AG1-449 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:54
Rawlings-Carson 500 kV
122.0 MW Capacity / 122.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-449 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC) has proposed an uprate to a planned/existing Storage generating facility located in the Dominion zone — Dinwiddie County, Virginia. This project is an increase to the Interconnection Customer's AE2-313 project, which will share the same point of interconnection. The AG1-449 queue position is a 122.0 MW uprate (122.0 MW Capacity uprate) to the previous project. The total installed facilities will have a capability of 436.0 MW with 310.4 MW of this output being recognized by PJM as Capacity. The proposed in-service date for this project is Saturday, December 31, 2022. This study does not imply a TO commitment to this in-service date.
Project Information | |
Queue Number | AG1-449 |
Project Name | Rawlings-Carson 500 kV |
Developer Name | RWE Solar Development, LLC |
State | Virginia |
County | Dinwiddie |
Transmission Owner | Dominion |
MFO | 436.0 MW |
MWE | 122.0 MW |
MWC | 122.0 MW |
Fuel Type | Storage |
Basecase Study Year | 2024 |
Point of Interconnection
AG1-449 will interconnect with the Dominion transmission system as a battery storage uprate to AE2-313 which is a tapping Carson to Rawlings 500 kV line.
Summer Peak Analysis
The Queue Project was evaluated as a 122.0 MW (Capacity 122.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Summer Peak Analysis | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
DVP |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1 |
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 165.38 % | 166.36 % | 2442.12 | B | 4062.66 | 34.38 | |
DVP |
6CARSON-6CHRL249 230.0 kV Ckt 1 line
314282 to 314285 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 161.45 % | 163.03 % | 559.3 | B | 911.82 | 9.49 | |
DVP |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line
314285 to 314316 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 157.94 % | 159.52 % | 559.3 | B | 892.17 | 9.49 | |
DVP |
6CARSON-6CHRL249 230.0 kV Ckt 1 line
314282 to 314285 ckt 1 |
DVP_P1-2: LN 2002
CONTINGENCY 'DVP_P1-2: LN 2002' OPEN BRANCH FROM BUS 314282 TO BUS 314331 CKT 1 /*6CARSON 230.0 - 6POE 230.0 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 1 /*3POE 115.0 - 6POE 230.0 END |
Single | AC | 153.69 % | 155.05 % | 559.3 | B | 867.18 | 7.56 | |
DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 150.59 % | 151.94 % | 559.3 | B | 849.77 | 8.23 | |
DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 148.61 % | 149.93 % | 571.52 | B | 856.87 | 8.22 | |
DVP |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line
314285 to 314316 ckt 1 |
DVP_P1-2: LN 2002
CONTINGENCY 'DVP_P1-2: LN 2002' OPEN BRANCH FROM BUS 314282 TO BUS 314331 CKT 1 /*6CARSON 230.0 - 6POE 230.0 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 1 /*3POE 115.0 - 6POE 230.0 END |
Single | AC | 150.29 % | 151.65 % | 559.3 | B | 848.17 | 7.56 | |
DVP |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 144.46 % | 145.19 % | 2442.12 | B | 3545.69 | 29.17 | |
DVP |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
314287 to 314276 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 143.79 % | 144.46 % | 663.64 | B | 958.69 | 7.72 | |
DVP |
6LOCKS-6HARR205 230.0 kV Ckt 1 line
314316 to 314301 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 139.86 % | 141.56 % | 441.8 | B | 625.43 | 7.54 | |
DVP |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer
314902 to 314282 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 138.03 % | 140.38 % | 903.9 | B | 1268.88 | 20.18 | |
DVP |
6HARR205-6TYLER 230.0 kV Ckt 1 line
314301 to 314346 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 132.12 % | 133.79 % | 441.8 | B | 591.09 | 7.54 | |
DVP |
6POE-6HARROWG 230.0 kV Ckt 1 line
314331 to 314299 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 131.34 % | 132.89 % | 441.8 | B | 587.1 | 7.22 | |
DVP |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line
314299 to 314263 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 131.3 % | 132.84 % | 441.8 | B | 586.9 | 7.22 | |
DVP |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
314914 to 314322 ckt 1 |
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 124.79 % | 126.31 % | 1058.16 | B | 1336.51 | 16.91 | |
DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P1-2: LN 574
CONTINGENCY 'DVP_P1-2: LN 574' OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2538 BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 120.91 % | 121.79 % | 3220.44 | B | 3922.21 | 38.28 | |
DVP |
6CARSON-6POE 230.0 kV Ckt 1 line
314282 to 314331 ckt 1 |
DVP_P1-2: LN 249
CONTINGENCY 'DVP_P1-2: LN 249' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 END |
Single | AC | 116.23 % | 117.29 % | 678.68 | B | 796.04 | 7.11 | |
DVP |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
314903 to 314908 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 114.51 % | 115.61 % | 2442.12 | B | 2823.26 | 31.19 | |
DVP |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line
965810 to 314902 ckt 1 |
DVP_P1-2: LN 585-A
CONTINGENCY 'DVP_P1-2: LN 585-A' OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1 /*8CARSON 500.0 - AE2-094 TAP 500.0 END |
Single | AC | 112.31 % | 114.51 % | 4070.2 | B | 4660.62 | 80.93 | |
DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 112.5 % | 113.57 % | 2442.12 | B | 2773.54 | 29.54 | |
DVP |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line
941030 to 314902 ckt 1 |
DVP_P1-2: LN 511-A
CONTINGENCY 'DVP_P1-2: LN 511-A' OPEN BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 109.71 % | 111.75 % | 4070.2 | B | 4548.37 | 68.22 | |
DVP |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line
965810 to 314902 ckt 1 |
DVP_P1-2: LN 585-B
CONTINGENCY 'DVP_P1-2: LN 585-B' OPEN BRANCH FROM BUS 941030 TO BUS 314940 CKT 1 /*AE2-094 TAP 500.0 - 8ROGERS RD 500.0 END |
Single | AC | 107.88 % | 110.09 % | 4070.2 | B | 4480.8 | 80.93 | |
DVP |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
314903 to 314908 ckt 1 |
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 110.25 % | 111.08 % | 2442.12 | B | 2712.66 | 29.66 | |
DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET PRECONTRATING 2538 BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Single | AC | 108.5 % | 109.81 % | 3220.44 | B | 3536.46 | 42.18 | |
DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P1-2: LN 574
CONTINGENCY 'DVP_P1-2: LN 574' OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2538 BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 108.68 % | 109.78 % | 3220.44 | B | 3535.5 | 40.75 | |
DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P1-2: LN 557
CONTINGENCY 'DVP_P1-2: LN 557' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Single | AC | 108.32 % | 109.32 % | 3220.44 | B | 3520.52 | 36.95 | |
DVP |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line
314940 to 941030 ckt 1 |
DVP_P1-2: LN 511-A
CONTINGENCY 'DVP_P1-2: LN 511-A' OPEN BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 105.02 % | 107.09 % | 4070.2 | B | 4358.61 | 68.22 | |
DVP |
6CARSON-6POE 230.0 kV Ckt 1 line
314282 to 314331 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 105.26 % | 106.44 % | 678.68 | B | 722.35 | 8.09 | |
DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P1-2: LN 562-A
CONTINGENCY 'DVP_P1-2: LN 562-A' OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 314923 TO BUS 314924 CKT 1 /*8SEPTA 500.0 - 8SURRY 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA 500.0 - 8YADKIN 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET PRECONTRATING 2538 BRANCH FROM BUS 314923 TO BUS 314924 CKT 1 /*8SEPTA 500.0 - 8SURRY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA 500.0 - 8YADKIN 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 99.35 % | 100.71 % | 3118.0 | B | 3140.01 | 41.41 | |
DVP |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
314260 to 314225 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 99.96 % | 100.67 % | 984.18 | B | 990.79 | 7.65 | |
DVP |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
314287 to 314260 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 99.96 % | 100.65 % | 984.18 | B | 990.56 | 7.65 | |
DVP |
6CARSON-6CHRL249 230.0 kV Ckt 1 line
314282 to 314285 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 181.93 % | 183.71 % | 684.0 | C | 1256.58 | 12.52 | |
DVP |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line
314285 to 314316 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 179.1 % | 180.89 % | 684.0 | C | 1237.27 | 12.52 | |
DVP |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer
314902 to 314282 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 164.35 % | 166.79 % | 1039.7 | C | 1734.12 | 26.9 | |
DVP |
6LOCKS-6HARR205 230.0 kV Ckt 1 line
314316 to 314301 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 160.75 % | 162.21 % | 541.0 | C | 877.56 | 9.84 | |
DVP |
6HARR205-6TYLER 230.0 kV Ckt 1 line
314301 to 314346 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 151.99 % | 153.48 % | 541.0 | C | 830.31 | 9.84 | |
DVP |
6POE-6HARROWG 230.0 kV Ckt 1 line
314331 to 314299 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 149.32 % | 150.77 % | 541.0 | C | 815.66 | 9.23 | |
DVP |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line
314299 to 314263 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 149.31 % | 150.76 % | 541.0 | C | 815.6 | 9.23 | |
DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P4-2: 56372
CONTINGENCY 'DVP_P4-2: 56372' OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Breaker | AC | 139.37 % | 139.79 % | 3144.0 | C | 4394.9 | 34.23 | |
DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P4-2: 557T574
CONTINGENCY 'DVP_P4-2: 557T574' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Breaker | AC | 137.4 % | 137.99 % | 3940.0 | C | 5436.69 | 44.96 | |
DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P4-2: H2T557
CONTINGENCY 'DVP_P4-2: H2T557' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2 /*6ELMONT 230.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Breaker | AC | 129.85 % | 130.42 % | 3940.0 | C | 5138.59 | 44.17 | |
DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P4-2: 557T567
CONTINGENCY 'DVP_P4-2: 557T567' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Breaker | AC | 127.8 % | 128.4 % | 3940.0 | C | 5059.0 | 43.47 | |
DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P4-5: L122
CONTINGENCY 'DVP_P4-5: L122' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Breaker | AC | 127.59 % | 128.17 % | 3940.0 | C | 5049.78 | 43.47 | |
DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P4-2: 557T574
CONTINGENCY 'DVP_P4-2: 557T574' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Breaker | AC | 126.84 % | 127.11 % | 3940.0 | C | 5008.13 | 40.74 | |
DVP |
6CARSON-6POE 230.0 kV Ckt 1 line
314282 to 314331 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 120.64 % | 121.71 % | 830.0 | C | 1010.2 | 11.02 | |
DVP |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer
314686 to 314906 ckt 2 |
DVP_P4-5: L912
CONTINGENCY 'DVP_P4-5: L912' OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 1 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 3 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BUS 313817 /*6CLOVER_1 230.0 END |
Breaker | AC | 105.57 % | 106.59 % | 1275.1 | C | 1359.17 | 13.37 | |
DVP |
8SEPTA-8SURRY 500.0 kV Ckt 1 line
314923 to 314924 ckt 1 |
DVP_P4-2: 56372
CONTINGENCY 'DVP_P4-2: 56372' OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Breaker | AC | 100.39 % | 101.15 % | 3637.0 | C | 3678.79 | 36.76 |
Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961941 | AG1-037 C | Adder | 0.81 MW | 0.69 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962331 | AG1-082 C | Adder | 3.25 MW | 2.76 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962341 | AG1-083 C | Adder | 3.25 MW | 2.76 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963041 | AG1-153 C | Adder | 8.25 MW | 7.01 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963111 | AG1-160 C | Adder | 8.33 MW | 7.08 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963291 | AG1-178 C O2 | Adder | 95.92 MW | 81.54 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963351 | AG1-184 O2 | Adder | 51.68 MW | 43.93 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964801 | AG1-343 C | Adder | 9.65 MW | 8.2 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965291 | AG1-394 C | Adder | 3.31 MW | 2.82 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965691 | AG1-437 C O1 | Adder | 16.59 MW | 14.1 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965701 | AG1-438 C O1 | Adder | 16.59 MW | 14.1 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965741 | AG1-442 O1 | Adder | 9.68 MW | 8.22 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965751 | AG1-443 O1 | Adder | 9.68 MW | 8.22 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965811 | AG1-449 | Adder | 34.38 MW | 29.22 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966361 | AG1-505 C | Adder | 24.56 MW | 20.88 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966371 | AG1-506 C | Adder | 24.56 MW | 20.88 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966621 | AG1-532 C | Adder | 2.15 MW | 1.82 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 313506 | AB1-173 C OP | Adder | 10.6 MW | 9.01 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314572 | 3EMPORIA | Adder | 0.66 MW | 0.56 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926070 | AC1-086 C | Adder | 32.51 MW | 27.63 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934521 | AD1-076 C | Adder | 89.82 MW | 76.35 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942931 | AE2-313 C | Adder | 53.03 MW | 45.08 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943171 | AE2-346 C | Adder | 2.27 MW | 1.93 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944011 | AF1-069 C | Adder | 19.19 MW | 16.31 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 960081 | AF2-299 C | Adder | 3.98 MW | 3.38 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315293 | 1DOMTR9 | Adder | 11.14 MW | 9.47 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315294 | 1DOMTR10 | Adder | 13.65 MW | 11.6 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316140 | AB2-099 C | Adder | 0.95 MW | 0.81 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 923262 | AB1-132 C OP | Adder | 22.07 MW | 18.76 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 923991 | AB2-040 C O1 | Adder | 11.54 MW | 9.81 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940491 | AE2-034 C | Adder | 12.03 MW | 10.22 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941031 | AE2-094 C | Adder | 58.73 MW | 49.92 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946281 | AF1-292 C | Adder | 2.36 MW | 2.01 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957521 | AF2-046 C | Adder | 27.28 MW | 23.19 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957531 | AF2-047 C | Adder | 28.58 MW | 24.29 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 938771 | AE1-103 C | Adder | 4.93 MW | 4.19 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940481 | AE2-033 C | Adder | 25.59 MW | 21.75 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940641 | AE2-051 C O1 | Adder | 26.72 MW | 22.71 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946011 | AF1-266 | Adder | 21.42 MW | 18.21 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314229 | 6MT RD221 | 80/20 | 0.23 MW | 0.23 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314236 | 6NRTHEST | 80/20 | 0.35 MW | 0.35 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314241 | 6OLDCHRC | 80/20 | 1.6 MW | 1.6 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314250 | 6ROCKVILLE | 80/20 | 0.6 MW | 0.6 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314309 | 6IRON208 | 80/20 | 0.82 MW | 0.82 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314421 | 6WINCHST | 80/20 | 0.25 MW | 0.25 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315060 | 1CHESTF5 | 80/20 | 114.17 MW | 114.17 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315061 | 1CHESTG7 | 80/20 | 7.26 MW | 7.26 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315062 | 1CHESTS7 | 80/20 | 3.33 MW | 3.33 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315063 | 1CHESTG8 | 80/20 | 7.14 MW | 7.14 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315064 | 1CHESTS8 | 80/20 | 3.68 MW | 3.68 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315065 | 1CHESTF6 | 80/20 | 180.35 MW | 180.35 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315067 | 1DARBY 1 | 80/20 | 4.79 MW | 4.79 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315068 | 1DARBY 2 | 80/20 | 4.79 MW | 4.79 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315069 | 1DARBY 3 | 80/20 | 4.81 MW | 4.81 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315070 | 1DARBY 4 | 80/20 | 4.82 MW | 4.82 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315076 | 1HOPPOLC | 80/20 | 2.89 MW | 2.89 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315077 | 1HOPHCF1 | 80/20 | 4.52 MW | 4.52 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315078 | 1HOPHCF2 | 80/20 | 4.52 MW | 4.52 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315079 | 1HOPHCF3 | 80/20 | 4.52 MW | 4.52 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315080 | 1HOPHCF4 | 80/20 | 6.86 MW | 6.86 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315083 | 1SPRUNCA | Adder | 18.29 MW | 15.55 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315084 | 1SPRUNCB | Adder | 18.29 MW | 15.55 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315092 | 1YORKTN3 | 80/20 | 43.31 MW | 43.31 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 925863 | AC1-065 C | Adder | 10.45 MW | 8.88 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926754 | AC1-161 C | 80/20 | 53.78 MW | 53.78 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926784 | AC1-164 C | 80/20 | 73.91 MW | 73.91 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 927044 | AC1-191 C | Adder | 16.47 MW | 14.0 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 927225 | AC1-216 C | 80/20 | 2.97 MW | 2.97 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934014 | AD1-025 C | 80/20 | 29.98 MW | 29.98 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934061 | AD1-033 C | Adder | 13.12 MW | 11.15 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934141 | AD1-041 C | Adder | 8.93 MW | 7.59 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934575 | AD1-082 C | Adder | 13.37 MW | 11.37 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 935164 | AD1-151 C | 80/20 | 28.68 MW | 28.68 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 936151 | AD2-021 | 80/20 | 0.07 MW | 0.07 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 936661 | AD2-085 C | Adder | 5.95 MW | 5.06 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 936761 | AD2-097 C | Adder | 3.47 MW | 2.95 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 937221 | AD2-160 C O1 | Adder | 10.19 MW | 8.66 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942151 | AE2-227 C | 80/20 | 3.9 MW | 3.9 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942161 | AE2-228 C | Adder | 3.79 MW | 3.22 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942341 | AE2-247 C | Adder | 2.58 MW | 2.19 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942371 | AE2-250 C O1 | Adder | 16.86 MW | 14.33 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942401 | AE2-253 C | Adder | 10.72 MW | 9.11 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942551 | AE2-270 | 80/20 | 47.76 MW | 47.76 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943431 | AF1-014 C | Adder | 2.17 MW | 1.84 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943461 | AF1-017 C | Adder | 2.33 MW | 1.98 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943471 | AF1-018 | Adder | 12.17 MW | 10.34 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943611 | AF1-032 C | Adder | 3.02 MW | 2.57 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943621 | AF1-033 C | 80/20 | 4.19 MW | 4.19 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944631 | AF1-128 O1 | 80/20 | 71.44 MW | 71.44 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944871 | AF1-152 C | Adder | 9.08 MW | 7.72 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 945361 | AF1-201 C O1 | Adder | 28.2 MW | 23.97 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961711 | AG1-011 | 80/20 | 50.91 MW | 50.91 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966871 | AG1-558 C | Adder | 4.1 MW | 3.49 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315116 | 1SURRY 1 | 80/20 | 45.59 MW | 45.59 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315120 | 1GRAVEL4 | 80/20 | 4.69 MW | 4.69 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315122 | 1GRAVEL6 | 80/20 | 4.68 MW | 4.68 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315233 | 1SURRY 2 | 80/20 | 47.38 MW | 47.38 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316033 | AB2-134 C | 80/20 | 3.89 MW | 3.89 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316075 | AC2-137 C | 80/20 | 0.65 MW | 0.65 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316108 | AB2-160 C | Adder | 9.49 MW | 8.07 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316132 | AB2-190 C | 80/20 | 33.45 MW | 33.45 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 932044 | AC2-012 C | Adder | 14.06 MW | 11.95 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 932591 | AC2-079 C O1 | Adder | 9.94 MW | 8.45 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 938535 | AE1-072 C | Adder | 30.49 MW | 25.91 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939195 | AE1-149 C | Adder | 18.56 MW | 15.77 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939414 | AE1-173_C1 | Adder | 50.54 MW | 42.95 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939415 | AE1-173_C2 | Adder | 43.32 MW | 36.82 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939416 | AE1-173_C3 | Adder | 50.54 MW | 42.95 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939431 | AE1-175 C | 80/20 | 4.36 MW | 4.36 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939611 | AE1-191 C | Adder | 17.86 MW | 15.18 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940231 | AE2-005 C | Adder | 2.29 MW | 1.94 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940431 | AE2-027 C O1 | Adder | 22.71 MW | 19.31 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940541 | AE2-040 | Adder | 4.55 MW | 3.86 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940551 | AE2-041 | Adder | 12.17 MW | 10.34 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940651 | AE2-052 | Adder | 6.19 MW | 5.26 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941101 | AE2-104 C O1 | Adder | 5.8 MW | 4.93 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941281 | AE2-122 C O1 | Adder | 49.71 MW | 42.26 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941291 | AE2-123 C O1 | Adder | 51.09 MW | 43.43 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941301 | AE2-124 C O1 | Adder | 46.45 MW | 39.48 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946261 | AF1-291 C | Adder | 3.79 MW | 3.22 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957491 | AF2-043 C | Adder | 3.7 MW | 3.15 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957601 | AF2-054 C | Adder | 3.51 MW | 2.98 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957631 | AF2-057 | Adder | 6.27 MW | 5.33 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957711 | AF2-065 C | 80/20 | 24.36 MW | 24.36 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962531 | AG1-102 C | Adder | 1.9 MW | 1.62 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962961 | AG1-145 C | 80/20 | 3.93 MW | 3.93 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963221 | AG1-171 C | 80/20 | 3.82 MW | 3.82 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963231 | AG1-172 C | 80/20 | 3.82 MW | 3.82 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963241 | AG1-173 C | 80/20 | 3.82 MW | 3.82 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963251 | AG1-174 C | 80/20 | 3.82 MW | 3.82 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964951 | AG1-359 O1 | Adder | 39.83 MW | 33.86 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965001 | AG1-364 C O1 | Adder | 12.55 MW | 10.67 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 933294 | AC2-141 C | 80/20 | 53.78 MW | 53.78 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941501 | AE2-147 C | Adder | 27.24 MW | 23.15 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941581 | AE2-155 C | 80/20 | 0.2 MW | 0.2 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941591 | AE2-156 O1 | Adder | 31.37 MW | 26.67 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942001 | AE2-212 C | Adder | 3.75 MW | 3.19 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957831 | AF2-077 C | Adder | 3.7 MW | 3.15 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957871 | AF2-081 C | Adder | 17.36 MW | 14.75 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957911 | AF2-085 | Adder | 5.92 MW | 5.03 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958161 | AF2-110 C | Adder | 2.39 MW | 2.03 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966611 | AG1-531 C | 80/20 | 10.35 MW | 10.35 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944581 | AF1-123 C O1 | Adder | 83.97 MW | 71.37 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944591 | AF1-124 C O1 | Adder | 83.97 MW | 71.37 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944601 | AF1-125 C O1 | Adder | 83.97 MW | 71.37 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 933981 | AD1-022 C | Adder | 14.4 MW | 12.24 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961681 | AG1-008 C | Adder | 27.33 MW | 23.23 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962271 | AG1-075 C O1 | Adder | 29.1 MW | 24.73 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962571 | AG1-106 C | Adder | 9.04 MW | 7.68 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965281 | AG1-393 C | Adder | 3.47 MW | 2.95 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316083 | AB2-161 C | Adder | 5.87 MW | 4.99 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961611 | AG1-000B C | 80/20 | 28.23 MW | 28.23 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.39 MW | 8.39 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.2 MW | 3.2 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 160.6 MW | 160.6 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 71.79 MW | 71.79 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 68.69 MW | 68.69 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.7 MW | 12.7 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.51 MW | 15.51 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.77 MW | 0.77 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.64 MW | 3.64 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.9 MW | 9.9 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.98 MW | 3.98 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.63 MW | 0.63 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.63 MW | 12.63 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.72 MW | 1.72 MW |
Details for 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | 80/20 | 0.42 MW | 0.42 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | 80/20 | 0.21 MW | 0.21 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | 80/20 | 0.83 MW | 0.83 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | 80/20 | 0.83 MW | 0.83 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 2.27 MW | 2.27 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 2.3 MW | 2.3 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 24.4 MW | 24.4 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 3.47 MW | 3.47 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.69 MW | 1.69 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 13.15 MW | 13.15 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964241 | AG1-285 C O1 | 80/20 | 4.61 MW | 4.61 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964791 | AG1-342 C | Adder | 1.47 MW | 1.25 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | 80/20 | 2.39 MW | 2.39 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | 80/20 | 0.88 MW | 0.88 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 1.15 MW | 1.15 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | 80/20 | 0.82 MW | 0.82 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965591 | AG1-427 C | 80/20 | 4.36 MW | 4.36 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 2.9 MW | 2.9 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | 80/20 | 3.67 MW | 3.67 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | 80/20 | 3.67 MW | 3.67 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | 80/20 | 10.24 MW | 10.24 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | 80/20 | 3.22 MW | 3.22 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | 80/20 | 3.22 MW | 3.22 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | 80/20 | 2.14 MW | 2.14 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | 80/20 | 2.14 MW | 2.14 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | 80/20 | 5.46 MW | 5.46 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | 80/20 | 1.86 MW | 1.86 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | 80/20 | 1.86 MW | 1.86 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 9.49 MW | 9.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 6.66 MW | 6.66 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 6.66 MW | 6.66 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 1.03 MW | 1.03 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 4.49 MW | 4.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313719 | 3CHESTNUT | 80/20 | 0.57 MW | 0.57 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.31 MW | 0.31 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.17 MW | 0.17 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.11 MW | 0.11 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.2 MW | 0.2 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.78 MW | 0.78 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.74 MW | 0.74 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | 80/20 | 3.62 MW | 3.62 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | 80/20 | 3.62 MW | 3.62 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 1.33 MW | 1.33 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.83 MW | 0.83 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.62 MW | 0.62 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.99 MW | 1.99 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315158 | 1KERR 1 | 80/20 | 0.17 MW | 0.17 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315159 | 1KERR 2 | 80/20 | 0.49 MW | 0.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315160 | 1KERR 3 | 80/20 | 0.49 MW | 0.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.49 MW | 0.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.49 MW | 0.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | 80/20 | 13.15 MW | 13.15 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.87 MW | 2.87 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.96 MW | 0.96 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | 80/20 | 3.58 MW | 3.58 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 4.4 MW | 4.4 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 5.29 MW | 5.29 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | Adder | 18.18 MW | 15.45 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934615 | AD1-087 C | Adder | 2.65 MW | 2.25 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935171 | AD1-152 C O1 | Adder | 2.79 MW | 2.37 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936265 | AD2-033 C | Adder | 4.38 MW | 3.72 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937481 | AD2-202 C O1 | Adder | 0.78 MW | 0.66 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 14.63 MW | 14.63 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.58 MW | 0.58 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 5.32 MW | 5.32 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | 80/20 | 1.3 MW | 1.3 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | 80/20 | 2.76 MW | 2.76 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.9 MW | 1.9 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.49 MW | 0.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.49 MW | 0.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 2.38 MW | 2.02 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 2.92 MW | 2.48 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315601 | 1CONETOE2SOL | 80/20 | 0.62 MW | 0.62 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.81 MW | 0.81 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316020 | AB2-059 C OP | 80/20 | 0.81 MW | 0.81 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316131 | AB2-060 C | 80/20 | 0.59 MW | 0.59 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | 80/20 | 0.24 MW | 0.24 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 922922 | AB1-081 C OP | 80/20 | 0.69 MW | 0.69 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 8.93 MW | 8.93 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 4.89 MW | 4.89 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924301 | AB2-077 C O1 | 80/20 | 0.77 MW | 0.77 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924311 | AB2-078 C O1 | 80/20 | 0.77 MW | 0.77 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924321 | AB2-079 C O1 | 80/20 | 0.77 MW | 0.77 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | 80/20 | 3.08 MW | 3.08 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 4.09 MW | 4.09 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C | 80/20 | 3.63 MW | 3.63 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | 80/20 | 2.02 MW | 2.02 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | 80/20 | 1.34 MW | 1.34 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 16.29 MW | 16.29 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 1.13 MW | 1.13 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | 80/20 | 19.72 MW | 19.72 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 6.88 MW | 6.88 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | 80/20 | 3.25 MW | 3.25 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 17.0 MW | 17.0 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 6.65 MW | 6.65 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 14.23 MW | 14.23 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.46 MW | 0.46 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | -0.78 MW | -0.66 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 3.49 MW | 3.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 3.49 MW | 3.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 3.49 MW | 3.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 7.24 MW | 7.24 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.99 MW | 1.99 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 4.49 MW | 4.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 4.49 MW | 4.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 4.49 MW | 4.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 7.79 MW | 7.79 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.71 MW | 0.71 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315608 | 3AA2-088SOLA | 80/20 | 0.43 MW | 0.43 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.82 MW | 0.82 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316096 | AB2-100 C1 | 80/20 | 0.85 MW | 0.85 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316098 | AB2-100 C2 | 80/20 | 0.85 MW | 0.85 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | 80/20 | 0.15 MW | 0.15 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 10.84 MW | 10.84 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 9.29 MW | 9.29 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 10.84 MW | 10.84 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | 80/20 | 3.1 MW | 3.1 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | Adder | 3.07 MW | 2.61 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | 80/20 | 3.53 MW | 3.53 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962561 | AG1-105 C O1 | Adder | 3.19 MW | 2.71 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | 80/20 | 6.89 MW | 6.89 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | 80/20 | 3.66 MW | 3.66 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | 80/20 | 2.37 MW | 2.37 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315602 | 1HOLLOMANSOL | 80/20 | 0.6 MW | 0.6 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313527 | AB2-043 C | 80/20 | 0.21 MW | 0.21 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.13 MW | 2.13 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.62 MW | 0.62 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 38.03 MW | 38.03 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.35 MW | 12.35 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.18 MW | 13.18 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.22 MW | 3.22 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.11 MW | 3.11 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.61 MW | 0.61 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.78 MW | 1.78 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.45 MW | 0.45 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.5 MW | 2.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
Details for 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | 80/20 | 0.42 MW | 0.42 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | 80/20 | 0.21 MW | 0.21 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | 80/20 | 0.83 MW | 0.83 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | 80/20 | 0.83 MW | 0.83 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 2.27 MW | 2.27 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 2.3 MW | 2.3 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 24.4 MW | 24.4 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 3.47 MW | 3.47 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.69 MW | 1.69 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 13.15 MW | 13.15 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964241 | AG1-285 C O1 | 80/20 | 4.61 MW | 4.61 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964791 | AG1-342 C | Adder | 1.47 MW | 1.25 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | 80/20 | 2.39 MW | 2.39 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | 80/20 | 0.88 MW | 0.88 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 1.15 MW | 1.15 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | 80/20 | 0.82 MW | 0.82 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965591 | AG1-427 C | 80/20 | 4.36 MW | 4.36 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 2.9 MW | 2.9 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | 80/20 | 3.67 MW | 3.67 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | 80/20 | 3.67 MW | 3.67 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | 80/20 | 10.24 MW | 10.24 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | 80/20 | 3.22 MW | 3.22 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | 80/20 | 3.22 MW | 3.22 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | 80/20 | 2.14 MW | 2.14 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | 80/20 | 2.14 MW | 2.14 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | 80/20 | 5.46 MW | 5.46 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | 80/20 | 1.86 MW | 1.86 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | 80/20 | 1.86 MW | 1.86 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 9.49 MW | 9.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 6.66 MW | 6.66 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 6.66 MW | 6.66 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 1.03 MW | 1.03 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 4.49 MW | 4.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313719 | 3CHESTNUT | 80/20 | 0.57 MW | 0.57 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.31 MW | 0.31 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.17 MW | 0.17 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.11 MW | 0.11 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.2 MW | 0.2 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.78 MW | 0.78 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.74 MW | 0.74 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | 80/20 | 3.62 MW | 3.62 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | 80/20 | 3.62 MW | 3.62 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 1.33 MW | 1.33 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.83 MW | 0.83 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.62 MW | 0.62 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.99 MW | 1.99 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315158 | 1KERR 1 | 80/20 | 0.17 MW | 0.17 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315159 | 1KERR 2 | 80/20 | 0.49 MW | 0.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315160 | 1KERR 3 | 80/20 | 0.49 MW | 0.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.49 MW | 0.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.49 MW | 0.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | 80/20 | 13.15 MW | 13.15 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.87 MW | 2.87 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.96 MW | 0.96 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | 80/20 | 3.58 MW | 3.58 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 4.4 MW | 4.4 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 5.29 MW | 5.29 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | Adder | 18.18 MW | 15.45 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934615 | AD1-087 C | Adder | 2.65 MW | 2.25 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935171 | AD1-152 C O1 | Adder | 2.79 MW | 2.37 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936265 | AD2-033 C | Adder | 4.38 MW | 3.72 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937481 | AD2-202 C O1 | Adder | 0.78 MW | 0.66 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 14.63 MW | 14.63 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.58 MW | 0.58 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 5.32 MW | 5.32 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | 80/20 | 1.3 MW | 1.3 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | 80/20 | 2.76 MW | 2.76 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.9 MW | 1.9 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.49 MW | 0.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.49 MW | 0.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 2.38 MW | 2.02 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 2.92 MW | 2.48 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315601 | 1CONETOE2SOL | 80/20 | 0.62 MW | 0.62 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.81 MW | 0.81 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316020 | AB2-059 C OP | 80/20 | 0.81 MW | 0.81 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316131 | AB2-060 C | 80/20 | 0.59 MW | 0.59 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | 80/20 | 0.24 MW | 0.24 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 922922 | AB1-081 C OP | 80/20 | 0.69 MW | 0.69 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 8.93 MW | 8.93 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 4.89 MW | 4.89 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924301 | AB2-077 C O1 | 80/20 | 0.77 MW | 0.77 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924311 | AB2-078 C O1 | 80/20 | 0.77 MW | 0.77 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924321 | AB2-079 C O1 | 80/20 | 0.77 MW | 0.77 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | 80/20 | 3.08 MW | 3.08 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 4.09 MW | 4.09 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C | 80/20 | 3.63 MW | 3.63 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | 80/20 | 2.02 MW | 2.02 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | 80/20 | 1.34 MW | 1.34 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 16.29 MW | 16.29 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 1.13 MW | 1.13 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | 80/20 | 19.72 MW | 19.72 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 6.88 MW | 6.88 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | 80/20 | 3.25 MW | 3.25 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 17.0 MW | 17.0 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 6.65 MW | 6.65 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 14.23 MW | 14.23 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.46 MW | 0.46 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | -0.78 MW | -0.66 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 3.49 MW | 3.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 3.49 MW | 3.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 3.49 MW | 3.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 7.24 MW | 7.24 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.99 MW | 1.99 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 4.49 MW | 4.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 4.49 MW | 4.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 4.49 MW | 4.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 7.79 MW | 7.79 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.71 MW | 0.71 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315608 | 3AA2-088SOLA | 80/20 | 0.43 MW | 0.43 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.82 MW | 0.82 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316096 | AB2-100 C1 | 80/20 | 0.85 MW | 0.85 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316098 | AB2-100 C2 | 80/20 | 0.85 MW | 0.85 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | 80/20 | 0.15 MW | 0.15 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 10.84 MW | 10.84 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 9.29 MW | 9.29 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 10.84 MW | 10.84 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | 80/20 | 3.1 MW | 3.1 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | Adder | 3.07 MW | 2.61 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | 80/20 | 3.53 MW | 3.53 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962561 | AG1-105 C O1 | Adder | 3.19 MW | 2.71 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | 80/20 | 6.89 MW | 6.89 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | 80/20 | 3.66 MW | 3.66 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | 80/20 | 2.37 MW | 2.37 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315602 | 1HOLLOMANSOL | 80/20 | 0.6 MW | 0.6 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313527 | AB2-043 C | 80/20 | 0.21 MW | 0.21 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.13 MW | 2.13 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.62 MW | 0.62 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 38.03 MW | 38.03 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.35 MW | 12.35 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.18 MW | 13.18 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.22 MW | 3.22 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.11 MW | 3.11 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.61 MW | 0.61 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.78 MW | 1.78 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.45 MW | 0.45 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.5 MW | 2.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
Details for 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 961671 | AG1-007 C | 80/20 | 0.41 MW | 0.41 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 961941 | AG1-037 C | 80/20 | 0.19 MW | 0.19 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 962331 | AG1-082 C | 80/20 | 0.77 MW | 0.77 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 962341 | AG1-083 C | 80/20 | 0.77 MW | 0.77 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963041 | AG1-153 C | 80/20 | 1.82 MW | 1.82 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963111 | AG1-160 C | 80/20 | 1.84 MW | 1.84 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963291 | AG1-178 C O2 | 80/20 | 18.64 MW | 18.64 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963301 | AG1-179 C | 80/20 | 4.0 MW | 4.0 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963311 | AG1-180 | 80/20 | 1.95 MW | 1.95 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963321 | AG1-181 C O1 | 80/20 | 5.71 MW | 5.71 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963351 | AG1-184 O2 | 80/20 | 10.04 MW | 10.04 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963361 | AG1-185 O1 | 80/20 | 2.77 MW | 2.77 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964111 | AG1-272 C | 80/20 | 0.85 MW | 0.85 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964121 | AG1-273 C | 80/20 | 0.85 MW | 0.85 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964131 | AG1-274 C | 80/20 | 0.85 MW | 0.85 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964241 | AG1-285 C O1 | 80/20 | 4.73 MW | 4.73 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964791 | AG1-342 C | 80/20 | 1.41 MW | 1.41 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964801 | AG1-343 C | 80/20 | 2.07 MW | 2.07 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 966801 | AG1-551 C | 80/20 | 0.8 MW | 0.8 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 966811 | AG1-552 C | 80/20 | 1.23 MW | 1.23 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965191 | AG1-384 C | 80/20 | 0.85 MW | 0.85 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965291 | AG1-394 C | 80/20 | 0.71 MW | 0.71 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965591 | AG1-427 C | 80/20 | 4.47 MW | 4.47 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965601 | AG1-428 C O2 | 80/20 | 3.34 MW | 3.34 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965691 | AG1-437 C O1 | 80/20 | 3.15 MW | 3.15 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965701 | AG1-438 C O1 | 80/20 | 3.15 MW | 3.15 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965711 | AG1-439 C O1 | 80/20 | 9.97 MW | 9.97 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965721 | AG1-440 C | 80/20 | 3.33 MW | 3.33 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965731 | AG1-441 C | 80/20 | 3.33 MW | 3.33 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965741 | AG1-442 O1 | 80/20 | 1.84 MW | 1.84 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965751 | AG1-443 O1 | 80/20 | 1.84 MW | 1.84 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965761 | AG1-444 O1 | 80/20 | 5.32 MW | 5.32 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965771 | AG1-445 | 80/20 | 1.93 MW | 1.93 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965781 | AG1-446 | 80/20 | 1.93 MW | 1.93 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965811 | AG1-449 | 80/20 | 7.56 MW | 7.56 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 966361 | AG1-505 C | 80/20 | 5.35 MW | 5.35 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 966371 | AG1-506 C | 80/20 | 5.35 MW | 5.35 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 966621 | AG1-532 C | 80/20 | 1.22 MW | 1.22 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 313506 | AB1-173 C OP | 80/20 | 5.15 MW | 5.15 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 313719 | 3CHESTNUT | 80/20 | 0.58 MW | 0.58 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314572 | 3EMPORIA | 80/20 | 0.36 MW | 0.36 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314582 | 3KELFORD | 80/20 | 0.16 MW | 0.16 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314623 | 3WITAKRS | 80/20 | 0.11 MW | 0.11 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314704 | 3LAWRENC | 80/20 | 0.24 MW | 0.24 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315126 | 1ROARAP2 | 80/20 | 0.84 MW | 0.84 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315128 | 1ROARAP4 | 80/20 | 0.8 MW | 0.8 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315131 | 1EDGECMA | 80/20 | 3.66 MW | 3.66 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315132 | 1EDGECMB | 80/20 | 3.66 MW | 3.66 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315136 | 1ROSEMG1 | 80/20 | 1.5 MW | 1.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315137 | 1ROSEMS1 | 80/20 | 0.93 MW | 0.93 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315138 | 1ROSEMG2 | 80/20 | 0.7 MW | 0.7 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315139 | 1GASTONA | 80/20 | 2.25 MW | 2.25 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315158 | 1KERR 1 | 80/20 | 0.18 MW | 0.18 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315159 | 1KERR 2 | 80/20 | 0.5 MW | 0.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315160 | 1KERR 3 | 80/20 | 0.5 MW | 0.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315161 | 1KERR 4 | 80/20 | 0.5 MW | 0.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315162 | 1KERR 5 | 80/20 | 0.5 MW | 0.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926070 | AC1-086 C | 80/20 | 14.89 MW | 14.89 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926201 | AC1-098 C | 80/20 | 2.89 MW | 2.89 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926211 | AC1-099 C | 80/20 | 0.97 MW | 0.97 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 927024 | AC1-189 C | 80/20 | 3.43 MW | 3.43 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 927145 | AC1-208 C | 80/20 | 4.54 MW | 4.54 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 934331 | AD1-057 C O1 | 80/20 | 5.69 MW | 5.69 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 936265 | AD2-033 C | 80/20 | 4.45 MW | 4.45 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 942931 | AE2-313 C | 80/20 | 11.66 MW | 11.66 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 943171 | AE2-346 C | 80/20 | 0.54 MW | 0.54 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 944011 | AF1-069 C | 80/20 | 4.24 MW | 4.24 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 944141 | AF1-082 | 80/20 | 1.31 MW | 1.31 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 945811 | AF1-246 C O1 | 80/20 | 2.26 MW | 2.26 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 959311 | AF2-222 C | 80/20 | 5.35 MW | 5.35 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 960081 | AF2-299 C | 80/20 | 2.26 MW | 2.26 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315163 | 1KERR 6 | 80/20 | 0.5 MW | 0.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315164 | 1KERR 7 | 80/20 | 0.5 MW | 0.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315601 | 1CONETOE2SOL | 80/20 | 0.6 MW | 0.6 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315606 | 3AA2-053SOLA | 80/20 | 0.86 MW | 0.86 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316020 | AB2-059 C OP | 80/20 | 0.82 MW | 0.82 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316118 | AC1-105 C | 80/20 | 1.8 MW | 1.8 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316129 | AC1-054 C | 80/20 | 3.65 MW | 3.65 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316131 | AB2-060 C | 80/20 | 0.6 MW | 0.6 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 922922 | AB1-081 C OP | 80/20 | 0.69 MW | 0.69 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923262 | AB1-132 C OP | 80/20 | 10.11 MW | 10.11 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923991 | AB2-040 C O1 | 80/20 | 5.61 MW | 5.61 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924301 | AB2-077 C O1 | 80/20 | 0.79 MW | 0.79 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924311 | AB2-078 C O1 | 80/20 | 0.79 MW | 0.79 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924321 | AB2-079 C O1 | 80/20 | 0.79 MW | 0.79 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925121 | AB2-169 C | 80/20 | 0.35 MW | 0.35 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925591 | AC1-034 C | 80/20 | 3.1 MW | 3.1 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925611 | AC1-036 C | 80/20 | 0.08 MW | 0.08 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 932631 | AC2-084 C | 80/20 | 4.12 MW | 4.12 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 939181 | AE1-148 C | 80/20 | 3.71 MW | 3.71 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940571 | AE2-044 C | 80/20 | 2.03 MW | 2.03 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940661 | AE2-053 O1 | 80/20 | 1.38 MW | 1.38 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 941031 | AE2-094 C | 80/20 | 12.97 MW | 12.97 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 946281 | AF1-292 C | 80/20 | 1.34 MW | 1.34 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 957481 | AF2-042 C | 80/20 | 16.15 MW | 16.15 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 957521 | AF2-046 C | 80/20 | 6.14 MW | 6.14 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 957861 | AF2-080 C | 80/20 | 3.12 MW | 3.12 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940481 | AE2-033 C | 80/20 | 21.61 MW | 21.61 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940641 | AE2-051 C O1 | 80/20 | 5.07 MW | 5.07 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 946011 | AF1-266 | 80/20 | 18.09 MW | 18.09 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314435 | 6SAPONY | 80/20 | 0.59 MW | 0.59 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314589 | 3MURPHYS | 80/20 | 0.03 MW | 0.03 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 934575 | AD1-082 C | Adder | -5.14 MW | -4.37 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 936761 | AD2-097 C | Adder | -1.06 MW | -0.9 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315102 | 1BRUNSWICKG1 | 80/20 | 2.8 MW | 2.8 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.8 MW | 2.8 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.8 MW | 2.8 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.81 MW | 5.81 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315141 | 1GASTONB | 80/20 | 2.25 MW | 2.25 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315241 | 1Z1-086 GT1 | 80/20 | 3.59 MW | 3.59 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315242 | 1Z1-086 GT2 | 80/20 | 3.59 MW | 3.59 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315243 | 1Z1-086 GT3 | 80/20 | 3.59 MW | 3.59 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315244 | 1Z1-086 ST | 80/20 | 6.24 MW | 6.24 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315607 | 3AA1-063SOLA | 80/20 | 0.71 MW | 0.71 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315608 | 3AA2-088SOLA | 80/20 | 0.36 MW | 0.36 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316087 | AB2-174 C | 80/20 | 0.96 MW | 0.96 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316096 | AB2-100 C1 | 80/20 | 1.04 MW | 1.04 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316098 | AB2-100 C2 | 80/20 | 1.04 MW | 1.04 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316132 | AB2-190 C | Adder | -8.72 MW | -7.41 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 938221 | AE1-035 C | 80/20 | 0.14 MW | 0.14 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940541 | AE2-040 | 80/20 | 3.96 MW | 3.96 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 960331 | AF2-324 C | 80/20 | 3.57 MW | 3.57 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 962561 | AG1-105 C O1 | 80/20 | 3.11 MW | 3.11 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 961681 | AG1-008 C | 80/20 | 6.15 MW | 6.15 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 962571 | AG1-106 C | 80/20 | 4.14 MW | 4.14 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965281 | AG1-393 C | 80/20 | 3.02 MW | 3.02 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315602 | 1HOLLOMANSOL | 80/20 | 0.55 MW | 0.55 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 313527 | AB2-043 C | 80/20 | 0.21 MW | 0.21 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316083 | AB2-161 C | Adder | -2.26 MW | -1.92 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.56 MW | 0.56 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.9 MW | 33.9 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.42 MW | 11.42 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.88 MW | 11.88 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.79 MW | 2.79 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.56 MW | 0.56 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.63 MW | 1.63 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.24 MW | 2.24 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961791 | AG1-021 C | 80/20 | 4.16 MW | 4.16 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961891 | AG1-030 C | 80/20 | 28.93 MW | 28.93 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962491 | AG1-098 C O1 | 80/20 | 17.55 MW | 17.55 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 2.0 MW | 2.0 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 1.95 MW | 1.95 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963171 | AG1-166 C | 80/20 | 4.16 MW | 4.16 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963181 | AG1-167 C | 80/20 | 4.16 MW | 4.16 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963191 | AG1-168 C | 80/20 | 4.16 MW | 4.16 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963201 | AG1-169 C | 80/20 | 4.16 MW | 4.16 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963211 | AG1-170 C | 80/20 | 4.16 MW | 4.16 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 4.07 MW | 4.07 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.98 MW | 1.98 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963321 | AG1-181 C O1 | 80/20 | 26.51 MW | 26.51 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963361 | AG1-185 O1 | 80/20 | 12.83 MW | 12.83 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964111 | AG1-272 C | 80/20 | 4.23 MW | 4.23 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964121 | AG1-273 C | 80/20 | 4.23 MW | 4.23 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964131 | AG1-274 C | 80/20 | 4.23 MW | 4.23 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964241 | AG1-285 C O1 | 80/20 | 15.99 MW | 15.99 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964791 | AG1-342 C | 80/20 | 3.76 MW | 3.76 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966691 | AG1-539 C | 80/20 | 2.14 MW | 2.14 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 0.93 MW | 0.93 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965191 | AG1-384 C | 80/20 | 4.23 MW | 4.23 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965591 | AG1-427 C | 80/20 | 15.27 MW | 15.27 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 3.4 MW | 3.4 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965641 | AG1-432 C O1 | 80/20 | 53.04 MW | 53.04 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | 80/20 | 5.62 MW | 5.62 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | 80/20 | 5.62 MW | 5.62 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | 80/20 | 3.25 MW | 3.25 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | 80/20 | 3.25 MW | 3.25 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 8.23 MW | 8.23 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965831 | AG1-451 | 80/20 | 8.84 MW | 8.84 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 7.46 MW | 7.46 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 7.46 MW | 7.46 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 0.64 MW | 0.64 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 3.09 MW | 3.09 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313719 | 3CHESTNUT | 80/20 | 0.47 MW | 0.47 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314429 | 3JTRSVLE | 80/20 | 0.94 MW | 0.94 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.2 MW | 0.2 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.21 MW | 0.21 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.63 MW | 0.63 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.6 MW | 0.6 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315153 | 1CLOVER1 | 80/20 | 11.3 MW | 11.3 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315154 | 1CLOVER2 | 80/20 | 11.2 MW | 11.2 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315158 | 1KERR 1 | 80/20 | 0.34 MW | 0.34 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315159 | 1KERR 2 | 80/20 | 0.96 MW | 0.96 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315160 | 1KERR 3 | 80/20 | 0.96 MW | 0.96 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.96 MW | 0.96 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.96 MW | 0.96 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.06 MW | 0.06 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926023 | AC1-080 C | 80/20 | 0.17 MW | 0.17 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.32 MW | 2.32 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.78 MW | 0.78 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 3.57 MW | 3.57 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927251 | AC1-221 C | 80/20 | 1.15 MW | 1.15 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927261 | AC1-222 C | 80/20 | 2.55 MW | 2.55 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934311 | AD1-055 C | 80/20 | 1.77 MW | 1.77 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934341 | AD1-058 C | 80/20 | 2.88 MW | 2.88 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934615 | AD1-087 C | 80/20 | 6.56 MW | 6.56 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934625 | AD1-088 C | 80/20 | 19.77 MW | 19.77 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934991 | AD1-131 C | 80/20 | 0.94 MW | 0.94 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935171 | AD1-152 C O1 | 80/20 | 6.46 MW | 6.46 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936265 | AD2-033 C | 80/20 | 20.14 MW | 20.14 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937481 | AD2-202 C O1 | 80/20 | 1.92 MW | 1.92 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942461 | AE2-259 C O1 | 80/20 | 26.52 MW | 26.52 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942751 | AE2-291 C | 80/20 | 4.09 MW | 4.09 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942761 | AE2-292 C O1 | 80/20 | 5.09 MW | 5.09 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 12.76 MW | 12.76 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943901 | AF1-058 C | 80/20 | 1.44 MW | 1.44 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.18 MW | 4.18 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | 80/20 | 5.25 MW | 5.25 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958801 | AF2-171 C | 80/20 | 31.07 MW | 31.07 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 959311 | AF2-222 C | 80/20 | 28.48 MW | 28.48 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960061 | AF2-297 C | 80/20 | 5.77 MW | 5.77 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.18 MW | 1.18 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.96 MW | 0.96 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.96 MW | 0.96 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315266 | 1PLYWOOD A | 80/20 | 0.99 MW | 0.99 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.66 MW | 0.66 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316118 | AC1-105 C | 80/20 | 4.65 MW | 4.65 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | 80/20 | 4.79 MW | 4.79 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316131 | AB2-060 C | 80/20 | 1.82 MW | 1.82 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.37 MW | 3.37 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924301 | AB2-077 C O1 | 80/20 | 2.23 MW | 2.23 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924311 | AB2-078 C O1 | 80/20 | 2.23 MW | 2.23 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924321 | AB2-079 C O1 | 80/20 | 2.23 MW | 2.23 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925611 | AC1-036 C | 80/20 | 0.4 MW | 0.4 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.31 MW | 3.31 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932761 | AC2-100 C | 80/20 | 2.64 MW | 2.64 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938371 | AE1-056 C | 80/20 | 14.45 MW | 14.45 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C | 80/20 | 7.88 MW | 7.88 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | 80/20 | 2.92 MW | 2.92 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 12.81 MW | 12.81 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941791 | AE2-182 C | 80/20 | 3.21 MW | 3.21 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.7 MW | 0.7 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946301 | AF1-294 C | 80/20 | 8.53 MW | 8.53 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | 80/20 | 37.49 MW | 37.49 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958211 | AF2-115 C | 80/20 | 5.2 MW | 5.2 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933501 | AC2-165 C | Adder | -6.86 MW | -5.83 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958501 | AF2-144 C | Adder | -1.04 MW | -0.89 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 3.07 MW | 3.07 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 3.07 MW | 3.07 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 3.07 MW | 3.07 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 6.38 MW | 6.38 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.12 MW | 1.12 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 3.81 MW | 3.81 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 3.81 MW | 3.81 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 3.81 MW | 3.81 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 6.62 MW | 6.62 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.59 MW | 0.59 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.55 MW | 0.55 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962561 | AG1-105 C O1 | 80/20 | 8.41 MW | 8.41 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313527 | AB2-043 C | 80/20 | 0.61 MW | 0.61 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316123 | AC1-075 C | 80/20 | 0.52 MW | 0.52 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.35 MW | 2.35 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.7 MW | 40.7 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.5 MW | 9.5 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.88 MW | 11.88 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.57 MW | 3.57 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.92 MW | 2.92 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.47 MW | 0.47 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.49 MW | 1.49 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.34 MW | 2.34 MW |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961791 | AG1-021 C | 80/20 | 4.16 MW | 4.16 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961891 | AG1-030 C | 80/20 | 28.93 MW | 28.93 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962491 | AG1-098 C O1 | 80/20 | 17.54 MW | 17.54 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 1.99 MW | 1.99 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 1.95 MW | 1.95 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963171 | AG1-166 C | 80/20 | 4.16 MW | 4.16 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963181 | AG1-167 C | 80/20 | 4.16 MW | 4.16 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963191 | AG1-168 C | 80/20 | 4.16 MW | 4.16 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963201 | AG1-169 C | 80/20 | 4.16 MW | 4.16 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963211 | AG1-170 C | 80/20 | 4.16 MW | 4.16 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 4.07 MW | 4.07 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.98 MW | 1.98 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963321 | AG1-181 C O1 | 80/20 | 26.5 MW | 26.5 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963361 | AG1-185 O1 | 80/20 | 12.82 MW | 12.82 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964111 | AG1-272 C | 80/20 | 4.23 MW | 4.23 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964121 | AG1-273 C | 80/20 | 4.23 MW | 4.23 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964131 | AG1-274 C | 80/20 | 4.23 MW | 4.23 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964241 | AG1-285 C O1 | 80/20 | 15.99 MW | 15.99 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964791 | AG1-342 C | 80/20 | 3.76 MW | 3.76 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966691 | AG1-539 C | 80/20 | 2.14 MW | 2.14 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 0.93 MW | 0.93 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965191 | AG1-384 C | 80/20 | 4.23 MW | 4.23 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965591 | AG1-427 C | 80/20 | 15.27 MW | 15.27 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 3.4 MW | 3.4 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965641 | AG1-432 C O1 | 80/20 | 53.03 MW | 53.03 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | 80/20 | 5.62 MW | 5.62 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | 80/20 | 5.62 MW | 5.62 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | 80/20 | 3.25 MW | 3.25 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | 80/20 | 3.25 MW | 3.25 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 8.22 MW | 8.22 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965831 | AG1-451 | 80/20 | 8.84 MW | 8.84 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 7.45 MW | 7.45 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 7.45 MW | 7.45 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 0.64 MW | 0.64 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 3.09 MW | 3.09 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313719 | 3CHESTNUT | 80/20 | 0.47 MW | 0.47 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314429 | 3JTRSVLE | 80/20 | 0.94 MW | 0.94 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.2 MW | 0.2 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.21 MW | 0.21 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.63 MW | 0.63 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.6 MW | 0.6 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315153 | 1CLOVER1 | 80/20 | 11.3 MW | 11.3 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315154 | 1CLOVER2 | 80/20 | 11.19 MW | 11.19 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315158 | 1KERR 1 | 80/20 | 0.34 MW | 0.34 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315159 | 1KERR 2 | 80/20 | 0.96 MW | 0.96 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315160 | 1KERR 3 | 80/20 | 0.96 MW | 0.96 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.96 MW | 0.96 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.96 MW | 0.96 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.06 MW | 0.06 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926023 | AC1-080 C | 80/20 | 0.17 MW | 0.17 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.32 MW | 2.32 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.78 MW | 0.78 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 3.57 MW | 3.57 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927251 | AC1-221 C | 80/20 | 1.15 MW | 1.15 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927261 | AC1-222 C | 80/20 | 2.55 MW | 2.55 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934311 | AD1-055 C | 80/20 | 1.77 MW | 1.77 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934341 | AD1-058 C | 80/20 | 2.88 MW | 2.88 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934615 | AD1-087 C | 80/20 | 6.55 MW | 6.55 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934625 | AD1-088 C | 80/20 | 19.76 MW | 19.76 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934991 | AD1-131 C | 80/20 | 0.94 MW | 0.94 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935171 | AD1-152 C O1 | 80/20 | 6.45 MW | 6.45 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936265 | AD2-033 C | 80/20 | 20.14 MW | 20.14 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937481 | AD2-202 C O1 | 80/20 | 1.92 MW | 1.92 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942461 | AE2-259 C O1 | 80/20 | 26.52 MW | 26.52 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942751 | AE2-291 C | 80/20 | 4.08 MW | 4.08 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942761 | AE2-292 C O1 | 80/20 | 5.09 MW | 5.09 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 12.75 MW | 12.75 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943901 | AF1-058 C | 80/20 | 1.44 MW | 1.44 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.18 MW | 4.18 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | 80/20 | 5.25 MW | 5.25 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958801 | AF2-171 C | 80/20 | 31.06 MW | 31.06 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 959311 | AF2-222 C | 80/20 | 28.47 MW | 28.47 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960061 | AF2-297 C | 80/20 | 5.77 MW | 5.77 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.18 MW | 1.18 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.96 MW | 0.96 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.96 MW | 0.96 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315266 | 1PLYWOOD A | 80/20 | 0.99 MW | 0.99 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.66 MW | 0.66 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316118 | AC1-105 C | 80/20 | 4.64 MW | 4.64 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | 80/20 | 4.79 MW | 4.79 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316131 | AB2-060 C | 80/20 | 1.82 MW | 1.82 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.37 MW | 3.37 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924301 | AB2-077 C O1 | 80/20 | 2.23 MW | 2.23 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924311 | AB2-078 C O1 | 80/20 | 2.23 MW | 2.23 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924321 | AB2-079 C O1 | 80/20 | 2.23 MW | 2.23 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925611 | AC1-036 C | 80/20 | 0.4 MW | 0.4 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.31 MW | 3.31 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932761 | AC2-100 C | 80/20 | 2.64 MW | 2.64 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938371 | AE1-056 C | 80/20 | 14.44 MW | 14.44 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C | 80/20 | 7.88 MW | 7.88 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | 80/20 | 2.92 MW | 2.92 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 12.79 MW | 12.79 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941791 | AE2-182 C | 80/20 | 3.21 MW | 3.21 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.7 MW | 0.7 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946301 | AF1-294 C | 80/20 | 8.53 MW | 8.53 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | 80/20 | 37.47 MW | 37.47 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958211 | AF2-115 C | 80/20 | 5.2 MW | 5.2 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933501 | AC2-165 C | Adder | -6.87 MW | -5.84 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314677 | 6BUCKING | 80/20 | 1.48 MW | 1.48 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958501 | AF2-144 C | Adder | -1.04 MW | -0.89 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 3.07 MW | 3.07 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 3.07 MW | 3.07 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 3.07 MW | 3.07 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 6.37 MW | 6.37 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.12 MW | 1.12 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 3.81 MW | 3.81 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 3.81 MW | 3.81 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 3.81 MW | 3.81 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 6.61 MW | 6.61 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.59 MW | 0.59 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.55 MW | 0.55 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962561 | AG1-105 C O1 | 80/20 | 8.41 MW | 8.41 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313527 | AB2-043 C | 80/20 | 0.61 MW | 0.61 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316123 | AC1-075 C | 80/20 | 0.52 MW | 0.52 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.35 MW | 2.35 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.63 MW | 40.63 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.4 MW | 9.4 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.82 MW | 11.82 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.56 MW | 3.56 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.91 MW | 2.91 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.47 MW | 0.47 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.48 MW | 1.48 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.33 MW | 2.33 MW |
6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
Details for 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 961671 | AG1-007 C | 80/20 | 0.41 MW | 0.41 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 961941 | AG1-037 C | 80/20 | 0.19 MW | 0.19 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 962331 | AG1-082 C | 80/20 | 0.77 MW | 0.77 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 962341 | AG1-083 C | 80/20 | 0.77 MW | 0.77 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963041 | AG1-153 C | 80/20 | 1.82 MW | 1.82 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963111 | AG1-160 C | 80/20 | 1.84 MW | 1.84 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963291 | AG1-178 C O2 | 80/20 | 18.64 MW | 18.64 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963301 | AG1-179 C | 80/20 | 4.0 MW | 4.0 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963311 | AG1-180 | 80/20 | 1.95 MW | 1.95 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963321 | AG1-181 C O1 | 80/20 | 5.71 MW | 5.71 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963351 | AG1-184 O2 | 80/20 | 10.04 MW | 10.04 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 963361 | AG1-185 O1 | 80/20 | 2.77 MW | 2.77 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964111 | AG1-272 C | 80/20 | 0.85 MW | 0.85 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964121 | AG1-273 C | 80/20 | 0.85 MW | 0.85 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964131 | AG1-274 C | 80/20 | 0.85 MW | 0.85 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964241 | AG1-285 C O1 | 80/20 | 4.73 MW | 4.73 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964791 | AG1-342 C | 80/20 | 1.41 MW | 1.41 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 964801 | AG1-343 C | 80/20 | 2.07 MW | 2.07 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 966801 | AG1-551 C | 80/20 | 0.8 MW | 0.8 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 966811 | AG1-552 C | 80/20 | 1.23 MW | 1.23 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965191 | AG1-384 C | 80/20 | 0.85 MW | 0.85 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965291 | AG1-394 C | 80/20 | 0.71 MW | 0.71 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965591 | AG1-427 C | 80/20 | 4.47 MW | 4.47 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965601 | AG1-428 C O2 | 80/20 | 3.34 MW | 3.34 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965691 | AG1-437 C O1 | 80/20 | 3.15 MW | 3.15 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965701 | AG1-438 C O1 | 80/20 | 3.15 MW | 3.15 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965711 | AG1-439 C O1 | 80/20 | 9.97 MW | 9.97 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965721 | AG1-440 C | 80/20 | 3.33 MW | 3.33 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965731 | AG1-441 C | 80/20 | 3.33 MW | 3.33 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965741 | AG1-442 O1 | 80/20 | 1.84 MW | 1.84 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965751 | AG1-443 O1 | 80/20 | 1.84 MW | 1.84 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965761 | AG1-444 O1 | 80/20 | 5.32 MW | 5.32 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965771 | AG1-445 | 80/20 | 1.93 MW | 1.93 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965781 | AG1-446 | 80/20 | 1.93 MW | 1.93 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965811 | AG1-449 | 80/20 | 7.56 MW | 7.56 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 966361 | AG1-505 C | 80/20 | 5.35 MW | 5.35 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 966371 | AG1-506 C | 80/20 | 5.35 MW | 5.35 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 966621 | AG1-532 C | 80/20 | 1.22 MW | 1.22 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 313506 | AB1-173 C OP | 80/20 | 5.15 MW | 5.15 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 313719 | 3CHESTNUT | 80/20 | 0.58 MW | 0.58 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314572 | 3EMPORIA | 80/20 | 0.36 MW | 0.36 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314582 | 3KELFORD | 80/20 | 0.16 MW | 0.16 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314623 | 3WITAKRS | 80/20 | 0.11 MW | 0.11 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314704 | 3LAWRENC | 80/20 | 0.24 MW | 0.24 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315126 | 1ROARAP2 | 80/20 | 0.84 MW | 0.84 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315128 | 1ROARAP4 | 80/20 | 0.8 MW | 0.8 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315131 | 1EDGECMA | 80/20 | 3.66 MW | 3.66 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315132 | 1EDGECMB | 80/20 | 3.66 MW | 3.66 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315136 | 1ROSEMG1 | 80/20 | 1.5 MW | 1.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315137 | 1ROSEMS1 | 80/20 | 0.93 MW | 0.93 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315138 | 1ROSEMG2 | 80/20 | 0.7 MW | 0.7 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315139 | 1GASTONA | 80/20 | 2.25 MW | 2.25 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315158 | 1KERR 1 | 80/20 | 0.18 MW | 0.18 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315159 | 1KERR 2 | 80/20 | 0.5 MW | 0.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315160 | 1KERR 3 | 80/20 | 0.5 MW | 0.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315161 | 1KERR 4 | 80/20 | 0.5 MW | 0.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315162 | 1KERR 5 | 80/20 | 0.5 MW | 0.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926070 | AC1-086 C | 80/20 | 14.89 MW | 14.89 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926201 | AC1-098 C | 80/20 | 2.89 MW | 2.89 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926211 | AC1-099 C | 80/20 | 0.97 MW | 0.97 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 927024 | AC1-189 C | 80/20 | 3.43 MW | 3.43 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 927145 | AC1-208 C | 80/20 | 4.54 MW | 4.54 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 934331 | AD1-057 C O1 | 80/20 | 5.69 MW | 5.69 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 936265 | AD2-033 C | 80/20 | 4.45 MW | 4.45 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 942931 | AE2-313 C | 80/20 | 11.66 MW | 11.66 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 943171 | AE2-346 C | 80/20 | 0.54 MW | 0.54 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 944011 | AF1-069 C | 80/20 | 4.24 MW | 4.24 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 944141 | AF1-082 | 80/20 | 1.31 MW | 1.31 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 945811 | AF1-246 C O1 | 80/20 | 2.26 MW | 2.26 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 959311 | AF2-222 C | 80/20 | 5.35 MW | 5.35 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 960081 | AF2-299 C | 80/20 | 2.26 MW | 2.26 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315163 | 1KERR 6 | 80/20 | 0.5 MW | 0.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315164 | 1KERR 7 | 80/20 | 0.5 MW | 0.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315601 | 1CONETOE2SOL | 80/20 | 0.6 MW | 0.6 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315606 | 3AA2-053SOLA | 80/20 | 0.86 MW | 0.86 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316020 | AB2-059 C OP | 80/20 | 0.82 MW | 0.82 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316118 | AC1-105 C | 80/20 | 1.8 MW | 1.8 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316129 | AC1-054 C | 80/20 | 3.65 MW | 3.65 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316131 | AB2-060 C | 80/20 | 0.6 MW | 0.6 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 922922 | AB1-081 C OP | 80/20 | 0.69 MW | 0.69 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923262 | AB1-132 C OP | 80/20 | 10.11 MW | 10.11 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923991 | AB2-040 C O1 | 80/20 | 5.61 MW | 5.61 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924301 | AB2-077 C O1 | 80/20 | 0.79 MW | 0.79 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924311 | AB2-078 C O1 | 80/20 | 0.79 MW | 0.79 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924321 | AB2-079 C O1 | 80/20 | 0.79 MW | 0.79 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925121 | AB2-169 C | 80/20 | 0.35 MW | 0.35 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925591 | AC1-034 C | 80/20 | 3.1 MW | 3.1 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925611 | AC1-036 C | 80/20 | 0.08 MW | 0.08 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 932631 | AC2-084 C | 80/20 | 4.12 MW | 4.12 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 939181 | AE1-148 C | 80/20 | 3.71 MW | 3.71 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940571 | AE2-044 C | 80/20 | 2.03 MW | 2.03 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940661 | AE2-053 O1 | 80/20 | 1.38 MW | 1.38 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 941031 | AE2-094 C | 80/20 | 12.97 MW | 12.97 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 946281 | AF1-292 C | 80/20 | 1.34 MW | 1.34 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 957481 | AF2-042 C | 80/20 | 16.15 MW | 16.15 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 957521 | AF2-046 C | 80/20 | 6.14 MW | 6.14 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 957861 | AF2-080 C | 80/20 | 3.12 MW | 3.12 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940481 | AE2-033 C | 80/20 | 21.61 MW | 21.61 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940641 | AE2-051 C O1 | 80/20 | 5.07 MW | 5.07 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 946011 | AF1-266 | 80/20 | 18.09 MW | 18.09 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314435 | 6SAPONY | 80/20 | 0.59 MW | 0.59 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314589 | 3MURPHYS | 80/20 | 0.03 MW | 0.03 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 934575 | AD1-082 C | Adder | -5.14 MW | -4.37 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 936761 | AD2-097 C | Adder | -1.06 MW | -0.9 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315102 | 1BRUNSWICKG1 | 80/20 | 2.8 MW | 2.8 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.8 MW | 2.8 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.8 MW | 2.8 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.81 MW | 5.81 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315141 | 1GASTONB | 80/20 | 2.25 MW | 2.25 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315241 | 1Z1-086 GT1 | 80/20 | 3.59 MW | 3.59 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315242 | 1Z1-086 GT2 | 80/20 | 3.59 MW | 3.59 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315243 | 1Z1-086 GT3 | 80/20 | 3.59 MW | 3.59 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315244 | 1Z1-086 ST | 80/20 | 6.24 MW | 6.24 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315607 | 3AA1-063SOLA | 80/20 | 0.71 MW | 0.71 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315608 | 3AA2-088SOLA | 80/20 | 0.36 MW | 0.36 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316087 | AB2-174 C | 80/20 | 0.96 MW | 0.96 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316096 | AB2-100 C1 | 80/20 | 1.04 MW | 1.04 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316098 | AB2-100 C2 | 80/20 | 1.04 MW | 1.04 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316132 | AB2-190 C | Adder | -8.72 MW | -7.41 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 938221 | AE1-035 C | 80/20 | 0.14 MW | 0.14 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940541 | AE2-040 | 80/20 | 3.96 MW | 3.96 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 960331 | AF2-324 C | 80/20 | 3.57 MW | 3.57 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 962561 | AG1-105 C O1 | 80/20 | 3.11 MW | 3.11 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 961681 | AG1-008 C | 80/20 | 6.15 MW | 6.15 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 962571 | AG1-106 C | 80/20 | 4.14 MW | 4.14 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 965281 | AG1-393 C | 80/20 | 3.02 MW | 3.02 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315602 | 1HOLLOMANSOL | 80/20 | 0.55 MW | 0.55 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 313527 | AB2-043 C | 80/20 | 0.21 MW | 0.21 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 316083 | AB2-161 C | Adder | -2.26 MW | -1.92 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.56 MW | 0.56 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.9 MW | 33.9 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.42 MW | 11.42 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.88 MW | 11.88 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.79 MW | 2.79 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.56 MW | 0.56 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.63 MW | 1.63 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.24 MW | 2.24 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | Adder | 0.69 MW | 0.58 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | Adder | 2.75 MW | 2.34 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | Adder | 2.75 MW | 2.34 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | Adder | 7.0 MW | 5.95 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | Adder | 7.07 MW | 6.01 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | Adder | 81.81 MW | 69.53 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | Adder | 44.07 MW | 37.46 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | Adder | 8.16 MW | 6.94 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | Adder | 2.8 MW | 2.38 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | Adder | 14.12 MW | 12.0 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | Adder | 14.12 MW | 12.0 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | Adder | 8.24 MW | 7.0 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | Adder | 8.24 MW | 7.0 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | Adder | 29.17 MW | 24.79 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | Adder | 20.75 MW | 17.64 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | Adder | 20.75 MW | 17.64 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | Adder | 1.79 MW | 1.52 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | Adder | 8.84 MW | 7.52 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | Adder | 0.55 MW | 0.47 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | Adder | 27.29 MW | 23.2 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | Adder | 76.6 MW | 65.11 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | Adder | 44.99 MW | 38.24 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | Adder | 1.93 MW | 1.64 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | Adder | 16.3 MW | 13.86 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | Adder | 3.31 MW | 2.81 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 9.49 MW | 8.06 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 11.63 MW | 9.88 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | Adder | 0.8 MW | 0.68 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | Adder | 18.53 MW | 15.75 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | Adder | 9.63 MW | 8.19 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | Adder | 10.27 MW | 8.73 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | Adder | 49.89 MW | 42.41 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | Adder | 1.96 MW | 1.67 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | Adder | 23.1 MW | 19.63 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | Adder | 24.41 MW | 20.75 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C | Adder | 4.19 MW | 3.56 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | Adder | 21.22 MW | 18.04 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | Adder | 22.83 MW | 19.41 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | Adder | 17.76 MW | 15.1 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314229 | 6MT RD221 | 80/20 | 0.19 MW | 0.19 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314241 | 6OLDCHRC | 80/20 | 1.36 MW | 1.36 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314421 | 6WINCHST | 80/20 | 0.21 MW | 0.21 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314491 | 3PENDLTN | 80/20 | 0.51 MW | 0.51 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314507 | 3THOMPSN | 80/20 | 0.52 MW | 0.52 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315060 | 1CHESTF5 | Adder | 92.66 MW | 78.76 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315065 | 1CHESTF6 | Adder | 143.8 MW | 122.23 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315092 | 1YORKTN3 | 80/20 | 37.33 MW | 37.33 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925863 | AC1-065 C | Adder | 8.85 MW | 7.52 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926661 | AC1-147 C | 80/20 | 0.58 MW | 0.58 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926754 | AC1-161 C | 80/20 | 46.75 MW | 46.75 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926784 | AC1-164 C | 80/20 | 62.84 MW | 62.84 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927044 | AC1-191 C | Adder | 13.68 MW | 11.63 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934014 | AD1-025 C | Adder | 24.9 MW | 21.16 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934061 | AD1-033 C | 80/20 | 11.3 MW | 11.3 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934141 | AD1-041 C | Adder | 7.57 MW | 6.44 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | Adder | 11.06 MW | 9.4 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935164 | AD1-151 C | Adder | 23.7 MW | 20.14 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936151 | AD2-021 | 80/20 | 0.06 MW | 0.06 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | Adder | 5.03 MW | 4.28 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937221 | AD2-160 C O1 | Adder | 8.77 MW | 7.45 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942151 | AE2-227 C | Adder | 3.03 MW | 2.57 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942161 | AE2-228 C | Adder | 3.03 MW | 2.57 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | Adder | 2.18 MW | 1.85 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942371 | AE2-250 C O1 | Adder | 13.62 MW | 11.58 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942401 | AE2-253 C | Adder | 9.22 MW | 7.84 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942551 | AE2-270 | Adder | 39.59 MW | 33.65 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943431 | AF1-014 C | Adder | 1.83 MW | 1.56 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | Adder | 1.97 MW | 1.68 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943471 | AF1-018 | Adder | 10.34 MW | 8.79 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943611 | AF1-032 C | Adder | 2.6 MW | 2.21 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943621 | AF1-033 C | 80/20 | 3.55 MW | 3.55 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944631 | AF1-128 O1 | Adder | 57.98 MW | 49.28 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944871 | AF1-152 C | Adder | 7.79 MW | 6.62 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945361 | AF1-201 C O1 | 80/20 | 24.2 MW | 24.2 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961711 | AG1-011 | Adder | 42.29 MW | 35.95 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966871 | AG1-558 C | Adder | 3.41 MW | 2.9 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315098 | 1CHESPKA | 80/20 | 0.68 MW | 0.68 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315099 | 1CHESPKB | 80/20 | 1.14 MW | 1.14 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315108 | 1ELIZAR1 | 80/20 | 5.03 MW | 5.03 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315109 | 1ELIZAR2 | 80/20 | 4.94 MW | 4.94 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315110 | 1ELIZAR3 | 80/20 | 5.09 MW | 5.09 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315116 | 1SURRY 1 | 80/20 | 38.51 MW | 38.51 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315119 | 1GRAVEL3 | 80/20 | 3.91 MW | 3.91 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315120 | 1GRAVEL4 | 80/20 | 3.96 MW | 3.96 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315121 | 1GRAVEL5 | 80/20 | 3.91 MW | 3.91 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315122 | 1GRAVEL6 | 80/20 | 3.96 MW | 3.96 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315233 | 1SURRY 2 | 80/20 | 41.51 MW | 41.51 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315260 | 1GOSPORTA | 80/20 | 0.55 MW | 0.55 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315261 | 1GOSPORTB | 80/20 | 0.7 MW | 0.7 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315262 | 1GOSPORTC | 80/20 | 0.59 MW | 0.59 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316075 | AC2-137 C | 80/20 | 0.54 MW | 0.54 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316108 | AB2-160 C | Adder | 7.67 MW | 6.52 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316132 | AB2-190 C | Adder | 27.66 MW | 23.52 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316258 | AE1-162 C | 80/20 | 0.55 MW | 0.55 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932044 | AC2-012 C | 80/20 | 12.09 MW | 12.09 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | Adder | 8.34 MW | 7.09 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938535 | AE1-072 C | Adder | 26.22 MW | 22.28 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939195 | AE1-149 C | Adder | 15.25 MW | 12.96 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | Adder | 43.27 MW | 36.78 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | Adder | 37.09 MW | 31.52 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | Adder | 43.27 MW | 36.78 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939431 | AE1-175 C | 80/20 | 3.75 MW | 3.75 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939611 | AE1-191 C | Adder | 15.14 MW | 12.87 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940231 | AE2-005 C | Adder | 1.94 MW | 1.65 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940431 | AE2-027 C O1 | Adder | 18.23 MW | 15.49 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | Adder | 3.77 MW | 3.2 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940551 | AE2-041 | Adder | 10.34 MW | 8.79 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | Adder | 5.08 MW | 4.32 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | Adder | 4.95 MW | 4.2 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941281 | AE2-122 C O1 | 80/20 | 42.77 MW | 42.77 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941291 | AE2-123 C O1 | 80/20 | 43.96 MW | 43.96 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941301 | AE2-124 C O1 | 80/20 | 39.96 MW | 39.96 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946261 | AF1-291 C | Adder | 3.03 MW | 2.58 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957491 | AF2-043 C | Adder | 3.18 MW | 2.7 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957601 | AF2-054 C | Adder | 2.98 MW | 2.53 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957631 | AF2-057 | 80/20 | 5.39 MW | 5.39 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957711 | AF2-065 C | Adder | 20.19 MW | 17.16 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962531 | AG1-102 C | Adder | 1.63 MW | 1.38 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962961 | AG1-145 C | 80/20 | 3.38 MW | 3.38 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963221 | AG1-171 C | Adder | 3.17 MW | 2.7 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963231 | AG1-172 C | Adder | 3.17 MW | 2.7 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963241 | AG1-173 C | Adder | 3.17 MW | 2.7 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963251 | AG1-174 C | Adder | 3.17 MW | 2.7 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964951 | AG1-359 O1 | 80/20 | 34.29 MW | 34.29 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965001 | AG1-364 C O1 | 80/20 | 10.79 MW | 10.79 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933294 | AC2-141 C | 80/20 | 46.75 MW | 46.75 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941501 | AE2-147 C | Adder | 23.37 MW | 19.86 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941581 | AE2-155 C | 80/20 | 0.17 MW | 0.17 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941591 | AE2-156 O1 | 80/20 | 26.98 MW | 26.98 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942001 | AE2-212 C | Adder | 3.02 MW | 2.56 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957831 | AF2-077 C | Adder | 3.17 MW | 2.7 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957871 | AF2-081 C | Adder | 14.93 MW | 12.69 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | Adder | 2.04 MW | 1.73 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966611 | AG1-531 C | 80/20 | 8.83 MW | 8.83 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944581 | AF1-123 C O1 | 80/20 | 72.43 MW | 72.43 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944591 | AF1-124 C O1 | 80/20 | 72.43 MW | 72.43 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944601 | AF1-125 C O1 | 80/20 | 72.43 MW | 72.43 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | Adder | 12.27 MW | 10.43 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | Adder | 23.14 MW | 19.67 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962271 | AG1-075 C O1 | Adder | 23.51 MW | 19.98 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | Adder | 7.59 MW | 6.45 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | Adder | 2.88 MW | 2.45 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | Adder | 4.85 MW | 4.12 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961611 | AG1-000B C | Adder | 23.75 MW | 20.19 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 7.12 MW | 7.12 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.77 MW | 2.77 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 136.96 MW | 136.96 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 63.0 MW | 63.0 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 59.61 MW | 59.61 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 10.77 MW | 10.77 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.41 MW | 13.41 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.66 MW | 0.66 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.19 MW | 3.19 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.64 MW | 8.64 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.46 MW | 3.46 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.55 MW | 0.55 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 10.92 MW | 10.92 MW |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.51 MW | 1.51 MW |
Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | 80/20 | 0.79 MW | 0.79 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | 80/20 | 0.79 MW | 0.79 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | Adder | 1.84 MW | 1.57 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 1.87 MW | 1.87 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 21.18 MW | 21.18 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 2.34 MW | 2.34 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.14 MW | 1.14 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 11.41 MW | 11.41 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | 80/20 | 2.42 MW | 2.42 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | Adder | 0.82 MW | 0.7 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 0.89 MW | 0.89 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | 80/20 | 0.83 MW | 0.83 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 1.96 MW | 1.96 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | 80/20 | 3.79 MW | 3.79 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | 80/20 | 3.79 MW | 3.79 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | 80/20 | 2.21 MW | 2.21 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | 80/20 | 2.21 MW | 2.21 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 7.72 MW | 7.72 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | Adder | 5.37 MW | 4.56 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | Adder | 5.37 MW | 4.56 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 0.69 MW | 0.69 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 3.17 MW | 3.17 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.21 MW | 0.21 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.15 MW | 0.15 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.6 MW | 0.6 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.57 MW | 0.57 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 0.98 MW | 0.98 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.61 MW | 0.61 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.46 MW | 0.46 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.45 MW | 1.45 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | 80/20 | 9.57 MW | 9.57 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.39 MW | 2.39 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.8 MW | 0.8 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 3.54 MW | 3.54 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 4.01 MW | 4.01 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | 80/20 | 19.94 MW | 19.94 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 11.9 MW | 11.9 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.34 MW | 4.34 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.27 MW | 1.27 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 2.5 MW | 2.12 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 3.06 MW | 2.6 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.65 MW | 0.65 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | Adder | 2.62 MW | 2.23 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 6.5 MW | 6.5 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.45 MW | 3.45 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.41 MW | 3.41 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | 80/20 | 2.6 MW | 2.6 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 13.29 MW | 13.29 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.76 MW | 0.76 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 6.75 MW | 6.75 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | 80/20 | 6.17 MW | 6.17 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C | 80/20 | 1.18 MW | 1.18 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 10.36 MW | 10.36 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 5.74 MW | 5.74 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 8.67 MW | 8.67 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314314 | 3LOCKS | 80/20 | 0.2 MW | 0.2 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.28 MW | 0.28 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315065 | 1CHESTF6 | 80/20 | 144.18 MW | 144.18 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315076 | 1HOPPOLC | 80/20 | 1.18 MW | 1.18 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315077 | 1HOPHCF1 | 80/20 | 1.84 MW | 1.84 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315078 | 1HOPHCF2 | 80/20 | 1.84 MW | 1.84 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315079 | 1HOPHCF3 | 80/20 | 1.84 MW | 1.84 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315080 | 1HOPHCF4 | 80/20 | 2.79 MW | 2.79 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927225 | AC1-216 C | 80/20 | 0.95 MW | 0.95 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934014 | AD1-025 C | 80/20 | 9.64 MW | 9.64 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934061 | AD1-033 C | Adder | 2.49 MW | 2.12 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | 80/20 | 5.52 MW | 5.52 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935111 | AD1-144 C | 80/20 | 0.1 MW | 0.1 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935164 | AD1-151 C | 80/20 | 9.82 MW | 9.82 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | 80/20 | 1.71 MW | 1.71 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | -2.89 MW | -2.46 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937221 | AD2-160 C O1 | Adder | 1.95 MW | 1.66 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942161 | AE2-228 C | 80/20 | 2.91 MW | 2.91 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | 80/20 | 0.74 MW | 0.74 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942371 | AE2-250 C O1 | 80/20 | 6.21 MW | 6.21 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942401 | AE2-253 C | Adder | 2.05 MW | 1.75 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942551 | AE2-270 | 80/20 | 15.73 MW | 15.73 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | 80/20 | 0.67 MW | 0.67 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943611 | AF1-032 C | 80/20 | 0.6 MW | 0.6 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943621 | AF1-033 C | 80/20 | 0.98 MW | 0.98 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944871 | AF1-152 C | Adder | 1.83 MW | 1.56 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958501 | AF2-144 C | Adder | -0.62 MW | -0.53 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961711 | AG1-011 | 80/20 | 16.37 MW | 16.37 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.83 MW | 2.83 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.83 MW | 2.83 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.89 MW | 5.89 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315115 | 1S HAMPT1 | 80/20 | 0.63 MW | 0.63 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315116 | 1SURRY 1 | 80/20 | 11.45 MW | 11.45 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315117 | 1GRAVELC | 80/20 | 0.4 MW | 0.4 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315119 | 1GRAVEL3 | 80/20 | 1.16 MW | 1.16 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315120 | 1GRAVEL4 | 80/20 | 1.18 MW | 1.18 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315121 | 1GRAVEL5 | 80/20 | 1.16 MW | 1.16 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315122 | 1GRAVEL6 | 80/20 | 1.18 MW | 1.18 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.45 MW | 1.45 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 3.65 MW | 3.65 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 3.65 MW | 3.65 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 3.65 MW | 3.65 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 6.34 MW | 6.34 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.61 MW | 0.61 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315608 | 3AA2-088SOLA | 80/20 | 0.45 MW | 0.45 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316033 | AB2-134 C | 80/20 | 1.25 MW | 1.25 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.57 MW | 0.57 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316096 | AB2-100 C1 | 80/20 | 0.55 MW | 0.55 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316098 | AB2-100 C2 | 80/20 | 0.55 MW | 0.55 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316108 | AB2-160 C | 80/20 | 3.5 MW | 3.5 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316132 | AB2-190 C | 80/20 | 11.34 MW | 11.34 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316258 | AE1-162 C | 80/20 | 0.15 MW | 0.15 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932044 | AC2-012 C | Adder | 2.72 MW | 2.31 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | 80/20 | 3.27 MW | 3.27 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | 80/20 | 0.15 MW | 0.15 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938535 | AE1-072 C | Adder | 5.89 MW | 5.01 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939195 | AE1-149 C | 80/20 | 8.31 MW | 8.31 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 10.5 MW | 10.5 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 9.0 MW | 9.0 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 10.5 MW | 10.5 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | 80/20 | 1.87 MW | 1.87 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | 80/20 | 2.77 MW | 2.77 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | 80/20 | 1.34 MW | 1.34 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941281 | AE2-122 C O1 | Adder | 9.51 MW | 8.09 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941291 | AE2-123 C O1 | Adder | 9.78 MW | 8.31 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941301 | AE2-124 C O1 | Adder | 8.88 MW | 7.55 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946261 | AF1-291 C | 80/20 | 2.93 MW | 2.93 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957491 | AF2-043 C | 80/20 | 0.74 MW | 0.74 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957631 | AF2-057 | Adder | 1.21 MW | 1.03 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957711 | AF2-065 C | 80/20 | 8.02 MW | 8.02 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963221 | AG1-171 C | 80/20 | 1.23 MW | 1.23 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963231 | AG1-172 C | 80/20 | 1.23 MW | 1.23 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963241 | AG1-173 C | 80/20 | 1.23 MW | 1.23 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963251 | AG1-174 C | 80/20 | 1.23 MW | 1.23 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964951 | AG1-359 O1 | Adder | 7.55 MW | 6.42 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965001 | AG1-364 C O1 | Adder | 2.42 MW | 2.06 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941501 | AE2-147 C | Adder | 5.5 MW | 4.67 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941591 | AE2-156 O1 | Adder | 6.05 MW | 5.14 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942001 | AE2-212 C | 80/20 | 2.52 MW | 2.52 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957871 | AF2-081 C | Adder | 3.34 MW | 2.84 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | 80/20 | 0.55 MW | 0.55 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966611 | AG1-531 C | Adder | 1.99 MW | 1.69 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | 80/20 | 3.25 MW | 3.25 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | 80/20 | 6.77 MW | 6.77 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962271 | AG1-075 C O1 | 80/20 | 10.71 MW | 10.71 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | 80/20 | 2.66 MW | 2.66 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | 80/20 | 1.43 MW | 1.43 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315602 | 1HOLLOMANSOL | 80/20 | 0.59 MW | 0.59 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315614 | AA2-178 C | 80/20 | 0.59 MW | 0.59 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | 80/20 | 2.42 MW | 2.42 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961611 | AG1-000B C | 80/20 | 7.53 MW | 7.53 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.69 MW | 1.69 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.46 MW | 0.46 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.86 MW | 29.86 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.07 MW | 8.07 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.53 MW | 9.53 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.56 MW | 2.56 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.3 MW | 2.3 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.23 MW | 1.23 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.45 MW | 0.45 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.85 MW | 1.85 MW |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
Details for 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | 80/20 | 0.33 MW | 0.33 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | 80/20 | 0.17 MW | 0.17 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | 80/20 | 0.69 MW | 0.69 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | 80/20 | 0.69 MW | 0.69 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 1.8 MW | 1.8 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 1.82 MW | 1.82 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 19.5 MW | 19.5 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 10.51 MW | 10.51 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | 80/20 | 2.02 MW | 2.02 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | Adder | 0.71 MW | 0.61 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 0.92 MW | 0.92 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | 80/20 | 0.69 MW | 0.69 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | Adder | 3.01 MW | 2.56 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | Adder | 3.01 MW | 2.56 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | 80/20 | 8.22 MW | 8.22 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | 80/20 | 2.56 MW | 2.56 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | 80/20 | 2.56 MW | 2.56 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | Adder | 1.76 MW | 1.49 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | Adder | 1.76 MW | 1.49 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | 80/20 | 4.38 MW | 4.38 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | 80/20 | 1.48 MW | 1.48 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | 80/20 | 1.48 MW | 1.48 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 7.54 MW | 7.54 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 5.29 MW | 5.29 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 5.29 MW | 5.29 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 0.81 MW | 0.81 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 3.54 MW | 3.54 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313719 | 3CHESTNUT | 80/20 | 0.46 MW | 0.46 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.24 MW | 0.24 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.14 MW | 0.14 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.08 MW | 0.08 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.62 MW | 0.62 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.59 MW | 0.59 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | 80/20 | 2.88 MW | 2.88 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | 80/20 | 2.88 MW | 2.88 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 1.05 MW | 1.05 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.65 MW | 0.65 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.49 MW | 0.49 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.57 MW | 1.57 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315159 | 1KERR 2 | 80/20 | 0.39 MW | 0.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315160 | 1KERR 3 | 80/20 | 0.39 MW | 0.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.39 MW | 0.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.39 MW | 0.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.06 MW | 0.06 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | 80/20 | 10.4 MW | 10.4 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.31 MW | 2.31 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.77 MW | 0.77 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | 80/20 | 2.88 MW | 2.88 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 3.52 MW | 3.52 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 4.2 MW | 4.2 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 11.62 MW | 11.62 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.48 MW | 0.48 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.23 MW | 4.23 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | 80/20 | 1.03 MW | 1.03 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | 80/20 | 2.19 MW | 2.19 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.49 MW | 1.49 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.39 MW | 0.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.39 MW | 0.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315601 | 1CONETOE2SOL | 80/20 | 0.49 MW | 0.49 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.65 MW | 0.65 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316020 | AB2-059 C OP | 80/20 | 0.65 MW | 0.65 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | 80/20 | 2.77 MW | 2.77 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | 80/20 | 0.2 MW | 0.2 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 922922 | AB1-081 C OP | 80/20 | 0.55 MW | 0.55 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 7.06 MW | 7.06 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.86 MW | 3.86 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924301 | AB2-077 C O1 | Adder | 0.61 MW | 0.52 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924311 | AB2-078 C O1 | Adder | 0.61 MW | 0.52 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924321 | AB2-079 C O1 | Adder | 0.61 MW | 0.52 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | 80/20 | 2.46 MW | 2.46 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.29 MW | 3.29 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C | 80/20 | 2.88 MW | 2.88 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | 80/20 | 1.61 MW | 1.61 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | 80/20 | 1.07 MW | 1.07 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 12.95 MW | 12.95 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.89 MW | 0.89 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | 80/20 | 15.66 MW | 15.66 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 5.74 MW | 5.74 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | 80/20 | 2.61 MW | 2.61 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 13.2 MW | 13.2 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 5.31 MW | 5.31 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 11.05 MW | 11.05 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314314 | 3LOCKS | 80/20 | 0.44 MW | 0.44 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.36 MW | 0.36 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.03 MW | 0.03 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | 80/20 | 2.41 MW | 2.41 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | -0.71 MW | -0.6 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942371 | AE2-250 C O1 | 80/20 | 13.91 MW | 13.91 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 2.77 MW | 2.77 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.77 MW | 2.77 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.77 MW | 2.77 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.76 MW | 5.76 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.57 MW | 1.57 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 3.56 MW | 3.56 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 3.56 MW | 3.56 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 3.56 MW | 3.56 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 6.2 MW | 6.2 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.58 MW | 0.58 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315608 | 3AA2-088SOLA | 80/20 | 0.37 MW | 0.37 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.65 MW | 0.65 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316096 | AB2-100 C1 | 80/20 | 0.66 MW | 0.66 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316098 | AB2-100 C2 | 80/20 | 0.66 MW | 0.66 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316108 | AB2-160 C | 80/20 | 7.83 MW | 7.83 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | 80/20 | 0.12 MW | 0.12 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939195 | AE1-149 C | 80/20 | 3.56 MW | 3.56 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 8.76 MW | 8.76 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 7.51 MW | 7.51 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 8.76 MW | 8.76 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940431 | AE2-027 C O1 | 80/20 | 11.71 MW | 11.71 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | 80/20 | 2.4 MW | 2.4 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | 80/20 | 1.19 MW | 1.19 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | 80/20 | 2.81 MW | 2.81 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | 80/20 | 5.75 MW | 5.75 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962271 | AG1-075 C O1 | 80/20 | 24.02 MW | 24.02 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | 80/20 | 2.89 MW | 2.89 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | 80/20 | 1.84 MW | 1.84 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315602 | 1HOLLOMANSOL | 80/20 | 0.49 MW | 0.49 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | 80/20 | 1.06 MW | 1.06 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.69 MW | 1.69 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.49 MW | 0.49 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 30.26 MW | 30.26 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.74 MW | 9.74 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.44 MW | 10.44 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.56 MW | 2.56 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.48 MW | 0.48 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.41 MW | 1.41 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.98 MW | 1.98 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 962491 | AG1-098 C O1 | 80/20 | 5.29 MW | 5.29 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 4.69 MW | 4.69 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 4.8 MW | 4.8 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 53.14 MW | 53.14 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 28.63 MW | 28.63 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 20.18 MW | 20.18 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 13.69 MW | 13.69 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 13.69 MW | 13.69 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | Adder | -5.34 MW | -4.54 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315153 | 1CLOVER1 | 80/20 | 8.1 MW | 8.1 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315154 | 1CLOVER2 | 80/20 | 8.02 MW | 8.02 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 927251 | AC1-221 C | 80/20 | 0.82 MW | 0.82 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 927261 | AC1-222 C | 80/20 | 1.17 MW | 1.17 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 934311 | AD1-055 C | 80/20 | 0.81 MW | 0.81 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 934341 | AD1-058 C | 80/20 | 2.06 MW | 2.06 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 934615 | AD1-087 C | 80/20 | 4.69 MW | 4.69 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 934625 | AD1-088 C | 80/20 | 5.83 MW | 5.83 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 934991 | AD1-131 C | 80/20 | 0.68 MW | 0.68 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 935171 | AD1-152 C O1 | 80/20 | 4.4 MW | 4.4 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 937481 | AD2-202 C O1 | 80/20 | 1.37 MW | 1.37 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 31.08 MW | 31.08 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 943901 | AF1-058 C | 80/20 | 0.65 MW | 0.65 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 11.38 MW | 11.38 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | 80/20 | 5.22 MW | 5.22 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 960061 | AF2-297 C | 80/20 | 2.6 MW | 2.6 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | Adder | -9.89 MW | -8.41 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | Adder | -5.82 MW | -4.95 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 932761 | AC2-100 C | 80/20 | 1.89 MW | 1.89 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 34.84 MW | 34.84 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 941791 | AE2-182 C | 80/20 | 0.95 MW | 0.95 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | 80/20 | 37.32 MW | 37.32 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 14.64 MW | 14.64 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 314295 | 6BIRDNECK | 80/20 | 0.01 MW | 0.01 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 314491 | 3PENDLTN | 80/20 | 0.11 MW | 0.11 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 314507 | 3THOMPSN | 80/20 | 0.11 MW | 0.11 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 314643 | 3O INLET | 80/20 | 0.14 MW | 0.14 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 926661 | AC1-147 C | 80/20 | 0.12 MW | 0.12 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 926754 | AC1-161 C | 80/20 | 14.62 MW | 14.62 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 934061 | AD1-033 C | 80/20 | 2.53 MW | 2.53 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | Adder | -7.33 MW | -6.23 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | -1.01 MW | -0.86 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 937221 | AD2-160 C O1 | 80/20 | 1.87 MW | 1.87 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 942401 | AE2-253 C | 80/20 | 1.97 MW | 1.97 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315098 | 1CHESPKA | 80/20 | 0.15 MW | 0.15 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315099 | 1CHESPKB | 80/20 | 0.24 MW | 0.24 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 7.21 MW | 7.21 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 7.21 MW | 7.21 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 7.21 MW | 7.21 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 14.98 MW | 14.98 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315108 | 1ELIZAR1 | 80/20 | 1.1 MW | 1.1 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315109 | 1ELIZAR2 | 80/20 | 1.08 MW | 1.08 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315110 | 1ELIZAR3 | 80/20 | 1.12 MW | 1.12 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315233 | 1SURRY 2 | 80/20 | 9.26 MW | 9.26 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 9.38 MW | 9.38 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 9.38 MW | 9.38 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 9.38 MW | 9.38 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 16.31 MW | 16.31 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315260 | 1GOSPORTA | 80/20 | 0.12 MW | 0.12 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315261 | 1GOSPORTB | 80/20 | 0.15 MW | 0.15 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315262 | 1GOSPORTC | 80/20 | 0.13 MW | 0.13 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 315603 | 6AA1-139SOLA | 80/20 | 0.74 MW | 0.74 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 932044 | AC2-012 C | 80/20 | 2.58 MW | 2.58 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 938535 | AE1-072 C | 80/20 | 5.33 MW | 5.33 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 23.04 MW | 23.04 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 19.75 MW | 19.75 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 23.04 MW | 23.04 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 941281 | AE2-122 C O1 | 80/20 | 9.37 MW | 9.37 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 941291 | AE2-123 C O1 | 80/20 | 9.62 MW | 9.62 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 941301 | AE2-124 C O1 | 80/20 | 8.77 MW | 8.77 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 957631 | AF2-057 | 80/20 | 1.15 MW | 1.15 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 964951 | AG1-359 O1 | 80/20 | 7.72 MW | 7.72 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 965001 | AG1-364 C O1 | 80/20 | 2.33 MW | 2.33 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 933294 | AC2-141 C | 80/20 | 14.62 MW | 14.62 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 941591 | AE2-156 O1 | 80/20 | 5.83 MW | 5.83 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 957871 | AF2-081 C | 80/20 | 3.11 MW | 3.11 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 944581 | AF1-123 C O1 | 80/20 | 18.48 MW | 18.48 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 944591 | AF1-124 C O1 | 80/20 | 18.48 MW | 18.48 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 944601 | AF1-125 C O1 | 80/20 | 18.48 MW | 18.48 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | Adder | -3.22 MW | -2.73 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.97 MW | 1.97 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 37.98 MW | 37.98 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.45 MW | 12.45 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.47 MW | 13.47 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.99 MW | 2.99 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.19 MW | 3.19 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.61 MW | 0.61 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.81 MW | 1.81 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.49 MW | 0.49 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.56 MW | 2.56 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
Details for 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | 80/20 | 0.33 MW | 0.33 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | 80/20 | 0.17 MW | 0.17 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | 80/20 | 0.69 MW | 0.69 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | 80/20 | 0.69 MW | 0.69 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 1.8 MW | 1.8 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 1.82 MW | 1.82 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 19.5 MW | 19.5 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 10.51 MW | 10.51 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | 80/20 | 2.02 MW | 2.02 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 0.92 MW | 0.92 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | 80/20 | 0.69 MW | 0.69 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | 80/20 | 8.22 MW | 8.22 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | 80/20 | 2.56 MW | 2.56 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | 80/20 | 2.56 MW | 2.56 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | 80/20 | 4.38 MW | 4.38 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | 80/20 | 1.48 MW | 1.48 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | 80/20 | 1.48 MW | 1.48 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 7.54 MW | 7.54 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 5.29 MW | 5.29 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 5.29 MW | 5.29 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 0.81 MW | 0.81 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 3.54 MW | 3.54 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313719 | 3CHESTNUT | 80/20 | 0.46 MW | 0.46 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.24 MW | 0.24 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.14 MW | 0.14 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.08 MW | 0.08 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.62 MW | 0.62 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.59 MW | 0.59 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | 80/20 | 2.88 MW | 2.88 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | 80/20 | 2.88 MW | 2.88 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 1.05 MW | 1.05 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.65 MW | 0.65 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.49 MW | 0.49 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.57 MW | 1.57 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315159 | 1KERR 2 | 80/20 | 0.39 MW | 0.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315160 | 1KERR 3 | 80/20 | 0.39 MW | 0.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.39 MW | 0.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.39 MW | 0.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.06 MW | 0.06 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | 80/20 | 10.4 MW | 10.4 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.31 MW | 2.31 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.77 MW | 0.77 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | 80/20 | 2.88 MW | 2.88 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 3.52 MW | 3.52 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 4.2 MW | 4.2 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 11.62 MW | 11.62 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.48 MW | 0.48 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.23 MW | 4.23 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | 80/20 | 1.03 MW | 1.03 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | 80/20 | 2.19 MW | 2.19 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.49 MW | 1.49 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.39 MW | 0.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.39 MW | 0.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315601 | 1CONETOE2SOL | 80/20 | 0.49 MW | 0.49 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.65 MW | 0.65 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316020 | AB2-059 C OP | 80/20 | 0.65 MW | 0.65 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | 80/20 | 2.77 MW | 2.77 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | 80/20 | 0.2 MW | 0.2 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 922922 | AB1-081 C OP | 80/20 | 0.55 MW | 0.55 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 7.06 MW | 7.06 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.86 MW | 3.86 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | 80/20 | 2.46 MW | 2.46 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.29 MW | 3.29 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C | 80/20 | 2.88 MW | 2.88 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | 80/20 | 1.61 MW | 1.61 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | 80/20 | 1.07 MW | 1.07 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 12.95 MW | 12.95 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.89 MW | 0.89 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | 80/20 | 15.66 MW | 15.66 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 5.74 MW | 5.74 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | 80/20 | 2.61 MW | 2.61 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 13.2 MW | 13.2 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 5.31 MW | 5.31 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 11.05 MW | 11.05 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314314 | 3LOCKS | 80/20 | 0.44 MW | 0.44 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.36 MW | 0.36 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.03 MW | 0.03 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | 80/20 | 2.41 MW | 2.41 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | -0.71 MW | -0.6 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942371 | AE2-250 C O1 | 80/20 | 13.91 MW | 13.91 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 2.77 MW | 2.77 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.77 MW | 2.77 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.77 MW | 2.77 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.76 MW | 5.76 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.57 MW | 1.57 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 3.56 MW | 3.56 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 3.56 MW | 3.56 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 3.56 MW | 3.56 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 6.2 MW | 6.2 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.58 MW | 0.58 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315608 | 3AA2-088SOLA | 80/20 | 0.37 MW | 0.37 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.65 MW | 0.65 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316096 | AB2-100 C1 | 80/20 | 0.66 MW | 0.66 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316098 | AB2-100 C2 | 80/20 | 0.66 MW | 0.66 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316108 | AB2-160 C | 80/20 | 7.83 MW | 7.83 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | 80/20 | 0.12 MW | 0.12 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939195 | AE1-149 C | 80/20 | 3.56 MW | 3.56 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 8.76 MW | 8.76 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 7.51 MW | 7.51 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 8.76 MW | 8.76 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940431 | AE2-027 C O1 | 80/20 | 11.71 MW | 11.71 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | 80/20 | 2.4 MW | 2.4 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | 80/20 | 1.19 MW | 1.19 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942001 | AE2-212 C | 80/20 | 7.58 MW | 7.58 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | 80/20 | 2.81 MW | 2.81 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | 80/20 | 5.75 MW | 5.75 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962271 | AG1-075 C O1 | 80/20 | 24.02 MW | 24.02 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | 80/20 | 2.89 MW | 2.89 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | 80/20 | 1.84 MW | 1.84 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315602 | 1HOLLOMANSOL | 80/20 | 0.49 MW | 0.49 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | 80/20 | 1.06 MW | 1.06 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.69 MW | 1.69 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.49 MW | 0.49 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 30.26 MW | 30.26 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.74 MW | 9.74 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.44 MW | 10.44 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.56 MW | 2.56 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.48 MW | 0.48 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.41 MW | 1.41 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.98 MW | 1.98 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
Details for 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | 80/20 | 0.33 MW | 0.33 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | 80/20 | 0.18 MW | 0.18 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | 80/20 | 0.72 MW | 0.72 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | 80/20 | 0.72 MW | 0.72 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 1.73 MW | 1.73 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 1.75 MW | 1.75 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 18.91 MW | 18.91 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 2.57 MW | 2.57 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.25 MW | 1.25 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 10.19 MW | 10.19 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | 80/20 | 2.29 MW | 2.29 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | Adder | 0.73 MW | 0.62 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 0.9 MW | 0.9 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | 80/20 | 0.79 MW | 0.79 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 2.14 MW | 2.14 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | 80/20 | 3.18 MW | 3.18 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | 80/20 | 3.18 MW | 3.18 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | 80/20 | 8.17 MW | 8.17 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | 80/20 | 2.49 MW | 2.49 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | 80/20 | 2.49 MW | 2.49 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | 80/20 | 1.85 MW | 1.85 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | 80/20 | 1.85 MW | 1.85 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | 80/20 | 4.36 MW | 4.36 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | 80/20 | 1.44 MW | 1.44 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | 80/20 | 1.44 MW | 1.44 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 7.22 MW | 7.22 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 5.06 MW | 5.06 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 5.06 MW | 5.06 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 0.75 MW | 0.75 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 3.38 MW | 3.38 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313719 | 3CHESTNUT | 80/20 | 0.45 MW | 0.45 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.23 MW | 0.23 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.14 MW | 0.14 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.08 MW | 0.08 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.61 MW | 0.61 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.58 MW | 0.58 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | 80/20 | 2.81 MW | 2.81 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | 80/20 | 2.81 MW | 2.81 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 1.01 MW | 1.01 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.63 MW | 0.63 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.51 MW | 1.51 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315159 | 1KERR 2 | 80/20 | 0.37 MW | 0.37 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315160 | 1KERR 3 | 80/20 | 0.37 MW | 0.37 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.37 MW | 0.37 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.37 MW | 0.37 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.06 MW | 0.06 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | 80/20 | 9.94 MW | 9.94 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.31 MW | 2.31 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.77 MW | 0.77 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | 80/20 | 2.88 MW | 2.88 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 3.49 MW | 3.49 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 4.05 MW | 4.05 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | Adder | 16.05 MW | 13.64 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 11.13 MW | 11.13 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.51 MW | 0.51 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.05 MW | 4.05 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | 80/20 | 1.01 MW | 1.01 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | Adder | 2.1 MW | 1.78 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.4 MW | 1.4 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.37 MW | 0.37 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.37 MW | 0.37 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 2.06 MW | 1.75 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 2.53 MW | 2.15 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315601 | 1CONETOE2SOL | 80/20 | 0.49 MW | 0.49 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.65 MW | 0.65 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316020 | AB2-059 C OP | 80/20 | 0.63 MW | 0.63 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | 80/20 | 2.7 MW | 2.7 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | 80/20 | 0.21 MW | 0.21 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 922922 | AB1-081 C OP | 80/20 | 0.54 MW | 0.54 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 6.75 MW | 6.75 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.68 MW | 3.68 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | 80/20 | 2.4 MW | 2.4 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.29 MW | 3.29 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C | Adder | 2.78 MW | 2.36 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | 80/20 | 1.57 MW | 1.57 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | Adder | 1.03 MW | 0.88 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 12.39 MW | 12.39 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.83 MW | 0.83 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | Adder | 15.0 MW | 12.75 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 6.29 MW | 6.29 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | 80/20 | 2.61 MW | 2.61 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C | 80/20 | 1.07 MW | 1.07 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 11.99 MW | 11.99 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 5.12 MW | 5.12 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 10.04 MW | 10.04 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.33 MW | 0.33 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | 80/20 | 8.21 MW | 8.21 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | 80/20 | 1.97 MW | 1.97 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | -0.68 MW | -0.58 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | 80/20 | 0.86 MW | 0.86 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | 80/20 | 0.78 MW | 0.78 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 2.65 MW | 2.65 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.65 MW | 2.65 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.65 MW | 2.65 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.51 MW | 5.51 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315115 | 1S HAMPT1 | 80/20 | 0.58 MW | 0.58 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.51 MW | 1.51 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 3.41 MW | 3.41 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 3.41 MW | 3.41 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 3.41 MW | 3.41 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 5.93 MW | 5.93 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.6 MW | 0.6 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315608 | 3AA2-088SOLA | 80/20 | 0.42 MW | 0.42 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.62 MW | 0.62 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316096 | AB2-100 C1 | 80/20 | 0.61 MW | 0.61 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316098 | AB2-100 C2 | 80/20 | 0.61 MW | 0.61 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | 80/20 | 4.22 MW | 4.22 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | 80/20 | 0.13 MW | 0.13 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939195 | AE1-149 C | 80/20 | 12.87 MW | 12.87 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | Adder | 8.72 MW | 7.41 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | Adder | 7.47 MW | 6.35 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | Adder | 8.72 MW | 7.41 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | 80/20 | 2.18 MW | 2.18 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | 80/20 | 4.29 MW | 4.29 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | 80/20 | 1.18 MW | 1.18 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | 80/20 | 0.49 MW | 0.49 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | Adder | 2.68 MW | 2.27 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | 80/20 | 2.75 MW | 2.75 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | 80/20 | 6.3 MW | 6.3 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | 80/20 | 2.76 MW | 2.76 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | 80/20 | 1.67 MW | 1.67 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315602 | 1HOLLOMANSOL | 80/20 | 0.51 MW | 0.51 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | 80/20 | 3.6 MW | 3.6 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.64 MW | 1.64 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.47 MW | 0.47 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.3 MW | 29.3 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.33 MW | 9.33 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.06 MW | 10.06 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.49 MW | 2.49 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.38 MW | 2.38 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.13 MW | 0.13 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.46 MW | 0.46 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.35 MW | 1.35 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.91 MW | 1.91 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
Details for 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | 80/20 | 0.33 MW | 0.33 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | 80/20 | 0.18 MW | 0.18 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | 80/20 | 0.72 MW | 0.72 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | 80/20 | 0.72 MW | 0.72 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 1.73 MW | 1.73 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 1.75 MW | 1.75 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 18.91 MW | 18.91 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 2.57 MW | 2.57 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.25 MW | 1.25 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 10.19 MW | 10.19 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | 80/20 | 2.29 MW | 2.29 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | Adder | 0.73 MW | 0.62 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 0.9 MW | 0.9 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | 80/20 | 0.79 MW | 0.79 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 2.14 MW | 2.14 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | 80/20 | 3.18 MW | 3.18 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | 80/20 | 3.18 MW | 3.18 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | 80/20 | 8.17 MW | 8.17 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | 80/20 | 2.49 MW | 2.49 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | 80/20 | 2.49 MW | 2.49 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | 80/20 | 1.85 MW | 1.85 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | 80/20 | 1.85 MW | 1.85 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | 80/20 | 4.36 MW | 4.36 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | 80/20 | 1.44 MW | 1.44 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | 80/20 | 1.44 MW | 1.44 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 7.22 MW | 7.22 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 5.06 MW | 5.06 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 5.06 MW | 5.06 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 0.75 MW | 0.75 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 3.38 MW | 3.38 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313719 | 3CHESTNUT | 80/20 | 0.45 MW | 0.45 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.23 MW | 0.23 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.14 MW | 0.14 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.08 MW | 0.08 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.61 MW | 0.61 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.58 MW | 0.58 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | 80/20 | 2.81 MW | 2.81 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | 80/20 | 2.81 MW | 2.81 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 1.01 MW | 1.01 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.63 MW | 0.63 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.51 MW | 1.51 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315159 | 1KERR 2 | 80/20 | 0.37 MW | 0.37 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315160 | 1KERR 3 | 80/20 | 0.37 MW | 0.37 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.37 MW | 0.37 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.37 MW | 0.37 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.06 MW | 0.06 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | 80/20 | 9.94 MW | 9.94 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.31 MW | 2.31 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.77 MW | 0.77 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | 80/20 | 2.88 MW | 2.88 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 3.49 MW | 3.49 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 4.05 MW | 4.05 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | Adder | 16.05 MW | 13.64 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 11.13 MW | 11.13 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.51 MW | 0.51 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.05 MW | 4.05 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | 80/20 | 1.01 MW | 1.01 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | Adder | 2.1 MW | 1.78 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.4 MW | 1.4 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.37 MW | 0.37 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.37 MW | 0.37 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 2.06 MW | 1.75 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 2.53 MW | 2.15 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315601 | 1CONETOE2SOL | 80/20 | 0.49 MW | 0.49 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.65 MW | 0.65 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316020 | AB2-059 C OP | 80/20 | 0.63 MW | 0.63 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | 80/20 | 2.7 MW | 2.7 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | 80/20 | 0.21 MW | 0.21 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 922922 | AB1-081 C OP | 80/20 | 0.54 MW | 0.54 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 6.75 MW | 6.75 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.68 MW | 3.68 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | 80/20 | 2.4 MW | 2.4 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.29 MW | 3.29 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C | Adder | 2.78 MW | 2.36 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | 80/20 | 1.57 MW | 1.57 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | Adder | 1.03 MW | 0.88 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 12.39 MW | 12.39 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.83 MW | 0.83 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | Adder | 15.0 MW | 12.75 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 6.29 MW | 6.29 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | 80/20 | 2.61 MW | 2.61 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C | 80/20 | 1.07 MW | 1.07 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 11.99 MW | 11.99 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 5.12 MW | 5.12 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 10.04 MW | 10.04 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.33 MW | 0.33 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | 80/20 | 8.21 MW | 8.21 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | 80/20 | 1.97 MW | 1.97 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | -0.68 MW | -0.58 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | 80/20 | 0.86 MW | 0.86 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | 80/20 | 0.78 MW | 0.78 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 2.65 MW | 2.65 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.65 MW | 2.65 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.65 MW | 2.65 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.51 MW | 5.51 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315115 | 1S HAMPT1 | 80/20 | 0.58 MW | 0.58 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.51 MW | 1.51 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 3.41 MW | 3.41 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 3.41 MW | 3.41 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 3.41 MW | 3.41 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 5.93 MW | 5.93 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.6 MW | 0.6 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315608 | 3AA2-088SOLA | 80/20 | 0.42 MW | 0.42 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.62 MW | 0.62 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316096 | AB2-100 C1 | 80/20 | 0.61 MW | 0.61 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316098 | AB2-100 C2 | 80/20 | 0.61 MW | 0.61 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | 80/20 | 4.22 MW | 4.22 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | 80/20 | 0.13 MW | 0.13 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939195 | AE1-149 C | 80/20 | 12.87 MW | 12.87 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | Adder | 8.72 MW | 7.41 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | Adder | 7.47 MW | 6.35 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | Adder | 8.72 MW | 7.41 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | 80/20 | 2.18 MW | 2.18 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | 80/20 | 4.29 MW | 4.29 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | 80/20 | 1.18 MW | 1.18 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | 80/20 | 0.49 MW | 0.49 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | Adder | 2.68 MW | 2.27 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | 80/20 | 2.75 MW | 2.75 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | 80/20 | 6.3 MW | 6.3 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | 80/20 | 2.76 MW | 2.76 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | 80/20 | 1.67 MW | 1.67 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315602 | 1HOLLOMANSOL | 80/20 | 0.51 MW | 0.51 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | 80/20 | 3.6 MW | 3.6 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.64 MW | 1.64 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.47 MW | 0.47 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.3 MW | 29.3 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.33 MW | 9.33 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.06 MW | 10.06 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.49 MW | 2.49 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.38 MW | 2.38 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.13 MW | 0.13 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.46 MW | 0.46 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.35 MW | 1.35 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.91 MW | 1.91 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 961671 | AG1-007 C | Adder | 0.41 MW | 0.34 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 961941 | AG1-037 C | Adder | 0.2 MW | 0.17 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 962331 | AG1-082 C | Adder | 0.82 MW | 0.69 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 962341 | AG1-083 C | Adder | 0.82 MW | 0.69 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 963041 | AG1-153 C | 80/20 | 3.99 MW | 3.99 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 963111 | AG1-160 C | 80/20 | 4.07 MW | 4.07 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 963291 | AG1-178 C O2 | 80/20 | 45.19 MW | 45.19 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 963351 | AG1-184 O2 | 80/20 | 24.35 MW | 24.35 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 964801 | AG1-343 C | Adder | 2.32 MW | 1.97 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 966801 | AG1-551 C | Adder | 0.96 MW | 0.82 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 966811 | AG1-552 C | Adder | 0.8 MW | 0.68 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 965291 | AG1-394 C | Adder | 0.8 MW | 0.68 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 965691 | AG1-437 C O1 | Adder | 4.22 MW | 3.58 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 965701 | AG1-438 C O1 | Adder | 4.22 MW | 3.58 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 965711 | AG1-439 C O1 | Adder | 10.16 MW | 8.64 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 965741 | AG1-442 O1 | Adder | 2.46 MW | 2.09 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 965751 | AG1-443 O1 | Adder | 2.46 MW | 2.09 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 965761 | AG1-444 O1 | Adder | 5.42 MW | 4.61 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 965811 | AG1-449 | 80/20 | 16.91 MW | 16.91 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 966361 | AG1-505 C | 80/20 | 11.5 MW | 11.5 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 966371 | AG1-506 C | 80/20 | 11.5 MW | 11.5 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 966621 | AG1-532 C | Adder | 0.5 MW | 0.42 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 313506 | AB1-173 C OP | Adder | 2.53 MW | 2.15 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 314572 | 3EMPORIA | Adder | 0.16 MW | 0.13 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315131 | 1EDGECMA | Adder | 3.35 MW | 2.85 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315132 | 1EDGECMB | Adder | 3.35 MW | 2.85 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315153 | 1CLOVER1 | 80/20 | 6.74 MW | 6.74 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315154 | 1CLOVER2 | 80/20 | 6.67 MW | 6.67 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 926070 | AC1-086 C | Adder | 8.13 MW | 6.91 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 926201 | AC1-098 C | Adder | 2.5 MW | 2.13 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 926211 | AC1-099 C | Adder | 0.84 MW | 0.71 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 927024 | AC1-189 C | Adder | 3.63 MW | 3.08 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 927145 | AC1-208 C | Adder | 3.65 MW | 3.1 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 927251 | AC1-221 C | Adder | 0.96 MW | 0.82 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 927261 | AC1-222 C | Adder | 1.38 MW | 1.17 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 934311 | AD1-055 C | Adder | 0.96 MW | 0.81 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 934331 | AD1-057 C O1 | Adder | 4.03 MW | 3.42 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 934341 | AD1-058 C | Adder | 2.41 MW | 2.05 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 934521 | AD1-076 C | 80/20 | 22.8 MW | 22.8 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 934615 | AD1-087 C | 80/20 | 3.91 MW | 3.91 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 934991 | AD1-131 C | Adder | 0.79 MW | 0.67 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 935171 | AD1-152 C O1 | 80/20 | 3.94 MW | 3.94 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 937481 | AD2-202 C O1 | 80/20 | 1.15 MW | 1.15 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 942931 | AE2-313 C | 80/20 | 26.05 MW | 26.05 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 943171 | AE2-346 C | Adder | 0.57 MW | 0.48 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 943901 | AF1-058 C | Adder | 0.77 MW | 0.66 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 944011 | AF1-069 C | 80/20 | 9.56 MW | 9.56 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 944141 | AF1-082 | Adder | 1.21 MW | 1.02 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 945811 | AF1-246 C O1 | 80/20 | 4.37 MW | 4.37 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 960061 | AF2-297 C | Adder | 3.08 MW | 2.62 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 960081 | AF2-299 C | Adder | 0.92 MW | 0.79 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315293 | 1DOMTR9 | Adder | 2.88 MW | 2.44 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315294 | 1DOMTR10 | Adder | 3.52 MW | 3.0 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 316118 | AC1-105 C | Adder | 2.09 MW | 1.77 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 316129 | AC1-054 C | Adder | 2.61 MW | 2.22 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 316140 | AB2-099 C | Adder | 0.24 MW | 0.2 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 923262 | AB1-132 C OP | Adder | 5.52 MW | 4.7 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 923991 | AB2-040 C O1 | Adder | 2.76 MW | 2.34 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 925591 | AC1-034 C | Adder | 2.86 MW | 2.43 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 932631 | AC2-084 C | Adder | 3.57 MW | 3.03 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 932761 | AC2-100 C | Adder | 2.22 MW | 1.88 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 940491 | AE2-034 C | 80/20 | 3.02 MW | 3.02 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 940571 | AE2-044 C | Adder | 1.88 MW | 1.59 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 941031 | AE2-094 C | 80/20 | 29.25 MW | 29.25 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 946281 | AF1-292 C | Adder | 0.55 MW | 0.47 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 957481 | AF2-042 C | 80/20 | 31.2 MW | 31.2 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 957521 | AF2-046 C | Adder | 6.69 MW | 5.69 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 957531 | AF2-047 C | 80/20 | 7.19 MW | 7.19 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 957861 | AF2-080 C | Adder | 3.3 MW | 2.8 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 938771 | AE1-103 C | Adder | 1.13 MW | 0.96 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 940481 | AE2-033 C | Adder | 5.7 MW | 4.84 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 940641 | AE2-051 C O1 | 80/20 | 12.36 MW | 12.36 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 946011 | AF1-266 | Adder | 4.77 MW | 4.05 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 933501 | AC2-165 C | Adder | -11.26 MW | -9.57 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 313526 | AB2-022 C | 80/20 | 0.17 MW | 0.17 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 314491 | 3PENDLTN | 80/20 | 0.14 MW | 0.14 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 314507 | 3THOMPSN | 80/20 | 0.14 MW | 0.14 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 314638 | 6ELIZ CT | 80/20 | 0.1 MW | 0.1 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 314639 | 6TANGLEW | 80/20 | 0.18 MW | 0.18 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 314643 | 3O INLET | 80/20 | 0.2 MW | 0.2 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 926661 | AC1-147 C | 80/20 | 0.16 MW | 0.16 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 926754 | AC1-161 C | 80/20 | 14.22 MW | 14.22 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 934061 | AD1-033 C | 80/20 | 3.23 MW | 3.23 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 936761 | AD2-097 C | Adder | -1.41 MW | -1.2 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 937221 | AD2-160 C O1 | 80/20 | 2.51 MW | 2.51 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 942401 | AE2-253 C | 80/20 | 2.64 MW | 2.64 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 943611 | AF1-032 C | 80/20 | 0.73 MW | 0.73 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 944871 | AF1-152 C | 80/20 | 2.23 MW | 2.23 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 958501 | AF2-144 C | Adder | -2.25 MW | -1.91 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315098 | 1CHESPKA | 80/20 | 0.19 MW | 0.19 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315099 | 1CHESPKB | 80/20 | 0.31 MW | 0.31 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315102 | 1BRUNSWICKG1 | 80/20 | 6.13 MW | 6.13 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315103 | 1BRUNSWICKG2 | 80/20 | 6.13 MW | 6.13 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315104 | 1BRUNSWICKG3 | 80/20 | 6.13 MW | 6.13 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315105 | 1BRUNSWICKS1 | 80/20 | 12.74 MW | 12.74 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315108 | 1ELIZAR1 | 80/20 | 1.4 MW | 1.4 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315109 | 1ELIZAR2 | 80/20 | 1.38 MW | 1.38 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315110 | 1ELIZAR3 | 80/20 | 1.42 MW | 1.42 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315241 | 1Z1-086 GT1 | 80/20 | 7.94 MW | 7.94 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315242 | 1Z1-086 GT2 | 80/20 | 7.94 MW | 7.94 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315243 | 1Z1-086 GT3 | 80/20 | 7.94 MW | 7.94 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315244 | 1Z1-086 ST | 80/20 | 13.8 MW | 13.8 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315260 | 1GOSPORTA | 80/20 | 0.15 MW | 0.15 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315261 | 1GOSPORTB | 80/20 | 0.19 MW | 0.19 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315262 | 1GOSPORTC | 80/20 | 0.16 MW | 0.16 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315603 | 6AA1-139SOLA | 80/20 | 1.02 MW | 1.02 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315605 | 6W1-029WIND | 80/20 | 0.49 MW | 0.49 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315611 | 6Z1-036WIND | 80/20 | 0.31 MW | 0.31 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 932044 | AC2-012 C | 80/20 | 3.34 MW | 3.34 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 938535 | AE1-072 C | 80/20 | 7.52 MW | 7.52 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 939414 | AE1-173_C1 | 80/20 | 20.57 MW | 20.57 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 939415 | AE1-173_C2 | 80/20 | 17.63 MW | 17.63 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 939416 | AE1-173_C3 | 80/20 | 20.57 MW | 20.57 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 940541 | AE2-040 | Adder | 1.0 MW | 0.85 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 941101 | AE2-104 C O1 | Adder | 1.29 MW | 1.09 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 941281 | AE2-122 C O1 | 80/20 | 12.06 MW | 12.06 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 941291 | AE2-123 C O1 | 80/20 | 12.4 MW | 12.4 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 941301 | AE2-124 C O1 | 80/20 | 11.29 MW | 11.29 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 957491 | AF2-043 C | 80/20 | 0.89 MW | 0.89 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 957631 | AF2-057 | 80/20 | 1.49 MW | 1.49 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 964951 | AG1-359 O1 | 80/20 | 9.83 MW | 9.83 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 965001 | AG1-364 C O1 | 80/20 | 2.98 MW | 2.98 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 933294 | AC2-141 C | 80/20 | 14.22 MW | 14.22 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 941501 | AE2-147 C | 80/20 | 6.68 MW | 6.68 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 941591 | AE2-156 O1 | 80/20 | 7.47 MW | 7.47 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 957871 | AF2-081 C | 80/20 | 4.28 MW | 4.28 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 958161 | AF2-110 C | Adder | 0.53 MW | 0.45 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 944581 | AF1-123 C O1 | 80/20 | 21.45 MW | 21.45 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 944591 | AF1-124 C O1 | 80/20 | 21.45 MW | 21.45 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 944601 | AF1-125 C O1 | 80/20 | 21.45 MW | 21.45 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 933981 | AD1-022 C | 80/20 | 3.66 MW | 3.66 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 960331 | AF2-324 C | Adder | 3.27 MW | 2.78 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 961681 | AG1-008 C | Adder | 6.71 MW | 5.7 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 962571 | AG1-106 C | Adder | 2.26 MW | 1.92 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 965281 | AG1-393 C | Adder | 0.77 MW | 0.65 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | 315614 | AA2-178 C | 80/20 | 0.69 MW | 0.69 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.75 MW | 2.75 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.74 MW | 0.74 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 49.1 MW | 49.1 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.32 MW | 13.32 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.6 MW | 15.6 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 4.16 MW | 4.16 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.77 MW | 3.77 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.23 MW | 0.23 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.02 MW | 2.02 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.58 MW | 0.58 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.03 MW | 3.03 MW |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961671 | AG1-007 C | Adder | 1.37 MW | 1.17 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961941 | AG1-037 C | Adder | 0.75 MW | 0.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962331 | AG1-082 C | Adder | 3.02 MW | 2.56 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962341 | AG1-083 C | Adder | 3.02 MW | 2.56 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962491 | AG1-098 C O1 | Adder | 15.53 MW | 13.2 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963041 | AG1-153 C | 80/20 | 9.13 MW | 9.13 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963111 | AG1-160 C | 80/20 | 9.24 MW | 9.24 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963291 | AG1-178 C O2 | 80/20 | 104.2 MW | 104.2 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963301 | AG1-179 C | Adder | 8.11 MW | 6.89 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963311 | AG1-180 | Adder | 3.95 MW | 3.36 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963351 | AG1-184 O2 | 80/20 | 56.14 MW | 56.14 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 964801 | AG1-343 C | Adder | 8.92 MW | 7.58 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966801 | AG1-551 C | Adder | 3.34 MW | 2.84 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966811 | AG1-552 C | Adder | 3.09 MW | 2.62 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965291 | AG1-394 C | Adder | 3.06 MW | 2.6 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965601 | AG1-428 C O2 | Adder | 6.77 MW | 5.75 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965691 | AG1-437 C O1 | Adder | 15.29 MW | 12.99 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965701 | AG1-438 C O1 | Adder | 15.29 MW | 12.99 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965711 | AG1-439 C O1 | Adder | 34.53 MW | 29.35 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965721 | AG1-440 C | Adder | 10.16 MW | 8.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965731 | AG1-441 C | Adder | 10.16 MW | 8.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965741 | AG1-442 O1 | Adder | 8.92 MW | 7.58 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965751 | AG1-443 O1 | Adder | 8.92 MW | 7.58 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965761 | AG1-444 O1 | Adder | 18.42 MW | 15.65 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965771 | AG1-445 | Adder | 5.87 MW | 4.99 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965781 | AG1-446 | Adder | 5.87 MW | 4.99 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965811 | AG1-449 | 80/20 | 38.28 MW | 38.28 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966361 | AG1-505 C | 80/20 | 27.11 MW | 27.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966371 | AG1-506 C | 80/20 | 27.11 MW | 27.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966621 | AG1-532 C | Adder | 2.05 MW | 1.74 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 313506 | AB1-173 C OP | Adder | 10.07 MW | 8.56 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314572 | 3EMPORIA | Adder | 0.63 MW | 0.54 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315131 | 1EDGECMA | Adder | 11.27 MW | 9.58 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315132 | 1EDGECMB | Adder | 11.27 MW | 9.58 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926070 | AC1-086 C | Adder | 30.8 MW | 26.18 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926201 | AC1-098 C | Adder | 9.0 MW | 7.65 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926211 | AC1-099 C | Adder | 3.02 MW | 2.56 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927024 | AC1-189 C | Adder | 12.38 MW | 10.52 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927145 | AC1-208 C | Adder | 13.16 MW | 11.18 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934331 | AD1-057 C O1 | Adder | 14.28 MW | 12.14 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934521 | AD1-076 C | Adder | 82.43 MW | 70.07 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934615 | AD1-087 C | Adder | 11.4 MW | 9.69 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934625 | AD1-088 C | Adder | 17.23 MW | 14.65 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935171 | AD1-152 C O1 | Adder | 11.76 MW | 9.99 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 937481 | AD2-202 C O1 | Adder | 3.34 MW | 2.84 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942931 | AE2-313 C | 80/20 | 59.03 MW | 59.03 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943171 | AE2-346 C | Adder | 2.11 MW | 1.79 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944011 | AF1-069 C | 80/20 | 21.4 MW | 21.4 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944141 | AF1-082 | Adder | 4.06 MW | 3.45 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 945811 | AF1-246 C O1 | 80/20 | 11.6 MW | 11.6 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960081 | AF2-299 C | Adder | 3.79 MW | 3.22 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315293 | 1DOMTR9 | Adder | 10.28 MW | 8.74 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315294 | 1DOMTR10 | Adder | 12.6 MW | 10.71 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316129 | AC1-054 C | Adder | 10.34 MW | 8.79 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316140 | AB2-099 C | Adder | 0.88 MW | 0.75 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923262 | AB1-132 C OP | Adder | 20.91 MW | 17.78 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923991 | AB2-040 C O1 | Adder | 10.97 MW | 9.33 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925591 | AC1-034 C | Adder | 9.64 MW | 8.2 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932631 | AC2-084 C | Adder | 12.83 MW | 10.91 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940491 | AE2-034 C | Adder | 10.97 MW | 9.32 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940571 | AE2-044 C | Adder | 6.31 MW | 5.37 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941031 | AE2-094 C | 80/20 | 65.5 MW | 65.5 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941791 | AE2-182 C | Adder | 2.8 MW | 2.38 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946281 | AF1-292 C | Adder | 2.25 MW | 1.91 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957481 | AF2-042 C | 80/20 | 82.88 MW | 82.88 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957521 | AF2-046 C | Adder | 25.27 MW | 21.48 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957531 | AF2-047 C | Adder | 26.07 MW | 22.16 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957861 | AF2-080 C | Adder | 11.24 MW | 9.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938771 | AE1-103 C | Adder | 4.46 MW | 3.79 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940481 | AE2-033 C | 80/20 | 24.36 MW | 24.36 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940641 | AE2-051 C O1 | 80/20 | 28.75 MW | 28.75 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946011 | AF1-266 | 80/20 | 20.39 MW | 20.39 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933501 | AC2-165 C | Adder | 14.15 MW | 12.03 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 313526 | AB2-022 C | 80/20 | 0.61 MW | 0.61 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314435 | 6SAPONY | 80/20 | 0.65 MW | 0.65 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314491 | 3PENDLTN | 80/20 | 0.53 MW | 0.53 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314507 | 3THOMPSN | 80/20 | 0.53 MW | 0.53 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314638 | 6ELIZ CT | 80/20 | 0.35 MW | 0.35 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314639 | 6TANGLEW | 80/20 | 0.65 MW | 0.65 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314643 | 3O INLET | 80/20 | 0.71 MW | 0.71 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315060 | 1CHESTF5 | Adder | 84.08 MW | 71.47 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315065 | 1CHESTF6 | Adder | 144.13 MW | 122.51 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315083 | 1SPRUNCA | Adder | 15.45 MW | 13.13 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315084 | 1SPRUNCB | Adder | 15.45 MW | 13.13 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926661 | AC1-147 C | 80/20 | 0.6 MW | 0.6 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926754 | AC1-161 C | 80/20 | 47.63 MW | 47.63 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926784 | AC1-164 C | Adder | 50.3 MW | 42.76 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934014 | AD1-025 C | Adder | 24.39 MW | 20.73 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934061 | AD1-033 C | 80/20 | 11.71 MW | 11.71 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934575 | AD1-082 C | 80/20 | 11.62 MW | 11.62 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935111 | AD1-144 C | 80/20 | 0.45 MW | 0.45 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935164 | AD1-151 C | Adder | 23.14 MW | 19.67 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936661 | AD2-085 C | 80/20 | 5.27 MW | 5.27 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936761 | AD2-097 C | Adder | 2.93 MW | 2.49 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 937221 | AD2-160 C O1 | 80/20 | 9.11 MW | 9.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942151 | AE2-227 C | Adder | 2.91 MW | 2.47 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942161 | AE2-228 C | Adder | 3.06 MW | 2.6 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942341 | AE2-247 C | 80/20 | 2.28 MW | 2.28 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942371 | AE2-250 C O1 | Adder | 14.04 MW | 11.94 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942401 | AE2-253 C | 80/20 | 9.58 MW | 9.58 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942551 | AE2-270 | Adder | 38.74 MW | 32.93 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943461 | AF1-017 C | 80/20 | 2.06 MW | 2.06 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943611 | AF1-032 C | 80/20 | 2.7 MW | 2.7 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943621 | AF1-033 C | Adder | 3.48 MW | 2.96 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944631 | AF1-128 O1 | Adder | 52.61 MW | 44.72 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944871 | AF1-152 C | 80/20 | 8.16 MW | 8.16 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 945361 | AF1-201 C O1 | Adder | 21.89 MW | 18.61 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958501 | AF2-144 C | Adder | 2.7 MW | 2.3 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961711 | AG1-011 | Adder | 41.43 MW | 35.21 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315098 | 1CHESPKA | 80/20 | 0.71 MW | 0.71 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315099 | 1CHESPKB | 80/20 | 1.17 MW | 1.17 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315102 | 1BRUNSWICKG1 | 80/20 | 14.04 MW | 14.04 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315103 | 1BRUNSWICKG2 | 80/20 | 14.04 MW | 14.04 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315104 | 1BRUNSWICKG3 | 80/20 | 14.04 MW | 14.04 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315105 | 1BRUNSWICKS1 | 80/20 | 29.17 MW | 29.17 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315108 | 1ELIZAR1 | 80/20 | 5.19 MW | 5.19 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315109 | 1ELIZAR2 | 80/20 | 5.11 MW | 5.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315110 | 1ELIZAR3 | 80/20 | 5.26 MW | 5.26 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315233 | 1SURRY 2 | 80/20 | 38.85 MW | 38.85 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315241 | 1Z1-086 GT1 | 80/20 | 18.05 MW | 18.05 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315242 | 1Z1-086 GT2 | 80/20 | 18.05 MW | 18.05 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315243 | 1Z1-086 GT3 | 80/20 | 18.05 MW | 18.05 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315244 | 1Z1-086 ST | 80/20 | 31.37 MW | 31.37 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315260 | 1GOSPORTA | 80/20 | 0.56 MW | 0.56 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315261 | 1GOSPORTB | 80/20 | 0.72 MW | 0.72 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315262 | 1GOSPORTC | 80/20 | 0.61 MW | 0.61 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315603 | 6AA1-139SOLA | 80/20 | 3.71 MW | 3.71 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315605 | 6W1-029WIND | 80/20 | 1.81 MW | 1.81 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315611 | 6Z1-036WIND | 80/20 | 1.12 MW | 1.12 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316108 | AB2-160 C | Adder | 7.91 MW | 6.72 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316132 | AB2-190 C | Adder | 27.03 MW | 22.98 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316258 | AE1-162 C | 80/20 | 0.55 MW | 0.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932044 | AC2-012 C | 80/20 | 12.48 MW | 12.48 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932591 | AC2-079 C O1 | 80/20 | 8.74 MW | 8.74 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938535 | AE1-072 C | 80/20 | 27.27 MW | 27.27 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938551 | AE1-074 C | 80/20 | 0.66 MW | 0.66 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939195 | AE1-149 C | 80/20 | 16.04 MW | 16.04 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939414 | AE1-173_C1 | 80/20 | 51.97 MW | 51.97 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939415 | AE1-173_C2 | 80/20 | 44.54 MW | 44.54 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939416 | AE1-173_C3 | 80/20 | 51.97 MW | 51.97 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939431 | AE1-175 C | Adder | 3.28 MW | 2.79 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940431 | AE2-027 C O1 | Adder | 18.18 MW | 15.45 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940541 | AE2-040 | 80/20 | 4.33 MW | 4.33 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940651 | AE2-052 | 80/20 | 5.35 MW | 5.35 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941101 | AE2-104 C O1 | 80/20 | 5.17 MW | 5.17 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941281 | AE2-122 C O1 | 80/20 | 44.26 MW | 44.26 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941291 | AE2-123 C O1 | 80/20 | 45.49 MW | 45.49 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941301 | AE2-124 C O1 | 80/20 | 41.37 MW | 41.37 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946261 | AF1-291 C | Adder | 3.06 MW | 2.6 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957491 | AF2-043 C | 80/20 | 3.31 MW | 3.31 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957631 | AF2-057 | 80/20 | 5.57 MW | 5.57 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957711 | AF2-065 C | Adder | 19.76 MW | 16.79 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962531 | AG1-102 C | Adder | 1.46 MW | 1.24 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962961 | AG1-145 C | Adder | 2.96 MW | 2.52 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963221 | AG1-171 C | Adder | 3.11 MW | 2.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963231 | AG1-172 C | Adder | 3.11 MW | 2.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963241 | AG1-173 C | Adder | 3.11 MW | 2.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963251 | AG1-174 C | Adder | 3.11 MW | 2.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 964951 | AG1-359 O1 | 80/20 | 35.55 MW | 35.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965001 | AG1-364 C O1 | 80/20 | 11.14 MW | 11.14 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933294 | AC2-141 C | 80/20 | 47.63 MW | 47.63 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941501 | AE2-147 C | 80/20 | 24.48 MW | 24.48 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941591 | AE2-156 O1 | 80/20 | 27.85 MW | 27.85 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942001 | AE2-212 C | Adder | 3.14 MW | 2.67 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957831 | AF2-077 C | Adder | 2.84 MW | 2.41 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957871 | AF2-081 C | 80/20 | 15.52 MW | 15.52 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957911 | AF2-085 | 80/20 | 6.61 MW | 6.61 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958161 | AF2-110 C | 80/20 | 2.13 MW | 2.13 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966611 | AG1-531 C | Adder | 8.46 MW | 7.19 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944581 | AF1-123 C O1 | 80/20 | 75.16 MW | 75.16 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944591 | AF1-124 C O1 | 80/20 | 75.16 MW | 75.16 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944601 | AF1-125 C O1 | 80/20 | 75.16 MW | 75.16 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933981 | AD1-022 C | Adder | 13.25 MW | 11.26 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960331 | AF2-324 C | Adder | 11.0 MW | 9.35 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961681 | AG1-008 C | Adder | 25.32 MW | 21.53 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962271 | AG1-075 C O1 | Adder | 24.24 MW | 20.6 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962571 | AG1-106 C | Adder | 8.56 MW | 7.28 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965281 | AG1-393 C | 80/20 | 3.31 MW | 3.31 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316083 | AB2-161 C | 80/20 | 5.1 MW | 5.1 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961611 | AG1-000B C | Adder | 23.45 MW | 19.94 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.27 MW | 8.27 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.78 MW | 2.78 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 153.85 MW | 153.85 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 57.72 MW | 57.72 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 59.09 MW | 59.09 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.52 MW | 12.52 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.66 MW | 13.66 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.74 MW | 0.74 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.92 MW | 2.92 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.22 MW | 8.22 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.16 MW | 3.16 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.51 MW | 0.51 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 11.07 MW | 11.07 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.39 MW | 1.39 MW |
Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 961671 | AG1-007 C | 80/20 | 0.37 MW | 0.37 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 961941 | AG1-037 C | 80/20 | 0.17 MW | 0.17 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 962331 | AG1-082 C | 80/20 | 0.66 MW | 0.66 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 962341 | AG1-083 C | 80/20 | 0.66 MW | 0.66 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 963041 | AG1-153 C | 80/20 | 1.71 MW | 1.71 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 963111 | AG1-160 C | 80/20 | 1.73 MW | 1.73 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 963291 | AG1-178 C O2 | 80/20 | 17.29 MW | 17.29 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 963301 | AG1-179 C | 80/20 | 3.8 MW | 3.8 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 963321 | AG1-181 C O1 | 80/20 | 5.37 MW | 5.37 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 963351 | AG1-184 O2 | 80/20 | 9.32 MW | 9.32 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 963361 | AG1-185 O1 | 80/20 | 2.6 MW | 2.6 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 964111 | AG1-272 C | 80/20 | 0.8 MW | 0.8 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 964121 | AG1-273 C | 80/20 | 0.8 MW | 0.8 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 964131 | AG1-274 C | 80/20 | 0.8 MW | 0.8 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 964241 | AG1-285 C O1 | 80/20 | 4.44 MW | 4.44 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 964791 | AG1-342 C | 80/20 | 1.32 MW | 1.32 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 966801 | AG1-551 C | 80/20 | 0.71 MW | 0.71 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 966811 | AG1-552 C | 80/20 | 1.13 MW | 1.13 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 965191 | AG1-384 C | 80/20 | 0.8 MW | 0.8 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 965591 | AG1-427 C | 80/20 | 4.2 MW | 4.2 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 965601 | AG1-428 C O2 | 80/20 | 3.17 MW | 3.17 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 965711 | AG1-439 C O1 | 80/20 | 9.08 MW | 9.08 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 965721 | AG1-440 C | 80/20 | 3.09 MW | 3.09 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 965731 | AG1-441 C | 80/20 | 3.09 MW | 3.09 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 965761 | AG1-444 O1 | 80/20 | 4.84 MW | 4.84 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 965771 | AG1-445 | 80/20 | 1.79 MW | 1.79 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 965781 | AG1-446 | 80/20 | 1.79 MW | 1.79 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 965811 | AG1-449 | 80/20 | 7.11 MW | 7.11 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 966361 | AG1-505 C | 80/20 | 5.03 MW | 5.03 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 966371 | AG1-506 C | 80/20 | 5.03 MW | 5.03 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 966621 | AG1-532 C | 80/20 | 1.16 MW | 1.16 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 313506 | AB1-173 C OP | 80/20 | 4.85 MW | 4.85 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 313719 | 3CHESTNUT | 80/20 | 0.54 MW | 0.54 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 314572 | 3EMPORIA | 80/20 | 0.34 MW | 0.34 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 314582 | 3KELFORD | 80/20 | 0.14 MW | 0.14 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 314623 | 3WITAKRS | 80/20 | 0.1 MW | 0.1 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315126 | 1ROARAP2 | 80/20 | 0.77 MW | 0.77 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315128 | 1ROARAP4 | 80/20 | 0.74 MW | 0.74 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315131 | 1EDGECMA | 80/20 | 3.38 MW | 3.38 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315132 | 1EDGECMB | 80/20 | 3.38 MW | 3.38 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315136 | 1ROSEMG1 | 80/20 | 1.4 MW | 1.4 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315137 | 1ROSEMS1 | 80/20 | 0.87 MW | 0.87 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315138 | 1ROSEMG2 | 80/20 | 0.66 MW | 0.66 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315139 | 1GASTONA | 80/20 | 2.12 MW | 2.12 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315158 | 1KERR 1 | 80/20 | 0.17 MW | 0.17 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315159 | 1KERR 2 | 80/20 | 0.46 MW | 0.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315160 | 1KERR 3 | 80/20 | 0.46 MW | 0.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315161 | 1KERR 4 | 80/20 | 0.46 MW | 0.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315162 | 1KERR 5 | 80/20 | 0.46 MW | 0.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 920591 | AA2-165 C | 80/20 | 0.07 MW | 0.07 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 926070 | AC1-086 C | 80/20 | 13.99 MW | 13.99 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 926201 | AC1-098 C | 80/20 | 2.62 MW | 2.62 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 926211 | AC1-099 C | 80/20 | 0.88 MW | 0.88 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 927024 | AC1-189 C | 80/20 | 3.11 MW | 3.11 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 927145 | AC1-208 C | 80/20 | 4.15 MW | 4.15 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 934331 | AD1-057 C O1 | 80/20 | 5.31 MW | 5.31 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 936265 | AD2-033 C | 80/20 | 4.18 MW | 4.18 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 942931 | AE2-313 C | 80/20 | 10.97 MW | 10.97 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 943171 | AE2-346 C | 80/20 | 0.46 MW | 0.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 944011 | AF1-069 C | 80/20 | 3.98 MW | 3.98 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 944141 | AF1-082 | 80/20 | 1.21 MW | 1.21 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 945811 | AF1-246 C O1 | 80/20 | 2.12 MW | 2.12 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 959311 | AF2-222 C | 80/20 | 5.03 MW | 5.03 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 960081 | AF2-299 C | 80/20 | 2.16 MW | 2.16 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315163 | 1KERR 6 | 80/20 | 0.46 MW | 0.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315164 | 1KERR 7 | 80/20 | 0.46 MW | 0.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315601 | 1CONETOE2SOL | 80/20 | 0.55 MW | 0.55 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315606 | 3AA2-053SOLA | 80/20 | 0.78 MW | 0.78 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 316020 | AB2-059 C OP | 80/20 | 0.75 MW | 0.75 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 316129 | AC1-054 C | 80/20 | 3.38 MW | 3.38 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 316131 | AB2-060 C | 80/20 | 0.57 MW | 0.57 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 316140 | AB2-099 C | 80/20 | 0.19 MW | 0.19 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 922922 | AB1-081 C OP | 80/20 | 0.64 MW | 0.64 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 923262 | AB1-132 C OP | 80/20 | 9.5 MW | 9.5 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 923991 | AB2-040 C O1 | 80/20 | 5.29 MW | 5.29 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 924301 | AB2-077 C O1 | 80/20 | 0.74 MW | 0.74 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 924311 | AB2-078 C O1 | 80/20 | 0.74 MW | 0.74 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 924321 | AB2-079 C O1 | 80/20 | 0.74 MW | 0.74 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 925591 | AC1-034 C | 80/20 | 2.87 MW | 2.87 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 925611 | AC1-036 C | 80/20 | 0.08 MW | 0.08 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 932631 | AC2-084 C | 80/20 | 3.74 MW | 3.74 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 939181 | AE1-148 C | 80/20 | 3.46 MW | 3.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 940571 | AE2-044 C | 80/20 | 1.88 MW | 1.88 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 940661 | AE2-053 O1 | 80/20 | 1.28 MW | 1.28 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 941031 | AE2-094 C | 80/20 | 12.19 MW | 12.19 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 946281 | AF1-292 C | 80/20 | 1.28 MW | 1.28 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 957481 | AF2-042 C | 80/20 | 15.18 MW | 15.18 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 957521 | AF2-046 C | 80/20 | 4.99 MW | 4.99 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 957861 | AF2-080 C | 80/20 | 2.82 MW | 2.82 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 940481 | AE2-033 C | 80/20 | 20.92 MW | 20.92 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 940641 | AE2-051 C O1 | 80/20 | 4.73 MW | 4.73 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 946011 | AF1-266 | 80/20 | 17.51 MW | 17.51 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 314435 | 6SAPONY | 80/20 | 0.57 MW | 0.57 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 934575 | AD1-082 C | Adder | -10.61 MW | -9.02 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 936761 | AD2-097 C | Adder | -0.98 MW | -0.83 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315102 | 1BRUNSWICKG1 | 80/20 | 2.63 MW | 2.63 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.63 MW | 2.63 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.63 MW | 2.63 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.46 MW | 5.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315141 | 1GASTONB | 80/20 | 2.12 MW | 2.12 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315241 | 1Z1-086 GT1 | 80/20 | 3.37 MW | 3.37 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315242 | 1Z1-086 GT2 | 80/20 | 3.37 MW | 3.37 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315243 | 1Z1-086 GT3 | 80/20 | 3.37 MW | 3.37 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315244 | 1Z1-086 ST | 80/20 | 5.86 MW | 5.86 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315607 | 3AA1-063SOLA | 80/20 | 0.63 MW | 0.63 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 316087 | AB2-174 C | 80/20 | 0.9 MW | 0.9 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 316096 | AB2-100 C1 | 80/20 | 1.0 MW | 1.0 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 316098 | AB2-100 C2 | 80/20 | 1.0 MW | 1.0 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 316132 | AB2-190 C | Adder | -8.94 MW | -7.6 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 938221 | AE1-035 C | 80/20 | 0.12 MW | 0.12 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 940541 | AE2-040 | 80/20 | 3.83 MW | 3.83 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 960331 | AF2-324 C | 80/20 | 3.3 MW | 3.3 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 962561 | AG1-105 C O1 | 80/20 | 2.92 MW | 2.92 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 961681 | AG1-008 C | 80/20 | 5.0 MW | 5.0 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 962571 | AG1-106 C | 80/20 | 3.89 MW | 3.89 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 965281 | AG1-393 C | 80/20 | 2.93 MW | 2.93 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 315602 | 1HOLLOMANSOL | 80/20 | 0.48 MW | 0.48 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 313527 | AB2-043 C | 80/20 | 0.2 MW | 0.2 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | 316083 | AB2-161 C | Adder | -4.66 MW | -3.96 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.52 MW | 0.52 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 31.54 MW | 31.54 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.73 MW | 10.73 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.11 MW | 11.11 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.68 MW | 2.68 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.6 MW | 2.6 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.52 MW | 0.52 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.52 MW | 1.52 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.09 MW | 2.09 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | Adder | 1.18 MW | 1.0 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | Adder | 0.7 MW | 0.6 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | Adder | 2.81 MW | 2.39 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | Adder | 2.81 MW | 2.39 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | Adder | 7.41 MW | 6.3 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | Adder | 7.52 MW | 6.39 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 90.06 MW | 90.06 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | Adder | 6.26 MW | 5.32 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | Adder | 3.05 MW | 2.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 48.52 MW | 48.52 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | Adder | 8.32 MW | 7.07 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | Adder | 3.05 MW | 2.6 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | Adder | 2.63 MW | 2.23 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | Adder | 2.86 MW | 2.43 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | Adder | 5.22 MW | 4.44 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | Adder | 14.84 MW | 12.61 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | Adder | 14.84 MW | 12.61 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | Adder | 29.88 MW | 25.4 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | Adder | 8.65 MW | 7.36 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | Adder | 8.65 MW | 7.36 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | Adder | 15.93 MW | 13.54 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | Adder | 31.19 MW | 26.51 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | Adder | 21.79 MW | 18.52 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | Adder | 21.79 MW | 18.52 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | Adder | 1.64 MW | 1.4 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | Adder | 8.3 MW | 7.05 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | Adder | 0.51 MW | 0.43 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | Adder | 9.41 MW | 8.0 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | Adder | 9.41 MW | 8.0 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | Adder | 26.1 MW | 22.18 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | Adder | 7.87 MW | 6.69 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | Adder | 2.64 MW | 2.24 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | Adder | 10.83 MW | 9.21 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | Adder | 11.28 MW | 9.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | Adder | 12.0 MW | 10.2 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | Adder | 81.5 MW | 69.28 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934615 | AD1-087 C | Adder | 8.57 MW | 7.29 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935171 | AD1-152 C O1 | Adder | 8.79 MW | 7.47 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937481 | AD2-202 C O1 | Adder | 2.51 MW | 2.13 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | Adder | 48.08 MW | 40.87 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | Adder | 1.97 MW | 1.67 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | Adder | 17.5 MW | 14.88 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | Adder | 3.39 MW | 2.88 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | Adder | 8.97 MW | 7.63 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | Adder | 3.05 MW | 2.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 9.97 MW | 8.47 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 12.21 MW | 10.38 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | Adder | 8.28 MW | 7.04 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | Adder | 0.82 MW | 0.7 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | Adder | 17.72 MW | 15.06 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | Adder | 9.04 MW | 7.68 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | Adder | 8.04 MW | 6.84 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | Adder | 11.21 MW | 9.53 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | Adder | 11.1 MW | 9.43 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | Adder | 5.27 MW | 4.48 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | Adder | 53.57 MW | 45.54 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | Adder | 1.81 MW | 1.54 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | Adder | 64.1 MW | 54.48 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | Adder | 23.55 MW | 20.02 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | Adder | 26.37 MW | 22.42 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | Adder | 9.84 MW | 8.36 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C | Adder | 4.43 MW | 3.77 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | Adder | 18.91 MW | 16.08 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 25.41 MW | 25.41 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | Adder | 15.83 MW | 13.46 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313526 | AB2-022 C | 80/20 | 0.66 MW | 0.66 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314295 | 6BIRDNECK | 80/20 | 0.08 MW | 0.08 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314421 | 6WINCHST | 80/20 | 0.24 MW | 0.24 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314491 | 3PENDLTN | 80/20 | 0.59 MW | 0.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314507 | 3THOMPSN | 80/20 | 0.59 MW | 0.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314638 | 6ELIZ CT | 80/20 | 0.38 MW | 0.38 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314639 | 6TANGLEW | 80/20 | 0.7 MW | 0.7 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314643 | 3O INLET | 80/20 | 0.77 MW | 0.77 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315060 | 1CHESTF5 | Adder | 70.2 MW | 59.67 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315092 | 1YORKTN3 | 80/20 | 42.37 MW | 42.37 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925863 | AC1-065 C | Adder | 8.8 MW | 7.48 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926661 | AC1-147 C | 80/20 | 0.66 MW | 0.66 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926754 | AC1-161 C | 80/20 | 56.87 MW | 56.87 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926784 | AC1-164 C | Adder | 59.74 MW | 50.78 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934014 | AD1-025 C | Adder | 22.48 MW | 19.11 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934061 | AD1-033 C | 80/20 | 12.97 MW | 12.97 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934141 | AD1-041 C | Adder | 7.64 MW | 6.5 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | Adder | 9.64 MW | 8.19 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935111 | AD1-144 C | 80/20 | 0.49 MW | 0.49 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935164 | AD1-151 C | Adder | 20.59 MW | 17.5 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936591 | AD2-074 C | Adder | 7.03 MW | 5.98 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | Adder | 5.14 MW | 4.37 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937221 | AD2-160 C O1 | 80/20 | 10.02 MW | 10.02 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | Adder | 2.22 MW | 1.89 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942371 | AE2-250 C O1 | Adder | 9.7 MW | 8.24 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942401 | AE2-253 C | 80/20 | 10.54 MW | 10.54 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942551 | AE2-270 | Adder | 35.23 MW | 29.95 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943431 | AF1-014 C | Adder | 1.82 MW | 1.55 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | Adder | 2.01 MW | 1.71 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943471 | AF1-018 | Adder | 10.44 MW | 8.88 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943611 | AF1-032 C | 80/20 | 2.92 MW | 2.92 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943621 | AF1-033 C | 80/20 | 3.67 MW | 3.67 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943741 | AF1-042 C | Adder | 3.68 MW | 3.13 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944631 | AF1-128 O1 | Adder | 43.93 MW | 37.34 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944871 | AF1-152 C | 80/20 | 8.71 MW | 8.71 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945361 | AF1-201 C O1 | 80/20 | 26.72 MW | 26.72 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961711 | AG1-011 | Adder | 38.18 MW | 32.45 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961951 | AG1-038 C | Adder | 4.07 MW | 3.46 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966661 | AG1-536 C | Adder | 6.69 MW | 5.69 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315098 | 1CHESPKA | 80/20 | 0.78 MW | 0.78 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315099 | 1CHESPKB | 80/20 | 1.29 MW | 1.29 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315108 | 1ELIZAR1 | 80/20 | 5.75 MW | 5.75 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315109 | 1ELIZAR2 | 80/20 | 5.65 MW | 5.65 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315110 | 1ELIZAR3 | 80/20 | 5.83 MW | 5.83 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315116 | 1SURRY 1 | 80/20 | 39.11 MW | 39.11 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315120 | 1GRAVEL4 | 80/20 | 4.02 MW | 4.02 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315122 | 1GRAVEL6 | 80/20 | 4.02 MW | 4.02 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315233 | 1SURRY 2 | 80/20 | 52.52 MW | 52.52 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315260 | 1GOSPORTA | 80/20 | 0.62 MW | 0.62 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315261 | 1GOSPORTB | 80/20 | 0.8 MW | 0.8 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315262 | 1GOSPORTC | 80/20 | 0.68 MW | 0.68 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315603 | 6AA1-139SOLA | 80/20 | 4.08 MW | 4.08 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315605 | 6W1-029WIND | 80/20 | 1.93 MW | 1.93 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315611 | 6Z1-036WIND | 80/20 | 1.17 MW | 1.17 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316108 | AB2-160 C | Adder | 5.46 MW | 4.64 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316132 | AB2-190 C | Adder | 24.18 MW | 20.55 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316258 | AE1-162 C | 80/20 | 0.58 MW | 0.58 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932044 | AC2-012 C | 80/20 | 13.79 MW | 13.79 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | Adder | 8.11 MW | 6.89 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938535 | AE1-072 C | 80/20 | 29.87 MW | 29.87 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939195 | AE1-149 C | Adder | 12.63 MW | 10.74 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939245 | AE1-155 C | Adder | 15.94 MW | 13.55 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 48.59 MW | 48.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 41.65 MW | 41.65 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 48.59 MW | 48.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939431 | AE1-175 C | 80/20 | 4.07 MW | 4.07 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939611 | AE1-191 C | Adder | 15.29 MW | 12.99 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940231 | AE2-005 C | Adder | 1.92 MW | 1.64 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | Adder | 3.34 MW | 2.84 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940551 | AE2-041 | Adder | 10.44 MW | 8.88 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | Adder | 4.21 MW | 3.58 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | 80/20 | 5.37 MW | 5.37 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941281 | AE2-122 C O1 | 80/20 | 48.96 MW | 48.96 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941291 | AE2-123 C O1 | 80/20 | 50.31 MW | 50.31 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941301 | AE2-124 C O1 | 80/20 | 45.76 MW | 45.76 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957491 | AF2-043 C | 80/20 | 3.58 MW | 3.58 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957601 | AF2-054 C | Adder | 3.07 MW | 2.61 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957631 | AF2-057 | 80/20 | 6.15 MW | 6.15 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957711 | AF2-065 C | Adder | 17.97 MW | 15.27 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962531 | AG1-102 C | 80/20 | 1.77 MW | 1.77 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962861 | AG1-135 C | Adder | 7.63 MW | 6.48 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962961 | AG1-145 C | 80/20 | 3.67 MW | 3.67 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962971 | AG1-146 C | Adder | 4.09 MW | 3.47 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962981 | AG1-147 C | Adder | 9.54 MW | 8.11 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963221 | AG1-171 C | Adder | 2.86 MW | 2.43 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963231 | AG1-172 C | Adder | 2.86 MW | 2.43 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963241 | AG1-173 C | Adder | 2.86 MW | 2.43 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963251 | AG1-174 C | Adder | 2.86 MW | 2.43 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963611 | AG1-210 C | Adder | 0.76 MW | 0.64 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964211 | AG1-282 C | Adder | 2.39 MW | 2.03 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964951 | AG1-359 O1 | 80/20 | 39.38 MW | 39.38 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965001 | AG1-364 C O1 | 80/20 | 12.32 MW | 12.32 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933294 | AC2-141 C | 80/20 | 56.87 MW | 56.87 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941501 | AE2-147 C | 80/20 | 26.14 MW | 26.14 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941591 | AE2-156 O1 | 80/20 | 30.81 MW | 30.81 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957831 | AF2-077 C | 80/20 | 3.45 MW | 3.45 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957871 | AF2-081 C | 80/20 | 17.04 MW | 17.04 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | 80/20 | 2.21 MW | 2.21 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958261 | AF2-120 C | Adder | 7.78 MW | 6.62 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966611 | AG1-531 C | 80/20 | 9.46 MW | 9.46 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944581 | AF1-123 C O1 | 80/20 | 84.22 MW | 84.22 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944591 | AF1-124 C O1 | 80/20 | 84.22 MW | 84.22 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944601 | AF1-125 C O1 | 80/20 | 84.22 MW | 84.22 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | Adder | 12.97 MW | 11.02 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | Adder | 9.18 MW | 7.8 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | Adder | 23.6 MW | 20.06 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962271 | AG1-075 C O1 | Adder | 16.74 MW | 14.23 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | Adder | 7.26 MW | 6.17 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | Adder | 2.55 MW | 2.17 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | Adder | 4.23 MW | 3.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961611 | AG1-000B C | Adder | 23.54 MW | 20.0 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 6.21 MW | 6.21 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.51 MW | 1.51 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 108.3 MW | 108.3 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 22.8 MW | 22.8 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 31.12 MW | 31.12 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 9.41 MW | 9.41 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.76 MW | 7.76 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.53 MW | 0.53 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.18 MW | 1.18 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.78 MW | 3.78 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.8 MW | 1.8 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.22 MW | 0.22 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.24 MW | 6.24 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.57 MW | 0.57 MW |
Details for AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 961791 | AG1-021 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 961891 | AG1-030 C | 80/20 | 15.36 MW | 15.36 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 962491 | AG1-098 C O1 | 80/20 | 23.12 MW | 23.12 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 963041 | AG1-153 C | 80/20 | 17.62 MW | 17.62 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 963111 | AG1-160 C | 80/20 | 17.62 MW | 17.62 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 963171 | AG1-166 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 963181 | AG1-167 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 963191 | AG1-168 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 963201 | AG1-169 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 963211 | AG1-170 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 963321 | AG1-181 C O1 | 80/20 | 17.07 MW | 17.07 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 963361 | AG1-185 O1 | 80/20 | 8.26 MW | 8.26 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 964111 | AG1-272 C | 80/20 | 2.61 MW | 2.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 964121 | AG1-273 C | 80/20 | 2.61 MW | 2.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 964131 | AG1-274 C | 80/20 | 2.61 MW | 2.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 964241 | AG1-285 C O1 | 80/20 | 12.55 MW | 12.55 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 964791 | AG1-342 C | 80/20 | 6.0 MW | 6.0 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 966691 | AG1-539 C | 80/20 | 6.13 MW | 6.13 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 966761 | AG1-547 C | 80/20 | 4.06 MW | 4.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 965191 | AG1-384 C | 80/20 | 2.61 MW | 2.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 965591 | AG1-427 C | 80/20 | 11.9 MW | 11.9 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 965641 | AG1-432 C O1 | 80/20 | 20.93 MW | 20.93 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 965721 | AG1-440 C | 80/20 | 5.69 MW | 5.69 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 965731 | AG1-441 C | 80/20 | 5.69 MW | 5.69 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 965771 | AG1-445 | 80/20 | 3.29 MW | 3.29 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 965781 | AG1-446 | 80/20 | 3.29 MW | 3.29 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 965811 | AG1-449 | 80/20 | 80.93 MW | 80.93 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 965831 | AG1-451 | 80/20 | 3.49 MW | 3.49 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 966361 | AG1-505 C | 80/20 | 54.28 MW | 54.28 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 966371 | AG1-506 C | 80/20 | 54.28 MW | 54.28 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 246844 | 05SMG2 | 80/20 | 3.59 MW | 3.59 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 247284 | 05LEESVG | 80/20 | 0.99 MW | 0.99 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 314429 | 3JTRSVLE | 80/20 | 0.47 MW | 0.47 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315153 | 1CLOVER1 | 80/20 | 33.93 MW | 33.93 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315154 | 1CLOVER2 | 80/20 | 33.61 MW | 33.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315156 | 1HALLBR1 | 80/20 | 1.2 MW | 1.2 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315158 | 1KERR 1 | 80/20 | 0.38 MW | 0.38 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315159 | 1KERR 2 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315160 | 1KERR 3 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315161 | 1KERR 4 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315162 | 1KERR 5 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 926023 | AC1-080 C | 80/20 | 0.47 MW | 0.47 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 926051 | AC1-083 C O1 | 80/20 | 5.12 MW | 5.12 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 926645 | AC1-145 C | 80/20 | 0.4 MW | 0.4 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 927251 | AC1-221 C | 80/20 | 3.96 MW | 3.96 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 927261 | AC1-222 C | 80/20 | 6.24 MW | 6.24 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 933941 | AD1-017 C | 80/20 | 1.02 MW | 1.02 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 934311 | AD1-055 C | 80/20 | 4.33 MW | 4.33 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 934341 | AD1-058 C | 80/20 | 9.94 MW | 9.94 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 934615 | AD1-087 C | 80/20 | 19.68 MW | 19.68 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 934625 | AD1-088 C | 80/20 | 25.52 MW | 25.52 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 934991 | AD1-131 C | 80/20 | 3.26 MW | 3.26 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 935171 | AD1-152 C O1 | 80/20 | 19.14 MW | 19.14 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 936161 | AD2-022 C O1 | 80/20 | 13.16 MW | 13.16 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 936171 | AD2-023 C O1 | 80/20 | 7.68 MW | 7.68 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 936265 | AD2-033 C | 80/20 | 13.16 MW | 13.16 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 937481 | AD2-202 C O1 | 80/20 | 5.76 MW | 5.76 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 942461 | AE2-259 C O1 | 80/20 | 10.46 MW | 10.46 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 942671 | AE2-283 C | 80/20 | 4.94 MW | 4.94 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 942751 | AE2-291 C | 80/20 | 11.73 MW | 11.73 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 942761 | AE2-292 C O1 | 80/20 | 14.61 MW | 14.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 942931 | AE2-313 C | 80/20 | 124.49 MW | 124.49 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 943811 | AF1-049 C | 80/20 | 9.46 MW | 9.46 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 943901 | AF1-058 C | 80/20 | 3.46 MW | 3.46 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 944011 | AF1-069 C | 80/20 | 39.76 MW | 39.76 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 945811 | AF1-246 C O1 | 80/20 | 21.36 MW | 21.36 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 958801 | AF2-171 C | 80/20 | 15.43 MW | 15.43 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 959311 | AF2-222 C | 80/20 | 16.95 MW | 16.95 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 960061 | AF2-297 C | 80/20 | 13.84 MW | 13.84 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 961121 | AF2-403 | 80/20 | 1.0 MW | 1.0 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315163 | 1KERR 6 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315164 | 1KERR 7 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315266 | 1PLYWOOD A | 80/20 | 2.05 MW | 2.05 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 316118 | AC1-105 C | 80/20 | 9.08 MW | 9.08 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 316131 | AB2-060 C | 80/20 | 1.55 MW | 1.55 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 924301 | AB2-077 C O1 | 80/20 | 2.03 MW | 2.03 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 924311 | AB2-078 C O1 | 80/20 | 2.03 MW | 2.03 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 924321 | AB2-079 C O1 | 80/20 | 2.03 MW | 2.03 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 925611 | AC1-036 C | 80/20 | 0.25 MW | 0.25 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 925661 | AC1-042 C | 80/20 | 1.99 MW | 1.99 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 932761 | AC2-100 C | 80/20 | 9.12 MW | 9.12 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 938371 | AE1-056 C | 80/20 | 6.68 MW | 6.68 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 939181 | AE1-148 C | 80/20 | 8.21 MW | 8.21 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 940081 | AE1-250 C | 80/20 | 13.82 MW | 13.82 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 940661 | AE2-053 O1 | 80/20 | 3.04 MW | 3.04 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 941031 | AE2-094 C | 80/20 | 121.7 MW | 121.7 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 941431 | AE2-140 C O1 | 80/20 | 14.45 MW | 14.45 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 941791 | AE2-182 C | 80/20 | 4.15 MW | 4.15 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 941801 | AE2-185 C | 80/20 | 4.49 MW | 4.49 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 941821 | AE2-187 C | 80/20 | 4.49 MW | 4.49 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 946301 | AF1-294 C | 80/20 | 4.22 MW | 4.22 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 957481 | AF2-042 C | 80/20 | 152.55 MW | 152.55 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 958211 | AF2-115 C | 80/20 | 2.57 MW | 2.57 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 926754 | AC1-161 C | Adder | -33.24 MW | -28.25 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 934061 | AD1-033 C | Adder | -7.49 MW | -6.37 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 937221 | AD2-160 C O1 | Adder | -5.64 MW | -4.8 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 942401 | AE2-253 C | Adder | -5.94 MW | -5.05 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 943621 | AF1-033 C | Adder | -2.22 MW | -1.89 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315102 | 1BRUNSWICKG1 | 80/20 | 27.11 MW | 27.11 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315103 | 1BRUNSWICKG2 | 80/20 | 27.11 MW | 27.11 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315104 | 1BRUNSWICKG3 | 80/20 | 27.11 MW | 27.11 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315105 | 1BRUNSWICKS1 | 80/20 | 56.32 MW | 56.32 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315241 | 1Z1-086 GT1 | 80/20 | 34.42 MW | 34.42 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315242 | 1Z1-086 GT2 | 80/20 | 34.42 MW | 34.42 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315243 | 1Z1-086 GT3 | 80/20 | 34.42 MW | 34.42 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 315244 | 1Z1-086 ST | 80/20 | 59.82 MW | 59.82 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 932044 | AC2-012 C | Adder | -8.1 MW | -6.88 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 938741 | AE1-100 C O1 | 80/20 | 4.64 MW | 4.64 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 940601 | AE2-047 C O1 | 80/20 | 4.29 MW | 4.29 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 962561 | AG1-105 C O1 | 80/20 | 12.24 MW | 12.24 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 313527 | AB2-043 C | 80/20 | 0.54 MW | 0.54 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | 316123 | AC1-075 C | 80/20 | 1.41 MW | 1.41 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 9.93 MW | 9.93 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.18 MW | 3.18 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 186.51 MW | 186.51 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 64.82 MW | 64.82 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 67.55 MW | 67.55 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 15.03 MW | 15.03 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.82 MW | 15.82 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.85 MW | 0.85 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.18 MW | 3.18 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.25 MW | 9.25 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.13 MW | 2.13 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.57 MW | 0.57 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.73 MW | 12.73 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.55 MW | 1.55 MW |
Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | Adder | 1.07 MW | 0.91 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | Adder | 0.64 MW | 0.54 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | Adder | 2.55 MW | 2.16 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | Adder | 2.55 MW | 2.16 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962491 | AG1-098 C O1 | Adder | 9.67 MW | 8.22 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 7.01 MW | 7.01 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 7.12 MW | 7.12 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 85.77 MW | 85.77 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | Adder | 5.43 MW | 4.61 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | Adder | 2.64 MW | 2.25 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 46.21 MW | 46.21 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | Adder | 7.48 MW | 6.36 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | Adder | 2.8 MW | 2.38 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | Adder | 2.33 MW | 1.98 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | Adder | 2.57 MW | 2.18 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | Adder | 4.53 MW | 3.85 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | 80/20 | 13.62 MW | 13.62 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | 80/20 | 13.62 MW | 13.62 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | Adder | 27.25 MW | 23.16 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | Adder | 7.06 MW | 6.0 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | Adder | 7.06 MW | 6.0 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | 80/20 | 7.95 MW | 7.95 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | 80/20 | 7.95 MW | 7.95 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | Adder | 14.53 MW | 12.35 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | Adder | 4.08 MW | 3.47 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | Adder | 4.08 MW | 3.47 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 29.54 MW | 29.54 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 20.6 MW | 20.6 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 20.6 MW | 20.6 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | Adder | 1.41 MW | 1.2 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | Adder | 7.21 MW | 6.13 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | Adder | 0.44 MW | 0.37 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | Adder | 8.54 MW | 7.26 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | Adder | 8.54 MW | 7.26 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | Adder | 22.89 MW | 19.45 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | Adder | 7.1 MW | 6.03 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | Adder | 2.38 MW | 2.02 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | Adder | 9.89 MW | 8.41 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | Adder | 10.14 MW | 8.62 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | Adder | 10.72 MW | 9.11 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | 80/20 | 75.19 MW | 75.19 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934615 | AD1-087 C | Adder | 8.02 MW | 6.82 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934625 | AD1-088 C | Adder | 10.68 MW | 9.08 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935171 | AD1-152 C O1 | Adder | 8.21 MW | 6.98 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937481 | AD2-202 C O1 | Adder | 2.35 MW | 2.0 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 45.53 MW | 45.53 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | Adder | 1.78 MW | 1.51 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 16.59 MW | 16.59 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | Adder | 3.08 MW | 2.61 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | Adder | 8.43 MW | 7.17 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | Adder | 2.6 MW | 2.21 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 9.18 MW | 7.8 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 11.25 MW | 9.56 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | Adder | 7.4 MW | 6.29 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | Adder | 0.74 MW | 0.63 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | Adder | 15.54 MW | 13.21 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | Adder | 7.85 MW | 6.67 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | Adder | 7.3 MW | 6.21 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | Adder | 10.12 MW | 8.6 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C | Adder | 8.07 MW | 6.86 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | 80/20 | 10.28 MW | 10.28 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | Adder | 4.78 MW | 4.07 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | Adder | 2.99 MW | 2.54 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 50.76 MW | 50.76 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941791 | AE2-182 C | Adder | 1.74 MW | 1.48 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | Adder | 1.54 MW | 1.31 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | Adder | 60.22 MW | 51.18 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | Adder | 21.27 MW | 18.08 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | 80/20 | 24.43 MW | 24.43 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | Adder | 8.98 MW | 7.64 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C | 80/20 | 4.01 MW | 4.01 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | Adder | 15.24 MW | 12.96 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 24.42 MW | 24.42 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | Adder | 12.76 MW | 10.85 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313526 | AB2-022 C | 80/20 | 0.62 MW | 0.62 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314421 | 6WINCHST | 80/20 | 0.18 MW | 0.18 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314491 | 3PENDLTN | 80/20 | 0.55 MW | 0.55 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314507 | 3THOMPSN | 80/20 | 0.55 MW | 0.55 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314638 | 6ELIZ CT | 80/20 | 0.36 MW | 0.36 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314639 | 6TANGLEW | 80/20 | 0.66 MW | 0.66 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314643 | 3O INLET | 80/20 | 0.73 MW | 0.73 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315092 | 1YORKTN3 | 80/20 | 32.53 MW | 32.53 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926661 | AC1-147 C | 80/20 | 0.62 MW | 0.62 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926754 | AC1-161 C | 80/20 | 57.15 MW | 57.15 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934014 | AD1-025 C | Adder | 14.54 MW | 12.36 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934061 | AD1-033 C | 80/20 | 12.29 MW | 12.29 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | Adder | 7.03 MW | 5.98 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935111 | AD1-144 C | 80/20 | 0.44 MW | 0.44 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | 80/20 | 4.42 MW | 4.42 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937221 | AD2-160 C O1 | 80/20 | 9.48 MW | 9.48 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | 80/20 | 1.91 MW | 1.91 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942401 | AE2-253 C | 80/20 | 9.98 MW | 9.98 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942551 | AE2-270 | Adder | 22.2 MW | 18.87 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | 80/20 | 1.73 MW | 1.73 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943611 | AF1-032 C | 80/20 | 2.72 MW | 2.72 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943621 | AF1-033 C | Adder | 2.84 MW | 2.41 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944871 | AF1-152 C | 80/20 | 8.14 MW | 8.14 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945361 | AF1-201 C O1 | Adder | 17.29 MW | 14.7 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961711 | AG1-011 | Adder | 24.7 MW | 21.0 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315098 | 1CHESPKA | 80/20 | 0.73 MW | 0.73 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315099 | 1CHESPKB | 80/20 | 1.21 MW | 1.21 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 10.79 MW | 10.79 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 10.79 MW | 10.79 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 10.79 MW | 10.79 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 22.42 MW | 22.42 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315108 | 1ELIZAR1 | 80/20 | 5.41 MW | 5.41 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315109 | 1ELIZAR2 | 80/20 | 5.32 MW | 5.32 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315110 | 1ELIZAR3 | 80/20 | 5.48 MW | 5.48 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315115 | 1S HAMPT1 | 80/20 | 2.06 MW | 2.06 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315233 | 1SURRY 2 | 80/20 | 54.03 MW | 54.03 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 13.91 MW | 13.91 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 13.91 MW | 13.91 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 13.91 MW | 13.91 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 24.18 MW | 24.18 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315260 | 1GOSPORTA | 80/20 | 0.58 MW | 0.58 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315261 | 1GOSPORTB | 80/20 | 0.75 MW | 0.75 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315262 | 1GOSPORTC | 80/20 | 0.63 MW | 0.63 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315603 | 6AA1-139SOLA | 80/20 | 3.86 MW | 3.86 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315605 | 6W1-029WIND | 80/20 | 1.8 MW | 1.8 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315611 | 6Z1-036WIND | 80/20 | 1.09 MW | 1.09 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316258 | AE1-162 C | 80/20 | 0.49 MW | 0.49 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932044 | AC2-012 C | 80/20 | 12.94 MW | 12.94 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | Adder | 6.67 MW | 5.67 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938535 | AE1-072 C | 80/20 | 28.21 MW | 28.21 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 46.57 MW | 46.57 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 39.92 MW | 39.92 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 46.57 MW | 46.57 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939431 | AE1-175 C | Adder | 2.21 MW | 1.88 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | Adder | 2.68 MW | 2.27 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | 80/20 | 4.87 MW | 4.87 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941281 | AE2-122 C O1 | 80/20 | 46.19 MW | 46.19 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941291 | AE2-123 C O1 | 80/20 | 47.47 MW | 47.47 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941301 | AE2-124 C O1 | 80/20 | 43.2 MW | 43.2 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957491 | AF2-043 C | 80/20 | 3.33 MW | 3.33 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957631 | AF2-057 | 80/20 | 5.77 MW | 5.77 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957711 | AF2-065 C | Adder | 11.32 MW | 9.62 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962531 | AG1-102 C | Adder | 1.03 MW | 0.87 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962961 | AG1-145 C | Adder | 1.99 MW | 1.69 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963221 | AG1-171 C | Adder | 1.85 MW | 1.57 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963231 | AG1-172 C | Adder | 1.85 MW | 1.57 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963241 | AG1-173 C | Adder | 1.85 MW | 1.57 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963251 | AG1-174 C | Adder | 1.85 MW | 1.57 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964951 | AG1-359 O1 | 80/20 | 37.34 MW | 37.34 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965001 | AG1-364 C O1 | 80/20 | 11.57 MW | 11.57 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933294 | AC2-141 C | 80/20 | 57.15 MW | 57.15 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941501 | AE2-147 C | 80/20 | 24.42 MW | 24.42 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941591 | AE2-156 O1 | 80/20 | 28.93 MW | 28.93 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957831 | AF2-077 C | Adder | 2.0 MW | 1.7 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957871 | AF2-081 C | 80/20 | 16.11 MW | 16.11 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | 80/20 | 2.01 MW | 2.01 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966611 | AG1-531 C | 80/20 | 7.32 MW | 7.32 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944581 | AF1-123 C O1 | 80/20 | 80.97 MW | 80.97 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944591 | AF1-124 C O1 | 80/20 | 80.97 MW | 80.97 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944601 | AF1-125 C O1 | 80/20 | 80.97 MW | 80.97 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | 80/20 | 11.93 MW | 11.93 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | Adder | 8.34 MW | 7.09 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | Adder | 21.31 MW | 18.11 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | Adder | 6.36 MW | 5.41 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | Adder | 2.05 MW | 1.74 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315614 | AA2-178 C | 80/20 | 2.33 MW | 2.33 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | Adder | 3.09 MW | 2.62 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961611 | AG1-000B C | Adder | 17.64 MW | 15.0 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.82 MW | 5.82 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.5 MW | 1.5 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 102.45 MW | 102.45 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 24.75 MW | 24.75 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 31.15 MW | 31.15 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 8.81 MW | 8.81 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.64 MW | 7.64 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.49 MW | 0.49 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.26 MW | 1.26 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.92 MW | 3.92 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.61 MW | 1.61 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.23 MW | 0.23 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.14 MW | 6.14 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.61 MW | 0.61 MW |
Details for AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 961791 | AG1-021 C | 80/20 | 1.85 MW | 1.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 961891 | AG1-030 C | 80/20 | 13.82 MW | 13.82 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 962491 | AG1-098 C O1 | 80/20 | 20.69 MW | 20.69 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963041 | AG1-153 C | 80/20 | 17.6 MW | 17.6 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963111 | AG1-160 C | 80/20 | 18.44 MW | 18.44 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963171 | AG1-166 C | 80/20 | 1.85 MW | 1.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963181 | AG1-167 C | 80/20 | 1.85 MW | 1.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963191 | AG1-168 C | 80/20 | 1.85 MW | 1.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963201 | AG1-169 C | 80/20 | 1.85 MW | 1.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963211 | AG1-170 C | 80/20 | 1.85 MW | 1.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963321 | AG1-181 C O1 | 80/20 | 15.44 MW | 15.44 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963361 | AG1-185 O1 | 80/20 | 7.47 MW | 7.47 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964111 | AG1-272 C | 80/20 | 2.36 MW | 2.36 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964121 | AG1-273 C | 80/20 | 2.36 MW | 2.36 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964131 | AG1-274 C | 80/20 | 2.36 MW | 2.36 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964241 | AG1-285 C O1 | 80/20 | 11.41 MW | 11.41 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964791 | AG1-342 C | 80/20 | 5.47 MW | 5.47 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966691 | AG1-539 C | 80/20 | 5.64 MW | 5.64 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966761 | AG1-547 C | 80/20 | 3.77 MW | 3.77 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965191 | AG1-384 C | 80/20 | 2.36 MW | 2.36 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965591 | AG1-427 C | 80/20 | 10.81 MW | 10.81 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965641 | AG1-432 C O1 | 80/20 | 18.63 MW | 18.63 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965721 | AG1-440 C | 80/20 | 5.26 MW | 5.26 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965731 | AG1-441 C | 80/20 | 5.26 MW | 5.26 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965771 | AG1-445 | 80/20 | 3.04 MW | 3.04 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965781 | AG1-446 | 80/20 | 3.04 MW | 3.04 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965811 | AG1-449 | 80/20 | 68.22 MW | 68.22 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965831 | AG1-451 | 80/20 | 3.1 MW | 3.1 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966361 | AG1-505 C | 80/20 | 48.35 MW | 48.35 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966371 | AG1-506 C | 80/20 | 48.35 MW | 48.35 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 247284 | 05LEESVG | 80/20 | 0.93 MW | 0.93 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 314429 | 3JTRSVLE | 80/20 | 0.42 MW | 0.42 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315153 | 1CLOVER1 | 80/20 | 30.43 MW | 30.43 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315154 | 1CLOVER2 | 80/20 | 30.14 MW | 30.14 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315158 | 1KERR 1 | 80/20 | 0.35 MW | 0.35 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315159 | 1KERR 2 | 80/20 | 0.98 MW | 0.98 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315160 | 1KERR 3 | 80/20 | 0.98 MW | 0.98 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315161 | 1KERR 4 | 80/20 | 0.98 MW | 0.98 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315162 | 1KERR 5 | 80/20 | 0.98 MW | 0.98 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926023 | AC1-080 C | 80/20 | 0.43 MW | 0.43 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926051 | AC1-083 C O1 | 80/20 | 4.86 MW | 4.86 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926645 | AC1-145 C | 80/20 | 0.38 MW | 0.38 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 927251 | AC1-221 C | 80/20 | 3.73 MW | 3.73 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 927261 | AC1-222 C | 80/20 | 5.71 MW | 5.71 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 933941 | AD1-017 C | 80/20 | 0.97 MW | 0.97 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934311 | AD1-055 C | 80/20 | 3.96 MW | 3.96 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934341 | AD1-058 C | 80/20 | 9.36 MW | 9.36 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934615 | AD1-087 C | 80/20 | 17.65 MW | 17.65 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934625 | AD1-088 C | 80/20 | 22.84 MW | 22.84 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934991 | AD1-131 C | 80/20 | 3.07 MW | 3.07 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 935171 | AD1-152 C O1 | 80/20 | 17.29 MW | 17.29 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 936161 | AD2-022 C O1 | 80/20 | 12.6 MW | 12.6 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 936171 | AD2-023 C O1 | 80/20 | 7.35 MW | 7.35 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 936265 | AD2-033 C | 80/20 | 11.91 MW | 11.91 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 937481 | AD2-202 C O1 | 80/20 | 5.17 MW | 5.17 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942461 | AE2-259 C O1 | 80/20 | 9.31 MW | 9.31 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942671 | AE2-283 C | 80/20 | 4.59 MW | 4.59 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942751 | AE2-291 C | 80/20 | 10.79 MW | 10.79 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942761 | AE2-292 C O1 | 80/20 | 13.43 MW | 13.43 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942931 | AE2-313 C | 80/20 | 105.35 MW | 105.35 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943811 | AF1-049 C | 80/20 | 9.05 MW | 9.05 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943901 | AF1-058 C | 80/20 | 3.16 MW | 3.16 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 944011 | AF1-069 C | 80/20 | 45.58 MW | 45.58 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 944141 | AF1-082 | 80/20 | 1.87 MW | 1.87 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 945811 | AF1-246 C O1 | 80/20 | 19.09 MW | 19.09 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 958801 | AF2-171 C | 80/20 | 13.85 MW | 13.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 959311 | AF2-222 C | 80/20 | 15.31 MW | 15.31 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 960061 | AF2-297 C | 80/20 | 12.65 MW | 12.65 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 961121 | AF2-403 | 80/20 | 0.93 MW | 0.93 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315163 | 1KERR 6 | 80/20 | 0.98 MW | 0.98 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315164 | 1KERR 7 | 80/20 | 0.98 MW | 0.98 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315266 | 1PLYWOOD A | 80/20 | 1.88 MW | 1.88 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316020 | AB2-059 C OP | 80/20 | 1.17 MW | 1.17 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316118 | AC1-105 C | 80/20 | 8.29 MW | 8.29 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316131 | AB2-060 C | 80/20 | 1.41 MW | 1.41 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 922922 | AB1-081 C OP | 80/20 | 0.99 MW | 0.99 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 924301 | AB2-077 C O1 | 80/20 | 1.85 MW | 1.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 924311 | AB2-078 C O1 | 80/20 | 1.85 MW | 1.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 924321 | AB2-079 C O1 | 80/20 | 1.85 MW | 1.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 925591 | AC1-034 C | 80/20 | 4.44 MW | 4.44 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 925611 | AC1-036 C | 80/20 | 0.22 MW | 0.22 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 925661 | AC1-042 C | 80/20 | 1.85 MW | 1.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 932761 | AC2-100 C | 80/20 | 8.59 MW | 8.59 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 938371 | AE1-056 C | 80/20 | 5.99 MW | 5.99 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 939181 | AE1-148 C | 80/20 | 7.56 MW | 7.56 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940081 | AE1-250 C | 80/20 | 13.17 MW | 13.17 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940571 | AE2-044 C | 80/20 | 2.9 MW | 2.9 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940661 | AE2-053 O1 | 80/20 | 2.8 MW | 2.8 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941031 | AE2-094 C | 80/20 | 139.5 MW | 139.5 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941431 | AE2-140 C O1 | 80/20 | 13.82 MW | 13.82 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941791 | AE2-182 C | 80/20 | 3.71 MW | 3.71 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941801 | AE2-185 C | 80/20 | 4.17 MW | 4.17 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941821 | AE2-187 C | 80/20 | 4.17 MW | 4.17 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 946301 | AF1-294 C | 80/20 | 3.79 MW | 3.79 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 957481 | AF2-042 C | 80/20 | 136.39 MW | 136.39 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 958211 | AF2-115 C | 80/20 | 2.31 MW | 2.31 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926754 | AC1-161 C | Adder | -31.93 MW | -27.14 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934061 | AD1-033 C | Adder | -7.2 MW | -6.12 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 937221 | AD2-160 C O1 | Adder | -5.42 MW | -4.61 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942401 | AE2-253 C | Adder | -5.7 MW | -4.85 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943611 | AF1-032 C | Adder | -1.56 MW | -1.32 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943621 | AF1-033 C | Adder | -2.13 MW | -1.81 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315102 | 1BRUNSWICKG1 | 80/20 | 27.08 MW | 27.08 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315103 | 1BRUNSWICKG2 | 80/20 | 27.08 MW | 27.08 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315104 | 1BRUNSWICKG3 | 80/20 | 27.08 MW | 27.08 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315105 | 1BRUNSWICKS1 | 80/20 | 56.26 MW | 56.26 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315241 | 1Z1-086 GT1 | 80/20 | 36.01 MW | 36.01 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315242 | 1Z1-086 GT2 | 80/20 | 36.01 MW | 36.01 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315243 | 1Z1-086 GT3 | 80/20 | 36.01 MW | 36.01 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315244 | 1Z1-086 ST | 80/20 | 62.59 MW | 62.59 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 932044 | AC2-012 C | Adder | -7.78 MW | -6.61 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 938741 | AE1-100 C O1 | 80/20 | 4.44 MW | 4.44 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940601 | AE2-047 C O1 | 80/20 | 4.11 MW | 4.11 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 957491 | AF2-043 C | Adder | -1.91 MW | -1.62 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 962561 | AG1-105 C O1 | 80/20 | 11.17 MW | 11.17 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 313527 | AB2-043 C | 80/20 | 0.49 MW | 0.49 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316123 | AC1-075 C | 80/20 | 1.29 MW | 1.29 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 9.63 MW | 9.63 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.07 MW | 3.07 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 180.98 MW | 180.98 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.2 MW | 62.2 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 65.2 MW | 65.2 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 14.58 MW | 14.58 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.29 MW | 15.29 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.82 MW | 0.82 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.05 MW | 3.05 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.9 MW | 8.9 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.07 MW | 2.07 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.55 MW | 0.55 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.3 MW | 12.3 MW |
AE2-094 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.49 MW | 1.49 MW |
Details for AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 961791 | AG1-021 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 961891 | AG1-030 C | 80/20 | 15.36 MW | 15.36 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 962491 | AG1-098 C O1 | 80/20 | 23.12 MW | 23.12 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963041 | AG1-153 C | 80/20 | 17.62 MW | 17.62 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963111 | AG1-160 C | 80/20 | 17.62 MW | 17.62 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963171 | AG1-166 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963181 | AG1-167 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963191 | AG1-168 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963201 | AG1-169 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963211 | AG1-170 C | 80/20 | 2.06 MW | 2.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963321 | AG1-181 C O1 | 80/20 | 17.07 MW | 17.07 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963361 | AG1-185 O1 | 80/20 | 8.26 MW | 8.26 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 964111 | AG1-272 C | 80/20 | 2.61 MW | 2.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 964121 | AG1-273 C | 80/20 | 2.61 MW | 2.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 964131 | AG1-274 C | 80/20 | 2.61 MW | 2.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 964241 | AG1-285 C O1 | 80/20 | 12.55 MW | 12.55 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 964791 | AG1-342 C | 80/20 | 6.0 MW | 6.0 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 966691 | AG1-539 C | 80/20 | 6.13 MW | 6.13 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 966761 | AG1-547 C | 80/20 | 4.06 MW | 4.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965191 | AG1-384 C | 80/20 | 2.61 MW | 2.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965591 | AG1-427 C | 80/20 | 11.9 MW | 11.9 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965641 | AG1-432 C O1 | 80/20 | 20.93 MW | 20.93 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965721 | AG1-440 C | 80/20 | 5.69 MW | 5.69 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965731 | AG1-441 C | 80/20 | 5.69 MW | 5.69 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965771 | AG1-445 | 80/20 | 3.29 MW | 3.29 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965781 | AG1-446 | 80/20 | 3.29 MW | 3.29 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965811 | AG1-449 | 80/20 | 80.93 MW | 80.93 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965831 | AG1-451 | 80/20 | 3.49 MW | 3.49 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 966361 | AG1-505 C | 80/20 | 54.28 MW | 54.28 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 966371 | AG1-506 C | 80/20 | 54.28 MW | 54.28 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 246844 | 05SMG2 | 80/20 | 3.59 MW | 3.59 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 247284 | 05LEESVG | 80/20 | 0.99 MW | 0.99 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 314429 | 3JTRSVLE | 80/20 | 0.47 MW | 0.47 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315153 | 1CLOVER1 | 80/20 | 33.93 MW | 33.93 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315154 | 1CLOVER2 | 80/20 | 33.61 MW | 33.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315156 | 1HALLBR1 | 80/20 | 1.2 MW | 1.2 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315158 | 1KERR 1 | 80/20 | 0.38 MW | 0.38 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315159 | 1KERR 2 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315160 | 1KERR 3 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315161 | 1KERR 4 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315162 | 1KERR 5 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 926023 | AC1-080 C | 80/20 | 0.47 MW | 0.47 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 926051 | AC1-083 C O1 | 80/20 | 5.12 MW | 5.12 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 926645 | AC1-145 C | 80/20 | 0.4 MW | 0.4 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 927251 | AC1-221 C | 80/20 | 3.96 MW | 3.96 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 927261 | AC1-222 C | 80/20 | 6.24 MW | 6.24 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 933941 | AD1-017 C | 80/20 | 1.02 MW | 1.02 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934311 | AD1-055 C | 80/20 | 4.33 MW | 4.33 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934341 | AD1-058 C | 80/20 | 9.94 MW | 9.94 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934615 | AD1-087 C | 80/20 | 19.68 MW | 19.68 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934625 | AD1-088 C | 80/20 | 25.52 MW | 25.52 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934991 | AD1-131 C | 80/20 | 3.26 MW | 3.26 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 935171 | AD1-152 C O1 | 80/20 | 19.14 MW | 19.14 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 936161 | AD2-022 C O1 | 80/20 | 13.16 MW | 13.16 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 936171 | AD2-023 C O1 | 80/20 | 7.68 MW | 7.68 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 936265 | AD2-033 C | 80/20 | 13.16 MW | 13.16 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 937481 | AD2-202 C O1 | 80/20 | 5.76 MW | 5.76 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 942461 | AE2-259 C O1 | 80/20 | 10.46 MW | 10.46 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 942671 | AE2-283 C | 80/20 | 4.94 MW | 4.94 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 942751 | AE2-291 C | 80/20 | 11.73 MW | 11.73 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 942761 | AE2-292 C O1 | 80/20 | 14.61 MW | 14.61 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 942931 | AE2-313 C | 80/20 | 124.49 MW | 124.49 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 943811 | AF1-049 C | 80/20 | 9.46 MW | 9.46 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 943901 | AF1-058 C | 80/20 | 3.46 MW | 3.46 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 945811 | AF1-246 C O1 | 80/20 | 21.36 MW | 21.36 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 958801 | AF2-171 C | 80/20 | 15.43 MW | 15.43 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 959311 | AF2-222 C | 80/20 | 16.95 MW | 16.95 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 960061 | AF2-297 C | 80/20 | 13.84 MW | 13.84 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 961121 | AF2-403 | 80/20 | 1.0 MW | 1.0 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315163 | 1KERR 6 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315164 | 1KERR 7 | 80/20 | 1.06 MW | 1.06 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315266 | 1PLYWOOD A | 80/20 | 2.05 MW | 2.05 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 316118 | AC1-105 C | 80/20 | 9.08 MW | 9.08 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 316131 | AB2-060 C | 80/20 | 1.55 MW | 1.55 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 924301 | AB2-077 C O1 | 80/20 | 2.03 MW | 2.03 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 924311 | AB2-078 C O1 | 80/20 | 2.03 MW | 2.03 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 924321 | AB2-079 C O1 | 80/20 | 2.03 MW | 2.03 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 925611 | AC1-036 C | 80/20 | 0.25 MW | 0.25 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 925661 | AC1-042 C | 80/20 | 1.99 MW | 1.99 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 932761 | AC2-100 C | 80/20 | 9.12 MW | 9.12 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 938371 | AE1-056 C | 80/20 | 6.68 MW | 6.68 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 939181 | AE1-148 C | 80/20 | 8.21 MW | 8.21 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 940081 | AE1-250 C | 80/20 | 13.82 MW | 13.82 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 940661 | AE2-053 O1 | 80/20 | 3.04 MW | 3.04 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 941431 | AE2-140 C O1 | 80/20 | 14.45 MW | 14.45 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 941791 | AE2-182 C | 80/20 | 4.15 MW | 4.15 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 941801 | AE2-185 C | 80/20 | 4.49 MW | 4.49 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 941821 | AE2-187 C | 80/20 | 4.49 MW | 4.49 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 946301 | AF1-294 C | 80/20 | 4.22 MW | 4.22 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 957481 | AF2-042 C | 80/20 | 152.55 MW | 152.55 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 958211 | AF2-115 C | 80/20 | 2.57 MW | 2.57 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 926754 | AC1-161 C | Adder | -33.24 MW | -28.25 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934061 | AD1-033 C | Adder | -7.49 MW | -6.37 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 937221 | AD2-160 C O1 | Adder | -5.64 MW | -4.8 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 942401 | AE2-253 C | Adder | -5.94 MW | -5.05 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 943611 | AF1-032 C | Adder | -1.62 MW | -1.38 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 943621 | AF1-033 C | Adder | -2.22 MW | -1.89 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315102 | 1BRUNSWICKG1 | 80/20 | 27.11 MW | 27.11 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315103 | 1BRUNSWICKG2 | 80/20 | 27.11 MW | 27.11 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315104 | 1BRUNSWICKG3 | 80/20 | 27.11 MW | 27.11 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315105 | 1BRUNSWICKS1 | 80/20 | 56.32 MW | 56.32 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315241 | 1Z1-086 GT1 | 80/20 | 34.42 MW | 34.42 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315242 | 1Z1-086 GT2 | 80/20 | 34.42 MW | 34.42 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315243 | 1Z1-086 GT3 | 80/20 | 34.42 MW | 34.42 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315244 | 1Z1-086 ST | 80/20 | 59.82 MW | 59.82 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 932044 | AC2-012 C | Adder | -8.1 MW | -6.88 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 938741 | AE1-100 C O1 | 80/20 | 4.64 MW | 4.64 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 939431 | AE1-175 C | Adder | -2.17 MW | -1.85 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 940601 | AE2-047 C O1 | 80/20 | 4.29 MW | 4.29 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 957491 | AF2-043 C | Adder | -1.99 MW | -1.69 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 962961 | AG1-145 C | Adder | -1.96 MW | -1.67 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 962561 | AG1-105 C O1 | 80/20 | 12.24 MW | 12.24 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 313527 | AB2-043 C | 80/20 | 0.54 MW | 0.54 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 316123 | AC1-075 C | 80/20 | 1.41 MW | 1.41 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 9.93 MW | 9.93 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.18 MW | 3.18 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 186.51 MW | 186.51 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 64.82 MW | 64.82 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 67.55 MW | 67.55 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 15.03 MW | 15.03 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.82 MW | 15.82 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.85 MW | 0.85 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.18 MW | 3.18 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.25 MW | 9.25 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.13 MW | 2.13 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.57 MW | 0.57 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.73 MW | 12.73 MW |
AG1-449 TAP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.55 MW | 1.55 MW |
Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961671 | AG1-007 C | Adder | 1.17 MW | 1.0 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961941 | AG1-037 C | Adder | 0.7 MW | 0.6 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962331 | AG1-082 C | Adder | 2.81 MW | 2.39 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962341 | AG1-083 C | Adder | 2.81 MW | 2.39 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963041 | AG1-153 C | Adder | 7.06 MW | 6.0 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963111 | AG1-160 C | Adder | 7.16 MW | 6.08 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963291 | AG1-178 C O2 | Adder | 86.02 MW | 73.12 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963301 | AG1-179 C | Adder | 6.38 MW | 5.42 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963311 | AG1-180 | Adder | 3.11 MW | 2.64 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963351 | AG1-184 O2 | Adder | 46.34 MW | 39.39 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964801 | AG1-343 C | Adder | 8.36 MW | 7.11 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966801 | AG1-551 C | Adder | 3.04 MW | 2.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966811 | AG1-552 C | Adder | 2.64 MW | 2.25 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965291 | AG1-394 C | Adder | 2.87 MW | 2.44 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965601 | AG1-428 C O2 | Adder | 5.33 MW | 4.53 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965691 | AG1-437 C O1 | Adder | 14.83 MW | 12.61 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965701 | AG1-438 C O1 | Adder | 14.83 MW | 12.61 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965711 | AG1-439 C O1 | Adder | 29.74 MW | 25.28 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965741 | AG1-442 O1 | Adder | 8.65 MW | 7.35 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965751 | AG1-443 O1 | Adder | 8.65 MW | 7.35 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965761 | AG1-444 O1 | Adder | 15.86 MW | 13.48 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965811 | AG1-449 | Adder | 29.66 MW | 25.21 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966361 | AG1-505 C | Adder | 20.84 MW | 17.71 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966371 | AG1-506 C | Adder | 20.84 MW | 17.71 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966621 | AG1-532 C | Adder | 1.67 MW | 1.42 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 313506 | AB1-173 C OP | Adder | 8.39 MW | 7.13 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314572 | 3EMPORIA | Adder | 0.52 MW | 0.44 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315131 | 1EDGECMA | Adder | 9.36 MW | 7.96 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315132 | 1EDGECMB | Adder | 9.36 MW | 7.96 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926070 | AC1-086 C | Adder | 26.24 MW | 22.3 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926201 | AC1-098 C | Adder | 7.87 MW | 6.69 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926211 | AC1-099 C | Adder | 2.64 MW | 2.24 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 927024 | AC1-189 C | Adder | 10.78 MW | 9.17 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 927145 | AC1-208 C | Adder | 11.29 MW | 9.6 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934331 | AD1-057 C O1 | Adder | 12.0 MW | 10.2 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934521 | AD1-076 C | Adder | 81.45 MW | 69.23 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934615 | AD1-087 C | Adder | 8.43 MW | 7.16 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 937481 | AD2-202 C O1 | Adder | 2.47 MW | 2.1 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942931 | AE2-313 C | Adder | 45.72 MW | 38.87 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943171 | AE2-346 C | Adder | 1.97 MW | 1.67 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944011 | AF1-069 C | Adder | 16.62 MW | 14.12 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944141 | AF1-082 | Adder | 3.37 MW | 2.86 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 945811 | AF1-246 C O1 | Adder | 8.72 MW | 7.41 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 960081 | AF2-299 C | Adder | 3.09 MW | 2.62 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315293 | 1DOMTR9 | Adder | 9.95 MW | 8.46 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315294 | 1DOMTR10 | Adder | 12.2 MW | 10.37 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316129 | AC1-054 C | Adder | 8.37 MW | 7.12 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316140 | AB2-099 C | Adder | 0.82 MW | 0.7 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 923262 | AB1-132 C OP | Adder | 17.82 MW | 15.14 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 923991 | AB2-040 C O1 | Adder | 9.13 MW | 7.76 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 925591 | AC1-034 C | Adder | 8.0 MW | 6.8 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 932631 | AC2-084 C | Adder | 11.22 MW | 9.54 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940491 | AE2-034 C | Adder | 11.09 MW | 9.43 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940571 | AE2-044 C | Adder | 5.24 MW | 4.46 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941031 | AE2-094 C | Adder | 50.86 MW | 43.23 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946281 | AF1-292 C | Adder | 1.83 MW | 1.56 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957481 | AF2-042 C | Adder | 62.27 MW | 52.93 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957521 | AF2-046 C | Adder | 23.64 MW | 20.09 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957531 | AF2-047 C | Adder | 26.36 MW | 22.4 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957861 | AF2-080 C | Adder | 9.8 MW | 8.33 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 938771 | AE1-103 C | Adder | 4.46 MW | 3.79 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940481 | AE2-033 C | Adder | 19.25 MW | 16.36 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940641 | AE2-051 C O1 | Adder | 24.32 MW | 20.67 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946011 | AF1-266 | Adder | 16.11 MW | 13.7 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 313526 | AB2-022 C | 80/20 | 0.66 MW | 0.66 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314295 | 6BIRDNECK | 80/20 | 0.08 MW | 0.08 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314421 | 6WINCHST | 80/20 | 0.24 MW | 0.24 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314491 | 3PENDLTN | 80/20 | 0.59 MW | 0.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314507 | 3THOMPSN | 80/20 | 0.59 MW | 0.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314638 | 6ELIZ CT | 80/20 | 0.38 MW | 0.38 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314639 | 6TANGLEW | 80/20 | 0.7 MW | 0.7 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314643 | 3O INLET | 80/20 | 0.77 MW | 0.77 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315060 | 1CHESTF5 | Adder | 79.62 MW | 67.68 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315092 | 1YORKTN3 | 80/20 | 43.27 MW | 43.27 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 925863 | AC1-065 C | Adder | 9.35 MW | 7.95 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926661 | AC1-147 C | 80/20 | 0.66 MW | 0.66 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926754 | AC1-161 C | 80/20 | 56.44 MW | 56.44 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926784 | AC1-164 C | 80/20 | 64.19 MW | 64.19 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934014 | AD1-025 C | Adder | 23.85 MW | 20.27 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934061 | AD1-033 C | 80/20 | 12.94 MW | 12.94 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934141 | AD1-041 C | Adder | 8.1 MW | 6.88 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934575 | AD1-082 C | Adder | 10.11 MW | 8.6 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 935111 | AD1-144 C | 80/20 | 0.49 MW | 0.49 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 935164 | AD1-151 C | Adder | 22.06 MW | 18.75 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 936591 | AD2-074 C | Adder | 7.47 MW | 6.35 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 936661 | AD2-085 C | Adder | 5.22 MW | 4.44 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 937221 | AD2-160 C O1 | 80/20 | 10.01 MW | 10.01 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942151 | AE2-227 C | Adder | 2.23 MW | 1.9 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942341 | AE2-247 C | Adder | 2.26 MW | 1.92 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942371 | AE2-250 C O1 | Adder | 10.74 MW | 9.13 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942401 | AE2-253 C | 80/20 | 10.53 MW | 10.53 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942551 | AE2-270 | Adder | 37.52 MW | 31.89 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943431 | AF1-014 C | Adder | 1.94 MW | 1.65 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943461 | AF1-017 C | Adder | 2.05 MW | 1.74 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943471 | AF1-018 | Adder | 11.07 MW | 9.41 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943611 | AF1-032 C | 80/20 | 2.92 MW | 2.92 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943621 | AF1-033 C | 80/20 | 3.77 MW | 3.77 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943741 | AF1-042 C | Adder | 3.91 MW | 3.32 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944631 | AF1-128 O1 | Adder | 49.82 MW | 42.35 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944871 | AF1-152 C | 80/20 | 8.71 MW | 8.71 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 945361 | AF1-201 C O1 | 80/20 | 27.54 MW | 27.54 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961711 | AG1-011 | Adder | 40.51 MW | 34.44 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961951 | AG1-038 C | Adder | 4.32 MW | 3.67 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966661 | AG1-536 C | Adder | 7.12 MW | 6.05 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315098 | 1CHESPKA | 80/20 | 0.78 MW | 0.78 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315099 | 1CHESPKB | 80/20 | 1.29 MW | 1.29 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315108 | 1ELIZAR1 | 80/20 | 5.75 MW | 5.75 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315109 | 1ELIZAR2 | 80/20 | 5.65 MW | 5.65 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315110 | 1ELIZAR3 | 80/20 | 5.83 MW | 5.83 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315116 | 1SURRY 1 | 80/20 | 40.35 MW | 40.35 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315120 | 1GRAVEL4 | 80/20 | 4.15 MW | 4.15 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315122 | 1GRAVEL6 | 80/20 | 4.14 MW | 4.14 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315233 | 1SURRY 2 | 80/20 | 52.6 MW | 52.6 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315260 | 1GOSPORTA | 80/20 | 0.62 MW | 0.62 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315261 | 1GOSPORTB | 80/20 | 0.8 MW | 0.8 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315262 | 1GOSPORTC | 80/20 | 0.68 MW | 0.68 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315603 | 6AA1-139SOLA | 80/20 | 4.07 MW | 4.07 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315605 | 6W1-029WIND | 80/20 | 1.93 MW | 1.93 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315611 | 6Z1-036WIND | 80/20 | 1.17 MW | 1.17 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316108 | AB2-160 C | Adder | 6.05 MW | 5.14 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316132 | AB2-190 C | Adder | 25.87 MW | 21.99 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316258 | AE1-162 C | 80/20 | 0.59 MW | 0.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 932044 | AC2-012 C | 80/20 | 13.8 MW | 13.8 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 932591 | AC2-079 C O1 | Adder | 8.32 MW | 7.07 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 938535 | AE1-072 C | 80/20 | 29.82 MW | 29.82 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939195 | AE1-149 C | Adder | 13.4 MW | 11.39 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939245 | AE1-155 C | Adder | 16.95 MW | 14.41 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939414 | AE1-173_C1 | Adder | 47.03 MW | 39.97 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939415 | AE1-173_C2 | Adder | 40.31 MW | 34.26 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939416 | AE1-173_C3 | Adder | 47.03 MW | 39.97 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939431 | AE1-175 C | 80/20 | 4.21 MW | 4.21 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939611 | AE1-191 C | Adder | 16.2 MW | 13.77 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940231 | AE2-005 C | Adder | 2.05 MW | 1.74 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940431 | AE2-027 C O1 | Adder | 13.83 MW | 11.75 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940541 | AE2-040 | Adder | 3.4 MW | 2.89 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940551 | AE2-041 | Adder | 11.07 MW | 9.41 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940651 | AE2-052 | Adder | 4.47 MW | 3.8 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941101 | AE2-104 C O1 | 80/20 | 5.4 MW | 5.4 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941281 | AE2-122 C O1 | 80/20 | 48.91 MW | 48.91 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941291 | AE2-123 C O1 | 80/20 | 50.27 MW | 50.27 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941301 | AE2-124 C O1 | 80/20 | 45.71 MW | 45.71 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957491 | AF2-043 C | 80/20 | 3.58 MW | 3.58 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957601 | AF2-054 C | Adder | 3.24 MW | 2.75 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957631 | AF2-057 | 80/20 | 6.16 MW | 6.16 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957711 | AF2-065 C | Adder | 19.14 MW | 16.27 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962531 | AG1-102 C | 80/20 | 1.83 MW | 1.83 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962861 | AG1-135 C | Adder | 8.1 MW | 6.89 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962961 | AG1-145 C | 80/20 | 3.8 MW | 3.8 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962971 | AG1-146 C | Adder | 4.33 MW | 3.68 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962981 | AG1-147 C | Adder | 10.11 MW | 8.59 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963221 | AG1-171 C | Adder | 3.04 MW | 2.58 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963231 | AG1-172 C | Adder | 3.04 MW | 2.58 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963241 | AG1-173 C | Adder | 3.04 MW | 2.58 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963251 | AG1-174 C | Adder | 3.04 MW | 2.58 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963611 | AG1-210 C | Adder | 0.81 MW | 0.69 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964211 | AG1-282 C | Adder | 2.55 MW | 2.17 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964951 | AG1-359 O1 | 80/20 | 39.3 MW | 39.3 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965001 | AG1-364 C O1 | 80/20 | 12.32 MW | 12.32 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 933294 | AC2-141 C | 80/20 | 56.44 MW | 56.44 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941501 | AE2-147 C | 80/20 | 26.13 MW | 26.13 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941591 | AE2-156 O1 | 80/20 | 30.81 MW | 30.81 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942001 | AE2-212 C | Adder | 2.28 MW | 1.94 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957831 | AF2-077 C | 80/20 | 3.57 MW | 3.57 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957871 | AF2-081 C | 80/20 | 17.01 MW | 17.01 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958161 | AF2-110 C | 80/20 | 2.23 MW | 2.23 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958261 | AF2-120 C | Adder | 8.27 MW | 7.03 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966611 | AG1-531 C | 80/20 | 9.72 MW | 9.72 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944581 | AF1-123 C O1 | 80/20 | 83.88 MW | 83.88 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944591 | AF1-124 C O1 | 80/20 | 83.88 MW | 83.88 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944601 | AF1-125 C O1 | 80/20 | 83.88 MW | 83.88 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 933981 | AD1-022 C | Adder | 12.96 MW | 11.02 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 960331 | AF2-324 C | Adder | 9.14 MW | 7.76 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961681 | AG1-008 C | Adder | 23.68 MW | 20.13 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962271 | AG1-075 C O1 | Adder | 18.54 MW | 15.76 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962571 | AG1-106 C | Adder | 7.3 MW | 6.2 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965281 | AG1-393 C | Adder | 2.6 MW | 2.21 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316083 | AB2-161 C | Adder | 4.44 MW | 3.77 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961611 | AG1-000B C | Adder | 24.42 MW | 20.76 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 6.1 MW | 6.1 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.51 MW | 1.51 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 106.61 MW | 106.61 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 23.11 MW | 23.11 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 31.1 MW | 31.1 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 9.24 MW | 9.24 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.72 MW | 7.72 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.53 MW | 0.53 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.2 MW | 1.2 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.8 MW | 3.8 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.86 MW | 1.86 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.22 MW | 0.22 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.21 MW | 6.21 MW |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.57 MW | 0.57 MW |
Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 961671 | AG1-007 C | Adder | 1.28 MW | 1.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 961941 | AG1-037 C | Adder | 0.69 MW | 0.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 962331 | AG1-082 C | Adder | 2.78 MW | 2.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 962341 | AG1-083 C | Adder | 2.78 MW | 2.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 962491 | AG1-098 C O1 | Adder | 13.15 MW | 11.18 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 963041 | AG1-153 C | 80/20 | 9.99 MW | 9.99 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 963111 | AG1-160 C | 80/20 | 10.16 MW | 10.16 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 963291 | AG1-178 C O2 | 80/20 | 115.0 MW | 115.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 963301 | AG1-179 C | Adder | 6.85 MW | 5.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 963311 | AG1-180 | Adder | 3.34 MW | 2.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 963351 | AG1-184 O2 | 80/20 | 61.95 MW | 61.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 964241 | AG1-285 C O1 | Adder | 13.16 MW | 11.19 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 964791 | AG1-342 C | Adder | 4.82 MW | 4.1 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 964801 | AG1-343 C | Adder | 8.11 MW | 6.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 966801 | AG1-551 C | Adder | 3.14 MW | 2.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 966811 | AG1-552 C | Adder | 2.75 MW | 2.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965291 | AG1-394 C | Adder | 2.78 MW | 2.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965591 | AG1-427 C | Adder | 12.45 MW | 10.58 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965601 | AG1-428 C O2 | Adder | 5.72 MW | 4.86 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965691 | AG1-437 C O1 | 80/20 | 14.33 MW | 14.33 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965701 | AG1-438 C O1 | 80/20 | 14.33 MW | 14.33 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965711 | AG1-439 C O1 | Adder | 32.26 MW | 27.42 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965721 | AG1-440 C | Adder | 8.84 MW | 7.51 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965731 | AG1-441 C | Adder | 8.84 MW | 7.51 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965741 | AG1-442 O1 | 80/20 | 8.36 MW | 8.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965751 | AG1-443 O1 | 80/20 | 8.36 MW | 8.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965761 | AG1-444 O1 | Adder | 17.2 MW | 14.62 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965771 | AG1-445 | Adder | 5.11 MW | 4.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965781 | AG1-446 | Adder | 5.11 MW | 4.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965811 | AG1-449 | 80/20 | 42.18 MW | 42.18 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 966361 | AG1-505 C | 80/20 | 29.3 MW | 29.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 966371 | AG1-506 C | 80/20 | 29.3 MW | 29.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 966621 | AG1-532 C | Adder | 1.76 MW | 1.5 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 313506 | AB1-173 C OP | Adder | 8.8 MW | 7.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314572 | 3EMPORIA | Adder | 0.54 MW | 0.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315131 | 1EDGECMA | Adder | 10.49 MW | 8.92 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315132 | 1EDGECMB | Adder | 10.49 MW | 8.92 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315153 | 1CLOVER1 | 80/20 | 19.29 MW | 19.29 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315154 | 1CLOVER2 | 80/20 | 19.11 MW | 19.11 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926070 | AC1-086 C | Adder | 27.46 MW | 23.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926201 | AC1-098 C | Adder | 8.26 MW | 7.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926211 | AC1-099 C | Adder | 2.77 MW | 2.35 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 927024 | AC1-189 C | Adder | 11.57 MW | 9.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 927145 | AC1-208 C | Adder | 12.01 MW | 10.21 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 927251 | AC1-221 C | Adder | 2.79 MW | 2.37 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 927261 | AC1-222 C | Adder | 4.3 MW | 3.65 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934311 | AD1-055 C | Adder | 2.98 MW | 2.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934331 | AD1-057 C O1 | Adder | 13.04 MW | 11.08 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934341 | AD1-058 C | Adder | 7.0 MW | 5.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934521 | AD1-076 C | 80/20 | 77.72 MW | 77.72 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934615 | AD1-087 C | 80/20 | 11.2 MW | 11.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934625 | AD1-088 C | Adder | 14.52 MW | 12.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934991 | AD1-131 C | Adder | 2.29 MW | 1.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935171 | AD1-152 C O1 | Adder | 11.41 MW | 9.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937481 | AD2-202 C O1 | 80/20 | 3.28 MW | 3.28 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942931 | AE2-313 C | 80/20 | 65.01 MW | 65.01 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943171 | AE2-346 C | Adder | 1.94 MW | 1.65 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943901 | AF1-058 C | Adder | 2.38 MW | 2.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944011 | AF1-069 C | 80/20 | 23.7 MW | 23.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944141 | AF1-082 | Adder | 3.78 MW | 3.21 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945811 | AF1-246 C O1 | 80/20 | 11.87 MW | 11.87 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 960061 | AF2-297 C | Adder | 9.52 MW | 8.1 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 960081 | AF2-299 C | Adder | 3.26 MW | 2.77 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315293 | 1DOMTR9 | Adder | 9.68 MW | 8.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315294 | 1DOMTR10 | Adder | 11.87 MW | 10.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 316118 | AC1-105 C | Adder | 6.72 MW | 5.71 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 316129 | AC1-054 C | Adder | 9.07 MW | 7.71 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 316140 | AB2-099 C | Adder | 0.81 MW | 0.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923262 | AB1-132 C OP | Adder | 18.65 MW | 15.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923991 | AB2-040 C O1 | Adder | 9.58 MW | 8.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924301 | AB2-077 C O1 | Adder | 2.18 MW | 1.86 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924311 | AB2-078 C O1 | Adder | 2.18 MW | 1.86 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924321 | AB2-079 C O1 | Adder | 2.18 MW | 1.86 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 925591 | AC1-034 C | Adder | 8.97 MW | 7.62 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932631 | AC2-084 C | Adder | 11.77 MW | 10.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932761 | AC2-100 C | Adder | 6.42 MW | 5.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939181 | AE1-148 C | Adder | 10.26 MW | 8.72 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940491 | AE2-034 C | 80/20 | 10.39 MW | 10.39 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940571 | AE2-044 C | Adder | 5.87 MW | 4.99 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940661 | AE2-053 O1 | Adder | 3.8 MW | 3.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941031 | AE2-094 C | 80/20 | 72.55 MW | 72.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941791 | AE2-182 C | Adder | 2.36 MW | 2.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 946281 | AF1-292 C | Adder | 1.93 MW | 1.64 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957481 | AF2-042 C | 80/20 | 84.76 MW | 84.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957521 | AF2-046 C | Adder | 23.11 MW | 19.64 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957531 | AF2-047 C | 80/20 | 24.7 MW | 24.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957861 | AF2-080 C | Adder | 10.51 MW | 8.94 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938771 | AE1-103 C | 80/20 | 4.08 MW | 4.08 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940481 | AE2-033 C | Adder | 20.26 MW | 17.22 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940641 | AE2-051 C O1 | 80/20 | 31.78 MW | 31.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 946011 | AF1-266 | Adder | 16.96 MW | 14.42 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 313526 | AB2-022 C | 80/20 | 0.59 MW | 0.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314491 | 3PENDLTN | 80/20 | 0.51 MW | 0.51 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314507 | 3THOMPSN | 80/20 | 0.51 MW | 0.51 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314638 | 6ELIZ CT | 80/20 | 0.34 MW | 0.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314639 | 6TANGLEW | 80/20 | 0.63 MW | 0.63 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314643 | 3O INLET | 80/20 | 0.69 MW | 0.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926661 | AC1-147 C | 80/20 | 0.57 MW | 0.57 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926754 | AC1-161 C | 80/20 | 49.31 MW | 49.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934061 | AD1-033 C | 80/20 | 11.4 MW | 11.4 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934575 | AD1-082 C | Adder | 8.14 MW | 6.92 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935111 | AD1-144 C | 80/20 | 0.41 MW | 0.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936661 | AD2-085 C | Adder | 4.49 MW | 3.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937221 | AD2-160 C O1 | 80/20 | 8.85 MW | 8.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942341 | AE2-247 C | Adder | 1.94 MW | 1.65 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942401 | AE2-253 C | 80/20 | 9.31 MW | 9.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943461 | AF1-017 C | Adder | 1.76 MW | 1.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943611 | AF1-032 C | 80/20 | 2.58 MW | 2.58 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943621 | AF1-033 C | Adder | 2.68 MW | 2.27 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944871 | AF1-152 C | 80/20 | 7.82 MW | 7.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315098 | 1CHESPKA | 80/20 | 0.68 MW | 0.68 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315099 | 1CHESPKB | 80/20 | 1.12 MW | 1.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315102 | 1BRUNSWICKG1 | 80/20 | 15.38 MW | 15.38 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315103 | 1BRUNSWICKG2 | 80/20 | 15.38 MW | 15.38 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315104 | 1BRUNSWICKG3 | 80/20 | 15.38 MW | 15.38 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315105 | 1BRUNSWICKS1 | 80/20 | 31.94 MW | 31.94 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315108 | 1ELIZAR1 | 80/20 | 5.01 MW | 5.01 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315109 | 1ELIZAR2 | 80/20 | 4.92 MW | 4.92 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315110 | 1ELIZAR3 | 80/20 | 5.07 MW | 5.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315233 | 1SURRY 2 | 80/20 | 39.58 MW | 39.58 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315241 | 1Z1-086 GT1 | 80/20 | 19.84 MW | 19.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315242 | 1Z1-086 GT2 | 80/20 | 19.84 MW | 19.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315243 | 1Z1-086 GT3 | 80/20 | 19.84 MW | 19.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315244 | 1Z1-086 ST | 80/20 | 34.49 MW | 34.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315260 | 1GOSPORTA | 80/20 | 0.54 MW | 0.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315261 | 1GOSPORTB | 80/20 | 0.69 MW | 0.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315262 | 1GOSPORTC | 80/20 | 0.59 MW | 0.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315603 | 6AA1-139SOLA | 80/20 | 3.61 MW | 3.61 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315605 | 6W1-029WIND | 80/20 | 1.73 MW | 1.73 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | 80/20 | 1.07 MW | 1.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932044 | AC2-012 C | 80/20 | 11.99 MW | 11.99 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932591 | AC2-079 C O1 | Adder | 7.02 MW | 5.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938535 | AE1-072 C | 80/20 | 26.45 MW | 26.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939195 | AE1-149 C | Adder | 10.54 MW | 8.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939414 | AE1-173_C1 | 80/20 | 55.96 MW | 55.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939415 | AE1-173_C2 | 80/20 | 47.97 MW | 47.97 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939416 | AE1-173_C3 | 80/20 | 55.96 MW | 55.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940541 | AE2-040 | Adder | 3.58 MW | 3.05 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940651 | AE2-052 | Adder | 3.52 MW | 2.99 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941101 | AE2-104 C O1 | 80/20 | 4.75 MW | 4.75 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 42.86 MW | 42.86 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 44.04 MW | 44.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 40.09 MW | 40.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957491 | AF2-043 C | 80/20 | 3.16 MW | 3.16 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 5.35 MW | 5.35 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 964951 | AG1-359 O1 | 80/20 | 34.64 MW | 34.64 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965001 | AG1-364 C O1 | 80/20 | 10.71 MW | 10.71 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933294 | AC2-141 C | 80/20 | 49.31 MW | 49.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941501 | AE2-147 C | 80/20 | 23.45 MW | 23.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 26.79 MW | 26.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957871 | AF2-081 C | 80/20 | 15.07 MW | 15.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958161 | AF2-110 C | 80/20 | 1.96 MW | 1.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 966611 | AG1-531 C | Adder | 6.61 MW | 5.62 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 74.49 MW | 74.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 74.49 MW | 74.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 74.49 MW | 74.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933981 | AD1-022 C | 80/20 | 12.45 MW | 12.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 960331 | AF2-324 C | Adder | 10.24 MW | 8.71 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 962561 | AG1-105 C O1 | Adder | 10.24 MW | 8.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 961681 | AG1-008 C | Adder | 23.16 MW | 19.68 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 962571 | AG1-106 C | Adder | 7.64 MW | 6.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965281 | AG1-393 C | Adder | 2.74 MW | 2.33 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315614 | AA2-178 C | 80/20 | 2.36 MW | 2.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 316083 | AB2-161 C | Adder | 3.57 MW | 3.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 961611 | AG1-000B C | Adder | 17.17 MW | 14.6 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 7.88 MW | 7.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.26 MW | 2.26 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 141.97 MW | 141.97 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 41.78 MW | 41.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 47.44 MW | 47.44 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 11.93 MW | 11.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 11.34 MW | 11.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.67 MW | 0.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.1 MW | 2.1 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.25 MW | 6.25 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.21 MW | 2.21 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.38 MW | 0.38 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 9.13 MW | 9.13 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.01 MW | 1.01 MW |
Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961671 | AG1-007 C | Adder | 1.26 MW | 1.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961941 | AG1-037 C | Adder | 0.67 MW | 0.57 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962331 | AG1-082 C | Adder | 2.69 MW | 2.29 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962341 | AG1-083 C | Adder | 2.69 MW | 2.29 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962491 | AG1-098 C O1 | Adder | 13.17 MW | 11.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963041 | AG1-153 C | 80/20 | 9.67 MW | 9.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963111 | AG1-160 C | 80/20 | 9.82 MW | 9.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963291 | AG1-178 C O2 | 80/20 | 110.08 MW | 110.08 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963301 | AG1-179 C | Adder | 6.92 MW | 5.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963311 | AG1-180 | Adder | 3.37 MW | 2.87 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963351 | AG1-184 O2 | 80/20 | 59.3 MW | 59.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 964791 | AG1-342 C | Adder | 4.85 MW | 4.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 964801 | AG1-343 C | Adder | 7.87 MW | 6.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966801 | AG1-551 C | Adder | 3.04 MW | 2.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966811 | AG1-552 C | Adder | 2.72 MW | 2.32 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965291 | AG1-394 C | Adder | 2.7 MW | 2.29 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965601 | AG1-428 C O2 | Adder | 5.77 MW | 4.91 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965691 | AG1-437 C O1 | Adder | 13.73 MW | 11.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965701 | AG1-438 C O1 | Adder | 13.73 MW | 11.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965711 | AG1-439 C O1 | Adder | 31.64 MW | 26.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965721 | AG1-440 C | Adder | 8.85 MW | 7.52 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965731 | AG1-441 C | Adder | 8.85 MW | 7.52 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965741 | AG1-442 O1 | Adder | 8.01 MW | 6.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965751 | AG1-443 O1 | Adder | 8.01 MW | 6.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965761 | AG1-444 O1 | Adder | 16.88 MW | 14.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965771 | AG1-445 | Adder | 5.11 MW | 4.35 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965781 | AG1-446 | Adder | 5.11 MW | 4.35 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965811 | AG1-449 | 80/20 | 40.75 MW | 40.75 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966361 | AG1-505 C | 80/20 | 28.39 MW | 28.39 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966371 | AG1-506 C | 80/20 | 28.39 MW | 28.39 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966621 | AG1-532 C | Adder | 1.77 MW | 1.51 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 313506 | AB1-173 C OP | Adder | 8.8 MW | 7.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314572 | 3EMPORIA | Adder | 0.55 MW | 0.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315131 | 1EDGECMA | Adder | 10.37 MW | 8.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315132 | 1EDGECMB | Adder | 10.37 MW | 8.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315153 | 1CLOVER1 | 80/20 | 18.96 MW | 18.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315154 | 1CLOVER2 | 80/20 | 18.78 MW | 18.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926070 | AC1-086 C | Adder | 27.29 MW | 23.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926201 | AC1-098 C | Adder | 8.1 MW | 6.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926211 | AC1-099 C | Adder | 2.72 MW | 2.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927024 | AC1-189 C | Adder | 11.33 MW | 9.63 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927145 | AC1-208 C | Adder | 11.83 MW | 10.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927251 | AC1-221 C | Adder | 2.79 MW | 2.37 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927261 | AC1-222 C | Adder | 4.33 MW | 3.68 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934311 | AD1-055 C | Adder | 3.01 MW | 2.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934331 | AD1-057 C O1 | Adder | 12.92 MW | 10.98 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934341 | AD1-058 C | Adder | 6.99 MW | 5.94 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934521 | AD1-076 C | Adder | 74.07 MW | 62.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934615 | AD1-087 C | 80/20 | 11.01 MW | 11.01 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934625 | AD1-088 C | Adder | 14.55 MW | 12.37 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934991 | AD1-131 C | Adder | 2.29 MW | 1.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935171 | AD1-152 C O1 | 80/20 | 11.26 MW | 11.26 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 937481 | AD2-202 C O1 | 80/20 | 3.22 MW | 3.22 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942931 | AE2-313 C | 80/20 | 62.81 MW | 62.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943171 | AE2-346 C | Adder | 1.88 MW | 1.6 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943901 | AF1-058 C | Adder | 2.38 MW | 2.03 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944011 | AF1-069 C | 80/20 | 22.89 MW | 22.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944141 | AF1-082 | Adder | 3.73 MW | 3.17 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 945811 | AF1-246 C O1 | 80/20 | 11.59 MW | 11.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960061 | AF2-297 C | Adder | 9.54 MW | 8.11 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960081 | AF2-299 C | Adder | 3.28 MW | 2.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315293 | 1DOMTR9 | Adder | 9.27 MW | 7.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315294 | 1DOMTR10 | Adder | 11.36 MW | 9.66 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316118 | AC1-105 C | Adder | 6.75 MW | 5.73 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316129 | AC1-054 C | Adder | 9.04 MW | 7.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316140 | AB2-099 C | Adder | 0.78 MW | 0.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923262 | AB1-132 C OP | Adder | 18.53 MW | 15.75 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923991 | AB2-040 C O1 | Adder | 9.58 MW | 8.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 924301 | AB2-077 C O1 | Adder | 2.21 MW | 1.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 924311 | AB2-078 C O1 | Adder | 2.21 MW | 1.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 924321 | AB2-079 C O1 | Adder | 2.21 MW | 1.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925591 | AC1-034 C | Adder | 8.86 MW | 7.53 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932631 | AC2-084 C | Adder | 11.55 MW | 9.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932761 | AC2-100 C | Adder | 6.42 MW | 5.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939181 | AE1-148 C | Adder | 10.31 MW | 8.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940491 | AE2-034 C | 80/20 | 9.85 MW | 9.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940571 | AE2-044 C | Adder | 5.8 MW | 4.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940661 | AE2-053 O1 | Adder | 3.82 MW | 3.25 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941031 | AE2-094 C | 80/20 | 70.04 MW | 70.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941791 | AE2-182 C | Adder | 2.36 MW | 2.01 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946281 | AF1-292 C | Adder | 1.95 MW | 1.66 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957481 | AF2-042 C | 80/20 | 82.8 MW | 82.8 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957521 | AF2-046 C | Adder | 22.41 MW | 19.05 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957531 | AF2-047 C | 80/20 | 23.4 MW | 23.4 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957861 | AF2-080 C | Adder | 10.29 MW | 8.74 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938771 | AE1-103 C | Adder | 3.9 MW | 3.32 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940481 | AE2-033 C | 80/20 | 20.85 MW | 20.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940641 | AE2-051 C O1 | 80/20 | 30.26 MW | 30.26 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946011 | AF1-266 | Adder | 17.46 MW | 14.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 313526 | AB2-022 C | 80/20 | 0.55 MW | 0.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314295 | 6BIRDNECK | 80/20 | 0.06 MW | 0.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314435 | 6SAPONY | 80/20 | 0.55 MW | 0.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314491 | 3PENDLTN | 80/20 | 0.47 MW | 0.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314507 | 3THOMPSN | 80/20 | 0.47 MW | 0.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314638 | 6ELIZ CT | 80/20 | 0.32 MW | 0.32 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314639 | 6TANGLEW | 80/20 | 0.58 MW | 0.58 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314643 | 3O INLET | 80/20 | 0.63 MW | 0.63 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926661 | AC1-147 C | 80/20 | 0.53 MW | 0.53 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926754 | AC1-161 C | 80/20 | 43.84 MW | 43.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934061 | AD1-033 C | 80/20 | 10.51 MW | 10.51 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934575 | AD1-082 C | Adder | 8.67 MW | 7.37 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935111 | AD1-144 C | 80/20 | 0.39 MW | 0.39 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936661 | AD2-085 C | Adder | 4.39 MW | 3.73 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 937221 | AD2-160 C O1 | 80/20 | 8.18 MW | 8.18 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942341 | AE2-247 C | Adder | 1.9 MW | 1.61 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942401 | AE2-253 C | 80/20 | 8.6 MW | 8.6 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943461 | AF1-017 C | Adder | 1.72 MW | 1.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943611 | AF1-032 C | 80/20 | 2.41 MW | 2.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943621 | AF1-033 C | Adder | 2.68 MW | 2.28 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944871 | AF1-152 C | 80/20 | 7.3 MW | 7.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315098 | 1CHESPKA | 80/20 | 0.63 MW | 0.63 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315099 | 1CHESPKB | 80/20 | 1.04 MW | 1.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315102 | 1BRUNSWICKG1 | 80/20 | 14.88 MW | 14.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315103 | 1BRUNSWICKG2 | 80/20 | 14.88 MW | 14.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315104 | 1BRUNSWICKG3 | 80/20 | 14.88 MW | 14.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315105 | 1BRUNSWICKS1 | 80/20 | 30.91 MW | 30.91 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315108 | 1ELIZAR1 | 80/20 | 4.63 MW | 4.63 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315109 | 1ELIZAR2 | 80/20 | 4.55 MW | 4.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315110 | 1ELIZAR3 | 80/20 | 4.69 MW | 4.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315233 | 1SURRY 2 | 80/20 | 33.69 MW | 33.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315241 | 1Z1-086 GT1 | 80/20 | 19.18 MW | 19.18 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315242 | 1Z1-086 GT2 | 80/20 | 19.18 MW | 19.18 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315243 | 1Z1-086 GT3 | 80/20 | 19.18 MW | 19.18 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315244 | 1Z1-086 ST | 80/20 | 33.34 MW | 33.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315260 | 1GOSPORTA | 80/20 | 0.5 MW | 0.5 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315261 | 1GOSPORTB | 80/20 | 0.64 MW | 0.64 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315262 | 1GOSPORTC | 80/20 | 0.54 MW | 0.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315603 | 6AA1-139SOLA | 80/20 | 3.33 MW | 3.33 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315605 | 6W1-029WIND | 80/20 | 1.62 MW | 1.62 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315611 | 6Z1-036WIND | 80/20 | 1.0 MW | 1.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932044 | AC2-012 C | 80/20 | 11.1 MW | 11.1 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932591 | AC2-079 C O1 | Adder | 7.04 MW | 5.98 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938535 | AE1-072 C | 80/20 | 24.48 MW | 24.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939195 | AE1-149 C | Adder | 11.58 MW | 9.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939414 | AE1-173_C1 | 80/20 | 52.92 MW | 52.92 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939415 | AE1-173_C2 | 80/20 | 45.36 MW | 45.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939416 | AE1-173_C3 | 80/20 | 52.92 MW | 52.92 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940541 | AE2-040 | 80/20 | 3.7 MW | 3.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940651 | AE2-052 | Adder | 3.86 MW | 3.28 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941101 | AE2-104 C O1 | 80/20 | 4.5 MW | 4.5 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941281 | AE2-122 C O1 | 80/20 | 39.58 MW | 39.58 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941291 | AE2-123 C O1 | 80/20 | 40.68 MW | 40.68 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941301 | AE2-124 C O1 | 80/20 | 37.02 MW | 37.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957491 | AF2-043 C | 80/20 | 2.95 MW | 2.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957631 | AF2-057 | 80/20 | 4.95 MW | 4.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 964951 | AG1-359 O1 | 80/20 | 31.93 MW | 31.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965001 | AG1-364 C O1 | 80/20 | 9.91 MW | 9.91 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933294 | AC2-141 C | 80/20 | 43.84 MW | 43.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941501 | AE2-147 C | 80/20 | 21.9 MW | 21.9 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941591 | AE2-156 O1 | 80/20 | 24.78 MW | 24.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957871 | AF2-081 C | 80/20 | 13.93 MW | 13.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958161 | AF2-110 C | 80/20 | 1.86 MW | 1.86 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966611 | AG1-531 C | Adder | 6.54 MW | 5.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944581 | AF1-123 C O1 | 80/20 | 68.19 MW | 68.19 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944591 | AF1-124 C O1 | 80/20 | 68.19 MW | 68.19 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944601 | AF1-125 C O1 | 80/20 | 68.19 MW | 68.19 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933981 | AD1-022 C | Adder | 11.9 MW | 10.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960331 | AF2-324 C | Adder | 10.12 MW | 8.6 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962561 | AG1-105 C O1 | Adder | 10.31 MW | 8.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961681 | AG1-008 C | Adder | 22.46 MW | 19.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962571 | AG1-106 C | Adder | 7.59 MW | 6.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965281 | AG1-393 C | 80/20 | 2.83 MW | 2.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315614 | AA2-178 C | 80/20 | 2.24 MW | 2.24 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316083 | AB2-161 C | Adder | 3.81 MW | 3.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961611 | AG1-000B C | Adder | 17.57 MW | 14.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 7.89 MW | 7.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.47 MW | 2.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 144.81 MW | 144.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 49.17 MW | 49.17 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 52.33 MW | 52.33 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 11.95 MW | 11.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.27 MW | 12.27 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.69 MW | 0.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.47 MW | 2.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.13 MW | 7.13 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.54 MW | 2.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.44 MW | 0.44 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 9.91 MW | 9.91 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.19 MW | 1.19 MW |
Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 961671 | AG1-007 C | Adder | 1.27 MW | 1.08 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 961941 | AG1-037 C | Adder | 0.7 MW | 0.6 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 962331 | AG1-082 C | Adder | 2.81 MW | 2.38 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 962341 | AG1-083 C | Adder | 2.81 MW | 2.38 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 962491 | AG1-098 C O1 | Adder | 14.33 MW | 12.18 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963041 | AG1-153 C | 80/20 | 8.79 MW | 8.79 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963111 | AG1-160 C | 80/20 | 8.91 MW | 8.91 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963291 | AG1-178 C O2 | 80/20 | 100.91 MW | 100.91 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963301 | AG1-179 C | Adder | 7.38 MW | 6.28 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963311 | AG1-180 | Adder | 3.6 MW | 3.06 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963321 | AG1-181 C O1 | Adder | 19.78 MW | 16.81 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963351 | AG1-184 O2 | 80/20 | 54.36 MW | 54.36 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963361 | AG1-185 O1 | Adder | 9.57 MW | 8.13 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 964111 | AG1-272 C | Adder | 3.0 MW | 2.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 964121 | AG1-273 C | Adder | 3.0 MW | 2.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 964131 | AG1-274 C | Adder | 3.0 MW | 2.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 964241 | AG1-285 C O1 | Adder | 14.93 MW | 12.69 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 964791 | AG1-342 C | Adder | 5.01 MW | 4.26 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 964801 | AG1-343 C | Adder | 8.29 MW | 7.05 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 966801 | AG1-551 C | Adder | 3.11 MW | 2.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 966811 | AG1-552 C | Adder | 2.84 MW | 2.42 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965191 | AG1-384 C | Adder | 3.0 MW | 2.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965291 | AG1-394 C | Adder | 2.85 MW | 2.42 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965591 | AG1-427 C | Adder | 14.14 MW | 12.02 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965601 | AG1-428 C O2 | Adder | 6.16 MW | 5.24 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965691 | AG1-437 C O1 | Adder | 14.31 MW | 12.16 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965701 | AG1-438 C O1 | Adder | 14.31 MW | 12.16 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965711 | AG1-439 C O1 | Adder | 31.92 MW | 27.14 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965721 | AG1-440 C | Adder | 9.29 MW | 7.89 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965731 | AG1-441 C | Adder | 9.29 MW | 7.89 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965741 | AG1-442 O1 | Adder | 8.35 MW | 7.1 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965751 | AG1-443 O1 | Adder | 8.35 MW | 7.1 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965761 | AG1-444 O1 | Adder | 17.03 MW | 14.47 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965771 | AG1-445 | Adder | 5.36 MW | 4.56 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965781 | AG1-446 | Adder | 5.36 MW | 4.56 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965811 | AG1-449 | 80/20 | 36.95 MW | 36.95 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 966361 | AG1-505 C | 80/20 | 26.04 MW | 26.04 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 966371 | AG1-506 C | 80/20 | 26.04 MW | 26.04 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 966621 | AG1-532 C | Adder | 1.87 MW | 1.59 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 313506 | AB1-173 C OP | Adder | 9.23 MW | 7.85 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314572 | 3EMPORIA | Adder | 0.58 MW | 0.49 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315131 | 1EDGECMA | Adder | 10.38 MW | 8.83 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315132 | 1EDGECMB | Adder | 10.38 MW | 8.83 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315153 | 1CLOVER1 | 80/20 | 18.47 MW | 18.47 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926070 | AC1-086 C | Adder | 28.32 MW | 24.07 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926201 | AC1-098 C | Adder | 8.32 MW | 7.07 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926211 | AC1-099 C | Adder | 2.79 MW | 2.37 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 927024 | AC1-189 C | Adder | 11.46 MW | 9.74 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 927145 | AC1-208 C | Adder | 12.14 MW | 10.31 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934331 | AD1-057 C O1 | Adder | 13.15 MW | 11.17 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934521 | AD1-076 C | Adder | 77.37 MW | 65.77 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934615 | AD1-087 C | Adder | 10.72 MW | 9.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934625 | AD1-088 C | Adder | 15.89 MW | 13.5 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 935171 | AD1-152 C O1 | Adder | 10.98 MW | 9.34 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936265 | AD2-033 C | Adder | 15.28 MW | 12.99 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 937481 | AD2-202 C O1 | Adder | 3.14 MW | 2.67 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942931 | AE2-313 C | 80/20 | 56.97 MW | 56.97 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943171 | AE2-346 C | Adder | 1.96 MW | 1.67 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943901 | AF1-058 C | Adder | 2.37 MW | 2.02 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944011 | AF1-069 C | 80/20 | 20.68 MW | 20.68 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944141 | AF1-082 | Adder | 3.74 MW | 3.18 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 945811 | AF1-246 C O1 | 80/20 | 11.01 MW | 11.01 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 959311 | AF2-222 C | Adder | 19.41 MW | 16.5 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 960061 | AF2-297 C | Adder | 9.49 MW | 8.07 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 960081 | AF2-299 C | Adder | 3.46 MW | 2.94 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315293 | 1DOMTR9 | Adder | 9.63 MW | 8.19 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315294 | 1DOMTR10 | Adder | 11.8 MW | 10.03 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 316118 | AC1-105 C | Adder | 6.84 MW | 5.82 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 316129 | AC1-054 C | Adder | 9.47 MW | 8.05 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 316140 | AB2-099 C | Adder | 0.82 MW | 0.7 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 923262 | AB1-132 C OP | Adder | 19.23 MW | 16.34 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 923991 | AB2-040 C O1 | Adder | 10.05 MW | 8.54 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 924301 | AB2-077 C O1 | Adder | 2.41 MW | 2.05 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 924311 | AB2-078 C O1 | Adder | 2.41 MW | 2.05 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 924321 | AB2-079 C O1 | Adder | 2.41 MW | 2.05 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 925591 | AC1-034 C | Adder | 8.88 MW | 7.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932631 | AC2-084 C | Adder | 11.86 MW | 10.08 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939181 | AE1-148 C | Adder | 10.92 MW | 9.28 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940491 | AE2-034 C | 80/20 | 10.33 MW | 10.33 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940571 | AE2-044 C | Adder | 5.82 MW | 4.94 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940661 | AE2-053 O1 | Adder | 4.04 MW | 3.44 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941031 | AE2-094 C | 80/20 | 63.29 MW | 63.29 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941791 | AE2-182 C | Adder | 2.58 MW | 2.19 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 946281 | AF1-292 C | Adder | 2.05 MW | 1.75 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957481 | AF2-042 C | 80/20 | 78.64 MW | 78.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957521 | AF2-046 C | Adder | 23.5 MW | 19.98 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957531 | AF2-047 C | 80/20 | 24.54 MW | 24.54 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957861 | AF2-080 C | Adder | 10.4 MW | 8.84 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938771 | AE1-103 C | 80/20 | 4.17 MW | 4.17 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940481 | AE2-033 C | 80/20 | 22.08 MW | 22.08 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940641 | AE2-051 C O1 | 80/20 | 27.88 MW | 27.88 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 946011 | AF1-266 | 80/20 | 18.48 MW | 18.48 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933501 | AC2-165 C | Adder | 12.21 MW | 10.38 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 313526 | AB2-022 C | 80/20 | 0.58 MW | 0.58 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314435 | 6SAPONY | 80/20 | 0.59 MW | 0.59 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314491 | 3PENDLTN | 80/20 | 0.51 MW | 0.51 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314507 | 3THOMPSN | 80/20 | 0.51 MW | 0.51 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314638 | 6ELIZ CT | 80/20 | 0.34 MW | 0.34 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314639 | 6TANGLEW | 80/20 | 0.62 MW | 0.62 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314643 | 3O INLET | 80/20 | 0.67 MW | 0.67 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315060 | 1CHESTF5 | Adder | 68.83 MW | 58.5 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315065 | 1CHESTF6 | Adder | 115.83 MW | 98.45 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315083 | 1SPRUNCA | Adder | 12.39 MW | 10.53 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315084 | 1SPRUNCB | Adder | 12.39 MW | 10.53 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926661 | AC1-147 C | 80/20 | 0.57 MW | 0.57 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926754 | AC1-161 C | 80/20 | 46.21 MW | 46.21 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926784 | AC1-164 C | Adder | 42.9 MW | 36.47 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934014 | AD1-025 C | Adder | 21.44 MW | 18.22 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934061 | AD1-033 C | 80/20 | 11.17 MW | 11.17 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934575 | AD1-082 C | Adder | 10.28 MW | 8.74 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 935111 | AD1-144 C | 80/20 | 0.42 MW | 0.42 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 935164 | AD1-151 C | Adder | 20.11 MW | 17.09 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936661 | AD2-085 C | 80/20 | 4.86 MW | 4.86 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936761 | AD2-097 C | Adder | 2.35 MW | 2.0 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 937221 | AD2-160 C O1 | 80/20 | 8.68 MW | 8.68 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942161 | AE2-228 C | Adder | 2.49 MW | 2.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942341 | AE2-247 C | 80/20 | 2.11 MW | 2.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942371 | AE2-250 C O1 | Adder | 11.78 MW | 10.01 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942401 | AE2-253 C | 80/20 | 9.13 MW | 9.13 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942551 | AE2-270 | Adder | 33.9 MW | 28.81 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943461 | AF1-017 C | 80/20 | 1.91 MW | 1.91 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943611 | AF1-032 C | 80/20 | 2.57 MW | 2.57 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943621 | AF1-033 C | Adder | 3.19 MW | 2.71 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944631 | AF1-128 O1 | Adder | 43.07 MW | 36.61 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944871 | AF1-152 C | 80/20 | 7.74 MW | 7.74 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 945361 | AF1-201 C O1 | Adder | 20.2 MW | 17.17 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 958501 | AF2-144 C | Adder | 2.35 MW | 2.0 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 961711 | AG1-011 | Adder | 36.41 MW | 30.95 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315098 | 1CHESPKA | 80/20 | 0.67 MW | 0.67 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315099 | 1CHESPKB | 80/20 | 1.11 MW | 1.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315102 | 1BRUNSWICKG1 | 80/20 | 13.52 MW | 13.52 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315103 | 1BRUNSWICKG2 | 80/20 | 13.52 MW | 13.52 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315104 | 1BRUNSWICKG3 | 80/20 | 13.52 MW | 13.52 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315105 | 1BRUNSWICKS1 | 80/20 | 28.08 MW | 28.08 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315108 | 1ELIZAR1 | 80/20 | 4.95 MW | 4.95 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315109 | 1ELIZAR2 | 80/20 | 4.86 MW | 4.86 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315110 | 1ELIZAR3 | 80/20 | 5.01 MW | 5.01 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315233 | 1SURRY 2 | 80/20 | 37.85 MW | 37.85 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315241 | 1Z1-086 GT1 | 80/20 | 17.4 MW | 17.4 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315242 | 1Z1-086 GT2 | 80/20 | 17.4 MW | 17.4 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315243 | 1Z1-086 GT3 | 80/20 | 17.4 MW | 17.4 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315244 | 1Z1-086 ST | 80/20 | 30.24 MW | 30.24 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315260 | 1GOSPORTA | 80/20 | 0.54 MW | 0.54 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315261 | 1GOSPORTB | 80/20 | 0.69 MW | 0.69 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315262 | 1GOSPORTC | 80/20 | 0.58 MW | 0.58 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315603 | 6AA1-139SOLA | 80/20 | 3.54 MW | 3.54 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315605 | 6W1-029WIND | 80/20 | 1.71 MW | 1.71 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315611 | 6Z1-036WIND | 80/20 | 1.06 MW | 1.06 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 316108 | AB2-160 C | Adder | 6.63 MW | 5.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 316132 | AB2-190 C | Adder | 23.52 MW | 20.0 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 316258 | AE1-162 C | 80/20 | 0.51 MW | 0.51 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932044 | AC2-012 C | 80/20 | 11.88 MW | 11.88 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932591 | AC2-079 C O1 | 80/20 | 7.96 MW | 7.96 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938535 | AE1-072 C | 80/20 | 25.98 MW | 25.98 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939195 | AE1-149 C | Adder | 14.02 MW | 11.92 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939414 | AE1-173_C1 | 80/20 | 50.22 MW | 50.22 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939415 | AE1-173_C2 | 80/20 | 43.05 MW | 43.05 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939416 | AE1-173_C3 | 80/20 | 50.22 MW | 50.22 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939431 | AE1-175 C | Adder | 3.0 MW | 2.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940431 | AE2-027 C O1 | Adder | 14.87 MW | 12.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940541 | AE2-040 | 80/20 | 3.92 MW | 3.92 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940651 | AE2-052 | Adder | 4.67 MW | 3.97 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941101 | AE2-104 C O1 | 80/20 | 4.86 MW | 4.86 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941281 | AE2-122 C O1 | 80/20 | 42.2 MW | 42.2 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941291 | AE2-123 C O1 | 80/20 | 43.37 MW | 43.37 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941301 | AE2-124 C O1 | 80/20 | 39.44 MW | 39.44 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 946261 | AF1-291 C | Adder | 2.48 MW | 2.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957491 | AF2-043 C | 80/20 | 3.14 MW | 3.14 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957631 | AF2-057 | 80/20 | 5.3 MW | 5.3 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957711 | AF2-065 C | Adder | 17.29 MW | 14.7 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 962531 | AG1-102 C | Adder | 1.33 MW | 1.13 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 962961 | AG1-145 C | Adder | 2.7 MW | 2.3 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963221 | AG1-171 C | Adder | 2.73 MW | 2.32 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963231 | AG1-172 C | Adder | 2.73 MW | 2.32 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963241 | AG1-173 C | Adder | 2.73 MW | 2.32 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 963251 | AG1-174 C | Adder | 2.73 MW | 2.32 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 964951 | AG1-359 O1 | 80/20 | 33.93 MW | 33.93 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965001 | AG1-364 C O1 | 80/20 | 10.61 MW | 10.61 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933294 | AC2-141 C | 80/20 | 46.21 MW | 46.21 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941501 | AE2-147 C | 80/20 | 23.22 MW | 23.22 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941591 | AE2-156 O1 | 80/20 | 26.52 MW | 26.52 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942001 | AE2-212 C | Adder | 2.61 MW | 2.22 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957831 | AF2-077 C | Adder | 2.6 MW | 2.21 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957871 | AF2-081 C | 80/20 | 14.79 MW | 14.79 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957911 | AF2-085 | 80/20 | 5.88 MW | 5.88 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 958161 | AF2-110 C | 80/20 | 2.0 MW | 2.0 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 966611 | AG1-531 C | Adder | 7.81 MW | 6.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944581 | AF1-123 C O1 | 80/20 | 72.03 MW | 72.03 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944591 | AF1-124 C O1 | 80/20 | 72.03 MW | 72.03 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944601 | AF1-125 C O1 | 80/20 | 72.03 MW | 72.03 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933981 | AD1-022 C | Adder | 12.42 MW | 10.56 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 960331 | AF2-324 C | Adder | 10.14 MW | 8.62 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 962561 | AG1-105 C O1 | Adder | 10.76 MW | 9.14 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 961681 | AG1-008 C | Adder | 23.55 MW | 20.02 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 962271 | AG1-075 C O1 | Adder | 20.33 MW | 17.28 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 962571 | AG1-106 C | Adder | 7.88 MW | 6.69 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 965281 | AG1-393 C | 80/20 | 3.0 MW | 3.0 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315614 | AA2-178 C | 80/20 | 2.35 MW | 2.35 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 316083 | AB2-161 C | Adder | 4.51 MW | 3.83 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 961611 | AG1-000B C | Adder | 21.22 MW | 18.04 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 7.51 MW | 7.51 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.24 MW | 2.24 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 136.24 MW | 136.24 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.27 MW | 42.27 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 47.05 MW | 47.05 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 11.37 MW | 11.37 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 11.16 MW | 11.16 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.66 MW | 0.66 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.15 MW | 2.15 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.27 MW | 6.27 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.44 MW | 2.44 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.38 MW | 0.38 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 9.02 MW | 9.02 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.03 MW | 1.03 MW |
Details for 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 961791 | AG1-021 C | 80/20 | 1.85 MW | 1.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 961891 | AG1-030 C | 80/20 | 13.82 MW | 13.82 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 962491 | AG1-098 C O1 | 80/20 | 20.69 MW | 20.69 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963041 | AG1-153 C | 80/20 | 17.6 MW | 17.6 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963111 | AG1-160 C | 80/20 | 18.44 MW | 18.44 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963171 | AG1-166 C | 80/20 | 1.85 MW | 1.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963181 | AG1-167 C | 80/20 | 1.85 MW | 1.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963191 | AG1-168 C | 80/20 | 1.85 MW | 1.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963201 | AG1-169 C | 80/20 | 1.85 MW | 1.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963211 | AG1-170 C | 80/20 | 1.85 MW | 1.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963321 | AG1-181 C O1 | 80/20 | 15.44 MW | 15.44 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963361 | AG1-185 O1 | 80/20 | 7.47 MW | 7.47 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964111 | AG1-272 C | 80/20 | 2.36 MW | 2.36 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964121 | AG1-273 C | 80/20 | 2.36 MW | 2.36 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964131 | AG1-274 C | 80/20 | 2.36 MW | 2.36 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964241 | AG1-285 C O1 | 80/20 | 11.41 MW | 11.41 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964791 | AG1-342 C | 80/20 | 5.47 MW | 5.47 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966691 | AG1-539 C | 80/20 | 5.64 MW | 5.64 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966761 | AG1-547 C | 80/20 | 3.77 MW | 3.77 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965191 | AG1-384 C | 80/20 | 2.36 MW | 2.36 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965591 | AG1-427 C | 80/20 | 10.81 MW | 10.81 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965641 | AG1-432 C O1 | 80/20 | 18.63 MW | 18.63 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965721 | AG1-440 C | 80/20 | 5.26 MW | 5.26 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965731 | AG1-441 C | 80/20 | 5.26 MW | 5.26 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965771 | AG1-445 | 80/20 | 3.04 MW | 3.04 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965781 | AG1-446 | 80/20 | 3.04 MW | 3.04 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965811 | AG1-449 | 80/20 | 68.22 MW | 68.22 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965831 | AG1-451 | 80/20 | 3.1 MW | 3.1 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966361 | AG1-505 C | 80/20 | 48.35 MW | 48.35 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966371 | AG1-506 C | 80/20 | 48.35 MW | 48.35 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 247284 | 05LEESVG | 80/20 | 0.93 MW | 0.93 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 314429 | 3JTRSVLE | 80/20 | 0.42 MW | 0.42 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315153 | 1CLOVER1 | 80/20 | 30.43 MW | 30.43 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315154 | 1CLOVER2 | 80/20 | 30.14 MW | 30.14 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315158 | 1KERR 1 | 80/20 | 0.35 MW | 0.35 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315159 | 1KERR 2 | 80/20 | 0.98 MW | 0.98 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315160 | 1KERR 3 | 80/20 | 0.98 MW | 0.98 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315161 | 1KERR 4 | 80/20 | 0.98 MW | 0.98 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315162 | 1KERR 5 | 80/20 | 0.98 MW | 0.98 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926023 | AC1-080 C | 80/20 | 0.43 MW | 0.43 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926051 | AC1-083 C O1 | 80/20 | 4.86 MW | 4.86 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926645 | AC1-145 C | 80/20 | 0.38 MW | 0.38 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 927251 | AC1-221 C | 80/20 | 3.73 MW | 3.73 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 927261 | AC1-222 C | 80/20 | 5.71 MW | 5.71 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 933941 | AD1-017 C | 80/20 | 0.97 MW | 0.97 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934311 | AD1-055 C | 80/20 | 3.96 MW | 3.96 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934341 | AD1-058 C | 80/20 | 9.36 MW | 9.36 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934615 | AD1-087 C | 80/20 | 17.65 MW | 17.65 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934625 | AD1-088 C | 80/20 | 22.84 MW | 22.84 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934991 | AD1-131 C | 80/20 | 3.07 MW | 3.07 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 935171 | AD1-152 C O1 | 80/20 | 17.29 MW | 17.29 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 936161 | AD2-022 C O1 | 80/20 | 12.6 MW | 12.6 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 936171 | AD2-023 C O1 | 80/20 | 7.35 MW | 7.35 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 936265 | AD2-033 C | 80/20 | 11.91 MW | 11.91 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 937481 | AD2-202 C O1 | 80/20 | 5.17 MW | 5.17 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942461 | AE2-259 C O1 | 80/20 | 9.31 MW | 9.31 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942671 | AE2-283 C | 80/20 | 4.59 MW | 4.59 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942751 | AE2-291 C | 80/20 | 10.79 MW | 10.79 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942761 | AE2-292 C O1 | 80/20 | 13.43 MW | 13.43 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942931 | AE2-313 C | 80/20 | 105.35 MW | 105.35 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943811 | AF1-049 C | 80/20 | 9.05 MW | 9.05 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943901 | AF1-058 C | 80/20 | 3.16 MW | 3.16 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 944141 | AF1-082 | 80/20 | 1.87 MW | 1.87 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 945811 | AF1-246 C O1 | 80/20 | 19.09 MW | 19.09 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 958801 | AF2-171 C | 80/20 | 13.85 MW | 13.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 959311 | AF2-222 C | 80/20 | 15.31 MW | 15.31 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 960061 | AF2-297 C | 80/20 | 12.65 MW | 12.65 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 961121 | AF2-403 | 80/20 | 0.93 MW | 0.93 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315163 | 1KERR 6 | 80/20 | 0.98 MW | 0.98 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315164 | 1KERR 7 | 80/20 | 0.98 MW | 0.98 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315266 | 1PLYWOOD A | 80/20 | 1.88 MW | 1.88 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316020 | AB2-059 C OP | 80/20 | 1.17 MW | 1.17 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316118 | AC1-105 C | 80/20 | 8.29 MW | 8.29 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316131 | AB2-060 C | 80/20 | 1.41 MW | 1.41 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 922922 | AB1-081 C OP | 80/20 | 0.99 MW | 0.99 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 924301 | AB2-077 C O1 | 80/20 | 1.85 MW | 1.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 924311 | AB2-078 C O1 | 80/20 | 1.85 MW | 1.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 924321 | AB2-079 C O1 | 80/20 | 1.85 MW | 1.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 925591 | AC1-034 C | 80/20 | 4.44 MW | 4.44 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 925611 | AC1-036 C | 80/20 | 0.22 MW | 0.22 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 925661 | AC1-042 C | 80/20 | 1.85 MW | 1.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 932761 | AC2-100 C | 80/20 | 8.59 MW | 8.59 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 938371 | AE1-056 C | 80/20 | 5.99 MW | 5.99 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 939181 | AE1-148 C | 80/20 | 7.56 MW | 7.56 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940081 | AE1-250 C | 80/20 | 13.17 MW | 13.17 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940571 | AE2-044 C | 80/20 | 2.9 MW | 2.9 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940661 | AE2-053 O1 | 80/20 | 2.8 MW | 2.8 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941431 | AE2-140 C O1 | 80/20 | 13.82 MW | 13.82 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941791 | AE2-182 C | 80/20 | 3.71 MW | 3.71 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941801 | AE2-185 C | 80/20 | 4.17 MW | 4.17 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941821 | AE2-187 C | 80/20 | 4.17 MW | 4.17 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 946301 | AF1-294 C | 80/20 | 3.79 MW | 3.79 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 957481 | AF2-042 C | 80/20 | 136.39 MW | 136.39 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 958211 | AF2-115 C | 80/20 | 2.31 MW | 2.31 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926754 | AC1-161 C | Adder | -31.93 MW | -27.14 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934061 | AD1-033 C | Adder | -7.2 MW | -6.12 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 937221 | AD2-160 C O1 | Adder | -5.42 MW | -4.61 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942401 | AE2-253 C | Adder | -5.7 MW | -4.85 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943611 | AF1-032 C | Adder | -1.56 MW | -1.32 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943621 | AF1-033 C | Adder | -2.13 MW | -1.81 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315102 | 1BRUNSWICKG1 | 80/20 | 27.08 MW | 27.08 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315103 | 1BRUNSWICKG2 | 80/20 | 27.08 MW | 27.08 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315104 | 1BRUNSWICKG3 | 80/20 | 27.08 MW | 27.08 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315105 | 1BRUNSWICKS1 | 80/20 | 56.26 MW | 56.26 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315241 | 1Z1-086 GT1 | 80/20 | 36.01 MW | 36.01 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315242 | 1Z1-086 GT2 | 80/20 | 36.01 MW | 36.01 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315243 | 1Z1-086 GT3 | 80/20 | 36.01 MW | 36.01 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315244 | 1Z1-086 ST | 80/20 | 62.59 MW | 62.59 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 932044 | AC2-012 C | Adder | -7.78 MW | -6.61 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 938741 | AE1-100 C O1 | 80/20 | 4.44 MW | 4.44 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 939431 | AE1-175 C | Adder | -2.09 MW | -1.78 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940601 | AE2-047 C O1 | 80/20 | 4.11 MW | 4.11 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 957491 | AF2-043 C | Adder | -1.91 MW | -1.62 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 962961 | AG1-145 C | Adder | -1.89 MW | -1.6 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 962561 | AG1-105 C O1 | 80/20 | 11.17 MW | 11.17 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 313527 | AB2-043 C | 80/20 | 0.49 MW | 0.49 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316123 | AC1-075 C | 80/20 | 1.29 MW | 1.29 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 9.63 MW | 9.63 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.07 MW | 3.07 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 180.98 MW | 180.98 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.2 MW | 62.2 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 65.2 MW | 65.2 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 14.58 MW | 14.58 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.29 MW | 15.29 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.82 MW | 0.82 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.05 MW | 3.05 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.9 MW | 8.9 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.07 MW | 2.07 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.55 MW | 0.55 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.3 MW | 12.3 MW |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.49 MW | 1.49 MW |
Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | 80/20 | 0.34 MW | 0.34 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | Adder | 0.15 MW | 0.13 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | Adder | 0.6 MW | 0.51 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | Adder | 0.6 MW | 0.51 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 1.93 MW | 1.93 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 1.96 MW | 1.96 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 20.41 MW | 20.41 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 3.04 MW | 3.04 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.48 MW | 1.48 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 10.99 MW | 10.99 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964241 | AG1-285 C O1 | 80/20 | 3.94 MW | 3.94 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 0.94 MW | 0.94 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965591 | AG1-427 C | 80/20 | 3.72 MW | 3.72 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 2.54 MW | 2.54 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | 80/20 | 8.24 MW | 8.24 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | 80/20 | 2.69 MW | 2.69 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | 80/20 | 2.69 MW | 2.69 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | 80/20 | 4.4 MW | 4.4 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | 80/20 | 1.56 MW | 1.56 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | 80/20 | 1.56 MW | 1.56 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 8.09 MW | 8.09 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 5.68 MW | 5.68 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 5.68 MW | 5.68 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 0.91 MW | 0.91 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 3.86 MW | 3.86 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313719 | 3CHESTNUT | 80/20 | 0.47 MW | 0.47 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.27 MW | 0.27 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.13 MW | 0.13 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.64 MW | 0.64 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.61 MW | 0.61 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | 80/20 | 2.99 MW | 2.99 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | 80/20 | 2.99 MW | 2.99 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 1.14 MW | 1.14 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.71 MW | 0.71 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.53 MW | 0.53 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.71 MW | 1.71 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315159 | 1KERR 2 | 80/20 | 0.41 MW | 0.41 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315160 | 1KERR 3 | 80/20 | 0.41 MW | 0.41 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.41 MW | 0.41 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.41 MW | 0.41 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.06 MW | 0.06 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | 80/20 | 11.26 MW | 11.26 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.29 MW | 2.29 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.77 MW | 0.77 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | 80/20 | 2.85 MW | 2.85 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 3.57 MW | 3.57 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 4.46 MW | 4.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934615 | AD1-087 C | Adder | 2.26 MW | 1.92 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937481 | AD2-202 C O1 | Adder | 0.66 MW | 0.56 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 12.48 MW | 12.48 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | Adder | 0.42 MW | 0.36 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.54 MW | 4.54 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | 80/20 | 1.07 MW | 1.07 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | 80/20 | 2.35 MW | 2.35 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.68 MW | 1.68 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.41 MW | 0.41 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.41 MW | 0.41 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315601 | 1CONETOE2SOL | 80/20 | 0.5 MW | 0.5 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.66 MW | 0.66 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316020 | AB2-059 C OP | 80/20 | 0.67 MW | 0.67 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | 80/20 | 2.88 MW | 2.88 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316131 | AB2-060 C | 80/20 | 0.5 MW | 0.5 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | Adder | 0.18 MW | 0.15 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 922922 | AB1-081 C OP | 80/20 | 0.57 MW | 0.57 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 7.64 MW | 7.64 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 4.2 MW | 4.2 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924301 | AB2-077 C O1 | 80/20 | 0.66 MW | 0.66 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924311 | AB2-078 C O1 | 80/20 | 0.66 MW | 0.66 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924321 | AB2-079 C O1 | 80/20 | 0.66 MW | 0.66 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | 80/20 | 2.54 MW | 2.54 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.26 MW | 3.26 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C | 80/20 | 3.06 MW | 3.06 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | 80/20 | 1.66 MW | 1.66 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | 80/20 | 1.13 MW | 1.13 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 13.9 MW | 13.9 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 1.0 MW | 1.0 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | 80/20 | 16.81 MW | 16.81 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | 80/20 | 2.59 MW | 2.59 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 15.62 MW | 15.62 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 5.6 MW | 5.6 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 13.08 MW | 13.08 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.43 MW | 0.43 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | Adder | -9.78 MW | -8.31 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | -0.63 MW | -0.54 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 2.97 MW | 2.97 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.97 MW | 2.97 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.97 MW | 2.97 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 6.17 MW | 6.17 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.71 MW | 1.71 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 3.82 MW | 3.82 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 3.82 MW | 3.82 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 3.82 MW | 3.82 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 6.65 MW | 6.65 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.53 MW | 0.53 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.71 MW | 0.71 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316096 | AB2-100 C1 | 80/20 | 0.76 MW | 0.76 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316098 | AB2-100 C2 | 80/20 | 0.76 MW | 0.76 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | Adder | 8.67 MW | 7.37 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | Adder | 7.43 MW | 6.32 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | Adder | 8.67 MW | 7.37 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | 80/20 | 2.85 MW | 2.85 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | 80/20 | 2.92 MW | 2.92 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962561 | AG1-105 C O1 | Adder | 2.72 MW | 2.31 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | 80/20 | 3.13 MW | 3.13 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | 80/20 | 2.18 MW | 2.18 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313527 | AB2-043 C | 80/20 | 0.18 MW | 0.18 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | Adder | -4.29 MW | -3.65 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.78 MW | 1.78 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 31.91 MW | 31.91 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.55 MW | 10.55 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.16 MW | 11.16 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.62 MW | 2.62 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.52 MW | 0.52 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.52 MW | 1.52 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.11 MW | 2.11 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 961671 | AG1-007 C | 80/20 | 1.07 MW | 1.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 961941 | AG1-037 C | 80/20 | 0.53 MW | 0.53 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 962331 | AG1-082 C | 80/20 | 2.11 MW | 2.11 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 962341 | AG1-083 C | 80/20 | 2.11 MW | 2.11 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 962491 | AG1-098 C O1 | 80/20 | 12.74 MW | 12.74 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 963041 | AG1-153 C | 80/20 | 9.79 MW | 9.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 963111 | AG1-160 C | 80/20 | 9.96 MW | 9.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 963291 | AG1-178 C O2 | 80/20 | 107.94 MW | 107.94 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 963301 | AG1-179 C | 80/20 | 6.04 MW | 6.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 963311 | AG1-180 | 80/20 | 2.94 MW | 2.94 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 963321 | AG1-181 C O1 | Adder | 15.14 MW | 12.87 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 963351 | AG1-184 O2 | 80/20 | 58.15 MW | 58.15 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 963361 | AG1-185 O1 | Adder | 7.33 MW | 6.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 964111 | AG1-272 C | Adder | 2.27 MW | 1.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 964121 | AG1-273 C | Adder | 2.27 MW | 1.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 964131 | AG1-274 C | Adder | 2.27 MW | 1.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 964241 | AG1-285 C O1 | Adder | 12.0 MW | 10.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 964791 | AG1-342 C | 80/20 | 4.5 MW | 4.5 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 964801 | AG1-343 C | 80/20 | 6.11 MW | 6.11 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 966801 | AG1-551 C | 80/20 | 2.46 MW | 2.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 966811 | AG1-552 C | 80/20 | 2.28 MW | 2.28 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965191 | AG1-384 C | Adder | 2.27 MW | 1.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965291 | AG1-394 C | 80/20 | 2.09 MW | 2.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965591 | AG1-427 C | Adder | 11.35 MW | 9.65 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965601 | AG1-428 C O2 | 80/20 | 5.04 MW | 5.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965691 | AG1-437 C O1 | 80/20 | 10.43 MW | 10.43 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965701 | AG1-438 C O1 | 80/20 | 10.43 MW | 10.43 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965711 | AG1-439 C O1 | 80/20 | 26.75 MW | 26.75 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965721 | AG1-440 C | 80/20 | 7.79 MW | 7.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965731 | AG1-441 C | 80/20 | 7.79 MW | 7.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965741 | AG1-442 O1 | 80/20 | 6.08 MW | 6.08 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965751 | AG1-443 O1 | 80/20 | 6.08 MW | 6.08 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965761 | AG1-444 O1 | 80/20 | 14.26 MW | 14.26 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965771 | AG1-445 | 80/20 | 4.5 MW | 4.5 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965781 | AG1-446 | 80/20 | 4.5 MW | 4.5 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965811 | AG1-449 | 80/20 | 41.41 MW | 41.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 966361 | AG1-505 C | 80/20 | 28.7 MW | 28.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 966371 | AG1-506 C | 80/20 | 28.7 MW | 28.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 966621 | AG1-532 C | 80/20 | 1.53 MW | 1.53 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 313506 | AB1-173 C OP | 80/20 | 7.47 MW | 7.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 313719 | 3CHESTNUT | 80/20 | 1.37 MW | 1.37 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 314572 | 3EMPORIA | 80/20 | 0.47 MW | 0.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 314582 | 3KELFORD | 80/20 | 0.41 MW | 0.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 314623 | 3WITAKRS | 80/20 | 0.26 MW | 0.26 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 314704 | 3LAWRENC | 80/20 | 0.34 MW | 0.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315126 | 1ROARAP2 | 80/20 | 1.55 MW | 1.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315128 | 1ROARAP4 | 80/20 | 1.48 MW | 1.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315131 | 1EDGECMA | 80/20 | 9.01 MW | 9.01 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315132 | 1EDGECMB | 80/20 | 9.01 MW | 9.01 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315136 | 1ROSEMG1 | 80/20 | 2.41 MW | 2.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315137 | 1ROSEMS1 | 80/20 | 1.5 MW | 1.5 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315138 | 1ROSEMG2 | 80/20 | 1.13 MW | 1.13 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315139 | 1GASTONA | 80/20 | 3.48 MW | 3.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315153 | 1CLOVER1 | 80/20 | 18.74 MW | 18.74 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315154 | 1CLOVER2 | 80/20 | 18.56 MW | 18.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315161 | 1KERR 4 | 80/20 | 1.23 MW | 1.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 920591 | AA2-165 C | 80/20 | 0.18 MW | 0.18 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 926070 | AC1-086 C | 80/20 | 22.95 MW | 22.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 926201 | AC1-098 C | 80/20 | 6.72 MW | 6.72 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 926211 | AC1-099 C | 80/20 | 2.25 MW | 2.25 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 927024 | AC1-189 C | 80/20 | 9.49 MW | 9.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 927145 | AC1-208 C | 80/20 | 9.95 MW | 9.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 927251 | AC1-221 C | 80/20 | 2.64 MW | 2.64 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 927261 | AC1-222 C | 80/20 | 4.08 MW | 4.08 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 934311 | AD1-055 C | 80/20 | 2.84 MW | 2.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 934331 | AD1-057 C O1 | 80/20 | 11.06 MW | 11.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 934341 | AD1-058 C | 80/20 | 6.62 MW | 6.62 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 934521 | AD1-076 C | 80/20 | 55.29 MW | 55.29 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 934615 | AD1-087 C | 80/20 | 10.88 MW | 10.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 934625 | AD1-088 C | 80/20 | 14.06 MW | 14.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 934991 | AD1-131 C | 80/20 | 2.17 MW | 2.17 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 935171 | AD1-152 C O1 | 80/20 | 11.02 MW | 11.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 936161 | AD2-022 C O1 | Adder | 9.2 MW | 7.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 936171 | AD2-023 C O1 | Adder | 5.37 MW | 4.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 936265 | AD2-033 C | Adder | 11.75 MW | 9.99 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 937481 | AD2-202 C O1 | 80/20 | 3.19 MW | 3.19 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 942931 | AE2-313 C | 80/20 | 63.83 MW | 63.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 943171 | AE2-346 C | 80/20 | 1.48 MW | 1.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 943901 | AF1-058 C | 80/20 | 2.26 MW | 2.26 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 944011 | AF1-069 C | 80/20 | 23.28 MW | 23.28 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 944141 | AF1-082 | 80/20 | 3.24 MW | 3.24 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 945811 | AF1-246 C O1 | 80/20 | 11.57 MW | 11.57 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 959311 | AF2-222 C | Adder | 14.51 MW | 12.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 960061 | AF2-297 C | 80/20 | 9.04 MW | 9.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 960081 | AF2-299 C | 80/20 | 2.83 MW | 2.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315266 | 1PLYWOOD A | 80/20 | 1.44 MW | 1.44 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315293 | 1DOMTR9 | 80/20 | 7.07 MW | 7.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315294 | 1DOMTR10 | 80/20 | 8.67 MW | 8.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315601 | 1CONETOE2SOL | 80/20 | 1.61 MW | 1.61 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315606 | 3AA2-053SOLA | 80/20 | 1.68 MW | 1.68 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 316020 | AB2-059 C OP | 80/20 | 2.02 MW | 2.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 316118 | AC1-105 C | 80/20 | 6.33 MW | 6.33 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 316129 | AC1-054 C | 80/20 | 7.82 MW | 7.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 316140 | AB2-099 C | 80/20 | 0.62 MW | 0.62 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 922922 | AB1-081 C OP | 80/20 | 1.72 MW | 1.72 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 923262 | AB1-132 C OP | 80/20 | 15.59 MW | 15.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 923991 | AB2-040 C O1 | 80/20 | 8.14 MW | 8.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 924301 | AB2-077 C O1 | Adder | 1.99 MW | 1.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 924311 | AB2-078 C O1 | Adder | 1.99 MW | 1.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 924321 | AB2-079 C O1 | Adder | 1.99 MW | 1.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 925121 | AB2-169 C | 80/20 | 1.16 MW | 1.16 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 925591 | AC1-034 C | 80/20 | 7.7 MW | 7.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 932631 | AC2-084 C | 80/20 | 9.59 MW | 9.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 932761 | AC2-100 C | 80/20 | 6.08 MW | 6.08 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 939181 | AE1-148 C | Adder | 9.19 MW | 7.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 940491 | AE2-034 C | Adder | 7.18 MW | 6.1 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 940571 | AE2-044 C | 80/20 | 5.04 MW | 5.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 940661 | AE2-053 O1 | Adder | 3.4 MW | 2.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 941031 | AE2-094 C | 80/20 | 71.26 MW | 71.26 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 941791 | AE2-182 C | 80/20 | 2.29 MW | 2.29 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 946281 | AF1-292 C | 80/20 | 1.68 MW | 1.68 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 957481 | AF2-042 C | 80/20 | 82.65 MW | 82.65 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 957521 | AF2-046 C | 80/20 | 17.49 MW | 17.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 957531 | AF2-047 C | Adder | 17.05 MW | 14.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 957861 | AF2-080 C | 80/20 | 8.62 MW | 8.62 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 938771 | AE1-103 C | Adder | 2.84 MW | 2.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 940481 | AE2-033 C | 80/20 | 18.27 MW | 18.27 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 946011 | AF1-266 | 80/20 | 15.3 MW | 15.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 314435 | 6SAPONY | 80/20 | 0.49 MW | 0.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 934061 | AD1-033 C | Adder | 6.81 MW | 5.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 934575 | AD1-082 C | Adder | 6.24 MW | 5.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 936661 | AD2-085 C | Adder | 3.07 MW | 2.61 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 937221 | AD2-160 C O1 | Adder | 5.35 MW | 4.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 942341 | AE2-247 C | Adder | 1.33 MW | 1.13 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 942401 | AE2-253 C | Adder | 5.63 MW | 4.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 943461 | AF1-017 C | Adder | 1.2 MW | 1.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 943611 | AF1-032 C | Adder | 1.64 MW | 1.39 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 944871 | AF1-152 C | Adder | 5.01 MW | 4.26 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315102 | 1BRUNSWICKG1 | 80/20 | 15.07 MW | 15.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315103 | 1BRUNSWICKG2 | 80/20 | 15.07 MW | 15.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315104 | 1BRUNSWICKG3 | 80/20 | 15.07 MW | 15.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315105 | 1BRUNSWICKS1 | 80/20 | 31.3 MW | 31.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315141 | 1GASTONB | 80/20 | 3.48 MW | 3.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315241 | 1Z1-086 GT1 | 80/20 | 19.46 MW | 19.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315242 | 1Z1-086 GT2 | 80/20 | 19.46 MW | 19.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315243 | 1Z1-086 GT3 | 80/20 | 19.46 MW | 19.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315244 | 1Z1-086 ST | 80/20 | 33.82 MW | 33.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315292 | 1DOMTR78 | 80/20 | 1.48 MW | 1.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315607 | 3AA1-063SOLA | 80/20 | 1.54 MW | 1.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315608 | 3AA2-088SOLA | 80/20 | 1.13 MW | 1.13 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 316087 | AB2-174 C | 80/20 | 1.33 MW | 1.33 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 316096 | AB2-100 C1 | 80/20 | 1.11 MW | 1.11 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 316098 | AB2-100 C2 | 80/20 | 1.11 MW | 1.11 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 932044 | AC2-012 C | Adder | 7.12 MW | 6.05 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 932591 | AC2-079 C O1 | Adder | 4.96 MW | 4.22 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 938221 | AE1-035 C | 80/20 | 0.4 MW | 0.4 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 938535 | AE1-072 C | Adder | 16.15 MW | 13.73 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 939414 | AE1-173_C1 | 80/20 | 47.94 MW | 47.94 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 939415 | AE1-173_C2 | 80/20 | 41.09 MW | 41.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 939416 | AE1-173_C3 | 80/20 | 47.94 MW | 47.94 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 940541 | AE2-040 | 80/20 | 3.25 MW | 3.25 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 941101 | AE2-104 C O1 | Adder | 3.11 MW | 2.65 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 941281 | AE2-122 C O1 | Adder | 25.59 MW | 21.75 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 941291 | AE2-123 C O1 | Adder | 26.3 MW | 22.35 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 941301 | AE2-124 C O1 | Adder | 23.95 MW | 20.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 957491 | AF2-043 C | Adder | 2.0 MW | 1.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 957631 | AF2-057 | Adder | 3.18 MW | 2.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 964951 | AG1-359 O1 | Adder | 20.71 MW | 17.6 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965001 | AG1-364 C O1 | Adder | 6.36 MW | 5.4 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 941501 | AE2-147 C | Adder | 15.03 MW | 12.77 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 941591 | AE2-156 O1 | Adder | 15.89 MW | 13.51 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 957871 | AF2-081 C | Adder | 9.15 MW | 7.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 958161 | AF2-110 C | Adder | 1.28 MW | 1.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 944581 | AF1-123 C O1 | Adder | 43.8 MW | 37.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 944591 | AF1-124 C O1 | Adder | 43.8 MW | 37.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 944601 | AF1-125 C O1 | Adder | 43.8 MW | 37.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 933981 | AD1-022 C | 80/20 | 8.97 MW | 8.97 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 960331 | AF2-324 C | 80/20 | 8.79 MW | 8.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 962561 | AG1-105 C O1 | 80/20 | 9.53 MW | 9.53 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 961681 | AG1-008 C | 80/20 | 17.52 MW | 17.52 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 962571 | AG1-106 C | 80/20 | 6.38 MW | 6.38 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 965281 | AG1-393 C | 80/20 | 2.48 MW | 2.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 315602 | 1HOLLOMANSOL | 80/20 | 1.6 MW | 1.6 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | 316083 | AB2-161 C | Adder | 2.74 MW | 2.33 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 7.34 MW | 7.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.19 MW | 2.19 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 133.56 MW | 133.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 41.98 MW | 41.98 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 46.08 MW | 46.08 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 11.11 MW | 11.11 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 10.92 MW | 10.92 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.63 MW | 0.63 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.1 MW | 2.1 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.17 MW | 6.17 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.97 MW | 1.97 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.38 MW | 0.38 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.8 MW | 8.8 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.01 MW | 1.01 MW |
Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | Adder | 0.34 MW | 0.29 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | 80/20 | 0.78 MW | 0.78 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | 80/20 | 0.78 MW | 0.78 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | Adder | 1.83 MW | 1.55 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 1.85 MW | 1.85 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 20.87 MW | 20.87 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 2.36 MW | 2.36 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.15 MW | 1.15 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 11.24 MW | 11.24 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | 80/20 | 2.39 MW | 2.39 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | Adder | 0.81 MW | 0.69 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 0.87 MW | 0.87 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | 80/20 | 0.82 MW | 0.82 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 1.97 MW | 1.97 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | 80/20 | 3.75 MW | 3.75 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | 80/20 | 3.75 MW | 3.75 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | Adder | 8.57 MW | 7.28 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | Adder | 2.47 MW | 2.1 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | Adder | 2.47 MW | 2.1 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | 80/20 | 2.19 MW | 2.19 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | 80/20 | 2.19 MW | 2.19 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | Adder | 4.57 MW | 3.88 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | Adder | 1.43 MW | 1.21 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | Adder | 1.43 MW | 1.21 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 7.65 MW | 7.65 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | Adder | 5.38 MW | 4.57 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | Adder | 5.38 MW | 4.57 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 0.67 MW | 0.67 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 3.11 MW | 3.11 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.2 MW | 0.2 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.15 MW | 0.15 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.59 MW | 0.59 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.57 MW | 0.57 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | Adder | 2.84 MW | 2.42 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | Adder | 2.84 MW | 2.42 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 0.96 MW | 0.96 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.59 MW | 0.59 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.45 MW | 0.45 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.42 MW | 1.42 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | 80/20 | 9.35 MW | 9.35 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.36 MW | 2.36 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.79 MW | 0.79 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | Adder | 3.05 MW | 2.6 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 3.5 MW | 3.5 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 3.94 MW | 3.94 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | 80/20 | 19.72 MW | 19.72 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 11.8 MW | 11.8 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.29 MW | 4.29 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | Adder | 1.02 MW | 0.87 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.25 MW | 1.25 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 2.47 MW | 2.1 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 3.03 MW | 2.57 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.64 MW | 0.64 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | Adder | 2.66 MW | 2.26 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 6.35 MW | 6.35 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.39 MW | 3.39 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | Adder | 2.43 MW | 2.06 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.37 MW | 3.37 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | 80/20 | 2.57 MW | 2.57 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | Adder | 1.59 MW | 1.35 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 13.13 MW | 13.13 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.74 MW | 0.74 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 6.67 MW | 6.67 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | 80/20 | 6.11 MW | 6.11 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | Adder | 2.77 MW | 2.36 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C | 80/20 | 1.16 MW | 1.16 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 9.92 MW | 9.92 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 5.66 MW | 5.66 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 8.3 MW | 8.3 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314314 | 3LOCKS | 80/20 | 0.22 MW | 0.22 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.27 MW | 0.27 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315065 | 1CHESTF6 | 80/20 | 131.81 MW | 131.81 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315076 | 1HOPPOLC | 80/20 | 1.14 MW | 1.14 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315077 | 1HOPHCF1 | 80/20 | 1.78 MW | 1.78 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315078 | 1HOPHCF2 | 80/20 | 1.78 MW | 1.78 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315079 | 1HOPHCF3 | 80/20 | 1.78 MW | 1.78 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315080 | 1HOPHCF4 | 80/20 | 2.7 MW | 2.7 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315083 | 1SPRUNCA | Adder | 3.34 MW | 2.84 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315084 | 1SPRUNCB | Adder | 3.34 MW | 2.84 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927225 | AC1-216 C | 80/20 | 0.93 MW | 0.93 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934014 | AD1-025 C | 80/20 | 9.41 MW | 9.41 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934061 | AD1-033 C | Adder | 2.47 MW | 2.1 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | 80/20 | 5.33 MW | 5.33 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935111 | AD1-144 C | 80/20 | 0.1 MW | 0.1 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935164 | AD1-151 C | 80/20 | 9.56 MW | 9.56 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | 80/20 | 1.68 MW | 1.68 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | 0.63 MW | 0.54 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937221 | AD2-160 C O1 | Adder | 1.94 MW | 1.65 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942161 | AE2-228 C | 80/20 | 2.67 MW | 2.67 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | 80/20 | 0.73 MW | 0.73 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942371 | AE2-250 C O1 | 80/20 | 6.85 MW | 6.85 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942401 | AE2-253 C | Adder | 2.04 MW | 1.73 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942551 | AE2-270 | 80/20 | 15.34 MW | 15.34 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | 80/20 | 0.66 MW | 0.66 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943611 | AF1-032 C | 80/20 | 0.6 MW | 0.6 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943621 | AF1-033 C | 80/20 | 0.98 MW | 0.98 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944871 | AF1-152 C | Adder | 1.82 MW | 1.54 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961711 | AG1-011 | 80/20 | 15.98 MW | 15.98 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.81 MW | 2.81 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.81 MW | 2.81 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.84 MW | 5.84 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315115 | 1S HAMPT1 | 80/20 | 0.62 MW | 0.62 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315116 | 1SURRY 1 | 80/20 | 11.33 MW | 11.33 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315117 | 1GRAVELC | 80/20 | 0.4 MW | 0.4 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315119 | 1GRAVEL3 | 80/20 | 1.15 MW | 1.15 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315120 | 1GRAVEL4 | 80/20 | 1.17 MW | 1.17 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315121 | 1GRAVEL5 | 80/20 | 1.15 MW | 1.15 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315122 | 1GRAVEL6 | 80/20 | 1.16 MW | 1.16 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.42 MW | 1.42 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 3.62 MW | 3.62 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 3.62 MW | 3.62 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 3.62 MW | 3.62 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 6.28 MW | 6.28 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.6 MW | 0.6 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315608 | 3AA2-088SOLA | 80/20 | 0.44 MW | 0.44 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316033 | AB2-134 C | 80/20 | 1.22 MW | 1.22 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.56 MW | 0.56 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316096 | AB2-100 C1 | 80/20 | 0.53 MW | 0.53 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316098 | AB2-100 C2 | 80/20 | 0.53 MW | 0.53 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316108 | AB2-160 C | 80/20 | 3.86 MW | 3.86 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316132 | AB2-190 C | 80/20 | 11.05 MW | 11.05 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316258 | AE1-162 C | 80/20 | 0.15 MW | 0.15 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932044 | AC2-012 C | Adder | 2.7 MW | 2.29 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | 80/20 | 3.18 MW | 3.18 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | 80/20 | 0.14 MW | 0.14 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938535 | AE1-072 C | Adder | 5.84 MW | 4.97 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939195 | AE1-149 C | 80/20 | 8.01 MW | 8.01 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 10.37 MW | 10.37 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 8.88 MW | 8.88 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 10.37 MW | 10.37 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940431 | AE2-027 C O1 | 80/20 | 6.55 MW | 6.55 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | 80/20 | 1.79 MW | 1.79 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | 80/20 | 2.67 MW | 2.67 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | 80/20 | 1.32 MW | 1.32 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941281 | AE2-122 C O1 | Adder | 9.44 MW | 8.02 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941291 | AE2-123 C O1 | Adder | 9.7 MW | 8.24 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941301 | AE2-124 C O1 | Adder | 8.81 MW | 7.49 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946261 | AF1-291 C | 80/20 | 2.69 MW | 2.69 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957491 | AF2-043 C | 80/20 | 0.73 MW | 0.73 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957631 | AF2-057 | Adder | 1.2 MW | 1.02 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957711 | AF2-065 C | 80/20 | 7.83 MW | 7.83 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963221 | AG1-171 C | 80/20 | 1.2 MW | 1.2 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963231 | AG1-172 C | 80/20 | 1.2 MW | 1.2 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963241 | AG1-173 C | 80/20 | 1.2 MW | 1.2 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963251 | AG1-174 C | 80/20 | 1.2 MW | 1.2 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964951 | AG1-359 O1 | Adder | 7.49 MW | 6.37 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965001 | AG1-364 C O1 | Adder | 2.4 MW | 2.04 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941501 | AE2-147 C | Adder | 5.45 MW | 4.63 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941591 | AE2-156 O1 | Adder | 6.0 MW | 5.1 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942001 | AE2-212 C | 80/20 | 2.35 MW | 2.35 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957871 | AF2-081 C | Adder | 3.31 MW | 2.81 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | 80/20 | 0.55 MW | 0.55 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966611 | AG1-531 C | 80/20 | 2.04 MW | 2.04 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944581 | AF1-123 C O1 | Adder | 15.24 MW | 12.96 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944591 | AF1-124 C O1 | Adder | 15.24 MW | 12.96 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944601 | AF1-125 C O1 | Adder | 15.24 MW | 12.96 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | 80/20 | 3.21 MW | 3.21 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | Adder | 2.78 MW | 2.36 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | 80/20 | 6.68 MW | 6.68 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962271 | AG1-075 C O1 | 80/20 | 11.82 MW | 11.82 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | 80/20 | 2.6 MW | 2.6 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | 80/20 | 1.37 MW | 1.37 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315602 | 1HOLLOMANSOL | 80/20 | 0.58 MW | 0.58 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315614 | AA2-178 C | 80/20 | 0.58 MW | 0.58 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | 80/20 | 2.34 MW | 2.34 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961611 | AG1-000B C | 80/20 | 7.43 MW | 7.43 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.7 MW | 1.7 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.46 MW | 0.46 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.98 MW | 29.98 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.05 MW | 8.05 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.54 MW | 9.54 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.57 MW | 2.57 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.31 MW | 2.31 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.23 MW | 1.23 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.46 MW | 0.46 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.85 MW | 1.85 MW |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | Adder | 0.34 MW | 0.29 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | 80/20 | 0.78 MW | 0.78 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | 80/20 | 0.78 MW | 0.78 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | Adder | 1.83 MW | 1.55 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 1.85 MW | 1.85 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 20.87 MW | 20.87 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 2.36 MW | 2.36 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.15 MW | 1.15 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 11.24 MW | 11.24 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | 80/20 | 2.39 MW | 2.39 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | Adder | 0.81 MW | 0.69 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 0.87 MW | 0.87 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | 80/20 | 0.82 MW | 0.82 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 1.97 MW | 1.97 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | 80/20 | 3.75 MW | 3.75 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | 80/20 | 3.75 MW | 3.75 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | Adder | 8.57 MW | 7.28 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | Adder | 2.47 MW | 2.1 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | Adder | 2.47 MW | 2.1 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | 80/20 | 2.19 MW | 2.19 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | 80/20 | 2.19 MW | 2.19 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | Adder | 4.57 MW | 3.88 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | Adder | 1.43 MW | 1.21 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | Adder | 1.43 MW | 1.21 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 7.65 MW | 7.65 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | Adder | 5.38 MW | 4.57 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | Adder | 5.38 MW | 4.57 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 0.67 MW | 0.67 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 3.11 MW | 3.11 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.2 MW | 0.2 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.15 MW | 0.15 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.59 MW | 0.59 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.57 MW | 0.57 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | Adder | 2.84 MW | 2.42 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | Adder | 2.84 MW | 2.42 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 0.96 MW | 0.96 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.59 MW | 0.59 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.45 MW | 0.45 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.42 MW | 1.42 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | 80/20 | 9.35 MW | 9.35 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.36 MW | 2.36 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.79 MW | 0.79 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | Adder | 3.05 MW | 2.6 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 3.5 MW | 3.5 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 3.94 MW | 3.94 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | 80/20 | 19.72 MW | 19.72 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 11.8 MW | 11.8 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.29 MW | 4.29 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | Adder | 1.02 MW | 0.87 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.25 MW | 1.25 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 2.47 MW | 2.1 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 3.03 MW | 2.57 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.64 MW | 0.64 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | Adder | 2.66 MW | 2.26 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 6.35 MW | 6.35 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.39 MW | 3.39 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | Adder | 2.43 MW | 2.06 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.37 MW | 3.37 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | 80/20 | 2.57 MW | 2.57 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | Adder | 1.59 MW | 1.35 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 13.13 MW | 13.13 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.74 MW | 0.74 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 6.67 MW | 6.67 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | 80/20 | 6.11 MW | 6.11 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | Adder | 2.77 MW | 2.36 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C | 80/20 | 1.16 MW | 1.16 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 9.92 MW | 9.92 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 5.66 MW | 5.66 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 8.3 MW | 8.3 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314314 | 3LOCKS | 80/20 | 0.22 MW | 0.22 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.27 MW | 0.27 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315065 | 1CHESTF6 | 80/20 | 131.81 MW | 131.81 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315076 | 1HOPPOLC | 80/20 | 1.14 MW | 1.14 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315077 | 1HOPHCF1 | 80/20 | 1.78 MW | 1.78 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315078 | 1HOPHCF2 | 80/20 | 1.78 MW | 1.78 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315079 | 1HOPHCF3 | 80/20 | 1.78 MW | 1.78 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315080 | 1HOPHCF4 | 80/20 | 2.7 MW | 2.7 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315083 | 1SPRUNCA | Adder | 3.34 MW | 2.84 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315084 | 1SPRUNCB | Adder | 3.34 MW | 2.84 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927225 | AC1-216 C | 80/20 | 0.93 MW | 0.93 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934014 | AD1-025 C | 80/20 | 9.41 MW | 9.41 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934061 | AD1-033 C | Adder | 2.47 MW | 2.1 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | 80/20 | 5.33 MW | 5.33 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935111 | AD1-144 C | 80/20 | 0.1 MW | 0.1 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935164 | AD1-151 C | 80/20 | 9.56 MW | 9.56 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | 80/20 | 1.68 MW | 1.68 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | 0.63 MW | 0.54 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937221 | AD2-160 C O1 | Adder | 1.94 MW | 1.65 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942161 | AE2-228 C | 80/20 | 2.67 MW | 2.67 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | 80/20 | 0.73 MW | 0.73 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942371 | AE2-250 C O1 | 80/20 | 6.85 MW | 6.85 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942401 | AE2-253 C | Adder | 2.04 MW | 1.73 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942551 | AE2-270 | 80/20 | 15.34 MW | 15.34 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | 80/20 | 0.66 MW | 0.66 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943611 | AF1-032 C | 80/20 | 0.6 MW | 0.6 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943621 | AF1-033 C | 80/20 | 0.98 MW | 0.98 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944871 | AF1-152 C | Adder | 1.82 MW | 1.54 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961711 | AG1-011 | 80/20 | 15.98 MW | 15.98 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.81 MW | 2.81 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.84 MW | 5.84 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315115 | 1S HAMPT1 | 80/20 | 0.62 MW | 0.62 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315116 | 1SURRY 1 | 80/20 | 11.33 MW | 11.33 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315117 | 1GRAVELC | 80/20 | 0.4 MW | 0.4 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315119 | 1GRAVEL3 | 80/20 | 1.15 MW | 1.15 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315120 | 1GRAVEL4 | 80/20 | 1.17 MW | 1.17 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315121 | 1GRAVEL5 | 80/20 | 1.15 MW | 1.15 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315122 | 1GRAVEL6 | 80/20 | 1.16 MW | 1.16 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.42 MW | 1.42 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 3.62 MW | 3.62 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 3.62 MW | 3.62 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 3.62 MW | 3.62 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 6.28 MW | 6.28 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.6 MW | 0.6 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315608 | 3AA2-088SOLA | 80/20 | 0.44 MW | 0.44 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316033 | AB2-134 C | 80/20 | 1.22 MW | 1.22 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.56 MW | 0.56 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316096 | AB2-100 C1 | 80/20 | 0.53 MW | 0.53 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316098 | AB2-100 C2 | 80/20 | 0.53 MW | 0.53 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316108 | AB2-160 C | 80/20 | 3.86 MW | 3.86 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316132 | AB2-190 C | 80/20 | 11.05 MW | 11.05 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316258 | AE1-162 C | 80/20 | 0.15 MW | 0.15 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932044 | AC2-012 C | Adder | 2.7 MW | 2.29 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | 80/20 | 3.18 MW | 3.18 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | 80/20 | 0.14 MW | 0.14 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938535 | AE1-072 C | Adder | 5.84 MW | 4.97 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939195 | AE1-149 C | 80/20 | 8.01 MW | 8.01 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 10.37 MW | 10.37 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 8.88 MW | 8.88 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 10.37 MW | 10.37 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940431 | AE2-027 C O1 | 80/20 | 6.55 MW | 6.55 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | 80/20 | 1.79 MW | 1.79 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | 80/20 | 2.67 MW | 2.67 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | 80/20 | 1.32 MW | 1.32 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941281 | AE2-122 C O1 | Adder | 9.44 MW | 8.02 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941291 | AE2-123 C O1 | Adder | 9.7 MW | 8.24 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941301 | AE2-124 C O1 | Adder | 8.81 MW | 7.49 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946261 | AF1-291 C | 80/20 | 2.69 MW | 2.69 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957491 | AF2-043 C | 80/20 | 0.73 MW | 0.73 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957631 | AF2-057 | Adder | 1.2 MW | 1.02 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957711 | AF2-065 C | 80/20 | 7.83 MW | 7.83 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963221 | AG1-171 C | 80/20 | 1.2 MW | 1.2 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963231 | AG1-172 C | 80/20 | 1.2 MW | 1.2 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963241 | AG1-173 C | 80/20 | 1.2 MW | 1.2 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963251 | AG1-174 C | 80/20 | 1.2 MW | 1.2 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964951 | AG1-359 O1 | Adder | 7.49 MW | 6.37 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965001 | AG1-364 C O1 | Adder | 2.4 MW | 2.04 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941501 | AE2-147 C | Adder | 5.45 MW | 4.63 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941591 | AE2-156 O1 | Adder | 6.0 MW | 5.1 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942001 | AE2-212 C | 80/20 | 2.35 MW | 2.35 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957871 | AF2-081 C | Adder | 3.31 MW | 2.81 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | 80/20 | 0.55 MW | 0.55 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966611 | AG1-531 C | 80/20 | 2.04 MW | 2.04 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944581 | AF1-123 C O1 | Adder | 15.24 MW | 12.96 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944591 | AF1-124 C O1 | Adder | 15.24 MW | 12.96 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944601 | AF1-125 C O1 | Adder | 15.24 MW | 12.96 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | 80/20 | 3.21 MW | 3.21 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | Adder | 2.78 MW | 2.36 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | 80/20 | 6.68 MW | 6.68 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962271 | AG1-075 C O1 | 80/20 | 11.82 MW | 11.82 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | 80/20 | 2.6 MW | 2.6 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | 80/20 | 1.37 MW | 1.37 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315602 | 1HOLLOMANSOL | 80/20 | 0.58 MW | 0.58 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315614 | AA2-178 C | 80/20 | 0.58 MW | 0.58 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | 80/20 | 2.34 MW | 2.34 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961611 | AG1-000B C | 80/20 | 7.43 MW | 7.43 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.7 MW | 1.7 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.46 MW | 0.46 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.98 MW | 29.98 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.05 MW | 8.05 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.54 MW | 9.54 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.57 MW | 2.57 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.31 MW | 2.31 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.23 MW | 1.23 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.46 MW | 0.46 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.85 MW | 1.85 MW |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
Details for 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.45 MW | 0.38 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.26 MW | 0.22 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961941 | AG1-037 C | Adder | 0.21 MW | 0.18 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.14 MW | 0.12 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962331 | AG1-082 C | Adder | 0.85 MW | 0.72 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.56 MW | 0.48 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962341 | AG1-083 C | Adder | 0.85 MW | 0.72 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.56 MW | 0.48 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962491 | AG1-098 C O1 | Adder | 4.07 MW | 3.46 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962492 | AG1-098 E O1 | Adder | 2.71 MW | 2.31 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.98 MW | 2.53 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 4.47 MW | 3.8 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | 50/50 | 3.02 MW | 3.02 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | 50/50 | 4.53 MW | 4.53 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 31.21 MW | 26.53 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | 50/50 | 3.75 MW | 3.75 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | 50/50 | 1.83 MW | 1.83 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963321 | AG1-181 C O1 | Adder | 6.53 MW | 5.55 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 16.82 MW | 14.29 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963361 | AG1-185 O1 | Adder | 3.16 MW | 2.69 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964111 | AG1-272 C | Adder | 0.97 MW | 0.83 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964112 | AG1-272 E | Adder | 0.29 MW | 0.25 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964121 | AG1-273 C | Adder | 0.97 MW | 0.83 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964122 | AG1-273 E | Adder | 0.29 MW | 0.25 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964131 | AG1-274 C | Adder | 0.97 MW | 0.83 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964132 | AG1-274 E | Adder | 0.29 MW | 0.25 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964241 | AG1-285 C O1 | Adder | 5.3 MW | 4.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964242 | AG1-285 E O1 | Adder | 3.53 MW | 3.0 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964791 | AG1-342 C | Adder | 1.74 MW | 1.48 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964792 | AG1-342 E | Adder | 1.37 MW | 1.17 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 2.41 MW | 2.05 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 1.9 MW | 1.61 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966801 | AG1-551 C | Adder | 0.92 MW | 0.78 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966802 | AG1-551 E | Adder | 0.39 MW | 0.33 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 1.21 MW | 1.03 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.52 MW | 0.44 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965191 | AG1-384 C | Adder | 0.97 MW | 0.83 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965192 | AG1-384 E | Adder | 0.29 MW | 0.25 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965291 | AG1-394 C | Adder | 0.83 MW | 0.7 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965292 | AG1-394 E | Adder | 0.55 MW | 0.47 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965591 | AG1-427 C | Adder | 5.01 MW | 4.26 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965592 | AG1-427 E | Adder | 3.35 MW | 2.85 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | 50/50 | 3.13 MW | 3.13 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | 50/50 | 2.08 MW | 2.08 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 11.05 MW | 9.39 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 7.37 MW | 6.26 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 3.59 MW | 3.05 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 2.39 MW | 2.03 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 3.59 MW | 3.05 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 2.39 MW | 2.03 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 5.9 MW | 5.01 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 2.07 MW | 1.76 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 2.07 MW | 1.76 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | 50/50 | 12.52 MW | 12.52 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 8.75 MW | 7.44 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 5.83 MW | 4.96 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 8.75 MW | 7.44 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 5.83 MW | 4.96 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | 50/50 | 1.09 MW | 1.09 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | 50/50 | 0.73 MW | 0.73 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | 50/50 | 4.76 MW | 4.76 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.32 MW | 0.32 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314704 | 3LAWRENC | 50/50 | 0.22 MW | 0.22 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.97 MW | 3.37 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.97 MW | 3.37 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315136 | 1ROSEMG1 | 50/50 | 1.41 MW | 1.41 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315137 | 1ROSEMS1 | 50/50 | 0.88 MW | 0.88 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315138 | 1ROSEMG2 | 50/50 | 0.66 MW | 0.66 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315139 | 1GASTONA | 50/50 | 2.1 MW | 2.1 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 3.66 MW | 3.11 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 2.05 MW | 1.74 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.31 MW | 0.26 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 2.06 MW | 1.75 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.72 MW | 1.46 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.15 MW | 3.53 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.24 MW | 0.2 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.75 MW | 1.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | 50/50 | 13.88 MW | 13.88 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | 50/50 | 6.32 MW | 6.32 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 3.04 MW | 2.58 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.81 MW | 1.54 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 1.02 MW | 0.87 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.6 MW | 0.51 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926274 | AC1-105 E | Adder | 1.12 MW | 0.95 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.84 MW | 3.26 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.91 MW | 1.62 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 4.7 MW | 4.0 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 2.09 MW | 1.77 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927251 | AC1-221 C | Adder | 0.9 MW | 0.77 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927252 | AC1-221 E | Adder | 0.9 MW | 0.77 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927261 | AC1-222 C | Adder | 1.43 MW | 1.22 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927262 | AC1-222 E | Adder | 1.36 MW | 1.16 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934311 | AD1-055 C | Adder | 1.0 MW | 0.85 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 5.69 MW | 4.83 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 3.04 MW | 2.58 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934341 | AD1-058 C | Adder | 2.26 MW | 1.92 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934342 | AD1-058 E | Adder | 0.58 MW | 0.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 3.43 MW | 2.92 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.61 MW | 1.37 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934625 | AD1-088 C | Adder | 4.49 MW | 3.82 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934626 | AD1-088 E | Adder | 2.11 MW | 1.8 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934991 | AD1-131 C | Adder | 0.74 MW | 0.63 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934992 | AD1-131 E | Adder | 0.5 MW | 0.42 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 3.56 MW | 3.02 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 2.37 MW | 2.02 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936265 | AD2-033 C | Adder | 5.08 MW | 4.32 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936266 | AD2-033 E | Adder | 3.38 MW | 2.88 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 1.0 MW | 0.85 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.47 MW | 0.4 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | 50/50 | 19.3 MW | 19.3 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | 50/50 | 12.87 MW | 12.87 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.59 MW | 0.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.25 MW | 0.22 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.79 MW | 0.68 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.53 MW | 0.45 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | 50/50 | 7.03 MW | 7.03 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | 50/50 | 2.73 MW | 2.73 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.42 MW | 1.21 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 3.6 MW | 3.06 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 4.97 MW | 4.22 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959311 | AF2-222 C | Adder | 6.18 MW | 5.25 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959312 | AF2-222 E | Adder | 4.14 MW | 3.52 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 3.18 MW | 2.7 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 2.12 MW | 1.8 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 2.02 MW | 2.02 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.35 MW | 1.35 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | 50/50 | 4.64 MW | 4.64 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 2.59 MW | 2.59 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 2.59 MW | 2.59 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316118 | AC1-105 C | Adder | 2.34 MW | 1.99 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 3.79 MW | 3.23 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316140 | AB2-099 C | Adder | 0.25 MW | 0.21 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316141 | AB2-099 E | Adder | 0.11 MW | 0.09 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.12 MW | 0.1 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.48 MW | 0.41 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.29 MW | 0.25 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.9 MW | 1.61 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | 50/50 | 9.42 MW | 9.42 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | 50/50 | 4.04 MW | 4.04 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | 50/50 | 2.26 MW | 2.26 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | 50/50 | 5.18 MW | 5.18 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | 50/50 | 4.24 MW | 4.24 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.69 MW | 2.28 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.86 MW | 1.58 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.88 MW | 0.75 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.59 MW | 0.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.88 MW | 0.75 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.59 MW | 0.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.88 MW | 0.75 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.59 MW | 0.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 2.13 MW | 1.81 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 3.38 MW | 2.87 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.55 MW | 2.17 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925612 | AC1-036 E | Adder | 0.59 MW | 0.5 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 4.34 MW | 3.69 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 2.14 MW | 1.81 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932761 | AC2-100 C | Adder | 2.08 MW | 1.77 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932762 | AC2-100 E | Adder | 1.01 MW | 0.86 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.44 MW | 0.37 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 4.1 MW | 3.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.73 MW | 2.32 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 2.21 MW | 1.88 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.95 MW | 0.81 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.52 MW | 1.29 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | 50/50 | 21.51 MW | 21.51 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | 50/50 | 9.63 MW | 9.63 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941791 | AE2-182 C | Adder | 0.73 MW | 0.62 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941792 | AE2-182 E | Adder | 0.34 MW | 0.29 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 1.2 MW | 1.2 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.81 MW | 0.81 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 25.68 MW | 21.83 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 17.12 MW | 14.55 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 6.96 MW | 5.92 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.5 MW | 2.98 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 3.48 MW | 2.96 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.54 MW | 1.31 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 17.91 MW | 17.91 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 12.07 MW | 12.07 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 14.99 MW | 14.99 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314331 | 6POE | Adder | 0.96 MW | 0.82 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.49 MW | 0.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.84 MW | -2.41 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.82 MW | -0.69 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -4.08 MW | -3.47 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315141 | 1GASTONB | 50/50 | 2.1 MW | 2.1 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315241 | 1Z1-086 GT1 | 50/50 | 5.9 MW | 5.9 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315242 | 1Z1-086 GT2 | 50/50 | 5.9 MW | 5.9 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315243 | 1Z1-086 GT3 | 50/50 | 5.9 MW | 5.9 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315244 | 1Z1-086 ST | 50/50 | 10.26 MW | 10.26 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316087 | AB2-174 C | 50/50 | 0.87 MW | 0.87 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.9 MW | 0.9 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.9 MW | 0.9 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.29 MW | 1.29 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 12.81 MW | 10.88 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 10.98 MW | 9.33 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 12.81 MW | 10.88 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 8.54 MW | 7.26 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 7.32 MW | 6.22 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 8.54 MW | 7.26 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 3.26 MW | 3.26 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 3.87 MW | 3.29 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 2.08 MW | 1.77 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962561 | AG1-105 C O1 | Adder | 3.78 MW | 3.21 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962562 | AG1-105 E O1 | Adder | 2.52 MW | 2.14 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | 50/50 | 1.75 MW | 1.75 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961681 | AG1-008 C | Adder | 6.97 MW | 5.93 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961682 | AG1-008 E | Adder | 3.49 MW | 2.96 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | 50/50 | 3.86 MW | 3.86 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 2.49 MW | 2.49 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.66 MW | 1.66 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.59 MW | 1.35 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 1.24 MW | 1.06 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.56 MW | 2.56 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.76 MW | 0.76 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 46.15 MW | 46.15 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 15.21 MW | 15.21 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.13 MW | 16.13 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.88 MW | 3.88 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.17 MW | 1.17 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.79 MW | 3.79 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.21 MW | 0.21 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.75 MW | 0.75 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.19 MW | 2.19 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.53 MW | 0.53 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.43 MW | 7.43 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.13 MW | 0.13 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.05 MW | 3.05 MW |
6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.36 MW | 0.36 MW |
Details for 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.45 MW | 0.38 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.26 MW | 0.22 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961941 | AG1-037 C | Adder | 0.21 MW | 0.18 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.14 MW | 0.12 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962331 | AG1-082 C | Adder | 0.85 MW | 0.72 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.56 MW | 0.48 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962341 | AG1-083 C | Adder | 0.85 MW | 0.72 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.56 MW | 0.48 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962491 | AG1-098 C O1 | Adder | 4.07 MW | 3.46 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962492 | AG1-098 E O1 | Adder | 2.71 MW | 2.31 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.98 MW | 2.53 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 4.47 MW | 3.8 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | 50/50 | 3.02 MW | 3.02 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | 50/50 | 4.53 MW | 4.53 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 31.21 MW | 26.53 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | 50/50 | 3.75 MW | 3.75 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | 50/50 | 1.83 MW | 1.83 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963321 | AG1-181 C O1 | Adder | 6.53 MW | 5.55 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 16.82 MW | 14.29 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963361 | AG1-185 O1 | Adder | 3.16 MW | 2.69 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964111 | AG1-272 C | Adder | 0.97 MW | 0.83 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964112 | AG1-272 E | Adder | 0.29 MW | 0.25 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964121 | AG1-273 C | Adder | 0.97 MW | 0.83 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964122 | AG1-273 E | Adder | 0.29 MW | 0.25 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964131 | AG1-274 C | Adder | 0.97 MW | 0.83 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964132 | AG1-274 E | Adder | 0.29 MW | 0.25 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964241 | AG1-285 C O1 | Adder | 5.3 MW | 4.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964242 | AG1-285 E O1 | Adder | 3.53 MW | 3.0 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964791 | AG1-342 C | Adder | 1.74 MW | 1.48 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964792 | AG1-342 E | Adder | 1.37 MW | 1.17 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 2.41 MW | 2.05 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 1.9 MW | 1.61 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966801 | AG1-551 C | Adder | 0.92 MW | 0.78 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966802 | AG1-551 E | Adder | 0.39 MW | 0.33 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 1.21 MW | 1.03 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.52 MW | 0.44 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965191 | AG1-384 C | Adder | 0.97 MW | 0.83 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965192 | AG1-384 E | Adder | 0.29 MW | 0.25 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965291 | AG1-394 C | Adder | 0.83 MW | 0.7 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965292 | AG1-394 E | Adder | 0.55 MW | 0.47 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965591 | AG1-427 C | Adder | 5.01 MW | 4.26 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965592 | AG1-427 E | Adder | 3.35 MW | 2.85 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | 50/50 | 3.13 MW | 3.13 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | 50/50 | 2.08 MW | 2.08 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 11.05 MW | 9.39 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 7.37 MW | 6.26 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 3.59 MW | 3.05 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 2.39 MW | 2.03 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 3.59 MW | 3.05 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 2.39 MW | 2.03 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 5.9 MW | 5.01 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 2.07 MW | 1.76 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 2.07 MW | 1.76 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | 50/50 | 12.52 MW | 12.52 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 8.75 MW | 7.44 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 5.83 MW | 4.96 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 8.75 MW | 7.44 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 5.83 MW | 4.96 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | 50/50 | 1.09 MW | 1.09 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | 50/50 | 0.73 MW | 0.73 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | 50/50 | 4.76 MW | 4.76 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.32 MW | 0.32 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314704 | 3LAWRENC | 50/50 | 0.22 MW | 0.22 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.97 MW | 3.37 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.97 MW | 3.37 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315136 | 1ROSEMG1 | 50/50 | 1.41 MW | 1.41 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315137 | 1ROSEMS1 | 50/50 | 0.88 MW | 0.88 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315138 | 1ROSEMG2 | 50/50 | 0.66 MW | 0.66 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315139 | 1GASTONA | 50/50 | 2.1 MW | 2.1 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 3.66 MW | 3.11 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 2.05 MW | 1.74 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.31 MW | 0.26 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 2.06 MW | 1.75 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.72 MW | 1.46 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.15 MW | 3.53 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.24 MW | 0.2 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.75 MW | 1.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | 50/50 | 13.88 MW | 13.88 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | 50/50 | 6.32 MW | 6.32 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 3.04 MW | 2.58 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.81 MW | 1.54 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 1.02 MW | 0.87 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.6 MW | 0.51 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926274 | AC1-105 E | Adder | 1.12 MW | 0.95 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.84 MW | 3.26 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.91 MW | 1.62 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 4.7 MW | 4.0 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 2.09 MW | 1.77 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927251 | AC1-221 C | Adder | 0.9 MW | 0.77 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927252 | AC1-221 E | Adder | 0.9 MW | 0.77 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927261 | AC1-222 C | Adder | 1.43 MW | 1.22 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927262 | AC1-222 E | Adder | 1.36 MW | 1.16 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934311 | AD1-055 C | Adder | 1.0 MW | 0.85 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 5.69 MW | 4.83 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 3.04 MW | 2.58 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934341 | AD1-058 C | Adder | 2.26 MW | 1.92 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934342 | AD1-058 E | Adder | 0.58 MW | 0.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 3.43 MW | 2.92 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.61 MW | 1.37 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934625 | AD1-088 C | Adder | 4.49 MW | 3.82 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934626 | AD1-088 E | Adder | 2.11 MW | 1.8 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934991 | AD1-131 C | Adder | 0.74 MW | 0.63 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934992 | AD1-131 E | Adder | 0.5 MW | 0.42 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 3.56 MW | 3.02 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 2.37 MW | 2.02 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936265 | AD2-033 C | Adder | 5.08 MW | 4.32 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936266 | AD2-033 E | Adder | 3.38 MW | 2.88 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 1.0 MW | 0.85 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.47 MW | 0.4 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | 50/50 | 19.3 MW | 19.3 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | 50/50 | 12.87 MW | 12.87 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.59 MW | 0.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.25 MW | 0.22 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.79 MW | 0.68 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.53 MW | 0.45 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | 50/50 | 7.03 MW | 7.03 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | 50/50 | 2.73 MW | 2.73 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.42 MW | 1.21 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 3.6 MW | 3.06 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 4.97 MW | 4.22 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959311 | AF2-222 C | Adder | 6.18 MW | 5.25 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959312 | AF2-222 E | Adder | 4.14 MW | 3.52 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 3.18 MW | 2.7 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 2.12 MW | 1.8 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 2.02 MW | 2.02 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.35 MW | 1.35 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | 50/50 | 4.64 MW | 4.64 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 2.59 MW | 2.59 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 2.59 MW | 2.59 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316118 | AC1-105 C | Adder | 2.34 MW | 1.99 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 3.79 MW | 3.23 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316140 | AB2-099 C | Adder | 0.25 MW | 0.21 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316141 | AB2-099 E | Adder | 0.11 MW | 0.09 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.12 MW | 0.1 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.48 MW | 0.41 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.29 MW | 0.25 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.9 MW | 1.61 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | 50/50 | 9.42 MW | 9.42 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | 50/50 | 4.04 MW | 4.04 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | 50/50 | 2.26 MW | 2.26 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | 50/50 | 5.18 MW | 5.18 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | 50/50 | 4.24 MW | 4.24 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.69 MW | 2.28 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.86 MW | 1.58 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.88 MW | 0.75 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.59 MW | 0.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.88 MW | 0.75 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.59 MW | 0.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.88 MW | 0.75 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.59 MW | 0.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 2.13 MW | 1.81 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 3.38 MW | 2.87 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.55 MW | 2.17 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925612 | AC1-036 E | Adder | 0.59 MW | 0.5 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 4.34 MW | 3.69 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 2.14 MW | 1.81 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932761 | AC2-100 C | Adder | 2.08 MW | 1.77 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932762 | AC2-100 E | Adder | 1.01 MW | 0.86 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.44 MW | 0.37 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 4.1 MW | 3.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.73 MW | 2.32 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 2.21 MW | 1.88 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.95 MW | 0.81 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.52 MW | 1.29 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | 50/50 | 21.51 MW | 21.51 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | 50/50 | 9.63 MW | 9.63 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941791 | AE2-182 C | Adder | 0.73 MW | 0.62 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941792 | AE2-182 E | Adder | 0.34 MW | 0.29 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 1.2 MW | 1.2 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.81 MW | 0.81 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 25.68 MW | 21.83 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 17.12 MW | 14.55 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 6.96 MW | 5.92 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.5 MW | 2.98 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 3.48 MW | 2.96 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.54 MW | 1.31 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 17.91 MW | 17.91 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 12.07 MW | 12.07 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 14.99 MW | 14.99 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314331 | 6POE | Adder | 0.96 MW | 0.82 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.49 MW | 0.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.84 MW | -2.41 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.82 MW | -0.69 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -4.08 MW | -3.47 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315141 | 1GASTONB | 50/50 | 2.1 MW | 2.1 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315241 | 1Z1-086 GT1 | 50/50 | 5.9 MW | 5.9 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315242 | 1Z1-086 GT2 | 50/50 | 5.9 MW | 5.9 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315243 | 1Z1-086 GT3 | 50/50 | 5.9 MW | 5.9 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315244 | 1Z1-086 ST | 50/50 | 10.26 MW | 10.26 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316087 | AB2-174 C | 50/50 | 0.87 MW | 0.87 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.9 MW | 0.9 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.9 MW | 0.9 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.29 MW | 1.29 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 12.81 MW | 10.88 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 10.98 MW | 9.33 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 12.81 MW | 10.88 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 8.54 MW | 7.26 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 7.32 MW | 6.22 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 8.54 MW | 7.26 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 3.26 MW | 3.26 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 3.87 MW | 3.29 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 2.08 MW | 1.77 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962561 | AG1-105 C O1 | Adder | 3.78 MW | 3.21 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962562 | AG1-105 E O1 | Adder | 2.52 MW | 2.14 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | 50/50 | 1.75 MW | 1.75 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961681 | AG1-008 C | Adder | 6.97 MW | 5.93 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961682 | AG1-008 E | Adder | 3.49 MW | 2.96 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | 50/50 | 3.86 MW | 3.86 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 2.49 MW | 2.49 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.66 MW | 1.66 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.59 MW | 1.35 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 1.24 MW | 1.06 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.56 MW | 2.56 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.76 MW | 0.76 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 46.15 MW | 46.15 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 15.21 MW | 15.21 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.13 MW | 16.13 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.88 MW | 3.88 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.17 MW | 1.17 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.79 MW | 3.79 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.21 MW | 0.21 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.75 MW | 0.75 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.19 MW | 2.19 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.53 MW | 0.53 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.43 MW | 7.43 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.13 MW | 0.13 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.05 MW | 3.05 MW |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.36 MW | 0.36 MW |
Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 962491 | AG1-098 C O1 | 50/50 | 7.35 MW | 7.35 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 962492 | AG1-098 E O1 | 50/50 | 4.9 MW | 4.9 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | 50/50 | 6.27 MW | 6.27 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | 50/50 | 9.4 MW | 9.4 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | 50/50 | 6.41 MW | 6.41 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | 50/50 | 9.62 MW | 9.62 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | 50/50 | 68.22 MW | 68.22 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | 50/50 | 36.75 MW | 36.75 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | 50/50 | 26.9 MW | 26.9 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | 50/50 | 18.32 MW | 18.32 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | 50/50 | 12.21 MW | 12.21 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | 50/50 | 18.32 MW | 18.32 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | 50/50 | 12.21 MW | 12.21 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | Adder | -4.75 MW | -4.04 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315153 | 1CLOVER1 | 50/50 | 11.06 MW | 11.06 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315154 | 1CLOVER2 | 50/50 | 10.96 MW | 10.96 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 927251 | AC1-221 C | Adder | 1.19 MW | 1.01 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 927252 | AC1-221 E | Adder | 1.19 MW | 1.01 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 927261 | AC1-222 C | Adder | 1.76 MW | 1.5 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 927262 | AC1-222 E | Adder | 1.68 MW | 1.43 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934311 | AD1-055 C | Adder | 1.22 MW | 1.04 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934312 | AD1-055 E | Adder | 0.32 MW | 0.27 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934341 | AD1-058 C | Adder | 2.99 MW | 2.54 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934342 | AD1-058 E | Adder | 0.76 MW | 0.65 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | 50/50 | 6.41 MW | 6.41 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | 50/50 | 3.01 MW | 3.01 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934625 | AD1-088 C | 50/50 | 8.1 MW | 8.1 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934626 | AD1-088 E | 50/50 | 3.81 MW | 3.81 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934991 | AD1-131 C | Adder | 0.98 MW | 0.83 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934992 | AD1-131 E | Adder | 0.65 MW | 0.56 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | 50/50 | 6.1 MW | 6.1 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | 50/50 | 4.07 MW | 4.07 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | 50/50 | 1.88 MW | 1.88 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | 50/50 | 0.88 MW | 0.88 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | 50/50 | 41.44 MW | 41.44 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | 50/50 | 27.62 MW | 27.62 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.98 MW | 0.83 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.65 MW | 0.55 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | 50/50 | 15.16 MW | 15.16 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | 50/50 | 5.89 MW | 5.89 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | 50/50 | 7.07 MW | 7.07 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | 50/50 | 9.77 MW | 9.77 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 3.91 MW | 3.32 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 2.61 MW | 2.21 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | -8.8 MW | -7.48 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | -5.17 MW | -4.39 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 932761 | AC2-100 C | Adder | 2.75 MW | 2.34 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 932762 | AC2-100 E | Adder | 1.34 MW | 1.14 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | 50/50 | 46.41 MW | 46.41 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | 50/50 | 20.79 MW | 20.79 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 941791 | AE2-182 C | 50/50 | 1.32 MW | 1.32 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 941792 | AE2-182 E | 50/50 | 0.61 MW | 0.61 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | 50/50 | 50.52 MW | 50.52 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | 50/50 | 33.68 MW | 33.68 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -4.25 MW | -3.61 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934575 | AD1-082 C | Adder | -7.31 MW | -6.22 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -1.09 MW | -0.92 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -5.43 MW | -4.62 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315102 | 1BRUNSWICKG1 | 50/50 | 9.64 MW | 9.64 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315103 | 1BRUNSWICKG2 | 50/50 | 9.64 MW | 9.64 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315104 | 1BRUNSWICKG3 | 50/50 | 9.64 MW | 9.64 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315105 | 1BRUNSWICKS1 | 50/50 | 20.03 MW | 20.03 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315241 | 1Z1-086 GT1 | 50/50 | 12.52 MW | 12.52 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315242 | 1Z1-086 GT2 | 50/50 | 12.52 MW | 12.52 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315243 | 1Z1-086 GT3 | 50/50 | 12.52 MW | 12.52 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315244 | 1Z1-086 ST | 50/50 | 21.77 MW | 21.77 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 316132 | AB2-190 C | Adder | -7.63 MW | -6.49 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | 50/50 | 27.4 MW | 27.4 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | 50/50 | 23.48 MW | 23.48 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | 50/50 | 27.4 MW | 27.4 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | 50/50 | 18.26 MW | 18.26 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | 50/50 | 15.65 MW | 15.65 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | 50/50 | 18.26 MW | 18.26 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 316083 | AB2-161 C | Adder | -3.21 MW | -2.73 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963312 | AG1-180 BAT | Adder | 3.26 MW | 2.77 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 946012 | AF1-266 BAT | 50/50 | 23.74 MW | 23.74 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 940542 | AE2-040 BAT | 50/50 | 5.25 MW | 5.25 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 940652 | AE2-052 BAT | 50/50 | 4.02 MW | 4.02 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.94 MW | 2.94 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.94 MW | 0.94 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 55.95 MW | 55.95 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 18.77 MW | 18.77 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 19.99 MW | 19.99 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 4.45 MW | 4.45 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.49 MW | 1.49 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.71 MW | 4.71 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.26 MW | 0.26 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.92 MW | 0.92 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.71 MW | 2.71 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 9.45 MW | 9.45 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.17 MW | 0.17 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.79 MW | 3.79 MW |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.45 MW | 0.45 MW |
Details for 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.36 MW | 0.31 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.2 MW | 0.17 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961941 | AG1-037 C | Adder | 0.17 MW | 0.15 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.12 MW | 0.1 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962331 | AG1-082 C | Adder | 0.7 MW | 0.59 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.46 MW | 0.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962341 | AG1-083 C | Adder | 0.7 MW | 0.59 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.46 MW | 0.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.34 MW | 1.99 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 3.51 MW | 2.98 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | Adder | 2.38 MW | 2.02 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | Adder | 3.56 MW | 3.03 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 24.66 MW | 20.96 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | Adder | 2.94 MW | 2.5 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | Adder | 1.43 MW | 1.22 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 13.29 MW | 11.29 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964241 | AG1-285 C O1 | Adder | 4.17 MW | 3.54 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964242 | AG1-285 E O1 | Adder | 2.78 MW | 2.36 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964791 | AG1-342 C | Adder | 1.37 MW | 1.17 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964792 | AG1-342 E | Adder | 1.08 MW | 0.92 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 2.04 MW | 1.73 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 1.6 MW | 1.36 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966801 | AG1-551 C | Adder | 0.74 MW | 0.63 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966802 | AG1-551 E | Adder | 0.32 MW | 0.27 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 0.97 MW | 0.82 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.41 MW | 0.35 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965291 | AG1-394 C | Adder | 0.7 MW | 0.59 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965292 | AG1-394 E | Adder | 0.47 MW | 0.4 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965591 | AG1-427 C | Adder | 3.94 MW | 3.35 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965592 | AG1-427 E | Adder | 2.63 MW | 2.24 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | Adder | 2.46 MW | 2.09 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | Adder | 1.63 MW | 1.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 8.83 MW | 7.51 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 5.89 MW | 5.01 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 2.84 MW | 2.41 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 1.89 MW | 1.61 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 2.84 MW | 2.41 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 1.89 MW | 1.61 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 4.71 MW | 4.0 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 1.64 MW | 1.4 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 1.64 MW | 1.4 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | Adder | 9.84 MW | 8.36 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 6.87 MW | 5.84 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 4.58 MW | 3.9 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 6.87 MW | 5.84 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 4.58 MW | 3.9 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | 50/50 | 0.85 MW | 0.85 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | 50/50 | 0.57 MW | 0.57 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | Adder | 3.75 MW | 3.18 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.25 MW | 0.25 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.15 MW | 2.68 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.15 MW | 2.68 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.92 MW | 2.48 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.67 MW | 1.42 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.25 MW | 0.21 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.65 MW | 1.4 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.37 MW | 1.17 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 3.54 MW | 3.01 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.19 MW | 0.16 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.39 MW | 1.18 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | Adder | 10.95 MW | 9.3 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | Adder | 4.98 MW | 4.24 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.44 MW | 2.07 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.45 MW | 1.23 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.82 MW | 0.69 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.41 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926274 | AC1-105 E | Adder | 0.88 MW | 0.75 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.07 MW | 2.61 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.53 MW | 1.3 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 3.75 MW | 3.19 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 1.67 MW | 1.42 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.5 MW | 3.83 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.41 MW | 2.04 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 2.7 MW | 2.29 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.26 MW | 1.07 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 2.8 MW | 2.38 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 1.86 MW | 1.58 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.79 MW | 0.67 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.37 MW | 0.32 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 15.17 MW | 12.89 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 10.11 MW | 8.6 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.49 MW | 0.41 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.21 MW | 0.18 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 5.52 MW | 4.7 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.15 MW | 1.82 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.13 MW | 0.96 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 2.82 MW | 2.4 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 3.9 MW | 3.32 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 1.58 MW | 1.58 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.05 MW | 1.05 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | Adder | 3.65 MW | 3.1 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 2.02 MW | 2.02 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 2.02 MW | 2.02 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316118 | AC1-105 C | Adder | 1.84 MW | 1.56 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 3.01 MW | 2.56 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316140 | AB2-099 C | Adder | 0.2 MW | 0.17 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316141 | AB2-099 E | Adder | 0.09 MW | 0.07 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.1 MW | 0.09 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.39 MW | 0.33 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.23 MW | 0.2 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.51 MW | 1.28 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 7.43 MW | 6.32 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.19 MW | 2.71 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | Adder | 1.78 MW | 1.51 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | 4.08 MW | 3.47 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | Adder | 3.34 MW | 2.84 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.13 MW | 1.81 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.46 MW | 1.25 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.69 MW | 0.59 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.46 MW | 0.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.69 MW | 0.59 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.46 MW | 0.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.69 MW | 0.59 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.46 MW | 0.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.68 MW | 2.28 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.02 MW | 1.72 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.47 MW | 2.95 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.71 MW | 1.45 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.36 MW | 0.3 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 3.24 MW | 2.75 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.16 MW | 1.83 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.76 MW | 1.49 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.75 MW | 0.64 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.2 MW | 1.02 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 16.9 MW | 14.37 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 7.57 MW | 6.44 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 0.94 MW | 0.94 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.63 MW | 0.63 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 20.18 MW | 17.15 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 13.45 MW | 11.43 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 5.8 MW | 4.93 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 2.92 MW | 2.48 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.79 MW | 2.37 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.24 MW | 1.05 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 13.88 MW | 13.88 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 9.36 MW | 9.36 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 11.62 MW | 11.62 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314314 | 3LOCKS | 50/50 | 0.44 MW | 0.44 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314331 | 6POE | Adder | 0.71 MW | 0.61 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.38 MW | 0.38 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.43 MW | -2.06 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934575 | AD1-082 C | Adder | 2.42 MW | 2.05 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934576 | AD1-082 E | Adder | 1.38 MW | 1.17 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.73 MW | -0.62 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.67 MW | -3.12 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942371 | AE2-250 C O1 | 50/50 | 14.0 MW | 14.0 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942372 | AE2-250 E O1 | 50/50 | 7.39 MW | 7.39 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.7 MW | 0.7 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.7 MW | 0.7 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316108 | AB2-160 C | 50/50 | 7.88 MW | 7.88 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316109 | AB2-160 E | 50/50 | 12.86 MW | 12.86 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.0 MW | 1.0 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939195 | AE1-149 C | Adder | 3.62 MW | 3.08 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939196 | AE1-149 E | Adder | 2.42 MW | 2.05 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 10.25 MW | 8.71 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 8.78 MW | 7.47 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 10.25 MW | 8.71 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 6.83 MW | 5.81 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 5.86 MW | 4.98 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 6.83 MW | 5.81 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940431 | AE2-027 C O1 | 50/50 | 11.69 MW | 11.69 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940432 | AE2-027 E O1 | 50/50 | 7.79 MW | 7.79 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 2.53 MW | 2.53 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | Adder | 1.21 MW | 1.03 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 3.07 MW | 2.61 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 1.65 MW | 1.4 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962561 | AG1-105 C O1 | Adder | 2.97 MW | 2.52 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962562 | AG1-105 E O1 | Adder | 1.98 MW | 1.68 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | Adder | 1.38 MW | 1.17 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961681 | AG1-008 C | Adder | 5.81 MW | 4.94 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961682 | AG1-008 E | Adder | 2.91 MW | 2.47 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962271 | AG1-075 C O1 | 50/50 | 24.16 MW | 24.16 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962272 | AG1-075 E O1 | 50/50 | 14.72 MW | 14.72 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | Adder | 3.04 MW | 2.59 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 1.93 MW | 1.93 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.29 MW | 1.29 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.3 MW | 1.11 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 0.98 MW | 0.83 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316083 | AB2-161 C | Adder | 1.06 MW | 0.9 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316084 | AB2-161 E | Adder | 1.73 MW | 1.47 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.02 MW | 2.02 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.6 MW | 0.6 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 36.41 MW | 36.41 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.9 MW | 11.9 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 12.67 MW | 12.67 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.06 MW | 3.06 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.93 MW | 0.93 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.98 MW | 2.98 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.59 MW | 0.59 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.72 MW | 1.72 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.42 MW | 0.42 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.92 MW | 5.92 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.4 MW | 2.4 MW |
6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.28 MW | 0.28 MW |
Details for 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.36 MW | 0.31 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.2 MW | 0.17 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961941 | AG1-037 C | Adder | 0.17 MW | 0.15 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.12 MW | 0.1 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962331 | AG1-082 C | Adder | 0.7 MW | 0.59 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.46 MW | 0.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962341 | AG1-083 C | Adder | 0.7 MW | 0.59 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.46 MW | 0.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.34 MW | 1.99 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 3.51 MW | 2.98 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | Adder | 2.38 MW | 2.02 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | Adder | 3.56 MW | 3.03 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 24.66 MW | 20.96 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | Adder | 2.94 MW | 2.5 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | Adder | 1.43 MW | 1.22 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 13.29 MW | 11.29 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 2.04 MW | 1.73 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 1.6 MW | 1.36 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 0.97 MW | 0.82 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.41 MW | 0.35 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965291 | AG1-394 C | Adder | 0.7 MW | 0.59 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965292 | AG1-394 E | Adder | 0.47 MW | 0.4 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | Adder | 2.46 MW | 2.09 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | Adder | 1.63 MW | 1.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 8.83 MW | 7.51 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 5.89 MW | 5.01 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 2.84 MW | 2.41 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 1.89 MW | 1.61 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 2.84 MW | 2.41 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 1.89 MW | 1.61 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 4.71 MW | 4.0 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 1.64 MW | 1.4 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 1.64 MW | 1.4 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | Adder | 9.84 MW | 8.36 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 6.87 MW | 5.84 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 4.58 MW | 3.9 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 6.87 MW | 5.84 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 4.58 MW | 3.9 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | 50/50 | 0.85 MW | 0.85 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | 50/50 | 0.57 MW | 0.57 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | Adder | 3.75 MW | 3.18 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.25 MW | 0.25 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.15 MW | 2.68 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.15 MW | 2.68 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.92 MW | 2.48 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.67 MW | 1.42 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.65 MW | 1.4 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.37 MW | 1.17 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 3.54 MW | 3.01 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.19 MW | 0.16 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.39 MW | 1.18 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | Adder | 10.95 MW | 9.3 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | Adder | 4.98 MW | 4.24 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.44 MW | 2.07 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.45 MW | 1.23 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.82 MW | 0.69 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.41 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.07 MW | 2.61 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.53 MW | 1.3 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 3.75 MW | 3.19 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 1.67 MW | 1.42 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.5 MW | 3.83 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.41 MW | 2.04 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 2.7 MW | 2.29 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.26 MW | 1.07 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 2.8 MW | 2.38 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 1.86 MW | 1.58 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.79 MW | 0.67 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.37 MW | 0.32 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 15.17 MW | 12.89 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 10.11 MW | 8.6 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.49 MW | 0.41 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.21 MW | 0.18 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 5.52 MW | 4.7 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.15 MW | 1.82 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.13 MW | 0.96 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 2.82 MW | 2.4 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 3.9 MW | 3.32 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 1.58 MW | 1.58 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.05 MW | 1.05 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | Adder | 3.65 MW | 3.1 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 2.02 MW | 2.02 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 2.02 MW | 2.02 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 3.01 MW | 2.56 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316140 | AB2-099 C | Adder | 0.2 MW | 0.17 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316141 | AB2-099 E | Adder | 0.09 MW | 0.07 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.1 MW | 0.09 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.39 MW | 0.33 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.23 MW | 0.2 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.51 MW | 1.28 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 7.43 MW | 6.32 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.19 MW | 2.71 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | Adder | 1.78 MW | 1.51 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | 4.08 MW | 3.47 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | Adder | 3.34 MW | 2.84 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.13 MW | 1.81 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.46 MW | 1.25 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.69 MW | 0.59 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.46 MW | 0.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.69 MW | 0.59 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.46 MW | 0.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.69 MW | 0.59 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.46 MW | 0.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.68 MW | 2.28 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.02 MW | 1.72 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.47 MW | 2.95 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.71 MW | 1.45 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 3.24 MW | 2.75 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.16 MW | 1.83 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.76 MW | 1.49 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.75 MW | 0.64 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.2 MW | 1.02 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 16.9 MW | 14.37 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 7.57 MW | 6.44 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 0.94 MW | 0.94 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.63 MW | 0.63 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 20.18 MW | 17.15 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 13.45 MW | 11.43 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 5.8 MW | 4.93 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 2.92 MW | 2.48 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.79 MW | 2.37 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.24 MW | 1.05 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 13.88 MW | 13.88 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 9.36 MW | 9.36 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 11.62 MW | 11.62 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314314 | 3LOCKS | 50/50 | 0.44 MW | 0.44 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314331 | 6POE | Adder | 0.71 MW | 0.61 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.38 MW | 0.38 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.43 MW | -2.06 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.73 MW | -0.62 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.67 MW | -3.12 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942371 | AE2-250 C O1 | 50/50 | 14.0 MW | 14.0 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942372 | AE2-250 E O1 | 50/50 | 7.39 MW | 7.39 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.7 MW | 0.7 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.7 MW | 0.7 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316108 | AB2-160 C | 50/50 | 7.88 MW | 7.88 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316109 | AB2-160 E | 50/50 | 12.86 MW | 12.86 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.0 MW | 1.0 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939195 | AE1-149 C | Adder | 3.62 MW | 3.08 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939196 | AE1-149 E | Adder | 2.42 MW | 2.05 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 10.25 MW | 8.71 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 8.78 MW | 7.47 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 10.25 MW | 8.71 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 6.83 MW | 5.81 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 5.86 MW | 4.98 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 6.83 MW | 5.81 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940431 | AE2-027 C O1 | 50/50 | 11.69 MW | 11.69 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940432 | AE2-027 E O1 | 50/50 | 7.79 MW | 7.79 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 2.53 MW | 2.53 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | Adder | 1.21 MW | 1.03 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942001 | AE2-212 C | 50/50 | 7.61 MW | 7.61 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942002 | AE2-212 E | 50/50 | 5.07 MW | 5.07 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 3.07 MW | 2.61 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 1.65 MW | 1.4 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | Adder | 1.38 MW | 1.17 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961681 | AG1-008 C | Adder | 5.81 MW | 4.94 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961682 | AG1-008 E | Adder | 2.91 MW | 2.47 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962271 | AG1-075 C O1 | 50/50 | 24.16 MW | 24.16 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962272 | AG1-075 E O1 | 50/50 | 14.72 MW | 14.72 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | Adder | 3.04 MW | 2.59 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 1.93 MW | 1.93 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.29 MW | 1.29 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 0.98 MW | 0.83 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.02 MW | 2.02 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.6 MW | 0.6 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 36.41 MW | 36.41 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.9 MW | 11.9 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 12.67 MW | 12.67 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.06 MW | 3.06 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.93 MW | 0.93 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.98 MW | 2.98 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.59 MW | 0.59 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.72 MW | 1.72 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.42 MW | 0.42 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.92 MW | 5.92 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.4 MW | 2.4 MW |
6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.28 MW | 0.28 MW |
Details for 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.35 MW | 0.3 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.2 MW | 0.17 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961941 | AG1-037 C | Adder | 0.18 MW | 0.15 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.12 MW | 0.1 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962331 | AG1-082 C | Adder | 0.73 MW | 0.62 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.49 MW | 0.41 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962341 | AG1-083 C | Adder | 0.73 MW | 0.62 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.49 MW | 0.41 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.2 MW | 1.87 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 3.3 MW | 2.8 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | Adder | 2.23 MW | 1.9 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | Adder | 3.34 MW | 2.84 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 23.42 MW | 19.91 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | Adder | 2.75 MW | 2.34 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | Adder | 1.34 MW | 1.14 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 12.62 MW | 10.72 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964241 | AG1-285 C O1 | Adder | 3.95 MW | 3.35 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964242 | AG1-285 E O1 | Adder | 2.63 MW | 2.24 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964791 | AG1-342 C | Adder | 1.3 MW | 1.1 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964792 | AG1-342 E | Adder | 1.02 MW | 0.87 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 2.3 MW | 1.96 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 1.81 MW | 1.54 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966801 | AG1-551 C | Adder | 0.75 MW | 0.64 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966802 | AG1-551 E | Adder | 0.32 MW | 0.28 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 0.94 MW | 0.8 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.4 MW | 0.34 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965291 | AG1-394 C | Adder | 0.79 MW | 0.67 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965292 | AG1-394 E | Adder | 0.53 MW | 0.45 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965591 | AG1-427 C | Adder | 3.73 MW | 3.17 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965592 | AG1-427 E | Adder | 2.49 MW | 2.12 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | Adder | 2.3 MW | 1.95 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | Adder | 1.53 MW | 1.3 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965691 | AG1-437 C O1 | Adder | 3.13 MW | 2.66 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965692 | AG1-437 E O1 | Adder | 2.09 MW | 1.77 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965701 | AG1-438 C O1 | Adder | 3.13 MW | 2.66 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965702 | AG1-438 E O1 | Adder | 2.09 MW | 1.77 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 8.7 MW | 7.4 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 5.8 MW | 4.93 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 2.73 MW | 2.32 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 1.82 MW | 1.55 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 2.73 MW | 2.32 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 1.82 MW | 1.55 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965741 | AG1-442 O1 | Adder | 1.83 MW | 1.55 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965751 | AG1-443 O1 | Adder | 1.83 MW | 1.55 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 4.64 MW | 3.94 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 1.58 MW | 1.34 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 1.58 MW | 1.34 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | Adder | 9.23 MW | 7.84 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 6.45 MW | 5.48 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 4.3 MW | 3.65 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 6.45 MW | 5.48 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 4.3 MW | 3.65 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | Adder | 0.8 MW | 0.68 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | Adder | 0.53 MW | 0.45 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | Adder | 3.56 MW | 3.02 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314541 | 3WATKINS | Adder | 0.25 MW | 0.21 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | Adder | 0.24 MW | 0.2 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.05 MW | 2.59 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.05 MW | 2.59 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.88 MW | 2.45 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.71 MW | 1.46 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.25 MW | 0.21 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.62 MW | 1.38 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.34 MW | 1.14 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.07 MW | 3.46 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.18 MW | 0.16 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.34 MW | 1.14 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | Adder | 10.42 MW | 8.86 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | Adder | 4.74 MW | 4.03 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.42 MW | 2.06 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.44 MW | 1.22 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.81 MW | 0.69 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.4 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926274 | AC1-105 E | Adder | 0.83 MW | 0.71 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.05 MW | 2.59 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.52 MW | 1.29 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 3.68 MW | 3.13 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 1.64 MW | 1.39 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.32 MW | 3.67 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.31 MW | 1.96 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 2.53 MW | 2.15 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.19 MW | 1.01 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 2.63 MW | 2.24 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 1.76 MW | 1.49 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.74 MW | 0.63 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.35 MW | 0.3 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 14.22 MW | 12.09 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 9.48 MW | 8.06 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.51 MW | 0.43 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.22 MW | 0.19 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 5.18 MW | 4.4 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.01 MW | 1.71 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.1 MW | 0.93 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 2.65 MW | 2.25 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 3.66 MW | 3.11 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | Adder | 1.47 MW | 1.25 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | Adder | 0.98 MW | 0.83 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | Adder | 3.44 MW | 2.93 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 1.87 MW | 1.87 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 1.87 MW | 1.87 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316118 | AC1-105 C | Adder | 1.74 MW | 1.48 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 2.91 MW | 2.48 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316140 | AB2-099 C | Adder | 0.21 MW | 0.18 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316141 | AB2-099 E | Adder | 0.09 MW | 0.08 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.11 MW | 0.1 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.39 MW | 0.33 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.22 MW | 0.19 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.46 MW | 1.24 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 7.08 MW | 6.01 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.03 MW | 2.58 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | Adder | 1.69 MW | 1.44 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | 3.87 MW | 3.29 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | Adder | 3.17 MW | 2.69 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.07 MW | 1.76 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.39 MW | 1.18 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.66 MW | 0.56 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.44 MW | 0.37 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.66 MW | 0.56 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.44 MW | 0.37 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.66 MW | 0.56 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.44 MW | 0.37 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 1.81 MW | 1.54 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.6 MW | 2.21 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 1.96 MW | 1.67 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.45 MW | 2.93 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.7 MW | 1.44 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.37 MW | 0.32 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 3.09 MW | 2.63 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.06 MW | 1.75 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.7 MW | 1.45 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.73 MW | 0.62 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.15 MW | 0.97 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 15.85 MW | 13.48 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 7.1 MW | 6.04 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | Adder | 0.87 MW | 0.74 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | Adder | 0.59 MW | 0.5 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 18.95 MW | 16.11 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 12.63 MW | 10.74 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 6.34 MW | 5.39 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.19 MW | 2.71 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.77 MW | 2.35 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.23 MW | 1.04 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314539 | 3UNCAMP | Adder | 2.18 MW | 1.85 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938771 | AE1-103 C | Adder | 1.03 MW | 0.88 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938772 | AE1-103 E | Adder | 1.43 MW | 1.21 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 12.59 MW | 12.59 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 8.49 MW | 8.49 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 10.54 MW | 10.54 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314331 | 6POE | 50/50 | 4.81 MW | 4.81 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.34 MW | 0.34 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -1.94 MW | -1.65 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934575 | AD1-082 C | 50/50 | 8.21 MW | 8.21 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934576 | AD1-082 E | 50/50 | 4.68 MW | 4.68 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936661 | AD2-085 C | Adder | 1.91 MW | 1.62 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936662 | AD2-085 E | Adder | 3.12 MW | 2.65 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.7 MW | -0.6 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.52 MW | -3.0 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942341 | AE2-247 C | Adder | 0.83 MW | 0.71 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942342 | AE2-247 E | Adder | 1.15 MW | 0.98 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943461 | AF1-017 C | Adder | 0.75 MW | 0.64 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943462 | AF1-017 E | Adder | 1.23 MW | 1.05 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.65 MW | 0.65 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.65 MW | 0.65 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 0.9 MW | 0.9 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932591 | AC2-079 C O1 | 50/50 | 4.15 MW | 4.15 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932592 | AC2-079 E O1 | 50/50 | 6.78 MW | 6.78 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939195 | AE1-149 C | 50/50 | 12.93 MW | 12.93 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939196 | AE1-149 E | 50/50 | 8.62 MW | 8.62 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 10.02 MW | 8.52 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 8.59 MW | 7.3 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 10.02 MW | 8.52 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 6.68 MW | 5.68 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 5.73 MW | 4.87 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 6.68 MW | 5.68 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 2.29 MW | 2.29 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | 50/50 | 4.31 MW | 4.31 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941101 | AE2-104 C O1 | Adder | 1.1 MW | 0.93 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941102 | AE2-104 E O1 | Adder | 1.74 MW | 1.48 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958161 | AF2-110 C | Adder | 0.45 MW | 0.39 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958162 | AF2-110 E | Adder | 0.71 MW | 0.6 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933981 | AD1-022 C | Adder | 2.62 MW | 2.23 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933982 | AD1-022 E | Adder | 1.42 MW | 1.21 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 2.98 MW | 2.53 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 1.6 MW | 1.36 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962561 | AG1-105 C O1 | Adder | 2.81 MW | 2.39 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962562 | AG1-105 E O1 | Adder | 1.87 MW | 1.59 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | Adder | 1.31 MW | 1.12 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961681 | AG1-008 C | Adder | 6.35 MW | 5.4 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961682 | AG1-008 E | Adder | 3.18 MW | 2.7 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | Adder | 2.9 MW | 2.46 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 1.75 MW | 1.75 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.17 MW | 1.17 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.35 MW | 1.15 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 0.93 MW | 0.79 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316083 | AB2-161 C | 50/50 | 3.6 MW | 3.6 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316084 | AB2-161 E | 50/50 | 5.88 MW | 5.88 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.93 MW | 1.93 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 34.67 MW | 34.67 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.22 MW | 11.22 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 12.01 MW | 12.01 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.92 MW | 2.92 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.9 MW | 0.9 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.83 MW | 2.83 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.55 MW | 0.55 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.62 MW | 1.62 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.72 MW | 5.72 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.28 MW | 2.28 MW |
6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
Details for 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.35 MW | 0.3 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.2 MW | 0.17 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961941 | AG1-037 C | Adder | 0.18 MW | 0.15 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.12 MW | 0.1 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962331 | AG1-082 C | Adder | 0.73 MW | 0.62 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.49 MW | 0.41 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962341 | AG1-083 C | Adder | 0.73 MW | 0.62 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.49 MW | 0.41 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.2 MW | 1.87 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 3.3 MW | 2.8 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | Adder | 2.23 MW | 1.9 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | Adder | 3.34 MW | 2.84 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 23.42 MW | 19.91 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | Adder | 2.75 MW | 2.34 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | Adder | 1.34 MW | 1.14 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 12.62 MW | 10.72 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964241 | AG1-285 C O1 | Adder | 3.95 MW | 3.35 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964242 | AG1-285 E O1 | Adder | 2.63 MW | 2.24 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964791 | AG1-342 C | Adder | 1.3 MW | 1.1 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964792 | AG1-342 E | Adder | 1.02 MW | 0.87 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 2.3 MW | 1.96 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 1.81 MW | 1.54 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966801 | AG1-551 C | Adder | 0.75 MW | 0.64 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966802 | AG1-551 E | Adder | 0.32 MW | 0.28 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 0.94 MW | 0.8 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.4 MW | 0.34 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965291 | AG1-394 C | Adder | 0.79 MW | 0.67 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965292 | AG1-394 E | Adder | 0.53 MW | 0.45 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965591 | AG1-427 C | Adder | 3.73 MW | 3.17 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965592 | AG1-427 E | Adder | 2.49 MW | 2.12 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | Adder | 2.3 MW | 1.95 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | Adder | 1.53 MW | 1.3 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965691 | AG1-437 C O1 | Adder | 3.13 MW | 2.66 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965692 | AG1-437 E O1 | Adder | 2.09 MW | 1.77 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965701 | AG1-438 C O1 | Adder | 3.13 MW | 2.66 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965702 | AG1-438 E O1 | Adder | 2.09 MW | 1.77 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 8.7 MW | 7.4 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 5.8 MW | 4.93 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 2.73 MW | 2.32 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 1.82 MW | 1.55 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 2.73 MW | 2.32 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 1.82 MW | 1.55 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965741 | AG1-442 O1 | Adder | 1.83 MW | 1.55 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965751 | AG1-443 O1 | Adder | 1.83 MW | 1.55 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 4.64 MW | 3.94 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 1.58 MW | 1.34 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 1.58 MW | 1.34 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | Adder | 9.23 MW | 7.84 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 6.45 MW | 5.48 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 4.3 MW | 3.65 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 6.45 MW | 5.48 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 4.3 MW | 3.65 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | Adder | 0.8 MW | 0.68 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | Adder | 0.53 MW | 0.45 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | Adder | 3.56 MW | 3.02 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314541 | 3WATKINS | Adder | 0.25 MW | 0.21 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | Adder | 0.24 MW | 0.2 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.05 MW | 2.59 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.05 MW | 2.59 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.88 MW | 2.45 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.71 MW | 1.46 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.25 MW | 0.21 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.62 MW | 1.38 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.34 MW | 1.14 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.07 MW | 3.46 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.18 MW | 0.16 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.34 MW | 1.14 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | Adder | 10.42 MW | 8.86 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | Adder | 4.74 MW | 4.03 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.42 MW | 2.06 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.44 MW | 1.22 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.81 MW | 0.69 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.4 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926274 | AC1-105 E | Adder | 0.83 MW | 0.71 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.05 MW | 2.59 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.52 MW | 1.29 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 3.68 MW | 3.13 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 1.64 MW | 1.39 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.32 MW | 3.67 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.31 MW | 1.96 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 2.53 MW | 2.15 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.19 MW | 1.01 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 2.63 MW | 2.24 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 1.76 MW | 1.49 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.74 MW | 0.63 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.35 MW | 0.3 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 14.22 MW | 12.09 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 9.48 MW | 8.06 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.51 MW | 0.43 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.22 MW | 0.19 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 5.18 MW | 4.4 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.01 MW | 1.71 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.1 MW | 0.93 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 2.65 MW | 2.25 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 3.66 MW | 3.11 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | Adder | 1.47 MW | 1.25 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | Adder | 0.98 MW | 0.83 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | Adder | 3.44 MW | 2.93 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 1.87 MW | 1.87 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 1.87 MW | 1.87 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316118 | AC1-105 C | Adder | 1.74 MW | 1.48 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 2.91 MW | 2.48 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316140 | AB2-099 C | Adder | 0.21 MW | 0.18 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316141 | AB2-099 E | Adder | 0.09 MW | 0.08 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.11 MW | 0.1 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.39 MW | 0.33 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.22 MW | 0.19 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.46 MW | 1.24 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 7.08 MW | 6.01 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.03 MW | 2.58 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | Adder | 1.69 MW | 1.44 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | 3.87 MW | 3.29 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | Adder | 3.17 MW | 2.69 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.07 MW | 1.76 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.39 MW | 1.18 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.66 MW | 0.56 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.44 MW | 0.37 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.66 MW | 0.56 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.44 MW | 0.37 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.66 MW | 0.56 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.44 MW | 0.37 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 1.81 MW | 1.54 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.6 MW | 2.21 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 1.96 MW | 1.67 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.45 MW | 2.93 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.7 MW | 1.44 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.37 MW | 0.32 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 3.09 MW | 2.63 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.06 MW | 1.75 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.7 MW | 1.45 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.73 MW | 0.62 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.15 MW | 0.97 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 15.85 MW | 13.48 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 7.1 MW | 6.04 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | Adder | 0.87 MW | 0.74 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | Adder | 0.59 MW | 0.5 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 18.95 MW | 16.11 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 12.63 MW | 10.74 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 6.34 MW | 5.39 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.19 MW | 2.71 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.77 MW | 2.35 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.23 MW | 1.04 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314539 | 3UNCAMP | Adder | 2.18 MW | 1.85 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938771 | AE1-103 C | Adder | 1.03 MW | 0.88 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938772 | AE1-103 E | Adder | 1.43 MW | 1.21 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 12.59 MW | 12.59 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 8.49 MW | 8.49 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 10.54 MW | 10.54 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314331 | 6POE | 50/50 | 4.81 MW | 4.81 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.34 MW | 0.34 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -1.94 MW | -1.65 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934575 | AD1-082 C | 50/50 | 8.21 MW | 8.21 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934576 | AD1-082 E | 50/50 | 4.68 MW | 4.68 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936661 | AD2-085 C | Adder | 1.91 MW | 1.62 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936662 | AD2-085 E | Adder | 3.12 MW | 2.65 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.7 MW | -0.6 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.52 MW | -3.0 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942341 | AE2-247 C | Adder | 0.83 MW | 0.71 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942342 | AE2-247 E | Adder | 1.15 MW | 0.98 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943461 | AF1-017 C | Adder | 0.75 MW | 0.64 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943462 | AF1-017 E | Adder | 1.23 MW | 1.05 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.65 MW | 0.65 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.65 MW | 0.65 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 0.9 MW | 0.9 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932591 | AC2-079 C O1 | 50/50 | 4.15 MW | 4.15 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932592 | AC2-079 E O1 | 50/50 | 6.78 MW | 6.78 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939195 | AE1-149 C | 50/50 | 12.93 MW | 12.93 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939196 | AE1-149 E | 50/50 | 8.62 MW | 8.62 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 10.02 MW | 8.52 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 8.59 MW | 7.3 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 10.02 MW | 8.52 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 6.68 MW | 5.68 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 5.73 MW | 4.87 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 6.68 MW | 5.68 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 2.29 MW | 2.29 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | 50/50 | 4.31 MW | 4.31 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941101 | AE2-104 C O1 | Adder | 1.1 MW | 0.93 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941102 | AE2-104 E O1 | Adder | 1.74 MW | 1.48 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958161 | AF2-110 C | Adder | 0.45 MW | 0.39 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958162 | AF2-110 E | Adder | 0.71 MW | 0.6 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933981 | AD1-022 C | Adder | 2.62 MW | 2.23 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933982 | AD1-022 E | Adder | 1.42 MW | 1.21 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 2.98 MW | 2.53 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 1.6 MW | 1.36 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962561 | AG1-105 C O1 | Adder | 2.81 MW | 2.39 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962562 | AG1-105 E O1 | Adder | 1.87 MW | 1.59 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | Adder | 1.31 MW | 1.12 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961681 | AG1-008 C | Adder | 6.35 MW | 5.4 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961682 | AG1-008 E | Adder | 3.18 MW | 2.7 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | Adder | 2.9 MW | 2.46 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 1.75 MW | 1.75 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.17 MW | 1.17 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.35 MW | 1.15 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 0.93 MW | 0.79 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316083 | AB2-161 C | 50/50 | 3.6 MW | 3.6 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316084 | AB2-161 E | 50/50 | 5.88 MW | 5.88 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.93 MW | 1.93 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 34.67 MW | 34.67 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.22 MW | 11.22 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 12.01 MW | 12.01 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.92 MW | 2.92 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.9 MW | 0.9 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.83 MW | 2.83 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.55 MW | 0.55 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.62 MW | 1.62 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.72 MW | 5.72 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.28 MW | 2.28 MW |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 961941 | AG1-037 C | Adder | 0.62 MW | 0.52 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 961942 | AG1-037 E | Adder | 0.41 MW | 0.35 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962331 | AG1-082 C | Adder | 2.46 MW | 2.09 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962332 | AG1-082 E | Adder | 1.64 MW | 1.4 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962341 | AG1-083 C | Adder | 2.46 MW | 2.09 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962342 | AG1-083 E | Adder | 1.64 MW | 1.4 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963041 | AG1-153 C | Adder | 8.1 MW | 6.89 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963042 | AG1-153 E | Adder | 12.16 MW | 10.33 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963111 | AG1-160 C | Adder | 8.24 MW | 7.0 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963112 | AG1-160 E | Adder | 12.36 MW | 10.51 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963291 | AG1-178 C O2 | 50/50 | 98.13 MW | 98.13 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963351 | AG1-184 O2 | 50/50 | 52.87 MW | 52.87 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 964801 | AG1-343 C | Adder | 7.17 MW | 6.09 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 964802 | AG1-343 E | Adder | 5.63 MW | 4.79 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966801 | AG1-551 C | Adder | 2.79 MW | 2.37 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966802 | AG1-551 E | Adder | 1.2 MW | 1.02 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965291 | AG1-394 C | Adder | 2.46 MW | 2.09 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965292 | AG1-394 E | Adder | 1.64 MW | 1.39 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965691 | AG1-437 C O1 | Adder | 13.54 MW | 11.51 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965692 | AG1-437 E O1 | Adder | 9.02 MW | 7.67 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965701 | AG1-438 C O1 | Adder | 13.54 MW | 11.51 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965702 | AG1-438 E O1 | Adder | 9.02 MW | 7.67 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965741 | AG1-442 O1 | Adder | 7.9 MW | 6.71 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965751 | AG1-443 O1 | Adder | 7.9 MW | 6.71 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965811 | AG1-449 | Adder | 34.23 MW | 29.09 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966361 | AG1-505 C | Adder | 23.78 MW | 20.21 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966362 | AG1-505 E | Adder | 15.85 MW | 13.47 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966371 | AG1-506 C | Adder | 23.78 MW | 20.21 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966372 | AG1-506 E | Adder | 15.85 MW | 13.47 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314541 | 3WATKINS | Adder | 0.89 MW | 0.76 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314594 | 6PLYMOTH | Adder | 0.13 MW | 0.11 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 920042 | AA2-088 E OP | Adder | 12.85 MW | 10.93 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934521 | AD1-076 C | Adder | 75.58 MW | 64.24 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934522 | AD1-076 E | Adder | 38.48 MW | 32.71 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934615 | AD1-087 C | Adder | 9.11 MW | 7.74 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934616 | AD1-087 E | Adder | 4.27 MW | 3.63 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937481 | AD2-202 C O1 | Adder | 2.67 MW | 2.27 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937482 | AD2-202 E O1 | Adder | 1.25 MW | 1.06 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942931 | AE2-313 C | Adder | 52.76 MW | 44.84 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942932 | AE2-313 E | Adder | 35.17 MW | 29.89 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943171 | AE2-346 C | Adder | 1.72 MW | 1.46 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943172 | AE2-346 E | Adder | 0.74 MW | 0.63 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944011 | AF1-069 C | Adder | 19.23 MW | 16.35 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944012 | AF1-069 E | Adder | 7.47 MW | 6.35 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945811 | AF1-246 C O1 | Adder | 9.64 MW | 8.2 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945812 | AF1-246 E O1 | Adder | 13.32 MW | 11.32 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315293 | 1DOMTR9 | Adder | 9.21 MW | 7.83 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315294 | 1DOMTR10 | Adder | 11.29 MW | 9.59 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 316140 | AB2-099 C | Adder | 0.72 MW | 0.61 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 316141 | AB2-099 E | Adder | 0.31 MW | 0.26 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 900672 | V4-068 E | Adder | 0.36 MW | 0.31 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 917332 | Z2-043 E | Adder | 1.25 MW | 1.07 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925122 | AB2-169 E | Adder | 7.49 MW | 6.37 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938222 | AE1-035 E | Adder | 1.41 MW | 1.2 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940491 | AE2-034 C | Adder | 10.43 MW | 8.86 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940492 | AE2-034 E | Adder | 4.47 MW | 3.8 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941031 | AE2-094 C | Adder | 58.86 MW | 50.03 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941032 | AE2-094 E | Adder | 26.36 MW | 22.41 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957481 | AF2-042 C | Adder | 68.89 MW | 58.56 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957482 | AF2-042 E | Adder | 45.93 MW | 39.04 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957521 | AF2-046 C | Adder | 20.45 MW | 17.38 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957522 | AF2-046 E | Adder | 10.29 MW | 8.74 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957531 | AF2-047 C | Adder | 24.78 MW | 21.06 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957532 | AF2-047 E | Adder | 12.46 MW | 10.59 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314539 | 3UNCAMP | Adder | 8.08 MW | 6.87 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 916042 | Z1-036 E | Adder | 44.34 MW | 37.69 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938771 | AE1-103 C | Adder | 3.96 MW | 3.37 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938772 | AE1-103 E | Adder | 5.47 MW | 4.65 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940641 | AE2-051 C O1 | 50/50 | 27.82 MW | 27.82 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940642 | AE2-051 E O1 | 50/50 | 18.55 MW | 18.55 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 313717 | 6SLIGO L2192 | Adder | 3.69 MW | 3.14 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314177 | 3HAYES89 | Adder | 0.06 MW | 0.05 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314466 | 6FENTRES | 50/50 | 3.81 MW | 3.81 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314491 | 3PENDLTN | 50/50 | 0.58 MW | 0.58 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314525 | 6KINGFORK | Adder | 6.63 MW | 5.63 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314550 | 6HICKORY | 50/50 | 7.0 MW | 7.0 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314632 | 6AYDLETOLD | Adder | 3.69 MW | 3.14 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 919152 | AA1-139 E | Adder | 10.82 MW | 9.2 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926661 | AC1-147 C | 50/50 | 0.65 MW | 0.65 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926662 | AC1-147 E | 50/50 | 2.23 MW | 2.23 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926754 | AC1-161 C | 50/50 | 60.55 MW | 60.55 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926755 | AC1-161 E | 50/50 | 25.85 MW | 25.85 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934061 | AD1-033 C | 50/50 | 12.88 MW | 12.88 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934062 | AD1-033 E | 50/50 | 8.58 MW | 8.58 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935112 | AD1-144 E | Adder | 1.45 MW | 1.23 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936661 | AD2-085 C | Adder | 4.22 MW | 3.59 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936662 | AD2-085 E | Adder | 6.88 MW | 5.85 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937221 | AD2-160 C O1 | 50/50 | 9.92 MW | 9.92 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937222 | AD2-160 E O1 | 50/50 | 5.2 MW | 5.2 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942341 | AE2-247 C | Adder | 1.82 MW | 1.55 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942342 | AE2-247 E | Adder | 2.52 MW | 2.14 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942401 | AE2-253 C | 50/50 | 10.43 MW | 10.43 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942402 | AE2-253 E | 50/50 | 4.69 MW | 4.69 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943461 | AF1-017 C | Adder | 1.65 MW | 1.4 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943462 | AF1-017 E | Adder | 2.69 MW | 2.29 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943611 | AF1-032 C | Adder | 2.82 MW | 2.4 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943612 | AF1-032 E | Adder | 1.5 MW | 1.27 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943621 | AF1-033 C | Adder | 2.84 MW | 2.42 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943622 | AF1-033 E | Adder | 1.46 MW | 1.24 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944871 | AF1-152 C | Adder | 8.42 MW | 7.15 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944872 | AF1-152 E | Adder | 5.61 MW | 4.77 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945361 | AF1-201 C O1 | Adder | 6.17 MW | 5.24 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315098 | 1CHESPKA | 50/50 | 0.77 MW | 0.77 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315099 | 1CHESPKB | 50/50 | 1.27 MW | 1.27 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315108 | 1ELIZAR1 | 50/50 | 5.67 MW | 5.67 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315109 | 1ELIZAR2 | 50/50 | 5.57 MW | 5.57 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315110 | 1ELIZAR3 | 50/50 | 5.74 MW | 5.74 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315233 | 1SURRY 2 | 50/50 | 56.18 MW | 56.18 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 913392 | Y1-086 E | Adder | 3.6 MW | 3.06 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 916192 | Z1-068 E | 50/50 | 3.19 MW | 3.19 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 923832 | AB2-022 E | Adder | 2.03 MW | 1.73 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932044 | AC2-012 C | 50/50 | 13.54 MW | 13.54 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932046 | AC2-012 E | 50/50 | 22.09 MW | 22.09 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938535 | AE1-072 C | Adder | 29.45 MW | 25.03 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938536 | AE1-072 E | Adder | 15.35 MW | 13.05 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939312 | AE1-162 E | Adder | 1.96 MW | 1.67 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939414 | AE1-173_C1 | 50/50 | 51.93 MW | 51.93 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939415 | AE1-173_C2 | 50/50 | 44.51 MW | 44.51 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939416 | AE1-173_C3 | 50/50 | 51.93 MW | 51.93 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939423 | AE1-173_E1 | 50/50 | 34.62 MW | 34.62 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939424 | AE1-173_E2 | 50/50 | 29.67 MW | 29.67 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939425 | AE1-173_E3 | 50/50 | 34.62 MW | 34.62 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941101 | AE2-104 C O1 | Adder | 4.92 MW | 4.18 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941102 | AE2-104 E O1 | Adder | 7.82 MW | 6.64 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941281 | AE2-122 C O1 | 50/50 | 48.37 MW | 48.37 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941282 | AE2-122 E O1 | 50/50 | 195.19 MW | 195.19 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941291 | AE2-123 C O1 | 50/50 | 49.71 MW | 49.71 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941292 | AE2-123 E O1 | 50/50 | 193.85 MW | 193.85 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941301 | AE2-124 C O1 | 50/50 | 45.24 MW | 45.24 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941302 | AE2-124 E O1 | 50/50 | 198.51 MW | 198.51 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957491 | AF2-043 C | Adder | 3.45 MW | 2.94 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957492 | AF2-043 E | Adder | 2.3 MW | 1.96 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957631 | AF2-057 | 50/50 | 6.04 MW | 6.04 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 964951 | AG1-359 O1 | 50/50 | 39.14 MW | 39.14 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965001 | AG1-364 C O1 | 50/50 | 12.11 MW | 12.11 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965002 | AG1-364 E O1 | 50/50 | 18.16 MW | 18.16 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 901082 | W1-029 E | Adder | 73.23 MW | 62.24 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 917122 | Z2-027 E | Adder | 1.72 MW | 1.46 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925522 | AC1-027 E | 50/50 | 1.95 MW | 1.95 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933294 | AC2-141 C | 50/50 | 60.55 MW | 60.55 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933295 | AC2-141 E | 50/50 | 25.85 MW | 25.85 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941501 | AE2-147 C | Adder | 25.25 MW | 21.46 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941502 | AE2-147 E | Adder | 16.83 MW | 14.31 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941591 | AE2-156 O1 | 50/50 | 30.29 MW | 30.29 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957871 | AF2-081 C | Adder | 16.83 MW | 14.31 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957872 | AF2-081 E | Adder | 7.21 MW | 6.13 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 958161 | AF2-110 C | Adder | 2.03 MW | 1.72 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 958162 | AF2-110 E | Adder | 3.17 MW | 2.69 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966611 | AG1-531 C | Adder | 7.39 MW | 6.29 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966612 | AG1-531 E | Adder | 4.93 MW | 4.19 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944581 | AF1-123 C O1 | 50/50 | 85.26 MW | 85.26 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944582 | AF1-123 E O1 | 50/50 | 195.23 MW | 195.23 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944591 | AF1-124 C O1 | 50/50 | 85.26 MW | 85.26 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944592 | AF1-124 E O1 | 50/50 | 195.23 MW | 195.23 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944601 | AF1-125 C O1 | 50/50 | 85.26 MW | 85.26 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944602 | AF1-125 E O1 | 50/50 | 195.23 MW | 195.23 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933981 | AD1-022 C | Adder | 11.92 MW | 10.13 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933982 | AD1-022 E | Adder | 6.49 MW | 5.51 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 961681 | AG1-008 C | Adder | 20.49 MW | 17.42 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 961682 | AG1-008 E | Adder | 10.25 MW | 8.71 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 918512 | AA1-065 E OP | Adder | 5.14 MW | 4.37 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 920692 | AA2-178 E | Adder | 5.96 MW | 5.07 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 961611 | AG1-000B C | Adder | 17.38 MW | 14.77 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 6.28 MW | 6.28 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.65 MW | 1.65 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 111.28 MW | 111.28 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 27.64 MW | 27.64 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 34.28 MW | 34.28 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 9.51 MW | 9.51 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 3.67 MW | 3.67 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.38 MW | 8.38 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.54 MW | 0.54 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.4 MW | 1.4 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.34 MW | 4.34 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.72 MW | 1.72 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 23.37 MW | 23.37 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.26 MW | 0.26 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.74 MW | 6.74 MW |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.68 MW | 0.68 MW |
Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963041 | AG1-153 C | 50/50 | 10.67 MW | 10.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963042 | AG1-153 E | 50/50 | 16.0 MW | 16.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963111 | AG1-160 C | 50/50 | 10.84 MW | 10.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963112 | AG1-160 E | 50/50 | 16.25 MW | 16.25 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963291 | AG1-178 C O2 | 50/50 | 122.97 MW | 122.97 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963351 | AG1-184 O2 | 50/50 | 66.25 MW | 66.25 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 965691 | AG1-437 C O1 | Adder | 16.02 MW | 13.62 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 965701 | AG1-438 C O1 | Adder | 9.12 MW | 7.75 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 965811 | AG1-449 | 50/50 | 44.96 MW | 44.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 966361 | AG1-505 C | 50/50 | 31.31 MW | 31.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 966362 | AG1-505 E | 50/50 | 20.88 MW | 20.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 966371 | AG1-506 C | 50/50 | 31.31 MW | 31.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 966372 | AG1-506 E | 50/50 | 20.88 MW | 20.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314541 | 3WATKINS | Adder | 1.07 MW | 0.91 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314594 | 6PLYMOTH | Adder | 0.15 MW | 0.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934521 | AD1-076 C | Adder | 86.88 MW | 73.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934522 | AD1-076 E | Adder | 44.24 MW | 37.6 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934615 | AD1-087 C | Adder | 12.12 MW | 10.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934616 | AD1-087 E | Adder | 5.68 MW | 4.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937481 | AD2-202 C O1 | Adder | 3.55 MW | 3.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937482 | AD2-202 E O1 | Adder | 1.66 MW | 1.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942931 | AE2-313 C | 50/50 | 69.31 MW | 69.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942932 | AE2-313 E | 50/50 | 46.21 MW | 46.21 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944011 | AF1-069 C | 50/50 | 25.25 MW | 25.25 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944012 | AF1-069 E | 50/50 | 9.81 MW | 9.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 945811 | AF1-246 C O1 | 50/50 | 12.77 MW | 12.77 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 945812 | AF1-246 E O1 | 50/50 | 17.64 MW | 17.64 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940491 | AE2-034 C | Adder | 11.62 MW | 9.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940492 | AE2-034 E | Adder | 4.98 MW | 4.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941031 | AE2-094 C | 50/50 | 77.3 MW | 77.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941032 | AE2-094 E | 50/50 | 34.62 MW | 34.62 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957481 | AF2-042 C | 50/50 | 91.24 MW | 91.24 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957482 | AF2-042 E | 50/50 | 60.83 MW | 60.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957531 | AF2-047 C | Adder | 27.62 MW | 23.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957532 | AF2-047 E | Adder | 13.89 MW | 11.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314539 | 3UNCAMP | Adder | 9.5 MW | 8.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 916042 | Z1-036 E | Adder | 47.15 MW | 40.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938771 | AE1-103 C | Adder | 4.59 MW | 3.9 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938772 | AE1-103 E | Adder | 6.34 MW | 5.39 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940641 | AE2-051 C O1 | 50/50 | 34.01 MW | 34.01 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940642 | AE2-051 E O1 | 50/50 | 22.67 MW | 22.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 313717 | 6SLIGO L2192 | Adder | 3.7 MW | 3.15 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314466 | 6FENTRES | 50/50 | 3.76 MW | 3.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314491 | 3PENDLTN | 50/50 | 0.57 MW | 0.57 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314525 | 6KINGFORK | Adder | 6.88 MW | 5.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314550 | 6HICKORY | 50/50 | 6.95 MW | 6.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314632 | 6AYDLETOLD | Adder | 3.71 MW | 3.16 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 919152 | AA1-139 E | 50/50 | 10.83 MW | 10.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926662 | AC1-147 E | Adder | 2.22 MW | 1.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926754 | AC1-161 C | 50/50 | 54.51 MW | 54.51 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926755 | AC1-161 E | 50/50 | 23.27 MW | 23.27 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934061 | AD1-033 C | 50/50 | 12.74 MW | 12.74 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934062 | AD1-033 E | 50/50 | 8.49 MW | 8.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 935112 | AD1-144 E | Adder | 1.5 MW | 1.27 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937221 | AD2-160 C O1 | 50/50 | 9.89 MW | 9.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937222 | AD2-160 E O1 | 50/50 | 5.19 MW | 5.19 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942401 | AE2-253 C | 50/50 | 10.4 MW | 10.4 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942402 | AE2-253 E | 50/50 | 4.67 MW | 4.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943611 | AF1-032 C | Adder | 2.89 MW | 2.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943612 | AF1-032 E | Adder | 1.54 MW | 1.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944871 | AF1-152 C | Adder | 8.75 MW | 7.44 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944872 | AF1-152 E | Adder | 5.83 MW | 4.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315102 | 1BRUNSWICKG1 | 50/50 | 16.41 MW | 16.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315103 | 1BRUNSWICKG2 | 50/50 | 16.41 MW | 16.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315104 | 1BRUNSWICKG3 | 50/50 | 16.41 MW | 16.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315105 | 1BRUNSWICKS1 | 50/50 | 34.1 MW | 34.1 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315108 | 1ELIZAR1 | 50/50 | 5.61 MW | 5.61 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315109 | 1ELIZAR2 | 50/50 | 5.52 MW | 5.52 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315110 | 1ELIZAR3 | 50/50 | 5.68 MW | 5.68 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315233 | 1SURRY 2 | 50/50 | 44.33 MW | 44.33 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315241 | 1Z1-086 GT1 | 50/50 | 21.17 MW | 21.17 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315242 | 1Z1-086 GT2 | 50/50 | 21.17 MW | 21.17 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315243 | 1Z1-086 GT3 | 50/50 | 21.17 MW | 21.17 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315244 | 1Z1-086 ST | 50/50 | 36.79 MW | 36.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315603 | 6AA1-139SOLA | 50/50 | 4.03 MW | 4.03 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 913392 | Y1-086 E | Adder | 3.67 MW | 3.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 916192 | Z1-068 E | 50/50 | 3.17 MW | 3.17 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 923832 | AB2-022 E | Adder | 2.07 MW | 1.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932044 | AC2-012 C | Adder | 13.44 MW | 11.43 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932046 | AC2-012 E | Adder | 21.94 MW | 18.64 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938535 | AE1-072 C | Adder | 29.56 MW | 25.13 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938536 | AE1-072 E | Adder | 15.41 MW | 13.1 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939414 | AE1-173_C1 | 50/50 | 60.41 MW | 60.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939415 | AE1-173_C2 | 50/50 | 51.78 MW | 51.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939416 | AE1-173_C3 | 50/50 | 60.41 MW | 60.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939423 | AE1-173_E1 | 50/50 | 40.27 MW | 40.27 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939424 | AE1-173_E2 | 50/50 | 34.52 MW | 34.52 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939425 | AE1-173_E3 | 50/50 | 40.27 MW | 40.27 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941101 | AE2-104 C O1 | Adder | 5.36 MW | 4.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941102 | AE2-104 E O1 | Adder | 8.53 MW | 7.25 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941281 | AE2-122 C O1 | 50/50 | 47.96 MW | 47.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941282 | AE2-122 E O1 | 50/50 | 193.55 MW | 193.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941291 | AE2-123 C O1 | 50/50 | 49.29 MW | 49.29 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941292 | AE2-123 E O1 | 50/50 | 192.22 MW | 192.22 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941301 | AE2-124 C O1 | 50/50 | 44.85 MW | 44.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941302 | AE2-124 E O1 | 50/50 | 196.81 MW | 196.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957491 | AF2-043 C | Adder | 3.54 MW | 3.01 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957492 | AF2-043 E | Adder | 2.36 MW | 2.01 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957631 | AF2-057 | Adder | 6.0 MW | 5.1 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 964951 | AG1-359 O1 | 50/50 | 38.71 MW | 38.71 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 965001 | AG1-364 C O1 | Adder | 12.01 MW | 10.21 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 965002 | AG1-364 E O1 | 50/50 | 18.02 MW | 18.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 901082 | W1-029 E | Adder | 76.14 MW | 64.72 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 917122 | Z2-027 E | Adder | 1.77 MW | 1.5 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 925522 | AC1-027 E | 50/50 | 1.93 MW | 1.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 933294 | AC2-141 C | 50/50 | 54.51 MW | 54.51 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 933295 | AC2-141 E | 50/50 | 23.27 MW | 23.27 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941501 | AE2-147 C | Adder | 26.26 MW | 22.32 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941502 | AE2-147 E | Adder | 17.5 MW | 14.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941591 | AE2-156 O1 | 50/50 | 30.04 MW | 30.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957871 | AF2-081 C | 50/50 | 16.84 MW | 16.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957872 | AF2-081 E | 50/50 | 7.22 MW | 7.22 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 958161 | AF2-110 C | Adder | 2.21 MW | 1.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 958162 | AF2-110 E | Adder | 3.46 MW | 2.94 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944581 | AF1-123 C O1 | 50/50 | 82.93 MW | 82.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944582 | AF1-123 E O1 | 50/50 | 189.89 MW | 189.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944591 | AF1-124 C O1 | 50/50 | 82.93 MW | 82.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944592 | AF1-124 E O1 | 50/50 | 189.89 MW | 189.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944601 | AF1-125 C O1 | 50/50 | 82.93 MW | 82.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944602 | AF1-125 E O1 | 50/50 | 189.89 MW | 189.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 933981 | AD1-022 C | Adder | 13.92 MW | 11.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 933982 | AD1-022 E | Adder | 7.58 MW | 6.44 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 920692 | AA2-178 E | Adder | 6.64 MW | 5.65 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.67 MW | 8.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.59 MW | 2.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 157.43 MW | 157.43 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 49.46 MW | 49.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 54.54 MW | 54.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 13.13 MW | 13.13 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 5.79 MW | 5.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.92 MW | 12.92 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.75 MW | 0.75 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.49 MW | 2.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.3 MW | 7.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.67 MW | 2.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 36.86 MW | 36.86 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.45 MW | 0.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 10.43 MW | 10.43 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.2 MW | 1.2 MW |
Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 963041 | AG1-153 C | 50/50 | 10.47 MW | 10.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 963042 | AG1-153 E | 50/50 | 15.7 MW | 15.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 963111 | AG1-160 C | 50/50 | 10.64 MW | 10.64 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 963112 | AG1-160 E | 50/50 | 15.96 MW | 15.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 963291 | AG1-178 C O2 | 50/50 | 120.81 MW | 120.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 963351 | AG1-184 O2 | 50/50 | 65.09 MW | 65.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 965691 | AG1-437 C O1 | Adder | 8.8 MW | 7.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 965701 | AG1-438 C O1 | Adder | 15.46 MW | 13.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 965811 | AG1-449 | 50/50 | 44.17 MW | 44.17 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 966361 | AG1-505 C | 50/50 | 30.7 MW | 30.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 966362 | AG1-505 E | 50/50 | 20.47 MW | 20.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 966371 | AG1-506 C | 50/50 | 30.7 MW | 30.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 966372 | AG1-506 E | 50/50 | 20.47 MW | 20.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314541 | 3WATKINS | Adder | 1.03 MW | 0.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314594 | 6PLYMOTH | Adder | 0.14 MW | 0.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934521 | AD1-076 C | Adder | 83.88 MW | 71.29 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934522 | AD1-076 E | Adder | 42.71 MW | 36.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934615 | AD1-087 C | Adder | 11.77 MW | 10.01 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934616 | AD1-087 E | Adder | 5.52 MW | 4.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 937481 | AD2-202 C O1 | Adder | 3.45 MW | 2.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 937482 | AD2-202 E O1 | Adder | 1.62 MW | 1.37 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 942931 | AE2-313 C | 50/50 | 68.08 MW | 68.08 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 942932 | AE2-313 E | 50/50 | 45.39 MW | 45.39 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944011 | AF1-069 C | 50/50 | 24.82 MW | 24.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944012 | AF1-069 E | 50/50 | 9.64 MW | 9.64 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 945811 | AF1-246 C O1 | 50/50 | 12.46 MW | 12.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 945812 | AF1-246 E O1 | 50/50 | 17.21 MW | 17.21 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 940491 | AE2-034 C | Adder | 11.23 MW | 9.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 940492 | AE2-034 E | Adder | 4.81 MW | 4.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941031 | AE2-094 C | 50/50 | 75.96 MW | 75.96 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941032 | AE2-094 E | 50/50 | 34.02 MW | 34.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957481 | AF2-042 C | 50/50 | 89.0 MW | 89.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957482 | AF2-042 E | 50/50 | 59.33 MW | 59.33 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957531 | AF2-047 C | Adder | 26.68 MW | 22.68 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957532 | AF2-047 E | Adder | 13.42 MW | 11.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314539 | 3UNCAMP | Adder | 9.15 MW | 7.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 916042 | Z1-036 E | Adder | 45.6 MW | 38.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 938771 | AE1-103 C | Adder | 4.43 MW | 3.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 938772 | AE1-103 E | Adder | 6.11 MW | 5.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 940641 | AE2-051 C O1 | 50/50 | 33.41 MW | 33.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 940642 | AE2-051 E O1 | 50/50 | 22.27 MW | 22.27 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 313717 | 6SLIGO L2192 | Adder | 3.59 MW | 3.05 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314295 | 6BIRDNECK | 50/50 | 0.07 MW | 0.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314466 | 6FENTRES | 50/50 | 3.65 MW | 3.65 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314491 | 3PENDLTN | 50/50 | 0.56 MW | 0.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314525 | 6KINGFORK | Adder | 6.63 MW | 5.64 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314550 | 6HICKORY | 50/50 | 6.73 MW | 6.73 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314632 | 6AYDLETOLD | Adder | 3.6 MW | 3.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 919152 | AA1-139 E | 50/50 | 10.49 MW | 10.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 926662 | AC1-147 E | Adder | 2.15 MW | 1.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 926754 | AC1-161 C | 50/50 | 53.06 MW | 53.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 926755 | AC1-161 E | 50/50 | 22.65 MW | 22.65 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934061 | AD1-033 C | 50/50 | 12.35 MW | 12.35 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934062 | AD1-033 E | 50/50 | 8.23 MW | 8.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 935112 | AD1-144 E | Adder | 1.45 MW | 1.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 937221 | AD2-160 C O1 | 50/50 | 9.58 MW | 9.58 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 937222 | AD2-160 E O1 | 50/50 | 5.03 MW | 5.03 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 942401 | AE2-253 C | 50/50 | 10.08 MW | 10.08 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 942402 | AE2-253 E | 50/50 | 4.53 MW | 4.53 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 943611 | AF1-032 C | Adder | 2.8 MW | 2.38 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 943612 | AF1-032 E | Adder | 1.49 MW | 1.26 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944871 | AF1-152 C | Adder | 8.47 MW | 7.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944872 | AF1-152 E | Adder | 5.65 MW | 4.8 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315102 | 1BRUNSWICKG1 | 50/50 | 16.11 MW | 16.11 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315103 | 1BRUNSWICKG2 | 50/50 | 16.11 MW | 16.11 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315104 | 1BRUNSWICKG3 | 50/50 | 16.11 MW | 16.11 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315105 | 1BRUNSWICKS1 | 50/50 | 33.46 MW | 33.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315108 | 1ELIZAR1 | 50/50 | 5.44 MW | 5.44 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315109 | 1ELIZAR2 | 50/50 | 5.34 MW | 5.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315110 | 1ELIZAR3 | 50/50 | 5.51 MW | 5.51 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315233 | 1SURRY 2 | 50/50 | 43.0 MW | 43.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315241 | 1Z1-086 GT1 | 50/50 | 20.78 MW | 20.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315242 | 1Z1-086 GT2 | 50/50 | 20.78 MW | 20.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315243 | 1Z1-086 GT3 | 50/50 | 20.78 MW | 20.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315244 | 1Z1-086 ST | 50/50 | 36.12 MW | 36.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315603 | 6AA1-139SOLA | 50/50 | 3.9 MW | 3.9 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 913392 | Y1-086 E | Adder | 3.56 MW | 3.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 916192 | Z1-068 E | 50/50 | 3.07 MW | 3.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 923832 | AB2-022 E | Adder | 2.01 MW | 1.71 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 932044 | AC2-012 C | Adder | 13.02 MW | 11.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 932046 | AC2-012 E | Adder | 21.24 MW | 18.05 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 938535 | AE1-072 C | Adder | 28.64 MW | 24.35 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 938536 | AE1-072 E | Adder | 14.93 MW | 12.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 939414 | AE1-173_C1 | 50/50 | 59.18 MW | 59.18 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 939415 | AE1-173_C2 | 50/50 | 50.73 MW | 50.73 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 939416 | AE1-173_C3 | 50/50 | 59.18 MW | 59.18 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 939423 | AE1-173_E1 | 50/50 | 39.46 MW | 39.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 939424 | AE1-173_E2 | 50/50 | 33.82 MW | 33.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 939425 | AE1-173_E3 | 50/50 | 39.46 MW | 39.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941101 | AE2-104 C O1 | Adder | 5.17 MW | 4.4 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941102 | AE2-104 E O1 | Adder | 8.23 MW | 6.99 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941281 | AE2-122 C O1 | 50/50 | 46.47 MW | 46.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941282 | AE2-122 E O1 | 50/50 | 187.51 MW | 187.51 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941291 | AE2-123 C O1 | 50/50 | 47.76 MW | 47.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941292 | AE2-123 E O1 | 50/50 | 186.22 MW | 186.22 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941301 | AE2-124 C O1 | 50/50 | 43.46 MW | 43.46 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941302 | AE2-124 E O1 | 50/50 | 190.69 MW | 190.69 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957491 | AF2-043 C | Adder | 3.43 MW | 2.92 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957492 | AF2-043 E | Adder | 2.29 MW | 1.94 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957631 | AF2-057 | Adder | 5.81 MW | 4.93 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 964951 | AG1-359 O1 | 50/50 | 37.52 MW | 37.52 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 965001 | AG1-364 C O1 | Adder | 11.63 MW | 9.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 965002 | AG1-364 E O1 | 50/50 | 17.45 MW | 17.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 901082 | W1-029 E | Adder | 73.68 MW | 62.63 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 917122 | Z2-027 E | Adder | 1.71 MW | 1.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 925522 | AC1-027 E | 50/50 | 1.87 MW | 1.87 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 933294 | AC2-141 C | 50/50 | 53.06 MW | 53.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 933295 | AC2-141 E | 50/50 | 22.65 MW | 22.65 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941501 | AE2-147 C | Adder | 25.41 MW | 21.6 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941502 | AE2-147 E | Adder | 16.94 MW | 14.4 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941591 | AE2-156 O1 | 50/50 | 29.09 MW | 29.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957871 | AF2-081 C | 50/50 | 16.32 MW | 16.32 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957872 | AF2-081 E | 50/50 | 6.99 MW | 6.99 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 958161 | AF2-110 C | Adder | 2.13 MW | 1.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 958162 | AF2-110 E | Adder | 3.34 MW | 2.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944581 | AF1-123 C O1 | 50/50 | 80.49 MW | 80.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944582 | AF1-123 E O1 | 50/50 | 184.31 MW | 184.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944591 | AF1-124 C O1 | 50/50 | 80.49 MW | 80.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944592 | AF1-124 E O1 | 50/50 | 184.31 MW | 184.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944601 | AF1-125 C O1 | 50/50 | 80.49 MW | 80.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944602 | AF1-125 E O1 | 50/50 | 184.31 MW | 184.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 933981 | AD1-022 C | Adder | 13.43 MW | 11.42 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 933982 | AD1-022 E | Adder | 7.31 MW | 6.22 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 920692 | AA2-178 E | Adder | 6.42 MW | 5.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.29 MW | 8.29 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.34 MW | 2.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 148.95 MW | 148.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.4 MW | 42.4 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 48.98 MW | 48.98 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.56 MW | 12.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 5.04 MW | 5.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 11.76 MW | 11.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.71 MW | 0.71 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.14 MW | 2.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.41 MW | 6.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.34 MW | 2.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 32.12 MW | 32.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.39 MW | 0.39 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 9.47 MW | 9.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.03 MW | 1.03 MW |
Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 963041 | AG1-153 C | 50/50 | 10.3 MW | 10.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 963042 | AG1-153 E | 50/50 | 15.45 MW | 15.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 963111 | AG1-160 C | 50/50 | 10.47 MW | 10.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 963112 | AG1-160 E | 50/50 | 15.71 MW | 15.71 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 963291 | AG1-178 C O2 | 50/50 | 118.8 MW | 118.8 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 963351 | AG1-184 O2 | 50/50 | 64.0 MW | 64.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 965691 | AG1-437 C O1 | Adder | 15.08 MW | 12.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 965701 | AG1-438 C O1 | Adder | 8.03 MW | 6.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 965811 | AG1-449 | 50/50 | 43.47 MW | 43.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 966361 | AG1-505 C | 50/50 | 30.2 MW | 30.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 966362 | AG1-505 E | 50/50 | 20.14 MW | 20.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 966371 | AG1-506 C | 50/50 | 30.2 MW | 30.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 966372 | AG1-506 E | 50/50 | 20.14 MW | 20.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 314541 | 3WATKINS | Adder | 1.01 MW | 0.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 314594 | 6PLYMOTH | Adder | 0.14 MW | 0.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 934521 | AD1-076 C | Adder | 81.81 MW | 69.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 934522 | AD1-076 E | Adder | 41.66 MW | 35.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 934615 | AD1-087 C | Adder | 11.57 MW | 9.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 934616 | AD1-087 E | Adder | 5.43 MW | 4.61 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 937481 | AD2-202 C O1 | Adder | 3.39 MW | 2.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 937482 | AD2-202 E O1 | Adder | 1.59 MW | 1.35 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 942931 | AE2-313 C | 50/50 | 67.0 MW | 67.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 942932 | AE2-313 E | 50/50 | 44.67 MW | 44.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 944011 | AF1-069 C | 50/50 | 24.43 MW | 24.43 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 944012 | AF1-069 E | 50/50 | 9.49 MW | 9.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 945811 | AF1-246 C O1 | 50/50 | 12.25 MW | 12.25 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 945812 | AF1-246 E O1 | 50/50 | 16.91 MW | 16.91 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 940491 | AE2-034 C | Adder | 10.95 MW | 9.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 940492 | AE2-034 E | Adder | 4.69 MW | 3.99 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941031 | AE2-094 C | 50/50 | 74.76 MW | 74.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941032 | AE2-094 E | 50/50 | 33.48 MW | 33.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 957481 | AF2-042 C | 50/50 | 87.48 MW | 87.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 957482 | AF2-042 E | 50/50 | 58.32 MW | 58.32 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 957531 | AF2-047 C | Adder | 26.02 MW | 22.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 957532 | AF2-047 E | Adder | 13.09 MW | 11.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 314539 | 3UNCAMP | Adder | 8.91 MW | 7.57 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 916042 | Z1-036 E | Adder | 44.46 MW | 37.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 938771 | AE1-103 C | Adder | 4.31 MW | 3.66 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 938772 | AE1-103 E | Adder | 5.95 MW | 5.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 940641 | AE2-051 C O1 | 50/50 | 32.84 MW | 32.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 940642 | AE2-051 E O1 | 50/50 | 21.9 MW | 21.9 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 313717 | 6SLIGO L2192 | 50/50 | 3.5 MW | 3.5 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 314295 | 6BIRDNECK | 50/50 | 0.07 MW | 0.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 314466 | 6FENTRES | 50/50 | 3.56 MW | 3.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 314491 | 3PENDLTN | 50/50 | 0.54 MW | 0.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 314525 | 6KINGFORK | Adder | 6.45 MW | 5.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 314550 | 6HICKORY | 50/50 | 6.56 MW | 6.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 314632 | 6AYDLETOLD | Adder | 3.51 MW | 2.98 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 919152 | AA1-139 E | 50/50 | 10.23 MW | 10.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 926662 | AC1-147 E | Adder | 2.09 MW | 1.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 926754 | AC1-161 C | 50/50 | 51.86 MW | 51.86 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 926755 | AC1-161 E | 50/50 | 22.14 MW | 22.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 934061 | AD1-033 C | 50/50 | 12.04 MW | 12.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 934062 | AD1-033 E | 50/50 | 8.03 MW | 8.03 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 935112 | AD1-144 E | Adder | 1.41 MW | 1.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 937221 | AD2-160 C O1 | 50/50 | 9.35 MW | 9.35 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 937222 | AD2-160 E O1 | 50/50 | 4.9 MW | 4.9 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 942401 | AE2-253 C | 50/50 | 9.83 MW | 9.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 942402 | AE2-253 E | 50/50 | 4.42 MW | 4.42 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 943611 | AF1-032 C | Adder | 2.73 MW | 2.32 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 943612 | AF1-032 E | Adder | 1.45 MW | 1.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 944871 | AF1-152 C | Adder | 8.26 MW | 7.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 944872 | AF1-152 E | Adder | 5.5 MW | 4.68 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315102 | 1BRUNSWICKG1 | 50/50 | 15.85 MW | 15.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315103 | 1BRUNSWICKG2 | 50/50 | 15.85 MW | 15.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315104 | 1BRUNSWICKG3 | 50/50 | 15.85 MW | 15.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315105 | 1BRUNSWICKS1 | 50/50 | 32.92 MW | 32.92 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315108 | 1ELIZAR1 | 50/50 | 5.3 MW | 5.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315109 | 1ELIZAR2 | 50/50 | 5.21 MW | 5.21 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315110 | 1ELIZAR3 | 50/50 | 5.37 MW | 5.37 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315233 | 1SURRY 2 | 50/50 | 41.94 MW | 41.94 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315241 | 1Z1-086 GT1 | 50/50 | 20.45 MW | 20.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315242 | 1Z1-086 GT2 | 50/50 | 20.45 MW | 20.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315243 | 1Z1-086 GT3 | 50/50 | 20.45 MW | 20.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315244 | 1Z1-086 ST | 50/50 | 35.54 MW | 35.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 315603 | 6AA1-139SOLA | 50/50 | 3.81 MW | 3.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 913392 | Y1-086 E | Adder | 3.47 MW | 2.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 916192 | Z1-068 E | 50/50 | 2.99 MW | 2.99 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 923832 | AB2-022 E | Adder | 1.96 MW | 1.66 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 932044 | AC2-012 C | Adder | 12.68 MW | 10.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 932046 | AC2-012 E | Adder | 20.69 MW | 17.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 938535 | AE1-072 C | Adder | 27.93 MW | 23.74 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 938536 | AE1-072 E | Adder | 14.56 MW | 12.38 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 939414 | AE1-173_C1 | 50/50 | 58.09 MW | 58.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 939415 | AE1-173_C2 | 50/50 | 49.79 MW | 49.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 939416 | AE1-173_C3 | 50/50 | 58.09 MW | 58.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 939423 | AE1-173_E1 | 50/50 | 38.73 MW | 38.73 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 939424 | AE1-173_E2 | 50/50 | 33.2 MW | 33.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 939425 | AE1-173_E3 | 50/50 | 38.73 MW | 38.73 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941101 | AE2-104 C O1 | Adder | 5.03 MW | 4.28 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941102 | AE2-104 E O1 | Adder | 8.0 MW | 6.8 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941281 | AE2-122 C O1 | 50/50 | 45.3 MW | 45.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941282 | AE2-122 E O1 | 50/50 | 182.78 MW | 182.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941291 | AE2-123 C O1 | 50/50 | 46.55 MW | 46.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941292 | AE2-123 E O1 | 50/50 | 181.52 MW | 181.52 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941301 | AE2-124 C O1 | 50/50 | 42.36 MW | 42.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941302 | AE2-124 E O1 | 50/50 | 185.88 MW | 185.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 957491 | AF2-043 C | Adder | 3.34 MW | 2.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 957492 | AF2-043 E | Adder | 2.23 MW | 1.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 957631 | AF2-057 | Adder | 5.66 MW | 4.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 964951 | AG1-359 O1 | 50/50 | 36.59 MW | 36.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 965001 | AG1-364 C O1 | Adder | 11.33 MW | 9.63 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 965002 | AG1-364 E O1 | 50/50 | 17.0 MW | 17.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 901082 | W1-029 E | Adder | 71.82 MW | 61.05 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 917122 | Z2-027 E | Adder | 1.67 MW | 1.42 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 925522 | AC1-027 E | 50/50 | 1.82 MW | 1.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 933294 | AC2-141 C | 50/50 | 51.86 MW | 51.86 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 933295 | AC2-141 E | 50/50 | 22.14 MW | 22.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941501 | AE2-147 C | Adder | 24.77 MW | 21.05 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941502 | AE2-147 E | Adder | 16.51 MW | 14.03 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 941591 | AE2-156 O1 | 50/50 | 28.34 MW | 28.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 957871 | AF2-081 C | 50/50 | 15.91 MW | 15.91 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 957872 | AF2-081 E | 50/50 | 6.82 MW | 6.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 958161 | AF2-110 C | Adder | 2.07 MW | 1.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 958162 | AF2-110 E | Adder | 3.24 MW | 2.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 944581 | AF1-123 C O1 | 50/50 | 78.55 MW | 78.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 944582 | AF1-123 E O1 | 50/50 | 179.85 MW | 179.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 944591 | AF1-124 C O1 | 50/50 | 78.55 MW | 78.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 944592 | AF1-124 E O1 | 50/50 | 179.85 MW | 179.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 944601 | AF1-125 C O1 | 50/50 | 78.55 MW | 78.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 944602 | AF1-125 E O1 | 50/50 | 179.85 MW | 179.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 933981 | AD1-022 C | Adder | 13.1 MW | 11.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 933982 | AD1-022 E | Adder | 7.13 MW | 6.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | 920692 | AA2-178 E | Adder | 6.26 MW | 5.32 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.15 MW | 8.15 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.31 MW | 2.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 146.54 MW | 146.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.27 MW | 42.27 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 48.49 MW | 48.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.34 MW | 12.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 4.95 MW | 4.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 11.62 MW | 11.62 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.7 MW | 0.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.13 MW | 2.13 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.36 MW | 6.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.3 MW | 2.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 31.52 MW | 31.52 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.39 MW | 0.39 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 9.36 MW | 9.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T567 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.03 MW | 1.03 MW |
Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 963041 | AG1-153 C | 50/50 | 10.3 MW | 10.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 963042 | AG1-153 E | 50/50 | 15.45 MW | 15.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 963111 | AG1-160 C | 50/50 | 10.47 MW | 10.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 963112 | AG1-160 E | 50/50 | 15.71 MW | 15.71 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 963291 | AG1-178 C O2 | 50/50 | 118.8 MW | 118.8 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 963351 | AG1-184 O2 | 50/50 | 64.0 MW | 64.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 965691 | AG1-437 C O1 | Adder | 15.08 MW | 12.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 965701 | AG1-438 C O1 | Adder | 8.03 MW | 6.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 965811 | AG1-449 | 50/50 | 43.47 MW | 43.47 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 966361 | AG1-505 C | 50/50 | 30.2 MW | 30.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 966362 | AG1-505 E | 50/50 | 20.14 MW | 20.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 966371 | AG1-506 C | 50/50 | 30.2 MW | 30.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 966372 | AG1-506 E | 50/50 | 20.14 MW | 20.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 314541 | 3WATKINS | Adder | 1.01 MW | 0.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 314594 | 6PLYMOTH | Adder | 0.14 MW | 0.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 934521 | AD1-076 C | Adder | 81.81 MW | 69.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 934522 | AD1-076 E | Adder | 41.66 MW | 35.41 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 934615 | AD1-087 C | Adder | 11.57 MW | 9.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 934616 | AD1-087 E | Adder | 5.43 MW | 4.61 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 937481 | AD2-202 C O1 | Adder | 3.39 MW | 2.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 937482 | AD2-202 E O1 | Adder | 1.59 MW | 1.35 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 942931 | AE2-313 C | 50/50 | 67.0 MW | 67.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 942932 | AE2-313 E | 50/50 | 44.67 MW | 44.67 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 944011 | AF1-069 C | 50/50 | 24.43 MW | 24.43 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 944012 | AF1-069 E | 50/50 | 9.49 MW | 9.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 945811 | AF1-246 C O1 | 50/50 | 12.25 MW | 12.25 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 945812 | AF1-246 E O1 | 50/50 | 16.91 MW | 16.91 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 940491 | AE2-034 C | Adder | 10.95 MW | 9.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 940492 | AE2-034 E | Adder | 4.69 MW | 3.99 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941031 | AE2-094 C | 50/50 | 74.76 MW | 74.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941032 | AE2-094 E | 50/50 | 33.48 MW | 33.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 957481 | AF2-042 C | 50/50 | 87.48 MW | 87.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 957482 | AF2-042 E | 50/50 | 58.32 MW | 58.32 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 957531 | AF2-047 C | Adder | 26.02 MW | 22.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 957532 | AF2-047 E | Adder | 13.09 MW | 11.12 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 314539 | 3UNCAMP | Adder | 8.91 MW | 7.57 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 916042 | Z1-036 E | Adder | 44.46 MW | 37.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 938771 | AE1-103 C | Adder | 4.31 MW | 3.66 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 938772 | AE1-103 E | Adder | 5.95 MW | 5.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 940641 | AE2-051 C O1 | 50/50 | 32.84 MW | 32.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 940642 | AE2-051 E O1 | 50/50 | 21.9 MW | 21.9 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 313717 | 6SLIGO L2192 | 50/50 | 3.5 MW | 3.5 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 314295 | 6BIRDNECK | 50/50 | 0.07 MW | 0.07 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 314466 | 6FENTRES | 50/50 | 3.56 MW | 3.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 314491 | 3PENDLTN | 50/50 | 0.54 MW | 0.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 314525 | 6KINGFORK | Adder | 6.45 MW | 5.48 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 314550 | 6HICKORY | 50/50 | 6.56 MW | 6.56 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 314632 | 6AYDLETOLD | Adder | 3.51 MW | 2.98 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 919152 | AA1-139 E | 50/50 | 10.23 MW | 10.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 926662 | AC1-147 E | Adder | 2.09 MW | 1.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 926754 | AC1-161 C | 50/50 | 51.86 MW | 51.86 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 926755 | AC1-161 E | 50/50 | 22.14 MW | 22.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 934061 | AD1-033 C | 50/50 | 12.04 MW | 12.04 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 934062 | AD1-033 E | 50/50 | 8.03 MW | 8.03 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 935112 | AD1-144 E | Adder | 1.41 MW | 1.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 937221 | AD2-160 C O1 | 50/50 | 9.35 MW | 9.35 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 937222 | AD2-160 E O1 | 50/50 | 4.9 MW | 4.9 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 942401 | AE2-253 C | 50/50 | 9.83 MW | 9.83 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 942402 | AE2-253 E | 50/50 | 4.42 MW | 4.42 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 943611 | AF1-032 C | Adder | 2.73 MW | 2.32 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 943612 | AF1-032 E | Adder | 1.45 MW | 1.23 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 944871 | AF1-152 C | Adder | 8.26 MW | 7.02 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 944872 | AF1-152 E | Adder | 5.5 MW | 4.68 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315102 | 1BRUNSWICKG1 | 50/50 | 15.85 MW | 15.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315103 | 1BRUNSWICKG2 | 50/50 | 15.85 MW | 15.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315104 | 1BRUNSWICKG3 | 50/50 | 15.85 MW | 15.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315105 | 1BRUNSWICKS1 | 50/50 | 32.92 MW | 32.92 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315108 | 1ELIZAR1 | 50/50 | 5.3 MW | 5.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315109 | 1ELIZAR2 | 50/50 | 5.21 MW | 5.21 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315110 | 1ELIZAR3 | 50/50 | 5.37 MW | 5.37 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315233 | 1SURRY 2 | 50/50 | 41.94 MW | 41.94 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315241 | 1Z1-086 GT1 | 50/50 | 20.45 MW | 20.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315242 | 1Z1-086 GT2 | 50/50 | 20.45 MW | 20.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315243 | 1Z1-086 GT3 | 50/50 | 20.45 MW | 20.45 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315244 | 1Z1-086 ST | 50/50 | 35.54 MW | 35.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 315603 | 6AA1-139SOLA | 50/50 | 3.81 MW | 3.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 913392 | Y1-086 E | Adder | 3.47 MW | 2.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 916192 | Z1-068 E | 50/50 | 2.99 MW | 2.99 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 923832 | AB2-022 E | Adder | 1.96 MW | 1.66 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 932044 | AC2-012 C | Adder | 12.68 MW | 10.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 932046 | AC2-012 E | Adder | 20.69 MW | 17.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 938535 | AE1-072 C | Adder | 27.93 MW | 23.74 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 938536 | AE1-072 E | Adder | 14.56 MW | 12.38 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 939414 | AE1-173_C1 | 50/50 | 58.09 MW | 58.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 939415 | AE1-173_C2 | 50/50 | 49.79 MW | 49.79 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 939416 | AE1-173_C3 | 50/50 | 58.09 MW | 58.09 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 939423 | AE1-173_E1 | 50/50 | 38.73 MW | 38.73 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 939424 | AE1-173_E2 | 50/50 | 33.2 MW | 33.2 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 939425 | AE1-173_E3 | 50/50 | 38.73 MW | 38.73 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941101 | AE2-104 C O1 | Adder | 5.03 MW | 4.28 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941102 | AE2-104 E O1 | Adder | 8.0 MW | 6.8 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941281 | AE2-122 C O1 | 50/50 | 45.3 MW | 45.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941282 | AE2-122 E O1 | 50/50 | 182.78 MW | 182.78 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941291 | AE2-123 C O1 | 50/50 | 46.55 MW | 46.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941292 | AE2-123 E O1 | 50/50 | 181.52 MW | 181.52 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941301 | AE2-124 C O1 | 50/50 | 42.36 MW | 42.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941302 | AE2-124 E O1 | 50/50 | 185.88 MW | 185.88 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 957491 | AF2-043 C | Adder | 3.34 MW | 2.84 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 957492 | AF2-043 E | Adder | 2.23 MW | 1.89 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 957631 | AF2-057 | Adder | 5.66 MW | 4.81 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 964951 | AG1-359 O1 | 50/50 | 36.59 MW | 36.59 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 965001 | AG1-364 C O1 | Adder | 11.33 MW | 9.63 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 965002 | AG1-364 E O1 | 50/50 | 17.0 MW | 17.0 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 901082 | W1-029 E | Adder | 71.82 MW | 61.05 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 917122 | Z2-027 E | Adder | 1.67 MW | 1.42 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 925522 | AC1-027 E | 50/50 | 1.82 MW | 1.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 933294 | AC2-141 C | 50/50 | 51.86 MW | 51.86 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 933295 | AC2-141 E | 50/50 | 22.14 MW | 22.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941501 | AE2-147 C | Adder | 24.77 MW | 21.05 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941502 | AE2-147 E | Adder | 16.51 MW | 14.03 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 941591 | AE2-156 O1 | 50/50 | 28.34 MW | 28.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 957871 | AF2-081 C | 50/50 | 15.91 MW | 15.91 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 957872 | AF2-081 E | 50/50 | 6.82 MW | 6.82 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 958161 | AF2-110 C | Adder | 2.07 MW | 1.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 958162 | AF2-110 E | Adder | 3.24 MW | 2.76 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 944581 | AF1-123 C O1 | 50/50 | 78.55 MW | 78.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 944582 | AF1-123 E O1 | 50/50 | 179.85 MW | 179.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 944591 | AF1-124 C O1 | 50/50 | 78.55 MW | 78.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 944592 | AF1-124 E O1 | 50/50 | 179.85 MW | 179.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 944601 | AF1-125 C O1 | 50/50 | 78.55 MW | 78.55 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 944602 | AF1-125 E O1 | 50/50 | 179.85 MW | 179.85 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 933981 | AD1-022 C | Adder | 13.1 MW | 11.14 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 933982 | AD1-022 E | Adder | 7.13 MW | 6.06 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | 920692 | AA2-178 E | Adder | 6.26 MW | 5.32 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.15 MW | 8.15 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.31 MW | 2.31 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 146.54 MW | 146.54 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.27 MW | 42.27 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 48.49 MW | 48.49 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.34 MW | 12.34 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 4.95 MW | 4.95 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 11.62 MW | 11.62 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.7 MW | 0.7 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.13 MW | 2.13 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.36 MW | 6.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.3 MW | 2.3 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 31.52 MW | 31.52 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.39 MW | 0.39 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 9.36 MW | 9.36 MW |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-5: L122 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.03 MW | 1.03 MW |
Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963041 | AG1-153 C | 50/50 | 9.71 MW | 9.71 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963042 | AG1-153 E | 50/50 | 14.57 MW | 14.57 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963111 | AG1-160 C | 50/50 | 9.84 MW | 9.84 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963112 | AG1-160 E | 50/50 | 14.75 MW | 14.75 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963291 | AG1-178 C O2 | 50/50 | 111.72 MW | 111.72 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 963351 | AG1-184 O2 | 50/50 | 60.19 MW | 60.19 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 965811 | AG1-449 | 50/50 | 40.74 MW | 40.74 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 966361 | AG1-505 C | 50/50 | 28.82 MW | 28.82 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 966362 | AG1-505 E | 50/50 | 19.22 MW | 19.22 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 966371 | AG1-506 C | 50/50 | 28.82 MW | 28.82 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 966372 | AG1-506 E | 50/50 | 19.22 MW | 19.22 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314541 | 3WATKINS | Adder | 1.14 MW | 0.97 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314594 | 6PLYMOTH | Adder | 0.15 MW | 0.13 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934521 | AD1-076 C | Adder | 13.0 MW | 11.05 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942931 | AE2-313 C | 50/50 | 62.83 MW | 62.83 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942932 | AE2-313 E | 50/50 | 41.88 MW | 41.88 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944011 | AF1-069 C | 50/50 | 22.79 MW | 22.79 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944012 | AF1-069 E | 50/50 | 8.85 MW | 8.85 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 945811 | AF1-246 C O1 | Adder | 12.29 MW | 10.45 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 945812 | AF1-246 E O1 | Adder | 16.98 MW | 14.43 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940491 | AE2-034 C | Adder | 12.01 MW | 10.21 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940492 | AE2-034 E | Adder | 5.15 MW | 4.38 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941031 | AE2-094 C | 50/50 | 69.74 MW | 69.74 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941032 | AE2-094 E | 50/50 | 31.23 MW | 31.23 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957481 | AF2-042 C | Adder | 87.81 MW | 74.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957482 | AF2-042 E | Adder | 58.54 MW | 49.76 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957531 | AF2-047 C | Adder | 28.54 MW | 24.26 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957532 | AF2-047 E | Adder | 14.36 MW | 12.2 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314539 | 3UNCAMP | Adder | 10.06 MW | 8.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 916042 | Z1-036 E | Adder | 48.57 MW | 41.28 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938771 | AE1-103 C | Adder | 4.87 MW | 4.14 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938772 | AE1-103 E | Adder | 6.72 MW | 5.71 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940481 | AE2-033 C | Adder | 25.69 MW | 21.84 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940482 | AE2-033 E | Adder | 17.32 MW | 14.72 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940641 | AE2-051 C O1 | 50/50 | 30.93 MW | 30.93 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940642 | AE2-051 E O1 | 50/50 | 20.62 MW | 20.62 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 946011 | AF1-266 | Adder | 21.5 MW | 18.28 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 313717 | 6SLIGO L2192 | Adder | 3.79 MW | 3.22 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314331 | 6POE | Adder | 3.47 MW | 2.95 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314466 | 6FENTRES | 50/50 | 3.84 MW | 3.84 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314491 | 3PENDLTN | 50/50 | 0.59 MW | 0.59 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314525 | 6KINGFORK | Adder | 7.31 MW | 6.21 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314550 | 6HICKORY | Adder | 7.09 MW | 6.03 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314632 | 6AYDLETOLD | Adder | 3.8 MW | 3.23 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 919152 | AA1-139 E | Adder | 11.06 MW | 9.4 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926662 | AC1-147 E | Adder | 2.29 MW | 1.94 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926754 | AC1-161 C | 50/50 | 53.74 MW | 53.74 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926755 | AC1-161 E | 50/50 | 22.94 MW | 22.94 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934061 | AD1-033 C | 50/50 | 13.01 MW | 13.01 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934062 | AD1-033 E | 50/50 | 8.67 MW | 8.67 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934575 | AD1-082 C | Adder | 12.31 MW | 10.46 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934576 | AD1-082 E | Adder | 7.02 MW | 5.97 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 935112 | AD1-144 E | Adder | 1.59 MW | 1.35 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 936661 | AD2-085 C | Adder | 5.72 MW | 4.86 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 936662 | AD2-085 E | Adder | 9.33 MW | 7.93 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937221 | AD2-160 C O1 | Adder | 10.1 MW | 8.59 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937222 | AD2-160 E O1 | Adder | 5.3 MW | 4.5 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942341 | AE2-247 C | Adder | 2.48 MW | 2.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942342 | AE2-247 E | Adder | 3.42 MW | 2.91 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942401 | AE2-253 C | Adder | 10.63 MW | 9.03 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942402 | AE2-253 E | Adder | 4.77 MW | 4.06 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943461 | AF1-017 C | Adder | 2.24 MW | 1.91 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943462 | AF1-017 E | Adder | 3.66 MW | 3.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943611 | AF1-032 C | Adder | 2.99 MW | 2.54 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943612 | AF1-032 E | Adder | 1.59 MW | 1.35 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943621 | AF1-033 C | Adder | 3.8 MW | 3.23 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943622 | AF1-033 E | Adder | 1.96 MW | 1.66 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944871 | AF1-152 C | Adder | 9.01 MW | 7.66 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944872 | AF1-152 E | Adder | 6.0 MW | 5.1 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315102 | 1BRUNSWICKG1 | 50/50 | 14.94 MW | 14.94 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315103 | 1BRUNSWICKG2 | 50/50 | 14.94 MW | 14.94 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315104 | 1BRUNSWICKG3 | 50/50 | 14.94 MW | 14.94 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315105 | 1BRUNSWICKS1 | 50/50 | 31.04 MW | 31.04 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315108 | 1ELIZAR1 | 50/50 | 5.77 MW | 5.77 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315109 | 1ELIZAR2 | 50/50 | 5.67 MW | 5.67 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315110 | 1ELIZAR3 | 50/50 | 5.84 MW | 5.84 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315233 | 1SURRY 2 | 50/50 | 44.9 MW | 44.9 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315241 | 1Z1-086 GT1 | 50/50 | 19.21 MW | 19.21 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315242 | 1Z1-086 GT2 | 50/50 | 19.21 MW | 19.21 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315243 | 1Z1-086 GT3 | 50/50 | 19.21 MW | 19.21 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315244 | 1Z1-086 ST | 50/50 | 33.39 MW | 33.39 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 913392 | Y1-086 E | Adder | 3.76 MW | 3.2 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 916192 | Z1-068 E | 50/50 | 3.25 MW | 3.25 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 923832 | AB2-022 E | Adder | 2.13 MW | 1.81 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 923852 | AB2-025 E | Adder | 1.8 MW | 1.53 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932044 | AC2-012 C | Adder | 13.85 MW | 11.77 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932046 | AC2-012 E | Adder | 22.6 MW | 19.21 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932591 | AC2-079 C O1 | Adder | 9.42 MW | 8.01 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932592 | AC2-079 E O1 | Adder | 15.37 MW | 13.06 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938535 | AE1-072 C | Adder | 30.24 MW | 25.7 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938536 | AE1-072 E | Adder | 15.76 MW | 13.4 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938552 | AE1-074 E | Adder | 1.95 MW | 1.66 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939195 | AE1-149 C | Adder | 16.87 MW | 14.34 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939196 | AE1-149 E | Adder | 11.24 MW | 9.56 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939312 | AE1-162 E | Adder | 2.37 MW | 2.01 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939414 | AE1-173_C1 | 50/50 | 56.32 MW | 56.32 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939415 | AE1-173_C2 | 50/50 | 48.28 MW | 48.28 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939416 | AE1-173_C3 | 50/50 | 56.32 MW | 56.32 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939423 | AE1-173_E1 | 50/50 | 37.55 MW | 37.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939424 | AE1-173_E2 | 50/50 | 32.18 MW | 32.18 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939425 | AE1-173_E3 | 50/50 | 37.55 MW | 37.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940541 | AE2-040 | Adder | 4.56 MW | 3.88 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940651 | AE2-052 | Adder | 5.62 MW | 4.78 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941101 | AE2-104 C O1 | Adder | 5.68 MW | 4.83 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941102 | AE2-104 E O1 | Adder | 9.03 MW | 7.67 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941281 | AE2-122 C O1 | 50/50 | 49.15 MW | 49.15 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941282 | AE2-122 E O1 | 50/50 | 198.31 MW | 198.31 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941291 | AE2-123 C O1 | 50/50 | 50.51 MW | 50.51 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941292 | AE2-123 E O1 | 50/50 | 196.95 MW | 196.95 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941301 | AE2-124 C O1 | 50/50 | 45.93 MW | 45.93 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941302 | AE2-124 E O1 | 50/50 | 201.55 MW | 201.55 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957491 | AF2-043 C | Adder | 3.66 MW | 3.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957492 | AF2-043 E | Adder | 2.44 MW | 2.07 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957631 | AF2-057 | Adder | 6.18 MW | 5.25 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 964951 | AG1-359 O1 | 50/50 | 39.49 MW | 39.49 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 965001 | AG1-364 C O1 | Adder | 12.36 MW | 10.51 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 965002 | AG1-364 E O1 | Adder | 18.55 MW | 15.77 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 901082 | W1-029 E | Adder | 78.37 MW | 66.61 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 917122 | Z2-027 E | Adder | 1.81 MW | 1.54 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 925522 | AC1-027 E | 50/50 | 1.98 MW | 1.98 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 933294 | AC2-141 C | 50/50 | 53.74 MW | 53.74 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 933295 | AC2-141 E | 50/50 | 22.94 MW | 22.94 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941501 | AE2-147 C | Adder | 27.02 MW | 22.97 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941502 | AE2-147 E | Adder | 18.02 MW | 15.31 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941591 | AE2-156 O1 | Adder | 30.92 MW | 26.28 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957871 | AF2-081 C | Adder | 17.21 MW | 14.63 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957872 | AF2-081 E | Adder | 7.38 MW | 6.27 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957911 | AF2-085 | 50/50 | 6.64 MW | 6.64 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 958161 | AF2-110 C | Adder | 2.34 MW | 1.99 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 958162 | AF2-110 E | Adder | 3.66 MW | 3.11 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 966611 | AG1-531 C | Adder | 9.31 MW | 7.91 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 966612 | AG1-531 E | Adder | 6.21 MW | 5.28 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944581 | AF1-123 C O1 | 50/50 | 83.7 MW | 83.7 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944582 | AF1-123 E O1 | 50/50 | 191.65 MW | 191.65 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944591 | AF1-124 C O1 | 50/50 | 83.7 MW | 83.7 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944592 | AF1-124 E O1 | 50/50 | 191.65 MW | 191.65 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944601 | AF1-125 C O1 | 50/50 | 83.7 MW | 83.7 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944602 | AF1-125 E O1 | 50/50 | 191.65 MW | 191.65 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 965281 | AG1-393 C | Adder | 3.48 MW | 2.96 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 965282 | AG1-393 E | Adder | 2.32 MW | 1.98 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 920692 | AA2-178 E | Adder | 6.86 MW | 5.83 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 316083 | AB2-161 C | Adder | 5.4 MW | 4.59 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 316084 | AB2-161 E | Adder | 8.81 MW | 7.49 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 961611 | AG1-000B C | Adder | 25.41 MW | 21.6 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.72 MW | 8.72 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.84 MW | 2.84 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 161.12 MW | 161.12 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 57.67 MW | 57.67 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 60.24 MW | 60.24 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 13.2 MW | 13.2 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 7.08 MW | 7.08 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 14.02 MW | 14.02 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.78 MW | 0.78 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.92 MW | 2.92 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.29 MW | 8.29 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.23 MW | 3.23 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 45.02 MW | 45.02 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.52 MW | 0.52 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 11.35 MW | 11.35 MW |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.39 MW | 1.39 MW |
Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.37 MW | 0.32 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.21 MW | 0.18 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962491 | AG1-098 C O1 | Adder | 3.58 MW | 3.04 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962492 | AG1-098 E O1 | Adder | 2.39 MW | 2.03 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.62 MW | 2.23 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 3.93 MW | 3.34 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | Adder | 2.66 MW | 2.26 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | Adder | 3.99 MW | 3.39 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 26.97 MW | 22.93 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | Adder | 3.31 MW | 2.81 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | Adder | 1.61 MW | 1.37 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963321 | AG1-181 C O1 | Adder | 5.68 MW | 4.83 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 14.53 MW | 12.35 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963361 | AG1-185 O1 | Adder | 2.75 MW | 2.34 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964111 | AG1-272 C | Adder | 0.85 MW | 0.72 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964112 | AG1-272 E | Adder | 0.25 MW | 0.21 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964121 | AG1-273 C | Adder | 0.85 MW | 0.72 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964122 | AG1-273 E | Adder | 0.25 MW | 0.21 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964131 | AG1-274 C | Adder | 0.85 MW | 0.72 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964132 | AG1-274 E | Adder | 0.25 MW | 0.21 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964241 | AG1-285 C O1 | Adder | 4.6 MW | 3.91 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964242 | AG1-285 E O1 | Adder | 3.07 MW | 2.61 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964791 | AG1-342 C | Adder | 1.52 MW | 1.29 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964792 | AG1-342 E | Adder | 1.19 MW | 1.01 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 1.0 MW | 0.85 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.43 MW | 0.36 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965191 | AG1-384 C | Adder | 0.85 MW | 0.72 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965192 | AG1-384 E | Adder | 0.25 MW | 0.21 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965591 | AG1-427 C | Adder | 4.35 MW | 3.7 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965592 | AG1-427 E | Adder | 2.91 MW | 2.47 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | Adder | 2.76 MW | 2.35 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | Adder | 1.84 MW | 1.56 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 9.02 MW | 7.67 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 6.02 MW | 5.11 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 3.04 MW | 2.59 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 2.03 MW | 1.73 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 3.04 MW | 2.59 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 2.03 MW | 1.73 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 4.81 MW | 4.09 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 1.76 MW | 1.5 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 1.76 MW | 1.5 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | Adder | 11.02 MW | 9.37 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 7.69 MW | 6.54 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 5.13 MW | 4.36 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 7.69 MW | 6.54 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 5.13 MW | 4.36 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | 50/50 | 0.97 MW | 0.97 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | 50/50 | 0.65 MW | 0.65 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | 50/50 | 4.12 MW | 4.12 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.29 MW | 0.29 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314704 | 3LAWRENC | 50/50 | 0.19 MW | 0.19 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.33 MW | 2.83 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.33 MW | 2.83 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.98 MW | 2.54 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.55 MW | 1.32 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.24 MW | 0.2 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.68 MW | 1.43 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.42 MW | 1.21 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.2 MW | 0.17 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.47 MW | 1.25 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | Adder | 11.96 MW | 10.16 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | Adder | 5.44 MW | 4.62 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.45 MW | 2.08 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.46 MW | 1.24 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.82 MW | 0.7 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.41 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926274 | AC1-105 E | Adder | 0.97 MW | 0.83 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.1 MW | 2.63 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.54 MW | 1.31 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 3.86 MW | 3.28 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 1.71 MW | 1.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927251 | AC1-221 C | Adder | 0.78 MW | 0.67 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927252 | AC1-221 E | Adder | 0.78 MW | 0.67 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927261 | AC1-222 C | Adder | 1.25 MW | 1.06 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927262 | AC1-222 E | Adder | 1.19 MW | 1.01 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934311 | AD1-055 C | Adder | 0.87 MW | 0.74 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934312 | AD1-055 E | Adder | 0.22 MW | 0.19 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.84 MW | 4.12 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.59 MW | 2.2 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934341 | AD1-058 C | Adder | 1.96 MW | 1.67 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934342 | AD1-058 E | Adder | 0.5 MW | 0.42 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 3.01 MW | 2.56 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.41 MW | 1.2 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934625 | AD1-088 C | Adder | 3.95 MW | 3.36 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934626 | AD1-088 E | Adder | 1.86 MW | 1.58 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934991 | AD1-131 C | Adder | 0.64 MW | 0.55 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934992 | AD1-131 E | Adder | 0.43 MW | 0.36 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 3.11 MW | 2.65 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 2.08 MW | 1.76 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936265 | AD2-033 C | Adder | 4.42 MW | 3.75 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936266 | AD2-033 E | Adder | 2.94 MW | 2.5 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.88 MW | 0.75 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.41 MW | 0.35 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 16.99 MW | 14.44 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 11.32 MW | 9.62 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.69 MW | 0.59 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.46 MW | 0.39 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 6.19 MW | 5.26 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.4 MW | 2.04 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.19 MW | 1.01 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 3.16 MW | 2.68 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 4.36 MW | 3.71 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959311 | AF2-222 C | Adder | 5.38 MW | 4.58 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959312 | AF2-222 E | Adder | 3.61 MW | 3.07 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 2.77 MW | 2.35 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 1.84 MW | 1.57 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 1.79 MW | 1.79 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.19 MW | 1.19 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | 50/50 | 4.05 MW | 4.05 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 2.33 MW | 2.33 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 2.33 MW | 2.33 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316118 | AC1-105 C | Adder | 2.03 MW | 1.73 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 3.19 MW | 2.71 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.37 MW | 0.31 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.24 MW | 0.2 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.59 MW | 1.35 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 8.12 MW | 6.9 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.48 MW | 2.96 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | 50/50 | 1.96 MW | 1.96 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | 50/50 | 4.48 MW | 4.48 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | 50/50 | 3.67 MW | 3.67 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.25 MW | 1.91 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.62 MW | 1.37 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.76 MW | 0.65 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.51 MW | 0.43 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.76 MW | 0.65 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.51 MW | 0.43 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.76 MW | 0.65 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.51 MW | 0.43 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.83 MW | 2.41 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.14 MW | 1.82 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925612 | AC1-036 E | Adder | 0.51 MW | 0.43 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.5 MW | 2.97 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.72 MW | 1.46 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932761 | AC2-100 C | Adder | 1.8 MW | 1.53 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932762 | AC2-100 E | Adder | 0.88 MW | 0.75 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 3.51 MW | 2.99 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.34 MW | 1.99 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.85 MW | 1.58 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.8 MW | 0.68 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.3 MW | 1.11 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 18.93 MW | 16.09 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 8.48 MW | 7.21 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941791 | AE2-182 C | Adder | 0.64 MW | 0.55 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941792 | AE2-182 E | Adder | 0.3 MW | 0.25 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 1.06 MW | 1.06 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.72 MW | 0.72 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 22.56 MW | 19.17 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 15.04 MW | 12.78 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.81 MW | 2.39 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.25 MW | 1.06 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 16.49 MW | 16.49 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 11.12 MW | 11.12 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 13.8 MW | 13.8 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.45 MW | 0.45 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.97 MW | -2.53 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934575 | AD1-082 C | Adder | -9.77 MW | -8.3 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.67 MW | -0.57 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.34 MW | -2.84 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316087 | AB2-174 C | 50/50 | 0.76 MW | 0.76 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.81 MW | 0.81 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.81 MW | 0.81 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316132 | AB2-190 C | Adder | -5.74 MW | -4.88 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.19 MW | 1.19 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 10.56 MW | 8.98 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 9.06 MW | 7.7 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 10.56 MW | 8.98 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 7.04 MW | 5.99 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 6.04 MW | 5.13 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 7.04 MW | 5.99 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 3.01 MW | 3.01 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 3.25 MW | 2.77 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 1.75 MW | 1.48 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962561 | AG1-105 C O1 | Adder | 3.28 MW | 2.79 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962562 | AG1-105 E O1 | Adder | 2.19 MW | 1.86 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | Adder | 1.51 MW | 1.28 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | Adder | 3.32 MW | 2.83 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 2.3 MW | 2.3 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.53 MW | 1.53 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 1.08 MW | 0.92 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316083 | AB2-161 C | Adder | -4.29 MW | -3.64 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940652 | AE2-052 BAT | 50/50 | 5.31 MW | 5.31 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.2 MW | 2.2 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 39.73 MW | 39.73 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.3 MW | 13.3 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.0 MW | 14.0 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.33 MW | 3.33 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.98 MW | 0.98 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.91 MW | 1.91 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.25 MW | 6.25 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.64 MW | 2.64 MW |
6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
Details for 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961791 | AG1-021 C | 50/50 | 2.18 MW | 2.18 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961792 | AG1-021 E | 50/50 | 1.46 MW | 1.46 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961891 | AG1-030 C | 50/50 | 15.91 MW | 15.91 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961892 | AG1-030 E | 50/50 | 10.61 MW | 10.61 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962491 | AG1-098 C O1 | 50/50 | 25.66 MW | 25.66 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962492 | AG1-098 E O1 | 50/50 | 17.11 MW | 17.11 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963171 | AG1-166 C | 50/50 | 2.18 MW | 2.18 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963172 | AG1-166 E | 50/50 | 1.46 MW | 1.46 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963181 | AG1-167 C | 50/50 | 2.18 MW | 2.18 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963182 | AG1-167 E | 50/50 | 1.46 MW | 1.46 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963191 | AG1-168 C | 50/50 | 2.18 MW | 2.18 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963192 | AG1-168 E | 50/50 | 1.46 MW | 1.46 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963201 | AG1-169 C | 50/50 | 2.18 MW | 2.18 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963202 | AG1-169 E | 50/50 | 1.46 MW | 1.46 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963211 | AG1-170 C | 50/50 | 2.18 MW | 2.18 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963212 | AG1-170 E | 50/50 | 1.46 MW | 1.46 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963321 | AG1-181 C O1 | 50/50 | 16.63 MW | 16.63 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963361 | AG1-185 O1 | 50/50 | 8.04 MW | 8.04 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964111 | AG1-272 C | 50/50 | 2.58 MW | 2.58 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964112 | AG1-272 E | 50/50 | 0.77 MW | 0.77 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964121 | AG1-273 C | 50/50 | 2.58 MW | 2.58 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964122 | AG1-273 E | 50/50 | 0.77 MW | 0.77 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964131 | AG1-274 C | 50/50 | 2.58 MW | 2.58 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964132 | AG1-274 E | 50/50 | 0.77 MW | 0.77 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964241 | AG1-285 C O1 | 50/50 | 11.57 MW | 11.57 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964242 | AG1-285 E O1 | 50/50 | 7.72 MW | 7.72 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964791 | AG1-342 C | 50/50 | 5.29 MW | 5.29 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964792 | AG1-342 E | 50/50 | 4.16 MW | 4.16 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 966691 | AG1-539 C | 50/50 | 4.88 MW | 4.88 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 966692 | AG1-539 E | 50/50 | 6.56 MW | 6.56 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965191 | AG1-384 C | 50/50 | 2.58 MW | 2.58 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965192 | AG1-384 E | 50/50 | 0.77 MW | 0.77 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965591 | AG1-427 C | 50/50 | 10.99 MW | 10.99 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965592 | AG1-427 E | 50/50 | 7.35 MW | 7.35 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965641 | AG1-432 C O1 | 50/50 | 24.21 MW | 24.21 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965642 | AG1-432 E O1 | 50/50 | 16.14 MW | 16.14 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965721 | AG1-440 C | Adder | 4.18 MW | 3.55 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965722 | AG1-440 E | Adder | 2.79 MW | 2.37 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965731 | AG1-441 C | Adder | 4.18 MW | 3.55 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965732 | AG1-441 E | Adder | 2.79 MW | 2.37 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965771 | AG1-445 | Adder | 2.42 MW | 2.05 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965781 | AG1-446 | Adder | 2.42 MW | 2.05 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965831 | AG1-451 | 50/50 | 4.04 MW | 4.04 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 313853 | 3PONTONDP | 50/50 | 0.73 MW | 0.73 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 314429 | 3JTRSVLE | 50/50 | 0.5 MW | 0.5 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 314713 | 3PAMPLIN | 50/50 | 1.82 MW | 1.82 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 315153 | 1CLOVER1 | 50/50 | 36.85 MW | 36.85 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 315154 | 1CLOVER2 | 50/50 | 36.49 MW | 36.49 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 926023 | AC1-080 C | 50/50 | 0.39 MW | 0.39 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 926274 | AC1-105 E | 50/50 | 3.82 MW | 3.82 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927251 | AC1-221 C | 50/50 | 2.11 MW | 2.11 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927252 | AC1-221 E | 50/50 | 2.11 MW | 2.11 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927261 | AC1-222 C | 50/50 | 5.42 MW | 5.42 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927262 | AC1-222 E | 50/50 | 5.16 MW | 5.16 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934311 | AD1-055 C | 50/50 | 3.76 MW | 3.76 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934312 | AD1-055 E | 50/50 | 0.97 MW | 0.97 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934341 | AD1-058 C | 50/50 | 5.3 MW | 5.3 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934342 | AD1-058 E | 50/50 | 1.35 MW | 1.35 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934615 | AD1-087 C | 50/50 | 21.34 MW | 21.34 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934616 | AD1-087 E | 50/50 | 10.01 MW | 10.01 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934625 | AD1-088 C | 50/50 | 28.35 MW | 28.35 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934626 | AD1-088 E | 50/50 | 13.34 MW | 13.34 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934991 | AD1-131 C | 50/50 | 1.74 MW | 1.74 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934992 | AD1-131 E | 50/50 | 1.16 MW | 1.16 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 935171 | AD1-152 C O1 | 50/50 | 19.21 MW | 19.21 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 935172 | AD1-152 E O1 | 50/50 | 12.81 MW | 12.81 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 936265 | AD2-033 C | 50/50 | 12.77 MW | 12.77 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 936266 | AD2-033 E | 50/50 | 8.51 MW | 8.51 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 937481 | AD2-202 C O1 | 50/50 | 6.25 MW | 6.25 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 937482 | AD2-202 E O1 | 50/50 | 2.93 MW | 2.93 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942461 | AE2-259 C O1 | 50/50 | 12.11 MW | 12.11 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942462 | AE2-259 E O1 | 50/50 | 8.07 MW | 8.07 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942751 | AE2-291 C | 50/50 | 9.33 MW | 9.33 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942752 | AE2-291 E | 50/50 | 6.22 MW | 6.22 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942761 | AE2-292 C O1 | 50/50 | 11.62 MW | 11.62 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942762 | AE2-292 E O1 | 50/50 | 7.75 MW | 7.75 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 943901 | AF1-058 C | 50/50 | 3.04 MW | 3.04 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 943902 | AF1-058 E | 50/50 | 2.02 MW | 2.02 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958801 | AF2-171 C | 50/50 | 16.35 MW | 16.35 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958802 | AF2-171 E | 50/50 | 10.9 MW | 10.9 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 959311 | AF2-222 C | 50/50 | 16.92 MW | 16.92 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 959312 | AF2-222 E | 50/50 | 11.33 MW | 11.33 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 960061 | AF2-297 C | 50/50 | 12.14 MW | 12.14 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 960062 | AF2-297 E | 50/50 | 8.09 MW | 8.09 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 315266 | 1PLYWOOD A | 50/50 | 1.79 MW | 1.79 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 316118 | AC1-105 C | 50/50 | 7.99 MW | 7.99 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 316131 | AB2-060 C | 50/50 | 1.4 MW | 1.4 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924162 | AB2-060 E OP | 50/50 | 3.86 MW | 3.86 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924301 | AB2-077 C O1 | 50/50 | 1.8 MW | 1.8 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924302 | AB2-077 E O1 | 50/50 | 1.2 MW | 1.2 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924311 | AB2-078 C O1 | 50/50 | 1.8 MW | 1.8 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924312 | AB2-078 E O1 | 50/50 | 1.2 MW | 1.2 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924321 | AB2-079 C O1 | 50/50 | 1.8 MW | 1.8 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924322 | AB2-079 E O1 | 50/50 | 1.2 MW | 1.2 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 925611 | AC1-036 C | 50/50 | 0.24 MW | 0.24 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 925612 | AC1-036 E | 50/50 | 1.55 MW | 1.55 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 932761 | AC2-100 C | 50/50 | 4.86 MW | 4.86 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 932762 | AC2-100 E | 50/50 | 2.37 MW | 2.37 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 938371 | AE1-056 C | 50/50 | 7.27 MW | 7.27 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 938372 | AE1-056 E | 50/50 | 3.97 MW | 3.97 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 939181 | AE1-148 C | 50/50 | 6.28 MW | 6.28 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 939182 | AE1-148 E | 50/50 | 4.19 MW | 4.19 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 940661 | AE2-053 O1 | 50/50 | 2.33 MW | 2.33 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 941791 | AE2-182 C | 50/50 | 4.61 MW | 4.61 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 941792 | AE2-182 E | 50/50 | 2.14 MW | 2.14 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 946301 | AF1-294 C | 50/50 | 4.48 MW | 4.48 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 946302 | AF1-294 E | 50/50 | 2.98 MW | 2.98 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958211 | AF2-115 C | 50/50 | 2.73 MW | 2.73 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958212 | AF2-115 E | 50/50 | 1.82 MW | 1.82 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924032 | AB2-045 E | 50/50 | 0.98 MW | 0.98 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 314677 | 6BUCKING | 50/50 | 0.36 MW | 0.36 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962561 | AG1-105 C O1 | 50/50 | 10.82 MW | 10.82 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962562 | AG1-105 E O1 | 50/50 | 7.22 MW | 7.22 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 313527 | AB2-043 C | 50/50 | 0.48 MW | 0.48 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924022 | AB2-043 E O1 | 50/50 | 2.53 MW | 2.53 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 316123 | AC1-075 C | 50/50 | 1.16 MW | 1.16 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 925997 | AC1-075 E | 50/50 | 3.86 MW | 3.86 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 926024 | AC1-080 E | 50/50 | 1.28 MW | 1.28 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963043 | AG1-153 BAT | Adder | 8.71 MW | 7.4 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963113 | AG1-160 BAT | Adder | 8.5 MW | 7.22 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965812 | AG1-449 BAT | 50/50 | 13.37 MW | 13.37 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.75 MW | 1.75 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 31.9 MW | 31.9 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 16.65 MW | 16.65 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.36 MW | 14.36 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.65 MW | 2.65 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.97 MW | 0.97 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.13 MW | 3.13 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.13 MW | 0.13 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.82 MW | 0.82 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.18 MW | 2.18 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.42 MW | 0.42 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.15 MW | 6.15 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.56 MW | 2.56 MW |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.39 MW | 0.39 MW |
Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962491 | AG1-098 C O1 | Adder | 11.3 MW | 9.61 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962492 | AG1-098 E O1 | Adder | 7.53 MW | 6.4 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963041 | AG1-153 C | 50/50 | 8.66 MW | 8.66 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963042 | AG1-153 E | 50/50 | 12.99 MW | 12.99 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963111 | AG1-160 C | 50/50 | 8.82 MW | 8.82 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963112 | AG1-160 E | 50/50 | 13.23 MW | 13.23 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963291 | AG1-178 C O2 | 50/50 | 94.4 MW | 94.4 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963351 | AG1-184 O2 | 50/50 | 50.86 MW | 50.86 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 964791 | AG1-342 C | Adder | 3.49 MW | 2.96 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 964792 | AG1-342 E | Adder | 2.74 MW | 2.33 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965811 | AG1-449 | 50/50 | 36.76 MW | 36.76 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966361 | AG1-505 C | 50/50 | 25.4 MW | 25.4 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966362 | AG1-505 E | 50/50 | 16.93 MW | 16.93 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966371 | AG1-506 C | 50/50 | 25.4 MW | 25.4 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966372 | AG1-506 E | 50/50 | 16.93 MW | 16.93 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314594 | 6PLYMOTH | Adder | 0.07 MW | 0.06 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315153 | 1CLOVER1 | 50/50 | 16.4 MW | 16.4 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315154 | 1CLOVER2 | 50/50 | 16.25 MW | 16.25 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926274 | AC1-105 E | Adder | 2.42 MW | 2.05 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 927251 | AC1-221 C | Adder | 2.17 MW | 1.84 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 927252 | AC1-221 E | Adder | 2.17 MW | 1.84 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 927261 | AC1-222 C | Adder | 3.34 MW | 2.84 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 927262 | AC1-222 E | Adder | 3.18 MW | 2.7 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934311 | AD1-055 C | Adder | 2.32 MW | 1.97 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934312 | AD1-055 E | Adder | 0.6 MW | 0.51 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934341 | AD1-058 C | Adder | 5.44 MW | 4.62 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934342 | AD1-058 E | Adder | 1.38 MW | 1.18 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934521 | AD1-076 C | Adder | 40.34 MW | 34.29 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934522 | AD1-076 E | Adder | 20.54 MW | 17.46 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934615 | AD1-087 C | 50/50 | 9.52 MW | 9.52 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934616 | AD1-087 E | 50/50 | 4.46 MW | 4.46 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934625 | AD1-088 C | Adder | 12.48 MW | 10.61 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934626 | AD1-088 E | Adder | 5.87 MW | 4.99 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934991 | AD1-131 C | Adder | 1.78 MW | 1.52 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934992 | AD1-131 E | Adder | 1.19 MW | 1.01 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935171 | AD1-152 C O1 | 50/50 | 9.49 MW | 9.49 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935172 | AD1-152 E O1 | 50/50 | 6.33 MW | 6.33 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936161 | AD2-022 C O1 | Adder | 3.14 MW | 2.67 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937481 | AD2-202 C O1 | 50/50 | 2.79 MW | 2.79 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937482 | AD2-202 E O1 | 50/50 | 1.31 MW | 1.31 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942931 | AE2-313 C | 50/50 | 56.66 MW | 56.66 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942932 | AE2-313 E | 50/50 | 37.77 MW | 37.77 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943901 | AF1-058 C | Adder | 1.85 MW | 1.57 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943902 | AF1-058 E | Adder | 1.23 MW | 1.05 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944011 | AF1-069 C | 50/50 | 20.67 MW | 20.67 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944012 | AF1-069 E | 50/50 | 8.03 MW | 8.03 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945811 | AF1-246 C O1 | 50/50 | 10.18 MW | 10.18 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945812 | AF1-246 E O1 | 50/50 | 14.05 MW | 14.05 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 960061 | AF2-297 C | Adder | 7.4 MW | 6.29 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 960062 | AF2-297 E | Adder | 4.94 MW | 4.2 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315293 | 1DOMTR9 | Adder | 5.09 MW | 4.32 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315294 | 1DOMTR10 | Adder | 6.23 MW | 5.3 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 316118 | AC1-105 C | Adder | 5.05 MW | 4.29 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932761 | AC2-100 C | Adder | 4.99 MW | 4.25 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932762 | AC2-100 E | Adder | 2.44 MW | 2.07 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940491 | AE2-034 C | Adder | 5.51 MW | 4.68 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940492 | AE2-034 E | Adder | 2.36 MW | 2.01 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941031 | AE2-094 C | 50/50 | 63.27 MW | 63.27 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941032 | AE2-094 E | 50/50 | 28.34 MW | 28.34 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941791 | AE2-182 C | Adder | 2.03 MW | 1.72 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941792 | AE2-182 E | Adder | 0.94 MW | 0.8 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957481 | AF2-042 C | 50/50 | 72.69 MW | 72.69 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957482 | AF2-042 E | 50/50 | 48.46 MW | 48.46 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957531 | AF2-047 C | Adder | 13.09 MW | 11.13 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957532 | AF2-047 E | Adder | 6.58 MW | 5.6 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 916042 | Z1-036 E | Adder | 23.07 MW | 19.61 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940641 | AE2-051 C O1 | 50/50 | 32.77 MW | 32.77 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940642 | AE2-051 E O1 | 50/50 | 21.85 MW | 21.85 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 313717 | 6SLIGO L2192 | Adder | 2.2 MW | 1.87 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314466 | 6FENTRES | 50/50 | 2.38 MW | 2.38 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314550 | 6HICKORY | Adder | 4.34 MW | 3.69 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314632 | 6AYDLETOLD | Adder | 2.19 MW | 1.86 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 919152 | AA1-139 E | Adder | 6.52 MW | 5.54 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926662 | AC1-147 E | Adder | 1.37 MW | 1.17 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926754 | AC1-161 C | 50/50 | 92.93 MW | 92.93 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926755 | AC1-161 E | 50/50 | 39.67 MW | 39.67 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934061 | AD1-033 C | 50/50 | 8.04 MW | 8.04 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934062 | AD1-033 E | 50/50 | 5.36 MW | 5.36 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937221 | AD2-160 C O1 | Adder | 6.04 MW | 5.14 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937222 | AD2-160 E O1 | Adder | 3.17 MW | 2.69 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942401 | AE2-253 C | Adder | 6.36 MW | 5.41 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942402 | AE2-253 E | Adder | 2.86 MW | 2.43 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944871 | AF1-152 C | Adder | 4.23 MW | 3.59 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944872 | AF1-152 E | Adder | 2.82 MW | 2.4 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315102 | 1BRUNSWICKG1 | 50/50 | 13.32 MW | 13.32 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315103 | 1BRUNSWICKG2 | 50/50 | 13.32 MW | 13.32 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315104 | 1BRUNSWICKG3 | 50/50 | 13.32 MW | 13.32 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315105 | 1BRUNSWICKS1 | 50/50 | 27.68 MW | 27.68 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315108 | 1ELIZAR1 | 50/50 | 3.55 MW | 3.55 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315110 | 1ELIZAR3 | 50/50 | 3.59 MW | 3.59 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315241 | 1Z1-086 GT1 | 50/50 | 17.23 MW | 17.23 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315242 | 1Z1-086 GT2 | 50/50 | 17.23 MW | 17.23 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315243 | 1Z1-086 GT3 | 50/50 | 17.23 MW | 17.23 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315244 | 1Z1-086 ST | 50/50 | 29.95 MW | 29.95 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 913392 | Y1-086 E | Adder | 2.03 MW | 1.72 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 916192 | Z1-068 E | Adder | 1.96 MW | 1.67 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 923832 | AB2-022 E | Adder | 1.14 MW | 0.97 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932044 | AC2-012 C | Adder | 8.32 MW | 7.07 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932046 | AC2-012 E | Adder | 13.58 MW | 11.54 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938535 | AE1-072 C | Adder | 17.53 MW | 14.9 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938536 | AE1-072 E | Adder | 9.14 MW | 7.77 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939414 | AE1-173_C1 | 50/50 | 40.31 MW | 40.31 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939415 | AE1-173_C2 | 50/50 | 34.55 MW | 34.55 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939416 | AE1-173_C3 | 50/50 | 40.31 MW | 40.31 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939423 | AE1-173_E1 | 50/50 | 26.87 MW | 26.87 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939424 | AE1-173_E2 | 50/50 | 23.03 MW | 23.03 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939425 | AE1-173_E3 | 50/50 | 26.87 MW | 26.87 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939431 | AE1-175 C | Adder | -1.97 MW | -1.68 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941281 | AE2-122 C O1 | Adder | 29.75 MW | 25.28 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941282 | AE2-122 E O1 | Adder | 120.03 MW | 102.03 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941291 | AE2-123 C O1 | Adder | 30.57 MW | 25.98 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941292 | AE2-123 E O1 | Adder | 119.21 MW | 101.33 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941301 | AE2-124 C O1 | Adder | 27.82 MW | 23.65 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941302 | AE2-124 E O1 | Adder | 122.09 MW | 103.78 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957631 | AF2-057 | Adder | 3.71 MW | 3.15 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962961 | AG1-145 C | Adder | -1.78 MW | -1.51 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 964951 | AG1-359 O1 | 50/50 | 24.51 MW | 24.51 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965001 | AG1-364 C O1 | Adder | 7.49 MW | 6.37 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965002 | AG1-364 E O1 | Adder | 11.24 MW | 9.55 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 901082 | W1-029 E | Adder | 36.78 MW | 31.26 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 917122 | Z2-027 E | Adder | 0.94 MW | 0.8 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925522 | AC1-027 E | Adder | 1.19 MW | 1.01 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933294 | AC2-141 C | 50/50 | 92.93 MW | 92.93 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933295 | AC2-141 E | 50/50 | 39.67 MW | 39.67 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941501 | AE2-147 C | Adder | 12.68 MW | 10.78 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941502 | AE2-147 E | Adder | 8.46 MW | 7.19 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941591 | AE2-156 O1 | Adder | 18.76 MW | 15.95 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957871 | AF2-081 C | Adder | 10.14 MW | 8.62 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957872 | AF2-081 E | Adder | 4.35 MW | 3.69 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944581 | AF1-123 C O1 | 50/50 | 58.19 MW | 58.19 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944582 | AF1-123 E O1 | 50/50 | 133.23 MW | 133.23 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944591 | AF1-124 C O1 | 50/50 | 58.19 MW | 58.19 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944592 | AF1-124 E O1 | 50/50 | 133.23 MW | 133.23 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944601 | AF1-125 C O1 | 50/50 | 58.19 MW | 58.19 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944602 | AF1-125 E O1 | 50/50 | 133.23 MW | 133.23 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962561 | AG1-105 C O1 | Adder | 7.28 MW | 6.19 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962562 | AG1-105 E O1 | Adder | 4.85 MW | 4.13 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 920692 | AA2-178 E | Adder | 3.15 MW | 2.68 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962533 | AG1-102 BAT | Adder | 2.82 MW | 2.4 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945363 | AF1-201 BAT | Adder | 3.06 MW | 2.6 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.88 MW | 5.88 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.77 MW | 1.77 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 107.61 MW | 107.61 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 34.98 MW | 34.98 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 37.49 MW | 37.49 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 8.91 MW | 8.91 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.75 MW | 2.75 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.85 MW | 8.85 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.49 MW | 0.49 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.72 MW | 1.72 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 5.07 MW | 5.07 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.25 MW | 1.25 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 17.5 MW | 17.5 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.31 MW | 0.31 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.11 MW | 7.11 MW |
8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.84 MW | 0.84 MW |
Light Load Analysis
The Queue Project was evaluated as a 122.0 MW (Capacity 122.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Light Load Analysis | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 126.81 % | 127.83 % | 549.0 | C | 701.79 | 6.74 | |
DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | DC | 127.32 % | 128.14 % | 678.68 | B | 869.66 | 7.92 | |
DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | DC | 126.29 % | 127.11 % | 678.68 | B | 862.67 | 7.92 | |
DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 113.93 % | 114.75 % | 661.76 | B | 759.37 | 7.09 | |
DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 107.58 % | 108.34 % | 661.76 | B | 716.95 | 8.69 | |
DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 113.91 % | 114.73 % | 661.76 | B | 759.24 | 7.09 | |
DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 111.85 % | 112.67 % | 661.76 | B | 745.6 | 7.09 | |
DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 105.34 % | 106.1 % | 661.76 | B | 702.13 | 8.69 | |
DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1 |
DVP_P4-2: H2T557
CONTINGENCY 'DVP_P4-2: H2T557' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2 /*6ELMONT 230.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Breaker | AC | 106.16 % | 107.4 % | 1050.6 | C | 1128.34 | 15.83 |
Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315065 | 1CHESTF6 | 50/50 | 56.2 MW | 56.2 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 916042 | Z1-036 E | Adder | 7.82 MW | 6.65 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | Adder | 1.32 MW | 1.12 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | 50/50 | 2.76 MW | 2.76 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 0.0 MW | 0.0 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 11.59 MW | 9.85 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941281 | AE2-122 C O1 | Adder | 7.98 MW | 6.78 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941282 | AE2-122 E O1 | Adder | 32.18 MW | 27.36 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941291 | AE2-123 C O1 | Adder | 8.2 MW | 6.97 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941292 | AE2-123 E O1 | Adder | 31.96 MW | 27.17 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941301 | AE2-124 C O1 | Adder | 7.4 MW | 6.29 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941302 | AE2-124 E O1 | Adder | 32.49 MW | 27.62 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941591 | AE2-156 O1 | Adder | 6.63 MW | 5.64 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942551 | AE2-270 | 50/50 | 37.93 MW | 37.93 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 3.79 MW | 3.22 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 1.47 MW | 1.25 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | Adder | 6.13 MW | 5.21 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957631 | AF2-057 | Adder | 1.34 MW | 1.14 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961711 | AG1-011 | 50/50 | 38.82 MW | 38.82 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.1 MW | 0.08 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.39 MW | 0.33 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.39 MW | 0.33 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 1.61 MW | 1.37 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 2.41 MW | 2.05 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963102 | AG1-159 E | Adder | 1.07 MW | 0.91 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | Adder | 1.63 MW | 1.39 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | Adder | 2.45 MW | 2.08 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 0.31 MW | 0.26 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 0.46 MW | 0.39 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964951 | AG1-359 | Adder | 7.61 MW | 6.47 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965001 | AG1-364 C O1 | Adder | 2.66 MW | 2.26 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965002 | AG1-364 E O1 | Adder | 3.98 MW | 3.39 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965741 | AG1-442 O1 | Adder | 2.01 MW | 1.71 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965751 | AG1-443 O1 | Adder | 2.01 MW | 1.71 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | Adder | 6.74 MW | 5.73 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314539 | 3UNCAMP | Adder | 2.31 MW | 1.97 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315292 | 1DOMTR78 | Adder | 2.79 MW | 2.38 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944581 | AF1-123 C O1 | Adder | 11.49 MW | 9.77 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944582 | AF1-123 E O1 | Adder | 26.32 MW | 22.37 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944591 | AF1-124 C O1 | Adder | 11.49 MW | 9.77 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944592 | AF1-124 E O1 | Adder | 26.32 MW | 22.37 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944601 | AF1-125 C O1 | Adder | 11.49 MW | 9.77 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944602 | AF1-125 E O1 | Adder | 26.32 MW | 22.37 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 C | Adder | 0.9 MW | 0.77 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963312 | AG1-180 E | Adder | 0.75 MW | 0.64 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 C | Adder | 9.94 MW | 8.45 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963352 | AG1-184 E | Adder | 70.93 MW | 60.29 MW |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961611 | AG1-000B C | 50/50 | 12.9 MW | 12.9 MW |
Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | 80/20 | 9.44 MW | 9.44 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 25.3 MW | 25.3 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.93 MW | 1.93 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.93 MW | 1.93 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315131 | 1EDGECMA | Adder | 1.33 MW | 1.13 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315132 | 1EDGECMB | Adder | 1.33 MW | 1.13 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 7.52 MW | 6.4 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.98 MW | 0.98 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940551 | AE2-041 | Adder | 2.15 MW | 1.83 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.22 MW | 1.22 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.94 MW | 1.94 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 12.9 MW | 12.9 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 7.36 MW | 6.25 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 29.7 MW | 25.24 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 7.56 MW | 6.43 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 29.49 MW | 25.07 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.88 MW | 5.84 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 30.17 MW | 25.65 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.79 MW | 4.92 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | 80/20 | 8.93 MW | 8.93 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943471 | AF1-018 | Adder | 2.15 MW | 1.83 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 4.21 MW | 4.21 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.64 MW | 1.64 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944141 | AF1-082 | Adder | 0.92 MW | 0.79 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945361 | AF1-201 C O1 | Adder | 0.0 MW | 0.0 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945362 | AF1-201 E O1 | Adder | 1.1 MW | 0.94 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.67 MW | 4.67 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.16 MW | 0.98 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 2.07 MW | 2.07 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.37 MW | 2.37 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | 80/20 | 9.5 MW | 9.5 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.4 MW | 0.4 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.4 MW | 0.4 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962531 | AG1-102 C | Adder | 0.34 MW | 0.29 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962532 | AG1-102 E | Adder | 0.7 MW | 0.6 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.89 MW | 1.89 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.83 MW | 2.83 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | Adder | 1.17 MW | 0.99 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.88 MW | 1.88 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.82 MW | 2.82 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.85 MW | 0.85 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.85 MW | 0.85 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.85 MW | 0.85 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.34 MW | 0.34 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.52 MW | 0.52 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.46 MW | 0.46 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 7.38 MW | 6.27 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.32 MW | 1.97 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.48 MW | 2.95 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.85 MW | 0.85 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.98 MW | 1.68 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.98 MW | 1.68 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965761 | AG1-444 O1 | Adder | 4.11 MW | 3.5 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.26 MW | 2.26 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.26 MW | 2.26 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.92 MW | 7.92 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 5.07 MW | 5.07 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966872 | AG1-558 E | Adder | 0.72 MW | 0.61 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315292 | 1DOMTR78 | Adder | 2.77 MW | 2.35 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 12.38 MW | 10.52 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 28.35 MW | 24.09 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 12.38 MW | 10.52 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 28.35 MW | 24.09 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 12.38 MW | 10.52 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 28.35 MW | 24.09 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.48 MW | 1.48 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.22 MW | 1.22 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 10.68 MW | 10.68 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 7.62 MW | 7.62 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.75 MW | 7.75 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 6.51 MW | 6.51 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 4.4 MW | 3.74 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 14.63 MW | 14.63 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946293 | AF1-293 BAT | 80/20 | 6.8 MW | 6.8 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 23.62 MW | 23.62 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 7.32 MW | 7.32 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 12.06 MW | 12.06 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.73 MW | 13.73 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.43 MW | 4.43 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 8.12 MW | 8.12 MW |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.74 MW | 7.74 MW |
Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | 80/20 | 9.44 MW | 9.44 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 25.3 MW | 25.3 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.93 MW | 1.93 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.93 MW | 1.93 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315131 | 1EDGECMA | Adder | 1.33 MW | 1.13 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315132 | 1EDGECMB | Adder | 1.33 MW | 1.13 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 7.52 MW | 6.4 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.98 MW | 0.98 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940551 | AE2-041 | Adder | 2.15 MW | 1.83 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.22 MW | 1.22 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.94 MW | 1.94 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 12.9 MW | 12.9 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 7.36 MW | 6.25 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 29.7 MW | 25.24 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 7.56 MW | 6.43 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 29.49 MW | 25.07 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.88 MW | 5.84 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 30.17 MW | 25.65 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.79 MW | 4.92 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | 80/20 | 8.93 MW | 8.93 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943471 | AF1-018 | Adder | 2.15 MW | 1.83 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 4.21 MW | 4.21 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.64 MW | 1.64 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944141 | AF1-082 | Adder | 0.92 MW | 0.79 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945361 | AF1-201 C O1 | Adder | 0.0 MW | 0.0 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945362 | AF1-201 E O1 | Adder | 1.1 MW | 0.94 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.67 MW | 4.67 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.16 MW | 0.98 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 2.07 MW | 2.07 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.37 MW | 2.37 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | 80/20 | 9.5 MW | 9.5 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.4 MW | 0.4 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.4 MW | 0.4 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962531 | AG1-102 C | Adder | 0.34 MW | 0.29 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962532 | AG1-102 E | Adder | 0.7 MW | 0.6 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.89 MW | 1.89 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.83 MW | 2.83 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | Adder | 1.17 MW | 0.99 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.88 MW | 1.88 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.82 MW | 2.82 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.85 MW | 0.85 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.85 MW | 0.85 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.85 MW | 0.85 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.34 MW | 0.34 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.52 MW | 0.52 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.46 MW | 0.46 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 7.38 MW | 6.27 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.32 MW | 1.97 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.48 MW | 2.95 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.85 MW | 0.85 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.98 MW | 1.68 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.98 MW | 1.68 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965761 | AG1-444 O1 | Adder | 4.11 MW | 3.5 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.26 MW | 2.26 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.26 MW | 2.26 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.92 MW | 7.92 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 5.07 MW | 5.07 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966872 | AG1-558 E | Adder | 0.72 MW | 0.61 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315292 | 1DOMTR78 | Adder | 2.77 MW | 2.35 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 12.38 MW | 10.52 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 28.35 MW | 24.09 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 12.38 MW | 10.52 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 28.35 MW | 24.09 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 12.38 MW | 10.52 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 28.35 MW | 24.09 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.48 MW | 1.48 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.22 MW | 1.22 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 10.68 MW | 10.68 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 7.62 MW | 7.62 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.75 MW | 7.75 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 6.51 MW | 6.51 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 4.4 MW | 3.74 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 14.63 MW | 14.63 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946293 | AF1-293 BAT | 80/20 | 6.8 MW | 6.8 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 23.62 MW | 23.62 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 7.32 MW | 7.32 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 12.06 MW | 12.06 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.73 MW | 13.73 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.43 MW | 4.43 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 8.12 MW | 8.12 MW |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.74 MW | 7.74 MW |
Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 26.41 MW | 26.41 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315065 | 1CHESTF6 | Adder | 22.19 MW | 18.86 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315083 | 1SPRUNCA | 80/20 | 1.74 MW | 1.74 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315084 | 1SPRUNCB | 80/20 | 1.74 MW | 1.74 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315131 | 1EDGECMA | Adder | 1.47 MW | 1.25 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315132 | 1EDGECMB | Adder | 1.47 MW | 1.25 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 916042 | Z1-036 E | Adder | 7.44 MW | 6.33 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940541 | AE2-040 | 80/20 | 0.99 MW | 0.99 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940651 | AE2-052 | 80/20 | 1.14 MW | 1.14 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940661 | AE2-053 O1 | 80/20 | 2.0 MW | 2.0 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941032 | AE2-094 E | 80/20 | 14.25 MW | 14.25 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941281 | AE2-122 C O1 | Adder | 7.09 MW | 6.03 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941282 | AE2-122 E O1 | Adder | 28.62 MW | 24.33 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941291 | AE2-123 C O1 | Adder | 7.29 MW | 6.2 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941292 | AE2-123 E O1 | Adder | 28.43 MW | 24.16 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941301 | AE2-124 C O1 | Adder | 6.63 MW | 5.64 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941302 | AE2-124 E O1 | Adder | 29.1 MW | 24.73 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941591 | AE2-156 O1 | Adder | 5.57 MW | 4.73 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942551 | AE2-270 | Adder | 7.96 MW | 6.76 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944011 | AF1-069 C | 80/20 | 4.66 MW | 4.66 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944012 | AF1-069 E | 80/20 | 1.81 MW | 1.81 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944141 | AF1-082 | Adder | 1.02 MW | 0.87 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946011 | AF1-266 | 80/20 | 4.71 MW | 4.71 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946291 | AF1-293 C O1 | 80/20 | 10.1 MW | 10.1 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946292 | AF1-293 E O1 | 80/20 | 15.15 MW | 15.15 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957631 | AF2-057 | Adder | 1.11 MW | 0.95 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957911 | AF2-085 | 80/20 | 2.09 MW | 2.09 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958502 | AF2-144 E | 80/20 | 2.27 MW | 2.27 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961711 | AG1-011 | Adder | 8.49 MW | 7.22 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962332 | AG1-082 E | 80/20 | 0.41 MW | 0.41 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962342 | AG1-083 E | 80/20 | 0.41 MW | 0.41 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963041 | AG1-153 C | 80/20 | 2.09 MW | 2.09 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963042 | AG1-153 E | 80/20 | 3.13 MW | 3.13 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963102 | AG1-159 E | 80/20 | 1.24 MW | 1.24 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963111 | AG1-160 C | 80/20 | 2.08 MW | 2.08 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963112 | AG1-160 E | 80/20 | 3.12 MW | 3.12 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964112 | AG1-272 E | 80/20 | 0.84 MW | 0.84 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964122 | AG1-273 E | 80/20 | 0.84 MW | 0.84 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964132 | AG1-274 E | 80/20 | 0.84 MW | 0.84 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964791 | AG1-342 C | 80/20 | 0.36 MW | 0.36 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964792 | AG1-342 E | 80/20 | 0.55 MW | 0.55 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964802 | AG1-343 E | 80/20 | 0.47 MW | 0.47 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964951 | AG1-359 | Adder | 7.13 MW | 6.06 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965001 | AG1-364 C O1 | Adder | 2.23 MW | 1.89 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965002 | AG1-364 E O1 | Adder | 3.34 MW | 2.84 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965192 | AG1-384 E | 80/20 | 0.84 MW | 0.84 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965741 | AG1-442 O1 | 80/20 | 2.02 MW | 2.02 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965751 | AG1-443 O1 | 80/20 | 2.02 MW | 2.02 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965761 | AG1-444 O1 | Adder | 4.48 MW | 3.81 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965771 | AG1-445 | 80/20 | 2.34 MW | 2.34 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965781 | AG1-446 | 80/20 | 2.34 MW | 2.34 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965811 | AG1-449 | 80/20 | 8.7 MW | 8.7 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965831 | AG1-451 | 80/20 | 4.87 MW | 4.87 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966251 | AG1-494 C | 80/20 | 1.33 MW | 1.33 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966252 | AG1-494 E | 80/20 | 2.0 MW | 2.0 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966691 | AG1-539 C | 80/20 | 1.85 MW | 1.85 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966692 | AG1-539 E | 80/20 | 2.49 MW | 2.49 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315292 | 1DOMTR78 | Adder | 2.84 MW | 2.42 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944581 | AF1-123 C O1 | Adder | 11.97 MW | 10.18 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944582 | AF1-123 E O1 | Adder | 27.42 MW | 23.3 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944591 | AF1-124 C O1 | Adder | 11.97 MW | 10.18 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944592 | AF1-124 E O1 | Adder | 27.42 MW | 23.3 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944601 | AF1-125 C O1 | Adder | 11.97 MW | 10.18 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944602 | AF1-125 E O1 | Adder | 27.42 MW | 23.3 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963311 | AG1-180 C | 80/20 | 1.5 MW | 1.5 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963312 | AG1-180 E | 80/20 | 1.24 MW | 1.24 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963351 | AG1-184 C | 80/20 | 11.59 MW | 11.59 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963352 | AG1-184 E | 80/20 | 8.27 MW | 8.27 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963361 | AG1-185 C | 80/20 | 7.65 MW | 7.65 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963362 | AG1-185 E | 80/20 | 6.43 MW | 6.43 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965581 | AG1-426 C | 80/20 | 4.76 MW | 4.76 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965582 | AG1-426 E | 80/20 | 7.15 MW | 7.15 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961611 | AG1-000B C | Adder | 4.0 MW | 3.4 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961063 | AF2-397 BAT | 80/20 | 25.66 MW | 25.66 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963473 | AG1-196 BAT | 80/20 | 10.03 MW | 10.03 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965542 | AG1-422 BAT | 80/20 | 3.02 MW | 3.02 MW |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966673 | AG1-537 BAT | 80/20 | 4.53 MW | 4.53 MW |
Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961062 | AF2-397 E | 80/20 | 26.23 MW | 26.23 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961062 | AF2-397 E | 80/20 | 26.23 MW | 26.23 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315065 | 1CHESTF6 | Adder | 22.19 MW | 18.86 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315083 | 1SPRUNCA | 80/20 | 1.74 MW | 1.74 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315084 | 1SPRUNCB | 80/20 | 1.74 MW | 1.74 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315131 | 1EDGECMA | Adder | 1.47 MW | 1.25 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315132 | 1EDGECMB | Adder | 1.47 MW | 1.25 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 916042 | Z1-036 E | Adder | 7.44 MW | 6.33 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940541 | AE2-040 | 80/20 | 0.99 MW | 0.99 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940651 | AE2-052 | Adder | 1.14 MW | 0.97 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940661 | AE2-053 O1 | 80/20 | 2.0 MW | 2.0 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941032 | AE2-094 E | 80/20 | 14.25 MW | 14.25 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941281 | AE2-122 C O1 | Adder | 7.09 MW | 6.03 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941282 | AE2-122 E O1 | Adder | 28.62 MW | 24.33 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941291 | AE2-123 C O1 | Adder | 7.29 MW | 6.2 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941292 | AE2-123 E O1 | Adder | 28.43 MW | 24.16 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941301 | AE2-124 C O1 | Adder | 6.63 MW | 5.64 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941302 | AE2-124 E O1 | Adder | 29.1 MW | 24.73 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941591 | AE2-156 O1 | Adder | 5.57 MW | 4.73 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942551 | AE2-270 | Adder | 7.96 MW | 6.76 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944011 | AF1-069 C | 80/20 | 4.66 MW | 4.66 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944012 | AF1-069 E | 80/20 | 1.81 MW | 1.81 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944141 | AF1-082 | Adder | 1.02 MW | 0.87 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946011 | AF1-266 | 80/20 | 4.71 MW | 4.71 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946291 | AF1-293 C O1 | 80/20 | 10.1 MW | 10.1 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946292 | AF1-293 E O1 | 80/20 | 15.15 MW | 15.15 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957631 | AF2-057 | Adder | 1.11 MW | 0.95 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957911 | AF2-085 | 80/20 | 2.09 MW | 2.09 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958502 | AF2-144 E | 80/20 | 2.27 MW | 2.27 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961062 | AF2-397 E | 80/20 | 26.99 MW | 26.99 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961711 | AG1-011 | Adder | 8.49 MW | 7.22 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962332 | AG1-082 E | 80/20 | 0.41 MW | 0.41 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962342 | AG1-083 E | 80/20 | 0.41 MW | 0.41 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963041 | AG1-153 C | 80/20 | 2.09 MW | 2.09 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963042 | AG1-153 E | 80/20 | 3.13 MW | 3.13 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963102 | AG1-159 E | 80/20 | 1.24 MW | 1.24 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963111 | AG1-160 C | 80/20 | 2.08 MW | 2.08 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963112 | AG1-160 E | 80/20 | 3.12 MW | 3.12 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964112 | AG1-272 E | 80/20 | 0.84 MW | 0.84 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964122 | AG1-273 E | 80/20 | 0.84 MW | 0.84 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964132 | AG1-274 E | 80/20 | 0.84 MW | 0.84 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964791 | AG1-342 C | 80/20 | 0.36 MW | 0.36 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964792 | AG1-342 E | 80/20 | 0.55 MW | 0.55 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964802 | AG1-343 E | 80/20 | 0.47 MW | 0.47 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964951 | AG1-359 | Adder | 7.13 MW | 6.06 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965001 | AG1-364 C O1 | Adder | 2.23 MW | 1.89 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965002 | AG1-364 E O1 | Adder | 3.34 MW | 2.84 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965192 | AG1-384 E | 80/20 | 0.84 MW | 0.84 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965741 | AG1-442 O1 | 80/20 | 2.02 MW | 2.02 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965751 | AG1-443 O1 | 80/20 | 2.02 MW | 2.02 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965761 | AG1-444 O1 | Adder | 4.48 MW | 3.81 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965771 | AG1-445 | 80/20 | 2.34 MW | 2.34 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965781 | AG1-446 | 80/20 | 2.34 MW | 2.34 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965811 | AG1-449 | 80/20 | 8.7 MW | 8.7 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965831 | AG1-451 | 80/20 | 4.87 MW | 4.87 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966251 | AG1-494 C | 80/20 | 1.33 MW | 1.33 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966252 | AG1-494 E | 80/20 | 2.0 MW | 2.0 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966691 | AG1-539 C | 80/20 | 1.85 MW | 1.85 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966692 | AG1-539 E | 80/20 | 2.49 MW | 2.49 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315292 | 1DOMTR78 | Adder | 2.84 MW | 2.42 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944581 | AF1-123 C O1 | Adder | 11.97 MW | 10.18 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944582 | AF1-123 E O1 | Adder | 27.42 MW | 23.3 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944591 | AF1-124 C O1 | Adder | 11.97 MW | 10.18 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944592 | AF1-124 E O1 | Adder | 27.42 MW | 23.3 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944601 | AF1-125 C O1 | Adder | 11.97 MW | 10.18 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944602 | AF1-125 E O1 | Adder | 27.42 MW | 23.3 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963311 | AG1-180 C | 80/20 | 1.5 MW | 1.5 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963312 | AG1-180 E | 80/20 | 1.24 MW | 1.24 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963351 | AG1-184 C | 80/20 | 11.59 MW | 11.59 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963352 | AG1-184 E | 80/20 | 8.27 MW | 8.27 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963361 | AG1-185 C | 80/20 | 7.65 MW | 7.65 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963362 | AG1-185 E | 80/20 | 6.43 MW | 6.43 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965581 | AG1-426 C | 80/20 | 4.76 MW | 4.76 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965582 | AG1-426 E | 80/20 | 7.15 MW | 7.15 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961611 | AG1-000B C | Adder | 4.0 MW | 3.4 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963473 | AG1-196 BAT | 80/20 | 10.03 MW | 10.03 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965542 | AG1-422 BAT | 80/20 | 3.02 MW | 3.02 MW |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966673 | AG1-537 BAT | 80/20 | 4.53 MW | 4.53 MW |
Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315060 | 1CHESTF5 | 50/50 | 40.8 MW | 40.8 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315065 | 1CHESTF6 | 50/50 | 102.16 MW | 102.16 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315083 | 1SPRUNCA | 50/50 | 6.62 MW | 6.62 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315084 | 1SPRUNCB | 50/50 | 6.62 MW | 6.62 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315131 | 1EDGECMA | Adder | 2.91 MW | 2.48 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315132 | 1EDGECMB | Adder | 2.91 MW | 2.48 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 916042 | Z1-036 E | Adder | 20.51 MW | 17.44 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940541 | AE2-040 | Adder | 2.72 MW | 2.31 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940551 | AE2-041 | 50/50 | 9.09 MW | 9.09 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940651 | AE2-052 | Adder | 4.19 MW | 3.56 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940661 | AE2-053 O1 | Adder | 2.08 MW | 1.77 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941031 | AE2-094 C | Adder | 0.0 MW | 0.0 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941032 | AE2-094 E | Adder | 27.09 MW | 23.03 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941281 | AE2-122 C O1 | Adder | 21.08 MW | 17.92 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941282 | AE2-122 E O1 | Adder | 85.06 MW | 72.31 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941291 | AE2-123 C O1 | Adder | 21.66 MW | 18.41 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941292 | AE2-123 E O1 | Adder | 84.48 MW | 71.81 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941301 | AE2-124 C O1 | Adder | 19.68 MW | 16.73 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941302 | AE2-124 E O1 | Adder | 86.36 MW | 73.4 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941591 | AE2-156 O1 | Adder | 16.74 MW | 14.22 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942551 | AE2-270 | 50/50 | 32.77 MW | 32.77 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943471 | AF1-018 | 50/50 | 9.09 MW | 9.09 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944011 | AF1-069 C | Adder | 8.85 MW | 7.53 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944012 | AF1-069 E | Adder | 3.44 MW | 2.92 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944141 | AF1-082 | Adder | 2.01 MW | 1.71 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945361 | AF1-201 C O1 | Adder | 0.0 MW | 0.0 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945362 | AF1-201 E O1 | Adder | 4.0 MW | 3.4 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946011 | AF1-266 | Adder | 12.73 MW | 10.82 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957631 | AF2-057 | Adder | 3.35 MW | 2.85 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957911 | AF2-085 | Adder | 3.82 MW | 3.25 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958501 | AF2-144 C | Adder | 0.0 MW | 0.0 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958502 | AF2-144 E | Adder | 1.41 MW | 1.2 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 961711 | AG1-011 | Adder | 34.59 MW | 29.4 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 961942 | AG1-037 E | Adder | 0.23 MW | 0.2 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962332 | AG1-082 E | Adder | 0.95 MW | 0.8 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962342 | AG1-083 E | Adder | 0.95 MW | 0.8 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962531 | AG1-102 C | Adder | 1.26 MW | 1.07 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962532 | AG1-102 E | Adder | 2.62 MW | 2.23 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963041 | AG1-153 C | Adder | 3.77 MW | 3.2 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963042 | AG1-153 E | Adder | 5.65 MW | 4.8 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963102 | AG1-159 E | Adder | 2.5 MW | 2.12 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963111 | AG1-160 C | Adder | 3.82 MW | 3.25 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963112 | AG1-160 E | Adder | 5.73 MW | 4.87 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963611 | AG1-210 C | Adder | 0.74 MW | 0.63 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963612 | AG1-210 E | Adder | 1.1 MW | 0.94 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963621 | AG1-213 C | Adder | 0.63 MW | 0.54 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963622 | AG1-213 E | Adder | 0.95 MW | 0.8 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 964801 | AG1-343 C | Adder | 0.73 MW | 0.62 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 964802 | AG1-343 E | Adder | 1.09 MW | 0.93 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 964951 | AG1-359 | Adder | 20.98 MW | 17.84 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965001 | AG1-364 C O1 | Adder | 6.7 MW | 5.69 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965002 | AG1-364 E O1 | Adder | 10.04 MW | 8.54 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965741 | AG1-442 O1 | Adder | 5.0 MW | 4.25 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965751 | AG1-443 O1 | Adder | 5.0 MW | 4.25 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965761 | AG1-444 O1 | Adder | 9.33 MW | 7.93 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965771 | AG1-445 | Adder | 2.84 MW | 2.41 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965781 | AG1-446 | Adder | 2.84 MW | 2.41 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965811 | AG1-449 | Adder | 15.83 MW | 13.45 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966661 | AG1-536 C | Adder | 6.07 MW | 5.16 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966662 | AG1-536 E | Adder | 8.15 MW | 6.93 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966872 | AG1-558 E | 50/50 | 4.36 MW | 4.36 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966882 | AG1-559 E | Adder | 2.1 MW | 1.78 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314539 | 3UNCAMP | Adder | 5.48 MW | 4.66 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315292 | 1DOMTR78 | Adder | 6.99 MW | 5.94 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944581 | AF1-123 C O1 | Adder | 34.94 MW | 29.7 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944582 | AF1-123 E O1 | Adder | 80.01 MW | 68.01 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944591 | AF1-124 C O1 | Adder | 34.94 MW | 29.7 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944592 | AF1-124 E O1 | Adder | 80.01 MW | 68.01 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944601 | AF1-125 C O1 | Adder | 34.94 MW | 29.7 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944602 | AF1-125 E O1 | Adder | 80.01 MW | 68.01 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963311 | AG1-180 C | Adder | 2.09 MW | 1.78 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963312 | AG1-180 E | Adder | 1.74 MW | 1.48 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963351 | AG1-184 C | Adder | 24.46 MW | 20.79 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963352 | AG1-184 E | Adder | 174.58 MW | 148.39 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 961611 | AG1-000B C | Adder | 15.05 MW | 12.8 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
System Reinforcements | |||
---|---|---|---|
RTEP ID | Title | Total Cost | |
b2990 | PJM Baseline Upgrade b2990. | $350,000 | |
n6130 | Rebuild 12.4 miles of 230 kV Line 259 from Chesterfield to Basin with 2-636 ACSR. | $31,000,000 | |
n5873 | Rebuild 0.16 miles of Line 2028 from Bremo to Bremo Dist with 2-636 ACSR. | $500,000 | |
n6219 | Rebuild 15.51 miles of 230 kV Line 298 from Buckingham to Bremo with 2-636 ACSR. | $23,265,000 | |
n7571 | Wreck and rebuild 230 kV line #298 from Buckingham to Farmville to a double circuit. | $44,400,000 | |
n7610 | Rebuild Line 230 kV Line #249 from Carson to Chaparral | $19,125,000 | |
b3694.8 | Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. | $15,365,000 | |
n6581 | Rebuild 12.68 miles of 230 kV Line 2002 from Carson to Poe with 2-636 ACSR. | $31,700,000 | |
b3694.7 | Energize in-service spare 500-230 kV Carson Tx#1 | $1,000,000 | |
n8238 | Rebuild 1.38 mi miles of 230 kV Line 217 from Varina to Charles City with 2-768.2 ACSS 250 C | $2,070,000 | |
n6379 | Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-636 ACSR. | $16,175,000 | |
b3694.12 | Upgrade equipment at Chesterfield substation to not limit ratings on Lines 211 and 228. | $0 | |
b3694.13 | Upgrade equipment at Hopewell substation to not limit ratings on Lines 211 and 228. | $0 | |
b2922 | PJM Baseline Upgrade b2922. Rebuild 8 of 11 miles of 230kV Lines #211 | $0 | |
b3694.11 | Reconductor approximately 2.9 miles of 230 kV Line #228 Chesterfield – Hopewell to achieve a minimum summer emergency rating of 1046 MVA. | $0 | |
n8255 | Rebuild 230 kV Line #249 from Chaparral to Locks | $7,840,000 | |
n8249 | Clover Substation: 230/500 kV Transformer Addition | $22,000,000 | |
n8149 | Add Additional 500/230 kV Transformer at Elmont Substation | $22,000,000 | |
n7567 | Rebuild 1.63 miles of 230 kV Line 2028 from Fork Union to Bremo Dist with 2-795 ACSR (26/7) 150 C | $2,445,000 | |
n6185.2 | Rebuild 17.42 miles of 230 kV Line 2028 from Fork Union to Mount Eagle with 2-636 ACSR. | $26,130,000 | |
s2609.8 | Rebuild approximately 10 miles segment of 230kV Line #205 from Locks to Tyler and upgrade the terminal equipment. The minimum summer normal rating of the line segment will be 1572MVA. | $27,000,000 | |
n6179 | Rebuild 12.3 miles of 230 kV Line 2003 from Poe to Harrowgate with 2-636 ACSR. | $30,750,000 | |
n8152 | Add additional 500/230 kV transformer at Midlothian Substation | $22,000,000 | |
n6178 | Rebuild 4.5 miles of 230 kV Line 2003 from Harrowgate to Tyler with 2-636 ACSR. | $11,250,000 | |
n8239 | Rebuild 9.46 miles of 230 kV Line 217 from Chesterfield to Varina with 2-768.2 ACSS 250 C | $14,190,000 | |
n6172 | Rebuild 37.41 miles of 500 kV Line 563 from Carson to Midlothian with 3-1351.5 125C ACSR. | $115,971,000 | |
n6539 | Build new 500 kV Line from Rawlings to Morrisville Substation 110 miles | $400,000,000 | |
b3692 | Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy. | $0 | |
b3020 | PJM baseline upgrade b3020: Rebuild 500kV Line #574 Ladysmith to Elmont . | $0 | |
n6055 | Replace Wave traps at Midlothian and North Anna 500kV substations | $300,000 | |
n5609 | Rebuild 41.13 miles of 500 kV Line 576 from Midlothian to North Anna with 3-1351.5 125C ACSR. | $127,503,000 | |
n8260 | Rebuild 500 kV Line #578 from Septa to Surry. | $36,126,000 |
Attachments
Download all tables in report
Uprate Chain | |||||
---|---|---|---|---|---|
Project | Project Status | MFO | MWE | MWC | Disposition |
AE2-313 | Active | 314.0 | 314.0 | 188.4 | Transition Cycle 1 |
AG1-449 | Active | 436.0 | 122.0 | 122.0 | Transition Cycle 1 |
Conclusion
The Transition Sort load flow retool results indicate that AG1-449 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.