Queue | 16.43 MW | 16.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.29 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.01 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.07 MW | 0.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.26 MW | 0.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 41.5 MW | 41.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.4 MW | 15.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.05 MW | 1.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.17 MW | 0.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.15 MW | 3.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.23 MW | 0.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.7 MW | 9.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.57 MW | 0.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.76 MW | 6.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.35 MW | 0.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.33 MW | 1.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.49 MW | 2.49 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961651 | AG1-005 C O1 | Adder | 11.16 MW | 9.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961652 | AG1-005 E O1 | Adder | 7.44 MW | 6.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962691 | AG1-118 C O1 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962692 | AG1-118 E O1 | Adder | 8.76 MW | 7.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962701 | AG1-119 C | Adder | 14.23 MW | 12.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962702 | AG1-119 E | Adder | 9.48 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962711 | AG1-120 C O1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962712 | AG1-120 E O1 | Adder | 3.56 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962721 | AG1-121 C O1 | Adder | 4.04 MW | 3.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962722 | AG1-121 E O1 | Adder | 18.88 MW | 16.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962781 | AG1-127 C | Adder | 4.17 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962782 | AG1-127 E | Adder | 2.77 MW | 2.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 966821 | AG1-553 C O1 | Adder | 18.15 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 966822 | AG1-553 E O1 | Adder | 3.66 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965061 | AG1-371 | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965081 | AG1-373 | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965141 | AG1-379 C | Adder | 20.95 MW | 17.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965142 | AG1-379 E | Adder | 9.59 MW | 8.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965551 | AG1-423 C O1 | Adder | 9.49 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965552 | AG1-423 E O1 | Adder | 6.32 MW | 5.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965661 | AG1-434 C O1 | Adder | 2.81 MW | 2.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965662 | AG1-434 E O1 | Adder | 13.15 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965671 | AG1-435 C O1 | Adder | 2.8 MW | 2.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965672 | AG1-435 E O1 | Adder | 13.08 MW | 11.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965931 | AG1-462 C O1 | Adder | 11.75 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965932 | AG1-462 E O1 | Adder | 7.83 MW | 6.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 966441 | AG1-513 C | Adder | 0.3 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 966442 | AG1-513 E | Adder | 0.44 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 272364 | ESS H440N ;R | Adder | 1.63 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 290021 | O50 E | Adder | 24.43 MW | 20.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 290051 | GSG-6; E | Adder | 6.51 MW | 5.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 295109 | WESTBROOK E | Adder | 3.49 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 295111 | SUBLETTE E | Adder | 1.77 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 918052 | AA1-018 E OP | Adder | 18.15 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 919581 | AA2-030 C | Adder | 12.28 MW | 10.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 920272 | AA2-123 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 926331 | AC1-110 1 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 926341 | AC1-110 2 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 927091 | AC1-204 GEN1 | 50/50 | 19.36 MW | 19.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 927093 | AC1-204 GEN2 | 50/50 | 19.47 MW | 19.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 927202 | AC1-214 E O1 | Adder | 4.78 MW | 4.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 927451 | AC1-142A 1 | Adder | 3.72 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 927461 | AC1-142A 2 | Adder | 3.74 MW | 3.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 933911 | AD1-013 C | Adder | 1.14 MW | 0.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 933912 | AD1-013 E | Adder | 1.83 MW | 1.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 933931 | AD1-016 C | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 933932 | AD1-016 E | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934051 | AD1-031 C O1 | Adder | 2.19 MW | 1.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934052 | AD1-031 E O1 | Adder | 3.57 MW | 3.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934432 | AD1-067 E | Adder | 0.34 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934971 | AD1-129 C | Adder | 0.59 MW | 0.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934972 | AD1-129 E | Adder | 0.39 MW | 0.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 936291 | AD2-038 C O1 | Adder | 3.71 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 936292 | AD2-038 E O1 | Adder | 17.39 MW | 14.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 936511 | AD2-066 C O1 | Adder | 6.37 MW | 5.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 936512 | AD2-066 E O1 | Adder | 4.24 MW | 3.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937001 | AD2-134 C | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937002 | AD2-134 E | Adder | 6.3 MW | 5.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937311 | AD2-172 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937312 | AD2-172 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937401 | AD2-194 1 | Adder | 12.23 MW | 10.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937411 | AD2-194 2 | 50/50 | 12.29 MW | 12.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942421 | AE2-255 C O1 | Adder | 3.82 MW | 3.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942422 | AE2-255 E O1 | Adder | 11.45 MW | 9.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942651 | AE2-281 C O1 | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942652 | AE2-281 E O1 | Adder | 6.05 MW | 5.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942991 | AE2-321 C | Adder | 5.32 MW | 4.52 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942992 | AE2-321 E | Adder | 2.62 MW | 2.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 943801 | AF1-048 C | Adder | 2.48 MW | 2.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 943802 | AF1-048 E | Adder | 1.66 MW | 1.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946542 | AF1-318 E O1 | Adder | 18.59 MW | 15.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958481 | AF2-142 C | Adder | 12.52 MW | 10.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958482 | AF2-142 E | Adder | 8.35 MW | 7.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958491 | AF2-143 C | Adder | 12.66 MW | 10.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958492 | AF2-143 E | Adder | 8.44 MW | 7.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958911 | AF2-182 C | Adder | 14.09 MW | 11.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958912 | AF2-182 E | Adder | 9.39 MW | 7.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958921 | AF2-183 C | Adder | 2.5 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958922 | AF2-183 E | Adder | 3.76 MW | 3.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959081 | AF2-199 C | Adder | 4.82 MW | 4.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959082 | AF2-199 E | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959091 | AF2-200 C O1 | Adder | 9.63 MW | 8.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959092 | AF2-200 E O1 | Adder | 6.42 MW | 5.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959101 | AF2-201 C O1 | Adder | 4.02 MW | 3.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959102 | AF2-201 E O1 | Adder | 11.54 MW | 9.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959351 | AF2-226 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959352 | AF2-226 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960281 | AF2-319 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960282 | AF2-319 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960581 | AF2-349 C | Adder | 14.25 MW | 12.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960582 | AF2-349 E | Adder | 9.5 MW | 8.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960721 | AF2-363 C O1 | Adder | 3.67 MW | 3.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960722 | AF2-363 E O1 | Adder | 2.44 MW | 2.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960751 | AF2-366 C | Adder | 4.16 MW | 3.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960752 | AF2-366 E | Adder | 2.77 MW | 2.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961011 | AF2-392 C O1 | Adder | 2.75 MW | 2.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961012 | AF2-392 E O1 | Adder | 12.85 MW | 10.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961021 | AF2-393 O1 | Adder | 4.68 MW | 3.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961031 | AF2-394 O1 | Adder | 3.12 MW | 2.65 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274728 | ELWOOD EC;5P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274729 | ELWOOD EC;1P | 50/50 | 5.21 MW | 5.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274730 | ELWOOD EC;6P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274732 | ELWOOD EC;7P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274734 | ELWOOD EC;8P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274736 | ELWOOD EC;9P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274859 | EASYR;U1 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274860 | EASYR;U2 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274861 | TOP CROP ;1U | 50/50 | 0.93 MW | 0.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274862 | TOP CROP ;2U | 50/50 | 1.78 MW | 1.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 276170 | Z1-108 E | Adder | 1.61 MW | 1.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 276591 | L-013 2 | Adder | 2.25 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293516 | O-009 E1 | Adder | 6.48 MW | 5.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293517 | O-009 E2 | Adder | 3.29 MW | 2.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293518 | O-009 E3 | Adder | 3.63 MW | 3.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293644 | O22 E1 | 50/50 | 24.24 MW | 24.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293645 | O22 E2 | 50/50 | 47.06 MW | 47.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293715 | O-029 E | Adder | 6.93 MW | 5.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293716 | O-029 E | Adder | 3.8 MW | 3.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293717 | O-029 E | Adder | 3.49 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293771 | O-035 E | Adder | 4.69 MW | 3.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 294401 | BSHIL;1U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 294410 | BSHIL;2U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 294763 | P-046 E | Adder | 6.25 MW | 5.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 915011 | Y3-013 1 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 915021 | Y3-013 2 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 915031 | Y3-013 3 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 916211 | Z1-072 E | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 916221 | Z1-073 E | Adder | 3.38 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 925581 | AC1-033 C | Adder | 1.08 MW | 0.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 925582 | AC1-033 E | Adder | 7.2 MW | 6.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 930482 | AB1-089 CT | Adder | 24.12 MW | 20.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 930483 | AB1-089 ST | Adder | 19.18 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 930761 | AB1-122 CT1 | Adder | 68.76 MW | 58.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 930771 | AB1-122 CT2 | Adder | 93.21 MW | 79.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938511 | AE1-070 1 | 50/50 | 14.44 MW | 14.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938521 | AE1-070 2 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938851 | AE1-113 C O1 | Adder | 10.08 MW | 8.56 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938852 | AE1-113 E O1 | Adder | 35.73 MW | 30.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938861 | AE1-114 C O1 | Adder | 2.65 MW | 2.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938862 | AE1-114 E O1 | Adder | 9.05 MW | 7.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 939051 | AE1-134 1 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 939061 | AE1-134 2 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 939321 | AE1-163 C O1 | Adder | 6.89 MW | 5.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 939322 | AE1-163 E O1 | Adder | 42.35 MW | 35.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 940501 | AE2-035 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 940502 | AE2-035 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 941131 | AE2-107 C | Adder | 3.95 MW | 3.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 941132 | AE2-107 E | Adder | 2.63 MW | 2.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946151 | AF1-280 C O1 | Adder | 10.73 MW | 9.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946152 | AF1-280 E O1 | Adder | 4.93 MW | 4.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946161 | AF1-281 C O1 | Adder | 0.24 MW | 0.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946162 | AF1-281 E O1 | Adder | 1.33 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946321 | AF1-296 C O1 | Adder | 2.86 MW | 2.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946322 | AF1-296 E O1 | Adder | 13.39 MW | 11.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946501 | AF1-314 C | Adder | 2.91 MW | 2.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946502 | AF1-314 E | Adder | 13.66 MW | 11.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946541 | AF1-318 C O1 | Adder | 3.97 MW | 3.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946661 | AF1-330 C | Adder | 1.3 MW | 1.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946662 | AF1-330 E | Adder | 0.29 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946671 | AF1-331 | Adder | 1.48 MW | 1.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957331 | AF2-027 C | Adder | 1.65 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957332 | AF2-027 E | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957401 | AF2-034 C | Adder | 1.87 MW | 1.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957402 | AF2-034 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957471 | AF2-041 C | Adder | 14.45 MW | 12.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957472 | AF2-041 E | Adder | 7.23 MW | 6.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957751 | AF2-069 C | Adder | 0.17 MW | 0.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957752 | AF2-069 E | Adder | 0.56 MW | 0.48 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957762 | AF2-070 E | Adder | 1.19 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958341 | AF2-128 C O1 | Adder | 1.04 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958342 | AF2-128 E O1 | Adder | 4.87 MW | 4.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 990901 | L-005 E | Adder | 10.43 MW | 8.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934101 | AD2-000 1 | Adder | 5.56 MW | 4.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934111 | AD2-000 2 | Adder | 7.54 MW | 6.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 290108 | LEEDK;1U E | Adder | 14.62 MW | 12.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958023 | AF2-096 BAT | Adder | 8.72 MW | 7.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 964362 | AG1-298 BAT | Adder | 42.67 MW | 36.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 954981 | J974 C | External Queue | 3.01 MW | 3.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 954982 | J974 E | External Queue | 16.3 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.29 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.03 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.08 MW | 0.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.34 MW | 42.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.14 MW | 15.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.05 MW | 1.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.18 MW | 0.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.11 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.23 MW | 0.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.68 MW | 9.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.57 MW | 0.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.76 MW | 6.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.35 MW | 0.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.51 MW | 2.51 MW |
| Details for AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962012 | AG1-044 E | 50/50 | 0.16 MW | 0.16 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966821 | AG1-553 C O1 | 50/50 | 56.08 MW | 56.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966822 | AG1-553 E O1 | 50/50 | 11.29 MW | 11.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965061 | AG1-371 | 50/50 | 17.78 MW | 17.78 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965081 | AG1-373 | 50/50 | 5.93 MW | 5.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965661 | AG1-434 C O1 | 50/50 | 18.61 MW | 18.61 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965662 | AG1-434 E O1 | 50/50 | 87.14 MW | 87.14 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965671 | AG1-435 C O1 | Adder | 3.34 MW | 2.84 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965672 | AG1-435 E O1 | Adder | 15.63 MW | 13.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965931 | AG1-462 C O1 | 50/50 | 36.3 MW | 36.3 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965932 | AG1-462 E O1 | 50/50 | 24.2 MW | 24.2 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 272364 | ESS H440N ;R | Adder | 2.07 MW | 1.76 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 290051 | GSG-6; E | Adder | 8.51 MW | 7.23 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.55 MW | 3.87 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295110 | SUBLETTE C | 50/50 | 0.13 MW | 0.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295111 | SUBLETTE E | 50/50 | 5.31 MW | 5.31 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919221 | AA1-146 | 50/50 | 8.98 MW | 8.98 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919581 | AA2-030 C | 50/50 | 52.74 MW | 52.74 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.48 MW | 4.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933911 | AD1-013 C | Adder | 1.43 MW | 1.22 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934051 | AD1-031 C O1 | 50/50 | 2.92 MW | 2.92 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934052 | AD1-031 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937001 | AD2-134 C | Adder | 2.06 MW | 1.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937002 | AD2-134 E | Adder | 8.22 MW | 6.99 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958911 | AF2-182 C | 50/50 | 60.46 MW | 60.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958912 | AF2-182 E | 50/50 | 40.3 MW | 40.3 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958921 | AF2-183 C | 50/50 | 10.75 MW | 10.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958922 | AF2-183 E | 50/50 | 16.12 MW | 16.12 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959081 | AF2-199 C | 50/50 | 35.57 MW | 35.57 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959082 | AF2-199 E | 50/50 | 17.78 MW | 17.78 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959091 | AF2-200 C O1 | 50/50 | 71.13 MW | 71.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959092 | AF2-200 E O1 | 50/50 | 47.42 MW | 47.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961011 | AF2-392 C O1 | 50/50 | 9.47 MW | 9.47 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961012 | AF2-392 E O1 | 50/50 | 44.36 MW | 44.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961021 | AF2-393 O1 | 50/50 | 16.15 MW | 16.15 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961031 | AF2-394 O1 | 50/50 | 10.77 MW | 10.77 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274662 | QUAD CITI;1U | 50/50 | 36.61 MW | 36.61 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274663 | QUAD CITI;2U | 50/50 | 36.71 MW | 36.71 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274699 | CORDOVA ;1C | 50/50 | 6.45 MW | 6.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274700 | CORDOVA ;2C | 50/50 | 6.45 MW | 6.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274701 | CORDOVA ;1S | 50/50 | 7.25 MW | 7.25 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274715 | NELSON EC;1C | 50/50 | 9.63 MW | 9.63 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274716 | NELSON EC;1S | 50/50 | 7.03 MW | 7.03 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274717 | NELSON EC;2C | 50/50 | 9.7 MW | 9.7 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274718 | NELSON EC;2S | 50/50 | 7.09 MW | 7.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274857 | BIG SKY ;U1 | 50/50 | 0.87 MW | 0.87 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274858 | BIG SKY ;U2 | 50/50 | 0.87 MW | 0.87 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274859 | EASYR;U1 E | 50/50 | 32.24 MW | 32.24 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274860 | EASYR;U2 E | 50/50 | 32.24 MW | 32.24 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274877 | BISHOP HL;1U | 50/50 | 0.38 MW | 0.38 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274878 | BISHOP HL;2U | 50/50 | 0.38 MW | 0.38 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276156 | O-029 C | 50/50 | 0.46 MW | 0.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276157 | O-029 C | 50/50 | 0.49 MW | 0.49 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276158 | O-029 C | 50/50 | 0.9 MW | 0.9 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293513 | O-009 C1 | 50/50 | 0.85 MW | 0.85 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293514 | O-009 C2 | 50/50 | 0.43 MW | 0.43 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293516 | O-009 E1 | 50/50 | 19.89 MW | 19.89 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293517 | O-009 E2 | 50/50 | 10.1 MW | 10.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293518 | O-009 E3 | 50/50 | 11.12 MW | 11.12 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293715 | O-029 E | 50/50 | 21.26 MW | 21.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293716 | O-029 E | 50/50 | 11.66 MW | 11.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293717 | O-029 E | 50/50 | 10.71 MW | 10.71 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293771 | O-035 E | Adder | 5.37 MW | 4.56 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294401 | BSHIL;1U E | 50/50 | 8.83 MW | 8.83 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294410 | BSHIL;2U E | 50/50 | 8.83 MW | 8.83 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916211 | Z1-072 E | Adder | 4.06 MW | 3.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916221 | Z1-073 E | Adder | 4.42 MW | 3.76 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925581 | AC1-033 C | 50/50 | 1.45 MW | 1.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925582 | AC1-033 E | 50/50 | 9.68 MW | 9.68 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938861 | AE1-114 C O1 | 50/50 | 5.06 MW | 5.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938862 | AE1-114 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939051 | AE1-134 1 | 50/50 | 4.1 MW | 4.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939061 | AE1-134 2 | 50/50 | 4.1 MW | 4.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946151 | AF1-280 C O1 | 50/50 | 46.01 MW | 46.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946152 | AF1-280 E O1 | 50/50 | 21.16 MW | 21.16 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946162 | AF1-281 E O1 | 50/50 | 5.71 MW | 5.71 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946321 | AF1-296 C O1 | 50/50 | 8.66 MW | 8.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946322 | AF1-296 E O1 | 50/50 | 40.52 MW | 40.52 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957471 | AF2-041 C | 50/50 | 106.7 MW | 106.7 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957472 | AF2-041 E | 50/50 | 53.35 MW | 53.35 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957762 | AF2-070 E | Adder | 1.36 MW | 1.16 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990901 | L-005 E | Adder | 12.01 MW | 10.21 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951381 | J504 | External Queue | 5.04 MW | 5.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951421 | J514 | External Queue | 3.06 MW | 3.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951511 | J530 C | External Queue | 4.95 MW | 4.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951512 | J530 E | External Queue | 19.82 MW | 19.82 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 955971 | J1084 | External Queue | 29.54 MW | 29.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 956411 | J1131 | External Queue | 15.48 MW | 15.48 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990947 | J1432 E | External Queue | 41.55 MW | 41.55 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 991091 | J1477 | External Queue | 7.74 MW | 7.74 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.7 MW | 6.7 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.36 MW | 52.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.73 MW | 21.73 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.17 MW | 0.17 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.12 MW | 5.12 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.7 MW | 16.7 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.08 MW | 1.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.54 MW | 2.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961651 | AG1-005 C O1 | Adder | 11.16 MW | 9.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961652 | AG1-005 E O1 | Adder | 7.44 MW | 6.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962691 | AG1-118 C O1 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962692 | AG1-118 E O1 | Adder | 8.76 MW | 7.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962701 | AG1-119 C | Adder | 14.23 MW | 12.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962702 | AG1-119 E | Adder | 9.49 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962711 | AG1-120 C O1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962712 | AG1-120 E O1 | Adder | 3.56 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962721 | AG1-121 C O1 | Adder | 4.04 MW | 3.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962722 | AG1-121 E O1 | Adder | 18.89 MW | 16.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962781 | AG1-127 C | Adder | 4.17 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962782 | AG1-127 E | Adder | 2.77 MW | 2.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 966821 | AG1-553 C O1 | Adder | 18.16 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 966822 | AG1-553 E O1 | Adder | 3.66 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965061 | AG1-371 | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965081 | AG1-373 | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965141 | AG1-379 C | Adder | 20.95 MW | 17.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965142 | AG1-379 E | Adder | 9.59 MW | 8.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965551 | AG1-423 C O1 | Adder | 9.49 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965552 | AG1-423 E O1 | Adder | 6.32 MW | 5.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965661 | AG1-434 C O1 | Adder | 2.81 MW | 2.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965662 | AG1-434 E O1 | Adder | 13.15 MW | 11.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965671 | AG1-435 C O1 | Adder | 2.8 MW | 2.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965672 | AG1-435 E O1 | Adder | 13.09 MW | 11.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965931 | AG1-462 C O1 | Adder | 11.75 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965932 | AG1-462 E O1 | Adder | 7.83 MW | 6.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 966441 | AG1-513 C | Adder | 0.3 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 966442 | AG1-513 E | Adder | 0.44 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 272364 | ESS H440N ;R | Adder | 1.63 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 290021 | O50 E | Adder | 24.43 MW | 20.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 290051 | GSG-6; E | Adder | 6.51 MW | 5.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 295109 | WESTBROOK E | Adder | 3.49 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 295111 | SUBLETTE E | Adder | 1.77 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 919581 | AA2-030 C | Adder | 12.28 MW | 10.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 920272 | AA2-123 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 926331 | AC1-110 1 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 926341 | AC1-110 2 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 927091 | AC1-204 GEN1 | 50/50 | 19.36 MW | 19.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 927093 | AC1-204 GEN2 | 50/50 | 19.47 MW | 19.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 927202 | AC1-214 E O1 | Adder | 4.78 MW | 4.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 927451 | AC1-142A 1 | Adder | 3.72 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 927461 | AC1-142A 2 | Adder | 3.74 MW | 3.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 933911 | AD1-013 C | Adder | 1.14 MW | 0.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 933912 | AD1-013 E | Adder | 1.83 MW | 1.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 933931 | AD1-016 C | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 933932 | AD1-016 E | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934051 | AD1-031 C O1 | Adder | 2.19 MW | 1.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934052 | AD1-031 E O1 | Adder | 3.57 MW | 3.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934432 | AD1-067 E | Adder | 0.34 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934971 | AD1-129 C | Adder | 0.59 MW | 0.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934972 | AD1-129 E | Adder | 0.39 MW | 0.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 936291 | AD2-038 C O1 | Adder | 3.71 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 936292 | AD2-038 E O1 | Adder | 17.39 MW | 14.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 936511 | AD2-066 C O1 | Adder | 6.37 MW | 5.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 936512 | AD2-066 E O1 | Adder | 4.24 MW | 3.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937001 | AD2-134 C | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937002 | AD2-134 E | Adder | 6.3 MW | 5.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937311 | AD2-172 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937312 | AD2-172 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937401 | AD2-194 1 | Adder | 12.23 MW | 10.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937411 | AD2-194 2 | 50/50 | 12.29 MW | 12.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942421 | AE2-255 C O1 | Adder | 3.82 MW | 3.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942422 | AE2-255 E O1 | Adder | 11.45 MW | 9.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942651 | AE2-281 C O1 | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942652 | AE2-281 E O1 | Adder | 6.05 MW | 5.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942991 | AE2-321 C | Adder | 5.32 MW | 4.52 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942992 | AE2-321 E | Adder | 2.62 MW | 2.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 943801 | AF1-048 C | Adder | 2.49 MW | 2.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 943802 | AF1-048 E | Adder | 1.66 MW | 1.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946542 | AF1-318 E O1 | Adder | 18.6 MW | 15.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958491 | AF2-143 C | Adder | 12.66 MW | 10.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958492 | AF2-143 E | Adder | 8.44 MW | 7.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958911 | AF2-182 C | Adder | 14.09 MW | 11.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958912 | AF2-182 E | Adder | 9.4 MW | 7.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958921 | AF2-183 C | Adder | 2.51 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958922 | AF2-183 E | Adder | 3.76 MW | 3.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959081 | AF2-199 C | Adder | 4.82 MW | 4.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959082 | AF2-199 E | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959091 | AF2-200 C O1 | Adder | 9.64 MW | 8.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959092 | AF2-200 E O1 | Adder | 6.42 MW | 5.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959101 | AF2-201 C O1 | Adder | 4.02 MW | 3.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959102 | AF2-201 E O1 | Adder | 11.54 MW | 9.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959351 | AF2-226 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959352 | AF2-226 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960281 | AF2-319 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960282 | AF2-319 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960581 | AF2-349 C | Adder | 14.25 MW | 12.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960582 | AF2-349 E | Adder | 9.5 MW | 8.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960721 | AF2-363 C O1 | Adder | 3.67 MW | 3.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960722 | AF2-363 E O1 | Adder | 2.44 MW | 2.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960751 | AF2-366 C | Adder | 4.16 MW | 3.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960752 | AF2-366 E | Adder | 2.77 MW | 2.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961011 | AF2-392 C O1 | Adder | 2.75 MW | 2.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961012 | AF2-392 E O1 | Adder | 12.86 MW | 10.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961021 | AF2-393 O1 | Adder | 4.68 MW | 3.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961031 | AF2-394 O1 | Adder | 3.12 MW | 2.65 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274728 | ELWOOD EC;5P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274730 | ELWOOD EC;6P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274732 | ELWOOD EC;7P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274734 | ELWOOD EC;8P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274735 | ELWOOD EC;4P | 50/50 | 5.21 MW | 5.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274736 | ELWOOD EC;9P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274859 | EASYR;U1 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274860 | EASYR;U2 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274861 | TOP CROP ;1U | 50/50 | 0.93 MW | 0.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274862 | TOP CROP ;2U | 50/50 | 1.78 MW | 1.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 276170 | Z1-108 E | Adder | 1.61 MW | 1.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 276591 | L-013 2 | Adder | 2.25 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293516 | O-009 E1 | Adder | 6.48 MW | 5.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293517 | O-009 E2 | Adder | 3.29 MW | 2.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293518 | O-009 E3 | Adder | 3.63 MW | 3.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293644 | O22 E1 | 50/50 | 24.25 MW | 24.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293645 | O22 E2 | 50/50 | 47.06 MW | 47.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293715 | O-029 E | Adder | 6.93 MW | 5.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293716 | O-029 E | Adder | 3.8 MW | 3.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293717 | O-029 E | Adder | 3.49 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293771 | O-035 E | Adder | 4.69 MW | 3.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 294401 | BSHIL;1U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 294410 | BSHIL;2U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 294763 | P-046 E | Adder | 6.25 MW | 5.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 915011 | Y3-013 1 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 915021 | Y3-013 2 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 915031 | Y3-013 3 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 916211 | Z1-072 E | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 916221 | Z1-073 E | Adder | 3.38 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 925581 | AC1-033 C | Adder | 1.08 MW | 0.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 925582 | AC1-033 E | Adder | 7.2 MW | 6.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 930482 | AB1-089 CT | Adder | 24.13 MW | 20.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 930483 | AB1-089 ST | Adder | 19.18 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 930761 | AB1-122 CT1 | Adder | 68.77 MW | 58.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 930771 | AB1-122 CT2 | Adder | 93.22 MW | 79.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938511 | AE1-070 1 | 50/50 | 14.45 MW | 14.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938521 | AE1-070 2 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938851 | AE1-113 C O1 | Adder | 10.08 MW | 8.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938852 | AE1-113 E O1 | Adder | 35.73 MW | 30.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938861 | AE1-114 C O1 | Adder | 2.65 MW | 2.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938862 | AE1-114 E O1 | Adder | 9.06 MW | 7.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 939051 | AE1-134 1 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 939061 | AE1-134 2 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 939321 | AE1-163 C O1 | Adder | 6.89 MW | 5.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 939322 | AE1-163 E O1 | Adder | 42.35 MW | 36.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 940501 | AE2-035 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 940502 | AE2-035 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 941131 | AE2-107 C | Adder | 3.95 MW | 3.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 941132 | AE2-107 E | Adder | 2.63 MW | 2.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946151 | AF1-280 C O1 | Adder | 10.73 MW | 9.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946152 | AF1-280 E O1 | Adder | 4.93 MW | 4.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946161 | AF1-281 C O1 | Adder | 0.24 MW | 0.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946162 | AF1-281 E O1 | Adder | 1.33 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946321 | AF1-296 C O1 | Adder | 2.86 MW | 2.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946322 | AF1-296 E O1 | Adder | 13.4 MW | 11.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946501 | AF1-314 C | Adder | 2.91 MW | 2.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946502 | AF1-314 E | Adder | 13.67 MW | 11.62 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946541 | AF1-318 C O1 | Adder | 3.97 MW | 3.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946661 | AF1-330 C | Adder | 1.3 MW | 1.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946662 | AF1-330 E | Adder | 0.29 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946671 | AF1-331 | Adder | 1.48 MW | 1.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957331 | AF2-027 C | Adder | 1.65 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957332 | AF2-027 E | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957401 | AF2-034 C | Adder | 1.87 MW | 1.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957402 | AF2-034 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957471 | AF2-041 C | Adder | 14.45 MW | 12.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957472 | AF2-041 E | Adder | 7.23 MW | 6.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957751 | AF2-069 C | Adder | 0.17 MW | 0.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957752 | AF2-069 E | Adder | 0.56 MW | 0.48 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957762 | AF2-070 E | Adder | 1.19 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958341 | AF2-128 C O1 | Adder | 1.04 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958342 | AF2-128 E O1 | Adder | 4.88 MW | 4.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 990901 | L-005 E | Adder | 10.43 MW | 8.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934101 | AD2-000 1 | Adder | 5.56 MW | 4.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934111 | AD2-000 2 | Adder | 7.54 MW | 6.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 290108 | LEEDK;1U E | Adder | 14.62 MW | 12.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958023 | AF2-096 BAT | Adder | 8.72 MW | 7.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 964362 | AG1-298 BAT | Adder | 42.66 MW | 36.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 954981 | J974 C | External Queue | 3.01 MW | 3.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 954982 | J974 E | External Queue | 16.3 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.29 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.02 MW | 1.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.08 MW | 0.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.37 MW | 42.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.16 MW | 15.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.05 MW | 1.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.18 MW | 0.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.11 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.23 MW | 0.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.68 MW | 9.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.57 MW | 0.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.75 MW | 6.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.35 MW | 0.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.51 MW | 2.51 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961651 | AG1-005 C O1 | Adder | 13.25 MW | 11.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961652 | AG1-005 E O1 | Adder | 8.83 MW | 7.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962012 | AG1-044 E | Adder | 0.06 MW | 0.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 17.0 MW | 14.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 11.33 MW | 9.63 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962701 | AG1-119 C | Adder | 18.64 MW | 15.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962702 | AG1-119 E | Adder | 12.42 MW | 10.56 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 6.95 MW | 5.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 4.63 MW | 3.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962721 | AG1-121 C O1 | Adder | 4.77 MW | 4.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962722 | AG1-121 E O1 | Adder | 22.31 MW | 18.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962781 | AG1-127 C | Adder | 5.4 MW | 4.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962782 | AG1-127 E | Adder | 3.59 MW | 3.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 964581 | AG1-321 C O1 | Adder | 11.37 MW | 9.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 964582 | AG1-321 E O1 | Adder | 6.62 MW | 5.63 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966821 | AG1-553 C O1 | Adder | 22.74 MW | 19.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966822 | AG1-553 E O1 | Adder | 4.58 MW | 3.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965061 | AG1-371 | Adder | 3.07 MW | 2.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965081 | AG1-373 | Adder | 1.02 MW | 0.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965141 | AG1-379 C | Adder | 22.38 MW | 19.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965142 | AG1-379 E | Adder | 10.24 MW | 8.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 12.43 MW | 10.56 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 8.28 MW | 7.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 3.58 MW | 3.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 16.76 MW | 14.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965671 | AG1-435 C O1 | Adder | 3.3 MW | 2.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965672 | AG1-435 E O1 | Adder | 15.47 MW | 13.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965931 | AG1-462 C O1 | Adder | 14.72 MW | 12.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965932 | AG1-462 E O1 | Adder | 9.81 MW | 8.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966441 | AG1-513 C | Adder | 0.39 MW | 0.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966442 | AG1-513 E | Adder | 0.58 MW | 0.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 272364 | ESS H440N ;R | Adder | 2.1 MW | 1.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 290021 | O50 E | Adder | 26.1 MW | 22.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 290051 | GSG-6; E | Adder | 8.37 MW | 7.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.48 MW | 3.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.26 MW | 1.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 919581 | AA2-030 C | Adder | 15.6 MW | 13.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 920272 | AA2-123 E | Adder | 2.11 MW | 1.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.52 MW | 1.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.52 MW | 1.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927093 | AC1-204 GEN2 | 50/50 | 18.22 MW | 18.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927202 | AC1-214 E O1 | Adder | 5.67 MW | 4.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927451 | AC1-142A 1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927461 | AC1-142A 2 | Adder | 5.37 MW | 4.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933911 | AD1-013 C | Adder | 1.47 MW | 1.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933912 | AD1-013 E | Adder | 2.35 MW | 2.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933931 | AD1-016 C | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933932 | AD1-016 E | Adder | 1.31 MW | 1.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934051 | AD1-031 C O1 | Adder | 2.59 MW | 2.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934052 | AD1-031 E O1 | Adder | 4.22 MW | 3.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934432 | AD1-067 E | Adder | 0.44 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934971 | AD1-129 C | Adder | 0.78 MW | 0.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934972 | AD1-129 E | Adder | 0.52 MW | 0.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.35 MW | 2.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 11.01 MW | 9.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 7.24 MW | 6.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.82 MW | 4.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937001 | AD2-134 C | Adder | 2.02 MW | 1.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937002 | AD2-134 E | Adder | 8.09 MW | 6.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937311 | AD2-172 C | Adder | 2.14 MW | 1.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937312 | AD2-172 E | Adder | 2.95 MW | 2.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937401 | AD2-194 1 | Adder | 11.36 MW | 9.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937411 | AD2-194 2 | 50/50 | 11.5 MW | 11.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942111 | AE2-223 C | Adder | 1.51 MW | 1.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942112 | AE2-223 E | Adder | 10.12 MW | 8.6 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 4.08 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 12.24 MW | 10.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.62 MW | 0.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.83 MW | 3.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942991 | AE2-321 C | Adder | 7.07 MW | 6.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942992 | AE2-321 E | Adder | 3.48 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943121 | AE2-341 C | Adder | 8.03 MW | 6.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943122 | AE2-341 E | Adder | 3.94 MW | 3.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 2.64 MW | 2.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943801 | AF1-048 C | Adder | 3.3 MW | 2.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943802 | AF1-048 E | Adder | 2.2 MW | 1.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946542 | AF1-318 E O1 | Adder | 22.06 MW | 18.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958491 | AF2-143 C | Adder | 8.02 MW | 6.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958492 | AF2-143 E | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958911 | AF2-182 C | Adder | 18.05 MW | 15.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958912 | AF2-182 E | Adder | 12.03 MW | 10.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958921 | AF2-183 C | Adder | 3.21 MW | 2.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958922 | AF2-183 E | Adder | 4.81 MW | 4.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959081 | AF2-199 C | Adder | 6.15 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959082 | AF2-199 E | Adder | 3.07 MW | 2.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 12.29 MW | 10.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 8.2 MW | 6.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 5.23 MW | 4.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 15.02 MW | 12.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959341 | AF2-225 C | Adder | 4.88 MW | 4.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959342 | AF2-225 E | Adder | 6.74 MW | 5.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959351 | AF2-226 C | 50/50 | 7.16 MW | 7.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959352 | AF2-226 E | 50/50 | 10.74 MW | 10.74 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960281 | AF2-319 C | 50/50 | 7.16 MW | 7.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960282 | AF2-319 E | 50/50 | 10.74 MW | 10.74 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960381 | AF2-329 | Adder | 3.37 MW | 2.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960581 | AF2-349 C | Adder | 18.9 MW | 16.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960582 | AF2-349 E | Adder | 12.6 MW | 10.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.77 MW | 4.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.18 MW | 2.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960751 | AF2-366 C | Adder | 5.38 MW | 4.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960752 | AF2-366 E | Adder | 3.59 MW | 3.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961011 | AF2-392 C O1 | Adder | 3.49 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961012 | AF2-392 E O1 | Adder | 16.32 MW | 13.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961021 | AF2-393 O1 | Adder | 5.94 MW | 5.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961031 | AF2-394 O1 | Adder | 3.96 MW | 3.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274704 | KENDALL ;1C | 50/50 | 6.35 MW | 6.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274705 | KENDALL ;1S | 50/50 | 4.24 MW | 4.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274706 | KENDALL ;2C | 50/50 | 6.35 MW | 6.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274707 | KENDALL ;2S | 50/50 | 4.24 MW | 4.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274728 | ELWOOD EC;5P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274730 | ELWOOD EC;6P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274732 | ELWOOD EC;7P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274734 | ELWOOD EC;8P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274736 | ELWOOD EC;9P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274859 | EASYR;U1 E | Adder | 9.66 MW | 8.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274860 | EASYR;U2 E | Adder | 9.66 MW | 8.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 1.12 MW | 1.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 2.14 MW | 2.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 276170 | Z1-108 E | Adder | 2.16 MW | 1.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 276591 | L-013 2 | Adder | 2.95 MW | 2.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293516 | O-009 E1 | Adder | 8.09 MW | 6.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293517 | O-009 E2 | Adder | 4.11 MW | 3.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293518 | O-009 E3 | Adder | 4.52 MW | 3.85 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293644 | O22 E1 | 50/50 | 29.21 MW | 29.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293645 | O22 E2 | 50/50 | 56.7 MW | 56.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293715 | O-029 E | Adder | 8.65 MW | 7.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293716 | O-029 E | Adder | 4.74 MW | 4.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293717 | O-029 E | Adder | 4.36 MW | 3.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293771 | O-035 E | Adder | 5.56 MW | 4.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 294401 | BSHIL;1U E | Adder | 7.77 MW | 6.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 294410 | BSHIL;2U E | Adder | 7.77 MW | 6.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 294763 | P-046 E | Adder | 8.14 MW | 6.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 916211 | Z1-072 E | Adder | 4.2 MW | 3.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 916221 | Z1-073 E | Adder | 4.35 MW | 3.69 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 917502 | Z2-087 E | Adder | 13.49 MW | 11.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 924042 | AB2-047 E O1 | Adder | 16.86 MW | 14.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 925581 | AC1-033 C | Adder | 1.27 MW | 1.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 925582 | AC1-033 E | Adder | 8.52 MW | 7.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930482 | AB1-089 CT | Adder | 31.55 MW | 26.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930483 | AB1-089 ST | Adder | 25.08 MW | 21.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 73.53 MW | 62.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 101.92 MW | 86.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938511 | AE1-070 1 | 50/50 | 13.52 MW | 13.52 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938521 | AE1-070 2 | Adder | 12.21 MW | 10.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 10.77 MW | 9.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 38.17 MW | 32.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.42 MW | 2.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 11.67 MW | 9.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939051 | AE1-134 1 | Adder | 1.21 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939061 | AE1-134 2 | Adder | 1.21 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 4.36 MW | 3.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 26.81 MW | 22.79 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939741 | AE1-205 C O1 | Adder | 6.51 MW | 5.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939742 | AE1-205 E O1 | Adder | 8.99 MW | 7.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 940501 | AE2-035 C | Adder | 2.14 MW | 1.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 940502 | AE2-035 E | Adder | 2.95 MW | 2.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 941131 | AE2-107 C | Adder | 5.09 MW | 4.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 941132 | AE2-107 E | Adder | 3.39 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 941731 | AE2-173 O1 | Adder | 3.88 MW | 3.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946151 | AF1-280 C O1 | Adder | 13.74 MW | 11.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946152 | AF1-280 E O1 | Adder | 6.32 MW | 5.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946161 | AF1-281 C O1 | Adder | 0.3 MW | 0.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946162 | AF1-281 E O1 | Adder | 1.7 MW | 1.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946321 | AF1-296 C O1 | Adder | 3.6 MW | 3.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946322 | AF1-296 E O1 | Adder | 16.83 MW | 14.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946501 | AF1-314 C | Adder | 3.79 MW | 3.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946502 | AF1-314 E | Adder | 17.79 MW | 15.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946541 | AF1-318 C O1 | Adder | 4.71 MW | 4.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946661 | AF1-330 C | Adder | 1.73 MW | 1.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946662 | AF1-330 E | Adder | 0.38 MW | 0.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946671 | AF1-331 | Adder | 1.91 MW | 1.62 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957331 | AF2-027 C | Adder | 2.3 MW | 1.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957332 | AF2-027 E | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957401 | AF2-034 C | 50/50 | 2.21 MW | 2.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957402 | AF2-034 E | 50/50 | 1.88 MW | 1.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957471 | AF2-041 C | Adder | 18.44 MW | 15.67 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957472 | AF2-041 E | Adder | 9.22 MW | 7.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957751 | AF2-069 C | Adder | 0.21 MW | 0.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957752 | AF2-069 E | Adder | 0.67 MW | 0.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957761 | AF2-070 C | Adder | 0.29 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957762 | AF2-070 E | Adder | 1.41 MW | 1.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958341 | AF2-128 C O1 | Adder | 1.24 MW | 1.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958342 | AF2-128 E O1 | Adder | 5.78 MW | 4.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 990901 | L-005 E | Adder | 12.26 MW | 10.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.95 MW | 5.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934111 | AD2-000 2 | Adder | 8.24 MW | 7.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 290108 | LEEDK;1U E | Adder | 18.85 MW | 16.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958023 | AF2-096 BAT | Adder | 8.6 MW | 7.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 954981 | J974 C | External Queue | 3.02 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 954982 | J974 E | External Queue | 10.86 MW | 10.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.3 MW | 0.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.02 MW | 1.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.06 MW | 0.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 57.43 MW | 57.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.2 MW | 21.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.27 MW | 1.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.17 MW | 0.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.22 MW | 4.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 12.32 MW | 12.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.69 MW | 0.69 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.14 MW | 8.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.36 MW | 0.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.89 MW | 1.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.43 MW | 3.43 MW |
| Details for AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 962012 | AG1-044 E | Adder | 0.16 MW | 0.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 966821 | AG1-553 C O1 | Adder | 56.0 MW | 47.6 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 966822 | AG1-553 E O1 | Adder | 11.28 MW | 9.59 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965061 | AG1-371 | 50/50 | 17.75 MW | 17.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965081 | AG1-373 | 50/50 | 5.92 MW | 5.92 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965661 | AG1-434 C O1 | 50/50 | 18.58 MW | 18.58 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965662 | AG1-434 E O1 | 50/50 | 86.99 MW | 86.99 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965931 | AG1-462 C O1 | Adder | 36.25 MW | 30.81 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965932 | AG1-462 E O1 | Adder | 24.16 MW | 20.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 295111 | SUBLETTE E | Adder | 5.31 MW | 4.51 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 919221 | AA1-146 | 50/50 | 8.97 MW | 8.97 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 919581 | AA2-030 C | 50/50 | 52.66 MW | 52.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 934051 | AD1-031 C O1 | Adder | 2.89 MW | 2.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 934052 | AD1-031 E O1 | Adder | 4.72 MW | 4.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958911 | AF2-182 C | 50/50 | 60.37 MW | 60.37 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958912 | AF2-182 E | 50/50 | 40.24 MW | 40.24 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958921 | AF2-183 C | 50/50 | 10.73 MW | 10.73 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958922 | AF2-183 E | 50/50 | 16.1 MW | 16.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959081 | AF2-199 C | 50/50 | 35.51 MW | 35.51 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959082 | AF2-199 E | 50/50 | 17.75 MW | 17.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959091 | AF2-200 C O1 | 50/50 | 71.01 MW | 71.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959092 | AF2-200 E O1 | 50/50 | 47.34 MW | 47.34 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961011 | AF2-392 C O1 | Adder | 9.47 MW | 8.05 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961012 | AF2-392 E O1 | Adder | 44.32 MW | 37.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961021 | AF2-393 O1 | Adder | 16.13 MW | 13.71 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961031 | AF2-394 O1 | Adder | 10.76 MW | 9.14 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274715 | NELSON EC;1C | 50/50 | 9.61 MW | 9.61 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274716 | NELSON EC;1S | 50/50 | 7.01 MW | 7.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274717 | NELSON EC;2C | 50/50 | 9.69 MW | 9.69 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274718 | NELSON EC;2S | 50/50 | 7.08 MW | 7.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274760 | LEE CO EC;1U | 50/50 | 4.85 MW | 4.85 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274764 | LEE CO EC;5U | 50/50 | 4.86 MW | 4.86 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274765 | LEE CO EC;6U | 50/50 | 4.86 MW | 4.86 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274859 | EASYR;U1 E | Adder | 32.19 MW | 27.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274860 | EASYR;U2 E | Adder | 32.19 MW | 27.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293516 | O-009 E1 | Adder | 19.85 MW | 16.87 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293517 | O-009 E2 | Adder | 10.08 MW | 8.57 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293518 | O-009 E3 | Adder | 11.1 MW | 9.44 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293715 | O-029 E | Adder | 21.22 MW | 18.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293716 | O-029 E | Adder | 11.64 MW | 9.89 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293717 | O-029 E | Adder | 10.69 MW | 9.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 294401 | BSHIL;1U E | Adder | 8.76 MW | 7.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 294410 | BSHIL;2U E | Adder | 8.76 MW | 7.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 925581 | AC1-033 C | Adder | 1.44 MW | 1.22 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 925582 | AC1-033 E | Adder | 9.61 MW | 8.17 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 938861 | AE1-114 C O1 | Adder | 5.1 MW | 4.34 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 938862 | AE1-114 E O1 | Adder | 17.41 MW | 14.8 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 939051 | AE1-134 1 | 50/50 | 4.09 MW | 4.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 939061 | AE1-134 2 | 50/50 | 4.09 MW | 4.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946151 | AF1-280 C O1 | 50/50 | 45.95 MW | 45.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946152 | AF1-280 E O1 | 50/50 | 21.13 MW | 21.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946162 | AF1-281 E O1 | 50/50 | 5.7 MW | 5.7 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946321 | AF1-296 C O1 | Adder | 8.65 MW | 7.35 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946322 | AF1-296 E O1 | Adder | 40.48 MW | 34.41 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 957471 | AF2-041 C | 50/50 | 106.52 MW | 106.52 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 957472 | AF2-041 E | 50/50 | 53.26 MW | 53.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951381 | J504 | External Queue | 5.06 MW | 5.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951421 | J514 | External Queue | 3.07 MW | 3.07 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951511 | J530 C | External Queue | 4.96 MW | 4.96 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951512 | J530 E | External Queue | 19.86 MW | 19.86 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 955971 | J1084 | External Queue | 29.58 MW | 29.58 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 956411 | J1131 | External Queue | 15.49 MW | 15.49 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 990947 | J1432 E | External Queue | 41.67 MW | 41.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 991091 | J1477 | External Queue | 7.75 MW | 7.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.15 MW | 0.15 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.54 MW | 5.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.0 MW | 52.0 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 20.86 MW | 20.86 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.23 MW | 0.23 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.29 MW | 0.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.96 MW | 4.96 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.67 MW | 16.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.88 MW | 1.88 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.4 MW | 2.4 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961651 | AG1-005 C O1 | Adder | 12.71 MW | 10.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961652 | AG1-005 E O1 | Adder | 8.47 MW | 7.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962012 | AG1-044 E | Adder | 0.06 MW | 0.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 17.56 MW | 14.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 11.71 MW | 9.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962701 | AG1-119 C | Adder | 19.08 MW | 16.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962702 | AG1-119 E | Adder | 12.72 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 7.14 MW | 6.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 4.76 MW | 4.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962721 | AG1-121 C O1 | Adder | 4.61 MW | 3.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962722 | AG1-121 E O1 | Adder | 21.58 MW | 18.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962781 | AG1-127 C | Adder | 5.57 MW | 4.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962782 | AG1-127 E | Adder | 3.71 MW | 3.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966821 | AG1-553 C O1 | Adder | 22.49 MW | 19.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966822 | AG1-553 E O1 | Adder | 4.53 MW | 3.85 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965061 | AG1-371 | Adder | 3.13 MW | 2.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965081 | AG1-373 | Adder | 1.04 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965141 | AG1-379 C | Adder | 22.42 MW | 19.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965142 | AG1-379 E | Adder | 10.26 MW | 8.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 12.72 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 8.48 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 3.64 MW | 3.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 17.03 MW | 14.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965671 | AG1-435 C O1 | Adder | 3.19 MW | 2.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965672 | AG1-435 E O1 | Adder | 14.96 MW | 12.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965931 | AG1-462 C O1 | Adder | 14.56 MW | 12.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965932 | AG1-462 E O1 | Adder | 9.7 MW | 8.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966441 | AG1-513 C | Adder | 0.4 MW | 0.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966442 | AG1-513 E | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290021 | O50 E | Adder | 26.14 MW | 22.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290051 | GSG-6; E | Adder | 8.56 MW | 7.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 919581 | AA2-030 C | Adder | 15.68 MW | 13.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 920272 | AA2-123 E | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927093 | AC1-204 GEN2 | 50/50 | 18.42 MW | 18.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927202 | AC1-214 E O1 | Adder | 5.46 MW | 4.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927451 | AC1-142A 1 | Adder | 5.49 MW | 4.67 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927461 | AC1-142A 2 | Adder | 5.52 MW | 4.69 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933931 | AD1-016 C | Adder | 0.82 MW | 0.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933932 | AD1-016 E | Adder | 1.34 MW | 1.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934051 | AD1-031 C O1 | Adder | 2.5 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934052 | AD1-031 E O1 | Adder | 4.08 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934971 | AD1-129 C | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934972 | AD1-129 E | Adder | 0.53 MW | 0.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.39 MW | 2.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 11.17 MW | 9.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 7.28 MW | 6.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.86 MW | 4.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937002 | AD2-134 E | Adder | 8.28 MW | 7.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937311 | AD2-172 C | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937312 | AD2-172 E | Adder | 3.0 MW | 2.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937401 | AD2-194 1 | Adder | 11.49 MW | 9.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937411 | AD2-194 2 | 50/50 | 11.63 MW | 11.63 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 4.08 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 12.26 MW | 10.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.89 MW | 3.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942991 | AE2-321 C | Adder | 7.24 MW | 6.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942992 | AE2-321 E | Adder | 3.57 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943121 | AE2-341 C | Adder | 8.48 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943122 | AE2-341 E | Adder | 4.16 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 5.64 MW | 4.79 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 2.79 MW | 2.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943801 | AF1-048 C | Adder | 3.39 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943802 | AF1-048 E | Adder | 2.26 MW | 1.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946542 | AF1-318 E O1 | Adder | 21.19 MW | 18.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958491 | AF2-143 C | Adder | 8.13 MW | 6.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958492 | AF2-143 E | Adder | 5.42 MW | 4.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958911 | AF2-182 C | Adder | 18.2 MW | 15.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958912 | AF2-182 E | Adder | 12.13 MW | 10.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958921 | AF2-183 C | Adder | 3.24 MW | 2.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958922 | AF2-183 E | Adder | 4.85 MW | 4.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959081 | AF2-199 C | Adder | 6.27 MW | 5.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959082 | AF2-199 E | Adder | 3.13 MW | 2.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 12.54 MW | 10.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 8.36 MW | 7.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 5.31 MW | 4.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 15.24 MW | 12.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959351 | AF2-226 C | 50/50 | 7.21 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959352 | AF2-226 E | 50/50 | 10.81 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960281 | AF2-319 C | 50/50 | 7.21 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960282 | AF2-319 E | 50/50 | 10.81 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960381 | AF2-329 | Adder | 3.56 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960581 | AF2-349 C | Adder | 19.33 MW | 16.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960582 | AF2-349 E | Adder | 12.89 MW | 10.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.9 MW | 4.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.27 MW | 2.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960751 | AF2-366 C | Adder | 5.55 MW | 4.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960752 | AF2-366 E | Adder | 3.7 MW | 3.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961011 | AF2-392 C O1 | Adder | 3.5 MW | 2.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961012 | AF2-392 E O1 | Adder | 16.4 MW | 13.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961021 | AF2-393 O1 | Adder | 5.97 MW | 5.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961031 | AF2-394 O1 | Adder | 3.98 MW | 3.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274704 | KENDALL ;1C | 50/50 | 6.46 MW | 6.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274705 | KENDALL ;1S | 50/50 | 4.32 MW | 4.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274706 | KENDALL ;2C | 50/50 | 6.46 MW | 6.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274707 | KENDALL ;2S | 50/50 | 4.32 MW | 4.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274728 | ELWOOD EC;5P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274730 | ELWOOD EC;6P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274732 | ELWOOD EC;7P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274734 | ELWOOD EC;8P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274736 | ELWOOD EC;9P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274859 | EASYR;U1 E | Adder | 9.76 MW | 8.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274860 | EASYR;U2 E | Adder | 9.76 MW | 8.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 1.13 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 2.15 MW | 2.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 276170 | Z1-108 E | Adder | 2.22 MW | 1.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 276591 | L-013 2 | Adder | 3.05 MW | 2.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293516 | O-009 E1 | Adder | 8.05 MW | 6.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293517 | O-009 E2 | Adder | 4.09 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293518 | O-009 E3 | Adder | 4.5 MW | 3.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293644 | O22 E1 | 50/50 | 29.41 MW | 29.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293645 | O22 E2 | 50/50 | 57.09 MW | 57.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293715 | O-029 E | Adder | 8.6 MW | 7.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293716 | O-029 E | Adder | 4.72 MW | 4.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293717 | O-029 E | Adder | 4.33 MW | 3.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293771 | O-035 E | Adder | 5.36 MW | 4.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294401 | BSHIL;1U E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294410 | BSHIL;2U E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294763 | P-046 E | Adder | 8.26 MW | 7.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 916211 | Z1-072 E | Adder | 4.05 MW | 3.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 916221 | Z1-073 E | Adder | 4.45 MW | 3.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 925581 | AC1-033 C | Adder | 1.23 MW | 1.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 925582 | AC1-033 E | Adder | 8.23 MW | 7.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930482 | AB1-089 CT | Adder | 32.18 MW | 27.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930483 | AB1-089 ST | Adder | 25.58 MW | 21.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 71.38 MW | 60.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 103.64 MW | 88.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938511 | AE1-070 1 | 50/50 | 13.67 MW | 13.67 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938521 | AE1-070 2 | Adder | 12.35 MW | 10.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 10.78 MW | 9.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 38.24 MW | 32.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.46 MW | 2.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 11.81 MW | 10.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939051 | AE1-134 1 | Adder | 1.22 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939061 | AE1-134 2 | Adder | 1.22 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 4.43 MW | 3.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 27.2 MW | 23.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 940501 | AE2-035 C | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 940502 | AE2-035 E | Adder | 3.0 MW | 2.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 941131 | AE2-107 C | Adder | 5.24 MW | 4.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 941132 | AE2-107 E | Adder | 3.49 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946151 | AF1-280 C O1 | Adder | 13.85 MW | 11.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946152 | AF1-280 E O1 | Adder | 6.37 MW | 5.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946161 | AF1-281 C O1 | Adder | 0.3 MW | 0.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946162 | AF1-281 E O1 | Adder | 1.72 MW | 1.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946321 | AF1-296 C O1 | Adder | 3.56 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946322 | AF1-296 E O1 | Adder | 16.69 MW | 14.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946501 | AF1-314 C | Adder | 3.84 MW | 3.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946502 | AF1-314 E | Adder | 18.05 MW | 15.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946541 | AF1-318 C O1 | Adder | 4.53 MW | 3.85 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946661 | AF1-330 C | Adder | 1.78 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946662 | AF1-330 E | Adder | 0.39 MW | 0.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957331 | AF2-027 C | Adder | 2.37 MW | 2.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957332 | AF2-027 E | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957401 | AF2-034 C | 50/50 | 2.25 MW | 2.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957402 | AF2-034 E | 50/50 | 1.91 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957471 | AF2-041 C | Adder | 18.81 MW | 15.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957472 | AF2-041 E | Adder | 9.4 MW | 7.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957762 | AF2-070 E | Adder | 1.36 MW | 1.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958341 | AF2-128 C O1 | Adder | 1.19 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958342 | AF2-128 E O1 | Adder | 5.55 MW | 4.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 990901 | L-005 E | Adder | 11.75 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.77 MW | 4.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934111 | AD2-000 2 | Adder | 8.38 MW | 7.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290108 | LEEDK;1U E | Adder | 19.41 MW | 16.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958023 | AF2-096 BAT | Adder | 7.3 MW | 6.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 953151 | J831 | External Queue | 3.03 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 953491 | J947 | External Queue | 15.9 MW | 15.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954141 | J878 | External Queue | 15.94 MW | 15.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954981 | J974 C | External Queue | 2.94 MW | 2.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954982 | J974 E | External Queue | 15.91 MW | 15.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 991321 | J1778 | External Queue | 7.97 MW | 7.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.42 MW | 0.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.4 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 57.54 MW | 57.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.5 MW | 16.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.33 MW | 1.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.51 MW | 3.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.27 MW | 0.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 11.83 MW | 11.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.72 MW | 0.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.53 MW | 8.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.37 MW | 1.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.5 MW | 3.5 MW |
| Details for PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961651 | AG1-005 C O1 | Adder | 10.22 MW | 8.69 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961652 | AG1-005 E O1 | Adder | 6.81 MW | 5.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 21.43 MW | 21.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 14.29 MW | 14.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962701 | AG1-119 C | Adder | 16.49 MW | 14.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962702 | AG1-119 E | Adder | 10.99 MW | 9.34 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962711 | AG1-120 C O1 | 50/50 | 7.6 MW | 7.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962712 | AG1-120 E O1 | 50/50 | 5.07 MW | 5.07 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962721 | AG1-121 C O1 | Adder | 3.55 MW | 3.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962722 | AG1-121 E O1 | Adder | 16.61 MW | 14.12 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.7 MW | 6.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.46 MW | 4.46 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 17.36 MW | 14.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.5 MW | 2.97 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.03 MW | 1.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 11.0 MW | 9.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 7.33 MW | 6.23 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965661 | AG1-434 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965671 | AG1-435 C O1 | Adder | 2.38 MW | 2.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965672 | AG1-435 E O1 | Adder | 11.13 MW | 9.46 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 11.24 MW | 9.55 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 7.49 MW | 6.37 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966091 | AG1-478 C | Adder | 1.03 MW | 0.87 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.26 MW | 0.22 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 272364 | ESS H440N ;R | 50/50 | 2.39 MW | 2.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 290051 | GSG-6; E | 50/50 | 9.48 MW | 9.48 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.13 MW | 0.13 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 5.08 MW | 5.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 2.0 MW | 1.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.36 MW | 11.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 920272 | AA2-123 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 4.04 MW | 3.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933911 | AD1-013 C | 50/50 | 1.68 MW | 1.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933912 | AD1-013 E | 50/50 | 2.68 MW | 2.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933932 | AD1-016 E | Adder | 1.11 MW | 0.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934051 | AD1-031 C O1 | Adder | 1.75 MW | 1.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934052 | AD1-031 E O1 | Adder | 2.86 MW | 2.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.02 MW | 0.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.5 MW | 0.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 5.89 MW | 5.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.71 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.29 MW | 2.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.17 MW | 9.17 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937312 | AD2-172 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 942991 | AE2-321 C | Adder | 6.02 MW | 5.11 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 942992 | AE2-321 E | Adder | 2.96 MW | 2.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 16.01 MW | 16.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 7.86 MW | 7.86 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 10.65 MW | 10.65 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 5.27 MW | 5.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943801 | AF1-048 C | Adder | 2.81 MW | 2.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943802 | AF1-048 E | Adder | 1.87 MW | 1.59 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 16.79 MW | 14.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958911 | AF2-182 C | Adder | 15.46 MW | 13.14 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958912 | AF2-182 E | Adder | 10.3 MW | 8.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.75 MW | 2.33 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958922 | AF2-183 E | Adder | 4.12 MW | 3.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 6.16 MW | 6.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 4.49 MW | 3.82 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 12.9 MW | 10.96 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.72 MW | 6.72 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960581 | AF2-349 C | Adder | 15.91 MW | 13.53 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960582 | AF2-349 E | Adder | 10.61 MW | 9.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960721 | AF2-363 C O1 | 50/50 | 5.2 MW | 5.2 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960722 | AF2-363 E O1 | 50/50 | 3.47 MW | 3.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.68 MW | 6.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.45 MW | 4.45 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.03 MW | 2.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 14.17 MW | 12.04 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.16 MW | 4.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.44 MW | 2.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274660 | LASCO STA;1U | 50/50 | 30.7 MW | 30.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274661 | LASCO STA;2U | 50/50 | 30.84 MW | 30.84 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 0.63 MW | 0.63 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 0.4 MW | 0.4 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 0.23 MW | 0.23 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276170 | Z1-108 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276173 | Z2-081 | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 2.91 MW | 2.91 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293061 | N-015 E | 50/50 | 16.25 MW | 16.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.35 MW | 2.85 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.69 MW | 3.14 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293715 | O-029 E | Adder | 7.06 MW | 6.0 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293716 | O-029 E | Adder | 3.87 MW | 3.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293717 | O-029 E | Adder | 3.56 MW | 3.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293771 | O-035 E | Adder | 3.96 MW | 3.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294392 | P-010 E | 50/50 | 20.63 MW | 20.63 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294401 | BSHIL;1U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294410 | BSHIL;2U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294763 | P-046 E | Adder | 6.99 MW | 5.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915011 | Y3-013 1 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915021 | Y3-013 2 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915031 | Y3-013 3 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 916211 | Z1-072 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 916221 | Z1-073 E | 50/50 | 4.92 MW | 4.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 925581 | AC1-033 C | Adder | 0.86 MW | 0.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 925582 | AC1-033 E | Adder | 5.79 MW | 4.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 27.37 MW | 23.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 21.76 MW | 18.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 38.35 MW | 32.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.97 MW | 2.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 10.12 MW | 8.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.04 MW | 0.88 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.04 MW | 0.88 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 5.12 MW | 4.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 4.72 MW | 4.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940502 | AE2-035 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 6.25 MW | 6.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 4.16 MW | 4.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 5.9 MW | 5.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 3.94 MW | 3.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.76 MW | 10.0 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.41 MW | 4.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.26 MW | 0.22 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.46 MW | 1.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.8 MW | 2.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 13.13 MW | 11.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946501 | AF1-314 C | Adder | 3.25 MW | 2.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946502 | AF1-314 E | Adder | 15.28 MW | 12.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 3.59 MW | 3.05 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946661 | AF1-330 C | Adder | 1.47 MW | 1.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946671 | AF1-331 | 50/50 | 2.18 MW | 2.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957331 | AF2-027 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957332 | AF2-027 E | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957401 | AF2-034 C | Adder | 0.7 MW | 0.59 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957402 | AF2-034 E | Adder | 0.6 MW | 0.51 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 18.47 MW | 18.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 9.24 MW | 9.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957752 | AF2-069 E | Adder | 0.47 MW | 0.4 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957762 | AF2-070 E | Adder | 1.01 MW | 0.85 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958021 | AF2-096 C | Adder | 21.16 MW | 17.99 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958022 | AF2-096 E | Adder | 9.96 MW | 8.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 0.95 MW | 0.81 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 4.46 MW | 3.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934111 | AD2-000 2 | Adder | 3.1 MW | 2.64 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.79 MW | 0.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 23.13 MW | 23.13 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 582.02 MW | 582.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.39 MW | 1.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.08 MW | 0.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.26 MW | 47.26 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.6 MW | 9.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.09 MW | 0.09 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.26 MW | 1.26 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.06 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.29 MW | 8.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.06 MW | 8.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.46 MW | 2.46 MW |
| Details for PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961651 | AG1-005 C O1 | Adder | 10.22 MW | 8.69 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961652 | AG1-005 E O1 | Adder | 6.81 MW | 5.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 21.43 MW | 21.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 14.29 MW | 14.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962701 | AG1-119 C | Adder | 16.49 MW | 14.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962702 | AG1-119 E | Adder | 10.99 MW | 9.34 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962711 | AG1-120 C O1 | 50/50 | 7.6 MW | 7.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962712 | AG1-120 E O1 | 50/50 | 5.07 MW | 5.07 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962721 | AG1-121 C O1 | Adder | 3.55 MW | 3.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962722 | AG1-121 E O1 | Adder | 16.61 MW | 14.12 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.7 MW | 6.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.46 MW | 4.46 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 17.36 MW | 14.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.5 MW | 2.97 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.03 MW | 1.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 11.0 MW | 9.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 7.33 MW | 6.23 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965661 | AG1-434 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965671 | AG1-435 C O1 | Adder | 2.38 MW | 2.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965672 | AG1-435 E O1 | Adder | 11.13 MW | 9.46 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 11.24 MW | 9.55 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 7.49 MW | 6.37 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966091 | AG1-478 C | Adder | 1.03 MW | 0.87 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.26 MW | 0.22 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 272364 | ESS H440N ;R | 50/50 | 2.39 MW | 2.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 290051 | GSG-6; E | 50/50 | 9.48 MW | 9.48 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.13 MW | 0.13 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 5.08 MW | 5.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 2.0 MW | 1.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.36 MW | 11.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 920272 | AA2-123 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 4.04 MW | 3.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933911 | AD1-013 C | 50/50 | 1.68 MW | 1.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933912 | AD1-013 E | 50/50 | 2.68 MW | 2.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933932 | AD1-016 E | Adder | 1.11 MW | 0.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934051 | AD1-031 C O1 | Adder | 1.75 MW | 1.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934052 | AD1-031 E O1 | Adder | 2.86 MW | 2.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.02 MW | 0.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.5 MW | 0.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 5.89 MW | 5.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.71 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.29 MW | 2.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.17 MW | 9.17 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937312 | AD2-172 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 942991 | AE2-321 C | Adder | 6.02 MW | 5.11 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 942992 | AE2-321 E | Adder | 2.96 MW | 2.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 16.01 MW | 16.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 7.86 MW | 7.86 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 10.65 MW | 10.65 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 5.27 MW | 5.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943801 | AF1-048 C | Adder | 2.81 MW | 2.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943802 | AF1-048 E | Adder | 1.87 MW | 1.59 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 16.79 MW | 14.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958911 | AF2-182 C | Adder | 15.46 MW | 13.14 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958912 | AF2-182 E | Adder | 10.3 MW | 8.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.75 MW | 2.33 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958922 | AF2-183 E | Adder | 4.12 MW | 3.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 6.16 MW | 6.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 4.49 MW | 3.82 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 12.9 MW | 10.96 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.72 MW | 6.72 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960581 | AF2-349 C | Adder | 15.91 MW | 13.53 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960582 | AF2-349 E | Adder | 10.61 MW | 9.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960721 | AF2-363 C O1 | 50/50 | 5.2 MW | 5.2 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960722 | AF2-363 E O1 | 50/50 | 3.47 MW | 3.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.68 MW | 6.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.45 MW | 4.45 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.03 MW | 2.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 14.17 MW | 12.04 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.16 MW | 4.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.44 MW | 2.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274660 | LASCO STA;1U | 50/50 | 30.7 MW | 30.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274661 | LASCO STA;2U | 50/50 | 30.84 MW | 30.84 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 0.63 MW | 0.63 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 0.4 MW | 0.4 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 0.23 MW | 0.23 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276170 | Z1-108 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276173 | Z2-081 | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 2.91 MW | 2.91 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293061 | N-015 E | 50/50 | 16.25 MW | 16.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.35 MW | 2.85 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.69 MW | 3.14 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293715 | O-029 E | Adder | 7.06 MW | 6.0 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293716 | O-029 E | Adder | 3.87 MW | 3.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293717 | O-029 E | Adder | 3.56 MW | 3.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293771 | O-035 E | Adder | 3.96 MW | 3.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294392 | P-010 E | 50/50 | 20.63 MW | 20.63 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294401 | BSHIL;1U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294410 | BSHIL;2U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294763 | P-046 E | Adder | 6.99 MW | 5.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915011 | Y3-013 1 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915021 | Y3-013 2 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915031 | Y3-013 3 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 916211 | Z1-072 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 916221 | Z1-073 E | 50/50 | 4.92 MW | 4.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 925581 | AC1-033 C | Adder | 0.86 MW | 0.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 925582 | AC1-033 E | Adder | 5.79 MW | 4.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 27.37 MW | 23.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 21.76 MW | 18.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 38.35 MW | 32.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.97 MW | 2.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 10.12 MW | 8.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.04 MW | 0.88 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.04 MW | 0.88 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 5.12 MW | 4.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 4.72 MW | 4.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940502 | AE2-035 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 6.25 MW | 6.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 4.16 MW | 4.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 5.9 MW | 5.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 3.94 MW | 3.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.76 MW | 10.0 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.41 MW | 4.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.26 MW | 0.22 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.46 MW | 1.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.8 MW | 2.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 13.13 MW | 11.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946501 | AF1-314 C | Adder | 3.25 MW | 2.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946502 | AF1-314 E | Adder | 15.28 MW | 12.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 3.59 MW | 3.05 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946661 | AF1-330 C | Adder | 1.47 MW | 1.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946671 | AF1-331 | 50/50 | 2.18 MW | 2.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957331 | AF2-027 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957332 | AF2-027 E | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957401 | AF2-034 C | Adder | 0.7 MW | 0.59 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957402 | AF2-034 E | Adder | 0.6 MW | 0.51 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 18.47 MW | 18.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 9.24 MW | 9.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957752 | AF2-069 E | Adder | 0.47 MW | 0.4 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957762 | AF2-070 E | Adder | 1.01 MW | 0.85 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958021 | AF2-096 C | Adder | 21.16 MW | 17.99 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958022 | AF2-096 E | Adder | 9.96 MW | 8.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 0.95 MW | 0.81 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 4.46 MW | 3.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934111 | AD2-000 2 | Adder | 3.1 MW | 2.64 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.79 MW | 0.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 23.13 MW | 23.13 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 582.02 MW | 582.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.39 MW | 1.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.08 MW | 0.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.26 MW | 47.26 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.6 MW | 9.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.09 MW | 0.09 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.26 MW | 1.26 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.06 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.29 MW | 8.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.06 MW | 8.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.46 MW | 2.46 MW |
| Details for PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961651 | AG1-005 C O1 | Adder | 9.9 MW | 8.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961652 | AG1-005 E O1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962691 | AG1-118 C O1 | Adder | 14.58 MW | 12.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962692 | AG1-118 E O1 | Adder | 9.72 MW | 8.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962701 | AG1-119 C | Adder | 15.25 MW | 12.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962702 | AG1-119 E | Adder | 10.17 MW | 8.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962711 | AG1-120 C O1 | Adder | 5.69 MW | 4.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962712 | AG1-120 E O1 | Adder | 3.79 MW | 3.22 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962721 | AG1-121 C O1 | Adder | 3.38 MW | 2.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962722 | AG1-121 E O1 | Adder | 15.82 MW | 13.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962781 | AG1-127 C | Adder | 4.6 MW | 3.91 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962782 | AG1-127 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966821 | AG1-553 C O1 | Adder | 14.68 MW | 12.48 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966822 | AG1-553 E O1 | Adder | 2.96 MW | 2.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965061 | AG1-371 | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965081 | AG1-373 | Adder | 0.74 MW | 0.63 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965551 | AG1-423 C O1 | Adder | 10.18 MW | 8.65 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965552 | AG1-423 E O1 | Adder | 6.78 MW | 5.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965661 | AG1-434 C O1 | Adder | 2.56 MW | 2.18 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965662 | AG1-434 E O1 | Adder | 12.01 MW | 10.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965671 | AG1-435 C O1 | Adder | 2.24 MW | 1.91 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965672 | AG1-435 E O1 | Adder | 10.49 MW | 8.92 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965931 | AG1-462 C O1 | Adder | 9.5 MW | 8.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965932 | AG1-462 E O1 | Adder | 6.33 MW | 5.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966091 | AG1-478 C | Adder | 0.98 MW | 0.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966092 | AG1-478 E | Adder | 0.25 MW | 0.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966441 | AG1-513 C | Adder | 0.43 MW | 0.36 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966442 | AG1-513 E | Adder | 0.64 MW | 0.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 272364 | ESS H440N ;R | Adder | 1.7 MW | 1.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290051 | GSG-6; E | Adder | 6.76 MW | 5.74 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295109 | WESTBROOK E | Adder | 3.62 MW | 3.08 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295111 | SUBLETTE E | Adder | 1.62 MW | 1.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 919581 | AA2-030 C | Adder | 10.91 MW | 9.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 920272 | AA2-123 E | Adder | 1.66 MW | 1.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926311 | AC1-109 1 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926321 | AC1-109 2 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926822 | AC1-168 E O1 | Adder | 5.34 MW | 4.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 927202 | AC1-214 E O1 | Adder | 3.81 MW | 3.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933911 | AD1-013 C | Adder | 1.19 MW | 1.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933912 | AD1-013 E | Adder | 1.9 MW | 1.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933931 | AD1-016 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933932 | AD1-016 E | Adder | 1.02 MW | 0.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934051 | AD1-031 C O1 | Adder | 1.62 MW | 1.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934052 | AD1-031 E O1 | Adder | 2.65 MW | 2.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934432 | AD1-067 E | Adder | 0.36 MW | 0.3 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936371 | AD2-047 C O1 | Adder | 2.19 MW | 1.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936372 | AD2-047 E O1 | Adder | 10.69 MW | 9.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936461 | AD2-060 | Adder | 1.29 MW | 1.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936511 | AD2-066 C O1 | Adder | 4.54 MW | 3.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936512 | AD2-066 E O1 | Adder | 3.02 MW | 2.57 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937001 | AD2-134 C | Adder | 1.64 MW | 1.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937002 | AD2-134 E | Adder | 6.53 MW | 5.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937311 | AD2-172 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937312 | AD2-172 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942991 | AE2-321 C | Adder | 5.54 MW | 4.71 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942992 | AE2-321 E | Adder | 2.73 MW | 2.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943121 | AE2-341 C | Adder | 8.38 MW | 7.12 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943122 | AE2-341 E | Adder | 4.11 MW | 3.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943591 | AF1-030 C O1 | Adder | 5.57 MW | 4.74 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943592 | AF1-030 E O1 | Adder | 2.76 MW | 2.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943802 | AF1-048 E | Adder | 1.73 MW | 1.47 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946542 | AF1-318 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958911 | AF2-182 C | Adder | 12.94 MW | 11.0 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958912 | AF2-182 E | Adder | 8.63 MW | 7.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958921 | AF2-183 C | Adder | 2.3 MW | 1.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958922 | AF2-183 E | Adder | 3.45 MW | 2.93 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959081 | AF2-199 C | Adder | 4.44 MW | 3.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959082 | AF2-199 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959091 | AF2-200 C O1 | Adder | 8.88 MW | 7.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959092 | AF2-200 E O1 | Adder | 5.92 MW | 5.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959101 | AF2-201 C O1 | Adder | 3.9 MW | 3.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959102 | AF2-201 E O1 | Adder | 11.2 MW | 9.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960381 | AF2-329 | Adder | 3.52 MW | 2.99 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960581 | AF2-349 C | Adder | 14.58 MW | 12.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960582 | AF2-349 E | Adder | 9.72 MW | 8.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960591 | AF2-350 C O1 | Adder | 3.86 MW | 3.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960592 | AF2-350 E O1 | Adder | 2.58 MW | 2.19 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960601 | AF2-351 C O1 | Adder | 0.52 MW | 0.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960602 | AF2-351 E O1 | Adder | 0.77 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960721 | AF2-363 C O1 | Adder | 3.9 MW | 3.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960722 | AF2-363 E O1 | Adder | 2.6 MW | 2.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960751 | AF2-366 C | Adder | 4.59 MW | 3.9 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960752 | AF2-366 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961011 | AF2-392 C O1 | Adder | 2.47 MW | 2.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961012 | AF2-392 E O1 | Adder | 11.57 MW | 9.84 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961021 | AF2-393 O1 | Adder | 4.21 MW | 3.58 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961031 | AF2-394 O1 | Adder | 2.81 MW | 2.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274660 | LASCO STA;1U | 50/50 | 32.88 MW | 32.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274661 | LASCO STA;2U | 50/50 | 33.02 MW | 33.02 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274737 | AURORA EC;1P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274739 | AURORA EC;2P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274741 | AURORA EC;5P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274742 | AURORA EC;6P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274746 | AURORA EC;0P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274847 | GR RIDGE ;BU | 50/50 | 0.67 MW | 0.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274859 | EASYR;U1 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274860 | EASYR;U2 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274871 | GR RIDGE ;2U | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 275149 | KELLYCK ;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276170 | Z1-108 E | Adder | 1.71 MW | 1.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276173 | Z2-081 | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276591 | L-013 2 | Adder | 2.73 MW | 2.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293061 | N-015 E | 50/50 | 17.26 MW | 17.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293516 | O-009 E1 | Adder | 5.55 MW | 4.71 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293517 | O-009 E2 | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293518 | O-009 E3 | Adder | 3.1 MW | 2.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293715 | O-029 E | Adder | 5.93 MW | 5.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293716 | O-029 E | Adder | 3.25 MW | 2.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293717 | O-029 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293771 | O-035 E | Adder | 3.73 MW | 3.17 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293799 | PILOT HIL;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294392 | P-010 E | 50/50 | 21.92 MW | 21.92 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294401 | BSHIL;1U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294410 | BSHIL;2U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294763 | P-046 E | Adder | 6.07 MW | 5.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915011 | Y3-013 1 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915021 | Y3-013 2 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915031 | Y3-013 3 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916211 | Z1-072 E | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916221 | Z1-073 E | Adder | 3.51 MW | 2.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925581 | AC1-033 C | Adder | 0.8 MW | 0.68 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925582 | AC1-033 E | Adder | 5.37 MW | 4.56 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930482 | AB1-089 CT | Adder | 24.74 MW | 21.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930483 | AB1-089 ST | Adder | 19.67 MW | 16.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930771 | AB1-122 CT2 | Adder | 6.53 MW | 5.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933411 | AC2-154 C | Adder | 1.22 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933412 | AC2-154 E | Adder | 2.0 MW | 1.7 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938861 | AE1-114 C O1 | Adder | 2.51 MW | 2.13 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938862 | AE1-114 E O1 | Adder | 8.56 MW | 7.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939051 | AE1-134 1 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939061 | AE1-134 2 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939351 | AE1-166 C O1 | Adder | 5.43 MW | 4.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939352 | AE1-166 E O1 | Adder | 5.02 MW | 4.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940501 | AE2-035 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940502 | AE2-035 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940752 | AE2-062 E | Adder | 0.06 MW | 0.05 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941131 | AE2-107 C | Adder | 4.28 MW | 3.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941132 | AE2-107 E | Adder | 2.85 MW | 2.43 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941551 | AE2-152 C O1 | Adder | 6.27 MW | 5.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941552 | AE2-152 E O1 | Adder | 4.18 MW | 3.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946151 | AF1-280 C O1 | Adder | 9.85 MW | 8.37 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946152 | AF1-280 E O1 | Adder | 4.53 MW | 3.85 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946321 | AF1-296 C O1 | Adder | 2.37 MW | 2.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946322 | AF1-296 E O1 | Adder | 11.08 MW | 9.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946501 | AF1-314 C | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946502 | AF1-314 E | Adder | 13.26 MW | 11.27 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946541 | AF1-318 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946661 | AF1-330 C | Adder | 1.36 MW | 1.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946662 | AF1-330 E | Adder | 0.3 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946671 | AF1-331 | Adder | 1.55 MW | 1.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957331 | AF2-027 C | Adder | 1.55 MW | 1.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957332 | AF2-027 E | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957401 | AF2-034 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957402 | AF2-034 E | Adder | 0.53 MW | 0.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957471 | AF2-041 C | Adder | 13.31 MW | 11.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957472 | AF2-041 E | Adder | 6.66 MW | 5.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957751 | AF2-069 C | Adder | 0.14 MW | 0.12 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957752 | AF2-069 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957761 | AF2-070 C | Adder | 0.2 MW | 0.17 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957762 | AF2-070 E | Adder | 0.95 MW | 0.81 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958011 | AF2-095 C O1 | Adder | 8.76 MW | 7.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958012 | AF2-095 E O1 | Adder | 4.12 MW | 3.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958021 | AF2-096 C | Adder | 22.39 MW | 19.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958022 | AF2-096 E | Adder | 10.54 MW | 8.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958341 | AF2-128 C O1 | Adder | 0.92 MW | 0.79 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958342 | AF2-128 E O1 | Adder | 4.32 MW | 3.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 990901 | L-005 E | Adder | 7.24 MW | 6.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290108 | LEEDK;1U E | Adder | 15.86 MW | 13.48 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 945351 | AF1-200 FTIR | 50/50 | 627.1 MW | 627.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.34 MW | 1.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.67 MW | 42.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.83 MW | 8.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.23 MW | 1.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.83 MW | 1.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.38 MW | 7.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.66 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.88 MW | 7.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.32 MW | 2.32 MW |
| Details for PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961651 | AG1-005 C O1 | Adder | 9.9 MW | 8.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961652 | AG1-005 E O1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962691 | AG1-118 C O1 | Adder | 14.58 MW | 12.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962692 | AG1-118 E O1 | Adder | 9.72 MW | 8.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962701 | AG1-119 C | Adder | 15.25 MW | 12.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962702 | AG1-119 E | Adder | 10.17 MW | 8.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962711 | AG1-120 C O1 | Adder | 5.69 MW | 4.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962712 | AG1-120 E O1 | Adder | 3.79 MW | 3.22 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962721 | AG1-121 C O1 | Adder | 3.38 MW | 2.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962722 | AG1-121 E O1 | Adder | 15.82 MW | 13.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962781 | AG1-127 C | Adder | 4.6 MW | 3.91 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962782 | AG1-127 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966821 | AG1-553 C O1 | Adder | 14.68 MW | 12.48 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966822 | AG1-553 E O1 | Adder | 2.96 MW | 2.51 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965061 | AG1-371 | Adder | 2.22 MW | 1.89 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965081 | AG1-373 | Adder | 0.74 MW | 0.63 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965551 | AG1-423 C O1 | Adder | 10.18 MW | 8.65 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965552 | AG1-423 E O1 | Adder | 6.78 MW | 5.77 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965661 | AG1-434 C O1 | Adder | 2.56 MW | 2.18 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965662 | AG1-434 E O1 | Adder | 12.01 MW | 10.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965671 | AG1-435 C O1 | Adder | 2.24 MW | 1.91 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965672 | AG1-435 E O1 | Adder | 10.49 MW | 8.92 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965931 | AG1-462 C O1 | Adder | 9.5 MW | 8.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965932 | AG1-462 E O1 | Adder | 6.33 MW | 5.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966091 | AG1-478 C | Adder | 0.98 MW | 0.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966092 | AG1-478 E | Adder | 0.25 MW | 0.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966441 | AG1-513 C | Adder | 0.43 MW | 0.36 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966442 | AG1-513 E | Adder | 0.64 MW | 0.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 272364 | ESS H440N ;R | Adder | 1.7 MW | 1.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 290051 | GSG-6; E | Adder | 6.76 MW | 5.74 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 295109 | WESTBROOK E | Adder | 3.62 MW | 3.08 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 295111 | SUBLETTE E | Adder | 1.62 MW | 1.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 919581 | AA2-030 C | Adder | 10.91 MW | 9.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 920272 | AA2-123 E | Adder | 1.66 MW | 1.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926311 | AC1-109 1 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926321 | AC1-109 2 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926822 | AC1-168 E O1 | Adder | 5.34 MW | 4.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 927202 | AC1-214 E O1 | Adder | 3.81 MW | 3.23 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933911 | AD1-013 C | Adder | 1.19 MW | 1.01 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933912 | AD1-013 E | Adder | 1.9 MW | 1.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933931 | AD1-016 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933932 | AD1-016 E | Adder | 1.02 MW | 0.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934051 | AD1-031 C O1 | Adder | 1.62 MW | 1.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934052 | AD1-031 E O1 | Adder | 2.65 MW | 2.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934432 | AD1-067 E | Adder | 0.36 MW | 0.3 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936371 | AD2-047 C O1 | Adder | 2.19 MW | 1.86 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936372 | AD2-047 E O1 | Adder | 10.69 MW | 9.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936461 | AD2-060 | Adder | 1.29 MW | 1.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936511 | AD2-066 C O1 | Adder | 4.54 MW | 3.86 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936512 | AD2-066 E O1 | Adder | 3.02 MW | 2.57 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937001 | AD2-134 C | Adder | 1.64 MW | 1.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937002 | AD2-134 E | Adder | 6.53 MW | 5.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937311 | AD2-172 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937312 | AD2-172 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 942991 | AE2-321 C | Adder | 5.54 MW | 4.71 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 942992 | AE2-321 E | Adder | 2.73 MW | 2.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943121 | AE2-341 C | Adder | 8.38 MW | 7.12 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943122 | AE2-341 E | Adder | 4.11 MW | 3.5 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943591 | AF1-030 C O1 | Adder | 5.57 MW | 4.74 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943592 | AF1-030 E O1 | Adder | 2.76 MW | 2.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943802 | AF1-048 E | Adder | 1.73 MW | 1.47 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946542 | AF1-318 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958911 | AF2-182 C | Adder | 12.94 MW | 11.0 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958912 | AF2-182 E | Adder | 8.63 MW | 7.33 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958921 | AF2-183 C | Adder | 2.3 MW | 1.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958922 | AF2-183 E | Adder | 3.45 MW | 2.93 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959081 | AF2-199 C | Adder | 4.44 MW | 3.77 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959082 | AF2-199 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959091 | AF2-200 C O1 | Adder | 8.88 MW | 7.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959092 | AF2-200 E O1 | Adder | 5.92 MW | 5.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959101 | AF2-201 C O1 | Adder | 3.9 MW | 3.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959102 | AF2-201 E O1 | Adder | 11.2 MW | 9.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960381 | AF2-329 | Adder | 3.52 MW | 2.99 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960581 | AF2-349 C | Adder | 14.58 MW | 12.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960582 | AF2-349 E | Adder | 9.72 MW | 8.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960591 | AF2-350 C O1 | Adder | 3.86 MW | 3.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960592 | AF2-350 E O1 | Adder | 2.58 MW | 2.19 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960601 | AF2-351 C O1 | Adder | 0.52 MW | 0.44 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960602 | AF2-351 E O1 | Adder | 0.77 MW | 0.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960721 | AF2-363 C O1 | Adder | 3.9 MW | 3.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960722 | AF2-363 E O1 | Adder | 2.6 MW | 2.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960751 | AF2-366 C | Adder | 4.59 MW | 3.9 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960752 | AF2-366 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961011 | AF2-392 C O1 | Adder | 2.47 MW | 2.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961012 | AF2-392 E O1 | Adder | 11.57 MW | 9.84 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961021 | AF2-393 O1 | Adder | 4.21 MW | 3.58 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961031 | AF2-394 O1 | Adder | 2.81 MW | 2.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274660 | LASCO STA;1U | 50/50 | 32.88 MW | 32.88 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274661 | LASCO STA;2U | 50/50 | 33.02 MW | 33.02 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274737 | AURORA EC;1P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274739 | AURORA EC;2P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274741 | AURORA EC;5P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274742 | AURORA EC;6P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274746 | AURORA EC;0P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274847 | GR RIDGE ;BU | 50/50 | 0.67 MW | 0.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274859 | EASYR;U1 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274860 | EASYR;U2 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274871 | GR RIDGE ;2U | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 275149 | KELLYCK ;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276170 | Z1-108 E | Adder | 1.71 MW | 1.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276173 | Z2-081 | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276591 | L-013 2 | Adder | 2.73 MW | 2.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293061 | N-015 E | 50/50 | 17.26 MW | 17.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293516 | O-009 E1 | Adder | 5.55 MW | 4.71 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293517 | O-009 E2 | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293518 | O-009 E3 | Adder | 3.1 MW | 2.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293715 | O-029 E | Adder | 5.93 MW | 5.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293716 | O-029 E | Adder | 3.25 MW | 2.76 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293717 | O-029 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293771 | O-035 E | Adder | 3.73 MW | 3.17 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293799 | PILOT HIL;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294392 | P-010 E | 50/50 | 21.92 MW | 21.92 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294401 | BSHIL;1U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294410 | BSHIL;2U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294763 | P-046 E | Adder | 6.07 MW | 5.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915011 | Y3-013 1 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915021 | Y3-013 2 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915031 | Y3-013 3 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 916211 | Z1-072 E | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 916221 | Z1-073 E | Adder | 3.51 MW | 2.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 925581 | AC1-033 C | Adder | 0.8 MW | 0.68 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 925582 | AC1-033 E | Adder | 5.37 MW | 4.56 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930482 | AB1-089 CT | Adder | 24.74 MW | 21.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930483 | AB1-089 ST | Adder | 19.67 MW | 16.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930771 | AB1-122 CT2 | Adder | 6.53 MW | 5.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933411 | AC2-154 C | Adder | 1.22 MW | 1.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933412 | AC2-154 E | Adder | 2.0 MW | 1.7 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 938861 | AE1-114 C O1 | Adder | 2.51 MW | 2.13 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 938862 | AE1-114 E O1 | Adder | 8.56 MW | 7.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939051 | AE1-134 1 | Adder | 0.85 MW | 0.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939061 | AE1-134 2 | Adder | 0.85 MW | 0.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939351 | AE1-166 C O1 | Adder | 5.43 MW | 4.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939352 | AE1-166 E O1 | Adder | 5.02 MW | 4.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940501 | AE2-035 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940502 | AE2-035 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940752 | AE2-062 E | Adder | 0.06 MW | 0.05 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941131 | AE2-107 C | Adder | 4.28 MW | 3.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941132 | AE2-107 E | Adder | 2.85 MW | 2.43 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941551 | AE2-152 C O1 | Adder | 6.27 MW | 5.33 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941552 | AE2-152 E O1 | Adder | 4.18 MW | 3.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946151 | AF1-280 C O1 | Adder | 9.85 MW | 8.37 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946152 | AF1-280 E O1 | Adder | 4.53 MW | 3.85 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946321 | AF1-296 C O1 | Adder | 2.37 MW | 2.01 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946322 | AF1-296 E O1 | Adder | 11.08 MW | 9.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946501 | AF1-314 C | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946502 | AF1-314 E | Adder | 13.26 MW | 11.27 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946541 | AF1-318 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946661 | AF1-330 C | Adder | 1.36 MW | 1.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946662 | AF1-330 E | Adder | 0.3 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946671 | AF1-331 | Adder | 1.55 MW | 1.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957331 | AF2-027 C | Adder | 1.55 MW | 1.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957332 | AF2-027 E | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957401 | AF2-034 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957402 | AF2-034 E | Adder | 0.53 MW | 0.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957471 | AF2-041 C | Adder | 13.31 MW | 11.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957472 | AF2-041 E | Adder | 6.66 MW | 5.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957751 | AF2-069 C | Adder | 0.14 MW | 0.12 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957752 | AF2-069 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957761 | AF2-070 C | Adder | 0.2 MW | 0.17 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957762 | AF2-070 E | Adder | 0.95 MW | 0.81 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958011 | AF2-095 C O1 | Adder | 8.76 MW | 7.44 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958012 | AF2-095 E O1 | Adder | 4.12 MW | 3.5 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958021 | AF2-096 C | Adder | 22.39 MW | 19.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958022 | AF2-096 E | Adder | 10.54 MW | 8.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958341 | AF2-128 C O1 | Adder | 0.92 MW | 0.79 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958342 | AF2-128 E O1 | Adder | 4.32 MW | 3.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 990901 | L-005 E | Adder | 7.24 MW | 6.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 290108 | LEEDK;1U E | Adder | 15.86 MW | 13.48 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 945351 | AF1-200 FTIR | 50/50 | 627.1 MW | 627.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.34 MW | 1.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.67 MW | 42.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.83 MW | 8.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.23 MW | 1.23 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.83 MW | 1.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.38 MW | 7.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.66 MW | 0.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.88 MW | 7.88 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.32 MW | 2.32 MW |
| Details for AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962012 | AG1-044 E | 50/50 | 0.16 MW | 0.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962721 | AG1-121 C O1 | Adder | 4.43 MW | 3.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962722 | AG1-121 E O1 | Adder | 20.72 MW | 17.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966821 | AG1-553 C O1 | 50/50 | 56.08 MW | 56.08 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966822 | AG1-553 E O1 | 50/50 | 11.29 MW | 11.29 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965661 | AG1-434 C O1 | 50/50 | 18.61 MW | 18.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965662 | AG1-434 E O1 | 50/50 | 87.14 MW | 87.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965671 | AG1-435 C O1 | Adder | 3.34 MW | 2.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965672 | AG1-435 E O1 | Adder | 15.63 MW | 13.29 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965931 | AG1-462 C O1 | 50/50 | 36.3 MW | 36.3 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965932 | AG1-462 E O1 | 50/50 | 24.2 MW | 24.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 272364 | ESS H440N ;R | Adder | 2.07 MW | 1.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 290051 | GSG-6; E | Adder | 8.51 MW | 7.23 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.55 MW | 3.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295110 | SUBLETTE C | 50/50 | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295111 | SUBLETTE E | 50/50 | 5.31 MW | 5.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919221 | AA1-146 | 50/50 | 8.98 MW | 8.98 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919581 | AA2-030 C | 50/50 | 52.74 MW | 52.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.48 MW | 4.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933911 | AD1-013 C | Adder | 1.43 MW | 1.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934051 | AD1-031 C O1 | 50/50 | 2.92 MW | 2.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934052 | AD1-031 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937001 | AD2-134 C | Adder | 2.06 MW | 1.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937002 | AD2-134 E | Adder | 8.22 MW | 6.99 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937311 | AD2-172 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937312 | AD2-172 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958911 | AF2-182 C | 50/50 | 60.46 MW | 60.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958912 | AF2-182 E | 50/50 | 40.3 MW | 40.3 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958921 | AF2-183 C | 50/50 | 10.75 MW | 10.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958922 | AF2-183 E | 50/50 | 16.12 MW | 16.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959101 | AF2-201 C O1 | Adder | 4.19 MW | 3.56 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 12.04 MW | 10.23 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961011 | AF2-392 C O1 | 50/50 | 9.47 MW | 9.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961012 | AF2-392 E O1 | 50/50 | 44.36 MW | 44.36 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961021 | AF2-393 O1 | 50/50 | 16.15 MW | 16.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961031 | AF2-394 O1 | 50/50 | 10.77 MW | 10.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274662 | QUAD CITI;1U | 50/50 | 36.61 MW | 36.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274663 | QUAD CITI;2U | 50/50 | 36.71 MW | 36.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274699 | CORDOVA ;1C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274700 | CORDOVA ;2C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274701 | CORDOVA ;1S | 50/50 | 7.25 MW | 7.25 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274715 | NELSON EC;1C | 50/50 | 9.63 MW | 9.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274716 | NELSON EC;1S | 50/50 | 7.03 MW | 7.03 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274717 | NELSON EC;2C | 50/50 | 9.7 MW | 9.7 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274718 | NELSON EC;2S | 50/50 | 7.09 MW | 7.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274857 | BIG SKY ;U1 | 50/50 | 0.87 MW | 0.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274858 | BIG SKY ;U2 | 50/50 | 0.87 MW | 0.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274859 | EASYR;U1 E | 50/50 | 32.24 MW | 32.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274860 | EASYR;U2 E | 50/50 | 32.24 MW | 32.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274877 | BISHOP HL;1U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274878 | BISHOP HL;2U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276156 | O-029 C | 50/50 | 0.46 MW | 0.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276157 | O-029 C | 50/50 | 0.49 MW | 0.49 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276158 | O-029 C | 50/50 | 0.9 MW | 0.9 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293513 | O-009 C1 | 50/50 | 0.85 MW | 0.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293514 | O-009 C2 | 50/50 | 0.43 MW | 0.43 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293516 | O-009 E1 | 50/50 | 19.89 MW | 19.89 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293517 | O-009 E2 | 50/50 | 10.1 MW | 10.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293518 | O-009 E3 | 50/50 | 11.12 MW | 11.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293715 | O-029 E | 50/50 | 21.26 MW | 21.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293716 | O-029 E | 50/50 | 11.66 MW | 11.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293717 | O-029 E | 50/50 | 10.71 MW | 10.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293771 | O-035 E | Adder | 5.37 MW | 4.56 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294401 | BSHIL;1U E | 50/50 | 8.83 MW | 8.83 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294410 | BSHIL;2U E | 50/50 | 8.83 MW | 8.83 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294763 | P-046 E | Adder | 6.53 MW | 5.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916211 | Z1-072 E | Adder | 4.06 MW | 3.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916221 | Z1-073 E | Adder | 4.42 MW | 3.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925581 | AC1-033 C | 50/50 | 1.45 MW | 1.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925582 | AC1-033 E | 50/50 | 9.68 MW | 9.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938861 | AE1-114 C O1 | 50/50 | 5.06 MW | 5.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938862 | AE1-114 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939051 | AE1-134 1 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939061 | AE1-134 2 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 940501 | AE2-035 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 940502 | AE2-035 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946151 | AF1-280 C O1 | 50/50 | 46.01 MW | 46.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946152 | AF1-280 E O1 | 50/50 | 21.16 MW | 21.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946162 | AF1-281 E O1 | 50/50 | 5.71 MW | 5.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946321 | AF1-296 C O1 | 50/50 | 8.66 MW | 8.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946322 | AF1-296 E O1 | 50/50 | 40.52 MW | 40.52 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946501 | AF1-314 C | Adder | 3.03 MW | 2.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946502 | AF1-314 E | Adder | 14.26 MW | 12.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957762 | AF2-070 E | Adder | 1.36 MW | 1.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990901 | L-005 E | Adder | 12.01 MW | 10.21 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965082 | AG1-373 BAT | 50/50 | 10.18 MW | 10.18 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965062 | AG1-371 BAT | 50/50 | 30.54 MW | 30.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951031 | J344 C | External Queue | 2.71 MW | 2.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951032 | J344 E | External Queue | 8.14 MW | 8.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951381 | J504 | External Queue | 5.04 MW | 5.04 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951421 | J514 | External Queue | 3.06 MW | 3.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951511 | J530 C | External Queue | 4.95 MW | 4.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951512 | J530 E | External Queue | 19.82 MW | 19.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951841 | J555 C | External Queue | 1.82 MW | 1.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951842 | J555 E | External Queue | 9.84 MW | 9.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 954702 | J844 E | External Queue | 12.62 MW | 12.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 955971 | J1084 | External Queue | 29.54 MW | 29.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 956411 | J1131 | External Queue | 15.48 MW | 15.48 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990947 | J1432 E | External Queue | 41.55 MW | 41.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 991091 | J1477 | External Queue | 7.74 MW | 7.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.7 MW | 6.7 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.36 MW | 52.36 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.73 MW | 21.73 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.17 MW | 0.17 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.12 MW | 5.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.7 MW | 16.7 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.08 MW | 1.08 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.54 MW | 2.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 20.68 MW | 20.68 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 13.79 MW | 13.79 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962701 | AG1-119 C | Adder | 13.59 MW | 11.55 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962702 | AG1-119 E | Adder | 9.06 MW | 7.7 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962711 | AG1-120 C O1 | Adder | 6.32 MW | 5.37 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962712 | AG1-120 E O1 | Adder | 4.21 MW | 3.58 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.08 MW | 6.08 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.05 MW | 4.05 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 15.36 MW | 13.05 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.09 MW | 2.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 4.75 MW | 4.75 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.58 MW | 1.58 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965141 | AG1-379 C | Adder | 9.32 MW | 7.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965142 | AG1-379 E | Adder | 4.27 MW | 3.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 9.08 MW | 7.71 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 6.05 MW | 5.14 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965661 | AG1-434 C O1 | 50/50 | 4.96 MW | 4.96 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965662 | AG1-434 E O1 | 50/50 | 23.23 MW | 23.23 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 9.94 MW | 8.45 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 6.63 MW | 5.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966091 | AG1-478 C | Adder | 0.89 MW | 0.76 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.22 MW | 0.19 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.29 MW | 0.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.43 MW | 0.37 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 272364 | ESS H440N ;R | Adder | 2.19 MW | 1.86 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 290021 | O50 E | Adder | 10.87 MW | 9.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 290051 | GSG-6; E | Adder | 8.69 MW | 7.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 295109 | WESTBROOK E | Adder | 4.65 MW | 3.96 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 1.87 MW | 1.59 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.9 MW | 11.81 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 2.63 MW | 2.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 2.63 MW | 2.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 933911 | AD1-013 C | Adder | 1.54 MW | 1.31 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 933912 | AD1-013 E | Adder | 2.45 MW | 2.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.4 MW | 0.34 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.27 MW | 0.23 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.45 MW | 3.78 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 2.97 MW | 2.52 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 937001 | AD2-134 C | Adder | 2.1 MW | 1.79 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 937002 | AD2-134 E | Adder | 8.41 MW | 7.14 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.33 MW | 1.13 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 937312 | AD2-172 E | Adder | 1.83 MW | 1.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 942421 | AE2-255 C O1 | Adder | 1.7 MW | 1.44 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 942422 | AE2-255 E O1 | Adder | 5.1 MW | 4.33 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 10.68 MW | 10.68 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 5.25 MW | 5.25 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 7.1 MW | 7.1 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 3.51 MW | 3.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 958911 | AF2-182 C | Adder | 14.78 MW | 12.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 958912 | AF2-182 E | Adder | 9.85 MW | 8.37 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.63 MW | 2.23 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 958922 | AF2-183 E | Adder | 3.94 MW | 3.35 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 9.51 MW | 9.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 4.75 MW | 4.75 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 19.01 MW | 19.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 12.67 MW | 12.67 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 3.25 MW | 2.76 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 9.33 MW | 7.93 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 4.48 MW | 4.48 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 960721 | AF2-363 C O1 | Adder | 4.31 MW | 3.66 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 960722 | AF2-363 E O1 | Adder | 2.87 MW | 2.44 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.06 MW | 6.06 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.04 MW | 4.04 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 2.93 MW | 2.49 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 13.72 MW | 11.66 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.0 MW | 4.25 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.33 MW | 2.83 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274658 | DRESDEN ;2U | 50/50 | 25.41 MW | 25.41 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 4.54 MW | 4.54 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 4.54 MW | 4.54 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 7.61 MW | 6.47 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 7.61 MW | 6.47 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 3.04 MW | 3.04 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.06 MW | 5.16 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.08 MW | 2.62 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.39 MW | 2.88 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293715 | O-029 E | Adder | 6.48 MW | 5.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293716 | O-029 E | Adder | 3.55 MW | 3.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293717 | O-029 E | Adder | 3.27 MW | 2.78 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 294763 | P-046 E | Adder | 5.06 MW | 4.3 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 916221 | Z1-073 E | Adder | 4.52 MW | 3.84 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 21.19 MW | 18.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 16.85 MW | 14.32 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 930771 | AB1-122 CT2 | 50/50 | 77.18 MW | 77.18 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 938851 | AE1-113 C O1 | Adder | 4.48 MW | 3.81 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 938852 | AE1-113 E O1 | Adder | 15.9 MW | 13.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.42 MW | 2.05 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 8.24 MW | 7.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.08 MW | 0.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.08 MW | 0.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.33 MW | 1.13 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 940502 | AE2-035 E | Adder | 1.83 MW | 1.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 5.7 MW | 5.7 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 3.8 MW | 3.8 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.25 MW | 9.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.17 MW | 4.4 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.25 MW | 0.21 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.4 MW | 1.19 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.46 MW | 2.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 11.51 MW | 9.78 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946501 | AF1-314 C | Adder | 2.35 MW | 2.0 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946502 | AF1-314 E | Adder | 11.05 MW | 9.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946671 | AF1-331 | Adder | 2.0 MW | 1.7 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 28.51 MW | 28.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 14.26 MW | 14.26 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 934111 | AD2-000 2 | 50/50 | 6.24 MW | 6.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.72 MW | 0.72 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 21.09 MW | 21.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 957403 | AF2-034 BAT | 50/50 | 1.02 MW | 1.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 945351 | AF1-200 FTIR | Adder | 182.13 MW | 154.81 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 955971 | J1084 | External Queue | 8.52 MW | 8.52 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.02 MW | 0.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.24 MW | 0.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.12 MW | 0.12 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.36 MW | 9.36 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.71 MW | 5.71 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.24 MW | 0.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.34 MW | 1.34 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.09 MW | 0.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.79 MW | 4.79 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.13 MW | 0.13 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.55 MW | 1.55 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.08 MW | 0.08 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.59 MW | 0.59 MW |
| Details for AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 962012 | AG1-044 E | 50/50 | 0.16 MW | 0.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 962721 | AG1-121 C O1 | Adder | 4.43 MW | 3.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 962722 | AG1-121 E O1 | Adder | 20.73 MW | 17.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 966821 | AG1-553 C O1 | 50/50 | 56.1 MW | 56.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 966822 | AG1-553 E O1 | 50/50 | 11.29 MW | 11.29 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965661 | AG1-434 C O1 | 50/50 | 18.61 MW | 18.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965662 | AG1-434 E O1 | 50/50 | 87.14 MW | 87.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965671 | AG1-435 C O1 | Adder | 3.34 MW | 2.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965672 | AG1-435 E O1 | Adder | 15.64 MW | 13.3 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965931 | AG1-462 C O1 | 50/50 | 36.31 MW | 36.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965932 | AG1-462 E O1 | 50/50 | 24.2 MW | 24.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 272364 | ESS H440N ;R | Adder | 2.07 MW | 1.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 290051 | GSG-6; E | Adder | 8.51 MW | 7.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 295109 | WESTBROOK E | Adder | 4.56 MW | 3.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 295110 | SUBLETTE C | 50/50 | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 295111 | SUBLETTE E | 50/50 | 5.32 MW | 5.32 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 919221 | AA1-146 | 50/50 | 8.98 MW | 8.98 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 919581 | AA2-030 C | 50/50 | 52.75 MW | 52.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 927202 | AC1-214 E O1 | Adder | 5.48 MW | 4.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 933911 | AD1-013 C | Adder | 1.44 MW | 1.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 934051 | AD1-031 C O1 | 50/50 | 2.92 MW | 2.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 934052 | AD1-031 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 937001 | AD2-134 C | Adder | 2.06 MW | 1.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 937002 | AD2-134 E | Adder | 8.23 MW | 7.0 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 937311 | AD2-172 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 937312 | AD2-172 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 958911 | AF2-182 C | 50/50 | 60.47 MW | 60.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 958912 | AF2-182 E | 50/50 | 40.31 MW | 40.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 958921 | AF2-183 C | 50/50 | 10.75 MW | 10.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 958922 | AF2-183 E | 50/50 | 16.12 MW | 16.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 959101 | AF2-201 C O1 | Adder | 4.2 MW | 3.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 959102 | AF2-201 E O1 | Adder | 12.05 MW | 10.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 961011 | AF2-392 C O1 | 50/50 | 9.48 MW | 9.48 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 961012 | AF2-392 E O1 | 50/50 | 44.37 MW | 44.37 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 961021 | AF2-393 O1 | 50/50 | 16.15 MW | 16.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 961031 | AF2-394 O1 | 50/50 | 10.77 MW | 10.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274662 | QUAD CITI;1U | 50/50 | 36.61 MW | 36.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274663 | QUAD CITI;2U | 50/50 | 36.72 MW | 36.72 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274699 | CORDOVA ;1C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274700 | CORDOVA ;2C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274701 | CORDOVA ;1S | 50/50 | 7.25 MW | 7.25 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274715 | NELSON EC;1C | 50/50 | 9.63 MW | 9.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274716 | NELSON EC;1S | 50/50 | 7.03 MW | 7.03 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274717 | NELSON EC;2C | 50/50 | 9.71 MW | 9.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274718 | NELSON EC;2S | 50/50 | 7.09 MW | 7.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274877 | BISHOP HL;1U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274878 | BISHOP HL;2U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 276156 | O-029 C | 50/50 | 0.46 MW | 0.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 276157 | O-029 C | 50/50 | 0.5 MW | 0.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 276158 | O-029 C | 50/50 | 0.9 MW | 0.9 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293513 | O-009 C1 | 50/50 | 0.85 MW | 0.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293514 | O-009 C2 | 50/50 | 0.43 MW | 0.43 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293516 | O-009 E1 | 50/50 | 19.89 MW | 19.89 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293517 | O-009 E2 | 50/50 | 10.1 MW | 10.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293518 | O-009 E3 | 50/50 | 11.13 MW | 11.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293715 | O-029 E | 50/50 | 21.27 MW | 21.27 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293716 | O-029 E | 50/50 | 11.66 MW | 11.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293717 | O-029 E | 50/50 | 10.72 MW | 10.72 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293771 | O-035 E | Adder | 5.37 MW | 4.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 294401 | BSHIL;1U E | 50/50 | 8.84 MW | 8.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 294410 | BSHIL;2U E | 50/50 | 8.84 MW | 8.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 294763 | P-046 E | Adder | 6.53 MW | 5.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 916211 | Z1-072 E | Adder | 4.06 MW | 3.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 916221 | Z1-073 E | Adder | 4.42 MW | 3.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 925581 | AC1-033 C | 50/50 | 1.45 MW | 1.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 925582 | AC1-033 E | 50/50 | 9.69 MW | 9.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 938861 | AE1-114 C O1 | 50/50 | 5.06 MW | 5.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 938862 | AE1-114 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 939051 | AE1-134 1 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 939061 | AE1-134 2 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 940501 | AE2-035 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 940502 | AE2-035 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946151 | AF1-280 C O1 | 50/50 | 46.02 MW | 46.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946152 | AF1-280 E O1 | 50/50 | 21.16 MW | 21.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946162 | AF1-281 E O1 | 50/50 | 5.71 MW | 5.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946321 | AF1-296 C O1 | 50/50 | 8.66 MW | 8.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946322 | AF1-296 E O1 | 50/50 | 40.53 MW | 40.53 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946501 | AF1-314 C | Adder | 3.04 MW | 2.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946502 | AF1-314 E | Adder | 14.27 MW | 12.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 957762 | AF2-070 E | Adder | 1.37 MW | 1.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 990901 | L-005 E | Adder | 12.02 MW | 10.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965082 | AG1-373 BAT | 50/50 | 10.18 MW | 10.18 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965062 | AG1-371 BAT | 50/50 | 30.54 MW | 30.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951031 | J344 C | External Queue | 2.71 MW | 2.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951032 | J344 E | External Queue | 8.14 MW | 8.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951381 | J504 | External Queue | 5.04 MW | 5.04 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951421 | J514 | External Queue | 3.06 MW | 3.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951511 | J530 C | External Queue | 4.95 MW | 4.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951512 | J530 E | External Queue | 19.82 MW | 19.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951841 | J555 C | External Queue | 1.82 MW | 1.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951842 | J555 E | External Queue | 9.84 MW | 9.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 954702 | J844 E | External Queue | 12.62 MW | 12.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 955971 | J1084 | External Queue | 29.54 MW | 29.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 956411 | J1131 | External Queue | 15.48 MW | 15.48 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 990947 | J1432 E | External Queue | 41.55 MW | 41.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 991091 | J1477 | External Queue | 7.74 MW | 7.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.58 MW | 0.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.76 MW | 6.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.44 MW | 52.44 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.78 MW | 21.78 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.16 MW | 0.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.13 MW | 5.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.71 MW | 16.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.05 MW | 1.05 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.55 MW | 2.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 962012 | AG1-044 E | 50/50 | 0.16 MW | 0.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 962721 | AG1-121 C O1 | Adder | 4.43 MW | 3.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 962722 | AG1-121 E O1 | Adder | 20.73 MW | 17.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 966821 | AG1-553 C O1 | 50/50 | 56.1 MW | 56.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 966822 | AG1-553 E O1 | 50/50 | 11.29 MW | 11.29 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965661 | AG1-434 C O1 | 50/50 | 18.61 MW | 18.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965662 | AG1-434 E O1 | 50/50 | 87.14 MW | 87.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965671 | AG1-435 C O1 | Adder | 3.34 MW | 2.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965672 | AG1-435 E O1 | Adder | 15.64 MW | 13.3 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965931 | AG1-462 C O1 | 50/50 | 36.31 MW | 36.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965932 | AG1-462 E O1 | 50/50 | 24.2 MW | 24.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 272364 | ESS H440N ;R | Adder | 2.07 MW | 1.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 290051 | GSG-6; E | Adder | 8.51 MW | 7.23 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 295109 | WESTBROOK E | Adder | 4.56 MW | 3.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 295110 | SUBLETTE C | 50/50 | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 295111 | SUBLETTE E | 50/50 | 5.32 MW | 5.32 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 919221 | AA1-146 | 50/50 | 8.98 MW | 8.98 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 919581 | AA2-030 C | 50/50 | 52.75 MW | 52.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 927202 | AC1-214 E O1 | Adder | 5.48 MW | 4.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 933911 | AD1-013 C | Adder | 1.44 MW | 1.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 934051 | AD1-031 C O1 | 50/50 | 2.92 MW | 2.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 934052 | AD1-031 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 937001 | AD2-134 C | Adder | 2.06 MW | 1.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 937002 | AD2-134 E | Adder | 8.23 MW | 7.0 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 937311 | AD2-172 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 937312 | AD2-172 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 958911 | AF2-182 C | 50/50 | 60.47 MW | 60.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 958912 | AF2-182 E | 50/50 | 40.31 MW | 40.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 958921 | AF2-183 C | 50/50 | 10.75 MW | 10.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 958922 | AF2-183 E | 50/50 | 16.12 MW | 16.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 959101 | AF2-201 C O1 | Adder | 4.2 MW | 3.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 959102 | AF2-201 E O1 | Adder | 12.05 MW | 10.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 961011 | AF2-392 C O1 | 50/50 | 9.48 MW | 9.48 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 961012 | AF2-392 E O1 | 50/50 | 44.37 MW | 44.37 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 961021 | AF2-393 O1 | 50/50 | 16.15 MW | 16.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 961031 | AF2-394 O1 | 50/50 | 10.77 MW | 10.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274662 | QUAD CITI;1U | 50/50 | 36.61 MW | 36.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274663 | QUAD CITI;2U | 50/50 | 36.72 MW | 36.72 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274699 | CORDOVA ;1C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274700 | CORDOVA ;2C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274701 | CORDOVA ;1S | 50/50 | 7.25 MW | 7.25 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274715 | NELSON EC;1C | 50/50 | 9.63 MW | 9.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274716 | NELSON EC;1S | 50/50 | 7.03 MW | 7.03 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274717 | NELSON EC;2C | 50/50 | 9.71 MW | 9.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274718 | NELSON EC;2S | 50/50 | 7.09 MW | 7.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274877 | BISHOP HL;1U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274878 | BISHOP HL;2U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 276156 | O-029 C | 50/50 | 0.46 MW | 0.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 276157 | O-029 C | 50/50 | 0.5 MW | 0.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 276158 | O-029 C | 50/50 | 0.9 MW | 0.9 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293513 | O-009 C1 | 50/50 | 0.85 MW | 0.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293514 | O-009 C2 | 50/50 | 0.43 MW | 0.43 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293516 | O-009 E1 | 50/50 | 19.89 MW | 19.89 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293517 | O-009 E2 | 50/50 | 10.1 MW | 10.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293518 | O-009 E3 | 50/50 | 11.13 MW | 11.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293715 | O-029 E | 50/50 | 21.27 MW | 21.27 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293716 | O-029 E | 50/50 | 11.66 MW | 11.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293717 | O-029 E | 50/50 | 10.72 MW | 10.72 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293771 | O-035 E | Adder | 5.37 MW | 4.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 294401 | BSHIL;1U E | 50/50 | 8.84 MW | 8.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 294410 | BSHIL;2U E | 50/50 | 8.84 MW | 8.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 294763 | P-046 E | Adder | 6.53 MW | 5.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 916211 | Z1-072 E | Adder | 4.06 MW | 3.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 916221 | Z1-073 E | Adder | 4.42 MW | 3.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 925581 | AC1-033 C | 50/50 | 1.45 MW | 1.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 925582 | AC1-033 E | 50/50 | 9.69 MW | 9.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 938861 | AE1-114 C O1 | 50/50 | 5.06 MW | 5.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 938862 | AE1-114 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 939051 | AE1-134 1 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 939061 | AE1-134 2 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 940501 | AE2-035 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 940502 | AE2-035 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946151 | AF1-280 C O1 | 50/50 | 46.02 MW | 46.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946152 | AF1-280 E O1 | 50/50 | 21.16 MW | 21.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946162 | AF1-281 E O1 | 50/50 | 5.71 MW | 5.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946321 | AF1-296 C O1 | 50/50 | 8.66 MW | 8.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946322 | AF1-296 E O1 | 50/50 | 40.53 MW | 40.53 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946501 | AF1-314 C | Adder | 3.04 MW | 2.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946502 | AF1-314 E | Adder | 14.27 MW | 12.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 957762 | AF2-070 E | Adder | 1.37 MW | 1.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 990901 | L-005 E | Adder | 12.02 MW | 10.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965082 | AG1-373 BAT | 50/50 | 10.18 MW | 10.18 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965062 | AG1-371 BAT | 50/50 | 30.54 MW | 30.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951031 | J344 C | External Queue | 2.71 MW | 2.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951032 | J344 E | External Queue | 8.14 MW | 8.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951381 | J504 | External Queue | 5.04 MW | 5.04 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951421 | J514 | External Queue | 3.06 MW | 3.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951511 | J530 C | External Queue | 4.95 MW | 4.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951512 | J530 E | External Queue | 19.82 MW | 19.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951841 | J555 C | External Queue | 1.82 MW | 1.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951842 | J555 E | External Queue | 9.84 MW | 9.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 954702 | J844 E | External Queue | 12.62 MW | 12.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 955971 | J1084 | External Queue | 29.54 MW | 29.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 956411 | J1131 | External Queue | 15.48 MW | 15.48 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 990947 | J1432 E | External Queue | 41.55 MW | 41.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 991091 | J1477 | External Queue | 7.74 MW | 7.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.76 MW | 6.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.43 MW | 52.43 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.78 MW | 21.78 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.16 MW | 0.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.13 MW | 5.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.71 MW | 16.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.05 MW | 1.05 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.55 MW | 2.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962012 | AG1-044 E | 50/50 | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962701 | AG1-119 C | Adder | 26.65 MW | 22.65 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962702 | AG1-119 E | Adder | 17.77 MW | 15.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966821 | AG1-553 C O1 | Adder | 45.28 MW | 38.49 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966822 | AG1-553 E O1 | Adder | 9.12 MW | 7.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965551 | AG1-423 C O1 | Adder | 17.77 MW | 15.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965552 | AG1-423 E O1 | Adder | 11.84 MW | 10.07 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965661 | AG1-434 C O1 | 50/50 | 16.66 MW | 16.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965662 | AG1-434 E O1 | 50/50 | 78.01 MW | 78.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965931 | AG1-462 C O1 | Adder | 29.3 MW | 24.91 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965932 | AG1-462 E O1 | Adder | 19.54 MW | 16.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 272364 | ESS H440N ;R | Adder | 2.01 MW | 1.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290051 | GSG-6; E | Adder | 8.22 MW | 6.99 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295109 | WESTBROOK E | Adder | 4.4 MW | 3.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295111 | SUBLETTE E | Adder | 4.56 MW | 3.88 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919221 | AA1-146 | 50/50 | 7.02 MW | 7.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919581 | AA2-030 C | 50/50 | 41.23 MW | 41.23 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933911 | AD1-013 C | Adder | 1.4 MW | 1.19 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933912 | AD1-013 E | Adder | 2.23 MW | 1.9 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934051 | AD1-031 C O1 | Adder | 2.31 MW | 1.96 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934052 | AD1-031 E O1 | Adder | 3.76 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934432 | AD1-067 E | Adder | 0.43 MW | 0.37 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934972 | AD1-129 E | Adder | 0.44 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937001 | AD2-134 C | Adder | 1.99 MW | 1.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937002 | AD2-134 E | Adder | 7.95 MW | 6.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937311 | AD2-172 C | Adder | 2.99 MW | 2.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937312 | AD2-172 E | Adder | 4.13 MW | 3.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958911 | AF2-182 C | 50/50 | 41.62 MW | 41.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958912 | AF2-182 E | 50/50 | 27.75 MW | 27.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958921 | AF2-183 C | 50/50 | 7.4 MW | 7.4 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958922 | AF2-183 E | 50/50 | 11.1 MW | 11.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959101 | AF2-201 C O1 | Adder | 7.32 MW | 6.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959102 | AF2-201 E O1 | Adder | 21.01 MW | 17.86 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960581 | AF2-349 C | Adder | 15.01 MW | 12.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960582 | AF2-349 E | Adder | 10.01 MW | 8.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961011 | AF2-392 C O1 | 50/50 | 7.79 MW | 7.79 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961012 | AF2-392 E O1 | 50/50 | 36.47 MW | 36.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961021 | AF2-393 O1 | 50/50 | 13.28 MW | 13.28 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961031 | AF2-394 O1 | 50/50 | 8.85 MW | 8.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274715 | NELSON EC;1C | 50/50 | 7.53 MW | 7.53 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274716 | NELSON EC;1S | 50/50 | 5.49 MW | 5.49 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274717 | NELSON EC;2C | 50/50 | 7.59 MW | 7.59 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274718 | NELSON EC;2S | 50/50 | 5.54 MW | 5.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274760 | LEE CO EC;1U | 50/50 | 3.14 MW | 3.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274764 | LEE CO EC;5U | 50/50 | 3.15 MW | 3.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274765 | LEE CO EC;6U | 50/50 | 3.15 MW | 3.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274859 | EASYR;U1 E | Adder | 20.86 MW | 17.73 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274860 | EASYR;U2 E | Adder | 20.86 MW | 17.73 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293516 | O-009 E1 | Adder | 16.04 MW | 13.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293517 | O-009 E2 | Adder | 8.15 MW | 6.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293518 | O-009 E3 | Adder | 8.97 MW | 7.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293715 | O-029 E | Adder | 17.15 MW | 14.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293716 | O-029 E | Adder | 9.4 MW | 7.99 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293717 | O-029 E | Adder | 8.64 MW | 7.34 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294401 | BSHIL;1U E | Adder | 6.98 MW | 5.94 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294410 | BSHIL;2U E | Adder | 6.98 MW | 5.94 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294763 | P-046 E | Adder | 11.39 MW | 9.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 916221 | Z1-073 E | Adder | 4.27 MW | 3.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 925581 | AC1-033 C | Adder | 1.14 MW | 0.97 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 925582 | AC1-033 E | Adder | 7.66 MW | 6.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930482 | AB1-089 CT | Adder | 45.39 MW | 38.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930483 | AB1-089 ST | Adder | 36.09 MW | 30.67 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938861 | AE1-114 C O1 | Adder | 5.75 MW | 4.88 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938862 | AE1-114 E O1 | Adder | 19.61 MW | 16.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939051 | AE1-134 1 | 50/50 | 3.2 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939061 | AE1-134 2 | 50/50 | 3.2 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940501 | AE2-035 C | Adder | 2.99 MW | 2.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940502 | AE2-035 E | Adder | 4.13 MW | 3.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946151 | AF1-280 C O1 | 50/50 | 31.68 MW | 31.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946152 | AF1-280 E O1 | 50/50 | 14.57 MW | 14.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946161 | AF1-281 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946162 | AF1-281 E O1 | 50/50 | 3.93 MW | 3.93 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946321 | AF1-296 C O1 | Adder | 7.08 MW | 6.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946322 | AF1-296 E O1 | Adder | 33.16 MW | 28.19 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946501 | AF1-314 C | Adder | 5.3 MW | 4.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946502 | AF1-314 E | Adder | 24.88 MW | 21.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946671 | AF1-331 | Adder | 1.82 MW | 1.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990901 | L-005 E | Adder | 9.46 MW | 8.04 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965082 | AG1-373 BAT | 50/50 | 11.42 MW | 11.42 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965062 | AG1-371 BAT | 50/50 | 34.25 MW | 34.25 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951381 | J504 | External Queue | 4.22 MW | 4.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951421 | J514 | External Queue | 2.51 MW | 2.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951511 | J530 C | External Queue | 3.88 MW | 3.88 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951512 | J530 E | External Queue | 15.5 MW | 15.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953922 | J855 E | External Queue | 6.83 MW | 6.83 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 955971 | J1084 | External Queue | 22.66 MW | 22.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 956411 | J1131 | External Queue | 11.85 MW | 11.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990726 | J1377 | External Queue | 7.58 MW | 7.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990947 | J1432 E | External Queue | 33.18 MW | 33.18 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 991091 | J1477 | External Queue | 5.93 MW | 5.93 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.36 MW | 0.36 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.42 MW | 0.42 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.35 MW | 3.35 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 61.98 MW | 61.98 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.54 MW | 17.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.1 MW | 0.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.44 MW | 0.44 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.3 MW | 4.3 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.26 MW | 0.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.2 MW | 15.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.83 MW | 2.83 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.96 MW | 1.96 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.09 MW | 1.09 MW |
| Details for AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962012 | AG1-044 E | 50/50 | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962701 | AG1-119 C | Adder | 26.65 MW | 22.65 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962702 | AG1-119 E | Adder | 17.77 MW | 15.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966821 | AG1-553 C O1 | Adder | 45.28 MW | 38.49 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966822 | AG1-553 E O1 | Adder | 9.12 MW | 7.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965551 | AG1-423 C O1 | Adder | 17.77 MW | 15.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965552 | AG1-423 E O1 | Adder | 11.84 MW | 10.07 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965661 | AG1-434 C O1 | 50/50 | 16.66 MW | 16.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965662 | AG1-434 E O1 | 50/50 | 78.0 MW | 78.0 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965931 | AG1-462 C O1 | Adder | 29.31 MW | 24.91 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965932 | AG1-462 E O1 | Adder | 19.54 MW | 16.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 272364 | ESS H440N ;R | Adder | 2.01 MW | 1.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290051 | GSG-6; E | Adder | 8.21 MW | 6.98 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295109 | WESTBROOK E | Adder | 4.4 MW | 3.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295111 | SUBLETTE E | Adder | 4.56 MW | 3.88 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 919221 | AA1-146 | 50/50 | 7.02 MW | 7.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 919581 | AA2-030 C | 50/50 | 41.23 MW | 41.23 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933911 | AD1-013 C | Adder | 1.4 MW | 1.19 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933912 | AD1-013 E | Adder | 2.23 MW | 1.9 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934051 | AD1-031 C O1 | Adder | 2.31 MW | 1.96 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934052 | AD1-031 E O1 | Adder | 3.76 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934432 | AD1-067 E | Adder | 0.43 MW | 0.37 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934972 | AD1-129 E | Adder | 0.44 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937001 | AD2-134 C | Adder | 1.99 MW | 1.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937002 | AD2-134 E | Adder | 7.94 MW | 6.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937311 | AD2-172 C | Adder | 2.99 MW | 2.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937312 | AD2-172 E | Adder | 4.13 MW | 3.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958911 | AF2-182 C | 50/50 | 41.62 MW | 41.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958912 | AF2-182 E | 50/50 | 27.75 MW | 27.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958921 | AF2-183 C | 50/50 | 7.4 MW | 7.4 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958922 | AF2-183 E | 50/50 | 11.1 MW | 11.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959101 | AF2-201 C O1 | Adder | 7.32 MW | 6.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959102 | AF2-201 E O1 | Adder | 21.01 MW | 17.86 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960581 | AF2-349 C | Adder | 15.01 MW | 12.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960582 | AF2-349 E | Adder | 10.01 MW | 8.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961011 | AF2-392 C O1 | 50/50 | 7.79 MW | 7.79 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961012 | AF2-392 E O1 | 50/50 | 36.46 MW | 36.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961021 | AF2-393 O1 | 50/50 | 13.28 MW | 13.28 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961031 | AF2-394 O1 | 50/50 | 8.85 MW | 8.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274715 | NELSON EC;1C | 50/50 | 7.53 MW | 7.53 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274716 | NELSON EC;1S | 50/50 | 5.49 MW | 5.49 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274717 | NELSON EC;2C | 50/50 | 7.59 MW | 7.59 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274718 | NELSON EC;2S | 50/50 | 5.54 MW | 5.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274760 | LEE CO EC;1U | 50/50 | 3.14 MW | 3.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274764 | LEE CO EC;5U | 50/50 | 3.15 MW | 3.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274765 | LEE CO EC;6U | 50/50 | 3.15 MW | 3.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274859 | EASYR;U1 E | Adder | 20.86 MW | 17.73 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274860 | EASYR;U2 E | Adder | 20.86 MW | 17.73 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293516 | O-009 E1 | Adder | 16.04 MW | 13.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293517 | O-009 E2 | Adder | 8.15 MW | 6.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293518 | O-009 E3 | Adder | 8.97 MW | 7.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293715 | O-029 E | Adder | 17.15 MW | 14.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293716 | O-029 E | Adder | 9.4 MW | 7.99 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293717 | O-029 E | Adder | 8.64 MW | 7.34 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294401 | BSHIL;1U E | Adder | 6.98 MW | 5.94 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294410 | BSHIL;2U E | Adder | 6.98 MW | 5.94 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294763 | P-046 E | Adder | 11.39 MW | 9.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 916221 | Z1-073 E | Adder | 4.26 MW | 3.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 925581 | AC1-033 C | Adder | 1.14 MW | 0.97 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 925582 | AC1-033 E | Adder | 7.66 MW | 6.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930482 | AB1-089 CT | Adder | 45.4 MW | 38.59 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930483 | AB1-089 ST | Adder | 36.09 MW | 30.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938861 | AE1-114 C O1 | Adder | 5.75 MW | 4.88 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938862 | AE1-114 E O1 | Adder | 19.6 MW | 16.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939051 | AE1-134 1 | 50/50 | 3.2 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939061 | AE1-134 2 | 50/50 | 3.2 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940501 | AE2-035 C | Adder | 2.99 MW | 2.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940502 | AE2-035 E | Adder | 4.13 MW | 3.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946151 | AF1-280 C O1 | 50/50 | 31.68 MW | 31.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946152 | AF1-280 E O1 | 50/50 | 14.57 MW | 14.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946161 | AF1-281 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946162 | AF1-281 E O1 | 50/50 | 3.93 MW | 3.93 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946321 | AF1-296 C O1 | Adder | 7.08 MW | 6.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946322 | AF1-296 E O1 | Adder | 33.16 MW | 28.19 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946501 | AF1-314 C | Adder | 5.3 MW | 4.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946502 | AF1-314 E | Adder | 24.89 MW | 21.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946671 | AF1-331 | Adder | 1.81 MW | 1.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990901 | L-005 E | Adder | 9.46 MW | 8.04 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965082 | AG1-373 BAT | 50/50 | 11.42 MW | 11.42 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965062 | AG1-371 BAT | 50/50 | 34.26 MW | 34.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 951381 | J504 | External Queue | 4.22 MW | 4.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 951421 | J514 | External Queue | 2.51 MW | 2.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 951511 | J530 C | External Queue | 3.87 MW | 3.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 951512 | J530 E | External Queue | 15.5 MW | 15.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953922 | J855 E | External Queue | 6.84 MW | 6.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 955971 | J1084 | External Queue | 22.65 MW | 22.65 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 956411 | J1131 | External Queue | 11.85 MW | 11.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990726 | J1377 | External Queue | 7.58 MW | 7.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990947 | J1432 E | External Queue | 33.17 MW | 33.17 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 991091 | J1477 | External Queue | 5.92 MW | 5.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.36 MW | 0.36 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.43 MW | 0.43 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.36 MW | 3.36 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.1 MW | 62.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.55 MW | 17.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.1 MW | 0.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.44 MW | 0.44 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.31 MW | 4.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.26 MW | 0.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.21 MW | 15.21 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.83 MW | 2.83 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.96 MW | 1.96 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.1 MW | 1.1 MW |
| Details for NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 966821 | AG1-553 C O1 | Adder | 11.93 MW | 10.14 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 966822 | AG1-553 E O1 | Adder | 2.4 MW | 2.04 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 965931 | AG1-462 C O1 | Adder | 7.72 MW | 6.56 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 965932 | AG1-462 E O1 | Adder | 5.15 MW | 4.37 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 272364 | ESS H440N ;R | Adder | -3.12 MW | -2.65 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 919581 | AA2-030 C | Adder | 15.44 MW | 13.13 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 937311 | AD2-172 C | Adder | -2.08 MW | -1.77 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 958911 | AF2-182 C | Adder | 14.0 MW | 11.9 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 958912 | AF2-182 E | Adder | 9.34 MW | 7.93 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 958921 | AF2-183 C | Adder | 2.49 MW | 2.12 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 958922 | AF2-183 E | Adder | 3.73 MW | 3.17 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 274859 | EASYR;U1 E | Adder | 6.59 MW | 5.6 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 274860 | EASYR;U2 E | Adder | 6.59 MW | 5.6 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 925581 | AC1-033 C | Adder | -0.97 MW | -0.83 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 939051 | AE1-134 1 | Adder | 1.2 MW | 1.02 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 939061 | AE1-134 2 | Adder | 1.2 MW | 1.02 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 940501 | AE2-035 C | Adder | -2.08 MW | -1.77 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 946151 | AF1-280 C O1 | Adder | 10.66 MW | 9.06 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 946152 | AF1-280 E O1 | Adder | 4.9 MW | 4.17 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 946161 | AF1-281 C O1 | Adder | 0.23 MW | 0.2 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 946162 | AF1-281 E O1 | Adder | 1.32 MW | 1.12 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 962013 | AG1-044 BAT | 50/50 | 0.16 MW | 0.16 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 961022 | AF2-393 BAT | 50/50 | 25.7 MW | 25.7 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 961032 | AF2-394 BAT | 50/50 | 17.13 MW | 17.13 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.15 MW | 0.15 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.06 MW | 0.06 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.14 MW | 9.14 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.89 MW | 1.89 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.1 MW | 0.1 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.58 MW | 0.58 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.54 MW | 2.54 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.66 MW | 0.66 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.22 MW | 0.22 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962012 | AG1-044 E | 50/50 | 0.16 MW | 0.16 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962721 | AG1-121 C O1 | Adder | 4.43 MW | 3.77 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962722 | AG1-121 E O1 | Adder | 20.72 MW | 17.61 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966821 | AG1-553 C O1 | 50/50 | 56.08 MW | 56.08 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966822 | AG1-553 E O1 | 50/50 | 11.29 MW | 11.29 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965671 | AG1-435 C O1 | Adder | 3.34 MW | 2.84 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965672 | AG1-435 E O1 | Adder | 15.63 MW | 13.29 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965931 | AG1-462 C O1 | 50/50 | 36.3 MW | 36.3 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965932 | AG1-462 E O1 | 50/50 | 24.2 MW | 24.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 272364 | ESS H440N ;R | Adder | 2.07 MW | 1.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 290051 | GSG-6; E | Adder | 8.51 MW | 7.23 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.55 MW | 3.87 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295110 | SUBLETTE C | 50/50 | 0.13 MW | 0.13 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295111 | SUBLETTE E | 50/50 | 5.31 MW | 5.31 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919221 | AA1-146 | 50/50 | 8.98 MW | 8.98 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919581 | AA2-030 C | 50/50 | 52.74 MW | 52.74 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.48 MW | 4.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933911 | AD1-013 C | Adder | 1.43 MW | 1.22 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934051 | AD1-031 C O1 | 50/50 | 2.92 MW | 2.92 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934052 | AD1-031 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937001 | AD2-134 C | Adder | 2.06 MW | 1.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937002 | AD2-134 E | Adder | 8.22 MW | 6.99 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937311 | AD2-172 C | Adder | 1.71 MW | 1.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937312 | AD2-172 E | Adder | 2.37 MW | 2.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958911 | AF2-182 C | 50/50 | 60.46 MW | 60.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958912 | AF2-182 E | 50/50 | 40.3 MW | 40.3 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958921 | AF2-183 C | 50/50 | 10.75 MW | 10.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958922 | AF2-183 E | 50/50 | 16.12 MW | 16.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959101 | AF2-201 C O1 | Adder | 4.19 MW | 3.56 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 12.04 MW | 10.23 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961011 | AF2-392 C O1 | 50/50 | 9.47 MW | 9.47 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961012 | AF2-392 E O1 | 50/50 | 44.36 MW | 44.36 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961021 | AF2-393 O1 | 50/50 | 16.15 MW | 16.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961031 | AF2-394 O1 | 50/50 | 10.77 MW | 10.77 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274662 | QUAD CITI;1U | 50/50 | 36.61 MW | 36.61 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274663 | QUAD CITI;2U | 50/50 | 36.71 MW | 36.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274699 | CORDOVA ;1C | 50/50 | 6.45 MW | 6.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274700 | CORDOVA ;2C | 50/50 | 6.45 MW | 6.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274701 | CORDOVA ;1S | 50/50 | 7.25 MW | 7.25 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274715 | NELSON EC;1C | 50/50 | 9.63 MW | 9.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274716 | NELSON EC;1S | 50/50 | 7.03 MW | 7.03 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274717 | NELSON EC;2C | 50/50 | 9.7 MW | 9.7 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274718 | NELSON EC;2S | 50/50 | 7.09 MW | 7.09 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274857 | BIG SKY ;U1 | 50/50 | 0.87 MW | 0.87 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274858 | BIG SKY ;U2 | 50/50 | 0.87 MW | 0.87 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274859 | EASYR;U1 E | 50/50 | 32.24 MW | 32.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274860 | EASYR;U2 E | 50/50 | 32.24 MW | 32.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274877 | BISHOP HL;1U | 50/50 | 0.38 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274878 | BISHOP HL;2U | 50/50 | 0.38 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276156 | O-029 C | 50/50 | 0.46 MW | 0.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276157 | O-029 C | 50/50 | 0.49 MW | 0.49 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276158 | O-029 C | 50/50 | 0.9 MW | 0.9 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293513 | O-009 C1 | 50/50 | 0.85 MW | 0.85 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293514 | O-009 C2 | 50/50 | 0.43 MW | 0.43 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293516 | O-009 E1 | 50/50 | 19.89 MW | 19.89 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293517 | O-009 E2 | 50/50 | 10.1 MW | 10.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293518 | O-009 E3 | 50/50 | 11.12 MW | 11.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293715 | O-029 E | 50/50 | 21.26 MW | 21.26 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293716 | O-029 E | 50/50 | 11.66 MW | 11.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293717 | O-029 E | 50/50 | 10.71 MW | 10.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293771 | O-035 E | Adder | 5.37 MW | 4.56 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294401 | BSHIL;1U E | 50/50 | 8.83 MW | 8.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294410 | BSHIL;2U E | 50/50 | 8.83 MW | 8.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294763 | P-046 E | Adder | 6.53 MW | 5.55 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916211 | Z1-072 E | Adder | 4.06 MW | 3.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916221 | Z1-073 E | Adder | 4.42 MW | 3.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925581 | AC1-033 C | 50/50 | 1.45 MW | 1.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925582 | AC1-033 E | 50/50 | 9.68 MW | 9.68 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938861 | AE1-114 C O1 | 50/50 | 5.06 MW | 5.06 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938862 | AE1-114 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939051 | AE1-134 1 | 50/50 | 4.1 MW | 4.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939061 | AE1-134 2 | 50/50 | 4.1 MW | 4.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 940501 | AE2-035 C | Adder | 1.71 MW | 1.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 940502 | AE2-035 E | Adder | 2.37 MW | 2.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946151 | AF1-280 C O1 | 50/50 | 46.01 MW | 46.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946152 | AF1-280 E O1 | 50/50 | 21.16 MW | 21.16 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946162 | AF1-281 E O1 | 50/50 | 5.71 MW | 5.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946321 | AF1-296 C O1 | 50/50 | 8.66 MW | 8.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946322 | AF1-296 E O1 | 50/50 | 40.52 MW | 40.52 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946501 | AF1-314 C | Adder | 3.03 MW | 2.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946502 | AF1-314 E | Adder | 14.26 MW | 12.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957762 | AF2-070 E | Adder | 1.36 MW | 1.16 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990901 | L-005 E | Adder | 12.01 MW | 10.21 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965082 | AG1-373 BAT | 50/50 | 10.18 MW | 10.18 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965062 | AG1-371 BAT | 50/50 | 30.54 MW | 30.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951031 | J344 C | External Queue | 2.71 MW | 2.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951032 | J344 E | External Queue | 8.14 MW | 8.14 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951381 | J504 | External Queue | 5.04 MW | 5.04 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951421 | J514 | External Queue | 3.06 MW | 3.06 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951511 | J530 C | External Queue | 4.95 MW | 4.95 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951512 | J530 E | External Queue | 19.82 MW | 19.82 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951841 | J555 C | External Queue | 1.82 MW | 1.82 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951842 | J555 E | External Queue | 9.84 MW | 9.84 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 954702 | J844 E | External Queue | 12.62 MW | 12.62 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 955971 | J1084 | External Queue | 29.54 MW | 29.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 956411 | J1131 | External Queue | 15.48 MW | 15.48 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990947 | J1432 E | External Queue | 41.55 MW | 41.55 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 991091 | J1477 | External Queue | 7.74 MW | 7.74 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.7 MW | 6.7 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.36 MW | 52.36 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.73 MW | 21.73 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.17 MW | 0.17 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.12 MW | 5.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.7 MW | 16.7 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.08 MW | 1.08 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.54 MW | 2.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 966821 | AG1-553 C O1 | Adder | 11.93 MW | 10.14 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 966822 | AG1-553 E O1 | Adder | 2.4 MW | 2.04 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 965931 | AG1-462 C O1 | Adder | 7.72 MW | 6.56 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 965932 | AG1-462 E O1 | Adder | 5.15 MW | 4.37 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 272364 | ESS H440N ;R | Adder | -3.12 MW | -2.65 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 919581 | AA2-030 C | Adder | 15.44 MW | 13.13 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 937311 | AD2-172 C | Adder | -2.08 MW | -1.77 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 958911 | AF2-182 C | Adder | 14.0 MW | 11.9 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 958912 | AF2-182 E | Adder | 9.34 MW | 7.93 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 958921 | AF2-183 C | Adder | 2.49 MW | 2.12 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 958922 | AF2-183 E | Adder | 3.73 MW | 3.17 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 274859 | EASYR;U1 E | Adder | 6.59 MW | 5.6 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 274860 | EASYR;U2 E | Adder | 6.59 MW | 5.6 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 925581 | AC1-033 C | Adder | -0.97 MW | -0.83 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 939051 | AE1-134 1 | Adder | 1.2 MW | 1.02 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 939061 | AE1-134 2 | Adder | 1.2 MW | 1.02 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 940501 | AE2-035 C | Adder | -2.08 MW | -1.77 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 946151 | AF1-280 C O1 | Adder | 10.66 MW | 9.06 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 946152 | AF1-280 E O1 | Adder | 4.9 MW | 4.17 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 946161 | AF1-281 C O1 | Adder | 0.23 MW | 0.2 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 946162 | AF1-281 E O1 | Adder | 1.32 MW | 1.12 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 962013 | AG1-044 BAT | 50/50 | 0.16 MW | 0.16 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 961022 | AF2-393 BAT | 50/50 | 25.7 MW | 25.7 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | 961032 | AF2-394 BAT | 50/50 | 17.13 MW | 17.13 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.15 MW | 0.15 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.06 MW | 0.06 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.14 MW | 9.14 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.89 MW | 1.89 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.1 MW | 0.1 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.58 MW | 0.58 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.54 MW | 2.54 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.66 MW | 0.66 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.22 MW | 0.22 MW |
| NELSON ;4M-NELSON ; B 138.0 kV Ckt 1 line l/o COMED_P4_155-45-BT2-34_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962012 | AG1-044 E | 50/50 | 0.13 MW | 0.13 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962701 | AG1-119 C | Adder | 26.65 MW | 22.65 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962702 | AG1-119 E | Adder | 17.77 MW | 15.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966821 | AG1-553 C O1 | Adder | 45.28 MW | 38.49 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966822 | AG1-553 E O1 | Adder | 9.12 MW | 7.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965551 | AG1-423 C O1 | Adder | 17.77 MW | 15.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965552 | AG1-423 E O1 | Adder | 11.84 MW | 10.07 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965931 | AG1-462 C O1 | Adder | 29.3 MW | 24.91 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965932 | AG1-462 E O1 | Adder | 19.54 MW | 16.61 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 272364 | ESS H440N ;R | Adder | 2.01 MW | 1.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290051 | GSG-6; E | Adder | 8.22 MW | 6.99 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295109 | WESTBROOK E | Adder | 4.4 MW | 3.74 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295111 | SUBLETTE E | Adder | 4.56 MW | 3.88 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919221 | AA1-146 | 50/50 | 7.02 MW | 7.02 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919581 | AA2-030 C | 50/50 | 41.23 MW | 41.23 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933911 | AD1-013 C | Adder | 1.4 MW | 1.19 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933912 | AD1-013 E | Adder | 2.23 MW | 1.9 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934051 | AD1-031 C O1 | Adder | 2.31 MW | 1.96 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934052 | AD1-031 E O1 | Adder | 3.76 MW | 3.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934432 | AD1-067 E | Adder | 0.43 MW | 0.37 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934972 | AD1-129 E | Adder | 0.44 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937001 | AD2-134 C | Adder | 1.99 MW | 1.69 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937002 | AD2-134 E | Adder | 7.95 MW | 6.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937311 | AD2-172 C | Adder | 2.99 MW | 2.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937312 | AD2-172 E | Adder | 4.13 MW | 3.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958911 | AF2-182 C | 50/50 | 41.62 MW | 41.62 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958912 | AF2-182 E | 50/50 | 27.75 MW | 27.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958921 | AF2-183 C | 50/50 | 7.4 MW | 7.4 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958922 | AF2-183 E | 50/50 | 11.1 MW | 11.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959101 | AF2-201 C O1 | Adder | 7.32 MW | 6.22 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959102 | AF2-201 E O1 | Adder | 21.01 MW | 17.86 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960581 | AF2-349 C | Adder | 15.01 MW | 12.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960582 | AF2-349 E | Adder | 10.01 MW | 8.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961011 | AF2-392 C O1 | 50/50 | 7.79 MW | 7.79 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961012 | AF2-392 E O1 | 50/50 | 36.47 MW | 36.47 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961021 | AF2-393 O1 | 50/50 | 13.28 MW | 13.28 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961031 | AF2-394 O1 | 50/50 | 8.85 MW | 8.85 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274715 | NELSON EC;1C | 50/50 | 7.53 MW | 7.53 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274716 | NELSON EC;1S | 50/50 | 5.49 MW | 5.49 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274717 | NELSON EC;2C | 50/50 | 7.59 MW | 7.59 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274718 | NELSON EC;2S | 50/50 | 5.54 MW | 5.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274761 | LEE CO EC;2U | 50/50 | 3.14 MW | 3.14 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274764 | LEE CO EC;5U | 50/50 | 3.15 MW | 3.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274765 | LEE CO EC;6U | 50/50 | 3.15 MW | 3.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274859 | EASYR;U1 E | Adder | 20.86 MW | 17.73 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274860 | EASYR;U2 E | Adder | 20.86 MW | 17.73 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293516 | O-009 E1 | Adder | 16.04 MW | 13.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293517 | O-009 E2 | Adder | 8.15 MW | 6.92 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293518 | O-009 E3 | Adder | 8.97 MW | 7.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293715 | O-029 E | Adder | 17.15 MW | 14.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293716 | O-029 E | Adder | 9.4 MW | 7.99 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293717 | O-029 E | Adder | 8.64 MW | 7.34 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294401 | BSHIL;1U E | Adder | 6.98 MW | 5.94 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294410 | BSHIL;2U E | Adder | 6.98 MW | 5.94 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294763 | P-046 E | Adder | 11.39 MW | 9.68 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 916221 | Z1-073 E | Adder | 4.27 MW | 3.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 925581 | AC1-033 C | Adder | 1.14 MW | 0.97 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 925582 | AC1-033 E | Adder | 7.66 MW | 6.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930482 | AB1-089 CT | Adder | 45.39 MW | 38.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930483 | AB1-089 ST | Adder | 36.09 MW | 30.67 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938861 | AE1-114 C O1 | Adder | 5.75 MW | 4.88 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938862 | AE1-114 E O1 | Adder | 19.61 MW | 16.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939051 | AE1-134 1 | 50/50 | 3.2 MW | 3.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939061 | AE1-134 2 | 50/50 | 3.2 MW | 3.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940501 | AE2-035 C | Adder | 2.99 MW | 2.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940502 | AE2-035 E | Adder | 4.13 MW | 3.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946151 | AF1-280 C O1 | 50/50 | 31.68 MW | 31.68 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946152 | AF1-280 E O1 | 50/50 | 14.57 MW | 14.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946161 | AF1-281 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946162 | AF1-281 E O1 | 50/50 | 3.93 MW | 3.93 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946321 | AF1-296 C O1 | Adder | 7.08 MW | 6.02 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946322 | AF1-296 E O1 | Adder | 33.16 MW | 28.19 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946501 | AF1-314 C | Adder | 5.3 MW | 4.5 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946502 | AF1-314 E | Adder | 24.88 MW | 21.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946671 | AF1-331 | Adder | 1.82 MW | 1.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990901 | L-005 E | Adder | 9.46 MW | 8.04 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965082 | AG1-373 BAT | 50/50 | 11.42 MW | 11.42 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965062 | AG1-371 BAT | 50/50 | 34.25 MW | 34.25 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951381 | J504 | External Queue | 4.22 MW | 4.22 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951421 | J514 | External Queue | 2.51 MW | 2.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951511 | J530 C | External Queue | 3.88 MW | 3.88 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951512 | J530 E | External Queue | 15.5 MW | 15.5 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953922 | J855 E | External Queue | 6.83 MW | 6.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 955971 | J1084 | External Queue | 22.66 MW | 22.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 956411 | J1131 | External Queue | 11.85 MW | 11.85 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990726 | J1377 | External Queue | 7.58 MW | 7.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990947 | J1432 E | External Queue | 33.18 MW | 33.18 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 991091 | J1477 | External Queue | 5.93 MW | 5.93 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.36 MW | 0.36 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.42 MW | 0.42 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.35 MW | 3.35 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 61.98 MW | 61.98 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.54 MW | 17.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.1 MW | 0.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.44 MW | 0.44 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.3 MW | 4.3 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.26 MW | 0.26 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.2 MW | 15.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.83 MW | 2.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.96 MW | 1.96 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.09 MW | 1.09 MW |
| Details for CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 272364 | ESS H440N ;R | Adder | -2.75 MW | -2.34 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 919581 | AA2-030 C | Adder | -18.48 MW | -15.71 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937311 | AD2-172 C | Adder | -2.57 MW | -2.19 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274751 | CRETE EC ;1U | 50/50 | 6.41 MW | 6.41 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274752 | CRETE EC ;2U | 50/50 | 6.41 MW | 6.41 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274753 | CRETE EC ;3U | 50/50 | 6.41 MW | 6.41 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274754 | CRETE EC ;4U | 50/50 | 6.41 MW | 6.41 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276591 | L-013 2 | Adder | -3.83 MW | -3.26 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | -3.93 MW | -3.34 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | -3.93 MW | -3.34 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | -3.93 MW | -3.34 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925581 | AC1-033 C | Adder | -1.49 MW | -1.27 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930761 | AB1-122 CT1 | Adder | -71.88 MW | -61.1 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930771 | AB1-122 CT2 | Adder | -79.63 MW | -67.69 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940501 | AE2-035 C | Adder | -2.57 MW | -2.19 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966823 | AG1-553 BAT | 50/50 | 18.18 MW | 18.18 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962013 | AG1-044 BAT | 50/50 | 0.07 MW | 0.07 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961022 | AF2-393 BAT | 50/50 | 7.11 MW | 7.11 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961032 | AF2-394 BAT | 50/50 | 4.74 MW | 4.74 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958923 | AF2-183 BAT | 50/50 | 9.55 MW | 9.55 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946163 | AF1-281 BAT | 50/50 | 2.39 MW | 2.39 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965082 | AG1-373 BAT | 50/50 | 3.12 MW | 3.12 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965062 | AG1-371 BAT | 50/50 | 9.35 MW | 9.35 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943803 | AF1-048 BAT | 50/50 | 6.67 MW | 6.67 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920273 | AA2-123 BAT | 50/50 | 2.56 MW | 2.56 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276172 | Z1-108 BAT | 50/50 | 2.61 MW | 2.61 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957333 | AF2-027 BAT | 50/50 | 6.55 MW | 6.55 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959353 | AF2-226 BAT | 50/50 | 7.61 MW | 7.61 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960283 | AF2-319 BAT | 50/50 | 7.61 MW | 7.61 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966443 | AG1-513 BAT | 50/50 | 1.32 MW | 1.32 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960382 | AF2-329 BAT | 50/50 | 5.57 MW | 5.57 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957403 | AF2-034 BAT | 50/50 | 1.42 MW | 1.42 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966093 | AG1-478 BAT | 50/50 | 1.29 MW | 1.29 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945352 | AF1-200 NFTW | 50/50 | 282.83 MW | 282.83 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958023 | AF2-096 BAT | 50/50 | 11.94 MW | 11.94 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960603 | AF2-351 BAT | 50/50 | 2.44 MW | 2.44 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958013 | AF2-095 BAT | 50/50 | 4.87 MW | 4.87 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966433 | AG1-512 BAT | 50/50 | 4.19 MW | 4.19 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 950351 | J466 | External Queue | 2.26 MW | 2.26 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 950791 | J201 C | External Queue | 0.3 MW | 0.3 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 950792 | J201 E | External Queue | 1.22 MW | 1.22 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 950871 | J246 C | External Queue | 0.11 MW | 0.11 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 950872 | J246 E | External Queue | 0.43 MW | 0.43 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 950942 | J325 E | External Queue | 0.3 MW | 0.3 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952161 | J571 | External Queue | 0.51 MW | 0.51 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952201 | J589 C | External Queue | 2.41 MW | 2.41 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952202 | J589 E | External Queue | 13.02 MW | 13.02 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952312 | J646 E | External Queue | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952401 | J752 C | External Queue | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952402 | J752 E | External Queue | 6.36 MW | 6.36 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952611 | J717 C | External Queue | 2.39 MW | 2.39 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952612 | J717 E | External Queue | 12.94 MW | 12.94 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952761 | J728 C | External Queue | 2.22 MW | 2.22 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952762 | J728 E | External Queue | 12.05 MW | 12.05 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952881 | J758 | External Queue | 15.68 MW | 15.68 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952971 | J793 | External Queue | 98.27 MW | 98.27 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953071 | J794 C | External Queue | 0.15 MW | 0.15 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953072 | J794 E | External Queue | 0.81 MW | 0.81 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953161 | J837 C | External Queue | 2.34 MW | 2.34 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953162 | J837 E | External Queue | 12.66 MW | 12.66 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953171 | J838 C | External Queue | 1.17 MW | 1.17 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953172 | J838 E | External Queue | 6.32 MW | 6.32 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953271 | J701 C | External Queue | 0.58 MW | 0.58 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953272 | J701 E | External Queue | 3.12 MW | 3.12 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953291 | J796 | External Queue | 18.26 MW | 18.26 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953321 | J799 | External Queue | 13.81 MW | 13.81 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953351 | J805 | External Queue | 10.35 MW | 10.35 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953361 | J806 | External Queue | 11.53 MW | 11.53 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953871 | J847 | External Queue | 13.56 MW | 13.56 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953941 | J857 | External Queue | 9.7 MW | 9.7 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954111 | J875 | External Queue | 11.15 MW | 11.15 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954351 | J903 | External Queue | 5.36 MW | 5.36 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954421 | J913 C | External Queue | 11.99 MW | 11.99 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954751 | J351 | External Queue | 59.84 MW | 59.84 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954941 | J968 C | External Queue | 2.34 MW | 2.34 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954942 | J968 E | External Queue | 12.65 MW | 12.65 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 955141 | J992 | External Queue | 15.11 MW | 15.11 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 955151 | J993 | External Queue | 10.33 MW | 10.33 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 955181 | J996 | External Queue | 5.85 MW | 5.85 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 955741 | J1058 | External Queue | 50.72 MW | 50.72 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 955781 | J1062 | External Queue | 10.76 MW | 10.76 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 955821 | J1067 | External Queue | 21.7 MW | 21.7 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 955841 | J1069 C | External Queue | 2.34 MW | 2.34 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 955842 | J1069 E | External Queue | 12.65 MW | 12.65 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990141 | J1224 | External Queue | 11.21 MW | 11.21 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990151 | J1226 | External Queue | 14.35 MW | 14.35 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990496 | J1323 | External Queue | 2.06 MW | 2.06 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990526 | J1329 | External Queue | 1.47 MW | 1.47 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990541 | J1332 | External Queue | 33.84 MW | 33.84 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990546 | J1333 | External Queue | 27.97 MW | 27.97 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990551 | J1334 | External Queue | 27.97 MW | 27.97 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990556 | J1335 | External Queue | 27.97 MW | 27.97 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990561 | J1336 | External Queue | 27.97 MW | 27.97 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990576 | J1339 | External Queue | 27.97 MW | 27.97 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990581 | J1340 | External Queue | 27.97 MW | 27.97 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990646 | J1355 | External Queue | 11.53 MW | 11.53 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990661 | J1358 | External Queue | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990741 | J1381 | External Queue | 14.07 MW | 14.07 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990761 | J1386 | External Queue | 18.86 MW | 18.86 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990791 | J1392 | External Queue | 8.26 MW | 8.26 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 990976 | J1447 | External Queue | 55.39 MW | 55.39 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991111 | J1481 | External Queue | 14.07 MW | 14.07 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991166 | J1527 | External Queue | 15.9 MW | 15.9 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991176 | J1571 | External Queue | 12.81 MW | 12.81 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991181 | J1586 | External Queue | 38.98 MW | 38.98 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991226 | J1663 | External Queue | 16.0 MW | 16.0 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991186 | J1593 | External Queue | 10.45 MW | 10.45 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991241 | J1678 | External Queue | 6.33 MW | 6.33 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991246 | J1684 | External Queue | 24.61 MW | 24.61 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991271 | J1724 | External Queue | 13.18 MW | 13.18 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991281 | J1726 | External Queue | 19.63 MW | 19.63 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991296 | J1743 | External Queue | 24.81 MW | 24.81 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991311 | J1772 | External Queue | 14.99 MW | 14.99 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991331 | J1785 | External Queue | 8.74 MW | 8.74 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 991336 | J1802 | External Queue | 14.24 MW | 14.24 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.46 MW | 0.46 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 4.61 MW | 4.61 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 2.37 MW | 2.37 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.29 MW | 7.29 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 4.86 MW | 4.86 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.68 MW | 0.68 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 4.63 MW | 4.63 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 9.57 MW | 9.57 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| CRETE EC ;BP-E FRANKFO; B 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 12.46 MW | 12.46 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961651 | AG1-005 C O1 | Adder | 12.46 MW | 10.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961652 | AG1-005 E O1 | Adder | 8.31 MW | 7.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962721 | AG1-121 C O1 | Adder | 4.27 MW | 3.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962722 | AG1-121 E O1 | Adder | 19.98 MW | 16.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 963831 | AG1-236 C | 50/50 | 3.92 MW | 3.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 963832 | AG1-236 E | 50/50 | 26.24 MW | 26.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 964581 | AG1-321 C O1 | Adder | 11.85 MW | 10.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 964582 | AG1-321 E O1 | Adder | 6.9 MW | 5.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 966821 | AG1-553 C O1 | Adder | 19.15 MW | 16.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 966822 | AG1-553 E O1 | Adder | 3.86 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965061 | AG1-371 | Adder | 1.99 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965081 | AG1-373 | Adder | 0.66 MW | 0.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965091 | AG1-374 C | 50/50 | 21.84 MW | 21.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965092 | AG1-374 E | 50/50 | 14.56 MW | 14.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965331 | AG1-398 | 50/50 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965341 | AG1-399 C | 50/50 | 7.19 MW | 7.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965342 | AG1-399 E | 50/50 | 33.66 MW | 33.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965351 | AG1-400 | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965371 | AG1-402 | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965391 | AG1-404 | 50/50 | 13.62 MW | 13.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965661 | AG1-434 C O1 | Adder | 2.4 MW | 2.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965662 | AG1-434 E O1 | Adder | 11.22 MW | 9.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965671 | AG1-435 C O1 | Adder | 2.91 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965672 | AG1-435 E O1 | Adder | 13.62 MW | 11.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965911 | AG1-460 C | 50/50 | 2.05 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965912 | AG1-460 E | 50/50 | 3.07 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965931 | AG1-462 C O1 | Adder | 12.39 MW | 10.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965932 | AG1-462 E O1 | Adder | 8.26 MW | 7.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 272364 | ESS H440N ;R | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290051 | GSG-6; E | Adder | 5.74 MW | 4.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290261 | S-027 E | 50/50 | 19.21 MW | 19.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290265 | S-028 E | 50/50 | 19.21 MW | 19.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 295109 | WESTBROOK E | Adder | 3.07 MW | 2.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 295111 | SUBLETTE E | Adder | 1.64 MW | 1.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 919581 | AA2-030 C | Adder | 11.53 MW | 9.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925771 | AC1-053 C | 50/50 | 3.92 MW | 3.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925772 | AC1-053 E | 50/50 | 26.24 MW | 26.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 927202 | AC1-214 E O1 | Adder | 5.02 MW | 4.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 933911 | AD1-013 C | Adder | 1.01 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 933912 | AD1-013 E | Adder | 1.61 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934051 | AD1-031 C O1 | Adder | 2.21 MW | 1.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934052 | AD1-031 E O1 | Adder | 3.61 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934432 | AD1-067 E | Adder | 0.3 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 935141 | AD1-148 | 50/50 | 5.64 MW | 5.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936771 | AD2-100 C | 50/50 | 22.11 MW | 22.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936772 | AD2-100 E | 50/50 | 14.74 MW | 14.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936971 | AD2-131 C | 50/50 | 1.46 MW | 1.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936972 | AD2-131 E | 50/50 | 7.32 MW | 7.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937001 | AD2-134 C | Adder | 1.39 MW | 1.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937002 | AD2-134 E | Adder | 5.55 MW | 4.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937311 | AD2-172 C | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937312 | AD2-172 E | Adder | 1.98 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942111 | AE2-223 C | 50/50 | 2.19 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942112 | AE2-223 E | 50/50 | 14.69 MW | 14.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942481 | AE2-261 C | 50/50 | 30.63 MW | 30.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942482 | AE2-261 E | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 945871 | AF1-252 O1 | 50/50 | 11.82 MW | 11.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 945881 | AF1-253 | 50/50 | 8.19 MW | 8.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946542 | AF1-318 E O1 | Adder | 20.54 MW | 17.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958911 | AF2-182 C | Adder | 12.9 MW | 10.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958912 | AF2-182 E | Adder | 8.6 MW | 7.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958921 | AF2-183 C | Adder | 2.29 MW | 1.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958922 | AF2-183 E | Adder | 3.44 MW | 2.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959081 | AF2-199 C | Adder | 3.98 MW | 3.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959082 | AF2-199 E | Adder | 1.99 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959091 | AF2-200 C O1 | Adder | 7.96 MW | 6.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959092 | AF2-200 E O1 | Adder | 5.31 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959101 | AF2-201 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959102 | AF2-201 E O1 | Adder | 10.09 MW | 8.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959341 | AF2-225 C | 50/50 | 7.09 MW | 7.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959342 | AF2-225 E | 50/50 | 9.79 MW | 9.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959611 | AF2-252 C | 50/50 | 2.43 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959612 | AF2-252 E | 50/50 | 3.64 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960141 | AF2-305 | 50/50 | 1.37 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960261 | AF2-317 | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960611 | AF2-352 C | 50/50 | 2.43 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960612 | AF2-352 E | 50/50 | 3.64 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961011 | AF2-392 C O1 | Adder | 2.57 MW | 2.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961012 | AF2-392 E O1 | Adder | 12.02 MW | 10.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961021 | AF2-393 O1 | Adder | 4.38 MW | 3.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961031 | AF2-394 O1 | Adder | 2.92 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274650 | KINCAID ;1U | 50/50 | 16.0 MW | 16.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274651 | KINCAID ;2U | 50/50 | 15.99 MW | 15.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274853 | TWINGROVE;U1 | 50/50 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274854 | TWINGROVE;U2 | 50/50 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274859 | EASYR;U1 E | Adder | 6.81 MW | 5.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274860 | EASYR;U2 E | Adder | 6.81 MW | 5.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274880 | RADFORD R;1U | 50/50 | 1.16 MW | 1.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 276615 | W2-048 GEN | 50/50 | 8.02 MW | 8.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 276621 | X2-022 GEN | 50/50 | 28.76 MW | 28.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293516 | O-009 E1 | Adder | 6.22 MW | 5.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293517 | O-009 E2 | Adder | 3.16 MW | 2.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293518 | O-009 E3 | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293715 | O-029 E | Adder | 6.65 MW | 5.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293716 | O-029 E | Adder | 3.65 MW | 3.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293717 | O-029 E | Adder | 3.35 MW | 2.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293771 | O-035 E | Adder | 4.92 MW | 4.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293777 | CAYUG;1U E | Adder | 10.27 MW | 8.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293778 | CAYUG;2U E | Adder | 10.27 MW | 8.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293798 | W4-005 E | 50/50 | 38.82 MW | 38.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294401 | BSHIL;1U E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294410 | BSHIL;2U E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294763 | P-046 E | Adder | 5.47 MW | 4.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 916211 | Z1-072 E | Adder | 3.73 MW | 3.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 916221 | Z1-073 E | Adder | 2.98 MW | 2.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 917502 | Z2-087 E | 50/50 | 19.59 MW | 19.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924042 | AB2-047 E O1 | 50/50 | 24.48 MW | 24.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924261 | AB2-070 C O1 | 50/50 | 3.86 MW | 3.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924262 | AB2-070 E O1 | 50/50 | 23.4 MW | 23.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925581 | AC1-033 C | Adder | 1.09 MW | 0.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925582 | AC1-033 E | Adder | 7.3 MW | 6.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930482 | AB1-089 CT | Adder | 20.14 MW | 17.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930483 | AB1-089 ST | Adder | 16.01 MW | 13.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930761 | AB1-122 CT1 | Adder | 40.35 MW | 34.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 938861 | AE1-114 C O1 | Adder | 2.38 MW | 2.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 938862 | AE1-114 E O1 | Adder | 8.12 MW | 6.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939051 | AE1-134 1 | Adder | 0.9 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939061 | AE1-134 2 | Adder | 0.9 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939401 | AE1-172 C O1 | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939402 | AE1-172 E O1 | Adder | 16.31 MW | 13.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939741 | AE1-205 C O1 | 50/50 | 9.46 MW | 9.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939742 | AE1-205 E O1 | 50/50 | 13.06 MW | 13.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 940501 | AE2-035 C | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 940502 | AE2-035 E | Adder | 1.98 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 941731 | AE2-173 O1 | 50/50 | 5.63 MW | 5.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944221 | AF1-090 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944222 | AF1-090 E O1 | 50/50 | 31.22 MW | 31.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946151 | AF1-280 C O1 | Adder | 9.82 MW | 8.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946152 | AF1-280 E O1 | Adder | 4.52 MW | 3.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946321 | AF1-296 C O1 | Adder | 2.98 MW | 2.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946322 | AF1-296 E O1 | Adder | 13.95 MW | 11.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946501 | AF1-314 C | Adder | 2.54 MW | 2.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946502 | AF1-314 E | Adder | 11.95 MW | 10.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946541 | AF1-318 C O1 | Adder | 4.39 MW | 3.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946671 | AF1-331 | Adder | 1.31 MW | 1.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957381 | AF2-032 C | 50/50 | 2.3 MW | 2.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957382 | AF2-032 E | 50/50 | 1.08 MW | 1.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957471 | AF2-041 C | Adder | 11.94 MW | 10.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957472 | AF2-041 E | Adder | 5.97 MW | 5.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957752 | AF2-069 E | Adder | 0.59 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957761 | AF2-070 C | Adder | 0.26 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957762 | AF2-070 E | Adder | 1.25 MW | 1.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958341 | AF2-128 C O1 | Adder | 1.16 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958342 | AF2-128 E O1 | Adder | 5.44 MW | 4.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990901 | L-005 E | Adder | 10.6 MW | 9.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934101 | AD2-000 1 | Adder | 3.26 MW | 2.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944202 | AF1-088 FTWR | 50/50 | 260.6 MW | 260.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942602 | AE2-276 BAT | 50/50 | 13.03 MW | 13.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 941343 | AE2-130 BAT | 50/50 | 29.76 MW | 29.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953401 | J811 | External Queue | 18.24 MW | 18.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953641 | J813 | External Queue | 40.35 MW | 40.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953881 | J848 C | External Queue | 5.27 MW | 5.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953882 | J848 E | External Queue | 28.49 MW | 28.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 954411 | J912 | External Queue | 14.3 MW | 14.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 954681 | J949 C | External Queue | 32.68 MW | 32.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 956451 | J1139 | External Queue | 20.06 MW | 20.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990056 | J1201 | External Queue | 7.03 MW | 7.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990071 | J1204 | External Queue | 65.85 MW | 65.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990271 | J1263 | External Queue | 106.84 MW | 106.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991196 | J1626 | External Queue | 27.64 MW | 27.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991266 | J1714 | External Queue | 18.43 MW | 18.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991261 | J1713 C | External Queue | 3.03 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991262 | J1713 E | External Queue | 3.46 MW | 3.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.61 MW | 3.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.65 MW | 1.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.0 MW | 15.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 69.74 MW | 69.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 68.94 MW | 68.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.87 MW | 12.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.61 MW | 1.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.25 MW | 15.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.26 MW | 1.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.93 MW | 7.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.06 MW | 2.06 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961651 | AG1-005 C O1 | Adder | 11.16 MW | 9.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961652 | AG1-005 E O1 | Adder | 7.44 MW | 6.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962691 | AG1-118 C O1 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962692 | AG1-118 E O1 | Adder | 8.76 MW | 7.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962701 | AG1-119 C | Adder | 14.23 MW | 12.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962702 | AG1-119 E | Adder | 9.48 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962711 | AG1-120 C O1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962712 | AG1-120 E O1 | Adder | 3.56 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962721 | AG1-121 C O1 | Adder | 4.04 MW | 3.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962722 | AG1-121 E O1 | Adder | 18.88 MW | 16.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962781 | AG1-127 C | Adder | 4.17 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962782 | AG1-127 E | Adder | 2.77 MW | 2.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 966821 | AG1-553 C O1 | Adder | 18.15 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 966822 | AG1-553 E O1 | Adder | 3.66 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965061 | AG1-371 | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965081 | AG1-373 | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965141 | AG1-379 C | Adder | 20.95 MW | 17.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965142 | AG1-379 E | Adder | 9.59 MW | 8.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965551 | AG1-423 C O1 | Adder | 9.49 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965552 | AG1-423 E O1 | Adder | 6.32 MW | 5.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965661 | AG1-434 C O1 | Adder | 2.81 MW | 2.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965662 | AG1-434 E O1 | Adder | 13.15 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965671 | AG1-435 C O1 | Adder | 2.8 MW | 2.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965672 | AG1-435 E O1 | Adder | 13.08 MW | 11.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965931 | AG1-462 C O1 | Adder | 11.75 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965932 | AG1-462 E O1 | Adder | 7.83 MW | 6.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 966441 | AG1-513 C | Adder | 0.3 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 966442 | AG1-513 E | Adder | 0.44 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 272364 | ESS H440N ;R | Adder | 1.63 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 290021 | O50 E | Adder | 24.43 MW | 20.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 290051 | GSG-6; E | Adder | 6.51 MW | 5.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 295109 | WESTBROOK E | Adder | 3.49 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 295111 | SUBLETTE E | Adder | 1.77 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 918052 | AA1-018 E OP | Adder | 18.15 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 919581 | AA2-030 C | Adder | 12.28 MW | 10.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 920272 | AA2-123 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 926331 | AC1-110 1 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 926341 | AC1-110 2 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 927091 | AC1-204 GEN1 | 50/50 | 19.36 MW | 19.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 927093 | AC1-204 GEN2 | 50/50 | 19.47 MW | 19.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 927202 | AC1-214 E O1 | Adder | 4.78 MW | 4.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 927451 | AC1-142A 1 | Adder | 3.72 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 927461 | AC1-142A 2 | Adder | 3.74 MW | 3.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 933911 | AD1-013 C | Adder | 1.14 MW | 0.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 933912 | AD1-013 E | Adder | 1.83 MW | 1.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 933931 | AD1-016 C | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 933932 | AD1-016 E | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934051 | AD1-031 C O1 | Adder | 2.19 MW | 1.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934052 | AD1-031 E O1 | Adder | 3.57 MW | 3.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934432 | AD1-067 E | Adder | 0.34 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934971 | AD1-129 C | Adder | 0.59 MW | 0.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934972 | AD1-129 E | Adder | 0.39 MW | 0.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 936291 | AD2-038 C O1 | Adder | 3.71 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 936292 | AD2-038 E O1 | Adder | 17.39 MW | 14.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 936511 | AD2-066 C O1 | Adder | 6.37 MW | 5.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 936512 | AD2-066 E O1 | Adder | 4.24 MW | 3.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937001 | AD2-134 C | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937002 | AD2-134 E | Adder | 6.3 MW | 5.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937311 | AD2-172 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937312 | AD2-172 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937401 | AD2-194 1 | Adder | 12.23 MW | 10.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937411 | AD2-194 2 | 50/50 | 12.29 MW | 12.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942421 | AE2-255 C O1 | Adder | 3.82 MW | 3.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942422 | AE2-255 E O1 | Adder | 11.45 MW | 9.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942651 | AE2-281 C O1 | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942652 | AE2-281 E O1 | Adder | 6.05 MW | 5.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942991 | AE2-321 C | Adder | 5.32 MW | 4.52 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942992 | AE2-321 E | Adder | 2.62 MW | 2.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 943801 | AF1-048 C | Adder | 2.48 MW | 2.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 943802 | AF1-048 E | Adder | 1.66 MW | 1.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946542 | AF1-318 E O1 | Adder | 18.59 MW | 15.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958481 | AF2-142 C | Adder | 12.52 MW | 10.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958482 | AF2-142 E | Adder | 8.35 MW | 7.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958491 | AF2-143 C | Adder | 12.66 MW | 10.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958492 | AF2-143 E | Adder | 8.44 MW | 7.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958911 | AF2-182 C | Adder | 14.09 MW | 11.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958912 | AF2-182 E | Adder | 9.39 MW | 7.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958921 | AF2-183 C | Adder | 2.5 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958922 | AF2-183 E | Adder | 3.76 MW | 3.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959081 | AF2-199 C | Adder | 4.82 MW | 4.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959082 | AF2-199 E | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959091 | AF2-200 C O1 | Adder | 9.63 MW | 8.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959092 | AF2-200 E O1 | Adder | 6.42 MW | 5.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959101 | AF2-201 C O1 | Adder | 4.02 MW | 3.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959102 | AF2-201 E O1 | Adder | 11.54 MW | 9.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959351 | AF2-226 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959352 | AF2-226 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960281 | AF2-319 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960282 | AF2-319 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960581 | AF2-349 C | Adder | 14.25 MW | 12.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960582 | AF2-349 E | Adder | 9.5 MW | 8.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960721 | AF2-363 C O1 | Adder | 3.67 MW | 3.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960722 | AF2-363 E O1 | Adder | 2.44 MW | 2.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960751 | AF2-366 C | Adder | 4.16 MW | 3.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960752 | AF2-366 E | Adder | 2.77 MW | 2.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961011 | AF2-392 C O1 | Adder | 2.75 MW | 2.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961012 | AF2-392 E O1 | Adder | 12.85 MW | 10.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961021 | AF2-393 O1 | Adder | 4.68 MW | 3.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961031 | AF2-394 O1 | Adder | 3.12 MW | 2.65 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274728 | ELWOOD EC;5P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274729 | ELWOOD EC;1P | 50/50 | 5.21 MW | 5.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274730 | ELWOOD EC;6P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274732 | ELWOOD EC;7P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274734 | ELWOOD EC;8P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274736 | ELWOOD EC;9P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274859 | EASYR;U1 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274860 | EASYR;U2 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274861 | TOP CROP ;1U | 50/50 | 0.93 MW | 0.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274862 | TOP CROP ;2U | 50/50 | 1.78 MW | 1.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 276170 | Z1-108 E | Adder | 1.61 MW | 1.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 276591 | L-013 2 | Adder | 2.25 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293516 | O-009 E1 | Adder | 6.48 MW | 5.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293517 | O-009 E2 | Adder | 3.29 MW | 2.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293518 | O-009 E3 | Adder | 3.63 MW | 3.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293644 | O22 E1 | 50/50 | 24.24 MW | 24.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293645 | O22 E2 | 50/50 | 47.06 MW | 47.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293715 | O-029 E | Adder | 6.93 MW | 5.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293716 | O-029 E | Adder | 3.8 MW | 3.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293717 | O-029 E | Adder | 3.49 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293771 | O-035 E | Adder | 4.69 MW | 3.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 294401 | BSHIL;1U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 294410 | BSHIL;2U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 294763 | P-046 E | Adder | 6.25 MW | 5.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 915011 | Y3-013 1 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 915021 | Y3-013 2 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 915031 | Y3-013 3 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 916211 | Z1-072 E | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 916221 | Z1-073 E | Adder | 3.38 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 925581 | AC1-033 C | Adder | 1.08 MW | 0.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 925582 | AC1-033 E | Adder | 7.2 MW | 6.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 930482 | AB1-089 CT | Adder | 24.12 MW | 20.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 930483 | AB1-089 ST | Adder | 19.18 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 930761 | AB1-122 CT1 | Adder | 68.76 MW | 58.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 930771 | AB1-122 CT2 | Adder | 93.21 MW | 79.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938511 | AE1-070 1 | 50/50 | 14.44 MW | 14.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938521 | AE1-070 2 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938851 | AE1-113 C O1 | Adder | 10.08 MW | 8.56 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938852 | AE1-113 E O1 | Adder | 35.73 MW | 30.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938861 | AE1-114 C O1 | Adder | 2.65 MW | 2.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938862 | AE1-114 E O1 | Adder | 9.05 MW | 7.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 939051 | AE1-134 1 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 939061 | AE1-134 2 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 939321 | AE1-163 C O1 | Adder | 6.89 MW | 5.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 939322 | AE1-163 E O1 | Adder | 42.35 MW | 35.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 940501 | AE2-035 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 940502 | AE2-035 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 941131 | AE2-107 C | Adder | 3.95 MW | 3.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 941132 | AE2-107 E | Adder | 2.63 MW | 2.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946151 | AF1-280 C O1 | Adder | 10.73 MW | 9.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946152 | AF1-280 E O1 | Adder | 4.93 MW | 4.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946161 | AF1-281 C O1 | Adder | 0.24 MW | 0.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946162 | AF1-281 E O1 | Adder | 1.33 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946321 | AF1-296 C O1 | Adder | 2.86 MW | 2.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946322 | AF1-296 E O1 | Adder | 13.39 MW | 11.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946501 | AF1-314 C | Adder | 2.91 MW | 2.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946502 | AF1-314 E | Adder | 13.66 MW | 11.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946541 | AF1-318 C O1 | Adder | 3.97 MW | 3.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946661 | AF1-330 C | Adder | 1.3 MW | 1.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946662 | AF1-330 E | Adder | 0.29 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946671 | AF1-331 | Adder | 1.48 MW | 1.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957331 | AF2-027 C | Adder | 1.65 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957332 | AF2-027 E | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957401 | AF2-034 C | Adder | 1.87 MW | 1.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957402 | AF2-034 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957471 | AF2-041 C | Adder | 14.45 MW | 12.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957472 | AF2-041 E | Adder | 7.23 MW | 6.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957751 | AF2-069 C | Adder | 0.17 MW | 0.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957752 | AF2-069 E | Adder | 0.56 MW | 0.48 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957762 | AF2-070 E | Adder | 1.19 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958341 | AF2-128 C O1 | Adder | 1.04 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958342 | AF2-128 E O1 | Adder | 4.87 MW | 4.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 990901 | L-005 E | Adder | 10.43 MW | 8.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934101 | AD2-000 1 | Adder | 5.56 MW | 4.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934111 | AD2-000 2 | Adder | 7.54 MW | 6.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 290108 | LEEDK;1U E | Adder | 14.62 MW | 12.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958023 | AF2-096 BAT | Adder | 8.72 MW | 7.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 964362 | AG1-298 BAT | Adder | 42.67 MW | 36.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 954981 | J974 C | External Queue | 3.01 MW | 3.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 954982 | J974 E | External Queue | 16.3 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.29 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.03 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.08 MW | 0.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.34 MW | 42.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.14 MW | 15.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.05 MW | 1.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.18 MW | 0.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.11 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.23 MW | 0.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.68 MW | 9.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.57 MW | 0.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.76 MW | 6.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.35 MW | 0.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.51 MW | 2.51 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961651 | AG1-005 C O1 | 50/50 | 22.19 MW | 22.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961652 | AG1-005 E O1 | 50/50 | 14.79 MW | 14.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962721 | AG1-121 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962722 | AG1-121 E O1 | 50/50 | 44.72 MW | 44.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966821 | AG1-553 C O1 | 50/50 | 23.66 MW | 23.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966822 | AG1-553 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965141 | AG1-379 C | 50/50 | 36.67 MW | 36.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965142 | AG1-379 E | 50/50 | 16.79 MW | 16.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965672 | AG1-435 E O1 | 50/50 | 31.26 MW | 31.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965931 | AG1-462 C O1 | 50/50 | 15.32 MW | 15.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965932 | AG1-462 E O1 | 50/50 | 10.21 MW | 10.21 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 290021 | O50 E | 50/50 | 42.77 MW | 42.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 918052 | AA1-018 E OP | 50/50 | 64.27 MW | 64.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926822 | AC1-168 E O1 | 50/50 | 10.02 MW | 10.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927202 | AC1-214 E O1 | 50/50 | 10.86 MW | 10.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934051 | AD1-031 C O1 | 50/50 | 5.34 MW | 5.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936292 | AD2-038 E O1 | 50/50 | 60.89 MW | 60.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942421 | AE2-255 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942422 | AE2-255 E O1 | 50/50 | 20.05 MW | 20.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942652 | AE2-281 E O1 | 50/50 | 21.18 MW | 21.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946542 | AF1-318 E O1 | 50/50 | 37.91 MW | 37.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958481 | AF2-142 C | 50/50 | 44.33 MW | 44.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958482 | AF2-142 E | 50/50 | 29.55 MW | 29.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958491 | AF2-143 C | 50/50 | 44.34 MW | 44.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958492 | AF2-143 E | 50/50 | 29.56 MW | 29.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959351 | AF2-226 C | 50/50 | 9.82 MW | 9.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959352 | AF2-226 E | 50/50 | 14.73 MW | 14.73 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960281 | AF2-319 C | 50/50 | 9.82 MW | 9.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960282 | AF2-319 E | 50/50 | 14.73 MW | 14.73 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274677 | POWERTON ;5U | 50/50 | 64.38 MW | 64.38 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274678 | POWERTON ;6U | 50/50 | 64.56 MW | 64.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274701 | CORDOVA ;1S | 50/50 | 3.08 MW | 3.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274861 | TOP CROP ;1U | 50/50 | 1.54 MW | 1.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274862 | TOP CROP ;2U | 50/50 | 2.94 MW | 2.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274891 | OTTER CRK;1U | 50/50 | 1.64 MW | 1.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293516 | O-009 E1 | Adder | 7.88 MW | 6.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293517 | O-009 E2 | Adder | 4.0 MW | 3.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293518 | O-009 E3 | Adder | 4.4 MW | 3.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293644 | O22 E1 | 50/50 | 40.08 MW | 40.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293645 | O22 E2 | 50/50 | 77.79 MW | 77.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293715 | O-029 E | Adder | 8.42 MW | 7.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293716 | O-029 E | Adder | 4.62 MW | 3.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293717 | O-029 E | Adder | 4.24 MW | 3.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293771 | O-035 E | 50/50 | 10.64 MW | 10.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294401 | BSHIL;1U E | 50/50 | 15.9 MW | 15.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294410 | BSHIL;2U E | 50/50 | 15.9 MW | 15.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 916211 | Z1-072 E | 50/50 | 8.05 MW | 8.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925581 | AC1-033 C | 50/50 | 2.6 MW | 2.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925582 | AC1-033 E | 50/50 | 17.43 MW | 17.43 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 930761 | AB1-122 CT1 | 50/50 | 395.01 MW | 395.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938851 | AE1-113 C O1 | 50/50 | 17.64 MW | 17.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938852 | AE1-113 E O1 | 50/50 | 62.55 MW | 62.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939321 | AE1-163 C O1 | 50/50 | 24.14 MW | 24.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939322 | AE1-163 E O1 | 50/50 | 148.28 MW | 148.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946321 | AF1-296 C O1 | Adder | 3.45 MW | 2.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946322 | AF1-296 E O1 | Adder | 16.16 MW | 13.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946541 | AF1-318 C O1 | 50/50 | 8.1 MW | 8.1 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958342 | AF2-128 E O1 | 50/50 | 9.69 MW | 9.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990901 | L-005 E | 50/50 | 27.78 MW | 27.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934101 | AD2-000 1 | 50/50 | 31.94 MW | 31.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.49 MW | 11.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.6 MW | 37.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.43 MW | 38.43 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.55 MW | 0.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.22 MW | 7.22 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.7 MW | 14.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.92 MW | 0.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.08 MW | 4.08 MW |
| Details for 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961651 | AG1-005 C O1 | 50/50 | 22.19 MW | 22.19 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961652 | AG1-005 E O1 | 50/50 | 14.79 MW | 14.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962721 | AG1-121 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962722 | AG1-121 E O1 | 50/50 | 44.72 MW | 44.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966821 | AG1-553 C O1 | 50/50 | 23.66 MW | 23.66 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966822 | AG1-553 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965141 | AG1-379 C | 50/50 | 36.67 MW | 36.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965142 | AG1-379 E | 50/50 | 16.79 MW | 16.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965672 | AG1-435 E O1 | 50/50 | 31.26 MW | 31.26 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965931 | AG1-462 C O1 | 50/50 | 15.32 MW | 15.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965932 | AG1-462 E O1 | 50/50 | 10.21 MW | 10.21 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 290021 | O50 E | 50/50 | 42.77 MW | 42.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 918052 | AA1-018 E OP | 50/50 | 64.27 MW | 64.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926822 | AC1-168 E O1 | 50/50 | 10.02 MW | 10.02 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927202 | AC1-214 E O1 | 50/50 | 10.86 MW | 10.86 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934051 | AD1-031 C O1 | 50/50 | 5.34 MW | 5.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936292 | AD2-038 E O1 | 50/50 | 60.89 MW | 60.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942421 | AE2-255 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942422 | AE2-255 E O1 | 50/50 | 20.05 MW | 20.05 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942652 | AE2-281 E O1 | 50/50 | 21.18 MW | 21.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946542 | AF1-318 E O1 | 50/50 | 37.91 MW | 37.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958481 | AF2-142 C | 50/50 | 44.33 MW | 44.33 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958482 | AF2-142 E | 50/50 | 29.55 MW | 29.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958491 | AF2-143 C | 50/50 | 44.34 MW | 44.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958492 | AF2-143 E | 50/50 | 29.56 MW | 29.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959351 | AF2-226 C | 50/50 | 9.82 MW | 9.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959352 | AF2-226 E | 50/50 | 14.73 MW | 14.73 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960281 | AF2-319 C | 50/50 | 9.82 MW | 9.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960282 | AF2-319 E | 50/50 | 14.73 MW | 14.73 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274677 | POWERTON ;5U | 50/50 | 64.38 MW | 64.38 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274678 | POWERTON ;6U | 50/50 | 64.56 MW | 64.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274701 | CORDOVA ;1S | 50/50 | 3.08 MW | 3.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274861 | TOP CROP ;1U | 50/50 | 1.54 MW | 1.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274862 | TOP CROP ;2U | 50/50 | 2.94 MW | 2.94 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274891 | OTTER CRK;1U | 50/50 | 1.64 MW | 1.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293516 | O-009 E1 | Adder | 7.88 MW | 6.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293517 | O-009 E2 | Adder | 4.0 MW | 3.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293518 | O-009 E3 | Adder | 4.4 MW | 3.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293644 | O22 E1 | 50/50 | 40.08 MW | 40.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293645 | O22 E2 | 50/50 | 77.79 MW | 77.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293715 | O-029 E | Adder | 8.42 MW | 7.16 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293716 | O-029 E | Adder | 4.62 MW | 3.92 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293717 | O-029 E | Adder | 4.24 MW | 3.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293771 | O-035 E | 50/50 | 10.64 MW | 10.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294401 | BSHIL;1U E | 50/50 | 15.9 MW | 15.9 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294410 | BSHIL;2U E | 50/50 | 15.9 MW | 15.9 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 916211 | Z1-072 E | 50/50 | 8.05 MW | 8.05 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925581 | AC1-033 C | 50/50 | 2.6 MW | 2.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925582 | AC1-033 E | 50/50 | 17.43 MW | 17.43 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 930761 | AB1-122 CT1 | Adder | -179.99 MW | -152.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938851 | AE1-113 C O1 | 50/50 | 17.64 MW | 17.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938852 | AE1-113 E O1 | 50/50 | 62.55 MW | 62.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939321 | AE1-163 C O1 | 50/50 | 24.14 MW | 24.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939322 | AE1-163 E O1 | 50/50 | 148.28 MW | 148.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946321 | AF1-296 C O1 | Adder | 3.45 MW | 2.93 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946322 | AF1-296 E O1 | Adder | 16.16 MW | 13.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946541 | AF1-318 C O1 | 50/50 | 8.1 MW | 8.1 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958342 | AF2-128 E O1 | 50/50 | 9.69 MW | 9.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990901 | L-005 E | 50/50 | 27.78 MW | 27.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.49 MW | 11.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.6 MW | 37.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.43 MW | 38.43 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.55 MW | 0.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.22 MW | 7.22 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.7 MW | 14.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.92 MW | 0.92 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.08 MW | 4.08 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961651 | AG1-005 C O1 | 50/50 | 22.22 MW | 22.22 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961652 | AG1-005 E O1 | 50/50 | 14.81 MW | 14.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962721 | AG1-121 C O1 | 50/50 | 9.57 MW | 9.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962722 | AG1-121 E O1 | 50/50 | 44.77 MW | 44.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966821 | AG1-553 C O1 | 50/50 | 23.71 MW | 23.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966822 | AG1-553 E O1 | 50/50 | 4.78 MW | 4.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965141 | AG1-379 C | 50/50 | 36.7 MW | 36.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965142 | AG1-379 E | 50/50 | 16.8 MW | 16.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965672 | AG1-435 E O1 | 50/50 | 31.29 MW | 31.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965931 | AG1-462 C O1 | 50/50 | 15.35 MW | 15.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965932 | AG1-462 E O1 | 50/50 | 10.23 MW | 10.23 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 290021 | O50 E | 50/50 | 42.8 MW | 42.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926822 | AC1-168 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927202 | AC1-214 E O1 | 50/50 | 10.87 MW | 10.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.35 MW | 5.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936292 | AD2-038 E O1 | 50/50 | 60.91 MW | 60.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942421 | AE2-255 C O1 | 50/50 | 6.69 MW | 6.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942422 | AE2-255 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942652 | AE2-281 E O1 | 50/50 | 21.19 MW | 21.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946542 | AF1-318 E O1 | 50/50 | 37.96 MW | 37.96 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958491 | AF2-143 C | 50/50 | 44.35 MW | 44.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958492 | AF2-143 E | 50/50 | 29.57 MW | 29.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274662 | QUAD CITI;1U | 50/50 | 15.52 MW | 15.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274677 | POWERTON ;5U | 50/50 | 64.4 MW | 64.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274678 | POWERTON ;6U | 50/50 | 64.59 MW | 64.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274701 | CORDOVA ;1S | 50/50 | 3.09 MW | 3.09 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293516 | O-009 E1 | Adder | 7.89 MW | 6.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293517 | O-009 E2 | Adder | 4.01 MW | 3.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293518 | O-009 E3 | Adder | 4.41 MW | 3.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293715 | O-029 E | Adder | 8.44 MW | 7.17 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293716 | O-029 E | Adder | 4.63 MW | 3.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293717 | O-029 E | Adder | 4.25 MW | 3.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293771 | O-035 E | 50/50 | 10.65 MW | 10.65 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.91 MW | 15.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.91 MW | 15.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 916211 | Z1-072 E | 50/50 | 8.06 MW | 8.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925581 | AC1-033 C | 50/50 | 2.61 MW | 2.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925582 | AC1-033 E | 50/50 | 17.45 MW | 17.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 930761 | AB1-122 CT1 | 50/50 | 395.13 MW | 395.13 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938851 | AE1-113 C O1 | 50/50 | 17.66 MW | 17.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938852 | AE1-113 E O1 | 50/50 | 62.6 MW | 62.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939321 | AE1-163 C O1 | 50/50 | 24.15 MW | 24.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939322 | AE1-163 E O1 | 50/50 | 148.34 MW | 148.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946321 | AF1-296 C O1 | Adder | 3.46 MW | 2.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946322 | AF1-296 E O1 | Adder | 16.2 MW | 13.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946541 | AF1-318 C O1 | 50/50 | 8.11 MW | 8.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958342 | AF2-128 E O1 | 50/50 | 9.7 MW | 9.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990901 | L-005 E | 50/50 | 27.81 MW | 27.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934101 | AD2-000 1 | 50/50 | 31.95 MW | 31.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951511 | J530 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951512 | J530 E | External Queue | 15.79 MW | 15.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951821 | J541 C | External Queue | 5.02 MW | 5.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951822 | J541 E | External Queue | 27.15 MW | 27.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.7 MW | 11.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.89 MW | 37.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.61 MW | 38.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.26 MW | 7.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.37 MW | 0.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.74 MW | 14.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.78 MW | 0.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.11 MW | 4.11 MW |
| Details for 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961651 | AG1-005 C O1 | 50/50 | 22.22 MW | 22.22 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961652 | AG1-005 E O1 | 50/50 | 14.81 MW | 14.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962721 | AG1-121 C O1 | 50/50 | 9.57 MW | 9.57 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962722 | AG1-121 E O1 | 50/50 | 44.77 MW | 44.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966821 | AG1-553 C O1 | 50/50 | 23.71 MW | 23.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966822 | AG1-553 E O1 | 50/50 | 4.78 MW | 4.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965141 | AG1-379 C | 50/50 | 36.7 MW | 36.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965142 | AG1-379 E | 50/50 | 16.8 MW | 16.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965672 | AG1-435 E O1 | 50/50 | 31.29 MW | 31.29 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965911 | AG1-460 C | Adder | 0.84 MW | 0.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965912 | AG1-460 E | Adder | 1.26 MW | 1.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965931 | AG1-462 C O1 | 50/50 | 15.35 MW | 15.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965932 | AG1-462 E O1 | 50/50 | 10.23 MW | 10.23 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 290021 | O50 E | 50/50 | 42.8 MW | 42.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926822 | AC1-168 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927202 | AC1-214 E O1 | 50/50 | 10.87 MW | 10.87 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.35 MW | 5.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936292 | AD2-038 E O1 | 50/50 | 60.91 MW | 60.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942421 | AE2-255 C O1 | 50/50 | 6.69 MW | 6.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942422 | AE2-255 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942481 | AE2-261 C | Adder | 12.56 MW | 10.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942482 | AE2-261 E | Adder | 8.38 MW | 7.12 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942652 | AE2-281 E O1 | 50/50 | 21.19 MW | 21.19 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946542 | AF1-318 E O1 | 50/50 | 37.96 MW | 37.96 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958491 | AF2-143 C | 50/50 | 44.35 MW | 44.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958492 | AF2-143 E | 50/50 | 29.57 MW | 29.57 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274662 | QUAD CITI;1U | 50/50 | 15.52 MW | 15.52 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274677 | POWERTON ;5U | 50/50 | 64.4 MW | 64.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274678 | POWERTON ;6U | 50/50 | 64.59 MW | 64.59 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274701 | CORDOVA ;1S | 50/50 | 3.09 MW | 3.09 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293516 | O-009 E1 | Adder | 7.89 MW | 6.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293517 | O-009 E2 | Adder | 4.01 MW | 3.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293518 | O-009 E3 | Adder | 4.41 MW | 3.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293715 | O-029 E | Adder | 8.44 MW | 7.17 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293716 | O-029 E | Adder | 4.63 MW | 3.93 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293717 | O-029 E | Adder | 4.25 MW | 3.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293771 | O-035 E | 50/50 | 10.65 MW | 10.65 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.91 MW | 15.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.91 MW | 15.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 916211 | Z1-072 E | 50/50 | 8.06 MW | 8.06 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925581 | AC1-033 C | 50/50 | 2.61 MW | 2.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925582 | AC1-033 E | 50/50 | 17.45 MW | 17.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 930761 | AB1-122 CT1 | Adder | -179.87 MW | -152.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938851 | AE1-113 C O1 | 50/50 | 17.66 MW | 17.66 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938852 | AE1-113 E O1 | 50/50 | 62.6 MW | 62.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939321 | AE1-163 C O1 | 50/50 | 24.15 MW | 24.15 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939322 | AE1-163 E O1 | 50/50 | 148.34 MW | 148.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946321 | AF1-296 C O1 | Adder | 3.46 MW | 2.94 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946322 | AF1-296 E O1 | Adder | 16.2 MW | 13.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946541 | AF1-318 C O1 | 50/50 | 8.11 MW | 8.11 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957381 | AF2-032 C | Adder | 0.96 MW | 0.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957382 | AF2-032 E | Adder | 0.45 MW | 0.38 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958342 | AF2-128 E O1 | 50/50 | 9.7 MW | 9.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990901 | L-005 E | 50/50 | 27.81 MW | 27.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951031 | J344 C | External Queue | 2.36 MW | 2.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951032 | J344 E | External Queue | 7.09 MW | 7.09 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951511 | J530 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951512 | J530 E | External Queue | 15.79 MW | 15.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951821 | J541 C | External Queue | 5.02 MW | 5.02 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951822 | J541 E | External Queue | 27.15 MW | 27.15 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951841 | J555 C | External Queue | 1.61 MW | 1.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951842 | J555 E | External Queue | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954721 | J750 C | External Queue | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954722 | J750 E | External Queue | 9.84 MW | 9.84 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991191 | J1610 | External Queue | 7.16 MW | 7.16 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.7 MW | 11.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.89 MW | 37.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.61 MW | 38.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.26 MW | 7.26 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.37 MW | 0.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.74 MW | 14.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.78 MW | 0.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.11 MW | 4.11 MW |
Light Load Analysis
The Queue Project was evaluated as a 284.0 MW (Capacity 236.4 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 154.21 % | 155.61 % | 971.0 | B | 1510.97 | 13.59 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 154.21 % | 155.61 % | 971.0 | B | 1510.97 | 13.59 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P1-2_345-L2001__B-S-B
CONTINGENCY 'COMED_P1-2_345-L2001__B-S-B' TRIP BRANCH FROM BUS 270728 TO BUS 270766 CKT 1 /*E FRANKFO; B 345.0 - GOODINGS ;3B 345.0 TRIP BRANCH FROM BUS 270728 TO BUS 274750 CKT 1 /*E FRANKFO; B 345.0 - CRETE EC ;BP 345.0 TRIP BRANCH FROM BUS 958020 TO BUS 270728 CKT 1 /*AF2-096 TAP 345.0 - E FRANKFO; B 345.0 END |
Single | DC | 99.57 % | 100.52 % | 971.0 | B | 976.05 | 9.27 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 153.8 % | 155.12 % | 1409.0 | B | 2185.64 | 19.68 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 153.8 % | 155.12 % | 1409.0 | B | 2185.64 | 19.68 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 150.23 % | 151.63 % | 971.0 | STE | 1472.33 | 13.59 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 150.23 % | 151.63 % | 971.0 | STE | 1472.33 | 13.59 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 135.3 % | 136.42 % | 1483.0 | STE | 2023.09 | 17.22 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 135.3 % | 136.42 % | 1483.0 | STE | 2023.09 | 17.22 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
Base Case | Single | DC | 113.3 % | 114.31 % | 1091.0 | A | 1247.12 | 10.97 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
COMED_P1-2_765-L11216__-S
CONTINGENCY 'COMED_P1-2_765-L11216__-S' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 END |
Single | DC | 99.48 % | 100.35 % | 1483.0 | STE | 1488.26 | 13.04 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 143.21 % | 144.4 % | 1399.0 | B | 2020.16 | 17.22 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 143.21 % | 144.4 % | 1399.0 | B | 2020.16 | 17.22 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
Base Case | Single | DC | 113.03 % | 114.03 % | 1091.0 | A | 1244.07 | 10.97 | |
| CE/NIPS |
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
270677 to 255109 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 131.29 % | 132.4 % | 1441.0 | B | 1907.88 | 16.07 | |
| CE/NIPS |
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
270677 to 255109 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 131.29 % | 132.4 % | 1441.0 | B | 1907.88 | 16.07 | |
| CE/NIPS |
ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line
270886 to 255104 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 119.95 % | 121.07 % | 1091.0 | B | 1320.87 | 12.3 | |
| CE/NIPS |
ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line
270886 to 255104 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 119.95 % | 121.07 % | 1091.0 | B | 1320.87 | 12.3 | |
| AEP/CE |
WILTON ;-05DUMONT 765.0 kV Ckt 1 line
270644 to 243206 ckt 1 |
Base Case | Single | DC | 114.53 % | 115.53 % | 3555.0 | A | 4107.09 | 37.81 | |
| AEP/CE |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line
270771 to 243229 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 107.85 % | 109.0 % | 971.0 | B | 1058.39 | 11.13 | |
| AEP/CE |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line
270771 to 243229 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 107.85 % | 109.0 % | 971.0 | B | 1058.39 | 11.13 | |
| CE |
E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line
270729 to 274804 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 99.94 % | 100.85 % | 1483.0 | STE | 1495.67 | 13.59 | |
| CE |
E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line
270729 to 274804 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 99.94 % | 100.85 % | 1483.0 | STE | 1495.67 | 13.59 | |
| CE/NIPS |
17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line
255112 to 270886 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 99.91 % | 100.85 % | 1310.0 | B | 1321.13 | 12.3 | |
| CE/NIPS |
17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line
255112 to 270886 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 99.91 % | 100.85 % | 1310.0 | B | 1321.13 | 12.3 | |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 93.0 MW | 93.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 89.8 MW | 89.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.51 MW | 0.51 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 0.97 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.0 MW | 1.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.72 MW | 0.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.55 MW | 0.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 3.48 MW | 3.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 3.48 MW | 3.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 1.34 MW | 1.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.79 MW | 0.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.79 MW | 0.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.42 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.55 MW | 1.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.02 MW | 1.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.47 MW | 1.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.47 MW | 1.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 0.86 MW | 0.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.95 MW | 0.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 5.89 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.47 MW | 0.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 0.87 MW | 0.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 1.56 MW | 1.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 4.43 MW | 4.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 6.16 MW | 6.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 3.33 MW | 3.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 7.74 MW | 7.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 4.42 MW | 4.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 4.42 MW | 4.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 5.0 MW | 5.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 0.81 MW | 0.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.46 MW | 0.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 2.88 MW | 2.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 1.61 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 3.11 MW | 3.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 6.04 MW | 6.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 3.08 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 1.69 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.55 MW | 1.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.02 MW | 2.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 4.73 MW | 4.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 4.73 MW | 4.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 6.83 MW | 6.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 6.64 MW | 6.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 6.34 MW | 6.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 2.7 MW | 2.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 2.7 MW | 2.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 2.96 MW | 2.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.27 MW | 0.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.01 MW | 2.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.12 MW | 0.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 0.93 MW | 0.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 3.05 MW | 3.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 1.95 MW | 1.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 5.12 MW | 5.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 6.36 MW | 6.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.16 MW | 1.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 7.02 MW | 7.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 5.93 MW | 5.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 7.64 MW | 7.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 4.87 MW | 4.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.06 MW | 2.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.18 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 12.33 MW | 12.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 57.54 MW | 57.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 13.98 MW | 13.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 1.61 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 6.44 MW | 6.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 18.01 MW | 18.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 4.04 MW | 4.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 24.8 MW | 24.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 15.38 MW | 15.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 3.68 MW | 3.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.15 MW | 1.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 7.69 MW | 7.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 5.77 MW | 5.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 3.54 MW | 3.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 3.04 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.03 MW | 2.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.27 MW | 0.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 11.65 MW | 11.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 2.76 MW | 2.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 12.96 MW | 12.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 17.04 MW | 17.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.0 MW | 2.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.95 MW | 0.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.62 MW | 0.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.03 MW | 1.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 8.1 MW | 8.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 4.53 MW | 4.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 2.88 MW | 2.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 4.32 MW | 4.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.4 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 2.09 MW | 2.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 0.67 MW | 0.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 4.28 MW | 4.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.4 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 2.09 MW | 2.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 2.51 MW | 2.51 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 11.76 MW | 11.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 5.35 MW | 5.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 3.57 MW | 3.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 6.96 MW | 6.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.05 MW | 0.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 3.56 MW | 3.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 16.65 MW | 16.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 7.64 MW | 7.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 43.13 MW | 43.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 5.23 MW | 5.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.33 MW | 0.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 12.34 MW | 12.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 9.36 MW | 9.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 9.36 MW | 9.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 6.24 MW | 6.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 2.62 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 12.24 MW | 12.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 2.4 MW | 2.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 11.24 MW | 11.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965791 | AG1-447 | 80/20 | 46.86 MW | 46.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.63 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 5.42 MW | 5.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.61 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 6.8 MW | 6.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 5.44 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 8.15 MW | 8.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 13.91 MW | 13.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 2.83 MW | 2.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 4.24 MW | 4.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 0.94 MW | 0.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.41 MW | 1.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 210.26 MW | 210.26 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 93.0 MW | 93.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 89.8 MW | 89.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.51 MW | 0.51 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 0.97 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.0 MW | 1.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.72 MW | 0.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.55 MW | 0.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 3.48 MW | 3.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 3.48 MW | 3.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 1.34 MW | 1.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.79 MW | 0.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.79 MW | 0.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.42 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.55 MW | 1.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.02 MW | 1.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.47 MW | 1.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.47 MW | 1.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 0.86 MW | 0.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.95 MW | 0.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 5.89 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.47 MW | 0.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 0.87 MW | 0.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 1.56 MW | 1.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 4.43 MW | 4.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 6.16 MW | 6.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 3.33 MW | 3.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 7.74 MW | 7.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 4.42 MW | 4.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 4.42 MW | 4.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 5.0 MW | 5.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 0.81 MW | 0.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.46 MW | 0.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 2.88 MW | 2.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 1.61 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 3.11 MW | 3.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 6.04 MW | 6.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 3.08 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 1.69 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.55 MW | 1.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.02 MW | 2.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 4.73 MW | 4.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 4.73 MW | 4.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 6.83 MW | 6.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 6.64 MW | 6.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 6.34 MW | 6.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 2.7 MW | 2.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 2.7 MW | 2.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 2.96 MW | 2.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.27 MW | 0.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.01 MW | 2.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.12 MW | 0.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 0.93 MW | 0.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 3.05 MW | 3.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 1.95 MW | 1.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 5.12 MW | 5.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 6.36 MW | 6.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.16 MW | 1.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 7.02 MW | 7.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 5.93 MW | 5.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 7.64 MW | 7.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 4.87 MW | 4.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.06 MW | 2.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.18 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 12.33 MW | 12.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 57.54 MW | 57.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 13.98 MW | 13.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 1.61 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 6.44 MW | 6.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 18.01 MW | 18.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 4.04 MW | 4.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 24.8 MW | 24.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 15.38 MW | 15.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 3.68 MW | 3.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.15 MW | 1.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 7.69 MW | 7.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 5.77 MW | 5.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 3.54 MW | 3.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 3.04 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.03 MW | 2.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.27 MW | 0.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 11.65 MW | 11.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 2.76 MW | 2.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 12.96 MW | 12.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 17.04 MW | 17.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.0 MW | 2.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.95 MW | 0.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.62 MW | 0.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.03 MW | 1.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 8.1 MW | 8.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 4.53 MW | 4.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 2.88 MW | 2.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 4.32 MW | 4.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.4 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 2.09 MW | 2.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 0.67 MW | 0.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 4.28 MW | 4.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.4 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 2.09 MW | 2.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 2.51 MW | 2.51 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 11.76 MW | 11.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 5.35 MW | 5.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 3.57 MW | 3.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 6.96 MW | 6.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.05 MW | 0.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 3.56 MW | 3.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 16.65 MW | 16.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 7.64 MW | 7.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 43.13 MW | 43.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 5.23 MW | 5.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.33 MW | 0.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 12.34 MW | 12.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 9.36 MW | 9.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 9.36 MW | 9.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 6.24 MW | 6.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 2.62 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 12.24 MW | 12.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 2.4 MW | 2.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 11.24 MW | 11.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965791 | AG1-447 | 80/20 | 46.86 MW | 46.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.63 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 5.42 MW | 5.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.61 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 6.8 MW | 6.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 5.44 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 8.15 MW | 8.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 13.91 MW | 13.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 2.83 MW | 2.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 4.24 MW | 4.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 0.94 MW | 0.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.41 MW | 1.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 210.26 MW | 210.26 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274658 | DRESDEN ;2U | 80/20 | 65.77 MW | 65.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274659 | DRESDEN ;3U | 80/20 | 60.12 MW | 60.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274847 | GR RIDGE ;BU | 80/20 | 0.79 MW | 0.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274848 | CAMPGROVE;RU | 80/20 | 0.6 MW | 0.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274849 | CRESCENT ;1U | 80/20 | 0.23 MW | 0.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274850 | MENDOTA H;RU | 80/20 | 0.34 MW | 0.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274851 | PROVIDENC;RU | 80/20 | 0.24 MW | 0.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274855 | GSG-6 ;RU | 80/20 | 0.56 MW | 0.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274856 | ECOGROVE ;U1 | 80/20 | 0.49 MW | 0.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274857 | BIG SKY ;U1 | 80/20 | 0.38 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274858 | BIG SKY ;U2 | 80/20 | 0.38 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274859 | EASYR;U1 E | 80/20 | 2.37 MW | 2.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274860 | EASYR;U2 E | 80/20 | 2.37 MW | 2.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274861 | TOP CROP ;1U | 80/20 | 0.51 MW | 0.51 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274862 | TOP CROP ;2U | 80/20 | 0.97 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274863 | CAYUGA RI;1U | 80/20 | 0.53 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274864 | CAYUGA RI;2U | 80/20 | 0.53 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274871 | GR RIDGE ;2U | 80/20 | 0.29 MW | 0.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274872 | LEE DEKAL;1U | 80/20 | 1.04 MW | 1.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274877 | BISHOP HL;1U | 80/20 | 0.47 MW | 0.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274878 | BISHOP HL;2U | 80/20 | 0.47 MW | 0.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274879 | MINONK ;1U | 80/20 | 1.09 MW | 1.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274887 | PILOT HIL;1U | 80/20 | 1.06 MW | 1.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274888 | KELLY CRK;1U | 80/20 | 1.06 MW | 1.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 274891 | OTTER CRK;1U | 80/20 | 0.7 MW | 0.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 275149 | KELLYCK ;1E | 80/20 | 4.26 MW | 4.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 276156 | O-029 C | 80/20 | 0.3 MW | 0.3 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 276157 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 276158 | O-029 C | 80/20 | 0.59 MW | 0.59 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 290021 | O50 E | 80/20 | 4.36 MW | 4.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 290051 | GSG-6; E | 80/20 | 2.24 MW | 2.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 290108 | LEEDK;1U E | 80/20 | 5.2 MW | 5.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293061 | N-015 E | 80/20 | 3.46 MW | 3.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293513 | O-009 C1 | 80/20 | 0.55 MW | 0.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293514 | O-009 C2 | 80/20 | 0.28 MW | 0.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293515 | O-009 C3 | 80/20 | 0.31 MW | 0.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293516 | O-009 E1 | 80/20 | 1.96 MW | 1.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293517 | O-009 E2 | 80/20 | 1.0 MW | 1.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293518 | O-009 E3 | 80/20 | 1.1 MW | 1.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293644 | O22 E1 | 80/20 | 2.25 MW | 2.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293645 | O22 E2 | 80/20 | 4.37 MW | 4.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293715 | O-029 E | 80/20 | 2.1 MW | 2.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293716 | O-029 E | 80/20 | 1.15 MW | 1.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293717 | O-029 E | 80/20 | 1.06 MW | 1.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293771 | O-035 E | 80/20 | 1.39 MW | 1.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293777 | CAYUG;1U E | 80/20 | 3.17 MW | 3.17 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293778 | CAYUG;2U E | 80/20 | 3.17 MW | 3.17 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 293799 | PILOT HIL;1E | 80/20 | 4.8 MW | 4.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 294392 | P-010 E | 80/20 | 4.4 MW | 4.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 294401 | BSHIL;1U E | 80/20 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 294410 | BSHIL;2U E | 80/20 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 294763 | P-046 E | 80/20 | 2.02 MW | 2.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 295108 | WESTBROOK C | 80/20 | 0.18 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 295109 | WESTBROOK E | 80/20 | 1.35 MW | 1.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 295110 | SUBLETTE C | 80/20 | 0.08 MW | 0.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 295111 | SUBLETTE E | 80/20 | 0.63 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 916211 | Z1-072 E | 80/20 | 2.11 MW | 2.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 916221 | Z1-073 E | 80/20 | 1.31 MW | 1.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 918052 | AA1-018 E OP | 80/20 | 4.69 MW | 4.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 925581 | AC1-033 C | 80/20 | 0.61 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 925582 | AC1-033 E | 80/20 | 4.08 MW | 4.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 926821 | AC1-168 C O1 | 80/20 | 0.5 MW | 0.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 926822 | AC1-168 E O1 | 80/20 | 3.37 MW | 3.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 927201 | AC1-214 C O1 | 80/20 | 0.45 MW | 0.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 927202 | AC1-214 E O1 | 80/20 | 1.42 MW | 1.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 934431 | AD1-067 C | 80/20 | 0.03 MW | 0.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 934432 | AD1-067 E | 80/20 | 0.12 MW | 0.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 934721 | AD1-100 C | 80/20 | 8.53 MW | 8.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 934722 | AD1-100 E | 80/20 | 39.79 MW | 39.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 936371 | AD2-047 C O1 | 80/20 | 2.07 MW | 2.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 936372 | AD2-047 E O1 | 80/20 | 10.11 MW | 10.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 937001 | AD2-134 C | 80/20 | 1.08 MW | 1.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 937002 | AD2-134 E | 80/20 | 4.34 MW | 4.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 938851 | AE1-113 C O1 | 80/20 | 3.59 MW | 3.59 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 938852 | AE1-113 E O1 | 80/20 | 12.74 MW | 12.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 938861 | AE1-114 C O1 | 80/20 | 1.69 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 938862 | AE1-114 E O1 | 80/20 | 5.77 MW | 5.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 939321 | AE1-163 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 939322 | AE1-163 E O1 | 80/20 | 18.09 MW | 18.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 939401 | AE1-172 C O1 | 80/20 | 2.19 MW | 2.19 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 939402 | AE1-172 E O1 | 80/20 | 10.29 MW | 10.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 942421 | AE2-255 C O1 | 80/20 | 1.36 MW | 1.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 942422 | AE2-255 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 942651 | AE2-281 C O1 | 80/20 | 0.42 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 942652 | AE2-281 E O1 | 80/20 | 2.58 MW | 2.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 943801 | AF1-048 C | 80/20 | 2.07 MW | 2.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 943802 | AF1-048 E | 80/20 | 1.38 MW | 1.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 946161 | AF1-281 C O1 | 80/20 | 0.18 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 946162 | AF1-281 E O1 | 80/20 | 1.04 MW | 1.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 946321 | AF1-296 C O1 | 80/20 | 1.7 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 946322 | AF1-296 E O1 | 80/20 | 7.94 MW | 7.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 946501 | AF1-314 C | 80/20 | 1.88 MW | 1.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 946502 | AF1-314 E | 80/20 | 8.82 MW | 8.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 946541 | AF1-318 C O1 | 80/20 | 2.52 MW | 2.52 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 946542 | AF1-318 E O1 | 80/20 | 11.79 MW | 11.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 957331 | AF2-027 C | 80/20 | 1.38 MW | 1.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 957332 | AF2-027 E | 80/20 | 2.07 MW | 2.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 957371 | AF2-031 C O1 | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 957372 | AF2-031 E O1 | 80/20 | 0.62 MW | 0.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 957401 | AF2-034 C | 80/20 | 0.29 MW | 0.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 957402 | AF2-034 E | 80/20 | 0.44 MW | 0.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 957751 | AF2-069 C | 80/20 | 0.1 MW | 0.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 957752 | AF2-069 E | 80/20 | 0.33 MW | 0.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 957761 | AF2-070 C | 80/20 | 0.15 MW | 0.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 957762 | AF2-070 E | 80/20 | 0.71 MW | 0.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 958011 | AF2-095 C O1 | 80/20 | 3.04 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 958021 | AF2-096 C | 80/20 | 6.13 MW | 6.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 958341 | AF2-128 C O1 | 80/20 | 0.67 MW | 0.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 958342 | AF2-128 E O1 | 80/20 | 3.13 MW | 3.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 958921 | AF2-183 C | 80/20 | 1.96 MW | 1.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 958922 | AF2-183 E | 80/20 | 2.94 MW | 2.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 959101 | AF2-201 C O1 | 80/20 | 2.59 MW | 2.59 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 959102 | AF2-201 E O1 | 80/20 | 7.45 MW | 7.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 959351 | AF2-226 C | 80/20 | 1.38 MW | 1.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 959352 | AF2-226 E | 80/20 | 2.07 MW | 2.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 960281 | AF2-319 C | 80/20 | 1.38 MW | 1.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 960282 | AF2-319 E | 80/20 | 2.07 MW | 2.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 960381 | AF2-329 | 80/20 | 2.82 MW | 2.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 960601 | AF2-351 C O1 | 80/20 | 0.61 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 960602 | AF2-351 E O1 | 80/20 | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 961011 | AF2-392 C O1 | 80/20 | 1.71 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 961012 | AF2-392 E O1 | 80/20 | 8.0 MW | 8.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 961021 | AF2-393 O1 | 80/20 | 3.64 MW | 3.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 961031 | AF2-394 O1 | 80/20 | 2.43 MW | 2.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 961501 | AF2-441 C O1 | 80/20 | 4.73 MW | 4.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 961502 | AF2-441 E O1 | 80/20 | 7.09 MW | 7.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 962012 | AG1-044 E | 80/20 | 0.03 MW | 0.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 962721 | AG1-121 C | 80/20 | 2.46 MW | 2.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 962722 | AG1-121 E | 80/20 | 11.5 MW | 11.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 964361 | AG1-298 O1 | 80/20 | 28.8 MW | 28.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 965661 | AG1-434 C | 80/20 | 1.77 MW | 1.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 965662 | AG1-434 E | 80/20 | 8.3 MW | 8.3 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 965671 | AG1-435 C | 80/20 | 1.66 MW | 1.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 965672 | AG1-435 E | 80/20 | 7.75 MW | 7.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 965791 | AG1-447 | 80/20 | 46.75 MW | 46.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 966091 | AG1-478 C | 80/20 | 0.3 MW | 0.3 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 966092 | AG1-478 E | 80/20 | 0.45 MW | 0.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 966431 | AG1-512 C | 80/20 | 3.21 MW | 3.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 966432 | AG1-512 E | 80/20 | 4.82 MW | 4.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 966441 | AG1-513 C | 80/20 | 0.27 MW | 0.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 966442 | AG1-513 E | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 966651 | AG1-535 O1 | 80/20 | 4.44 MW | 4.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 966821 | AG1-553 C O1 | 80/20 | 3.71 MW | 3.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 966822 | AG1-553 E O1 | 80/20 | 5.56 MW | 5.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 919221 | AA1-146 | 80/20 | 9.46 MW | 9.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 965061 | AG1-371 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 965062 | AG1-371 E | 80/20 | 2.87 MW | 2.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 965081 | AG1-373 C | 80/20 | 0.64 MW | 0.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 965082 | AG1-373 E | 80/20 | 0.96 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L2001__B-S-B | 945351 | AF1-200 FTIR | 80/20 | 128.55 MW | 128.55 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 133.62 MW | 133.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 128.3 MW | 128.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.6 MW | 1.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.49 MW | 0.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.73 MW | 0.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.51 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 1.46 MW | 1.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.5 MW | 1.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 1.2 MW | 1.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 2.22 MW | 2.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 2.21 MW | 2.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.57 MW | 1.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 1.29 MW | 1.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 8.95 MW | 8.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.69 MW | 0.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 1.25 MW | 1.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 2.41 MW | 2.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 6.85 MW | 6.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 8.86 MW | 8.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 4.78 MW | 4.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 11.11 MW | 11.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 7.02 MW | 7.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 1.17 MW | 1.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.59 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.66 MW | 0.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 2.11 MW | 2.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 2.32 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 4.77 MW | 4.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 9.25 MW | 9.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 4.44 MW | 4.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 2.44 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 10.52 MW | 10.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 10.09 MW | 10.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 8.91 MW | 8.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 4.26 MW | 4.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.88 MW | 2.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.17 MW | 0.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 4.42 MW | 4.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 2.8 MW | 2.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 7.66 MW | 7.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 8.42 MW | 8.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 1.43 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 9.58 MW | 9.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 10.82 MW | 10.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 8.58 MW | 8.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.98 MW | 2.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.06 MW | 0.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.25 MW | 0.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 17.95 MW | 17.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 83.78 MW | 83.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 3.22 MW | 3.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 21.23 MW | 21.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 2.31 MW | 2.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 9.24 MW | 9.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 7.31 MW | 7.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 25.92 MW | 25.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 12.21 MW | 12.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 33.59 MW | 33.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 4.84 MW | 4.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 22.71 MW | 22.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 5.5 MW | 5.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.72 MW | 1.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 11.49 MW | 11.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 8.31 MW | 8.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 4.8 MW | 4.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 4.36 MW | 4.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.91 MW | 2.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 2.2 MW | 2.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 16.86 MW | 16.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 3.96 MW | 3.96 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 18.62 MW | 18.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 5.26 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 24.61 MW | 24.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.85 MW | 2.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 4.28 MW | 4.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 1.56 MW | 1.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 2.33 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.9 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.22 MW | 0.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.7 MW | 0.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.3 MW | 0.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.48 MW | 1.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 6.39 MW | 6.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 11.4 MW | 11.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 6.54 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 6.22 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 15.72 MW | 15.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 6.13 MW | 6.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.92 MW | 1.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 3.62 MW | 3.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 16.95 MW | 16.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 7.71 MW | 7.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 14.82 MW | 14.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 22.23 MW | 22.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.07 MW | 0.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 24.05 MW | 24.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 93.36 MW | 93.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 7.86 MW | 7.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.5 MW | 0.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 4.01 MW | 4.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 18.76 MW | 18.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 9.49 MW | 9.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 3.76 MW | 3.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 17.61 MW | 17.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 3.47 MW | 3.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 16.25 MW | 16.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.91 MW | 0.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 3.07 MW | 3.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.58 MW | 0.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 16.35 MW | 16.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 7.87 MW | 7.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 11.81 MW | 11.81 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 20.06 MW | 20.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 4.07 MW | 4.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 6.1 MW | 6.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 1.35 MW | 1.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 301.12 MW | 301.12 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 133.62 MW | 133.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 128.3 MW | 128.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.6 MW | 1.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.49 MW | 0.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.73 MW | 0.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.51 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 1.46 MW | 1.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.5 MW | 1.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 1.2 MW | 1.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 2.22 MW | 2.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 2.21 MW | 2.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.57 MW | 1.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 1.29 MW | 1.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 8.95 MW | 8.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.69 MW | 0.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 1.25 MW | 1.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 2.41 MW | 2.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 6.85 MW | 6.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 8.86 MW | 8.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 4.78 MW | 4.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 11.11 MW | 11.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 7.02 MW | 7.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 1.17 MW | 1.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.59 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.66 MW | 0.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 2.11 MW | 2.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 2.32 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 4.77 MW | 4.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 9.25 MW | 9.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 4.44 MW | 4.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 2.44 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 10.52 MW | 10.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 10.09 MW | 10.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 8.91 MW | 8.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 4.26 MW | 4.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.88 MW | 2.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.17 MW | 0.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 4.42 MW | 4.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 2.8 MW | 2.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 7.66 MW | 7.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 8.42 MW | 8.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 1.43 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 9.58 MW | 9.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 10.82 MW | 10.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 8.58 MW | 8.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.98 MW | 2.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.06 MW | 0.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.25 MW | 0.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 17.95 MW | 17.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 83.78 MW | 83.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 3.22 MW | 3.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 21.23 MW | 21.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 2.31 MW | 2.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 9.24 MW | 9.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 7.31 MW | 7.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 25.92 MW | 25.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 12.21 MW | 12.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 33.59 MW | 33.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 4.84 MW | 4.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 22.71 MW | 22.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 5.5 MW | 5.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.72 MW | 1.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 11.49 MW | 11.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 8.31 MW | 8.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 4.8 MW | 4.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 4.36 MW | 4.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.91 MW | 2.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 2.2 MW | 2.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 16.86 MW | 16.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 3.96 MW | 3.96 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 18.62 MW | 18.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 5.26 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 24.61 MW | 24.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.85 MW | 2.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 4.28 MW | 4.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 1.56 MW | 1.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 2.33 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.9 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.22 MW | 0.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.7 MW | 0.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.3 MW | 0.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.48 MW | 1.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 6.39 MW | 6.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 11.4 MW | 11.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 6.54 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 6.22 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 15.72 MW | 15.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 6.13 MW | 6.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.92 MW | 1.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 3.62 MW | 3.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 16.95 MW | 16.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 7.71 MW | 7.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 14.82 MW | 14.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 22.23 MW | 22.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.07 MW | 0.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 24.05 MW | 24.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 93.36 MW | 93.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 7.86 MW | 7.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.5 MW | 0.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 4.01 MW | 4.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 18.76 MW | 18.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 9.49 MW | 9.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 3.76 MW | 3.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 17.61 MW | 17.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 3.47 MW | 3.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 16.25 MW | 16.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.91 MW | 0.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 3.07 MW | 3.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.58 MW | 0.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 16.35 MW | 16.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 7.87 MW | 7.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 11.81 MW | 11.81 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 20.06 MW | 20.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 4.07 MW | 4.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 6.1 MW | 6.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 1.35 MW | 1.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 301.12 MW | 301.12 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 93.0 MW | 93.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 89.8 MW | 89.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.51 MW | 0.51 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 0.97 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.0 MW | 1.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.72 MW | 0.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.55 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 1.34 MW | 1.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.79 MW | 0.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.79 MW | 0.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.42 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.55 MW | 1.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.02 MW | 1.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.47 MW | 1.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.47 MW | 1.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 0.86 MW | 0.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.95 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 5.89 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.47 MW | 0.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 0.87 MW | 0.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 1.56 MW | 1.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 4.43 MW | 4.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 6.16 MW | 6.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 3.33 MW | 3.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 7.74 MW | 7.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 4.42 MW | 4.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 4.42 MW | 4.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 5.0 MW | 5.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 0.81 MW | 0.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.46 MW | 0.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 2.88 MW | 2.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 1.61 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 3.11 MW | 3.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 6.04 MW | 6.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 3.08 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 1.69 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.55 MW | 1.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.02 MW | 2.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 4.73 MW | 4.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 4.73 MW | 4.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 6.83 MW | 6.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 6.64 MW | 6.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 6.34 MW | 6.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 2.7 MW | 2.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 2.7 MW | 2.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 2.96 MW | 2.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.27 MW | 0.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.01 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.12 MW | 0.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 0.93 MW | 0.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 3.05 MW | 3.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 1.95 MW | 1.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 5.12 MW | 5.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 6.36 MW | 6.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.16 MW | 1.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 7.02 MW | 7.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 5.93 MW | 5.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 7.64 MW | 7.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 4.87 MW | 4.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.06 MW | 2.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 12.33 MW | 12.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 57.54 MW | 57.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 2.08 MW | 2.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 13.98 MW | 13.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 1.61 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 6.44 MW | 6.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 18.01 MW | 18.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 4.04 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 24.8 MW | 24.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 15.38 MW | 15.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 3.68 MW | 3.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.15 MW | 1.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 7.69 MW | 7.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 5.77 MW | 5.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 3.54 MW | 3.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 3.04 MW | 3.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.03 MW | 2.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.27 MW | 0.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.53 MW | 1.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 11.65 MW | 11.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 2.76 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 12.96 MW | 12.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 17.04 MW | 17.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.0 MW | 2.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.95 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.62 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.03 MW | 1.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 8.1 MW | 8.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 4.53 MW | 4.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 2.88 MW | 2.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 4.32 MW | 4.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 1.91 MW | 1.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.4 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 2.09 MW | 2.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 0.67 MW | 0.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 1.91 MW | 1.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 4.28 MW | 4.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.26 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.4 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 2.09 MW | 2.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 2.51 MW | 2.51 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 11.76 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 5.35 MW | 5.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 3.57 MW | 3.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 6.96 MW | 6.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 3.56 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 16.65 MW | 16.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 7.64 MW | 7.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 43.13 MW | 43.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 5.23 MW | 5.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.33 MW | 0.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 12.34 MW | 12.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 9.36 MW | 9.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 9.36 MW | 9.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 6.24 MW | 6.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 2.62 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 12.24 MW | 12.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 2.4 MW | 2.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 11.24 MW | 11.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.42 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.63 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 3.62 MW | 3.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 5.42 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.61 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 6.8 MW | 6.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 5.44 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 8.15 MW | 8.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 13.91 MW | 13.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 2.83 MW | 2.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 4.24 MW | 4.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 0.94 MW | 0.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.41 MW | 1.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 210.26 MW | 210.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965792 | AG1-447 BAT | 80/20 | 8.14 MW | 8.14 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 93.0 MW | 93.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 89.8 MW | 89.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.51 MW | 0.51 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 0.97 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.0 MW | 1.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.72 MW | 0.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.55 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 1.34 MW | 1.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.79 MW | 0.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.79 MW | 0.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.42 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.55 MW | 1.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.02 MW | 1.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.47 MW | 1.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.47 MW | 1.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 0.86 MW | 0.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.95 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 5.89 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.47 MW | 0.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 0.87 MW | 0.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 1.56 MW | 1.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 4.43 MW | 4.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 6.16 MW | 6.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 3.33 MW | 3.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 7.74 MW | 7.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 4.42 MW | 4.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 4.42 MW | 4.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 5.0 MW | 5.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 0.81 MW | 0.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.46 MW | 0.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 2.88 MW | 2.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 1.61 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 3.11 MW | 3.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 6.04 MW | 6.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 3.08 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 1.69 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.55 MW | 1.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.02 MW | 2.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 4.73 MW | 4.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 4.73 MW | 4.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 6.83 MW | 6.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 6.64 MW | 6.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 6.34 MW | 6.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 2.7 MW | 2.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 2.7 MW | 2.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 2.96 MW | 2.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.27 MW | 0.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.01 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.12 MW | 0.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 0.93 MW | 0.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 3.05 MW | 3.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 1.95 MW | 1.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 5.12 MW | 5.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 6.36 MW | 6.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.16 MW | 1.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 7.02 MW | 7.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 5.93 MW | 5.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 7.64 MW | 7.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 4.87 MW | 4.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.06 MW | 2.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 12.33 MW | 12.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 57.54 MW | 57.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 2.08 MW | 2.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 13.98 MW | 13.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 1.61 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 6.44 MW | 6.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 18.01 MW | 18.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 4.04 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 24.8 MW | 24.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 15.38 MW | 15.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 3.68 MW | 3.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.15 MW | 1.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 7.69 MW | 7.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 5.77 MW | 5.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 3.54 MW | 3.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 3.04 MW | 3.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.03 MW | 2.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.27 MW | 0.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.53 MW | 1.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 11.65 MW | 11.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 2.76 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 12.96 MW | 12.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 17.04 MW | 17.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.0 MW | 2.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.95 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.62 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.03 MW | 1.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 8.1 MW | 8.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 4.53 MW | 4.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 2.88 MW | 2.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 4.32 MW | 4.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 1.91 MW | 1.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.4 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 2.09 MW | 2.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 0.67 MW | 0.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 1.91 MW | 1.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 4.28 MW | 4.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.26 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.4 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 2.09 MW | 2.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 2.51 MW | 2.51 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 11.76 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 5.35 MW | 5.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 3.57 MW | 3.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 6.96 MW | 6.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 3.56 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 16.65 MW | 16.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 7.64 MW | 7.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 43.13 MW | 43.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 5.23 MW | 5.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.33 MW | 0.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 12.34 MW | 12.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 9.36 MW | 9.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 9.36 MW | 9.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 6.24 MW | 6.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 2.62 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 12.24 MW | 12.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 2.4 MW | 2.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 11.24 MW | 11.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.42 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.63 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 3.62 MW | 3.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 5.42 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.61 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 6.8 MW | 6.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 5.44 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 8.15 MW | 8.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 13.91 MW | 13.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 2.83 MW | 2.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 4.24 MW | 4.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 0.94 MW | 0.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.41 MW | 1.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 210.26 MW | 210.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965792 | AG1-447 BAT | 80/20 | 8.14 MW | 8.14 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 121.1 MW | 121.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 112.32 MW | 112.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.45 MW | 1.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 1.1 MW | 1.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.43 MW | 0.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.64 MW | 0.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 1.21 MW | 1.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.24 MW | 1.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 1.05 MW | 1.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.91 MW | 0.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 4.41 MW | 4.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 4.41 MW | 4.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.98 MW | 0.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.98 MW | 0.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.54 MW | 0.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.95 MW | 1.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.86 MW | 0.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.86 MW | 0.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 2.0 MW | 2.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.26 MW | 1.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.65 MW | 1.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.65 MW | 1.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 1.07 MW | 1.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 1.05 MW | 1.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 6.58 MW | 6.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.6 MW | 0.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 1.1 MW | 1.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 1.93 MW | 1.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 5.5 MW | 5.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 7.98 MW | 7.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 4.2 MW | 4.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 9.77 MW | 9.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 5.49 MW | 5.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 5.49 MW | 5.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 6.35 MW | 6.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 1.03 MW | 1.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.52 MW | 0.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.58 MW | 0.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 3.65 MW | 3.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.85 MW | 1.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 2.04 MW | 2.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 4.76 MW | 4.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 9.24 MW | 9.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 3.9 MW | 3.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 2.14 MW | 2.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.97 MW | 1.97 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.55 MW | 2.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 5.88 MW | 5.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 5.88 MW | 5.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 8.46 MW | 8.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 7.41 MW | 7.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 8.06 MW | 8.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 3.42 MW | 3.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 3.42 MW | 3.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 3.75 MW | 3.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.34 MW | 0.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.54 MW | 2.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.15 MW | 0.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 1.17 MW | 1.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 3.86 MW | 3.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 2.46 MW | 2.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 6.36 MW | 6.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 7.01 MW | 7.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 7.95 MW | 7.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.44 MW | 1.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 8.71 MW | 8.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 1.12 MW | 1.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 7.51 MW | 7.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.42 MW | 1.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 9.48 MW | 9.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.92 MW | 0.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 6.17 MW | 6.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.82 MW | 0.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.22 MW | 0.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 15.38 MW | 15.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 71.78 MW | 71.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 2.58 MW | 2.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 15.6 MW | 15.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 2.03 MW | 2.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 8.13 MW | 8.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 6.58 MW | 6.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 23.34 MW | 23.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 10.74 MW | 10.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 4.65 MW | 4.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 28.54 MW | 28.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 4.07 MW | 4.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 19.08 MW | 19.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 4.57 MW | 4.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.43 MW | 1.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 9.54 MW | 9.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 7.48 MW | 7.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 3.85 MW | 3.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.57 MW | 2.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 944222 | AF1-090 E O1 | 80/20 | 6.67 MW | 6.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.34 MW | 0.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.94 MW | 1.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 14.76 MW | 14.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 3.49 MW | 3.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 16.4 MW | 16.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 4.59 MW | 4.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 21.49 MW | 21.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.53 MW | 2.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 3.79 MW | 3.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.75 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.61 MW | 0.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.3 MW | 1.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 4.7 MW | 4.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 1.22 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 5.71 MW | 5.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 3.65 MW | 3.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 5.47 MW | 5.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 4.82 MW | 4.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 13.85 MW | 13.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.73 MW | 1.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.51 MW | 0.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 5.37 MW | 5.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.41 MW | 1.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.73 MW | 1.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 3.18 MW | 3.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 14.89 MW | 14.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 6.78 MW | 6.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 4.52 MW | 4.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 9.95 MW | 9.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 4.5 MW | 4.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 21.07 MW | 21.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.42 MW | 1.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 9.48 MW | 9.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 32.61 MW | 32.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 6.5 MW | 6.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 15.31 MW | 15.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 7.74 MW | 7.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 3.32 MW | 3.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 15.53 MW | 15.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 14.23 MW | 14.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965911 | AG1-460 C | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965912 | AG1-460 E | 80/20 | 1.06 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.75 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 1.6 MW | 1.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 2.41 MW | 2.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.51 MW | 0.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.77 MW | 0.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 6.89 MW | 6.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 10.33 MW | 10.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 17.63 MW | 17.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 3.59 MW | 3.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 5.38 MW | 5.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 1.2 MW | 1.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.79 MW | 1.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 264.83 MW | 264.83 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 121.1 MW | 121.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 112.32 MW | 112.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.45 MW | 1.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 1.1 MW | 1.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.43 MW | 0.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.64 MW | 0.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 1.21 MW | 1.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.24 MW | 1.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 1.05 MW | 1.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.91 MW | 0.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 4.41 MW | 4.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 4.41 MW | 4.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.98 MW | 0.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.98 MW | 0.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.54 MW | 0.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.95 MW | 1.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.86 MW | 0.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.86 MW | 0.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 2.0 MW | 2.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.26 MW | 1.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.65 MW | 1.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.65 MW | 1.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 1.07 MW | 1.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 1.05 MW | 1.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 6.58 MW | 6.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.6 MW | 0.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 1.1 MW | 1.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 1.93 MW | 1.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 5.5 MW | 5.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 7.98 MW | 7.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 4.2 MW | 4.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 9.77 MW | 9.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 5.49 MW | 5.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 5.49 MW | 5.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 6.35 MW | 6.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 1.03 MW | 1.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.52 MW | 0.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.58 MW | 0.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 3.65 MW | 3.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.85 MW | 1.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 2.04 MW | 2.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 4.76 MW | 4.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 9.24 MW | 9.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 3.9 MW | 3.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 2.14 MW | 2.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.97 MW | 1.97 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.55 MW | 2.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 5.88 MW | 5.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 5.88 MW | 5.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 8.46 MW | 8.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 7.41 MW | 7.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 8.06 MW | 8.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 3.42 MW | 3.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 3.42 MW | 3.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 3.75 MW | 3.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.34 MW | 0.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.54 MW | 2.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.15 MW | 0.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 1.17 MW | 1.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 3.86 MW | 3.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 2.46 MW | 2.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 6.36 MW | 6.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 7.01 MW | 7.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 7.95 MW | 7.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.44 MW | 1.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 8.71 MW | 8.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 1.12 MW | 1.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 7.51 MW | 7.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.42 MW | 1.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 9.48 MW | 9.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.92 MW | 0.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 6.17 MW | 6.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.82 MW | 0.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.22 MW | 0.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 15.38 MW | 15.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 71.78 MW | 71.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 2.58 MW | 2.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 15.6 MW | 15.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 2.03 MW | 2.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 8.13 MW | 8.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 6.58 MW | 6.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 23.34 MW | 23.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 10.74 MW | 10.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 4.65 MW | 4.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 28.54 MW | 28.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 4.07 MW | 4.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 19.08 MW | 19.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 4.57 MW | 4.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.43 MW | 1.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 9.54 MW | 9.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 7.48 MW | 7.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 3.85 MW | 3.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.57 MW | 2.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 944222 | AF1-090 E O1 | 80/20 | 6.67 MW | 6.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.34 MW | 0.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.94 MW | 1.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 14.76 MW | 14.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 3.49 MW | 3.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 16.4 MW | 16.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 4.59 MW | 4.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 21.49 MW | 21.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.53 MW | 2.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 3.79 MW | 3.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.75 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.61 MW | 0.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.3 MW | 1.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 4.7 MW | 4.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 1.22 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 5.71 MW | 5.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 3.65 MW | 3.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 5.47 MW | 5.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 4.82 MW | 4.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 13.85 MW | 13.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.73 MW | 1.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.51 MW | 0.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 5.37 MW | 5.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.41 MW | 1.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.73 MW | 1.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 3.18 MW | 3.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 14.89 MW | 14.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 6.78 MW | 6.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 4.52 MW | 4.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 9.95 MW | 9.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 4.5 MW | 4.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 21.07 MW | 21.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.42 MW | 1.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 9.48 MW | 9.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 32.61 MW | 32.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 6.5 MW | 6.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 15.31 MW | 15.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 7.74 MW | 7.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 3.32 MW | 3.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 15.53 MW | 15.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 14.23 MW | 14.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965911 | AG1-460 C | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965912 | AG1-460 E | 80/20 | 1.06 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.75 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 1.6 MW | 1.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 2.41 MW | 2.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.51 MW | 0.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.77 MW | 0.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 6.89 MW | 6.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 10.33 MW | 10.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 17.63 MW | 17.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 3.59 MW | 3.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 5.38 MW | 5.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 1.2 MW | 1.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.79 MW | 1.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 264.83 MW | 264.83 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274658 | DRESDEN ;2U | 80/20 | 80.75 MW | 80.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274659 | DRESDEN ;3U | 80/20 | 69.94 MW | 69.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274847 | GR RIDGE ;BU | 80/20 | 0.93 MW | 0.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.71 MW | 0.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.28 MW | 0.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.4 MW | 0.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.28 MW | 0.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 0.74 MW | 0.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 0.76 MW | 0.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 0.66 MW | 0.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 0.58 MW | 0.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274859 | EASYR;U1 E | 80/20 | 2.8 MW | 2.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274860 | EASYR;U2 E | 80/20 | 2.8 MW | 2.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274861 | TOP CROP ;1U | 80/20 | 0.77 MW | 0.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274862 | TOP CROP ;2U | 80/20 | 1.47 MW | 1.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 0.6 MW | 0.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 0.6 MW | 0.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274871 | GR RIDGE ;2U | 80/20 | 0.35 MW | 0.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 1.22 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274879 | MINONK ;1U | 80/20 | 1.33 MW | 1.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274887 | PILOT HIL;1U | 80/20 | 1.04 MW | 1.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274888 | KELLY CRK;1U | 80/20 | 1.04 MW | 1.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 0.66 MW | 0.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274891 | OTTER CRK;1U | 80/20 | 0.68 MW | 0.68 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 275149 | KELLYCK ;1E | 80/20 | 4.17 MW | 4.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.35 MW | 0.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.38 MW | 0.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 290021 | O50 E | 80/20 | 5.31 MW | 5.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 290051 | GSG-6; E | 80/20 | 2.64 MW | 2.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 290108 | LEEDK;1U E | 80/20 | 6.12 MW | 6.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 3.37 MW | 3.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 3.37 MW | 3.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293061 | N-015 E | 80/20 | 4.07 MW | 4.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.65 MW | 0.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.33 MW | 0.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.37 MW | 0.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293516 | O-009 E1 | 80/20 | 2.32 MW | 2.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293517 | O-009 E2 | 80/20 | 1.18 MW | 1.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293518 | O-009 E3 | 80/20 | 1.3 MW | 1.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293644 | O22 E1 | 80/20 | 3.42 MW | 3.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293645 | O22 E2 | 80/20 | 6.63 MW | 6.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293715 | O-029 E | 80/20 | 2.48 MW | 2.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293716 | O-029 E | 80/20 | 1.36 MW | 1.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293717 | O-029 E | 80/20 | 1.25 MW | 1.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 1.64 MW | 1.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293777 | CAYUG;1U E | 80/20 | 3.61 MW | 3.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293778 | CAYUG;2U E | 80/20 | 3.61 MW | 3.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293799 | PILOT HIL;1E | 80/20 | 4.69 MW | 4.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 294392 | P-010 E | 80/20 | 5.17 MW | 5.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 2.2 MW | 2.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 2.2 MW | 2.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 294763 | P-046 E | 80/20 | 2.39 MW | 2.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.21 MW | 0.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 295109 | WESTBROOK E | 80/20 | 1.59 MW | 1.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.09 MW | 0.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 295111 | SUBLETTE E | 80/20 | 0.74 MW | 0.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 916211 | Z1-072 E | 80/20 | 2.48 MW | 2.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 916221 | Z1-073 E | 80/20 | 1.55 MW | 1.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 3.91 MW | 3.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 918052 | AA1-018 E OP | 80/20 | 4.57 MW | 4.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 4.89 MW | 4.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 0.72 MW | 0.72 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 4.82 MW | 4.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 3.96 MW | 3.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.53 MW | 0.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 1.67 MW | 1.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.03 MW | 0.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 934432 | AD1-067 E | 80/20 | 0.14 MW | 0.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 934721 | AD1-100 C | 80/20 | 9.73 MW | 9.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 934722 | AD1-100 E | 80/20 | 45.4 MW | 45.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 936371 | AD2-047 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 936372 | AD2-047 E O1 | 80/20 | 9.88 MW | 9.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 1.28 MW | 1.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 937002 | AD2-134 E | 80/20 | 5.11 MW | 5.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C O1 | 80/20 | 4.38 MW | 4.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 938852 | AE1-113 E O1 | 80/20 | 15.53 MW | 15.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 938862 | AE1-114 E O1 | 80/20 | 6.83 MW | 6.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | 80/20 | 3.05 MW | 3.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 939322 | AE1-163 E O1 | 80/20 | 18.71 MW | 18.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 2.5 MW | 2.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 939402 | AE1-172 E O1 | 80/20 | 11.72 MW | 11.72 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 2.81 MW | 2.81 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 0.88 MW | 0.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 5.87 MW | 5.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942422 | AE2-255 E O1 | 80/20 | 4.98 MW | 4.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942652 | AE2-281 E O1 | 80/20 | 2.67 MW | 2.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 943801 | AF1-048 C | 80/20 | 2.45 MW | 2.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 943802 | AF1-048 E | 80/20 | 1.63 MW | 1.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.22 MW | 0.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946162 | AF1-281 E O1 | 80/20 | 1.23 MW | 1.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 2.01 MW | 2.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946322 | AF1-296 E O1 | 80/20 | 9.4 MW | 9.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 2.22 MW | 2.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946502 | AF1-314 E | 80/20 | 10.43 MW | 10.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 2.95 MW | 2.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 13.82 MW | 13.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957331 | AF2-027 C | 80/20 | 1.63 MW | 1.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957332 | AF2-027 E | 80/20 | 2.45 MW | 2.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957401 | AF2-034 C | 80/20 | 0.37 MW | 0.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957402 | AF2-034 E | 80/20 | 0.56 MW | 0.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 0.39 MW | 0.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958011 | AF2-095 C O1 | 80/20 | 2.98 MW | 2.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958021 | AF2-096 C | 80/20 | 8.26 MW | 8.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 3.67 MW | 3.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 2.32 MW | 2.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958922 | AF2-183 E | 80/20 | 3.48 MW | 3.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 3.07 MW | 3.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959102 | AF2-201 E O1 | 80/20 | 8.8 MW | 8.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959352 | AF2-226 E | 80/20 | 3.14 MW | 3.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 1.06 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 1.6 MW | 1.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960282 | AF2-319 E | 80/20 | 3.14 MW | 3.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960381 | AF2-329 | 80/20 | 3.29 MW | 3.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960601 | AF2-351 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960602 | AF2-351 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 1.06 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 1.6 MW | 1.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 961012 | AF2-392 E O1 | 80/20 | 9.46 MW | 9.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 4.31 MW | 4.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 2.87 MW | 2.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 2.9 MW | 2.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 13.55 MW | 13.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965092 | AG1-374 E | 80/20 | 3.99 MW | 3.99 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C | 80/20 | 2.1 MW | 2.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965662 | AG1-434 E | 80/20 | 9.84 MW | 9.84 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 1.95 MW | 1.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 9.15 MW | 9.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966091 | AG1-478 C | 80/20 | 0.32 MW | 0.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966092 | AG1-478 E | 80/20 | 0.49 MW | 0.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966431 | AG1-512 C | 80/20 | 1.01 MW | 1.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966432 | AG1-512 E | 80/20 | 1.52 MW | 1.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966441 | AG1-513 C | 80/20 | 0.32 MW | 0.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966442 | AG1-513 E | 80/20 | 0.48 MW | 0.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 4.39 MW | 4.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966822 | AG1-553 E O1 | 80/20 | 6.58 MW | 6.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 11.2 MW | 11.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965061 | AG1-371 C | 80/20 | 2.27 MW | 2.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965062 | AG1-371 E | 80/20 | 3.41 MW | 3.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965081 | AG1-373 C | 80/20 | 0.76 MW | 0.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965082 | AG1-373 E | 80/20 | 1.14 MW | 1.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 945351 | AF1-200 FTIR | 80/20 | 151.26 MW | 151.26 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274658 | DRESDEN ;2U | 80/20 | 92.86 MW | 92.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274659 | DRESDEN ;3U | 80/20 | 84.87 MW | 84.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.1 MW | 1.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274849 | CRESCENT ;1U | 80/20 | 0.32 MW | 0.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274850 | MENDOTA H;RU | 80/20 | 0.48 MW | 0.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274851 | PROVIDENC;RU | 80/20 | 0.33 MW | 0.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274853 | TWINGROVE;U1 | 80/20 | 0.85 MW | 0.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274854 | TWINGROVE;U2 | 80/20 | 0.87 MW | 0.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274855 | GSG-6 ;RU | 80/20 | 0.8 MW | 0.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.69 MW | 0.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.53 MW | 0.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.53 MW | 0.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274859 | EASYR;U1 E | 80/20 | 3.35 MW | 3.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274860 | EASYR;U2 E | 80/20 | 3.35 MW | 3.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274861 | TOP CROP ;1U | 80/20 | 0.85 MW | 0.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274862 | TOP CROP ;2U | 80/20 | 1.62 MW | 1.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.67 MW | 0.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.67 MW | 0.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.49 MW | 1.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274877 | BISHOP HL;1U | 80/20 | 0.65 MW | 0.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274878 | BISHOP HL;2U | 80/20 | 0.65 MW | 0.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274879 | MINONK ;1U | 80/20 | 1.52 MW | 1.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274887 | PILOT HIL;1U | 80/20 | 1.17 MW | 1.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274888 | KELLY CRK;1U | 80/20 | 1.17 MW | 1.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274889 | BRIGHTSTK;1U | 80/20 | 0.75 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274891 | OTTER CRK;1U | 80/20 | 0.78 MW | 0.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 275149 | KELLYCK ;1E | 80/20 | 4.67 MW | 4.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276156 | O-029 C | 80/20 | 0.42 MW | 0.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276157 | O-029 C | 80/20 | 0.46 MW | 0.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276158 | O-029 C | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290021 | O50 E | 80/20 | 6.09 MW | 6.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290051 | GSG-6; E | 80/20 | 3.2 MW | 3.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290108 | LEEDK;1U E | 80/20 | 7.43 MW | 7.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290261 | S-027 E | 80/20 | 3.86 MW | 3.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290265 | S-028 E | 80/20 | 3.86 MW | 3.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293061 | N-015 E | 80/20 | 4.81 MW | 4.81 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293513 | O-009 C1 | 80/20 | 0.78 MW | 0.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293514 | O-009 C2 | 80/20 | 0.4 MW | 0.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293515 | O-009 C3 | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293516 | O-009 E1 | 80/20 | 2.76 MW | 2.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293517 | O-009 E2 | 80/20 | 1.4 MW | 1.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293518 | O-009 E3 | 80/20 | 1.55 MW | 1.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293644 | O22 E1 | 80/20 | 3.76 MW | 3.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293645 | O22 E2 | 80/20 | 7.29 MW | 7.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293715 | O-029 E | 80/20 | 2.96 MW | 2.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293716 | O-029 E | 80/20 | 1.62 MW | 1.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293717 | O-029 E | 80/20 | 1.49 MW | 1.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293771 | O-035 E | 80/20 | 1.92 MW | 1.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293777 | CAYUG;1U E | 80/20 | 4.03 MW | 4.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293778 | CAYUG;2U E | 80/20 | 4.03 MW | 4.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293799 | PILOT HIL;1E | 80/20 | 5.26 MW | 5.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294392 | P-010 E | 80/20 | 6.1 MW | 6.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294401 | BSHIL;1U E | 80/20 | 2.58 MW | 2.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294410 | BSHIL;2U E | 80/20 | 2.58 MW | 2.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294763 | P-046 E | 80/20 | 2.85 MW | 2.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295108 | WESTBROOK C | 80/20 | 0.26 MW | 0.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295109 | WESTBROOK E | 80/20 | 1.93 MW | 1.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295110 | SUBLETTE C | 80/20 | 0.11 MW | 0.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295111 | SUBLETTE E | 80/20 | 0.89 MW | 0.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 916211 | Z1-072 E | 80/20 | 2.91 MW | 2.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 916221 | Z1-073 E | 80/20 | 1.87 MW | 1.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 917502 | Z2-087 E | 80/20 | 4.47 MW | 4.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 918052 | AA1-018 E OP | 80/20 | 5.2 MW | 5.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 924041 | AB2-047 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 924042 | AB2-047 E O1 | 80/20 | 5.59 MW | 5.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925581 | AC1-033 C | 80/20 | 0.85 MW | 0.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925582 | AC1-033 E | 80/20 | 5.66 MW | 5.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 926821 | AC1-168 C O1 | 80/20 | 0.69 MW | 0.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 926822 | AC1-168 E O1 | 80/20 | 4.64 MW | 4.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 927201 | AC1-214 C O1 | 80/20 | 0.62 MW | 0.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 927202 | AC1-214 E O1 | 80/20 | 1.96 MW | 1.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934432 | AD1-067 E | 80/20 | 0.17 MW | 0.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934721 | AD1-100 C | 80/20 | 10.57 MW | 10.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934722 | AD1-100 E | 80/20 | 49.33 MW | 49.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936371 | AD2-047 C O1 | 80/20 | 2.27 MW | 2.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936372 | AD2-047 E O1 | 80/20 | 11.07 MW | 11.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 937001 | AD2-134 C | 80/20 | 1.55 MW | 1.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 937002 | AD2-134 E | 80/20 | 6.18 MW | 6.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938851 | AE1-113 C O1 | 80/20 | 5.03 MW | 5.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938852 | AE1-113 E O1 | 80/20 | 17.82 MW | 17.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938861 | AE1-114 C O1 | 80/20 | 2.39 MW | 2.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938862 | AE1-114 E O1 | 80/20 | 8.17 MW | 8.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939321 | AE1-163 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939322 | AE1-163 E O1 | 80/20 | 21.32 MW | 21.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939401 | AE1-172 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939402 | AE1-172 E O1 | 80/20 | 12.91 MW | 12.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 941731 | AE2-173 O1 | 80/20 | 3.21 MW | 3.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942111 | AE2-223 C | 80/20 | 1.0 MW | 1.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942112 | AE2-223 E | 80/20 | 6.71 MW | 6.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942421 | AE2-255 C O1 | 80/20 | 1.9 MW | 1.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942422 | AE2-255 E O1 | 80/20 | 5.71 MW | 5.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942651 | AE2-281 C O1 | 80/20 | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942652 | AE2-281 E O1 | 80/20 | 3.05 MW | 3.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 943801 | AF1-048 C | 80/20 | 2.94 MW | 2.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 943802 | AF1-048 E | 80/20 | 1.96 MW | 1.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946161 | AF1-281 C O1 | 80/20 | 0.26 MW | 0.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946162 | AF1-281 E O1 | 80/20 | 1.47 MW | 1.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946321 | AF1-296 C O1 | 80/20 | 2.39 MW | 2.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946322 | AF1-296 E O1 | 80/20 | 11.18 MW | 11.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946501 | AF1-314 C | 80/20 | 2.65 MW | 2.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946502 | AF1-314 E | 80/20 | 12.47 MW | 12.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946541 | AF1-318 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946542 | AF1-318 E O1 | 80/20 | 16.15 MW | 16.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957331 | AF2-027 C | 80/20 | 1.93 MW | 1.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957332 | AF2-027 E | 80/20 | 2.9 MW | 2.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957401 | AF2-034 C | 80/20 | 0.42 MW | 0.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957402 | AF2-034 E | 80/20 | 0.64 MW | 0.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957751 | AF2-069 C | 80/20 | 0.14 MW | 0.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957752 | AF2-069 E | 80/20 | 0.46 MW | 0.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957761 | AF2-070 C | 80/20 | 0.2 MW | 0.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957762 | AF2-070 E | 80/20 | 0.98 MW | 0.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958011 | AF2-095 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958021 | AF2-096 C | 80/20 | 9.02 MW | 9.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958341 | AF2-128 C O1 | 80/20 | 0.92 MW | 0.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958342 | AF2-128 E O1 | 80/20 | 4.29 MW | 4.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958921 | AF2-183 C | 80/20 | 2.77 MW | 2.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958922 | AF2-183 E | 80/20 | 4.16 MW | 4.16 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959101 | AF2-201 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959102 | AF2-201 E O1 | 80/20 | 10.53 MW | 10.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959351 | AF2-226 C | 80/20 | 2.3 MW | 2.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959352 | AF2-226 E | 80/20 | 3.45 MW | 3.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959611 | AF2-252 C | 80/20 | 1.22 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959612 | AF2-252 E | 80/20 | 1.83 MW | 1.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960281 | AF2-319 C | 80/20 | 2.3 MW | 2.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960282 | AF2-319 E | 80/20 | 3.45 MW | 3.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960381 | AF2-329 | 80/20 | 4.09 MW | 4.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960601 | AF2-351 C O1 | 80/20 | 0.67 MW | 0.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960602 | AF2-351 E O1 | 80/20 | 1.0 MW | 1.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960611 | AF2-352 C | 80/20 | 1.22 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960612 | AF2-352 E | 80/20 | 1.83 MW | 1.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961011 | AF2-392 C O1 | 80/20 | 2.42 MW | 2.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961012 | AF2-392 E O1 | 80/20 | 11.31 MW | 11.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961021 | AF2-393 O1 | 80/20 | 5.15 MW | 5.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961031 | AF2-394 O1 | 80/20 | 3.43 MW | 3.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961501 | AF2-441 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961502 | AF2-441 E O1 | 80/20 | 6.23 MW | 6.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 962012 | AG1-044 E | 80/20 | 0.05 MW | 0.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 962721 | AG1-121 C | 80/20 | 3.39 MW | 3.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 962722 | AG1-121 E | 80/20 | 15.87 MW | 15.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965092 | AG1-374 E | 80/20 | 4.57 MW | 4.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965341 | AG1-399 C O1 | 80/20 | 2.3 MW | 2.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965342 | AG1-399 E O1 | 80/20 | 10.78 MW | 10.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965351 | AG1-400 O1 | 80/20 | 8.18 MW | 8.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965371 | AG1-402 O1 | 80/20 | 8.18 MW | 8.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965391 | AG1-404 O1 | 80/20 | 5.45 MW | 5.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965661 | AG1-434 C | 80/20 | 2.52 MW | 2.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965662 | AG1-434 E | 80/20 | 11.82 MW | 11.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965671 | AG1-435 C | 80/20 | 2.29 MW | 2.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965672 | AG1-435 E | 80/20 | 10.72 MW | 10.72 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966091 | AG1-478 C | 80/20 | 0.37 MW | 0.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966092 | AG1-478 E | 80/20 | 0.56 MW | 0.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966431 | AG1-512 C | 80/20 | 1.15 MW | 1.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966432 | AG1-512 E | 80/20 | 1.73 MW | 1.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966441 | AG1-513 C | 80/20 | 0.39 MW | 0.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966442 | AG1-513 E | 80/20 | 0.58 MW | 0.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966821 | AG1-553 C O1 | 80/20 | 5.22 MW | 5.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966822 | AG1-553 E O1 | 80/20 | 7.83 MW | 7.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 919221 | AA1-146 | 80/20 | 13.39 MW | 13.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965061 | AG1-371 C | 80/20 | 2.73 MW | 2.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965062 | AG1-371 E | 80/20 | 4.1 MW | 4.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965081 | AG1-373 C | 80/20 | 0.91 MW | 0.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965082 | AG1-373 E | 80/20 | 1.37 MW | 1.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 945351 | AF1-200 FTIR | 80/20 | 202.38 MW | 202.38 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 121.1 MW | 121.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 112.32 MW | 112.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.45 MW | 1.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 1.1 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.43 MW | 0.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.64 MW | 0.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.44 MW | 0.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 1.21 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.24 MW | 1.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 1.05 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.91 MW | 0.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 4.41 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 4.41 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.98 MW | 0.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.98 MW | 0.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.54 MW | 0.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.95 MW | 1.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 2.0 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.26 MW | 1.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.65 MW | 1.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.65 MW | 1.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 1.07 MW | 1.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 1.05 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 6.58 MW | 6.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.6 MW | 0.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 1.1 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 1.93 MW | 1.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 5.5 MW | 5.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 7.98 MW | 7.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 4.2 MW | 4.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 9.77 MW | 9.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 5.49 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 5.49 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 6.35 MW | 6.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.52 MW | 0.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.58 MW | 0.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 3.65 MW | 3.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.85 MW | 1.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 2.04 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 4.76 MW | 4.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 9.24 MW | 9.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 3.9 MW | 3.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 2.14 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.97 MW | 1.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.55 MW | 2.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 5.88 MW | 5.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 5.88 MW | 5.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 8.46 MW | 8.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 7.41 MW | 7.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 8.06 MW | 8.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 3.42 MW | 3.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 3.42 MW | 3.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 3.75 MW | 3.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.34 MW | 0.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.54 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.15 MW | 0.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 1.17 MW | 1.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 3.86 MW | 3.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 2.46 MW | 2.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 6.36 MW | 6.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 7.01 MW | 7.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 7.95 MW | 7.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.44 MW | 1.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 8.71 MW | 8.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 1.12 MW | 1.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 7.51 MW | 7.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.42 MW | 1.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 9.48 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.92 MW | 0.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 6.17 MW | 6.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.82 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.22 MW | 0.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 15.38 MW | 15.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 71.78 MW | 71.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 2.58 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 15.6 MW | 15.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 2.03 MW | 2.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 8.13 MW | 8.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 6.58 MW | 6.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 23.34 MW | 23.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 10.74 MW | 10.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 4.65 MW | 4.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 28.54 MW | 28.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 4.07 MW | 4.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 19.08 MW | 19.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 4.57 MW | 4.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.43 MW | 1.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 9.54 MW | 9.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 7.48 MW | 7.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 3.85 MW | 3.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.57 MW | 2.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 944222 | AF1-090 E O1 | 80/20 | 6.67 MW | 6.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.34 MW | 0.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.94 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 14.76 MW | 14.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 3.49 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 16.4 MW | 16.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 4.59 MW | 4.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 21.49 MW | 21.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.53 MW | 2.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 3.79 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.5 MW | 0.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.75 MW | 0.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.55 MW | 0.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.83 MW | 0.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.61 MW | 0.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.3 MW | 1.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 4.7 MW | 4.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 1.22 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 5.71 MW | 5.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 3.65 MW | 3.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 5.47 MW | 5.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 4.82 MW | 4.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 13.85 MW | 13.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.73 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.51 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 0.83 MW | 0.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 5.37 MW | 5.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.41 MW | 1.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.73 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 3.18 MW | 3.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 14.89 MW | 14.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 6.78 MW | 6.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 4.52 MW | 4.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 9.95 MW | 9.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 21.07 MW | 21.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.42 MW | 1.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 9.48 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 32.61 MW | 32.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.41 MW | 0.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 15.31 MW | 15.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 7.74 MW | 7.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 3.32 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 15.53 MW | 15.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 3.04 MW | 3.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 14.23 MW | 14.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965911 | AG1-460 C | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965912 | AG1-460 E | 80/20 | 1.06 MW | 1.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.5 MW | 0.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.75 MW | 0.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 1.6 MW | 1.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 2.41 MW | 2.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.51 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 4.42 MW | 4.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 6.89 MW | 6.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 10.33 MW | 10.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 17.63 MW | 17.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 3.59 MW | 3.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 5.38 MW | 5.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 1.2 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.79 MW | 1.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 264.83 MW | 264.83 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 121.1 MW | 121.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 112.32 MW | 112.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.45 MW | 1.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 1.1 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.43 MW | 0.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.64 MW | 0.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.44 MW | 0.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 1.21 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.24 MW | 1.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 1.05 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.91 MW | 0.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 4.41 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 4.41 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.98 MW | 0.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.98 MW | 0.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.54 MW | 0.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.95 MW | 1.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 2.0 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.26 MW | 1.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.65 MW | 1.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.65 MW | 1.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 1.07 MW | 1.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 1.05 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 6.58 MW | 6.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.6 MW | 0.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 1.1 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 1.93 MW | 1.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 5.5 MW | 5.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 7.98 MW | 7.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 4.2 MW | 4.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 9.77 MW | 9.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 5.49 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 5.49 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 6.35 MW | 6.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.52 MW | 0.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.58 MW | 0.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 3.65 MW | 3.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.85 MW | 1.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 2.04 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 4.76 MW | 4.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 9.24 MW | 9.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 3.9 MW | 3.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 2.14 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.97 MW | 1.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.55 MW | 2.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 5.88 MW | 5.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 5.88 MW | 5.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 8.46 MW | 8.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 7.41 MW | 7.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 8.06 MW | 8.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 3.42 MW | 3.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 3.42 MW | 3.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 3.75 MW | 3.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.34 MW | 0.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.54 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.15 MW | 0.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 1.17 MW | 1.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 3.86 MW | 3.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 2.46 MW | 2.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 6.36 MW | 6.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 7.01 MW | 7.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 7.95 MW | 7.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.44 MW | 1.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 8.71 MW | 8.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 1.12 MW | 1.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 7.51 MW | 7.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.42 MW | 1.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 9.48 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.92 MW | 0.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 6.17 MW | 6.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.82 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.22 MW | 0.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 15.38 MW | 15.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 71.78 MW | 71.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 2.58 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 15.6 MW | 15.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 2.03 MW | 2.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 8.13 MW | 8.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 6.58 MW | 6.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 23.34 MW | 23.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 10.74 MW | 10.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 4.65 MW | 4.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 28.54 MW | 28.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 4.07 MW | 4.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 19.08 MW | 19.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 4.57 MW | 4.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.43 MW | 1.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 9.54 MW | 9.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 7.48 MW | 7.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 3.85 MW | 3.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.57 MW | 2.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 944222 | AF1-090 E O1 | 80/20 | 6.67 MW | 6.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.34 MW | 0.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.94 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 14.76 MW | 14.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 3.49 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 16.4 MW | 16.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 4.59 MW | 4.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 21.49 MW | 21.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.53 MW | 2.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 3.79 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.5 MW | 0.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.75 MW | 0.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.55 MW | 0.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.83 MW | 0.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.61 MW | 0.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.3 MW | 1.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 4.7 MW | 4.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 1.22 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 5.71 MW | 5.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 3.65 MW | 3.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 5.47 MW | 5.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 4.82 MW | 4.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 13.85 MW | 13.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.73 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.51 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 0.83 MW | 0.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 5.37 MW | 5.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.41 MW | 1.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.73 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 3.18 MW | 3.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 14.89 MW | 14.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 6.78 MW | 6.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 4.52 MW | 4.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 9.95 MW | 9.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 21.07 MW | 21.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.42 MW | 1.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 9.48 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 32.61 MW | 32.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.41 MW | 0.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 15.31 MW | 15.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 7.74 MW | 7.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 3.32 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 15.53 MW | 15.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 3.04 MW | 3.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 14.23 MW | 14.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965911 | AG1-460 C | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965912 | AG1-460 E | 80/20 | 1.06 MW | 1.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.5 MW | 0.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.75 MW | 0.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 1.6 MW | 1.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 2.41 MW | 2.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.51 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 4.42 MW | 4.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 6.89 MW | 6.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 10.33 MW | 10.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 17.63 MW | 17.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 3.59 MW | 3.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 5.38 MW | 5.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 1.2 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.79 MW | 1.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 264.83 MW | 264.83 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274658 | DRESDEN ;2U | 80/20 | 80.75 MW | 80.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274659 | DRESDEN ;3U | 80/20 | 69.94 MW | 69.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274847 | GR RIDGE ;BU | 80/20 | 0.93 MW | 0.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.71 MW | 0.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.28 MW | 0.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.4 MW | 0.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.28 MW | 0.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 0.74 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 0.76 MW | 0.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 0.66 MW | 0.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 0.58 MW | 0.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 0.44 MW | 0.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 0.44 MW | 0.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274859 | EASYR;U1 E | 80/20 | 2.8 MW | 2.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274860 | EASYR;U2 E | 80/20 | 2.8 MW | 2.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274861 | TOP CROP ;1U | 80/20 | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274862 | TOP CROP ;2U | 80/20 | 1.47 MW | 1.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 0.6 MW | 0.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 0.6 MW | 0.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274871 | GR RIDGE ;2U | 80/20 | 0.35 MW | 0.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 1.22 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274879 | MINONK ;1U | 80/20 | 1.33 MW | 1.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274887 | PILOT HIL;1U | 80/20 | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274888 | KELLY CRK;1U | 80/20 | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 0.66 MW | 0.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274891 | OTTER CRK;1U | 80/20 | 0.68 MW | 0.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 275149 | KELLYCK ;1E | 80/20 | 4.17 MW | 4.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.35 MW | 0.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.38 MW | 0.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 290021 | O50 E | 80/20 | 5.31 MW | 5.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 290051 | GSG-6; E | 80/20 | 2.64 MW | 2.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 290108 | LEEDK;1U E | 80/20 | 6.12 MW | 6.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 3.37 MW | 3.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 3.37 MW | 3.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293061 | N-015 E | 80/20 | 4.07 MW | 4.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.65 MW | 0.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.33 MW | 0.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.37 MW | 0.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293516 | O-009 E1 | 80/20 | 2.32 MW | 2.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293517 | O-009 E2 | 80/20 | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293518 | O-009 E3 | 80/20 | 1.3 MW | 1.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293644 | O22 E1 | 80/20 | 3.42 MW | 3.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293645 | O22 E2 | 80/20 | 6.63 MW | 6.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293715 | O-029 E | 80/20 | 2.48 MW | 2.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293716 | O-029 E | 80/20 | 1.36 MW | 1.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293717 | O-029 E | 80/20 | 1.25 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 1.64 MW | 1.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293777 | CAYUG;1U E | 80/20 | 3.61 MW | 3.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293778 | CAYUG;2U E | 80/20 | 3.61 MW | 3.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293799 | PILOT HIL;1E | 80/20 | 4.69 MW | 4.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 294392 | P-010 E | 80/20 | 5.17 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 2.2 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 2.2 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 294763 | P-046 E | 80/20 | 2.39 MW | 2.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.21 MW | 0.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 295109 | WESTBROOK E | 80/20 | 1.59 MW | 1.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 295111 | SUBLETTE E | 80/20 | 0.74 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 916211 | Z1-072 E | 80/20 | 2.48 MW | 2.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 916221 | Z1-073 E | 80/20 | 1.55 MW | 1.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 3.91 MW | 3.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 918052 | AA1-018 E OP | 80/20 | 4.57 MW | 4.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 4.89 MW | 4.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 0.72 MW | 0.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 4.82 MW | 4.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 3.96 MW | 3.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 1.67 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.03 MW | 0.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 934432 | AD1-067 E | 80/20 | 0.14 MW | 0.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 934721 | AD1-100 C | 80/20 | 9.73 MW | 9.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 934722 | AD1-100 E | 80/20 | 45.4 MW | 45.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 936371 | AD2-047 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 936372 | AD2-047 E O1 | 80/20 | 9.88 MW | 9.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 1.28 MW | 1.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 937002 | AD2-134 E | 80/20 | 5.11 MW | 5.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C O1 | 80/20 | 4.38 MW | 4.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 938852 | AE1-113 E O1 | 80/20 | 15.53 MW | 15.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 938862 | AE1-114 E O1 | 80/20 | 6.83 MW | 6.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | 80/20 | 3.05 MW | 3.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 939322 | AE1-163 E O1 | 80/20 | 18.71 MW | 18.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 2.5 MW | 2.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 939402 | AE1-172 E O1 | 80/20 | 11.72 MW | 11.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 2.81 MW | 2.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 0.88 MW | 0.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 5.87 MW | 5.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942422 | AE2-255 E O1 | 80/20 | 4.98 MW | 4.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942652 | AE2-281 E O1 | 80/20 | 2.67 MW | 2.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 943801 | AF1-048 C | 80/20 | 2.45 MW | 2.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 943802 | AF1-048 E | 80/20 | 1.63 MW | 1.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.22 MW | 0.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946162 | AF1-281 E O1 | 80/20 | 1.23 MW | 1.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 2.01 MW | 2.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946322 | AF1-296 E O1 | 80/20 | 9.4 MW | 9.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 2.22 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946502 | AF1-314 E | 80/20 | 10.43 MW | 10.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 2.95 MW | 2.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 13.82 MW | 13.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957331 | AF2-027 C | 80/20 | 1.63 MW | 1.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957332 | AF2-027 E | 80/20 | 2.45 MW | 2.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957401 | AF2-034 C | 80/20 | 0.37 MW | 0.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957402 | AF2-034 E | 80/20 | 0.56 MW | 0.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 0.39 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 0.83 MW | 0.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958011 | AF2-095 C O1 | 80/20 | 2.98 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958021 | AF2-096 C | 80/20 | 8.26 MW | 8.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 3.67 MW | 3.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 2.32 MW | 2.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958922 | AF2-183 E | 80/20 | 3.48 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 3.07 MW | 3.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959102 | AF2-201 E O1 | 80/20 | 8.8 MW | 8.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959352 | AF2-226 E | 80/20 | 3.14 MW | 3.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 1.06 MW | 1.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 1.6 MW | 1.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960282 | AF2-319 E | 80/20 | 3.14 MW | 3.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960381 | AF2-329 | 80/20 | 3.29 MW | 3.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960601 | AF2-351 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960602 | AF2-351 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 1.06 MW | 1.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 1.6 MW | 1.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 961012 | AF2-392 E O1 | 80/20 | 9.46 MW | 9.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 4.31 MW | 4.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 2.87 MW | 2.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 2.9 MW | 2.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 13.55 MW | 13.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965092 | AG1-374 E | 80/20 | 3.99 MW | 3.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C | 80/20 | 2.1 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965662 | AG1-434 E | 80/20 | 9.84 MW | 9.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 1.95 MW | 1.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 9.15 MW | 9.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966091 | AG1-478 C | 80/20 | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966092 | AG1-478 E | 80/20 | 0.49 MW | 0.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966431 | AG1-512 C | 80/20 | 1.01 MW | 1.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966432 | AG1-512 E | 80/20 | 1.52 MW | 1.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966441 | AG1-513 C | 80/20 | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966442 | AG1-513 E | 80/20 | 0.48 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 4.39 MW | 4.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966822 | AG1-553 E O1 | 80/20 | 6.58 MW | 6.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 11.2 MW | 11.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965061 | AG1-371 C | 80/20 | 2.27 MW | 2.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965062 | AG1-371 E | 80/20 | 3.41 MW | 3.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965081 | AG1-373 C | 80/20 | 0.76 MW | 0.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965082 | AG1-373 E | 80/20 | 1.14 MW | 1.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 945351 | AF1-200 FTIR | 80/20 | 151.26 MW | 151.26 MW |
| Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 109.06 MW | 109.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 106.54 MW | 106.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.32 MW | 1.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 1.02 MW | 1.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.4 MW | 0.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.6 MW | 0.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.41 MW | 0.41 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 1.18 MW | 1.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.22 MW | 1.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 0.99 MW | 0.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.85 MW | 0.85 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.65 MW | 0.65 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.81 MW | 0.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 1.55 MW | 1.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.97 MW | 0.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.97 MW | 0.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.49 MW | 0.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.84 MW | 1.84 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.8 MW | 0.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.8 MW | 0.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 1.8 MW | 1.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.24 MW | 1.24 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 2.01 MW | 2.01 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 2.01 MW | 2.01 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 1.05 MW | 1.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 1.1 MW | 1.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 8.03 MW | 8.03 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.52 MW | 0.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 1.02 MW | 1.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 1.88 MW | 1.88 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 5.35 MW | 5.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 7.22 MW | 7.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 3.94 MW | 3.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 9.18 MW | 9.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 5.39 MW | 5.39 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 5.39 MW | 5.39 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 5.79 MW | 5.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 0.96 MW | 0.96 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.49 MW | 0.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.54 MW | 0.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 3.4 MW | 3.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.73 MW | 1.73 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 1.9 MW | 1.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 3.61 MW | 3.61 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 7.0 MW | 7.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 3.64 MW | 3.64 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 2.0 MW | 2.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.83 MW | 1.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.38 MW | 2.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 5.86 MW | 5.86 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 5.86 MW | 5.86 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 8.28 MW | 8.28 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 9.05 MW | 9.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 7.35 MW | 7.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 3.19 MW | 3.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 3.19 MW | 3.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 3.51 MW | 3.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.32 MW | 0.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.38 MW | 2.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.14 MW | 0.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 1.09 MW | 1.09 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 3.6 MW | 3.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 2.31 MW | 2.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 6.25 MW | 6.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 7.37 MW | 7.37 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 1.17 MW | 1.17 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 7.81 MW | 7.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 8.5 MW | 8.5 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 1.04 MW | 1.04 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 6.99 MW | 6.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.38 MW | 1.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 9.25 MW | 9.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 5.72 MW | 5.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.76 MW | 0.76 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.43 MW | 2.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.21 MW | 0.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 15.27 MW | 15.27 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 71.26 MW | 71.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 2.52 MW | 2.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 3.9 MW | 3.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 19.05 MW | 19.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 1.91 MW | 1.91 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 7.63 MW | 7.63 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 5.96 MW | 5.96 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 21.11 MW | 21.11 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 10.04 MW | 10.04 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 4.69 MW | 4.69 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 28.83 MW | 28.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 4.08 MW | 4.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 19.14 MW | 19.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 4.49 MW | 4.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.4 MW | 1.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 9.38 MW | 9.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 2.26 MW | 2.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 6.77 MW | 6.77 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.67 MW | 0.67 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 3.6 MW | 3.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.4 MW | 2.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.32 MW | 0.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.81 MW | 1.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 13.78 MW | 13.78 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 3.26 MW | 3.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 15.33 MW | 15.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 4.29 MW | 4.29 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 20.08 MW | 20.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.36 MW | 2.36 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 3.54 MW | 3.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.48 MW | 0.48 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.72 MW | 0.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.18 MW | 0.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.57 MW | 0.57 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.25 MW | 0.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.21 MW | 1.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 5.74 MW | 5.74 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 9.02 MW | 9.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 1.14 MW | 1.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 5.33 MW | 5.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 3.41 MW | 3.41 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 5.11 MW | 5.11 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 4.51 MW | 4.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 12.94 MW | 12.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.21 MW | 2.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 3.31 MW | 3.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.7 MW | 1.7 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 2.55 MW | 2.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.5 MW | 0.5 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 0.81 MW | 0.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.21 MW | 2.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 3.31 MW | 3.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 5.09 MW | 5.09 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 1.15 MW | 1.15 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.72 MW | 1.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.7 MW | 1.7 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 2.55 MW | 2.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 2.97 MW | 2.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 13.91 MW | 13.91 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 6.33 MW | 6.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 4.22 MW | 4.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 7.83 MW | 7.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 11.74 MW | 11.74 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 4.19 MW | 4.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 19.62 MW | 19.62 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.38 MW | 1.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 9.25 MW | 9.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 144.54 MW | 144.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 6.38 MW | 6.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.4 MW | 0.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 3.2 MW | 3.2 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 15.0 MW | 15.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 11.38 MW | 11.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 11.38 MW | 11.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 7.59 MW | 7.59 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 3.1 MW | 3.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 14.49 MW | 14.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 2.83 MW | 2.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 13.25 MW | 13.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.52 MW | 0.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.78 MW | 0.78 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 1.79 MW | 1.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 2.69 MW | 2.69 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.48 MW | 0.48 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.72 MW | 0.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 14.56 MW | 14.56 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 9.64 MW | 9.64 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 16.46 MW | 16.46 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 3.35 MW | 3.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 5.02 MW | 5.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 1.12 MW | 1.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.67 MW | 1.67 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 251.18 MW | 251.18 MW |
| Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 109.06 MW | 109.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 106.54 MW | 106.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.32 MW | 1.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 1.02 MW | 1.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.4 MW | 0.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.6 MW | 0.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.41 MW | 0.41 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 1.18 MW | 1.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.22 MW | 1.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 0.99 MW | 0.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.85 MW | 0.85 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.65 MW | 0.65 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.81 MW | 0.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 1.55 MW | 1.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.97 MW | 0.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.97 MW | 0.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.49 MW | 0.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.84 MW | 1.84 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.8 MW | 0.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.8 MW | 0.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 1.8 MW | 1.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.24 MW | 1.24 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 2.01 MW | 2.01 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 2.01 MW | 2.01 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 1.05 MW | 1.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 1.1 MW | 1.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 8.03 MW | 8.03 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.52 MW | 0.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 1.02 MW | 1.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 1.88 MW | 1.88 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 5.35 MW | 5.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 7.22 MW | 7.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 3.94 MW | 3.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 9.18 MW | 9.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 5.39 MW | 5.39 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 5.39 MW | 5.39 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 5.79 MW | 5.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 0.96 MW | 0.96 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.49 MW | 0.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.54 MW | 0.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 3.4 MW | 3.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.73 MW | 1.73 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 1.9 MW | 1.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 3.61 MW | 3.61 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 7.0 MW | 7.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 3.64 MW | 3.64 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 2.0 MW | 2.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.83 MW | 1.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.38 MW | 2.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 5.86 MW | 5.86 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 5.86 MW | 5.86 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 8.28 MW | 8.28 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 9.05 MW | 9.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 7.35 MW | 7.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 3.19 MW | 3.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 3.19 MW | 3.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 3.51 MW | 3.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.32 MW | 0.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.38 MW | 2.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.14 MW | 0.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 1.09 MW | 1.09 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 3.6 MW | 3.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 2.31 MW | 2.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 6.25 MW | 6.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 7.37 MW | 7.37 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 1.17 MW | 1.17 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 7.81 MW | 7.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 8.5 MW | 8.5 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 1.04 MW | 1.04 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 6.99 MW | 6.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.38 MW | 1.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 9.25 MW | 9.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 5.72 MW | 5.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.76 MW | 0.76 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.43 MW | 2.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.21 MW | 0.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 15.27 MW | 15.27 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 71.26 MW | 71.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 2.52 MW | 2.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 3.9 MW | 3.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 19.05 MW | 19.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 1.91 MW | 1.91 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 7.63 MW | 7.63 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 5.96 MW | 5.96 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 21.11 MW | 21.11 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 10.04 MW | 10.04 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 4.69 MW | 4.69 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 28.83 MW | 28.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 4.08 MW | 4.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 19.14 MW | 19.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 4.49 MW | 4.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.4 MW | 1.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 9.38 MW | 9.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 2.26 MW | 2.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 6.77 MW | 6.77 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.67 MW | 0.67 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 3.6 MW | 3.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.4 MW | 2.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.32 MW | 0.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.81 MW | 1.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 13.78 MW | 13.78 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 3.26 MW | 3.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 15.33 MW | 15.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 4.29 MW | 4.29 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 20.08 MW | 20.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.36 MW | 2.36 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 3.54 MW | 3.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.48 MW | 0.48 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.72 MW | 0.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.18 MW | 0.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.57 MW | 0.57 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.25 MW | 0.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.21 MW | 1.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 5.74 MW | 5.74 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 9.02 MW | 9.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 1.14 MW | 1.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 5.33 MW | 5.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 3.41 MW | 3.41 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 5.11 MW | 5.11 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 4.51 MW | 4.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 12.94 MW | 12.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.21 MW | 2.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 3.31 MW | 3.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.7 MW | 1.7 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 2.55 MW | 2.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.5 MW | 0.5 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 0.81 MW | 0.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.21 MW | 2.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 3.31 MW | 3.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 5.09 MW | 5.09 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 1.15 MW | 1.15 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.72 MW | 1.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.7 MW | 1.7 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 2.55 MW | 2.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 2.97 MW | 2.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 13.91 MW | 13.91 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 6.33 MW | 6.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 4.22 MW | 4.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 7.83 MW | 7.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 11.74 MW | 11.74 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 4.19 MW | 4.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 19.62 MW | 19.62 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.38 MW | 1.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 9.25 MW | 9.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 144.54 MW | 144.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 6.38 MW | 6.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.4 MW | 0.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 3.2 MW | 3.2 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 15.0 MW | 15.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 11.38 MW | 11.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 11.38 MW | 11.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 7.59 MW | 7.59 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 3.1 MW | 3.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 14.49 MW | 14.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 2.83 MW | 2.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 13.25 MW | 13.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.52 MW | 0.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.78 MW | 0.78 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 1.79 MW | 1.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 2.69 MW | 2.69 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.48 MW | 0.48 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.72 MW | 0.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 14.56 MW | 14.56 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 9.64 MW | 9.64 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 16.46 MW | 16.46 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 3.35 MW | 3.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 5.02 MW | 5.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 1.12 MW | 1.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.67 MW | 1.67 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 251.18 MW | 251.18 MW |
| Details for ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 85.91 MW | 85.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 80.36 MW | 80.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.03 MW | 1.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.31 MW | 0.31 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.46 MW | 0.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.32 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 0.87 MW | 0.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 0.9 MW | 0.9 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 0.75 MW | 0.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.5 MW | 0.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.5 MW | 0.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 3.15 MW | 3.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 3.15 MW | 3.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.74 MW | 0.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 1.42 MW | 1.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.38 MW | 0.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.4 MW | 1.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.61 MW | 0.61 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.61 MW | 0.61 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 1.42 MW | 1.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 0.92 MW | 0.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.24 MW | 1.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.24 MW | 1.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 0.77 MW | 0.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.76 MW | 0.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 4.96 MW | 4.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.43 MW | 0.43 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 5.67 MW | 5.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 3.0 MW | 3.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 6.98 MW | 6.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 3.97 MW | 3.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 3.97 MW | 3.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 4.5 MW | 4.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 0.73 MW | 0.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.41 MW | 0.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 2.6 MW | 2.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.32 MW | 1.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 1.46 MW | 1.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 3.3 MW | 3.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 6.4 MW | 6.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 2.78 MW | 2.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 1.53 MW | 1.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.4 MW | 1.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 1.82 MW | 1.82 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 4.25 MW | 4.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 4.25 MW | 4.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 6.13 MW | 6.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 5.6 MW | 5.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 5.72 MW | 5.72 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 2.45 MW | 2.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 2.45 MW | 2.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 2.68 MW | 2.68 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.24 MW | 0.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 1.81 MW | 1.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.1 MW | 0.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 0.84 MW | 0.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 2.76 MW | 2.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 1.76 MW | 1.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 4.59 MW | 4.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 5.08 MW | 5.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 0.86 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 5.74 MW | 5.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 6.3 MW | 6.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 0.8 MW | 0.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 5.36 MW | 5.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 4.4 MW | 4.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 1.86 MW | 1.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.16 MW | 0.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 11.08 MW | 11.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 51.73 MW | 51.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 2.41 MW | 2.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 11.78 MW | 11.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 1.45 MW | 1.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 5.81 MW | 5.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 4.67 MW | 4.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 16.57 MW | 16.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 7.67 MW | 7.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 3.35 MW | 3.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 20.56 MW | 20.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 13.8 MW | 13.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 3.3 MW | 3.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.03 MW | 1.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 6.89 MW | 6.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 1.77 MW | 1.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 5.31 MW | 5.31 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.48 MW | 0.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 2.94 MW | 2.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 2.75 MW | 2.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 1.83 MW | 1.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.24 MW | 0.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.38 MW | 1.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 10.54 MW | 10.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 2.49 MW | 2.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 11.71 MW | 11.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 15.35 MW | 15.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 1.8 MW | 1.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 2.71 MW | 2.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.39 MW | 0.39 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.58 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.14 MW | 0.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.44 MW | 0.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.19 MW | 0.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 0.93 MW | 0.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 3.55 MW | 3.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 8.0 MW | 8.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 2.6 MW | 2.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 3.91 MW | 3.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 3.44 MW | 3.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 9.89 MW | 9.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.02 MW | 2.02 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 3.03 MW | 3.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.25 MW | 1.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 1.88 MW | 1.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.02 MW | 2.02 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 3.03 MW | 3.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 3.84 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.06 MW | 1.06 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.25 MW | 1.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 1.88 MW | 1.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 2.27 MW | 2.27 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 10.64 MW | 10.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 4.84 MW | 4.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 3.23 MW | 3.23 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 5.94 MW | 5.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 8.91 MW | 8.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 3.21 MW | 3.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 15.04 MW | 15.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 34.53 MW | 34.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 4.69 MW | 4.69 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.29 MW | 0.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 2.36 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 11.07 MW | 11.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 8.4 MW | 8.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 8.4 MW | 8.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 5.6 MW | 5.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 2.37 MW | 2.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 11.09 MW | 11.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 2.17 MW | 2.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 10.16 MW | 10.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.36 MW | 0.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.55 MW | 0.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 1.12 MW | 1.12 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 1.68 MW | 1.68 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.55 MW | 0.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 5.26 MW | 5.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 7.38 MW | 7.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 12.59 MW | 12.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 2.56 MW | 2.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 3.84 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 0.85 MW | 0.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.28 MW | 1.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 189.4 MW | 189.4 MW |
| Details for ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 85.91 MW | 85.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 80.36 MW | 80.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.03 MW | 1.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.31 MW | 0.31 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.46 MW | 0.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.32 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 0.87 MW | 0.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 0.9 MW | 0.9 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 0.75 MW | 0.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.5 MW | 0.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.5 MW | 0.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 3.15 MW | 3.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 3.15 MW | 3.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.74 MW | 0.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 1.42 MW | 1.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.38 MW | 0.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.4 MW | 1.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.61 MW | 0.61 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.61 MW | 0.61 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 1.42 MW | 1.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 0.92 MW | 0.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.24 MW | 1.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.24 MW | 1.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 0.77 MW | 0.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.76 MW | 0.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 4.96 MW | 4.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.43 MW | 0.43 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 5.67 MW | 5.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 3.0 MW | 3.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 6.98 MW | 6.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 3.97 MW | 3.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 3.97 MW | 3.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 4.5 MW | 4.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 0.73 MW | 0.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.41 MW | 0.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 2.6 MW | 2.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.32 MW | 1.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 1.46 MW | 1.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 3.3 MW | 3.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 6.4 MW | 6.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 2.78 MW | 2.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 1.53 MW | 1.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.4 MW | 1.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 1.82 MW | 1.82 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 4.25 MW | 4.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 4.25 MW | 4.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 6.13 MW | 6.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 5.6 MW | 5.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 5.72 MW | 5.72 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 2.45 MW | 2.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 2.45 MW | 2.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 2.68 MW | 2.68 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.24 MW | 0.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 1.81 MW | 1.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.1 MW | 0.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 0.84 MW | 0.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 2.76 MW | 2.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 1.76 MW | 1.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 4.59 MW | 4.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 5.08 MW | 5.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 0.86 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 5.74 MW | 5.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 6.3 MW | 6.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 0.8 MW | 0.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 5.36 MW | 5.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 4.4 MW | 4.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 1.86 MW | 1.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.16 MW | 0.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 11.08 MW | 11.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 51.73 MW | 51.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 2.41 MW | 2.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 11.78 MW | 11.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 1.45 MW | 1.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 5.81 MW | 5.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 4.67 MW | 4.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 16.57 MW | 16.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 7.67 MW | 7.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 3.35 MW | 3.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 20.56 MW | 20.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 13.8 MW | 13.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 3.3 MW | 3.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.03 MW | 1.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 6.89 MW | 6.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 1.77 MW | 1.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 5.31 MW | 5.31 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.48 MW | 0.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 2.94 MW | 2.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 2.75 MW | 2.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 1.83 MW | 1.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.24 MW | 0.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.38 MW | 1.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 10.54 MW | 10.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 2.49 MW | 2.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 11.71 MW | 11.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 15.35 MW | 15.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 1.8 MW | 1.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 2.71 MW | 2.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.39 MW | 0.39 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.58 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.14 MW | 0.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.44 MW | 0.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.19 MW | 0.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 0.93 MW | 0.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 3.55 MW | 3.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 8.0 MW | 8.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 2.6 MW | 2.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 3.91 MW | 3.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 3.44 MW | 3.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 9.89 MW | 9.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.02 MW | 2.02 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 3.03 MW | 3.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.25 MW | 1.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 1.88 MW | 1.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.02 MW | 2.02 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 3.03 MW | 3.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 3.84 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.06 MW | 1.06 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.25 MW | 1.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 1.88 MW | 1.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 2.27 MW | 2.27 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 10.64 MW | 10.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 4.84 MW | 4.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 3.23 MW | 3.23 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 5.94 MW | 5.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 8.91 MW | 8.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 3.21 MW | 3.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 15.04 MW | 15.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 34.53 MW | 34.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 4.69 MW | 4.69 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.29 MW | 0.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 2.36 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 11.07 MW | 11.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 8.4 MW | 8.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 8.4 MW | 8.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 5.6 MW | 5.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 2.37 MW | 2.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 11.09 MW | 11.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 2.17 MW | 2.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 10.16 MW | 10.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.36 MW | 0.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.55 MW | 0.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 1.12 MW | 1.12 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 1.68 MW | 1.68 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.55 MW | 0.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 5.26 MW | 5.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 7.38 MW | 7.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 12.59 MW | 12.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 2.56 MW | 2.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 3.84 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 0.85 MW | 0.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.28 MW | 1.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 189.4 MW | 189.4 MW |
| Details for WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274658 | DRESDEN ;2U | 80/20 | 243.95 MW | 243.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274659 | DRESDEN ;3U | 80/20 | 256.29 MW | 256.29 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274847 | GR RIDGE ;BU | 80/20 | 3.15 MW | 3.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 2.37 MW | 2.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.93 MW | 0.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 1.43 MW | 1.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.96 MW | 0.96 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 2.81 MW | 2.81 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 2.89 MW | 2.89 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 2.36 MW | 2.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 2.0 MW | 2.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 1.54 MW | 1.54 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 1.54 MW | 1.54 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274859 | EASYR;U1 E | 80/20 | 9.72 MW | 9.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274860 | EASYR;U2 E | 80/20 | 9.72 MW | 9.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274861 | TOP CROP ;1U | 80/20 | 1.83 MW | 1.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274862 | TOP CROP ;2U | 80/20 | 3.5 MW | 3.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 2.28 MW | 2.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 2.28 MW | 2.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274871 | GR RIDGE ;2U | 80/20 | 1.17 MW | 1.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 4.41 MW | 4.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 1.85 MW | 1.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 1.85 MW | 1.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274879 | MINONK ;1U | 80/20 | 4.04 MW | 4.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274880 | RADFORD R;1U | 80/20 | 2.97 MW | 2.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274887 | PILOT HIL;1U | 80/20 | 3.65 MW | 3.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274888 | KELLY CRK;1U | 80/20 | 3.65 MW | 3.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 2.5 MW | 2.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274891 | OTTER CRK;1U | 80/20 | 2.2 MW | 2.2 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 275149 | KELLYCK ;1E | 80/20 | 14.59 MW | 14.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 1.22 MW | 1.22 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 1.32 MW | 1.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 2.41 MW | 2.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276615 | W2-048 GEN | 80/20 | 4.51 MW | 4.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276621 | X2-022 GEN | 80/20 | 12.84 MW | 12.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290021 | O50 E | 80/20 | 16.14 MW | 16.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290051 | GSG-6; E | 80/20 | 9.44 MW | 9.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290108 | LEEDK;1U E | 80/20 | 22.05 MW | 22.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 12.8 MW | 12.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 12.8 MW | 12.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293061 | N-015 E | 80/20 | 13.78 MW | 13.78 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 2.25 MW | 2.25 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 1.14 MW | 1.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 1.26 MW | 1.26 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293516 | O-009 E1 | 80/20 | 8.01 MW | 8.01 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293517 | O-009 E2 | 80/20 | 4.07 MW | 4.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293518 | O-009 E3 | 80/20 | 4.48 MW | 4.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293644 | O22 E1 | 80/20 | 8.13 MW | 8.13 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293645 | O22 E2 | 80/20 | 15.79 MW | 15.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293715 | O-029 E | 80/20 | 8.56 MW | 8.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293716 | O-029 E | 80/20 | 4.69 MW | 4.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293717 | O-029 E | 80/20 | 4.31 MW | 4.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 5.51 MW | 5.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293777 | CAYUG;1U E | 80/20 | 13.69 MW | 13.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293778 | CAYUG;2U E | 80/20 | 13.69 MW | 13.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293798 | W4-005 E | 80/20 | 19.85 MW | 19.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293799 | PILOT HIL;1E | 80/20 | 16.44 MW | 16.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294392 | P-010 E | 80/20 | 17.5 MW | 17.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 7.41 MW | 7.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 7.41 MW | 7.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294763 | P-046 E | 80/20 | 8.27 MW | 8.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.77 MW | 0.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 295109 | WESTBROOK E | 80/20 | 5.69 MW | 5.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.32 MW | 0.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 295111 | SUBLETTE E | 80/20 | 2.59 MW | 2.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 916211 | Z1-072 E | 80/20 | 8.34 MW | 8.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 916221 | Z1-073 E | 80/20 | 5.52 MW | 5.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 14.82 MW | 14.82 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 918052 | AA1-018 E OP | 80/20 | 14.75 MW | 14.75 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 18.52 MW | 18.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924261 | AB2-070 C O1 | 80/20 | 3.36 MW | 3.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924262 | AB2-070 E O1 | 80/20 | 20.38 MW | 20.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 2.43 MW | 2.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 16.24 MW | 16.24 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925771 | AC1-053 C | 80/20 | 3.31 MW | 3.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925772 | AC1-053 E | 80/20 | 22.17 MW | 22.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 1.98 MW | 1.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 13.3 MW | 13.3 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 1.77 MW | 1.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 5.62 MW | 5.62 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.12 MW | 0.12 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934432 | AD1-067 E | 80/20 | 0.5 MW | 0.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934721 | AD1-100 C | 80/20 | 34.17 MW | 34.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934722 | AD1-100 E | 80/20 | 159.48 MW | 159.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 935141 | AD1-148 | 80/20 | 6.04 MW | 6.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 936371 | AD2-047 C O1 | 80/20 | 7.09 MW | 7.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 936372 | AD2-047 E O1 | 80/20 | 34.6 MW | 34.6 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 4.57 MW | 4.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 937002 | AD2-134 E | 80/20 | 18.25 MW | 18.25 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C O1 | 80/20 | 13.31 MW | 13.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938852 | AE1-113 E O1 | 80/20 | 47.21 MW | 47.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 6.94 MW | 6.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938862 | AE1-114 E O1 | 80/20 | 23.69 MW | 23.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | 80/20 | 9.68 MW | 9.68 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939322 | AE1-163 E O1 | 80/20 | 59.45 MW | 59.45 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 9.48 MW | 9.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939402 | AE1-172 E O1 | 80/20 | 44.49 MW | 44.49 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 10.64 MW | 10.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 3.32 MW | 3.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 22.23 MW | 22.23 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | 80/20 | 5.04 MW | 5.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942422 | AE2-255 E O1 | 80/20 | 15.13 MW | 15.13 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942652 | AE2-281 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 943801 | AF1-048 C | 80/20 | 8.48 MW | 8.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 943802 | AF1-048 E | 80/20 | 5.65 MW | 5.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.75 MW | 0.75 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946162 | AF1-281 E O1 | 80/20 | 4.27 MW | 4.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 6.93 MW | 6.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946322 | AF1-296 E O1 | 80/20 | 32.42 MW | 32.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 7.69 MW | 7.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946502 | AF1-314 E | 80/20 | 36.14 MW | 36.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 9.91 MW | 9.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 46.4 MW | 46.4 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957331 | AF2-027 C | 80/20 | 5.43 MW | 5.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957332 | AF2-027 E | 80/20 | 8.14 MW | 8.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957371 | AF2-031 C O1 | 80/20 | 1.69 MW | 1.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957372 | AF2-031 E O1 | 80/20 | 2.54 MW | 2.54 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957401 | AF2-034 C | 80/20 | 1.08 MW | 1.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957402 | AF2-034 E | 80/20 | 1.62 MW | 1.62 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.41 MW | 0.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 1.32 MW | 1.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.58 MW | 0.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 2.8 MW | 2.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958011 | AF2-095 C O1 | 80/20 | 10.42 MW | 10.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958021 | AF2-096 C | 80/20 | 20.27 MW | 20.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 12.32 MW | 12.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 8.05 MW | 8.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958922 | AF2-183 E | 80/20 | 12.07 MW | 12.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 10.63 MW | 10.63 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959102 | AF2-201 E O1 | 80/20 | 30.51 MW | 30.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959351 | AF2-226 C | 80/20 | 4.98 MW | 4.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959352 | AF2-226 E | 80/20 | 7.47 MW | 7.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 4.04 MW | 4.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 6.06 MW | 6.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960141 | AF2-305 | 80/20 | 1.19 MW | 1.19 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960261 | AF2-317 | 80/20 | 1.93 MW | 1.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960281 | AF2-319 C | 80/20 | 4.98 MW | 4.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960282 | AF2-319 E | 80/20 | 7.47 MW | 7.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960381 | AF2-329 | 80/20 | 12.58 MW | 12.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960601 | AF2-351 C O1 | 80/20 | 2.08 MW | 2.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960602 | AF2-351 E O1 | 80/20 | 3.13 MW | 3.13 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 4.04 MW | 4.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 6.06 MW | 6.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 7.02 MW | 7.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961012 | AF2-392 E O1 | 80/20 | 32.86 MW | 32.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 14.96 MW | 14.96 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 9.97 MW | 9.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961501 | AF2-441 C O1 | 80/20 | 18.23 MW | 18.23 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961502 | AF2-441 E O1 | 80/20 | 27.35 MW | 27.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 962012 | AG1-044 E | 80/20 | 0.14 MW | 0.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 9.72 MW | 9.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 45.49 MW | 45.49 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 963831 | AG1-236 C | 80/20 | 3.31 MW | 3.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 963832 | AG1-236 E | 80/20 | 22.17 MW | 22.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 964361 | AG1-298 O1 | 80/20 | 112.0 MW | 112.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965092 | AG1-374 E | 80/20 | 15.15 MW | 15.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965331 | AG1-398 | 80/20 | 0.95 MW | 0.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965341 | AG1-399 C O1 | 80/20 | 7.64 MW | 7.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965342 | AG1-399 E O1 | 80/20 | 35.79 MW | 35.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965351 | AG1-400 O1 | 80/20 | 27.14 MW | 27.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965371 | AG1-402 O1 | 80/20 | 27.14 MW | 27.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965391 | AG1-404 O1 | 80/20 | 18.1 MW | 18.1 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C | 80/20 | 7.35 MW | 7.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965662 | AG1-434 E | 80/20 | 34.42 MW | 34.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 6.57 MW | 6.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 30.74 MW | 30.74 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966091 | AG1-478 C | 80/20 | 1.06 MW | 1.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966092 | AG1-478 E | 80/20 | 1.59 MW | 1.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966431 | AG1-512 C | 80/20 | 3.56 MW | 3.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966432 | AG1-512 E | 80/20 | 5.35 MW | 5.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966441 | AG1-513 C | 80/20 | 1.16 MW | 1.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966442 | AG1-513 E | 80/20 | 1.74 MW | 1.74 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966651 | AG1-535 O1 | 80/20 | 17.93 MW | 17.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 15.12 MW | 15.12 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966822 | AG1-553 E O1 | 80/20 | 22.68 MW | 22.68 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 38.88 MW | 38.88 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965061 | AG1-371 C | 80/20 | 7.97 MW | 7.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965062 | AG1-371 E | 80/20 | 11.95 MW | 11.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965081 | AG1-373 C | 80/20 | 2.66 MW | 2.66 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965082 | AG1-373 E | 80/20 | 3.98 MW | 3.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 945351 | AF1-200 FTIR | 80/20 | 686.73 MW | 686.73 MW |
| Details for GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 76.84 MW | 76.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 72.87 MW | 72.87 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 0.92 MW | 0.92 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.71 MW | 0.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.28 MW | 0.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.41 MW | 0.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.29 MW | 0.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 0.8 MW | 0.8 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 0.83 MW | 0.83 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 0.68 MW | 0.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.59 MW | 0.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.45 MW | 0.45 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.45 MW | 0.45 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 2.85 MW | 2.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 2.85 MW | 2.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.64 MW | 0.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 1.22 MW | 1.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.65 MW | 0.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.65 MW | 0.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.34 MW | 0.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.26 MW | 1.26 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 1.27 MW | 1.27 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.22 MW | 1.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.22 MW | 1.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 0.71 MW | 0.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.7 MW | 0.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 4.88 MW | 4.88 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.36 MW | 0.36 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.39 MW | 0.39 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 0.71 MW | 0.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 5.08 MW | 5.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 2.72 MW | 2.72 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 6.32 MW | 6.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 3.65 MW | 3.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 3.65 MW | 3.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 4.03 MW | 4.03 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 0.66 MW | 0.66 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.34 MW | 0.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.37 MW | 0.37 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 2.35 MW | 2.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.2 MW | 1.2 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 1.32 MW | 1.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 2.84 MW | 2.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 5.51 MW | 5.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 2.52 MW | 2.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 1.38 MW | 1.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.27 MW | 1.27 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 1.65 MW | 1.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 3.91 MW | 3.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 3.91 MW | 3.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 5.5 MW | 5.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 5.11 MW | 5.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 2.21 MW | 2.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 2.21 MW | 2.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 2.42 MW | 2.42 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.22 MW | 0.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 1.64 MW | 1.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.09 MW | 0.09 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 0.76 MW | 0.76 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 2.49 MW | 2.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 1.59 MW | 1.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 4.23 MW | 4.23 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 4.69 MW | 4.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 5.29 MW | 5.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 0.72 MW | 0.72 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 4.85 MW | 4.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 3.97 MW | 3.97 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.53 MW | 0.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 1.68 MW | 1.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.03 MW | 0.03 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.14 MW | 0.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 10.16 MW | 10.16 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 47.44 MW | 47.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 2.37 MW | 2.37 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 11.57 MW | 11.57 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 1.31 MW | 1.31 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 5.25 MW | 5.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 4.19 MW | 4.19 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 14.84 MW | 14.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 2.03 MW | 2.03 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 6.93 MW | 6.93 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 3.06 MW | 3.06 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 18.82 MW | 18.82 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 12.73 MW | 12.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 3.04 MW | 3.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 0.95 MW | 0.95 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 6.35 MW | 6.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 1.59 MW | 1.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 4.76 MW | 4.76 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.44 MW | 0.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 2.69 MW | 2.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 2.48 MW | 2.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 1.66 MW | 1.66 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.22 MW | 0.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.25 MW | 1.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 2.04 MW | 2.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 9.54 MW | 9.54 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 2.25 MW | 2.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 10.59 MW | 10.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 2.97 MW | 2.97 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 13.89 MW | 13.89 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 1.63 MW | 1.63 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 2.44 MW | 2.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 1.11 MW | 1.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.35 MW | 0.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.52 MW | 0.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.4 MW | 0.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 0.84 MW | 0.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 3.49 MW | 3.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 6.81 MW | 6.81 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 3.69 MW | 3.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 2.36 MW | 2.36 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 3.53 MW | 3.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 3.11 MW | 3.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 8.94 MW | 8.94 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 1.74 MW | 1.74 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 2.61 MW | 2.61 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.15 MW | 1.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 1.73 MW | 1.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 1.74 MW | 1.74 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 2.61 MW | 2.61 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 3.49 MW | 3.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.7 MW | 0.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.05 MW | 1.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.15 MW | 1.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 1.73 MW | 1.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 2.05 MW | 2.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 9.62 MW | 9.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 4.38 MW | 4.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 2.92 MW | 2.92 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 7.29 MW | 7.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 2.91 MW | 2.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 13.6 MW | 13.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 46.8 MW | 46.8 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 4.33 MW | 4.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 2.18 MW | 2.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 10.22 MW | 10.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 7.75 MW | 7.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 7.75 MW | 7.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 5.17 MW | 5.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 2.14 MW | 2.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 10.02 MW | 10.02 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 1.96 MW | 1.96 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 9.18 MW | 9.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.34 MW | 0.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.51 MW | 0.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 0.97 MW | 0.97 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 1.45 MW | 1.45 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.33 MW | 0.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.5 MW | 0.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 7.96 MW | 7.96 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 6.68 MW | 6.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 11.38 MW | 11.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 2.31 MW | 2.31 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 3.47 MW | 3.47 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 0.77 MW | 0.77 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.16 MW | 1.16 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 171.61 MW | 171.61 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965792 | AG1-447 BAT | 80/20 | 4.39 MW | 4.39 MW |
| Details for GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 76.84 MW | 76.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 72.87 MW | 72.87 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 0.92 MW | 0.92 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 0.71 MW | 0.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.28 MW | 0.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.41 MW | 0.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.29 MW | 0.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 0.8 MW | 0.8 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 0.83 MW | 0.83 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 0.68 MW | 0.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.59 MW | 0.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.45 MW | 0.45 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.45 MW | 0.45 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 2.85 MW | 2.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 2.85 MW | 2.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.64 MW | 0.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 1.22 MW | 1.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.65 MW | 0.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.65 MW | 0.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.34 MW | 0.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.26 MW | 1.26 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 1.27 MW | 1.27 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.22 MW | 1.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.22 MW | 1.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 0.71 MW | 0.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.7 MW | 0.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 4.88 MW | 4.88 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.36 MW | 0.36 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.39 MW | 0.39 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 0.71 MW | 0.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 5.08 MW | 5.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 2.72 MW | 2.72 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 6.32 MW | 6.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 3.65 MW | 3.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 3.65 MW | 3.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 4.03 MW | 4.03 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 0.66 MW | 0.66 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.34 MW | 0.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.37 MW | 0.37 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 2.35 MW | 2.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.2 MW | 1.2 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 1.32 MW | 1.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 2.84 MW | 2.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 5.51 MW | 5.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 2.52 MW | 2.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 1.38 MW | 1.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.27 MW | 1.27 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 1.65 MW | 1.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 3.91 MW | 3.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 3.91 MW | 3.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 5.5 MW | 5.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 5.11 MW | 5.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 2.21 MW | 2.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 2.21 MW | 2.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 2.42 MW | 2.42 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.22 MW | 0.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 1.64 MW | 1.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.09 MW | 0.09 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 0.76 MW | 0.76 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 2.49 MW | 2.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 1.59 MW | 1.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 4.23 MW | 4.23 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 4.69 MW | 4.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 5.29 MW | 5.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 0.72 MW | 0.72 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 4.85 MW | 4.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 3.97 MW | 3.97 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.53 MW | 0.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 1.68 MW | 1.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.03 MW | 0.03 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.14 MW | 0.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 10.16 MW | 10.16 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 47.44 MW | 47.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 2.37 MW | 2.37 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 11.57 MW | 11.57 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 1.31 MW | 1.31 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 5.25 MW | 5.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 4.19 MW | 4.19 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 14.84 MW | 14.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 2.03 MW | 2.03 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 6.93 MW | 6.93 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 3.06 MW | 3.06 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 18.82 MW | 18.82 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 12.73 MW | 12.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 3.04 MW | 3.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 0.95 MW | 0.95 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 6.35 MW | 6.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 1.59 MW | 1.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 4.76 MW | 4.76 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.44 MW | 0.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 2.69 MW | 2.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 2.48 MW | 2.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 1.66 MW | 1.66 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.22 MW | 0.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.25 MW | 1.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 2.04 MW | 2.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 9.54 MW | 9.54 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 2.25 MW | 2.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 10.59 MW | 10.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 2.97 MW | 2.97 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 13.89 MW | 13.89 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 1.63 MW | 1.63 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 2.44 MW | 2.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 1.11 MW | 1.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.35 MW | 0.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.52 MW | 0.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.4 MW | 0.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 0.84 MW | 0.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 3.49 MW | 3.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 6.81 MW | 6.81 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 3.69 MW | 3.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 2.36 MW | 2.36 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 3.53 MW | 3.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 3.11 MW | 3.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 8.94 MW | 8.94 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 1.74 MW | 1.74 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 2.61 MW | 2.61 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.15 MW | 1.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 1.73 MW | 1.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 1.74 MW | 1.74 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 2.61 MW | 2.61 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 3.49 MW | 3.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.7 MW | 0.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.05 MW | 1.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.15 MW | 1.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 1.73 MW | 1.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 2.05 MW | 2.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 9.62 MW | 9.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 4.38 MW | 4.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 2.92 MW | 2.92 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 7.29 MW | 7.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 2.91 MW | 2.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 13.6 MW | 13.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 46.8 MW | 46.8 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 4.33 MW | 4.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 2.18 MW | 2.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 10.22 MW | 10.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 7.75 MW | 7.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 7.75 MW | 7.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 5.17 MW | 5.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 2.14 MW | 2.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 10.02 MW | 10.02 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 1.96 MW | 1.96 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 9.18 MW | 9.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.34 MW | 0.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.51 MW | 0.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 0.97 MW | 0.97 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 1.45 MW | 1.45 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.33 MW | 0.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.5 MW | 0.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 7.96 MW | 7.96 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 6.68 MW | 6.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 11.38 MW | 11.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 2.31 MW | 2.31 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 3.47 MW | 3.47 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 0.77 MW | 0.77 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.16 MW | 1.16 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 171.61 MW | 171.61 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965792 | AG1-447 BAT | 80/20 | 4.39 MW | 4.39 MW |
| Details for E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 93.0 MW | 93.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 89.8 MW | 89.8 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.14 MW | 1.14 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.51 MW | 0.51 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 0.97 MW | 0.97 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.0 MW | 1.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.72 MW | 0.72 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 3.48 MW | 3.48 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 3.48 MW | 3.48 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 1.34 MW | 1.34 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.79 MW | 0.79 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.79 MW | 0.79 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.42 MW | 0.42 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.55 MW | 1.55 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.02 MW | 1.02 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.47 MW | 1.47 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.47 MW | 1.47 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 0.86 MW | 0.86 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.95 MW | 0.95 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 5.89 MW | 5.89 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.47 MW | 0.47 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 0.87 MW | 0.87 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 1.56 MW | 1.56 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 4.43 MW | 4.43 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 6.16 MW | 6.16 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 3.33 MW | 3.33 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 7.74 MW | 7.74 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 5.0 MW | 5.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 0.81 MW | 0.81 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.46 MW | 0.46 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 2.88 MW | 2.88 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.46 MW | 1.46 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 1.61 MW | 1.61 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 3.11 MW | 3.11 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 6.04 MW | 6.04 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 3.08 MW | 3.08 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 1.69 MW | 1.69 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.55 MW | 1.55 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.02 MW | 2.02 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 4.73 MW | 4.73 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 4.73 MW | 4.73 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 6.83 MW | 6.83 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 6.64 MW | 6.64 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 6.34 MW | 6.34 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 2.7 MW | 2.7 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 2.7 MW | 2.7 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 2.96 MW | 2.96 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.27 MW | 0.27 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.01 MW | 2.01 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.12 MW | 0.12 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 0.93 MW | 0.93 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 3.05 MW | 3.05 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 1.95 MW | 1.95 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 5.12 MW | 5.12 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 6.36 MW | 6.36 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.16 MW | 1.16 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 7.02 MW | 7.02 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 5.93 MW | 5.93 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.14 MW | 1.14 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 7.64 MW | 7.64 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 4.87 MW | 4.87 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.06 MW | 2.06 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.18 MW | 0.18 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 12.33 MW | 12.33 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 57.54 MW | 57.54 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 2.08 MW | 2.08 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 13.98 MW | 13.98 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 1.61 MW | 1.61 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 6.44 MW | 6.44 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 18.01 MW | 18.01 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 4.04 MW | 4.04 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 24.8 MW | 24.8 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 15.38 MW | 15.38 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 3.68 MW | 3.68 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.15 MW | 1.15 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 7.69 MW | 7.69 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 5.77 MW | 5.77 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 3.54 MW | 3.54 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 3.04 MW | 3.04 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.03 MW | 2.03 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.27 MW | 0.27 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.53 MW | 1.53 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 11.65 MW | 11.65 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 2.76 MW | 2.76 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 12.96 MW | 12.96 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 17.04 MW | 17.04 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.0 MW | 2.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.95 MW | 0.95 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.62 MW | 0.62 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.03 MW | 1.03 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 8.1 MW | 8.1 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 4.53 MW | 4.53 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 2.88 MW | 2.88 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 4.32 MW | 4.32 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 1.91 MW | 1.91 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 2.86 MW | 2.86 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.4 MW | 1.4 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 2.09 MW | 2.09 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 0.67 MW | 0.67 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 1.91 MW | 1.91 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 2.86 MW | 2.86 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 4.28 MW | 4.28 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.26 MW | 1.26 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.4 MW | 1.4 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 2.09 MW | 2.09 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 2.51 MW | 2.51 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 11.76 MW | 11.76 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 5.35 MW | 5.35 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 3.57 MW | 3.57 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 6.96 MW | 6.96 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.05 MW | 0.05 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 16.65 MW | 16.65 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.14 MW | 1.14 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 7.64 MW | 7.64 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 43.13 MW | 43.13 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 5.23 MW | 5.23 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.33 MW | 0.33 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 12.34 MW | 12.34 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 9.36 MW | 9.36 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 9.36 MW | 9.36 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 6.24 MW | 6.24 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 2.62 MW | 2.62 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 12.24 MW | 12.24 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 2.4 MW | 2.4 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 11.24 MW | 11.24 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.42 MW | 0.42 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.63 MW | 0.63 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.61 MW | 0.61 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 6.8 MW | 6.8 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 5.44 MW | 5.44 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 8.15 MW | 8.15 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 13.91 MW | 13.91 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 2.83 MW | 2.83 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 4.24 MW | 4.24 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 0.94 MW | 0.94 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.41 MW | 1.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 210.26 MW | 210.26 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965792 | AG1-447 BAT | 80/20 | 8.14 MW | 8.14 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966433 | AG1-512 BAT | 80/20 | 30.96 MW | 30.96 MW |
| Details for E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 93.0 MW | 93.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 89.8 MW | 89.8 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.14 MW | 1.14 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.51 MW | 0.51 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 0.97 MW | 0.97 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.0 MW | 1.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.72 MW | 0.72 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 3.48 MW | 3.48 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 3.48 MW | 3.48 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 1.34 MW | 1.34 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.79 MW | 0.79 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.79 MW | 0.79 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.42 MW | 0.42 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.55 MW | 1.55 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.02 MW | 1.02 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.47 MW | 1.47 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.47 MW | 1.47 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 0.86 MW | 0.86 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.95 MW | 0.95 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 5.89 MW | 5.89 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.47 MW | 0.47 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 0.87 MW | 0.87 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 1.56 MW | 1.56 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 4.43 MW | 4.43 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 6.16 MW | 6.16 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 3.33 MW | 3.33 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 7.74 MW | 7.74 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 5.0 MW | 5.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 0.81 MW | 0.81 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.46 MW | 0.46 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 2.88 MW | 2.88 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.46 MW | 1.46 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 1.61 MW | 1.61 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 3.11 MW | 3.11 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 6.04 MW | 6.04 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 3.08 MW | 3.08 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 1.69 MW | 1.69 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.55 MW | 1.55 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.02 MW | 2.02 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 4.73 MW | 4.73 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 4.73 MW | 4.73 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 6.83 MW | 6.83 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 6.64 MW | 6.64 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 6.34 MW | 6.34 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 2.7 MW | 2.7 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 2.7 MW | 2.7 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 2.96 MW | 2.96 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.27 MW | 0.27 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.01 MW | 2.01 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.12 MW | 0.12 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 0.93 MW | 0.93 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 3.05 MW | 3.05 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 1.95 MW | 1.95 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 5.12 MW | 5.12 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 6.36 MW | 6.36 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.16 MW | 1.16 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 7.02 MW | 7.02 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 5.93 MW | 5.93 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.14 MW | 1.14 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 7.64 MW | 7.64 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 4.87 MW | 4.87 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.06 MW | 2.06 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.18 MW | 0.18 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 12.33 MW | 12.33 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 57.54 MW | 57.54 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 2.08 MW | 2.08 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 13.98 MW | 13.98 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 1.61 MW | 1.61 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 6.44 MW | 6.44 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 18.01 MW | 18.01 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 4.04 MW | 4.04 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 24.8 MW | 24.8 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 15.38 MW | 15.38 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 3.68 MW | 3.68 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.15 MW | 1.15 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 7.69 MW | 7.69 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 5.77 MW | 5.77 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 3.54 MW | 3.54 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 3.04 MW | 3.04 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.03 MW | 2.03 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.27 MW | 0.27 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.53 MW | 1.53 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 11.65 MW | 11.65 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 2.76 MW | 2.76 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 12.96 MW | 12.96 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 17.04 MW | 17.04 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.0 MW | 2.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.95 MW | 0.95 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.62 MW | 0.62 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.03 MW | 1.03 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 8.1 MW | 8.1 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 4.53 MW | 4.53 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 2.88 MW | 2.88 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 4.32 MW | 4.32 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 1.91 MW | 1.91 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 2.86 MW | 2.86 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.4 MW | 1.4 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 2.09 MW | 2.09 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 0.67 MW | 0.67 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 1.91 MW | 1.91 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 2.86 MW | 2.86 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 4.28 MW | 4.28 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.26 MW | 1.26 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.4 MW | 1.4 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 2.09 MW | 2.09 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 2.51 MW | 2.51 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 11.76 MW | 11.76 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 5.35 MW | 5.35 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 3.57 MW | 3.57 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 6.96 MW | 6.96 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.05 MW | 0.05 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 3.56 MW | 3.56 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 16.65 MW | 16.65 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.14 MW | 1.14 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 7.64 MW | 7.64 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 43.13 MW | 43.13 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 5.23 MW | 5.23 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.33 MW | 0.33 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 12.34 MW | 12.34 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 9.36 MW | 9.36 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 9.36 MW | 9.36 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 6.24 MW | 6.24 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 2.62 MW | 2.62 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 12.24 MW | 12.24 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 2.4 MW | 2.4 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 11.24 MW | 11.24 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.42 MW | 0.42 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.63 MW | 0.63 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.61 MW | 0.61 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 6.8 MW | 6.8 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 5.44 MW | 5.44 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 8.15 MW | 8.15 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 13.91 MW | 13.91 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 2.83 MW | 2.83 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 4.24 MW | 4.24 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 0.94 MW | 0.94 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.41 MW | 1.41 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 210.26 MW | 210.26 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965792 | AG1-447 BAT | 80/20 | 8.14 MW | 8.14 MW |
| E FRANKFO; R-UNIV PK N;RP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966433 | AG1-512 BAT | 80/20 | 30.96 MW | 30.96 MW |
| Details for 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 85.91 MW | 85.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 80.36 MW | 80.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.03 MW | 1.03 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 0.78 MW | 0.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.31 MW | 0.31 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.46 MW | 0.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.32 MW | 0.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 0.87 MW | 0.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 0.9 MW | 0.9 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 0.75 MW | 0.75 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.5 MW | 0.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.5 MW | 0.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.74 MW | 0.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 1.42 MW | 1.42 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.71 MW | 0.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.71 MW | 0.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.38 MW | 0.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.4 MW | 1.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.61 MW | 0.61 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.61 MW | 0.61 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 1.42 MW | 1.42 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 0.92 MW | 0.92 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.24 MW | 1.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.24 MW | 1.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 0.77 MW | 0.77 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.76 MW | 0.76 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 4.96 MW | 4.96 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.43 MW | 0.43 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 0.78 MW | 0.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 5.67 MW | 5.67 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 3.0 MW | 3.0 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 6.98 MW | 6.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 3.97 MW | 3.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 3.97 MW | 3.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 4.5 MW | 4.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 0.73 MW | 0.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.37 MW | 0.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.41 MW | 0.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 2.6 MW | 2.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.32 MW | 1.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 1.46 MW | 1.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 3.3 MW | 3.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 6.4 MW | 6.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 2.78 MW | 2.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 1.53 MW | 1.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.4 MW | 1.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 1.82 MW | 1.82 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 4.25 MW | 4.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 4.25 MW | 4.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 6.13 MW | 6.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 5.6 MW | 5.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 5.72 MW | 5.72 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 2.45 MW | 2.45 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 2.45 MW | 2.45 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 2.68 MW | 2.68 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.24 MW | 0.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 1.81 MW | 1.81 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.1 MW | 0.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 0.84 MW | 0.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 2.76 MW | 2.76 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 1.76 MW | 1.76 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 4.59 MW | 4.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 5.08 MW | 5.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 0.86 MW | 0.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 5.74 MW | 5.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 6.3 MW | 6.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 0.8 MW | 0.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 5.36 MW | 5.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 4.4 MW | 4.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 1.86 MW | 1.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.16 MW | 0.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 11.08 MW | 11.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 51.73 MW | 51.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 2.41 MW | 2.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 11.78 MW | 11.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 1.45 MW | 1.45 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 5.81 MW | 5.81 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 4.67 MW | 4.67 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 16.57 MW | 16.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 7.67 MW | 7.67 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 3.35 MW | 3.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 20.56 MW | 20.56 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 13.8 MW | 13.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 3.3 MW | 3.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.03 MW | 1.03 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 6.89 MW | 6.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 1.77 MW | 1.77 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 5.31 MW | 5.31 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.48 MW | 0.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 2.94 MW | 2.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 2.75 MW | 2.75 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 1.83 MW | 1.83 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.24 MW | 0.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.38 MW | 1.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 10.54 MW | 10.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 2.49 MW | 2.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 11.71 MW | 11.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 15.35 MW | 15.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 1.8 MW | 1.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 2.71 MW | 2.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.78 MW | 0.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.39 MW | 0.39 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.58 MW | 0.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.14 MW | 0.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.44 MW | 0.44 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.19 MW | 0.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 0.93 MW | 0.93 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 3.55 MW | 3.55 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 8.0 MW | 8.0 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 2.6 MW | 2.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 3.91 MW | 3.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 3.44 MW | 3.44 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 9.89 MW | 9.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.02 MW | 2.02 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 3.03 MW | 3.03 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.25 MW | 1.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 1.88 MW | 1.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.37 MW | 0.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.02 MW | 2.02 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 3.03 MW | 3.03 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 3.84 MW | 3.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.71 MW | 0.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.06 MW | 1.06 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.25 MW | 1.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 1.88 MW | 1.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 2.27 MW | 2.27 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 10.64 MW | 10.64 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 4.84 MW | 4.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 3.23 MW | 3.23 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 5.94 MW | 5.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 8.91 MW | 8.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 3.21 MW | 3.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 15.04 MW | 15.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 34.53 MW | 34.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 4.69 MW | 4.69 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.29 MW | 0.29 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 2.36 MW | 2.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 11.07 MW | 11.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 8.4 MW | 8.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 8.4 MW | 8.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 5.6 MW | 5.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 2.37 MW | 2.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 11.09 MW | 11.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 2.17 MW | 2.17 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 10.16 MW | 10.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.36 MW | 0.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.55 MW | 0.55 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 1.12 MW | 1.12 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 1.68 MW | 1.68 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.37 MW | 0.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.55 MW | 0.55 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 5.26 MW | 5.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 7.38 MW | 7.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 12.59 MW | 12.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 2.56 MW | 2.56 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 3.84 MW | 3.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 0.85 MW | 0.85 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.28 MW | 1.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 189.4 MW | 189.4 MW |
| Details for 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 85.91 MW | 85.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 80.36 MW | 80.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.03 MW | 1.03 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.78 MW | 0.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.31 MW | 0.31 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.46 MW | 0.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.32 MW | 0.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 0.87 MW | 0.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 0.9 MW | 0.9 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 0.75 MW | 0.75 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.5 MW | 0.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.5 MW | 0.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.74 MW | 0.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 1.42 MW | 1.42 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.71 MW | 0.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.71 MW | 0.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.38 MW | 0.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.4 MW | 1.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.61 MW | 0.61 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.61 MW | 0.61 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 1.42 MW | 1.42 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 0.92 MW | 0.92 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.24 MW | 1.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.24 MW | 1.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 0.77 MW | 0.77 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.76 MW | 0.76 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 4.96 MW | 4.96 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.43 MW | 0.43 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 0.78 MW | 0.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 5.67 MW | 5.67 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 3.0 MW | 3.0 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 6.98 MW | 6.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 3.97 MW | 3.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 3.97 MW | 3.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 4.5 MW | 4.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 0.73 MW | 0.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.37 MW | 0.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.41 MW | 0.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 2.6 MW | 2.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.32 MW | 1.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 1.46 MW | 1.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 3.3 MW | 3.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 6.4 MW | 6.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 2.78 MW | 2.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 1.53 MW | 1.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.4 MW | 1.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 1.82 MW | 1.82 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 4.25 MW | 4.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 4.25 MW | 4.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 6.13 MW | 6.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 5.6 MW | 5.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 5.72 MW | 5.72 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 2.45 MW | 2.45 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 2.45 MW | 2.45 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 2.68 MW | 2.68 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.24 MW | 0.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 1.81 MW | 1.81 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.1 MW | 0.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 0.84 MW | 0.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 2.76 MW | 2.76 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 1.76 MW | 1.76 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 4.59 MW | 4.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 5.08 MW | 5.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 0.86 MW | 0.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 5.74 MW | 5.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 6.3 MW | 6.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 0.8 MW | 0.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 5.36 MW | 5.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 4.4 MW | 4.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 1.86 MW | 1.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.16 MW | 0.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 11.08 MW | 11.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 51.73 MW | 51.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 2.41 MW | 2.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 11.78 MW | 11.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 1.45 MW | 1.45 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 5.81 MW | 5.81 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 4.67 MW | 4.67 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 16.57 MW | 16.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 7.67 MW | 7.67 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 3.35 MW | 3.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 20.56 MW | 20.56 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 13.8 MW | 13.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 3.3 MW | 3.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.03 MW | 1.03 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 6.89 MW | 6.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 1.77 MW | 1.77 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 5.31 MW | 5.31 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.48 MW | 0.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 2.94 MW | 2.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 2.75 MW | 2.75 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 1.83 MW | 1.83 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.24 MW | 0.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.38 MW | 1.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 10.54 MW | 10.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 2.49 MW | 2.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 11.71 MW | 11.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 15.35 MW | 15.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 1.8 MW | 1.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 2.71 MW | 2.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.78 MW | 0.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.39 MW | 0.39 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.58 MW | 0.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.14 MW | 0.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.44 MW | 0.44 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.19 MW | 0.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 0.93 MW | 0.93 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 3.55 MW | 3.55 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 8.0 MW | 8.0 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 2.6 MW | 2.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 3.91 MW | 3.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 3.44 MW | 3.44 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 9.89 MW | 9.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.02 MW | 2.02 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 3.03 MW | 3.03 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.25 MW | 1.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 1.88 MW | 1.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.37 MW | 0.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.02 MW | 2.02 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 3.03 MW | 3.03 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 3.84 MW | 3.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.71 MW | 0.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.06 MW | 1.06 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.25 MW | 1.25 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 1.88 MW | 1.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 2.27 MW | 2.27 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 10.64 MW | 10.64 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 4.84 MW | 4.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 3.23 MW | 3.23 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 5.94 MW | 5.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 8.91 MW | 8.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 3.21 MW | 3.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 15.04 MW | 15.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 34.53 MW | 34.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 4.69 MW | 4.69 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.29 MW | 0.29 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 2.36 MW | 2.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 11.07 MW | 11.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 8.4 MW | 8.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 8.4 MW | 8.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 5.6 MW | 5.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 2.37 MW | 2.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 11.09 MW | 11.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 2.17 MW | 2.17 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 10.16 MW | 10.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.36 MW | 0.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.55 MW | 0.55 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 1.12 MW | 1.12 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 1.68 MW | 1.68 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.37 MW | 0.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.55 MW | 0.55 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 5.26 MW | 5.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 7.38 MW | 7.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 12.59 MW | 12.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 2.56 MW | 2.56 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 3.84 MW | 3.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 0.85 MW | 0.85 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.28 MW | 1.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 189.4 MW | 189.4 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n4056.1 | Replace the 2 3000A 765kV CB's at Dumont station | $6,000,000 | |
| b3775.11 | Upgrade the limiting element at Stillwell substation to increase the rating of the Stillwell-Dumont. | $0 | |
| b3775.7 | Upgrade limiting element at Dumont substation on the Stillwell-Dumont 345 kV line. | $0 | |
| b3775.6 | Perform sag study mitigation work on the Dumont-Stillwell 345 kV line | $0 | |
| n5769.2 | Replace two Dumont 3000A Non-Oil breakers. | $2,000,000 | |
| (TBD) | Rebuild NIPS portion of line and upgrade substation conductor (MISO - Upgrade #2) | $8,000,000 | |
| n5769.4 | Rebuild/Recondutor 8.6 miles of ACSR ~ 954 ~ 45/7 ~ RAIL conductor to mitigate the overload | $17,200,000 | |
| n5769.3 | Replace 11 jumpers/risers at Dumont substation | $275,000 | |
| (TBD) | Upgrade transmission conductor and conductor drop.. (MISO - Upgrade #3) | $6,500,000 | |
| n5769.5 | Replace 4 Dumont switches (3000 A). | $2,400,000 | |
| (TBD) | Upgrade circuit breakers and MODs at Stillwell. (MISO Upgrade #4) | $1,500,000 | |
| n5769.6 | An engineering study will need to be conducted to determine if the Dumont Relay Compliance Trip limit settings can be adjusted | $600,000 | |
| n5252 | Mitigate the sag on L11215 | $9,000,000 | |
| n6860 | Wilton Upgrade exisiting Current Transformers | $1,000,000 | |
| b3775.1 | Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line | $0 | |
| s2631 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
| b3775.10 | Sag study on the Olive – University Park | $0 | |
| s2509 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
| n7925.1 | Reconductor/rebuild 0.82 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 5 | $1,640,000 | |
| n7925.2 | Reconductor/rebuild 1 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 6 | $2,000,000 | |
| n7925.3 | Replace two sullivan 3000A Wavetrap | $400,000 | |
| n7925.4 | Replace three 2-2000 AAC 91 Str | $300,000 | |
| b3775.9 | Upgrade existing terminal equipment (substation conductor) at Green Acres on the St. John to Green Acres 345 kV lin | $0 | |
| n5912.3 | The existing SLD/ALDR rating are 1767/2032 MVA. Reconductor the line and replace the 345kV BT 10-11 & BT 9-10 CB disconnect switches at TSS 177 along with upgrading the L17703 MOD. | $18,400,000 | |
| n5912 | Re-conductor of the line along with station conductor upgrade at Burnham | $1,000,000 | |
| n5912.1 | Replace station conductor, line reconductor and upgrade CBs. | $18,000,000 | |
| n5912.2 | TSS 177 Burnham line reconductoring and upgrading 2-345kV circuit breakers | $15,200,000 | |
| (TBD) | Upgrade 0.6 miles of line to bundled conductor and additional susbtation upgrades required. | $5,000,000 | |
| b3775.8 | Upgrade existing terminal equipment at St. John on the existing Crete to St. John 345 kV line | $0 | |
| b3775.3 | Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete | $0 | |
| b3775.2 | Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles). | $0 | |
| n8375 | AB1-122 - Tazewell 345 kV Line Sag Mitigation | $39,900,000 | |
| (TBD) | MISO review required. | $0 | |
| b3775.5 | Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker. | $0 | |
| n3515.1 | Cherry Valley - Garden Prarie 345 kV line - reconductoring and sag mitigation. | $19,400,000 | |
| n3515.2 | Cherry Valley - Garden Prarie 345 kV Line Circuit Breaker Replacement | $3,000,000 | |
| n3515.3 | 13.8 miles of rebuild plus 1 CB, station conductor, and relays at Cherry Valley | $88,000,000 | |
| n5324 | Re-conductor the line segment - Dresden - AB1-122 345 kV line | $4,000,000 | |
| n5324.1 | Dresden - AB1-122 345 kV line - Re-conductor the line segment and upgrade relay package. | $5,000,000 | |
| b3775.4 | Rebuild 345 kV double circuit extending from Crete to E. Frankfort. | $0 | |
| n8408 | Re-conductor E Frankfort - University Park North 345 kV line | $5,500,000 | |
| n7023.1 | Reconductor Electric Junction - Lombard L11124 345 kV Line | $14,600,000 | |
| n6639.1 | Replace station conductor at TSS111 EJ, replace MOD. Relay upgrades, re-conductor part of the line. | $22,300,000 | |
| n6639 | Re-conductor ComEd L15502 345 kV Line | $36,200,000 | |
| n5318.1 | Garden Prarie - Silver Lake R 345 kV Line - Reconductor and Station Bus Work | $45,700,000 | |
| n5318.2 | Reconductor 26.7 miles of 2338 kcmil. Mitigate sag limits. Upgrade relay package. Replace station conductor at both line terminals. Replace 2-345 kV breakers and CT's at TSS 138 Silver Lake. | $170,000,000 | |
| n6279 | TSS 116 Replace 345 kV Circuit Breaker | $3,200,000 | |
| n8389 | TSS 116 Replace Station Conductor | $1,000,000 | |
| n8427 | Replace Nelson Transformer 94 Station Conductor Leads. | $100,000 | |
| n8373 | Plano - Install 3rd Auto Transformer at TSS 167 Plano. | $20,000,000 | |
| (TBD) | MEC Review Required | $0 | |
| (TBD) | Upgrade the 345kV line conductor from AB1-089 Interconnect Substation to AG1-119 Interconnection Substation (POI) | $45,000,000 | |
| n5808 | AEP: eliminate the Eugene stuck breaker contingency. (AMIL upgrade will not be required) | $3,424,014 | |
| s2929 | Move 345 kV line 11126 (Electric Junction-Wayne) to Bus 6 and install 345 kV Bus Tie 5-6 CB. | $0 | |
| b3711 | Install 345 kV bus tie 5-20 circuit breaker in the ring at Dresden station in series with existing bus tie 5-6. | $4,260,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-553 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.