AG1-404 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:02
Blue Mound-Chestnut 345 kV
100.0 MW Capacity / 100.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-404 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Storage generating facility located in the ComEd zone — McLean County, Illinois. The installed facilities will have a total capability of 100.0 MW with 100.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-404 |
| Project Name | Blue Mound-Chestnut 345 kV |
| Developer Name | Wapella Bluffs Wind Project, LLC |
| State | Illinois |
| County | McLean |
| Transmission Owner | ComEd |
| MFO | 100.0 MW |
| MWE | 100.0 MW |
| MWC | 100.0 MW |
| Fuel Type | Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-404 will interconnect on the ComEd transmission system tapping the Blue Mound to Chestnut 345 kV line. Queue Position AG1-404 proposes to connect ‘Pumpkin Vine BESS III’ with 100 MW battery storage at Pumpkin Vine Wind I to be built under PJM queue AG1-399. The proposed addition is behind the Point-of-Interconnection between ComEd and Pumpkin Vine Wind I.
Summer Peak Analysis
The Queue Project was evaluated as a 100.0 MW (Capacity 100.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 157.51 % | 159.17 % | 2107.0 | STE | 3353.73 | 34.55 | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
COMED_P4_012-45-BT14-15
CONTINGENCY 'COMED_P4_012-45-BT14-15' TRIP BRANCH FROM BUS 270697 TO BUS 270717 CKT 1 /*COLLINS ; R 345.0 - DRESDEN ; R 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 153.0 % | 154.64 % | 2107.0 | STE | 3258.28 | 34.11 | |
| CE |
LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line
270704 to 939400 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 172.25 % | 174.14 % | 1846.0 | STE | 3214.71 | 34.55 | |
| CE |
LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line
270704 to 939400 ckt 1 |
COMED_P4_012-45-BT14-15
CONTINGENCY 'COMED_P4_012-45-BT14-15' TRIP BRANCH FROM BUS 270697 TO BUS 270717 CKT 1 /*COLLINS ; R 345.0 - DRESDEN ; R 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 165.75 % | 167.62 % | 1846.0 | STE | 3094.23 | 34.11 | |
| CE |
PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line
270852 to 270704 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 162.69 % | 164.57 % | 1837.0 | STE | 3023.24 | 34.57 | |
| CE |
PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line
270852 to 270704 ckt 1 |
COMED_P4_012-45-BT14-15
CONTINGENCY 'COMED_P4_012-45-BT14-15' TRIP BRANCH FROM BUS 270697 TO BUS 270717 CKT 1 /*COLLINS ; R 345.0 - DRESDEN ; R 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 156.2 % | 158.06 % | 1837.0 | STE | 2903.6 | 34.13 | |
| CE |
BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line
270668 to 270852 ckt 1 |
COMED_P4_BRO-45-BT2-3__
CONTINGENCY 'COMED_P4_BRO-45-BT2-3__' TRIP BRANCH FROM BUS 270853 TO BUS 270819 CKT 1 /*PONTIAC ; R 345.0 - MCLEAN ; R 345.0 TRIP BRANCH FROM BUS 348847 TO BUS 348848 CKT 2 /*7BROKAW 345.0 - 4BROKAW 138.0 END |
Breaker | AC | 129.67 % | 132.01 % | 1797.0 | STE | 2372.19 | 43.1 | |
| CE |
AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line
965340 to 270668 ckt 1 |
COMED_P4_BRO-45-BT2-3__
CONTINGENCY 'COMED_P4_BRO-45-BT2-3__' TRIP BRANCH FROM BUS 270853 TO BUS 270819 CKT 1 /*PONTIAC ; R 345.0 - MCLEAN ; R 345.0 TRIP BRANCH FROM BUS 348847 TO BUS 348848 CKT 2 /*7BROKAW 345.0 - 4BROKAW 138.0 END |
Breaker | AC | 102.44 % | 104.68 % | 1863.0 | STE | 1950.17 | 43.13 | |
| CE |
AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line
965340 to 270668 ckt 1 |
COMED_P4_BRO-45-BT3-4__A
CONTINGENCY 'COMED_P4_BRO-45-BT3-4__A' TRIP BRANCH FROM BUS 270853 TO BUS 270819 CKT 1 /*PONTIAC ; R 345.0 - MCLEAN ; R 345.0 TRIP BRANCH FROM BUS 348847 TO BUS 991235 CKT 1 /*7BROKAW 345.0 - J1676 TAP 345.0 END |
Breaker | AC | 102.08 % | 104.33 % | 1863.0 | STE | 1943.66 | 43.42 | |
| CE |
CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line
270685 to 965340 ckt 1 |
COMED_P4_BRO-45-BT2-3__
CONTINGENCY 'COMED_P4_BRO-45-BT2-3__' TRIP BRANCH FROM BUS 270853 TO BUS 270819 CKT 1 /*PONTIAC ; R 345.0 - MCLEAN ; R 345.0 TRIP BRANCH FROM BUS 348847 TO BUS 348848 CKT 2 /*7BROKAW 345.0 - 4BROKAW 138.0 END |
Breaker | AC | 97.71 % | 100.62 % | 1863.0 | STE | 1874.47 | 56.87 | |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 6.93 MW | 6.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 46.41 MW | 46.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964581 | AG1-321 C O1 | 50/50 | 63.38 MW | 63.38 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964582 | AG1-321 E O1 | 50/50 | 36.9 MW | 36.9 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965091 | AG1-374 C | 50/50 | 73.7 MW | 73.7 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 49.13 MW | 49.13 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 2.02 MW | 2.02 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C | 50/50 | 18.24 MW | 18.24 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E | 50/50 | 85.41 MW | 85.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 | 50/50 | 51.83 MW | 51.83 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 | 50/50 | 51.83 MW | 51.83 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 | 50/50 | 34.55 MW | 34.55 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.46 MW | 2.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.68 MW | 3.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 64.85 MW | 64.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 64.85 MW | 64.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 6.93 MW | 6.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 46.41 MW | 46.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.01 MW | 9.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936771 | AD2-100 C | 50/50 | 24.95 MW | 24.95 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936772 | AD2-100 E | 50/50 | 16.63 MW | 16.63 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936971 | AD2-131 C | 50/50 | 1.64 MW | 1.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936972 | AD2-131 E | 50/50 | 8.26 MW | 8.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 8.58 MW | 8.58 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 57.41 MW | 57.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942481 | AE2-261 C | 50/50 | 36.7 MW | 36.7 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942482 | AE2-261 E | 50/50 | 24.47 MW | 24.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 11.16 MW | 11.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.73 MW | 7.73 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959341 | AF2-225 C | 50/50 | 27.72 MW | 27.72 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959342 | AF2-225 E | 50/50 | 38.27 MW | 38.27 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.19 MW | 8.19 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.28 MW | 12.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.53 MW | 2.53 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.89 MW | 3.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.19 MW | 8.19 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.28 MW | 12.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274650 | KINCAID ;1U | 50/50 | 19.6 MW | 19.6 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274651 | KINCAID ;2U | 50/50 | 19.59 MW | 19.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 2.43 MW | 2.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 2.5 MW | 2.5 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274863 | CAYUGA RI;1U | 50/50 | 2.33 MW | 2.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274864 | CAYUGA RI;2U | 50/50 | 2.33 MW | 2.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 2.25 MW | 2.25 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 1.95 MW | 1.95 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 12.79 MW | 12.79 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 45.91 MW | 45.91 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293777 | CAYUG;1U E | 50/50 | 73.14 MW | 73.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293778 | CAYUG;2U E | 50/50 | 73.14 MW | 73.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 75.48 MW | 75.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 76.55 MW | 76.55 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 2.44 MW | 2.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 95.69 MW | 95.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 7.16 MW | 7.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 43.37 MW | 43.37 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939401 | AE1-172 C O1 | 50/50 | 30.02 MW | 30.02 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939402 | AE1-172 E O1 | 50/50 | 140.85 MW | 140.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939741 | AE1-205 C O1 | 50/50 | 36.95 MW | 36.95 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939742 | AE1-205 E O1 | 50/50 | 51.03 MW | 51.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 22.0 MW | 22.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 6.3 MW | 6.3 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 29.48 MW | 29.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957381 | AF2-032 C | 50/50 | 2.81 MW | 2.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 1.32 MW | 1.32 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 9.01 MW | 9.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.26 MW | 2.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.51 MW | 4.51 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952651 | J756 C | External Queue | 4.84 MW | 4.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952652 | J756 E | External Queue | 26.21 MW | 26.21 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952871 | J757 C | External Queue | 5.98 MW | 5.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952872 | J757 E | External Queue | 32.33 MW | 32.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953401 | J811 | External Queue | 11.09 MW | 11.09 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953651 | J815 | External Queue | 39.31 MW | 39.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953741 | J826 C | External Queue | 3.16 MW | 3.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953742 | J826 E | External Queue | 17.1 MW | 17.1 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953851 | J845 C | External Queue | 3.11 MW | 3.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953852 | J845 E | External Queue | 16.83 MW | 16.83 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953881 | J848 C | External Queue | 6.01 MW | 6.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953882 | J848 E | External Queue | 32.53 MW | 32.53 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954411 | J912 | External Queue | 14.81 MW | 14.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954721 | J750 C | External Queue | 3.98 MW | 3.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954722 | J750 E | External Queue | 21.54 MW | 21.54 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954821 | J955 | External Queue | 187.12 MW | 187.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 30.38 MW | 30.38 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.37 MW | 2.37 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 12.84 MW | 12.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956151 | J1102 | External Queue | 12.11 MW | 12.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.66 MW | 7.66 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 41.46 MW | 41.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956451 | J1139 | External Queue | 16.12 MW | 16.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 5.18 MW | 5.18 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990672 | J1360 E | External Queue | 58.47 MW | 58.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 16.3 MW | 16.3 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991191 | J1610 | External Queue | 16.68 MW | 16.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991196 | J1626 | External Queue | 16.81 MW | 16.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 C | External Queue | 12.89 MW | 12.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991237 | J1676 E | External Queue | 69.75 MW | 69.75 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991266 | J1714 | External Queue | 11.2 MW | 11.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 C | External Queue | 3.92 MW | 3.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991262 | J1713 E | External Queue | 21.21 MW | 21.21 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.84 MW | 0.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.95 MW | 0.95 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.41 MW | 1.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 22.42 MW | 22.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 50.04 MW | 50.04 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 2.02 MW | 2.02 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.4 MW | 7.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.65 MW | 1.65 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.35 MW | 3.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.45 MW | 0.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.54 MW | 5.54 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.42 MW | 5.42 MW |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963831 | AG1-236 C | 50/50 | 6.78 MW | 6.78 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963832 | AG1-236 E | 50/50 | 45.39 MW | 45.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964581 | AG1-321 C O1 | 50/50 | 63.1 MW | 63.1 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964582 | AG1-321 E O1 | 50/50 | 36.74 MW | 36.74 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965091 | AG1-374 C | 50/50 | 73.06 MW | 73.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965092 | AG1-374 E | 50/50 | 48.71 MW | 48.71 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965331 | AG1-398 | 50/50 | 1.98 MW | 1.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965341 | AG1-399 C | 50/50 | 18.01 MW | 18.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965342 | AG1-399 E | 50/50 | 84.31 MW | 84.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965351 | AG1-400 | 50/50 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965371 | AG1-402 | 50/50 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965391 | AG1-404 | 50/50 | 34.11 MW | 34.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965911 | AG1-460 C | 50/50 | 2.38 MW | 2.38 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965912 | AG1-460 E | 50/50 | 3.56 MW | 3.56 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290261 | S-027 E | 50/50 | 64.29 MW | 64.29 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290265 | S-028 E | 50/50 | 64.29 MW | 64.29 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925771 | AC1-053 C | 50/50 | 6.78 MW | 6.78 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925772 | AC1-053 E | 50/50 | 45.39 MW | 45.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 935141 | AD1-148 | 50/50 | 8.78 MW | 8.78 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936771 | AD2-100 C | 50/50 | 24.14 MW | 24.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936772 | AD2-100 E | 50/50 | 16.1 MW | 16.1 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936971 | AD2-131 C | 50/50 | 1.59 MW | 1.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936972 | AD2-131 E | 50/50 | 7.99 MW | 7.99 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942111 | AE2-223 C | 50/50 | 8.52 MW | 8.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942112 | AE2-223 E | 50/50 | 57.01 MW | 57.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942481 | AE2-261 C | 50/50 | 35.52 MW | 35.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942482 | AE2-261 E | 50/50 | 23.68 MW | 23.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945871 | AF1-252 O1 | 50/50 | 10.79 MW | 10.79 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945881 | AF1-253 | 50/50 | 7.47 MW | 7.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959341 | AF2-225 C | 50/50 | 27.52 MW | 27.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959342 | AF2-225 E | 50/50 | 38.0 MW | 38.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959611 | AF2-252 C | 50/50 | 8.12 MW | 8.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959612 | AF2-252 E | 50/50 | 12.18 MW | 12.18 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960141 | AF2-305 | 50/50 | 2.48 MW | 2.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960261 | AF2-317 | 50/50 | 3.79 MW | 3.79 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960611 | AF2-352 C | 50/50 | 8.12 MW | 8.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960612 | AF2-352 E | 50/50 | 12.18 MW | 12.18 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274650 | KINCAID ;1U | 50/50 | 18.97 MW | 18.97 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274651 | KINCAID ;2U | 50/50 | 18.97 MW | 18.97 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274853 | TWINGROVE;U1 | 50/50 | 2.41 MW | 2.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274854 | TWINGROVE;U2 | 50/50 | 2.48 MW | 2.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274863 | CAYUGA RI;1U | 50/50 | 2.33 MW | 2.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274864 | CAYUGA RI;2U | 50/50 | 2.33 MW | 2.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274880 | RADFORD R;1U | 50/50 | 2.21 MW | 2.21 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274889 | BRIGHTSTK;1U | 50/50 | 1.93 MW | 1.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276615 | W2-048 GEN | 50/50 | 12.47 MW | 12.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276621 | X2-022 GEN | 50/50 | 44.76 MW | 44.76 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293777 | CAYUG;1U E | 50/50 | 73.06 MW | 73.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293778 | CAYUG;2U E | 50/50 | 73.06 MW | 73.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293798 | W4-005 E | 50/50 | 74.12 MW | 74.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 917502 | Z2-087 E | 50/50 | 76.01 MW | 76.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924041 | AB2-047 C O1 | 50/50 | 2.42 MW | 2.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924042 | AB2-047 E O1 | 50/50 | 95.01 MW | 95.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924261 | AB2-070 C O1 | 50/50 | 7.01 MW | 7.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924262 | AB2-070 E O1 | 50/50 | 42.48 MW | 42.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939401 | AE1-172 C O1 | 50/50 | 30.03 MW | 30.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939402 | AE1-172 E O1 | 50/50 | 140.9 MW | 140.9 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939741 | AE1-205 C O1 | 50/50 | 36.69 MW | 36.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939742 | AE1-205 E O1 | 50/50 | 50.67 MW | 50.67 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 941731 | AE2-173 O1 | 50/50 | 21.84 MW | 21.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944221 | AF1-090 C O1 | 50/50 | 6.09 MW | 6.09 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944222 | AF1-090 E O1 | 50/50 | 28.49 MW | 28.49 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957381 | AF2-032 C | 50/50 | 2.73 MW | 2.73 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957382 | AF2-032 E | 50/50 | 1.28 MW | 1.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958023 | AF2-096 BAT | 50/50 | 8.75 MW | 8.75 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960603 | AF2-351 BAT | 50/50 | 2.18 MW | 2.18 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958013 | AF2-095 BAT | 50/50 | 4.36 MW | 4.36 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952651 | J756 C | External Queue | 4.53 MW | 4.53 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952652 | J756 E | External Queue | 24.49 MW | 24.49 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952871 | J757 C | External Queue | 5.57 MW | 5.57 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952872 | J757 E | External Queue | 30.14 MW | 30.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953401 | J811 | External Queue | 10.84 MW | 10.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953651 | J815 | External Queue | 38.25 MW | 38.25 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953741 | J826 C | External Queue | 3.12 MW | 3.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953742 | J826 E | External Queue | 16.89 MW | 16.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953851 | J845 C | External Queue | 3.08 MW | 3.08 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953852 | J845 E | External Queue | 16.65 MW | 16.65 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953881 | J848 C | External Queue | 5.87 MW | 5.87 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953882 | J848 E | External Queue | 31.74 MW | 31.74 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954411 | J912 | External Queue | 14.46 MW | 14.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954721 | J750 C | External Queue | 3.82 MW | 3.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954722 | J750 E | External Queue | 20.65 MW | 20.65 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954821 | J955 | External Queue | 182.06 MW | 182.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 955402 | J1022 E | External Queue | 30.01 MW | 30.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956151 | J1102 | External Queue | 11.51 MW | 11.51 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956281 | J1115 C | External Queue | 7.56 MW | 7.56 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956282 | J1115 E | External Queue | 40.92 MW | 40.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956451 | J1139 | External Queue | 15.98 MW | 15.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990056 | J1201 | External Queue | 5.05 MW | 5.05 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990672 | J1360 E | External Queue | 57.81 MW | 57.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990856 | J1408 | External Queue | 15.71 MW | 15.71 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991191 | J1610 | External Queue | 16.01 MW | 16.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991196 | J1626 | External Queue | 16.42 MW | 16.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991236 | J1676 C | External Queue | 12.76 MW | 12.76 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991237 | J1676 E | External Queue | 69.03 MW | 69.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991266 | J1714 | External Queue | 10.95 MW | 10.95 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991261 | J1713 C | External Queue | 3.85 MW | 3.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991262 | J1713 E | External Queue | 20.81 MW | 20.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.8 MW | 0.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.92 MW | 0.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.33 MW | 1.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 21.2 MW | 21.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 46.96 MW | 46.96 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.2 MW | 1.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 1.94 MW | 1.94 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.85 MW | 6.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.59 MW | 1.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.44 MW | 2.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.43 MW | 0.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.2 MW | 5.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.22 MW | 5.22 MW |
| Details for LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 6.93 MW | 6.93 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 46.41 MW | 46.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964581 | AG1-321 C O1 | 50/50 | 63.38 MW | 63.38 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964582 | AG1-321 E O1 | 50/50 | 36.9 MW | 36.9 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965091 | AG1-374 C | 50/50 | 73.7 MW | 73.7 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 49.13 MW | 49.13 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 2.02 MW | 2.02 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C | 50/50 | 18.24 MW | 18.24 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E | 50/50 | 85.41 MW | 85.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 | 50/50 | 51.83 MW | 51.83 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 | 50/50 | 51.83 MW | 51.83 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 | 50/50 | 34.55 MW | 34.55 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.46 MW | 2.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.68 MW | 3.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 64.85 MW | 64.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 64.85 MW | 64.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 6.93 MW | 6.93 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 46.41 MW | 46.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.01 MW | 9.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936771 | AD2-100 C | 50/50 | 24.95 MW | 24.95 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936772 | AD2-100 E | 50/50 | 16.63 MW | 16.63 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936971 | AD2-131 C | 50/50 | 1.64 MW | 1.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936972 | AD2-131 E | 50/50 | 8.26 MW | 8.26 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 8.58 MW | 8.58 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 57.41 MW | 57.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942481 | AE2-261 C | 50/50 | 36.7 MW | 36.7 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942482 | AE2-261 E | 50/50 | 24.47 MW | 24.47 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 11.16 MW | 11.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.73 MW | 7.73 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959341 | AF2-225 C | 50/50 | 27.72 MW | 27.72 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959342 | AF2-225 E | 50/50 | 38.27 MW | 38.27 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.19 MW | 8.19 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.28 MW | 12.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.53 MW | 2.53 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.89 MW | 3.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.19 MW | 8.19 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.28 MW | 12.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274650 | KINCAID ;1U | 50/50 | 19.6 MW | 19.6 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274651 | KINCAID ;2U | 50/50 | 19.59 MW | 19.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 2.43 MW | 2.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 2.5 MW | 2.5 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274863 | CAYUGA RI;1U | 50/50 | 2.33 MW | 2.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274864 | CAYUGA RI;2U | 50/50 | 2.33 MW | 2.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 2.25 MW | 2.25 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 1.95 MW | 1.95 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 12.79 MW | 12.79 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 45.91 MW | 45.91 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293777 | CAYUG;1U E | 50/50 | 73.14 MW | 73.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293778 | CAYUG;2U E | 50/50 | 73.14 MW | 73.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 75.48 MW | 75.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 76.55 MW | 76.55 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 2.44 MW | 2.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 95.69 MW | 95.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 7.16 MW | 7.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 43.37 MW | 43.37 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939741 | AE1-205 C O1 | 50/50 | 36.95 MW | 36.95 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939742 | AE1-205 E O1 | 50/50 | 51.03 MW | 51.03 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 22.0 MW | 22.0 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 6.3 MW | 6.3 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 29.48 MW | 29.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957381 | AF2-032 C | 50/50 | 2.81 MW | 2.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 1.32 MW | 1.32 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 9.01 MW | 9.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.26 MW | 2.26 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.51 MW | 4.51 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952651 | J756 C | External Queue | 4.84 MW | 4.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952652 | J756 E | External Queue | 26.21 MW | 26.21 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952871 | J757 C | External Queue | 5.98 MW | 5.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952872 | J757 E | External Queue | 32.33 MW | 32.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953401 | J811 | External Queue | 11.09 MW | 11.09 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953651 | J815 | External Queue | 39.31 MW | 39.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953741 | J826 C | External Queue | 3.16 MW | 3.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953742 | J826 E | External Queue | 17.1 MW | 17.1 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953851 | J845 C | External Queue | 3.11 MW | 3.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953852 | J845 E | External Queue | 16.83 MW | 16.83 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953881 | J848 C | External Queue | 6.01 MW | 6.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953882 | J848 E | External Queue | 32.53 MW | 32.53 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954411 | J912 | External Queue | 14.81 MW | 14.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954721 | J750 C | External Queue | 3.98 MW | 3.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954722 | J750 E | External Queue | 21.54 MW | 21.54 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954821 | J955 | External Queue | 187.12 MW | 187.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 30.38 MW | 30.38 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.37 MW | 2.37 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 12.84 MW | 12.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956151 | J1102 | External Queue | 12.11 MW | 12.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.66 MW | 7.66 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 41.46 MW | 41.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956451 | J1139 | External Queue | 16.12 MW | 16.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 5.18 MW | 5.18 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990672 | J1360 E | External Queue | 58.47 MW | 58.47 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 16.3 MW | 16.3 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991191 | J1610 | External Queue | 16.68 MW | 16.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991196 | J1626 | External Queue | 16.81 MW | 16.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991216 | J1653 | External Queue | 15.06 MW | 15.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 C | External Queue | 12.89 MW | 12.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991237 | J1676 E | External Queue | 69.75 MW | 69.75 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991266 | J1714 | External Queue | 11.2 MW | 11.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991276 | J1725 C | External Queue | 1.57 MW | 1.57 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991277 | J1725 E | External Queue | 8.48 MW | 8.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 C | External Queue | 3.92 MW | 3.92 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991262 | J1713 E | External Queue | 21.21 MW | 21.21 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.84 MW | 0.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.95 MW | 0.95 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.41 MW | 1.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 22.42 MW | 22.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 50.04 MW | 50.04 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 2.02 MW | 2.02 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.4 MW | 7.4 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.65 MW | 1.65 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.35 MW | 3.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.45 MW | 0.45 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.54 MW | 5.54 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.42 MW | 5.42 MW |
| Details for LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963831 | AG1-236 C | 50/50 | 6.78 MW | 6.78 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963832 | AG1-236 E | 50/50 | 45.39 MW | 45.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964581 | AG1-321 C O1 | 50/50 | 63.1 MW | 63.1 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964582 | AG1-321 E O1 | 50/50 | 36.74 MW | 36.74 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965091 | AG1-374 C | 50/50 | 73.06 MW | 73.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965092 | AG1-374 E | 50/50 | 48.71 MW | 48.71 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965331 | AG1-398 | 50/50 | 1.98 MW | 1.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965341 | AG1-399 C | 50/50 | 18.01 MW | 18.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965342 | AG1-399 E | 50/50 | 84.31 MW | 84.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965351 | AG1-400 | 50/50 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965371 | AG1-402 | 50/50 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965391 | AG1-404 | 50/50 | 34.11 MW | 34.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965911 | AG1-460 C | 50/50 | 2.38 MW | 2.38 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965912 | AG1-460 E | 50/50 | 3.56 MW | 3.56 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290261 | S-027 E | 50/50 | 64.29 MW | 64.29 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290265 | S-028 E | 50/50 | 64.29 MW | 64.29 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925771 | AC1-053 C | 50/50 | 6.78 MW | 6.78 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925772 | AC1-053 E | 50/50 | 45.39 MW | 45.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 935141 | AD1-148 | 50/50 | 8.78 MW | 8.78 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936771 | AD2-100 C | 50/50 | 24.14 MW | 24.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936772 | AD2-100 E | 50/50 | 16.1 MW | 16.1 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936971 | AD2-131 C | 50/50 | 1.59 MW | 1.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936972 | AD2-131 E | 50/50 | 7.99 MW | 7.99 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942111 | AE2-223 C | 50/50 | 8.52 MW | 8.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942112 | AE2-223 E | 50/50 | 57.01 MW | 57.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942481 | AE2-261 C | 50/50 | 35.52 MW | 35.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942482 | AE2-261 E | 50/50 | 23.68 MW | 23.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945871 | AF1-252 O1 | 50/50 | 10.79 MW | 10.79 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945881 | AF1-253 | 50/50 | 7.47 MW | 7.47 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959341 | AF2-225 C | 50/50 | 27.52 MW | 27.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959342 | AF2-225 E | 50/50 | 38.0 MW | 38.0 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959611 | AF2-252 C | 50/50 | 8.12 MW | 8.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959612 | AF2-252 E | 50/50 | 12.18 MW | 12.18 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960141 | AF2-305 | 50/50 | 2.48 MW | 2.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960261 | AF2-317 | 50/50 | 3.79 MW | 3.79 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960611 | AF2-352 C | 50/50 | 8.12 MW | 8.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960612 | AF2-352 E | 50/50 | 12.18 MW | 12.18 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274650 | KINCAID ;1U | 50/50 | 18.97 MW | 18.97 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274651 | KINCAID ;2U | 50/50 | 18.97 MW | 18.97 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274853 | TWINGROVE;U1 | 50/50 | 2.41 MW | 2.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274854 | TWINGROVE;U2 | 50/50 | 2.48 MW | 2.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274863 | CAYUGA RI;1U | 50/50 | 2.33 MW | 2.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274864 | CAYUGA RI;2U | 50/50 | 2.33 MW | 2.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274880 | RADFORD R;1U | 50/50 | 2.21 MW | 2.21 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274889 | BRIGHTSTK;1U | 50/50 | 1.93 MW | 1.93 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276615 | W2-048 GEN | 50/50 | 12.47 MW | 12.47 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276621 | X2-022 GEN | 50/50 | 44.76 MW | 44.76 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293777 | CAYUG;1U E | 50/50 | 73.06 MW | 73.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293778 | CAYUG;2U E | 50/50 | 73.06 MW | 73.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293798 | W4-005 E | 50/50 | 74.12 MW | 74.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 917502 | Z2-087 E | 50/50 | 76.01 MW | 76.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924041 | AB2-047 C O1 | 50/50 | 2.42 MW | 2.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924042 | AB2-047 E O1 | 50/50 | 95.01 MW | 95.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924261 | AB2-070 C O1 | 50/50 | 7.01 MW | 7.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924262 | AB2-070 E O1 | 50/50 | 42.48 MW | 42.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939741 | AE1-205 C O1 | 50/50 | 36.69 MW | 36.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939742 | AE1-205 E O1 | 50/50 | 50.67 MW | 50.67 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 941731 | AE2-173 O1 | 50/50 | 21.84 MW | 21.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944221 | AF1-090 C O1 | 50/50 | 6.09 MW | 6.09 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944222 | AF1-090 E O1 | 50/50 | 28.49 MW | 28.49 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957381 | AF2-032 C | 50/50 | 2.73 MW | 2.73 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957382 | AF2-032 E | 50/50 | 1.28 MW | 1.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958023 | AF2-096 BAT | 50/50 | 8.75 MW | 8.75 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960603 | AF2-351 BAT | 50/50 | 2.18 MW | 2.18 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958013 | AF2-095 BAT | 50/50 | 4.36 MW | 4.36 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952651 | J756 C | External Queue | 4.53 MW | 4.53 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952652 | J756 E | External Queue | 24.49 MW | 24.49 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952871 | J757 C | External Queue | 5.57 MW | 5.57 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952872 | J757 E | External Queue | 30.14 MW | 30.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953401 | J811 | External Queue | 10.84 MW | 10.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953651 | J815 | External Queue | 38.25 MW | 38.25 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953741 | J826 C | External Queue | 3.12 MW | 3.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953742 | J826 E | External Queue | 16.89 MW | 16.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953851 | J845 C | External Queue | 3.08 MW | 3.08 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953852 | J845 E | External Queue | 16.65 MW | 16.65 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953881 | J848 C | External Queue | 5.87 MW | 5.87 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953882 | J848 E | External Queue | 31.74 MW | 31.74 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954411 | J912 | External Queue | 14.46 MW | 14.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954721 | J750 C | External Queue | 3.82 MW | 3.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954722 | J750 E | External Queue | 20.65 MW | 20.65 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954821 | J955 | External Queue | 182.06 MW | 182.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 955402 | J1022 E | External Queue | 30.01 MW | 30.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956151 | J1102 | External Queue | 11.51 MW | 11.51 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956281 | J1115 C | External Queue | 7.56 MW | 7.56 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956282 | J1115 E | External Queue | 40.92 MW | 40.92 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956451 | J1139 | External Queue | 15.98 MW | 15.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990056 | J1201 | External Queue | 5.05 MW | 5.05 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990672 | J1360 E | External Queue | 57.81 MW | 57.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990856 | J1408 | External Queue | 15.71 MW | 15.71 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991191 | J1610 | External Queue | 16.01 MW | 16.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991196 | J1626 | External Queue | 16.42 MW | 16.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991236 | J1676 C | External Queue | 12.76 MW | 12.76 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991237 | J1676 E | External Queue | 69.03 MW | 69.03 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991266 | J1714 | External Queue | 10.95 MW | 10.95 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991261 | J1713 C | External Queue | 3.85 MW | 3.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991262 | J1713 E | External Queue | 20.81 MW | 20.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.8 MW | 0.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.92 MW | 0.92 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.33 MW | 1.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 21.2 MW | 21.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 46.96 MW | 46.96 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.2 MW | 1.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 1.94 MW | 1.94 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.85 MW | 6.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.59 MW | 1.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.44 MW | 2.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.43 MW | 0.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.2 MW | 5.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.22 MW | 5.22 MW |
| Details for PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 6.94 MW | 6.94 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 46.45 MW | 46.45 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964581 | AG1-321 C O1 | 50/50 | 63.41 MW | 63.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964582 | AG1-321 E O1 | 50/50 | 36.92 MW | 36.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965091 | AG1-374 C | 50/50 | 73.74 MW | 73.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 49.16 MW | 49.16 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 2.02 MW | 2.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C | 50/50 | 18.25 MW | 18.25 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E | 50/50 | 85.47 MW | 85.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 | 50/50 | 51.86 MW | 51.86 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 | 50/50 | 51.86 MW | 51.86 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 | 50/50 | 34.57 MW | 34.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.46 MW | 2.46 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.69 MW | 3.69 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 64.89 MW | 64.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 64.89 MW | 64.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 6.94 MW | 6.94 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 46.45 MW | 46.45 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.02 MW | 9.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936771 | AD2-100 C | 50/50 | 24.98 MW | 24.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936772 | AD2-100 E | 50/50 | 16.65 MW | 16.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936971 | AD2-131 C | 50/50 | 1.65 MW | 1.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936972 | AD2-131 E | 50/50 | 8.27 MW | 8.27 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 8.58 MW | 8.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 57.44 MW | 57.44 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942481 | AE2-261 C | 50/50 | 36.74 MW | 36.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942482 | AE2-261 E | 50/50 | 24.49 MW | 24.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 11.18 MW | 11.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.74 MW | 7.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959341 | AF2-225 C | 50/50 | 27.73 MW | 27.73 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959342 | AF2-225 E | 50/50 | 38.3 MW | 38.3 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.19 MW | 8.19 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.29 MW | 12.29 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.54 MW | 2.54 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.89 MW | 3.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.19 MW | 8.19 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.29 MW | 12.29 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274650 | KINCAID ;1U | 50/50 | 19.62 MW | 19.62 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274651 | KINCAID ;2U | 50/50 | 19.61 MW | 19.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 2.43 MW | 2.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 2.5 MW | 2.5 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 2.25 MW | 2.25 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 1.95 MW | 1.95 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 12.8 MW | 12.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 45.95 MW | 45.95 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 75.54 MW | 75.54 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 76.59 MW | 76.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 2.44 MW | 2.44 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 95.74 MW | 95.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 7.17 MW | 7.17 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 43.41 MW | 43.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939741 | AE1-205 C O1 | 50/50 | 36.98 MW | 36.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939742 | AE1-205 E O1 | 50/50 | 51.06 MW | 51.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 22.01 MW | 22.01 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 6.3 MW | 6.3 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 29.52 MW | 29.52 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957381 | AF2-032 C | 50/50 | 2.82 MW | 2.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 1.33 MW | 1.33 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 8.99 MW | 8.99 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.25 MW | 2.25 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.5 MW | 4.5 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952651 | J756 C | External Queue | 4.84 MW | 4.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952652 | J756 E | External Queue | 26.21 MW | 26.21 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952871 | J757 C | External Queue | 5.98 MW | 5.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952872 | J757 E | External Queue | 32.33 MW | 32.33 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953401 | J811 | External Queue | 11.09 MW | 11.09 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953651 | J815 | External Queue | 39.31 MW | 39.31 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953741 | J826 C | External Queue | 3.16 MW | 3.16 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953742 | J826 E | External Queue | 17.1 MW | 17.1 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953851 | J845 C | External Queue | 3.11 MW | 3.11 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953852 | J845 E | External Queue | 16.83 MW | 16.83 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953881 | J848 C | External Queue | 6.01 MW | 6.01 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953882 | J848 E | External Queue | 32.53 MW | 32.53 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954411 | J912 | External Queue | 14.81 MW | 14.81 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954721 | J750 C | External Queue | 3.98 MW | 3.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954722 | J750 E | External Queue | 21.54 MW | 21.54 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954821 | J955 | External Queue | 187.12 MW | 187.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 30.38 MW | 30.38 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.37 MW | 2.37 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 12.84 MW | 12.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956151 | J1102 | External Queue | 12.11 MW | 12.11 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.66 MW | 7.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 41.46 MW | 41.46 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956451 | J1139 | External Queue | 16.12 MW | 16.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 5.18 MW | 5.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990672 | J1360 E | External Queue | 58.47 MW | 58.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 16.3 MW | 16.3 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991191 | J1610 | External Queue | 16.68 MW | 16.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991196 | J1626 | External Queue | 16.81 MW | 16.81 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991216 | J1653 | External Queue | 15.06 MW | 15.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 C | External Queue | 12.89 MW | 12.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991237 | J1676 E | External Queue | 69.75 MW | 69.75 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991266 | J1714 | External Queue | 11.2 MW | 11.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991276 | J1725 C | External Queue | 1.57 MW | 1.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991277 | J1725 E | External Queue | 8.48 MW | 8.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 C | External Queue | 3.92 MW | 3.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991262 | J1713 E | External Queue | 21.21 MW | 21.21 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.85 MW | 0.85 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.98 MW | 0.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.42 MW | 1.42 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 22.67 MW | 22.67 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 50.25 MW | 50.25 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.28 MW | 1.28 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 2.07 MW | 2.07 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.44 MW | 7.44 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.66 MW | 1.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.39 MW | 3.39 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.45 MW | 0.45 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.58 MW | 5.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.57 MW | 5.57 MW |
| Details for PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963831 | AG1-236 C | 50/50 | 6.79 MW | 6.79 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963832 | AG1-236 E | 50/50 | 45.43 MW | 45.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964581 | AG1-321 C O1 | 50/50 | 63.13 MW | 63.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964582 | AG1-321 E O1 | 50/50 | 36.76 MW | 36.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965091 | AG1-374 C | 50/50 | 73.1 MW | 73.1 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965092 | AG1-374 E | 50/50 | 48.74 MW | 48.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965331 | AG1-398 | 50/50 | 1.98 MW | 1.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965341 | AG1-399 C | 50/50 | 18.02 MW | 18.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965342 | AG1-399 E | 50/50 | 84.37 MW | 84.37 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965351 | AG1-400 | 50/50 | 51.2 MW | 51.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965371 | AG1-402 | 50/50 | 51.2 MW | 51.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965391 | AG1-404 | 50/50 | 34.13 MW | 34.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965911 | AG1-460 C | 50/50 | 2.38 MW | 2.38 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965912 | AG1-460 E | 50/50 | 3.57 MW | 3.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290261 | S-027 E | 50/50 | 64.33 MW | 64.33 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290265 | S-028 E | 50/50 | 64.33 MW | 64.33 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925771 | AC1-053 C | 50/50 | 6.79 MW | 6.79 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925772 | AC1-053 E | 50/50 | 45.43 MW | 45.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 935141 | AD1-148 | 50/50 | 8.79 MW | 8.79 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936771 | AD2-100 C | 50/50 | 24.17 MW | 24.17 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936772 | AD2-100 E | 50/50 | 16.12 MW | 16.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936971 | AD2-131 C | 50/50 | 1.59 MW | 1.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936972 | AD2-131 E | 50/50 | 8.0 MW | 8.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942111 | AE2-223 C | 50/50 | 8.52 MW | 8.52 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942112 | AE2-223 E | 50/50 | 57.04 MW | 57.04 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942481 | AE2-261 C | 50/50 | 35.56 MW | 35.56 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942482 | AE2-261 E | 50/50 | 23.71 MW | 23.71 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945871 | AF1-252 O1 | 50/50 | 10.8 MW | 10.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945881 | AF1-253 | 50/50 | 7.48 MW | 7.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959341 | AF2-225 C | 50/50 | 27.54 MW | 27.54 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959342 | AF2-225 E | 50/50 | 38.02 MW | 38.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959611 | AF2-252 C | 50/50 | 8.12 MW | 8.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959612 | AF2-252 E | 50/50 | 12.18 MW | 12.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960141 | AF2-305 | 50/50 | 2.48 MW | 2.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960261 | AF2-317 | 50/50 | 3.8 MW | 3.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960611 | AF2-352 C | 50/50 | 8.12 MW | 8.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960612 | AF2-352 E | 50/50 | 12.18 MW | 12.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274650 | KINCAID ;1U | 50/50 | 19.0 MW | 19.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274651 | KINCAID ;2U | 50/50 | 18.99 MW | 18.99 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274853 | TWINGROVE;U1 | 50/50 | 2.41 MW | 2.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274854 | TWINGROVE;U2 | 50/50 | 2.48 MW | 2.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274880 | RADFORD R;1U | 50/50 | 2.21 MW | 2.21 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274889 | BRIGHTSTK;1U | 50/50 | 1.94 MW | 1.94 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276615 | W2-048 GEN | 50/50 | 12.48 MW | 12.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276621 | X2-022 GEN | 50/50 | 44.8 MW | 44.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293798 | W4-005 E | 50/50 | 74.18 MW | 74.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 917502 | Z2-087 E | 50/50 | 76.05 MW | 76.05 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924041 | AB2-047 C O1 | 50/50 | 2.42 MW | 2.42 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924042 | AB2-047 E O1 | 50/50 | 95.06 MW | 95.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924261 | AB2-070 C O1 | 50/50 | 7.02 MW | 7.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924262 | AB2-070 E O1 | 50/50 | 42.51 MW | 42.51 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939741 | AE1-205 C O1 | 50/50 | 36.71 MW | 36.71 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939742 | AE1-205 E O1 | 50/50 | 50.7 MW | 50.7 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 941731 | AE2-173 O1 | 50/50 | 21.85 MW | 21.85 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944221 | AF1-090 C O1 | 50/50 | 6.09 MW | 6.09 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944222 | AF1-090 E O1 | 50/50 | 28.53 MW | 28.53 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957381 | AF2-032 C | 50/50 | 2.73 MW | 2.73 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957382 | AF2-032 E | 50/50 | 1.28 MW | 1.28 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958023 | AF2-096 BAT | 50/50 | 8.73 MW | 8.73 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960603 | AF2-351 BAT | 50/50 | 2.17 MW | 2.17 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958013 | AF2-095 BAT | 50/50 | 4.35 MW | 4.35 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952651 | J756 C | External Queue | 4.53 MW | 4.53 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952652 | J756 E | External Queue | 24.49 MW | 24.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952871 | J757 C | External Queue | 5.57 MW | 5.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952872 | J757 E | External Queue | 30.14 MW | 30.14 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953401 | J811 | External Queue | 10.84 MW | 10.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953651 | J815 | External Queue | 38.25 MW | 38.25 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953741 | J826 C | External Queue | 3.12 MW | 3.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953742 | J826 E | External Queue | 16.89 MW | 16.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953851 | J845 C | External Queue | 3.08 MW | 3.08 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953852 | J845 E | External Queue | 16.65 MW | 16.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953881 | J848 C | External Queue | 5.87 MW | 5.87 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953882 | J848 E | External Queue | 31.74 MW | 31.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954411 | J912 | External Queue | 14.46 MW | 14.46 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954721 | J750 C | External Queue | 3.82 MW | 3.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954722 | J750 E | External Queue | 20.65 MW | 20.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954821 | J955 | External Queue | 182.06 MW | 182.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 955402 | J1022 E | External Queue | 30.01 MW | 30.01 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956151 | J1102 | External Queue | 11.51 MW | 11.51 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956281 | J1115 C | External Queue | 7.56 MW | 7.56 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956282 | J1115 E | External Queue | 40.92 MW | 40.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956451 | J1139 | External Queue | 15.98 MW | 15.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990056 | J1201 | External Queue | 5.05 MW | 5.05 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990672 | J1360 E | External Queue | 57.81 MW | 57.81 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990856 | J1408 | External Queue | 15.71 MW | 15.71 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991191 | J1610 | External Queue | 16.01 MW | 16.01 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991196 | J1626 | External Queue | 16.42 MW | 16.42 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991236 | J1676 C | External Queue | 12.76 MW | 12.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991237 | J1676 E | External Queue | 69.03 MW | 69.03 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991266 | J1714 | External Queue | 10.95 MW | 10.95 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991261 | J1713 C | External Queue | 3.85 MW | 3.85 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991262 | J1713 E | External Queue | 20.81 MW | 20.81 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.81 MW | 0.81 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.95 MW | 0.95 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.34 MW | 1.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 21.44 MW | 21.44 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 47.17 MW | 47.17 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.21 MW | 1.21 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 2.0 MW | 2.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.89 MW | 6.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.6 MW | 1.6 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.48 MW | 2.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.43 MW | 0.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.24 MW | 5.24 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.37 MW | 5.37 MW |
| Details for BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 963831 | AG1-236 C | 50/50 | 4.24 MW | 4.24 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 963832 | AG1-236 E | 50/50 | 28.39 MW | 28.39 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965091 | AG1-374 C | 50/50 | 102.44 MW | 102.44 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965092 | AG1-374 E | 50/50 | 68.29 MW | 68.29 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965331 | AG1-398 | 50/50 | 1.19 MW | 1.19 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965341 | AG1-399 C | 50/50 | 22.75 MW | 22.75 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965342 | AG1-399 E | 50/50 | 106.53 MW | 106.53 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965351 | AG1-400 | 50/50 | 64.64 MW | 64.64 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965371 | AG1-402 | 50/50 | 64.64 MW | 64.64 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965391 | AG1-404 | 50/50 | 43.1 MW | 43.1 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965911 | AG1-460 C | 50/50 | 1.97 MW | 1.97 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965912 | AG1-460 E | 50/50 | 2.96 MW | 2.96 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 290261 | S-027 E | 50/50 | 90.15 MW | 90.15 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 290265 | S-028 E | 50/50 | 90.15 MW | 90.15 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 925771 | AC1-053 C | 50/50 | 4.24 MW | 4.24 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 925772 | AC1-053 E | 50/50 | 28.39 MW | 28.39 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 935141 | AD1-148 | 50/50 | 5.95 MW | 5.95 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936771 | AD2-100 C | 50/50 | 19.97 MW | 19.97 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936772 | AD2-100 E | 50/50 | 13.31 MW | 13.31 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936971 | AD2-131 C | 50/50 | 1.31 MW | 1.31 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936972 | AD2-131 E | 50/50 | 6.61 MW | 6.61 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942111 | AE2-223 C | 50/50 | 3.15 MW | 3.15 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942112 | AE2-223 E | 50/50 | 21.05 MW | 21.05 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942481 | AE2-261 C | 50/50 | 29.45 MW | 29.45 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942482 | AE2-261 E | 50/50 | 19.63 MW | 19.63 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 945871 | AF1-252 O1 | 50/50 | 8.85 MW | 8.85 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 945881 | AF1-253 | 50/50 | 6.13 MW | 6.13 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959341 | AF2-225 C | 50/50 | 10.16 MW | 10.16 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959342 | AF2-225 E | 50/50 | 14.03 MW | 14.03 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959611 | AF2-252 C | 50/50 | 11.38 MW | 11.38 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959612 | AF2-252 E | 50/50 | 17.07 MW | 17.07 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960141 | AF2-305 | 50/50 | 1.5 MW | 1.5 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960261 | AF2-317 | 50/50 | 2.57 MW | 2.57 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960611 | AF2-352 C | 50/50 | 11.38 MW | 11.38 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960612 | AF2-352 E | 50/50 | 17.07 MW | 17.07 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274650 | KINCAID ;1U | 50/50 | 15.74 MW | 15.74 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274651 | KINCAID ;2U | 50/50 | 15.76 MW | 15.76 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274853 | TWINGROVE;U1 | 50/50 | 3.37 MW | 3.37 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274854 | TWINGROVE;U2 | 50/50 | 3.47 MW | 3.47 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274880 | RADFORD R;1U | 50/50 | 2.41 MW | 2.41 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274889 | BRIGHTSTK;1U | 50/50 | 0.71 MW | 0.71 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 276615 | W2-048 GEN | 50/50 | 8.45 MW | 8.45 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 276621 | X2-022 GEN | 50/50 | 30.31 MW | 30.31 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 293798 | W4-005 E | 50/50 | 80.89 MW | 80.89 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 917502 | Z2-087 E | 50/50 | 28.07 MW | 28.07 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924041 | AB2-047 C O1 | 50/50 | 0.89 MW | 0.89 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924042 | AB2-047 E O1 | 50/50 | 35.08 MW | 35.08 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924261 | AB2-070 C O1 | 50/50 | 4.23 MW | 4.23 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924262 | AB2-070 E O1 | 50/50 | 25.64 MW | 25.64 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 939741 | AE1-205 C O1 | 50/50 | 13.55 MW | 13.55 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 939742 | AE1-205 E O1 | 50/50 | 18.71 MW | 18.71 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 941731 | AE2-173 O1 | 50/50 | 8.06 MW | 8.06 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 944221 | AF1-090 C O1 | 50/50 | 4.99 MW | 4.99 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 944222 | AF1-090 E O1 | 50/50 | 23.38 MW | 23.38 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 957381 | AF2-032 C | 50/50 | 2.26 MW | 2.26 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 957382 | AF2-032 E | 50/50 | 1.06 MW | 1.06 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952651 | J756 C | External Queue | 3.89 MW | 3.89 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952652 | J756 E | External Queue | 21.04 MW | 21.04 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952871 | J757 C | External Queue | 4.56 MW | 4.56 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952872 | J757 E | External Queue | 24.69 MW | 24.69 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953401 | J811 | External Queue | 9.02 MW | 9.02 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953651 | J815 | External Queue | 32.09 MW | 32.09 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953741 | J826 C | External Queue | 1.83 MW | 1.83 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953742 | J826 E | External Queue | 9.9 MW | 9.9 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953851 | J845 C | External Queue | 1.82 MW | 1.82 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953852 | J845 E | External Queue | 9.84 MW | 9.84 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953881 | J848 C | External Queue | 4.93 MW | 4.93 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953882 | J848 E | External Queue | 26.67 MW | 26.67 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954411 | J912 | External Queue | 12.12 MW | 12.12 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954721 | J750 C | External Queue | 3.11 MW | 3.11 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954722 | J750 E | External Queue | 16.82 MW | 16.82 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954821 | J955 | External Queue | 154.2 MW | 154.2 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 955402 | J1022 E | External Queue | 17.6 MW | 17.6 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956151 | J1102 | External Queue | 10.09 MW | 10.09 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956281 | J1115 C | External Queue | 6.94 MW | 6.94 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956282 | J1115 E | External Queue | 37.57 MW | 37.57 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956451 | J1139 | External Queue | 11.74 MW | 11.74 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990056 | J1201 | External Queue | 4.21 MW | 4.21 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990672 | J1360 E | External Queue | 43.09 MW | 43.09 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990856 | J1408 | External Queue | 13.14 MW | 13.14 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991191 | J1610 | External Queue | 13.18 MW | 13.18 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991196 | J1626 | External Queue | 13.66 MW | 13.66 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991236 | J1676 C | External Queue | 7.61 MW | 7.61 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991237 | J1676 E | External Queue | 41.17 MW | 41.17 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991266 | J1714 | External Queue | 9.11 MW | 9.11 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991261 | J1713 C | External Queue | 3.18 MW | 3.18 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991262 | J1713 E | External Queue | 17.23 MW | 17.23 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.64 MW | 0.64 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.82 MW | 0.82 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.03 MW | 1.03 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 16.92 MW | 16.92 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 35.3 MW | 35.3 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.97 MW | 0.97 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 1.72 MW | 1.72 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.17 MW | 5.17 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.26 MW | 1.26 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.94 MW | 0.94 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.33 MW | 0.33 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.02 MW | 4.02 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 4.63 MW | 4.63 MW |
| Details for AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 963831 | AG1-236 C | 50/50 | 4.25 MW | 4.25 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 963832 | AG1-236 E | 50/50 | 28.45 MW | 28.45 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965331 | AG1-398 | 50/50 | 1.2 MW | 1.2 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965341 | AG1-399 C | 50/50 | 22.77 MW | 22.77 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965342 | AG1-399 E | 50/50 | 106.62 MW | 106.62 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965351 | AG1-400 | 50/50 | 64.7 MW | 64.7 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965371 | AG1-402 | 50/50 | 64.7 MW | 64.7 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965391 | AG1-404 | 50/50 | 43.13 MW | 43.13 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965911 | AG1-460 C | 50/50 | 1.97 MW | 1.97 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965912 | AG1-460 E | 50/50 | 2.96 MW | 2.96 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 925771 | AC1-053 C | 50/50 | 4.25 MW | 4.25 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 925772 | AC1-053 E | 50/50 | 28.45 MW | 28.45 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 935141 | AD1-148 | 50/50 | 5.96 MW | 5.96 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936771 | AD2-100 C | 50/50 | 20.02 MW | 20.02 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936772 | AD2-100 E | 50/50 | 13.34 MW | 13.34 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936971 | AD2-131 C | 50/50 | 1.32 MW | 1.32 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936972 | AD2-131 E | 50/50 | 6.62 MW | 6.62 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942111 | AE2-223 C | 50/50 | 3.15 MW | 3.15 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942112 | AE2-223 E | 50/50 | 21.1 MW | 21.1 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942481 | AE2-261 C | 50/50 | 29.52 MW | 29.52 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942482 | AE2-261 E | 50/50 | 19.68 MW | 19.68 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 945871 | AF1-252 O1 | 50/50 | 8.87 MW | 8.87 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 945881 | AF1-253 | 50/50 | 6.14 MW | 6.14 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959341 | AF2-225 C | 50/50 | 10.19 MW | 10.19 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959342 | AF2-225 E | 50/50 | 14.06 MW | 14.06 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960141 | AF2-305 | 50/50 | 1.5 MW | 1.5 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960261 | AF2-317 | 50/50 | 2.57 MW | 2.57 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274650 | KINCAID ;1U | 50/50 | 15.78 MW | 15.78 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274651 | KINCAID ;2U | 50/50 | 15.8 MW | 15.8 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274880 | RADFORD R;1U | 50/50 | 2.42 MW | 2.42 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274889 | BRIGHTSTK;1U | 50/50 | 0.72 MW | 0.72 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 276615 | W2-048 GEN | 50/50 | 8.46 MW | 8.46 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 276621 | X2-022 GEN | 50/50 | 30.37 MW | 30.37 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 293798 | W4-005 E | 50/50 | 80.99 MW | 80.99 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 917502 | Z2-087 E | 50/50 | 28.13 MW | 28.13 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924041 | AB2-047 C O1 | 50/50 | 0.9 MW | 0.9 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924042 | AB2-047 E O1 | 50/50 | 35.16 MW | 35.16 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924261 | AB2-070 C O1 | 50/50 | 4.24 MW | 4.24 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924262 | AB2-070 E O1 | 50/50 | 25.7 MW | 25.7 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 939741 | AE1-205 C O1 | 50/50 | 13.58 MW | 13.58 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 939742 | AE1-205 E O1 | 50/50 | 18.75 MW | 18.75 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 941731 | AE2-173 O1 | 50/50 | 8.08 MW | 8.08 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 944221 | AF1-090 C O1 | 50/50 | 5.01 MW | 5.01 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 944222 | AF1-090 E O1 | 50/50 | 23.44 MW | 23.44 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 957381 | AF2-032 C | 50/50 | 2.27 MW | 2.27 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 957382 | AF2-032 E | 50/50 | 1.07 MW | 1.07 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960613 | AF2-352 BAT | 50/50 | 21.53 MW | 21.53 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959613 | AF2-252 BAT | 50/50 | 21.53 MW | 21.53 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 958023 | AF2-096 BAT | Adder | 6.57 MW | 5.58 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952651 | J756 C | External Queue | 3.89 MW | 3.89 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952652 | J756 E | External Queue | 21.04 MW | 21.04 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952871 | J757 C | External Queue | 4.56 MW | 4.56 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952872 | J757 E | External Queue | 24.69 MW | 24.69 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953401 | J811 | External Queue | 9.02 MW | 9.02 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953651 | J815 | External Queue | 32.09 MW | 32.09 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953741 | J826 C | External Queue | 1.83 MW | 1.83 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953742 | J826 E | External Queue | 9.9 MW | 9.9 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953851 | J845 C | External Queue | 1.82 MW | 1.82 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953852 | J845 E | External Queue | 9.84 MW | 9.84 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953881 | J848 C | External Queue | 4.93 MW | 4.93 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953882 | J848 E | External Queue | 26.67 MW | 26.67 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954411 | J912 | External Queue | 12.12 MW | 12.12 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954721 | J750 C | External Queue | 3.11 MW | 3.11 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954722 | J750 E | External Queue | 16.82 MW | 16.82 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954821 | J955 | External Queue | 154.2 MW | 154.2 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 955402 | J1022 E | External Queue | 17.6 MW | 17.6 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956151 | J1102 | External Queue | 10.09 MW | 10.09 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956281 | J1115 C | External Queue | 6.94 MW | 6.94 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956282 | J1115 E | External Queue | 37.57 MW | 37.57 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956451 | J1139 | External Queue | 11.74 MW | 11.74 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990056 | J1201 | External Queue | 4.21 MW | 4.21 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990672 | J1360 E | External Queue | 43.09 MW | 43.09 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990856 | J1408 | External Queue | 13.14 MW | 13.14 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991191 | J1610 | External Queue | 13.18 MW | 13.18 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991196 | J1626 | External Queue | 13.66 MW | 13.66 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991236 | J1676 C | External Queue | 7.61 MW | 7.61 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991237 | J1676 E | External Queue | 41.17 MW | 41.17 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991266 | J1714 | External Queue | 9.11 MW | 9.11 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991261 | J1713 C | External Queue | 3.18 MW | 3.18 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991262 | J1713 E | External Queue | 17.23 MW | 17.23 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.66 MW | 0.66 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.87 MW | 0.87 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.04 MW | 1.04 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 17.3 MW | 17.3 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 35.62 MW | 35.62 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.99 MW | 0.99 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 1.81 MW | 1.81 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.24 MW | 5.24 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.28 MW | 1.28 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.99 MW | 0.99 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.34 MW | 0.34 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.07 MW | 4.07 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 4.87 MW | 4.87 MW |
| Details for AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 963831 | AG1-236 C | 50/50 | 3.72 MW | 3.72 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 963832 | AG1-236 E | 50/50 | 24.92 MW | 24.92 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 965331 | AG1-398 | 50/50 | 1.03 MW | 1.03 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 965341 | AG1-399 C | 50/50 | 22.92 MW | 22.92 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 965342 | AG1-399 E | 50/50 | 107.32 MW | 107.32 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 965351 | AG1-400 | 50/50 | 65.12 MW | 65.12 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 965371 | AG1-402 | 50/50 | 65.12 MW | 65.12 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 965391 | AG1-404 | 50/50 | 43.42 MW | 43.42 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 965911 | AG1-460 C | 50/50 | 1.93 MW | 1.93 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 965912 | AG1-460 E | 50/50 | 2.9 MW | 2.9 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 925771 | AC1-053 C | 50/50 | 3.72 MW | 3.72 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 925772 | AC1-053 E | 50/50 | 24.92 MW | 24.92 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 935141 | AD1-148 | 50/50 | 5.41 MW | 5.41 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 936771 | AD2-100 C | 50/50 | 19.6 MW | 19.6 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 936772 | AD2-100 E | 50/50 | 13.06 MW | 13.06 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 936971 | AD2-131 C | 50/50 | 1.29 MW | 1.29 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 936972 | AD2-131 E | 50/50 | 6.49 MW | 6.49 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 942111 | AE2-223 C | 50/50 | 2.5 MW | 2.5 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 942112 | AE2-223 E | 50/50 | 16.7 MW | 16.7 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 942481 | AE2-261 C | 50/50 | 28.85 MW | 28.85 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 942482 | AE2-261 E | 50/50 | 19.24 MW | 19.24 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 945871 | AF1-252 O1 | 50/50 | 8.73 MW | 8.73 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 945881 | AF1-253 | 50/50 | 6.05 MW | 6.05 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 959341 | AF2-225 C | 50/50 | 8.06 MW | 8.06 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 959342 | AF2-225 E | 50/50 | 11.14 MW | 11.14 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 960141 | AF2-305 | 50/50 | 1.29 MW | 1.29 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 960261 | AF2-317 | 50/50 | 2.34 MW | 2.34 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 274650 | KINCAID ;1U | 50/50 | 15.41 MW | 15.41 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 274651 | KINCAID ;2U | 50/50 | 15.44 MW | 15.44 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 274880 | RADFORD R;1U | 50/50 | 2.44 MW | 2.44 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 274889 | BRIGHTSTK;1U | 50/50 | 0.57 MW | 0.57 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 276615 | W2-048 GEN | 50/50 | 7.68 MW | 7.68 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 276621 | X2-022 GEN | 50/50 | 27.57 MW | 27.57 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 293798 | W4-005 E | 50/50 | 81.94 MW | 81.94 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 917502 | Z2-087 E | 50/50 | 22.27 MW | 22.27 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 924041 | AB2-047 C O1 | 50/50 | 0.71 MW | 0.71 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 924042 | AB2-047 E O1 | 50/50 | 27.84 MW | 27.84 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 924261 | AB2-070 C O1 | 50/50 | 3.65 MW | 3.65 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 924262 | AB2-070 E O1 | 50/50 | 22.12 MW | 22.12 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 939741 | AE1-205 C O1 | 50/50 | 10.75 MW | 10.75 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 939742 | AE1-205 E O1 | 50/50 | 14.85 MW | 14.85 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 941731 | AE2-173 O1 | 50/50 | 6.4 MW | 6.4 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 944221 | AF1-090 C O1 | 50/50 | 4.93 MW | 4.93 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 944222 | AF1-090 E O1 | 50/50 | 23.06 MW | 23.06 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 957381 | AF2-032 C | 50/50 | 2.21 MW | 2.21 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 957382 | AF2-032 E | 50/50 | 1.04 MW | 1.04 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 960613 | AF2-352 BAT | 50/50 | 21.43 MW | 21.43 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 959613 | AF2-252 BAT | 50/50 | 21.43 MW | 21.43 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 958023 | AF2-096 BAT | Adder | 6.61 MW | 5.62 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 952651 | J756 C | External Queue | 3.87 MW | 3.87 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 952652 | J756 E | External Queue | 20.95 MW | 20.95 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 952871 | J757 C | External Queue | 4.45 MW | 4.45 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 952872 | J757 E | External Queue | 24.05 MW | 24.05 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 953401 | J811 | External Queue | 8.98 MW | 8.98 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 953651 | J815 | External Queue | 31.63 MW | 31.63 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 953741 | J826 C | External Queue | 1.72 MW | 1.72 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 953742 | J826 E | External Queue | 9.3 MW | 9.3 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 953851 | J845 C | External Queue | 1.71 MW | 1.71 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 953852 | J845 E | External Queue | 9.24 MW | 9.24 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 953881 | J848 C | External Queue | 4.87 MW | 4.87 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 953882 | J848 E | External Queue | 26.35 MW | 26.35 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 954411 | J912 | External Queue | 12.01 MW | 12.01 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 954681 | J949 C | External Queue | 12.44 MW | 12.44 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 954721 | J750 C | External Queue | 3.02 MW | 3.02 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 954722 | J750 E | External Queue | 16.35 MW | 16.35 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 954821 | J955 | External Queue | 150.91 MW | 150.91 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 955402 | J1022 E | External Queue | 16.53 MW | 16.53 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 956151 | J1102 | External Queue | 10.09 MW | 10.09 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 956281 | J1115 C | External Queue | 7.22 MW | 7.22 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 956282 | J1115 E | External Queue | 39.05 MW | 39.05 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 956451 | J1139 | External Queue | 12.17 MW | 12.17 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 990056 | J1201 | External Queue | 4.18 MW | 4.18 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 990672 | J1360 E | External Queue | 46.38 MW | 46.38 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 990856 | J1408 | External Queue | 12.84 MW | 12.84 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 991191 | J1610 | External Queue | 12.84 MW | 12.84 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 991196 | J1626 | External Queue | 13.61 MW | 13.61 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 991236 | J1676 C | External Queue | 8.98 MW | 8.98 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 991237 | J1676 E | External Queue | 48.57 MW | 48.57 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 991266 | J1714 | External Queue | 9.07 MW | 9.07 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 991261 | J1713 C | External Queue | 3.24 MW | 3.24 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | 991262 | J1713 E | External Queue | 17.52 MW | 17.52 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.67 MW | 0.67 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.89 MW | 0.89 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.04 MW | 1.04 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 17.36 MW | 17.36 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 35.69 MW | 35.69 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.0 MW | 1.0 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 1.85 MW | 1.85 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.18 MW | 5.18 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.3 MW | 1.3 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.82 MW | 0.82 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.34 MW | 0.34 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.05 MW | 4.05 MW |
| AG1-399 TAP-BLUEMOUND; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT3-4__A | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 4.96 MW | 4.96 MW |
| Details for CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 963831 | AG1-236 C | 50/50 | 4.25 MW | 4.25 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 963832 | AG1-236 E | 50/50 | 28.45 MW | 28.45 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965331 | AG1-398 | 50/50 | 1.2 MW | 1.2 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965911 | AG1-460 C | 50/50 | 1.97 MW | 1.97 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965912 | AG1-460 E | 50/50 | 2.96 MW | 2.96 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 925771 | AC1-053 C | 50/50 | 4.25 MW | 4.25 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 925772 | AC1-053 E | 50/50 | 28.45 MW | 28.45 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 935141 | AD1-148 | 50/50 | 5.96 MW | 5.96 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936771 | AD2-100 C | 50/50 | 20.02 MW | 20.02 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936772 | AD2-100 E | 50/50 | 13.34 MW | 13.34 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936971 | AD2-131 C | 50/50 | 1.32 MW | 1.32 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936972 | AD2-131 E | 50/50 | 6.62 MW | 6.62 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942111 | AE2-223 C | 50/50 | 3.15 MW | 3.15 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942112 | AE2-223 E | 50/50 | 21.1 MW | 21.1 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942481 | AE2-261 C | 50/50 | 29.52 MW | 29.52 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942482 | AE2-261 E | 50/50 | 19.68 MW | 19.68 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 945871 | AF1-252 O1 | 50/50 | 8.87 MW | 8.87 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 945881 | AF1-253 | 50/50 | 6.14 MW | 6.14 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959341 | AF2-225 C | 50/50 | 10.19 MW | 10.19 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959342 | AF2-225 E | 50/50 | 14.06 MW | 14.06 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960141 | AF2-305 | 50/50 | 1.5 MW | 1.5 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960261 | AF2-317 | 50/50 | 2.57 MW | 2.57 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274650 | KINCAID ;1U | 50/50 | 15.78 MW | 15.78 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274651 | KINCAID ;2U | 50/50 | 15.8 MW | 15.8 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274880 | RADFORD R;1U | 50/50 | 2.42 MW | 2.42 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274889 | BRIGHTSTK;1U | 50/50 | 0.72 MW | 0.72 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 276615 | W2-048 GEN | 50/50 | 8.46 MW | 8.46 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 276621 | X2-022 GEN | 50/50 | 30.37 MW | 30.37 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 293798 | W4-005 E | 50/50 | 80.99 MW | 80.99 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 917502 | Z2-087 E | 50/50 | 28.13 MW | 28.13 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924041 | AB2-047 C O1 | 50/50 | 0.9 MW | 0.9 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924042 | AB2-047 E O1 | 50/50 | 35.16 MW | 35.16 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924261 | AB2-070 C O1 | 50/50 | 4.24 MW | 4.24 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924262 | AB2-070 E O1 | 50/50 | 25.7 MW | 25.7 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 939741 | AE1-205 C O1 | 50/50 | 13.58 MW | 13.58 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 939742 | AE1-205 E O1 | 50/50 | 18.75 MW | 18.75 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 941731 | AE2-173 O1 | 50/50 | 8.08 MW | 8.08 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 944221 | AF1-090 C O1 | 50/50 | 5.01 MW | 5.01 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 944222 | AF1-090 E O1 | 50/50 | 23.44 MW | 23.44 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 957381 | AF2-032 C | 50/50 | 2.27 MW | 2.27 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 957382 | AF2-032 E | 50/50 | 1.07 MW | 1.07 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965392 | AG1-404 BAT | 50/50 | 56.87 MW | 56.87 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965352 | AG1-400 BAT | 50/50 | 85.3 MW | 85.3 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965372 | AG1-402 BAT | 50/50 | 85.3 MW | 85.3 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960613 | AF2-352 BAT | 50/50 | 21.53 MW | 21.53 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959613 | AF2-252 BAT | 50/50 | 21.53 MW | 21.53 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952651 | J756 C | External Queue | 3.89 MW | 3.89 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952652 | J756 E | External Queue | 21.04 MW | 21.04 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952871 | J757 C | External Queue | 4.56 MW | 4.56 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952872 | J757 E | External Queue | 24.69 MW | 24.69 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953401 | J811 | External Queue | 9.02 MW | 9.02 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953651 | J815 | External Queue | 32.09 MW | 32.09 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953741 | J826 C | External Queue | 1.83 MW | 1.83 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953742 | J826 E | External Queue | 9.9 MW | 9.9 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953851 | J845 C | External Queue | 1.82 MW | 1.82 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953852 | J845 E | External Queue | 9.84 MW | 9.84 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953881 | J848 C | External Queue | 4.93 MW | 4.93 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953882 | J848 E | External Queue | 26.67 MW | 26.67 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954411 | J912 | External Queue | 12.12 MW | 12.12 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954721 | J750 C | External Queue | 3.11 MW | 3.11 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954722 | J750 E | External Queue | 16.82 MW | 16.82 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954821 | J955 | External Queue | 154.2 MW | 154.2 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 955402 | J1022 E | External Queue | 17.6 MW | 17.6 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956151 | J1102 | External Queue | 10.09 MW | 10.09 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956281 | J1115 C | External Queue | 6.94 MW | 6.94 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956282 | J1115 E | External Queue | 37.57 MW | 37.57 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956451 | J1139 | External Queue | 11.74 MW | 11.74 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990056 | J1201 | External Queue | 4.21 MW | 4.21 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990672 | J1360 E | External Queue | 43.09 MW | 43.09 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990856 | J1408 | External Queue | 13.14 MW | 13.14 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991191 | J1610 | External Queue | 13.18 MW | 13.18 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991196 | J1626 | External Queue | 13.66 MW | 13.66 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991236 | J1676 C | External Queue | 7.61 MW | 7.61 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991237 | J1676 E | External Queue | 41.17 MW | 41.17 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991266 | J1714 | External Queue | 9.11 MW | 9.11 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991261 | J1713 C | External Queue | 3.18 MW | 3.18 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991262 | J1713 E | External Queue | 17.23 MW | 17.23 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.66 MW | 0.66 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.87 MW | 0.87 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.04 MW | 1.04 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 17.3 MW | 17.3 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 35.62 MW | 35.62 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.99 MW | 0.99 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 1.81 MW | 1.81 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.24 MW | 5.24 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.28 MW | 1.28 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.99 MW | 0.99 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.34 MW | 0.34 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.07 MW | 4.07 MW |
| CHESTNUT ; B-AG1-399 TAP 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 4.87 MW | 4.87 MW |
Light Load Analysis
The Queue Project was evaluated as a 100.0 MW (Capacity 100.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
COMED_P1-2_345-L8014__R-S-A
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-A' TRIP BRANCH FROM BUS 270853 TO BUS 964580 CKT 1 /*PONTIAC ; R 345.0 - AG1-321 TAP 345.0 END |
Single | AC | 113.74 % | 115.25 % | 2107.0 | STE | 2428.3 | 34.11 | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
COMED_P1-2_345-L8014__R-S-B
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-B' TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Single | AC | 113.74 % | 115.25 % | 2107.0 | STE | 2428.3 | 34.11 | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 111.58 % | 113.07 % | 2107.0 | STE | 2382.46 | 34.28 | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
Base Case | Single | AC | 110.53 % | 112.27 % | 1364.0 | A | 1531.36 | 23.63 | |
| CE |
LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line
270704 to 939400 ckt 1 |
COMED_P1-2_345-L8014__R-S-A
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-A' TRIP BRANCH FROM BUS 270853 TO BUS 964580 CKT 1 /*PONTIAC ; R 345.0 - AG1-321 TAP 345.0 END |
Single | AC | 122.74 % | 124.47 % | 1846.0 | STE | 2297.81 | 34.11 | |
| CE |
LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line
270704 to 939400 ckt 1 |
COMED_P1-2_345-L8014__R-S-B
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-B' TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Single | AC | 122.74 % | 124.47 % | 1846.0 | STE | 2297.65 | 34.11 | |
| CE |
LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line
270704 to 939400 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 120.19 % | 121.91 % | 1846.0 | STE | 2250.44 | 34.28 | |
| CE |
LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line
270704 to 939400 ckt 1 |
Base Case | Single | DC | 101.86 % | 103.59 % | 1364.0 | A | 1412.97 | 23.63 | |
| CE |
PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line
270852 to 270704 ckt 1 |
COMED_P1-2_345-L8014__R-S-A
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-A' TRIP BRANCH FROM BUS 270853 TO BUS 964580 CKT 1 /*PONTIAC ; R 345.0 - AG1-321 TAP 345.0 END |
Single | AC | 113.56 % | 115.31 % | 1837.0 | STE | 2118.27 | 34.22 | |
| CE |
PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line
270852 to 270704 ckt 1 |
COMED_P1-2_345-L8014__R-S-B
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-B' TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Single | AC | 113.56 % | 115.3 % | 1837.0 | STE | 2118.11 | 34.22 | |
| CE |
PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line
270852 to 270704 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 111.23 % | 112.97 % | 1837.0 | STE | 2075.18 | 34.39 | |
| CE |
PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line
270853 to 964580 ckt 1 |
COMED_P1-2_345-L11212_B-S-B
CONTINGENCY 'COMED_P1-2_345-L11212_B-S-B' TRIP BRANCH FROM BUS 934720 TO BUS 939400 CKT 1 /*AD1-100 TAP 345.0 - AE1-172 TAP 345.0 END |
Single | DC | 122.02 % | 123.74 % | 1797.0 | STE | 2223.68 | 31.03 | |
| CE |
PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line
270853 to 964580 ckt 1 |
COMED_P1-2_345-L11212_B-S-C
CONTINGENCY 'COMED_P1-2_345-L11212_B-S-C' TRIP BRANCH FROM BUS 939400 TO BUS 270704 CKT 1 /*AE1-172 TAP 345.0 - LORETTO ; B 345.0 END |
Single | DC | 116.84 % | 118.56 % | 1797.0 | STE | 2130.61 | 31.03 | |
| CE |
AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line
964580 to 270717 ckt 1 |
COMED_P1-2_345-L11212_B-S-B
CONTINGENCY 'COMED_P1-2_345-L11212_B-S-B' TRIP BRANCH FROM BUS 934720 TO BUS 939400 CKT 1 /*AD1-100 TAP 345.0 - AE1-172 TAP 345.0 END |
Single | DC | 132.06 % | 133.93 % | 1656.0 | B | 2217.88 | 31.03 | |
| CE |
AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line
964580 to 270717 ckt 1 |
COMED_P1-2_345-L11212_B-S-C
CONTINGENCY 'COMED_P1-2_345-L11212_B-S-C' TRIP BRANCH FROM BUS 939400 TO BUS 270704 CKT 1 /*AE1-172 TAP 345.0 - LORETTO ; B 345.0 END |
Single | DC | 126.44 % | 128.31 % | 1656.0 | B | 2124.81 | 31.03 | |
| CE |
MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line
270819 to 270853 ckt 1 |
COMED_P1-2_345-L8002___-S
CONTINGENCY 'COMED_P1-2_345-L8002___-S' TRIP BRANCH FROM BUS 270852 TO BUS 270668 CKT 1 /*PONTIAC ; B 345.0 - BLUEMOUND; B 345.0 END |
Single | AC | 116.93 % | 118.04 % | 1837.0 | STE | 2168.43 | 22.1 | |
| CE |
MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line
270819 to 270853 ckt 1 |
COMED_P1-2_345-L9515___-S-B
CONTINGENCY 'COMED_P1-2_345-L9515___-S-B' TRIP BRANCH FROM BUS 965340 TO BUS 270668 CKT 1 /*AG1-399 TAP 345.0 - BLUEMOUND; B 345.0 END |
Single | AC | 110.16 % | 111.28 % | 1837.0 | STE | 2044.19 | 22.2 | |
| AMIL/CE |
7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line
348847 to 270819 ckt 1 |
COMED_P1-2_345-L8002___-S
CONTINGENCY 'COMED_P1-2_345-L8002___-S' TRIP BRANCH FROM BUS 270852 TO BUS 270668 CKT 1 /*PONTIAC ; B 345.0 - BLUEMOUND; B 345.0 END |
Single | AC | 99.88 % | 101.04 % | 1793.0 | B | 1811.65 | 22.31 | |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274853 | TWINGROVE;U1 | 80/20 | 5.64 MW | 5.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274854 | TWINGROVE;U2 | 80/20 | 5.8 MW | 5.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274863 | CAYUGA RI;1U | 80/20 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274864 | CAYUGA RI;2U | 80/20 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274880 | RADFORD R;1U | 80/20 | 5.2 MW | 5.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274889 | BRIGHTSTK;1U | 80/20 | 5.11 MW | 5.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276615 | W2-048 GEN | 80/20 | 7.12 MW | 7.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276621 | X2-022 GEN | 80/20 | 20.26 MW | 20.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290261 | S-027 E | 80/20 | 25.68 MW | 25.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290265 | S-028 E | 80/20 | 25.68 MW | 25.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293777 | CAYUG;1U E | 80/20 | 32.81 MW | 32.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293778 | CAYUG;2U E | 80/20 | 32.81 MW | 32.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293798 | W4-005 E | 80/20 | 34.79 MW | 34.79 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 917502 | Z2-087 E | 80/20 | 30.35 MW | 30.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924041 | AB2-047 C O1 | 80/20 | 5.67 MW | 5.67 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924042 | AB2-047 E O1 | 80/20 | 37.94 MW | 37.94 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924261 | AB2-070 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924262 | AB2-070 E O1 | 80/20 | 34.07 MW | 34.07 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925771 | AC1-053 C | 80/20 | 5.44 MW | 5.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925772 | AC1-053 E | 80/20 | 36.42 MW | 36.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 935141 | AD1-148 | 80/20 | 9.52 MW | 9.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 939401 | AE1-172 C O1 | 80/20 | 23.93 MW | 23.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 939402 | AE1-172 E O1 | 80/20 | 112.25 MW | 112.25 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 941731 | AE2-173 O1 | 80/20 | 21.8 MW | 21.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942111 | AE2-223 C | 80/20 | 6.8 MW | 6.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942112 | AE2-223 E | 80/20 | 45.52 MW | 45.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942601 | AE2-276 | 80/20 | 2.69 MW | 2.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944221 | AF1-090 C O1 | 80/20 | 4.89 MW | 4.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944222 | AF1-090 E O1 | 80/20 | 22.91 MW | 22.91 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945391 | AF1-204 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945392 | AF1-204 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945871 | AF1-252 O1 | 80/20 | 10.85 MW | 10.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945881 | AF1-253 | 80/20 | 7.51 MW | 7.51 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959611 | AF2-252 C | 80/20 | 8.11 MW | 8.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959612 | AF2-252 E | 80/20 | 12.16 MW | 12.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960141 | AF2-305 | 80/20 | 1.99 MW | 1.99 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960261 | AF2-317 | 80/20 | 3.05 MW | 3.05 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960611 | AF2-352 C | 80/20 | 8.11 MW | 8.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960612 | AF2-352 E | 80/20 | 12.16 MW | 12.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963831 | AG1-236 C | 80/20 | 5.44 MW | 5.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963832 | AG1-236 E | 80/20 | 36.42 MW | 36.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965092 | AG1-374 E | 80/20 | 30.4 MW | 30.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965341 | AG1-399 C O1 | 80/20 | 14.41 MW | 14.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965342 | AG1-399 E O1 | 80/20 | 67.45 MW | 67.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965351 | AG1-400 O1 | 80/20 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965371 | AG1-402 O1 | 80/20 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965391 | AG1-404 O1 | 80/20 | 34.11 MW | 34.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965911 | AG1-460 C | 80/20 | 2.39 MW | 2.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965912 | AG1-460 E | 80/20 | 3.59 MW | 3.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957382 | AF2-032 E | 80/20 | 0.4 MW | 0.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276172 | Z1-108 BAT | 80/20 | 1.22 MW | 1.22 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 920273 | AA2-123 BAT | 80/20 | 1.11 MW | 1.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 943803 | AF1-048 BAT | 80/20 | 2.88 MW | 2.88 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944201 | AF1-088 FTIR | 80/20 | 53.82 MW | 53.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957141 | AF2-008 FTIR | 80/20 | 26.91 MW | 26.91 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957333 | AF2-027 BAT | 80/20 | 3.09 MW | 3.09 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957373 | AF2-031 BAT | 80/20 | 1.64 MW | 1.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957403 | AF2-034 BAT | 80/20 | 0.71 MW | 0.71 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958013 | AF2-095 BAT | 80/20 | 4.56 MW | 4.56 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958023 | AF2-096 BAT | 80/20 | 9.11 MW | 9.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959353 | AF2-226 BAT | 80/20 | 2.64 MW | 2.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960283 | AF2-319 BAT | 80/20 | 2.64 MW | 2.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960382 | AF2-329 BAT | 80/20 | 2.94 MW | 2.94 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960603 | AF2-351 BAT | 80/20 | 2.28 MW | 2.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 961503 | AF2-441 BAT | 80/20 | 17.02 MW | 17.02 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 964362 | AG1-298 BAT | 80/20 | 42.2 MW | 42.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966093 | AG1-478 BAT | 80/20 | 0.85 MW | 0.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966433 | AG1-512 BAT | 80/20 | 3.35 MW | 3.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966443 | AG1-513 BAT | 80/20 | 0.7 MW | 0.7 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966652 | AG1-535 BAT | 80/20 | 6.98 MW | 6.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274853 | TWINGROVE;U1 | 80/20 | 5.64 MW | 5.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274854 | TWINGROVE;U2 | 80/20 | 5.8 MW | 5.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274863 | CAYUGA RI;1U | 80/20 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274864 | CAYUGA RI;2U | 80/20 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274880 | RADFORD R;1U | 80/20 | 5.2 MW | 5.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 5.11 MW | 5.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276615 | W2-048 GEN | 80/20 | 7.12 MW | 7.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276621 | X2-022 GEN | 80/20 | 20.26 MW | 20.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290261 | S-027 E | 80/20 | 25.68 MW | 25.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290265 | S-028 E | 80/20 | 25.68 MW | 25.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293777 | CAYUG;1U E | 80/20 | 32.81 MW | 32.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293778 | CAYUG;2U E | 80/20 | 32.81 MW | 32.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293798 | W4-005 E | 80/20 | 34.79 MW | 34.79 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 917502 | Z2-087 E | 80/20 | 30.35 MW | 30.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924041 | AB2-047 C O1 | 80/20 | 5.67 MW | 5.67 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924042 | AB2-047 E O1 | 80/20 | 37.94 MW | 37.94 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924261 | AB2-070 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924262 | AB2-070 E O1 | 80/20 | 34.07 MW | 34.07 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925771 | AC1-053 C | 80/20 | 5.44 MW | 5.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925772 | AC1-053 E | 80/20 | 36.42 MW | 36.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 935141 | AD1-148 | 80/20 | 9.52 MW | 9.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 939401 | AE1-172 C O1 | 80/20 | 23.93 MW | 23.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 939402 | AE1-172 E O1 | 80/20 | 112.25 MW | 112.25 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 941731 | AE2-173 O1 | 80/20 | 21.8 MW | 21.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942111 | AE2-223 C | 80/20 | 6.8 MW | 6.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942112 | AE2-223 E | 80/20 | 45.52 MW | 45.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942601 | AE2-276 | 80/20 | 2.69 MW | 2.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.89 MW | 4.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944222 | AF1-090 E O1 | 80/20 | 22.91 MW | 22.91 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945391 | AF1-204 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945392 | AF1-204 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945871 | AF1-252 O1 | 80/20 | 10.85 MW | 10.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945881 | AF1-253 | 80/20 | 7.51 MW | 7.51 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959611 | AF2-252 C | 80/20 | 8.11 MW | 8.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959612 | AF2-252 E | 80/20 | 12.16 MW | 12.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960141 | AF2-305 | 80/20 | 1.99 MW | 1.99 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960261 | AF2-317 | 80/20 | 3.05 MW | 3.05 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960611 | AF2-352 C | 80/20 | 8.11 MW | 8.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960612 | AF2-352 E | 80/20 | 12.16 MW | 12.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963831 | AG1-236 C | 80/20 | 5.44 MW | 5.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963832 | AG1-236 E | 80/20 | 36.42 MW | 36.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965092 | AG1-374 E | 80/20 | 30.4 MW | 30.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965341 | AG1-399 C O1 | 80/20 | 14.41 MW | 14.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965342 | AG1-399 E O1 | 80/20 | 67.45 MW | 67.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965351 | AG1-400 O1 | 80/20 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965371 | AG1-402 O1 | 80/20 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965391 | AG1-404 O1 | 80/20 | 34.11 MW | 34.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965911 | AG1-460 C | 80/20 | 2.39 MW | 2.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965912 | AG1-460 E | 80/20 | 3.59 MW | 3.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957382 | AF2-032 E | 80/20 | 0.4 MW | 0.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276172 | Z1-108 BAT | 80/20 | 1.22 MW | 1.22 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 920273 | AA2-123 BAT | 80/20 | 1.11 MW | 1.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 943803 | AF1-048 BAT | 80/20 | 2.88 MW | 2.88 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944201 | AF1-088 FTIR | 80/20 | 53.82 MW | 53.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957141 | AF2-008 FTIR | 80/20 | 26.91 MW | 26.91 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957333 | AF2-027 BAT | 80/20 | 3.09 MW | 3.09 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957373 | AF2-031 BAT | 80/20 | 1.64 MW | 1.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957403 | AF2-034 BAT | 80/20 | 0.71 MW | 0.71 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958013 | AF2-095 BAT | 80/20 | 4.56 MW | 4.56 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958023 | AF2-096 BAT | 80/20 | 9.11 MW | 9.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959353 | AF2-226 BAT | 80/20 | 2.64 MW | 2.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960283 | AF2-319 BAT | 80/20 | 2.64 MW | 2.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960382 | AF2-329 BAT | 80/20 | 2.94 MW | 2.94 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960603 | AF2-351 BAT | 80/20 | 2.28 MW | 2.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 961503 | AF2-441 BAT | 80/20 | 17.02 MW | 17.02 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 964362 | AG1-298 BAT | 80/20 | 42.2 MW | 42.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966093 | AG1-478 BAT | 80/20 | 0.85 MW | 0.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966433 | AG1-512 BAT | 80/20 | 3.35 MW | 3.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966443 | AG1-513 BAT | 80/20 | 0.7 MW | 0.7 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966652 | AG1-535 BAT | 80/20 | 6.98 MW | 6.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 5.66 MW | 5.66 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 5.82 MW | 5.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274863 | CAYUGA RI;1U | 50/50 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274864 | CAYUGA RI;2U | 50/50 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 5.24 MW | 5.24 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 5.12 MW | 5.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 7.19 MW | 7.19 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 20.46 MW | 20.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 25.77 MW | 25.77 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 25.77 MW | 25.77 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293777 | CAYUG;1U E | 50/50 | 32.82 MW | 32.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293778 | CAYUG;2U E | 50/50 | 32.82 MW | 32.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 35.04 MW | 35.04 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 30.43 MW | 30.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 5.68 MW | 5.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 38.03 MW | 38.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 5.67 MW | 5.67 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 34.35 MW | 34.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 5.49 MW | 5.49 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 36.74 MW | 36.74 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.62 MW | 9.62 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939401 | AE1-172 C O1 | 50/50 | 23.92 MW | 23.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939402 | AE1-172 E O1 | 50/50 | 112.22 MW | 112.22 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 21.86 MW | 21.86 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 6.82 MW | 6.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 45.64 MW | 45.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942601 | AE2-276 | Adder | 2.71 MW | 2.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 4.96 MW | 4.96 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 23.22 MW | 23.22 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945391 | AF1-204 C O1 | Adder | 3.3 MW | 2.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945392 | AF1-204 E O1 | Adder | 9.91 MW | 8.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 10.99 MW | 10.99 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.61 MW | 7.61 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.13 MW | 8.13 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.2 MW | 12.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.01 MW | 2.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.08 MW | 3.08 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.13 MW | 8.13 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.2 MW | 12.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 5.49 MW | 5.49 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 36.74 MW | 36.74 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 30.5 MW | 30.5 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 1.6 MW | 1.6 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C O1 | 50/50 | 14.48 MW | 14.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E O1 | 50/50 | 67.78 MW | 67.78 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 O1 | 50/50 | 51.41 MW | 51.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 O1 | 50/50 | 51.41 MW | 51.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 O1 | 50/50 | 34.28 MW | 34.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.42 MW | 2.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.63 MW | 3.63 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 0.41 MW | 0.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944201 | AF1-088 FTIR | Adder | 63.82 MW | 54.25 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957141 | AF2-008 FTIR | Adder | 31.91 MW | 27.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.62 MW | 4.62 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 9.22 MW | 9.22 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.31 MW | 2.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 4.84 MW | 4.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990271 | J1263 | External Queue | 30.69 MW | 30.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990351 | J1289 C | External Queue | 2.43 MW | 2.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 15.53 MW | 15.53 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 29.24 MW | 29.24 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.2 MW | 2.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 11.92 MW | 11.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.43 MW | 7.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 40.17 MW | 40.17 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 | External Queue | 80.35 MW | 80.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 | External Queue | 24.0 MW | 24.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991276 | J1725 | External Queue | 9.28 MW | 9.28 MW |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 3.89 MW | 3.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 4.0 MW | 4.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 4.47 MW | 4.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 4.47 MW | 4.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274880 | RADFORD R;1U | 80/20 | 3.62 MW | 3.62 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 3.51 MW | 3.51 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 276615 | W2-048 GEN | 80/20 | 4.99 MW | 4.99 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 276621 | X2-022 GEN | 80/20 | 14.21 MW | 14.21 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 17.72 MW | 17.72 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 17.72 MW | 17.72 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 293777 | CAYUG;1U E | 80/20 | 26.87 MW | 26.87 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 293778 | CAYUG;2U E | 80/20 | 26.87 MW | 26.87 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 293798 | W4-005 E | 80/20 | 24.23 MW | 24.23 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 20.82 MW | 20.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 3.89 MW | 3.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 26.03 MW | 26.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 924261 | AB2-070 C O1 | 80/20 | 3.92 MW | 3.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 924262 | AB2-070 E O1 | 80/20 | 23.77 MW | 23.77 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 925771 | AC1-053 C | 80/20 | 3.8 MW | 3.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 925772 | AC1-053 E | 80/20 | 25.45 MW | 25.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 935141 | AD1-148 | 80/20 | 6.68 MW | 6.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 20.93 MW | 20.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 939402 | AE1-172 E O1 | 80/20 | 98.19 MW | 98.19 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 14.96 MW | 14.96 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 4.67 MW | 4.67 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 31.24 MW | 31.24 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 944222 | AF1-090 E O1 | 80/20 | 16.26 MW | 16.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 7.69 MW | 7.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 | 80/20 | 5.33 MW | 5.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 5.59 MW | 5.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 8.39 MW | 8.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 960141 | AF2-305 | 80/20 | 1.39 MW | 1.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 960261 | AF2-317 | 80/20 | 2.14 MW | 2.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 5.59 MW | 5.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 8.39 MW | 8.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 963831 | AG1-236 C | 80/20 | 3.8 MW | 3.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 963832 | AG1-236 E | 80/20 | 25.45 MW | 25.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965092 | AG1-374 E | 80/20 | 20.97 MW | 20.97 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965331 | AG1-398 | 80/20 | 1.11 MW | 1.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965341 | AG1-399 C O1 | 80/20 | 9.98 MW | 9.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965342 | AG1-399 E O1 | 80/20 | 46.73 MW | 46.73 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965351 | AG1-400 O1 | 80/20 | 35.45 MW | 35.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965371 | AG1-402 O1 | 80/20 | 35.45 MW | 35.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965391 | AG1-404 O1 | 80/20 | 23.63 MW | 23.63 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965911 | AG1-460 C | 80/20 | 1.69 MW | 1.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965912 | AG1-460 E | 80/20 | 2.54 MW | 2.54 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 957382 | AF2-032 E | 80/20 | 0.28 MW | 0.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 957373 | AF2-031 BAT | 80/20 | 1.23 MW | 1.23 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 958013 | AF2-095 BAT | 80/20 | 4.06 MW | 4.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 958023 | AF2-096 BAT | 80/20 | 8.46 MW | 8.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 960603 | AF2-351 BAT | 80/20 | 2.03 MW | 2.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 961503 | AF2-441 BAT | 80/20 | 12.76 MW | 12.76 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 964362 | AG1-298 BAT | 80/20 | 31.81 MW | 31.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 966093 | AG1-478 BAT | 80/20 | 0.55 MW | 0.55 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 966433 | AG1-512 BAT | 80/20 | 2.4 MW | 2.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 966652 | AG1-535 BAT | 80/20 | 5.28 MW | 5.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 990056 | J1201 | External Queue | 3.2 MW | 3.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 990351 | J1289 C | External Queue | 1.71 MW | 1.71 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 990856 | J1408 | External Queue | 10.46 MW | 10.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 955402 | J1022 E | External Queue | 19.43 MW | 19.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 955711 | J1055 C | External Queue | 1.55 MW | 1.55 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 955712 | J1055 E | External Queue | 8.36 MW | 8.36 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 956281 | J1115 C | External Queue | 4.98 MW | 4.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 956282 | J1115 E | External Queue | 26.93 MW | 26.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 991236 | J1676 | External Queue | 53.84 MW | 53.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 991261 | J1713 | External Queue | 15.96 MW | 15.96 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 991276 | J1725 | External Queue | 6.54 MW | 6.54 MW |
| Details for LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274853 | TWINGROVE;U1 | 80/20 | 5.64 MW | 5.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274854 | TWINGROVE;U2 | 80/20 | 5.8 MW | 5.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274863 | CAYUGA RI;1U | 80/20 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274864 | CAYUGA RI;2U | 80/20 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274880 | RADFORD R;1U | 80/20 | 5.2 MW | 5.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274889 | BRIGHTSTK;1U | 80/20 | 5.11 MW | 5.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276615 | W2-048 GEN | 80/20 | 7.12 MW | 7.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276621 | X2-022 GEN | 80/20 | 20.26 MW | 20.26 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290261 | S-027 E | 80/20 | 25.68 MW | 25.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290265 | S-028 E | 80/20 | 25.68 MW | 25.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293777 | CAYUG;1U E | 80/20 | 32.81 MW | 32.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293778 | CAYUG;2U E | 80/20 | 32.81 MW | 32.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293798 | W4-005 E | 80/20 | 34.79 MW | 34.79 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 917502 | Z2-087 E | 80/20 | 30.35 MW | 30.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924041 | AB2-047 C O1 | 80/20 | 5.67 MW | 5.67 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924042 | AB2-047 E O1 | 80/20 | 37.94 MW | 37.94 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924261 | AB2-070 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924262 | AB2-070 E O1 | 80/20 | 34.07 MW | 34.07 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925771 | AC1-053 C | 80/20 | 5.44 MW | 5.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925772 | AC1-053 E | 80/20 | 36.42 MW | 36.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 935141 | AD1-148 | 80/20 | 9.52 MW | 9.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 941731 | AE2-173 O1 | 80/20 | 21.8 MW | 21.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942111 | AE2-223 C | 80/20 | 6.8 MW | 6.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942112 | AE2-223 E | 80/20 | 45.52 MW | 45.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942601 | AE2-276 | 80/20 | 2.69 MW | 2.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944221 | AF1-090 C O1 | 80/20 | 4.89 MW | 4.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944222 | AF1-090 E O1 | 80/20 | 22.91 MW | 22.91 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945391 | AF1-204 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945392 | AF1-204 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945871 | AF1-252 O1 | 80/20 | 10.85 MW | 10.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945881 | AF1-253 | 80/20 | 7.51 MW | 7.51 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959611 | AF2-252 C | 80/20 | 8.11 MW | 8.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959612 | AF2-252 E | 80/20 | 12.16 MW | 12.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960141 | AF2-305 | 80/20 | 1.99 MW | 1.99 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960261 | AF2-317 | 80/20 | 3.05 MW | 3.05 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960611 | AF2-352 C | 80/20 | 8.11 MW | 8.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960612 | AF2-352 E | 80/20 | 12.16 MW | 12.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963831 | AG1-236 C | 80/20 | 5.44 MW | 5.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963832 | AG1-236 E | 80/20 | 36.42 MW | 36.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965092 | AG1-374 E | 80/20 | 30.4 MW | 30.4 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965341 | AG1-399 C O1 | 80/20 | 14.41 MW | 14.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965342 | AG1-399 E O1 | 80/20 | 67.45 MW | 67.45 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965351 | AG1-400 O1 | 80/20 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965371 | AG1-402 O1 | 80/20 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965391 | AG1-404 O1 | 80/20 | 34.11 MW | 34.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965911 | AG1-460 C | 80/20 | 2.39 MW | 2.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965912 | AG1-460 E | 80/20 | 3.59 MW | 3.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957382 | AF2-032 E | 80/20 | 0.4 MW | 0.4 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276172 | Z1-108 BAT | 80/20 | 1.22 MW | 1.22 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 920273 | AA2-123 BAT | 80/20 | 1.11 MW | 1.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 943803 | AF1-048 BAT | 80/20 | 2.88 MW | 2.88 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944201 | AF1-088 FTIR | 80/20 | 53.82 MW | 53.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957141 | AF2-008 FTIR | 80/20 | 26.91 MW | 26.91 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957333 | AF2-027 BAT | 80/20 | 3.09 MW | 3.09 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957373 | AF2-031 BAT | 80/20 | 1.64 MW | 1.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957403 | AF2-034 BAT | 80/20 | 0.71 MW | 0.71 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958013 | AF2-095 BAT | 80/20 | 4.56 MW | 4.56 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958023 | AF2-096 BAT | 80/20 | 9.11 MW | 9.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959353 | AF2-226 BAT | 80/20 | 2.64 MW | 2.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960283 | AF2-319 BAT | 80/20 | 2.64 MW | 2.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960382 | AF2-329 BAT | 80/20 | 2.94 MW | 2.94 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960603 | AF2-351 BAT | 80/20 | 2.28 MW | 2.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 961503 | AF2-441 BAT | 80/20 | 17.02 MW | 17.02 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 964362 | AG1-298 BAT | 80/20 | 42.2 MW | 42.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966093 | AG1-478 BAT | 80/20 | 0.85 MW | 0.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966433 | AG1-512 BAT | 80/20 | 3.35 MW | 3.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966443 | AG1-513 BAT | 80/20 | 0.7 MW | 0.7 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966652 | AG1-535 BAT | 80/20 | 6.98 MW | 6.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274853 | TWINGROVE;U1 | 80/20 | 5.64 MW | 5.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274854 | TWINGROVE;U2 | 80/20 | 5.8 MW | 5.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274863 | CAYUGA RI;1U | 80/20 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274864 | CAYUGA RI;2U | 80/20 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274880 | RADFORD R;1U | 80/20 | 5.2 MW | 5.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 5.11 MW | 5.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276615 | W2-048 GEN | 80/20 | 7.12 MW | 7.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276621 | X2-022 GEN | 80/20 | 20.26 MW | 20.26 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290261 | S-027 E | 80/20 | 25.68 MW | 25.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290265 | S-028 E | 80/20 | 25.68 MW | 25.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293777 | CAYUG;1U E | 80/20 | 32.81 MW | 32.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293778 | CAYUG;2U E | 80/20 | 32.81 MW | 32.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293798 | W4-005 E | 80/20 | 34.79 MW | 34.79 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 917502 | Z2-087 E | 80/20 | 30.35 MW | 30.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924041 | AB2-047 C O1 | 80/20 | 5.67 MW | 5.67 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924042 | AB2-047 E O1 | 80/20 | 37.94 MW | 37.94 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924261 | AB2-070 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924262 | AB2-070 E O1 | 80/20 | 34.07 MW | 34.07 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925771 | AC1-053 C | 80/20 | 5.44 MW | 5.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925772 | AC1-053 E | 80/20 | 36.42 MW | 36.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 935141 | AD1-148 | 80/20 | 9.52 MW | 9.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 941731 | AE2-173 O1 | 80/20 | 21.8 MW | 21.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942111 | AE2-223 C | 80/20 | 6.8 MW | 6.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942112 | AE2-223 E | 80/20 | 45.52 MW | 45.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942601 | AE2-276 | 80/20 | 2.69 MW | 2.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.89 MW | 4.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944222 | AF1-090 E O1 | 80/20 | 22.91 MW | 22.91 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945391 | AF1-204 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945392 | AF1-204 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945871 | AF1-252 O1 | 80/20 | 10.85 MW | 10.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945881 | AF1-253 | 80/20 | 7.51 MW | 7.51 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959611 | AF2-252 C | 80/20 | 8.11 MW | 8.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959612 | AF2-252 E | 80/20 | 12.16 MW | 12.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960141 | AF2-305 | 80/20 | 1.99 MW | 1.99 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960261 | AF2-317 | 80/20 | 3.05 MW | 3.05 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960611 | AF2-352 C | 80/20 | 8.11 MW | 8.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960612 | AF2-352 E | 80/20 | 12.16 MW | 12.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963831 | AG1-236 C | 80/20 | 5.44 MW | 5.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963832 | AG1-236 E | 80/20 | 36.42 MW | 36.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965092 | AG1-374 E | 80/20 | 30.4 MW | 30.4 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965341 | AG1-399 C O1 | 80/20 | 14.41 MW | 14.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965342 | AG1-399 E O1 | 80/20 | 67.45 MW | 67.45 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965351 | AG1-400 O1 | 80/20 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965371 | AG1-402 O1 | 80/20 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965391 | AG1-404 O1 | 80/20 | 34.11 MW | 34.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965911 | AG1-460 C | 80/20 | 2.39 MW | 2.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965912 | AG1-460 E | 80/20 | 3.59 MW | 3.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957382 | AF2-032 E | 80/20 | 0.4 MW | 0.4 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276172 | Z1-108 BAT | 80/20 | 1.22 MW | 1.22 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 920273 | AA2-123 BAT | 80/20 | 1.11 MW | 1.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 943803 | AF1-048 BAT | 80/20 | 2.88 MW | 2.88 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944201 | AF1-088 FTIR | 80/20 | 53.82 MW | 53.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957141 | AF2-008 FTIR | 80/20 | 26.91 MW | 26.91 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957333 | AF2-027 BAT | 80/20 | 3.09 MW | 3.09 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957373 | AF2-031 BAT | 80/20 | 1.64 MW | 1.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957403 | AF2-034 BAT | 80/20 | 0.71 MW | 0.71 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958013 | AF2-095 BAT | 80/20 | 4.56 MW | 4.56 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958023 | AF2-096 BAT | 80/20 | 9.11 MW | 9.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959353 | AF2-226 BAT | 80/20 | 2.64 MW | 2.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960283 | AF2-319 BAT | 80/20 | 2.64 MW | 2.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960382 | AF2-329 BAT | 80/20 | 2.94 MW | 2.94 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960603 | AF2-351 BAT | 80/20 | 2.28 MW | 2.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 961503 | AF2-441 BAT | 80/20 | 17.02 MW | 17.02 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 964362 | AG1-298 BAT | 80/20 | 42.2 MW | 42.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966093 | AG1-478 BAT | 80/20 | 0.85 MW | 0.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966433 | AG1-512 BAT | 80/20 | 3.35 MW | 3.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966443 | AG1-513 BAT | 80/20 | 0.7 MW | 0.7 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966652 | AG1-535 BAT | 80/20 | 6.98 MW | 6.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 5.66 MW | 5.66 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 5.82 MW | 5.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274863 | CAYUGA RI;1U | 50/50 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274864 | CAYUGA RI;2U | 50/50 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 5.24 MW | 5.24 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 5.12 MW | 5.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 7.19 MW | 7.19 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 20.46 MW | 20.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 25.77 MW | 25.77 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 25.77 MW | 25.77 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293777 | CAYUG;1U E | 50/50 | 32.82 MW | 32.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293778 | CAYUG;2U E | 50/50 | 32.82 MW | 32.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 35.04 MW | 35.04 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 30.43 MW | 30.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 5.68 MW | 5.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 38.03 MW | 38.03 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 5.67 MW | 5.67 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 34.35 MW | 34.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 5.49 MW | 5.49 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 36.74 MW | 36.74 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.62 MW | 9.62 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 21.86 MW | 21.86 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 6.82 MW | 6.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 45.64 MW | 45.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942601 | AE2-276 | Adder | 2.71 MW | 2.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 4.96 MW | 4.96 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 23.22 MW | 23.22 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945391 | AF1-204 C O1 | Adder | 3.3 MW | 2.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945392 | AF1-204 E O1 | Adder | 9.91 MW | 8.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 10.99 MW | 10.99 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.61 MW | 7.61 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.13 MW | 8.13 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.2 MW | 12.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.01 MW | 2.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.08 MW | 3.08 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.13 MW | 8.13 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.2 MW | 12.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 5.49 MW | 5.49 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 36.74 MW | 36.74 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 30.5 MW | 30.5 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 1.6 MW | 1.6 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C O1 | 50/50 | 14.48 MW | 14.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E O1 | 50/50 | 67.78 MW | 67.78 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 O1 | 50/50 | 51.41 MW | 51.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 O1 | 50/50 | 51.41 MW | 51.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 O1 | 50/50 | 34.28 MW | 34.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.42 MW | 2.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.63 MW | 3.63 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 0.41 MW | 0.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944201 | AF1-088 FTIR | Adder | 63.82 MW | 54.25 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957141 | AF2-008 FTIR | Adder | 31.91 MW | 27.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.62 MW | 4.62 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 9.22 MW | 9.22 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.31 MW | 2.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 4.84 MW | 4.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990271 | J1263 | External Queue | 30.69 MW | 30.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990351 | J1289 C | External Queue | 2.43 MW | 2.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 15.53 MW | 15.53 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 29.24 MW | 29.24 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.2 MW | 2.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 11.92 MW | 11.92 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.43 MW | 7.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 40.17 MW | 40.17 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 | External Queue | 80.35 MW | 80.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 | External Queue | 24.0 MW | 24.0 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991276 | J1725 | External Queue | 9.28 MW | 9.28 MW |
| Details for LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 3.89 MW | 3.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 4.0 MW | 4.0 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 4.47 MW | 4.47 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 4.47 MW | 4.47 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 274880 | RADFORD R;1U | 80/20 | 3.62 MW | 3.62 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 3.51 MW | 3.51 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 276615 | W2-048 GEN | 80/20 | 4.99 MW | 4.99 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 276621 | X2-022 GEN | 80/20 | 14.21 MW | 14.21 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 17.72 MW | 17.72 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 17.72 MW | 17.72 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 293777 | CAYUG;1U E | 80/20 | 26.87 MW | 26.87 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 293778 | CAYUG;2U E | 80/20 | 26.87 MW | 26.87 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 293798 | W4-005 E | 80/20 | 24.23 MW | 24.23 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 20.82 MW | 20.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 3.89 MW | 3.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 26.03 MW | 26.03 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 924261 | AB2-070 C O1 | 80/20 | 3.92 MW | 3.92 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 924262 | AB2-070 E O1 | 80/20 | 23.77 MW | 23.77 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 925771 | AC1-053 C | 80/20 | 3.8 MW | 3.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 925772 | AC1-053 E | 80/20 | 25.45 MW | 25.45 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 935141 | AD1-148 | 80/20 | 6.68 MW | 6.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 14.96 MW | 14.96 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 4.67 MW | 4.67 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 31.24 MW | 31.24 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 944222 | AF1-090 E O1 | 80/20 | 16.26 MW | 16.26 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 7.69 MW | 7.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 | 80/20 | 5.33 MW | 5.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 5.59 MW | 5.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 8.39 MW | 8.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 960141 | AF2-305 | 80/20 | 1.39 MW | 1.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 960261 | AF2-317 | 80/20 | 2.14 MW | 2.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 5.59 MW | 5.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 8.39 MW | 8.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 963831 | AG1-236 C | 80/20 | 3.8 MW | 3.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 963832 | AG1-236 E | 80/20 | 25.45 MW | 25.45 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 965092 | AG1-374 E | 80/20 | 20.97 MW | 20.97 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 965331 | AG1-398 | 80/20 | 1.11 MW | 1.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 965341 | AG1-399 C O1 | 80/20 | 9.98 MW | 9.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 965342 | AG1-399 E O1 | 80/20 | 46.73 MW | 46.73 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 965351 | AG1-400 O1 | 80/20 | 35.45 MW | 35.45 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 965371 | AG1-402 O1 | 80/20 | 35.45 MW | 35.45 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 965391 | AG1-404 O1 | 80/20 | 23.63 MW | 23.63 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 965911 | AG1-460 C | 80/20 | 1.69 MW | 1.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 965912 | AG1-460 E | 80/20 | 2.54 MW | 2.54 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 957382 | AF2-032 E | 80/20 | 0.28 MW | 0.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 957373 | AF2-031 BAT | 80/20 | 1.23 MW | 1.23 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 958013 | AF2-095 BAT | 80/20 | 4.06 MW | 4.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 958023 | AF2-096 BAT | 80/20 | 8.46 MW | 8.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 960603 | AF2-351 BAT | 80/20 | 2.03 MW | 2.03 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 961503 | AF2-441 BAT | 80/20 | 12.76 MW | 12.76 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 964362 | AG1-298 BAT | 80/20 | 31.81 MW | 31.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 966093 | AG1-478 BAT | 80/20 | 0.55 MW | 0.55 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 966433 | AG1-512 BAT | 80/20 | 2.4 MW | 2.4 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 966652 | AG1-535 BAT | 80/20 | 5.28 MW | 5.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 990056 | J1201 | External Queue | 3.2 MW | 3.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 990351 | J1289 C | External Queue | 1.71 MW | 1.71 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 990856 | J1408 | External Queue | 10.46 MW | 10.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 955402 | J1022 E | External Queue | 19.43 MW | 19.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 955711 | J1055 C | External Queue | 1.55 MW | 1.55 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 955712 | J1055 E | External Queue | 8.36 MW | 8.36 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 956281 | J1115 C | External Queue | 4.98 MW | 4.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 956282 | J1115 E | External Queue | 26.93 MW | 26.93 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 991236 | J1676 | External Queue | 53.84 MW | 53.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 991261 | J1713 | External Queue | 15.96 MW | 15.96 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o Base Case | 991276 | J1725 | External Queue | 6.54 MW | 6.54 MW |
| Details for PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274853 | TWINGROVE;U1 | 80/20 | 5.66 MW | 5.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274854 | TWINGROVE;U2 | 80/20 | 5.82 MW | 5.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274880 | RADFORD R;1U | 80/20 | 5.22 MW | 5.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274889 | BRIGHTSTK;1U | 80/20 | 5.12 MW | 5.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276615 | W2-048 GEN | 80/20 | 7.15 MW | 7.15 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276621 | X2-022 GEN | 80/20 | 20.36 MW | 20.36 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290261 | S-027 E | 80/20 | 25.76 MW | 25.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290265 | S-028 E | 80/20 | 25.76 MW | 25.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293798 | W4-005 E | 80/20 | 34.93 MW | 34.93 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 917502 | Z2-087 E | 80/20 | 30.43 MW | 30.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924041 | AB2-047 C O1 | 80/20 | 5.68 MW | 5.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924042 | AB2-047 E O1 | 80/20 | 38.04 MW | 38.04 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924261 | AB2-070 C O1 | 80/20 | 5.65 MW | 5.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924262 | AB2-070 E O1 | 80/20 | 34.22 MW | 34.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925771 | AC1-053 C | 80/20 | 5.47 MW | 5.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925772 | AC1-053 E | 80/20 | 36.59 MW | 36.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 935141 | AD1-148 | 80/20 | 9.57 MW | 9.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 941731 | AE2-173 O1 | 80/20 | 21.86 MW | 21.86 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942111 | AE2-223 C | 80/20 | 6.82 MW | 6.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942112 | AE2-223 E | 80/20 | 45.64 MW | 45.64 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942601 | AE2-276 | 80/20 | 2.75 MW | 2.75 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944221 | AF1-090 C O1 | 80/20 | 4.93 MW | 4.93 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944222 | AF1-090 E O1 | 80/20 | 23.07 MW | 23.07 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945391 | AF1-204 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945392 | AF1-204 E O1 | 80/20 | 10.03 MW | 10.03 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945871 | AF1-252 O1 | 80/20 | 10.92 MW | 10.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945881 | AF1-253 | 80/20 | 7.56 MW | 7.56 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959611 | AF2-252 C | 80/20 | 8.13 MW | 8.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959612 | AF2-252 E | 80/20 | 12.2 MW | 12.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960141 | AF2-305 | 80/20 | 2.0 MW | 2.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960261 | AF2-317 | 80/20 | 3.06 MW | 3.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960611 | AF2-352 C | 80/20 | 8.13 MW | 8.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960612 | AF2-352 E | 80/20 | 12.2 MW | 12.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963831 | AG1-236 C | 80/20 | 5.47 MW | 5.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963832 | AG1-236 E | 80/20 | 36.59 MW | 36.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965092 | AG1-374 E | 80/20 | 30.49 MW | 30.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965341 | AG1-399 C O1 | 80/20 | 14.46 MW | 14.46 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965342 | AG1-399 E O1 | 80/20 | 67.68 MW | 67.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965351 | AG1-400 O1 | 80/20 | 51.34 MW | 51.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965371 | AG1-402 O1 | 80/20 | 51.34 MW | 51.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965391 | AG1-404 O1 | 80/20 | 34.22 MW | 34.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965911 | AG1-460 C | 80/20 | 2.4 MW | 2.4 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965912 | AG1-460 E | 80/20 | 3.61 MW | 3.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957382 | AF2-032 E | 80/20 | 0.41 MW | 0.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276172 | Z1-108 BAT | 80/20 | 1.2 MW | 1.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 920273 | AA2-123 BAT | 80/20 | 1.08 MW | 1.08 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 943803 | AF1-048 BAT | 80/20 | 2.82 MW | 2.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944201 | AF1-088 FTIR | 80/20 | 54.98 MW | 54.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957141 | AF2-008 FTIR | 80/20 | 27.49 MW | 27.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957333 | AF2-027 BAT | 80/20 | 3.03 MW | 3.03 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957373 | AF2-031 BAT | 80/20 | 1.61 MW | 1.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957403 | AF2-034 BAT | 80/20 | 0.7 MW | 0.7 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958013 | AF2-095 BAT | 80/20 | 4.52 MW | 4.52 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958023 | AF2-096 BAT | 80/20 | 9.02 MW | 9.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959353 | AF2-226 BAT | 80/20 | 2.58 MW | 2.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960283 | AF2-319 BAT | 80/20 | 2.58 MW | 2.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960382 | AF2-329 BAT | 80/20 | 2.89 MW | 2.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960603 | AF2-351 BAT | 80/20 | 2.26 MW | 2.26 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 961503 | AF2-441 BAT | 80/20 | 16.79 MW | 16.79 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 964362 | AG1-298 BAT | 80/20 | 41.62 MW | 41.62 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966093 | AG1-478 BAT | 80/20 | 0.84 MW | 0.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966433 | AG1-512 BAT | 80/20 | 3.3 MW | 3.3 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966443 | AG1-513 BAT | 80/20 | 0.68 MW | 0.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966652 | AG1-535 BAT | 80/20 | 6.88 MW | 6.88 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274853 | TWINGROVE;U1 | 80/20 | 5.66 MW | 5.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274854 | TWINGROVE;U2 | 80/20 | 5.82 MW | 5.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274880 | RADFORD R;1U | 80/20 | 5.22 MW | 5.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 5.12 MW | 5.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276615 | W2-048 GEN | 80/20 | 7.15 MW | 7.15 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276621 | X2-022 GEN | 80/20 | 20.36 MW | 20.36 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290261 | S-027 E | 80/20 | 25.76 MW | 25.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290265 | S-028 E | 80/20 | 25.76 MW | 25.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293798 | W4-005 E | 80/20 | 34.93 MW | 34.93 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 917502 | Z2-087 E | 80/20 | 30.43 MW | 30.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924041 | AB2-047 C O1 | 80/20 | 5.68 MW | 5.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924042 | AB2-047 E O1 | 80/20 | 38.04 MW | 38.04 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924261 | AB2-070 C O1 | 80/20 | 5.65 MW | 5.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924262 | AB2-070 E O1 | 80/20 | 34.22 MW | 34.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925771 | AC1-053 C | 80/20 | 5.47 MW | 5.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925772 | AC1-053 E | 80/20 | 36.59 MW | 36.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 935141 | AD1-148 | 80/20 | 9.57 MW | 9.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 941731 | AE2-173 O1 | 80/20 | 21.86 MW | 21.86 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942111 | AE2-223 C | 80/20 | 6.82 MW | 6.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942112 | AE2-223 E | 80/20 | 45.64 MW | 45.64 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942601 | AE2-276 | 80/20 | 2.75 MW | 2.75 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.93 MW | 4.93 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944222 | AF1-090 E O1 | 80/20 | 23.07 MW | 23.07 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945391 | AF1-204 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945392 | AF1-204 E O1 | 80/20 | 10.03 MW | 10.03 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945871 | AF1-252 O1 | 80/20 | 10.92 MW | 10.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945881 | AF1-253 | 80/20 | 7.56 MW | 7.56 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959611 | AF2-252 C | 80/20 | 8.13 MW | 8.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959612 | AF2-252 E | 80/20 | 12.2 MW | 12.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960141 | AF2-305 | 80/20 | 2.0 MW | 2.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960261 | AF2-317 | 80/20 | 3.06 MW | 3.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960611 | AF2-352 C | 80/20 | 8.13 MW | 8.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960612 | AF2-352 E | 80/20 | 12.2 MW | 12.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963831 | AG1-236 C | 80/20 | 5.47 MW | 5.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963832 | AG1-236 E | 80/20 | 36.59 MW | 36.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965092 | AG1-374 E | 80/20 | 30.49 MW | 30.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965341 | AG1-399 C O1 | 80/20 | 14.46 MW | 14.46 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965342 | AG1-399 E O1 | 80/20 | 67.68 MW | 67.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965351 | AG1-400 O1 | 80/20 | 51.34 MW | 51.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965371 | AG1-402 O1 | 80/20 | 51.34 MW | 51.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965391 | AG1-404 O1 | 80/20 | 34.22 MW | 34.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965911 | AG1-460 C | 80/20 | 2.4 MW | 2.4 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965912 | AG1-460 E | 80/20 | 3.61 MW | 3.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957382 | AF2-032 E | 80/20 | 0.41 MW | 0.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 964362 | AG1-298 BAT | 80/20 | 41.62 MW | 41.62 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966093 | AG1-478 BAT | 80/20 | 0.84 MW | 0.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966433 | AG1-512 BAT | 80/20 | 3.3 MW | 3.3 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966443 | AG1-513 BAT | 80/20 | 0.68 MW | 0.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966652 | AG1-535 BAT | 80/20 | 6.88 MW | 6.88 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276172 | Z1-108 BAT | 80/20 | 1.2 MW | 1.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 920273 | AA2-123 BAT | 80/20 | 1.08 MW | 1.08 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 943803 | AF1-048 BAT | 80/20 | 2.82 MW | 2.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944201 | AF1-088 FTIR | 80/20 | 54.98 MW | 54.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957141 | AF2-008 FTIR | 80/20 | 27.49 MW | 27.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957333 | AF2-027 BAT | 80/20 | 3.03 MW | 3.03 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957373 | AF2-031 BAT | 80/20 | 1.61 MW | 1.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957403 | AF2-034 BAT | 80/20 | 0.7 MW | 0.7 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958013 | AF2-095 BAT | 80/20 | 4.52 MW | 4.52 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958023 | AF2-096 BAT | 80/20 | 9.02 MW | 9.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959353 | AF2-226 BAT | 80/20 | 2.58 MW | 2.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960283 | AF2-319 BAT | 80/20 | 2.58 MW | 2.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960382 | AF2-329 BAT | 80/20 | 2.89 MW | 2.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960603 | AF2-351 BAT | 80/20 | 2.26 MW | 2.26 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 961503 | AF2-441 BAT | 80/20 | 16.79 MW | 16.79 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 5.68 MW | 5.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 5.84 MW | 5.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 5.26 MW | 5.26 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 5.14 MW | 5.14 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 7.22 MW | 7.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 20.56 MW | 20.56 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 25.84 MW | 25.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 25.84 MW | 25.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 35.18 MW | 35.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 30.51 MW | 30.51 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 5.7 MW | 5.7 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 38.14 MW | 38.14 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 5.7 MW | 5.7 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 34.5 MW | 34.5 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 5.51 MW | 5.51 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 36.91 MW | 36.91 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.66 MW | 9.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 21.92 MW | 21.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 6.84 MW | 6.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 45.77 MW | 45.77 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942601 | AE2-276 | Adder | 2.77 MW | 2.35 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 4.99 MW | 4.99 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 23.37 MW | 23.37 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945391 | AF1-204 C O1 | Adder | 3.36 MW | 2.86 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945392 | AF1-204 E O1 | Adder | 10.09 MW | 8.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 11.06 MW | 11.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.66 MW | 7.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.16 MW | 8.16 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.23 MW | 12.23 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.02 MW | 2.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.09 MW | 3.09 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.16 MW | 8.16 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.23 MW | 12.23 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 5.51 MW | 5.51 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 36.91 MW | 36.91 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 30.59 MW | 30.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 1.61 MW | 1.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C O1 | 50/50 | 14.53 MW | 14.53 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E O1 | 50/50 | 68.02 MW | 68.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 O1 | 50/50 | 51.59 MW | 51.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 O1 | 50/50 | 51.59 MW | 51.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 O1 | 50/50 | 34.39 MW | 34.39 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.44 MW | 2.44 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.65 MW | 3.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 0.41 MW | 0.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944201 | AF1-088 FTIR | Adder | 65.2 MW | 55.42 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957141 | AF2-008 FTIR | Adder | 32.6 MW | 27.71 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.58 MW | 4.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 9.13 MW | 9.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.29 MW | 2.29 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 4.84 MW | 4.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990271 | J1263 | External Queue | 30.69 MW | 30.69 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990351 | J1289 C | External Queue | 2.43 MW | 2.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 15.53 MW | 15.53 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 29.24 MW | 29.24 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.2 MW | 2.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 11.92 MW | 11.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.43 MW | 7.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 40.17 MW | 40.17 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 | External Queue | 80.35 MW | 80.35 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 | External Queue | 24.0 MW | 24.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991276 | J1725 | External Queue | 9.28 MW | 9.28 MW |
| Details for PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274853 | TWINGROVE;U1 | 80/20 | 5.16 MW | 5.16 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274854 | TWINGROVE;U2 | 80/20 | 5.3 MW | 5.3 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274863 | CAYUGA RI;1U | 80/20 | 4.12 MW | 4.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274864 | CAYUGA RI;2U | 80/20 | 4.12 MW | 4.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274880 | RADFORD R;1U | 80/20 | 4.71 MW | 4.71 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 4.69 MW | 4.69 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276615 | W2-048 GEN | 80/20 | 6.4 MW | 6.4 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276621 | X2-022 GEN | 80/20 | 18.23 MW | 18.23 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 290261 | S-027 E | 80/20 | 23.46 MW | 23.46 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 290265 | S-028 E | 80/20 | 23.46 MW | 23.46 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293777 | CAYUG;1U E | 80/20 | 24.77 MW | 24.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293778 | CAYUG;2U E | 80/20 | 24.77 MW | 24.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293798 | W4-005 E | 80/20 | 31.5 MW | 31.5 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 917502 | Z2-087 E | 80/20 | 27.86 MW | 27.86 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924041 | AB2-047 C O1 | 80/20 | 5.2 MW | 5.2 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924042 | AB2-047 E O1 | 80/20 | 34.83 MW | 34.83 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924261 | AB2-070 C O1 | 80/20 | 5.09 MW | 5.09 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924262 | AB2-070 E O1 | 80/20 | 30.81 MW | 30.81 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 925771 | AC1-053 C | 80/20 | 4.91 MW | 4.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 925772 | AC1-053 E | 80/20 | 32.88 MW | 32.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 935141 | AD1-148 | 80/20 | 8.57 MW | 8.57 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 937001 | AD2-134 C | Adder | -1.05 MW | -0.89 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 939401 | AE1-172 C O1 | 80/20 | 16.41 MW | 16.41 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 939402 | AE1-172 E O1 | 80/20 | 76.98 MW | 76.98 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 941731 | AE2-173 O1 | 80/20 | 20.02 MW | 20.02 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 942111 | AE2-223 C | 80/20 | 6.25 MW | 6.25 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 942112 | AE2-223 E | 80/20 | 41.8 MW | 41.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 944222 | AF1-090 E O1 | 80/20 | 20.38 MW | 20.38 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945391 | AF1-204 C O1 | 80/20 | 2.99 MW | 2.99 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945392 | AF1-204 E O1 | 80/20 | 8.96 MW | 8.96 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945871 | AF1-252 O1 | 80/20 | 9.65 MW | 9.65 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945881 | AF1-253 | 80/20 | 6.68 MW | 6.68 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959611 | AF2-252 C | 80/20 | 7.41 MW | 7.41 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959612 | AF2-252 E | 80/20 | 11.11 MW | 11.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960141 | AF2-305 | 80/20 | 1.8 MW | 1.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960261 | AF2-317 | 80/20 | 2.74 MW | 2.74 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960611 | AF2-352 C | 80/20 | 7.41 MW | 7.41 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960612 | AF2-352 E | 80/20 | 11.11 MW | 11.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 963831 | AG1-236 C | 80/20 | 4.91 MW | 4.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 963832 | AG1-236 E | 80/20 | 32.88 MW | 32.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965092 | AG1-374 E | 80/20 | 27.77 MW | 27.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965331 | AG1-398 | 80/20 | 1.43 MW | 1.43 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965341 | AG1-399 C O1 | 80/20 | 13.11 MW | 13.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965342 | AG1-399 E O1 | 80/20 | 61.37 MW | 61.37 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965351 | AG1-400 O1 | 80/20 | 46.55 MW | 46.55 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965371 | AG1-402 O1 | 80/20 | 46.55 MW | 46.55 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965391 | AG1-404 O1 | 80/20 | 31.03 MW | 31.03 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965911 | AG1-460 C | 80/20 | 2.13 MW | 2.13 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965912 | AG1-460 E | 80/20 | 3.2 MW | 3.2 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957382 | AF2-032 E | 80/20 | 0.36 MW | 0.36 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276172 | Z1-108 BAT | 80/20 | 1.53 MW | 1.53 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 920273 | AA2-123 BAT | 80/20 | 1.42 MW | 1.42 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 943803 | AF1-048 BAT | 80/20 | 3.68 MW | 3.68 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957333 | AF2-027 BAT | 80/20 | 3.8 MW | 3.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957373 | AF2-031 BAT | 80/20 | 1.37 MW | 1.37 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957403 | AF2-034 BAT | 80/20 | 0.88 MW | 0.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 958013 | AF2-095 BAT | 80/20 | 3.04 MW | 3.04 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 958023 | AF2-096 BAT | 80/20 | 5.64 MW | 5.64 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959353 | AF2-226 BAT | 80/20 | 3.15 MW | 3.15 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960283 | AF2-319 BAT | 80/20 | 3.15 MW | 3.15 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960382 | AF2-329 BAT | 80/20 | 3.35 MW | 3.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960603 | AF2-351 BAT | 80/20 | 1.52 MW | 1.52 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 961503 | AF2-441 BAT | 80/20 | 14.3 MW | 14.3 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 964362 | AG1-298 BAT | 80/20 | 35.23 MW | 35.23 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965063 | AG1-371 BAT | 80/20 | 4.54 MW | 4.54 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965083 | AG1-373 BAT | 80/20 | 1.51 MW | 1.51 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966093 | AG1-478 BAT | 80/20 | 0.82 MW | 0.82 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966433 | AG1-512 BAT | 80/20 | 2.94 MW | 2.94 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966443 | AG1-513 BAT | 80/20 | 0.88 MW | 0.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966652 | AG1-535 BAT | 80/20 | 5.8 MW | 5.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990056 | J1201 | External Queue | 4.53 MW | 4.53 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990271 | J1263 | External Queue | 30.31 MW | 30.31 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990351 | J1289 C | External Queue | 1.94 MW | 1.94 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990856 | J1408 | External Queue | 14.12 MW | 14.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955402 | J1022 E | External Queue | 27.43 MW | 27.43 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955711 | J1055 C | External Queue | 1.73 MW | 1.73 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955712 | J1055 E | External Queue | 9.35 MW | 9.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 956281 | J1115 C | External Queue | 6.91 MW | 6.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 956282 | J1115 E | External Queue | 37.36 MW | 37.36 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991236 | J1676 | External Queue | 74.89 MW | 74.89 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991261 | J1713 | External Queue | 22.4 MW | 22.4 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991276 | J1725 | External Queue | 7.14 MW | 7.14 MW |
| Details for PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274853 | TWINGROVE;U1 | 80/20 | 5.16 MW | 5.16 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274854 | TWINGROVE;U2 | 80/20 | 5.3 MW | 5.3 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274863 | CAYUGA RI;1U | 80/20 | 4.12 MW | 4.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274864 | CAYUGA RI;2U | 80/20 | 4.12 MW | 4.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274880 | RADFORD R;1U | 80/20 | 4.71 MW | 4.71 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274889 | BRIGHTSTK;1U | 80/20 | 4.69 MW | 4.69 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276615 | W2-048 GEN | 80/20 | 6.4 MW | 6.4 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276621 | X2-022 GEN | 80/20 | 18.23 MW | 18.23 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 290261 | S-027 E | 80/20 | 23.46 MW | 23.46 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 290265 | S-028 E | 80/20 | 23.46 MW | 23.46 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293777 | CAYUG;1U E | 80/20 | 24.77 MW | 24.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293778 | CAYUG;2U E | 80/20 | 24.77 MW | 24.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293798 | W4-005 E | 80/20 | 31.5 MW | 31.5 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 917502 | Z2-087 E | 80/20 | 27.86 MW | 27.86 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924041 | AB2-047 C O1 | 80/20 | 5.2 MW | 5.2 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924042 | AB2-047 E O1 | 80/20 | 34.83 MW | 34.83 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924261 | AB2-070 C O1 | 80/20 | 5.09 MW | 5.09 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924262 | AB2-070 E O1 | 80/20 | 30.81 MW | 30.81 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 925771 | AC1-053 C | 80/20 | 4.91 MW | 4.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 925772 | AC1-053 E | 80/20 | 32.88 MW | 32.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 935141 | AD1-148 | 80/20 | 8.57 MW | 8.57 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 937001 | AD2-134 C | Adder | -1.05 MW | -0.89 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 941731 | AE2-173 O1 | 80/20 | 20.02 MW | 20.02 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 942111 | AE2-223 C | 80/20 | 6.25 MW | 6.25 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 942112 | AE2-223 E | 80/20 | 41.8 MW | 41.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 944221 | AF1-090 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 944222 | AF1-090 E O1 | 80/20 | 20.38 MW | 20.38 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945391 | AF1-204 C O1 | 80/20 | 2.99 MW | 2.99 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945392 | AF1-204 E O1 | 80/20 | 8.96 MW | 8.96 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945871 | AF1-252 O1 | 80/20 | 9.65 MW | 9.65 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945881 | AF1-253 | 80/20 | 6.68 MW | 6.68 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959611 | AF2-252 C | 80/20 | 7.41 MW | 7.41 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959612 | AF2-252 E | 80/20 | 11.11 MW | 11.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960141 | AF2-305 | 80/20 | 1.8 MW | 1.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960261 | AF2-317 | 80/20 | 2.74 MW | 2.74 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960611 | AF2-352 C | 80/20 | 7.41 MW | 7.41 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960612 | AF2-352 E | 80/20 | 11.11 MW | 11.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 963831 | AG1-236 C | 80/20 | 4.91 MW | 4.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 963832 | AG1-236 E | 80/20 | 32.88 MW | 32.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965092 | AG1-374 E | 80/20 | 27.77 MW | 27.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965331 | AG1-398 | 80/20 | 1.43 MW | 1.43 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965341 | AG1-399 C O1 | 80/20 | 13.11 MW | 13.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965342 | AG1-399 E O1 | 80/20 | 61.37 MW | 61.37 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965351 | AG1-400 O1 | 80/20 | 46.55 MW | 46.55 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965371 | AG1-402 O1 | 80/20 | 46.55 MW | 46.55 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965391 | AG1-404 O1 | 80/20 | 31.03 MW | 31.03 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965911 | AG1-460 C | 80/20 | 2.13 MW | 2.13 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965912 | AG1-460 E | 80/20 | 3.2 MW | 3.2 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957382 | AF2-032 E | 80/20 | 0.36 MW | 0.36 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276172 | Z1-108 BAT | 80/20 | 1.53 MW | 1.53 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 920273 | AA2-123 BAT | 80/20 | 1.42 MW | 1.42 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 943803 | AF1-048 BAT | 80/20 | 3.68 MW | 3.68 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957333 | AF2-027 BAT | 80/20 | 3.8 MW | 3.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957373 | AF2-031 BAT | 80/20 | 1.37 MW | 1.37 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957403 | AF2-034 BAT | 80/20 | 0.88 MW | 0.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 958013 | AF2-095 BAT | 80/20 | 3.04 MW | 3.04 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 958023 | AF2-096 BAT | 80/20 | 5.64 MW | 5.64 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959353 | AF2-226 BAT | 80/20 | 3.15 MW | 3.15 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960283 | AF2-319 BAT | 80/20 | 3.15 MW | 3.15 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960382 | AF2-329 BAT | 80/20 | 3.35 MW | 3.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960603 | AF2-351 BAT | 80/20 | 1.52 MW | 1.52 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 961503 | AF2-441 BAT | 80/20 | 14.3 MW | 14.3 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 964362 | AG1-298 BAT | 80/20 | 35.23 MW | 35.23 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965063 | AG1-371 BAT | 80/20 | 4.54 MW | 4.54 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965083 | AG1-373 BAT | 80/20 | 1.51 MW | 1.51 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966093 | AG1-478 BAT | 80/20 | 0.82 MW | 0.82 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966433 | AG1-512 BAT | 80/20 | 2.94 MW | 2.94 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966443 | AG1-513 BAT | 80/20 | 0.88 MW | 0.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966652 | AG1-535 BAT | 80/20 | 5.8 MW | 5.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990056 | J1201 | External Queue | 4.53 MW | 4.53 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990271 | J1263 | External Queue | 30.31 MW | 30.31 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990351 | J1289 C | External Queue | 1.94 MW | 1.94 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990856 | J1408 | External Queue | 14.12 MW | 14.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955402 | J1022 E | External Queue | 27.43 MW | 27.43 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955711 | J1055 C | External Queue | 1.73 MW | 1.73 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955712 | J1055 E | External Queue | 9.35 MW | 9.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 956281 | J1115 C | External Queue | 6.91 MW | 6.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 956282 | J1115 E | External Queue | 37.36 MW | 37.36 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991236 | J1676 | External Queue | 74.89 MW | 74.89 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991261 | J1713 | External Queue | 22.4 MW | 22.4 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991276 | J1725 | External Queue | 7.14 MW | 7.14 MW |
| Details for AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274853 | TWINGROVE;U1 | 80/20 | 5.16 MW | 5.16 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274854 | TWINGROVE;U2 | 80/20 | 5.3 MW | 5.3 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274863 | CAYUGA RI;1U | 80/20 | 4.12 MW | 4.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274864 | CAYUGA RI;2U | 80/20 | 4.12 MW | 4.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274880 | RADFORD R;1U | 80/20 | 4.71 MW | 4.71 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 4.69 MW | 4.69 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276615 | W2-048 GEN | 80/20 | 6.4 MW | 6.4 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276621 | X2-022 GEN | 80/20 | 18.23 MW | 18.23 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 290261 | S-027 E | 80/20 | 23.46 MW | 23.46 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 290265 | S-028 E | 80/20 | 23.46 MW | 23.46 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293777 | CAYUG;1U E | 80/20 | 24.77 MW | 24.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293778 | CAYUG;2U E | 80/20 | 24.77 MW | 24.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293798 | W4-005 E | 80/20 | 31.5 MW | 31.5 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 917502 | Z2-087 E | 80/20 | 27.86 MW | 27.86 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924041 | AB2-047 C O1 | 80/20 | 5.2 MW | 5.2 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924042 | AB2-047 E O1 | 80/20 | 34.83 MW | 34.83 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924261 | AB2-070 C O1 | 80/20 | 5.09 MW | 5.09 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924262 | AB2-070 E O1 | 80/20 | 30.81 MW | 30.81 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 925771 | AC1-053 C | 80/20 | 4.91 MW | 4.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 925772 | AC1-053 E | 80/20 | 32.88 MW | 32.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 935141 | AD1-148 | 80/20 | 8.57 MW | 8.57 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 937001 | AD2-134 C | Adder | -1.05 MW | -0.89 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 939401 | AE1-172 C O1 | 80/20 | 16.41 MW | 16.41 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 939402 | AE1-172 E O1 | 80/20 | 76.98 MW | 76.98 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 941731 | AE2-173 O1 | 80/20 | 20.02 MW | 20.02 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 942111 | AE2-223 C | 80/20 | 6.25 MW | 6.25 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 942112 | AE2-223 E | 80/20 | 41.8 MW | 41.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 944222 | AF1-090 E O1 | 80/20 | 20.38 MW | 20.38 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945391 | AF1-204 C O1 | 80/20 | 2.99 MW | 2.99 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945392 | AF1-204 E O1 | 80/20 | 8.96 MW | 8.96 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945871 | AF1-252 O1 | 80/20 | 9.65 MW | 9.65 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945881 | AF1-253 | 80/20 | 6.68 MW | 6.68 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959611 | AF2-252 C | 80/20 | 7.41 MW | 7.41 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959612 | AF2-252 E | 80/20 | 11.11 MW | 11.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960141 | AF2-305 | 80/20 | 1.8 MW | 1.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960261 | AF2-317 | 80/20 | 2.74 MW | 2.74 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960611 | AF2-352 C | 80/20 | 7.41 MW | 7.41 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960612 | AF2-352 E | 80/20 | 11.11 MW | 11.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 963831 | AG1-236 C | 80/20 | 4.91 MW | 4.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 963832 | AG1-236 E | 80/20 | 32.88 MW | 32.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965092 | AG1-374 E | 80/20 | 27.77 MW | 27.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965331 | AG1-398 | 80/20 | 1.43 MW | 1.43 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965341 | AG1-399 C O1 | 80/20 | 13.11 MW | 13.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965342 | AG1-399 E O1 | 80/20 | 61.37 MW | 61.37 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965351 | AG1-400 O1 | 80/20 | 46.55 MW | 46.55 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965371 | AG1-402 O1 | 80/20 | 46.55 MW | 46.55 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965391 | AG1-404 O1 | 80/20 | 31.03 MW | 31.03 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965911 | AG1-460 C | 80/20 | 2.13 MW | 2.13 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965912 | AG1-460 E | 80/20 | 3.2 MW | 3.2 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957382 | AF2-032 E | 80/20 | 0.36 MW | 0.36 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276172 | Z1-108 BAT | 80/20 | 1.53 MW | 1.53 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 920273 | AA2-123 BAT | 80/20 | 1.42 MW | 1.42 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 943803 | AF1-048 BAT | 80/20 | 3.68 MW | 3.68 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957333 | AF2-027 BAT | 80/20 | 3.8 MW | 3.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957373 | AF2-031 BAT | 80/20 | 1.37 MW | 1.37 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957403 | AF2-034 BAT | 80/20 | 0.88 MW | 0.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 958013 | AF2-095 BAT | 80/20 | 3.04 MW | 3.04 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 958023 | AF2-096 BAT | 80/20 | 5.64 MW | 5.64 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959353 | AF2-226 BAT | 80/20 | 3.15 MW | 3.15 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960283 | AF2-319 BAT | 80/20 | 3.15 MW | 3.15 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960382 | AF2-329 BAT | 80/20 | 3.35 MW | 3.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960603 | AF2-351 BAT | 80/20 | 1.52 MW | 1.52 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 961503 | AF2-441 BAT | 80/20 | 14.3 MW | 14.3 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 964362 | AG1-298 BAT | 80/20 | 35.23 MW | 35.23 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965063 | AG1-371 BAT | 80/20 | 4.54 MW | 4.54 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965083 | AG1-373 BAT | 80/20 | 1.51 MW | 1.51 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966093 | AG1-478 BAT | 80/20 | 0.82 MW | 0.82 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966433 | AG1-512 BAT | 80/20 | 2.94 MW | 2.94 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966443 | AG1-513 BAT | 80/20 | 0.88 MW | 0.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966652 | AG1-535 BAT | 80/20 | 5.8 MW | 5.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990056 | J1201 | External Queue | 4.53 MW | 4.53 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990271 | J1263 | External Queue | 30.31 MW | 30.31 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990351 | J1289 C | External Queue | 1.94 MW | 1.94 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990856 | J1408 | External Queue | 14.12 MW | 14.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955402 | J1022 E | External Queue | 27.43 MW | 27.43 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955711 | J1055 C | External Queue | 1.73 MW | 1.73 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955712 | J1055 E | External Queue | 9.35 MW | 9.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 956281 | J1115 C | External Queue | 6.91 MW | 6.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 956282 | J1115 E | External Queue | 37.36 MW | 37.36 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991236 | J1676 | External Queue | 74.89 MW | 74.89 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991261 | J1713 | External Queue | 22.4 MW | 22.4 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991276 | J1725 | External Queue | 7.14 MW | 7.14 MW |
| Details for AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274853 | TWINGROVE;U1 | 80/20 | 5.16 MW | 5.16 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274854 | TWINGROVE;U2 | 80/20 | 5.3 MW | 5.3 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274863 | CAYUGA RI;1U | 80/20 | 4.12 MW | 4.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274864 | CAYUGA RI;2U | 80/20 | 4.12 MW | 4.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274880 | RADFORD R;1U | 80/20 | 4.71 MW | 4.71 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274889 | BRIGHTSTK;1U | 80/20 | 4.69 MW | 4.69 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276615 | W2-048 GEN | 80/20 | 6.4 MW | 6.4 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276621 | X2-022 GEN | 80/20 | 18.23 MW | 18.23 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 290261 | S-027 E | 80/20 | 23.46 MW | 23.46 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 290265 | S-028 E | 80/20 | 23.46 MW | 23.46 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293777 | CAYUG;1U E | 80/20 | 24.77 MW | 24.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293778 | CAYUG;2U E | 80/20 | 24.77 MW | 24.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293798 | W4-005 E | 80/20 | 31.5 MW | 31.5 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 917502 | Z2-087 E | 80/20 | 27.86 MW | 27.86 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924041 | AB2-047 C O1 | 80/20 | 5.2 MW | 5.2 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924042 | AB2-047 E O1 | 80/20 | 34.83 MW | 34.83 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924261 | AB2-070 C O1 | 80/20 | 5.09 MW | 5.09 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924262 | AB2-070 E O1 | 80/20 | 30.81 MW | 30.81 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 925771 | AC1-053 C | 80/20 | 4.91 MW | 4.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 925772 | AC1-053 E | 80/20 | 32.88 MW | 32.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 935141 | AD1-148 | 80/20 | 8.57 MW | 8.57 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 937001 | AD2-134 C | Adder | -1.05 MW | -0.89 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 941731 | AE2-173 O1 | 80/20 | 20.02 MW | 20.02 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 942111 | AE2-223 C | 80/20 | 6.25 MW | 6.25 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 942112 | AE2-223 E | 80/20 | 41.8 MW | 41.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 944221 | AF1-090 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 944222 | AF1-090 E O1 | 80/20 | 20.38 MW | 20.38 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945391 | AF1-204 C O1 | 80/20 | 2.99 MW | 2.99 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945392 | AF1-204 E O1 | 80/20 | 8.96 MW | 8.96 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945871 | AF1-252 O1 | 80/20 | 9.65 MW | 9.65 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945881 | AF1-253 | 80/20 | 6.68 MW | 6.68 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959611 | AF2-252 C | 80/20 | 7.41 MW | 7.41 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959612 | AF2-252 E | 80/20 | 11.11 MW | 11.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960141 | AF2-305 | 80/20 | 1.8 MW | 1.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960261 | AF2-317 | 80/20 | 2.74 MW | 2.74 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960611 | AF2-352 C | 80/20 | 7.41 MW | 7.41 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960612 | AF2-352 E | 80/20 | 11.11 MW | 11.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 963831 | AG1-236 C | 80/20 | 4.91 MW | 4.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 963832 | AG1-236 E | 80/20 | 32.88 MW | 32.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965092 | AG1-374 E | 80/20 | 27.77 MW | 27.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965331 | AG1-398 | 80/20 | 1.43 MW | 1.43 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965341 | AG1-399 C O1 | 80/20 | 13.11 MW | 13.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965342 | AG1-399 E O1 | 80/20 | 61.37 MW | 61.37 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965351 | AG1-400 O1 | 80/20 | 46.55 MW | 46.55 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965371 | AG1-402 O1 | 80/20 | 46.55 MW | 46.55 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965391 | AG1-404 O1 | 80/20 | 31.03 MW | 31.03 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965911 | AG1-460 C | 80/20 | 2.13 MW | 2.13 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965912 | AG1-460 E | 80/20 | 3.2 MW | 3.2 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957382 | AF2-032 E | 80/20 | 0.36 MW | 0.36 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276172 | Z1-108 BAT | 80/20 | 1.53 MW | 1.53 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 920273 | AA2-123 BAT | 80/20 | 1.42 MW | 1.42 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 943803 | AF1-048 BAT | 80/20 | 3.68 MW | 3.68 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957333 | AF2-027 BAT | 80/20 | 3.8 MW | 3.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957373 | AF2-031 BAT | 80/20 | 1.37 MW | 1.37 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957403 | AF2-034 BAT | 80/20 | 0.88 MW | 0.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 958013 | AF2-095 BAT | 80/20 | 3.04 MW | 3.04 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 958023 | AF2-096 BAT | 80/20 | 5.64 MW | 5.64 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959353 | AF2-226 BAT | 80/20 | 3.15 MW | 3.15 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960283 | AF2-319 BAT | 80/20 | 3.15 MW | 3.15 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960382 | AF2-329 BAT | 80/20 | 3.35 MW | 3.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960603 | AF2-351 BAT | 80/20 | 1.52 MW | 1.52 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 961503 | AF2-441 BAT | 80/20 | 14.3 MW | 14.3 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 964362 | AG1-298 BAT | 80/20 | 35.23 MW | 35.23 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965063 | AG1-371 BAT | 80/20 | 4.54 MW | 4.54 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965083 | AG1-373 BAT | 80/20 | 1.51 MW | 1.51 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966093 | AG1-478 BAT | 80/20 | 0.82 MW | 0.82 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966433 | AG1-512 BAT | 80/20 | 2.94 MW | 2.94 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966443 | AG1-513 BAT | 80/20 | 0.88 MW | 0.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966652 | AG1-535 BAT | 80/20 | 5.8 MW | 5.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990056 | J1201 | External Queue | 4.53 MW | 4.53 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990271 | J1263 | External Queue | 30.31 MW | 30.31 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990351 | J1289 C | External Queue | 1.94 MW | 1.94 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990856 | J1408 | External Queue | 14.12 MW | 14.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955402 | J1022 E | External Queue | 27.43 MW | 27.43 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955711 | J1055 C | External Queue | 1.73 MW | 1.73 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955712 | J1055 E | External Queue | 9.35 MW | 9.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 956281 | J1115 C | External Queue | 6.91 MW | 6.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 956282 | J1115 E | External Queue | 37.36 MW | 37.36 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991236 | J1676 | External Queue | 74.89 MW | 74.89 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991261 | J1713 | External Queue | 22.4 MW | 22.4 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991276 | J1725 | External Queue | 7.14 MW | 7.14 MW |
| Details for MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 274853 | TWINGROVE;U1 | 80/20 | 3.08 MW | 3.08 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 274854 | TWINGROVE;U2 | 80/20 | 3.16 MW | 3.16 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 274880 | RADFORD R;1U | 80/20 | 4.03 MW | 4.03 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 274889 | BRIGHTSTK;1U | 80/20 | 6.83 MW | 6.83 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 276615 | W2-048 GEN | 80/20 | 7.73 MW | 7.73 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 276621 | X2-022 GEN | 80/20 | 22.0 MW | 22.0 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 290261 | S-027 E | 80/20 | 14.0 MW | 14.0 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 290265 | S-028 E | 80/20 | 14.0 MW | 14.0 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 293798 | W4-005 E | 80/20 | 26.98 MW | 26.98 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 917502 | Z2-087 E | 80/20 | 40.58 MW | 40.58 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 924041 | AB2-047 C O1 | 80/20 | 7.58 MW | 7.58 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 924042 | AB2-047 E O1 | 80/20 | 50.72 MW | 50.72 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 924261 | AB2-070 C O1 | 80/20 | 6.45 MW | 6.45 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 924262 | AB2-070 E O1 | 80/20 | 39.05 MW | 39.05 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 925771 | AC1-053 C | 80/20 | 6.14 MW | 6.14 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 925772 | AC1-053 E | 80/20 | 41.09 MW | 41.09 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 935141 | AD1-148 | 80/20 | 10.34 MW | 10.34 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 937001 | AD2-134 C | Adder | -0.96 MW | -0.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 941731 | AE2-173 O1 | 80/20 | 29.15 MW | 29.15 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 942111 | AE2-223 C | 80/20 | 9.1 MW | 9.1 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 942112 | AE2-223 E | 80/20 | 60.86 MW | 60.86 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 942601 | AE2-276 | 80/20 | 2.79 MW | 2.79 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 944221 | AF1-090 C O1 | 80/20 | 4.74 MW | 4.74 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 944222 | AF1-090 E O1 | 80/20 | 22.18 MW | 22.18 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945391 | AF1-204 C O1 | 80/20 | 3.48 MW | 3.48 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945392 | AF1-204 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945871 | AF1-252 O1 | 80/20 | 10.5 MW | 10.5 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945881 | AF1-253 | 80/20 | 7.27 MW | 7.27 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 959611 | AF2-252 C | 80/20 | 4.42 MW | 4.42 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 959612 | AF2-252 E | 80/20 | 6.63 MW | 6.63 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960141 | AF2-305 | 80/20 | 2.28 MW | 2.28 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960261 | AF2-317 | 80/20 | 3.31 MW | 3.31 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960611 | AF2-352 C | 80/20 | 4.42 MW | 4.42 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960612 | AF2-352 E | 80/20 | 6.63 MW | 6.63 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 963831 | AG1-236 C | 80/20 | 6.14 MW | 6.14 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 963832 | AG1-236 E | 80/20 | 41.09 MW | 41.09 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965092 | AG1-374 E | 80/20 | 16.57 MW | 16.57 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965331 | AG1-398 | 80/20 | 1.82 MW | 1.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965341 | AG1-399 C O1 | 80/20 | 9.34 MW | 9.34 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965342 | AG1-399 E O1 | 80/20 | 43.71 MW | 43.71 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965351 | AG1-400 O1 | 80/20 | 33.15 MW | 33.15 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965371 | AG1-402 O1 | 80/20 | 33.15 MW | 33.15 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965391 | AG1-404 O1 | 80/20 | 22.1 MW | 22.1 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965911 | AG1-460 C | 80/20 | 2.3 MW | 2.3 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965912 | AG1-460 E | 80/20 | 3.45 MW | 3.45 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957382 | AF2-032 E | 80/20 | 0.39 MW | 0.39 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 276172 | Z1-108 BAT | 80/20 | 1.43 MW | 1.43 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 920273 | AA2-123 BAT | 80/20 | 1.31 MW | 1.31 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 943803 | AF1-048 BAT | 80/20 | 3.41 MW | 3.41 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 944201 | AF1-088 FTIR | 80/20 | 55.8 MW | 55.8 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957141 | AF2-008 FTIR | 80/20 | 27.9 MW | 27.9 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957333 | AF2-027 BAT | 80/20 | 3.59 MW | 3.59 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957373 | AF2-031 BAT | 80/20 | 1.58 MW | 1.58 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957403 | AF2-034 BAT | 80/20 | 0.83 MW | 0.83 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 958013 | AF2-095 BAT | 80/20 | 4.03 MW | 4.03 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 958023 | AF2-096 BAT | 80/20 | 7.82 MW | 7.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 959353 | AF2-226 BAT | 80/20 | 2.99 MW | 2.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960283 | AF2-319 BAT | 80/20 | 2.99 MW | 2.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960382 | AF2-329 BAT | 80/20 | 3.28 MW | 3.28 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960603 | AF2-351 BAT | 80/20 | 2.01 MW | 2.01 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 961503 | AF2-441 BAT | 80/20 | 16.45 MW | 16.45 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 964362 | AG1-298 BAT | 80/20 | 40.67 MW | 40.67 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965063 | AG1-371 BAT | 80/20 | 4.14 MW | 4.14 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965083 | AG1-373 BAT | 80/20 | 1.38 MW | 1.38 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966093 | AG1-478 BAT | 80/20 | 0.88 MW | 0.88 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966433 | AG1-512 BAT | 80/20 | 3.3 MW | 3.3 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966443 | AG1-513 BAT | 80/20 | 0.82 MW | 0.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966652 | AG1-535 BAT | 80/20 | 6.71 MW | 6.71 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990056 | J1201 | External Queue | 4.75 MW | 4.75 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990271 | J1263 | External Queue | 32.23 MW | 32.23 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990351 | J1289 C | External Queue | 2.13 MW | 2.13 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990856 | J1408 | External Queue | 14.85 MW | 14.85 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 955402 | J1022 E | External Queue | 34.21 MW | 34.21 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 955711 | J1055 C | External Queue | 1.99 MW | 1.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 955712 | J1055 E | External Queue | 10.78 MW | 10.78 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 956281 | J1115 C | External Queue | 6.82 MW | 6.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 956282 | J1115 E | External Queue | 36.91 MW | 36.91 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 991236 | J1676 | External Queue | 94.19 MW | 94.19 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 991261 | J1713 | External Queue | 23.71 MW | 23.71 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 991276 | J1725 | External Queue | 8.35 MW | 8.35 MW |
| Details for MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 274880 | RADFORD R;1U | 80/20 | 4.05 MW | 4.05 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 6.84 MW | 6.84 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 276615 | W2-048 GEN | 80/20 | 7.76 MW | 7.76 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 276621 | X2-022 GEN | 80/20 | 22.07 MW | 22.07 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 293798 | W4-005 E | 80/20 | 27.09 MW | 27.09 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 917502 | Z2-087 E | 80/20 | 40.64 MW | 40.64 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 924041 | AB2-047 C O1 | 80/20 | 7.59 MW | 7.59 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 924042 | AB2-047 E O1 | 80/20 | 50.8 MW | 50.8 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 924261 | AB2-070 C O1 | 80/20 | 6.47 MW | 6.47 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 924262 | AB2-070 E O1 | 80/20 | 39.17 MW | 39.17 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 925771 | AC1-053 C | 80/20 | 6.16 MW | 6.16 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 925772 | AC1-053 E | 80/20 | 41.22 MW | 41.22 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 935141 | AD1-148 | 80/20 | 10.38 MW | 10.38 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 937001 | AD2-134 C | Adder | -0.94 MW | -0.8 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 941731 | AE2-173 O1 | 80/20 | 29.2 MW | 29.2 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 942111 | AE2-223 C | 80/20 | 9.11 MW | 9.11 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 942112 | AE2-223 E | 80/20 | 60.96 MW | 60.96 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 942601 | AE2-276 | 80/20 | 2.84 MW | 2.84 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.76 MW | 4.76 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 944222 | AF1-090 E O1 | 80/20 | 22.3 MW | 22.3 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 945391 | AF1-204 C O1 | 80/20 | 3.53 MW | 3.53 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 945392 | AF1-204 E O1 | 80/20 | 10.58 MW | 10.58 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 945871 | AF1-252 O1 | 80/20 | 10.56 MW | 10.56 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 945881 | AF1-253 | 80/20 | 7.31 MW | 7.31 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960141 | AF2-305 | 80/20 | 2.29 MW | 2.29 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960261 | AF2-317 | 80/20 | 3.32 MW | 3.32 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 963831 | AG1-236 C | 80/20 | 6.16 MW | 6.16 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 963832 | AG1-236 E | 80/20 | 41.22 MW | 41.22 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965331 | AG1-398 | 80/20 | 1.82 MW | 1.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965341 | AG1-399 C O1 | 80/20 | 9.38 MW | 9.38 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965342 | AG1-399 E O1 | 80/20 | 43.9 MW | 43.9 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965351 | AG1-400 O1 | 80/20 | 33.29 MW | 33.29 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965371 | AG1-402 O1 | 80/20 | 33.29 MW | 33.29 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965391 | AG1-404 O1 | 80/20 | 22.2 MW | 22.2 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965911 | AG1-460 C | 80/20 | 2.31 MW | 2.31 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965912 | AG1-460 E | 80/20 | 3.47 MW | 3.47 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 957382 | AF2-032 E | 80/20 | 0.39 MW | 0.39 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 276172 | Z1-108 BAT | 80/20 | 1.41 MW | 1.41 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 920273 | AA2-123 BAT | 80/20 | 1.29 MW | 1.29 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 943803 | AF1-048 BAT | 80/20 | 3.36 MW | 3.36 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 944201 | AF1-088 FTIR | 80/20 | 56.76 MW | 56.76 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 957141 | AF2-008 FTIR | 80/20 | 28.38 MW | 28.38 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 957333 | AF2-027 BAT | 80/20 | 3.54 MW | 3.54 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 957373 | AF2-031 BAT | 80/20 | 1.56 MW | 1.56 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 957403 | AF2-034 BAT | 80/20 | 0.82 MW | 0.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 958013 | AF2-095 BAT | 80/20 | 3.99 MW | 3.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 958023 | AF2-096 BAT | 80/20 | 7.75 MW | 7.75 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 959353 | AF2-226 BAT | 80/20 | 2.94 MW | 2.94 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 959613 | AF2-252 BAT | 80/20 | 15.68 MW | 15.68 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960283 | AF2-319 BAT | 80/20 | 2.94 MW | 2.94 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960382 | AF2-329 BAT | 80/20 | 3.24 MW | 3.24 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960603 | AF2-351 BAT | 80/20 | 1.99 MW | 1.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960613 | AF2-352 BAT | 80/20 | 15.68 MW | 15.68 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 961503 | AF2-441 BAT | 80/20 | 16.26 MW | 16.26 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 964362 | AG1-298 BAT | 80/20 | 40.2 MW | 40.2 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965063 | AG1-371 BAT | 80/20 | 4.07 MW | 4.07 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965083 | AG1-373 BAT | 80/20 | 1.36 MW | 1.36 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 966093 | AG1-478 BAT | 80/20 | 0.87 MW | 0.87 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 966433 | AG1-512 BAT | 80/20 | 3.26 MW | 3.26 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 966443 | AG1-513 BAT | 80/20 | 0.81 MW | 0.81 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 966652 | AG1-535 BAT | 80/20 | 6.63 MW | 6.63 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 990056 | J1201 | External Queue | 4.75 MW | 4.75 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 990271 | J1263 | External Queue | 32.23 MW | 32.23 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 990351 | J1289 C | External Queue | 2.13 MW | 2.13 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 990856 | J1408 | External Queue | 14.85 MW | 14.85 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 955402 | J1022 E | External Queue | 34.21 MW | 34.21 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 955711 | J1055 C | External Queue | 1.99 MW | 1.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 955712 | J1055 E | External Queue | 10.78 MW | 10.78 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 956281 | J1115 C | External Queue | 6.82 MW | 6.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 956282 | J1115 E | External Queue | 36.91 MW | 36.91 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 991236 | J1676 | External Queue | 94.19 MW | 94.19 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 991261 | J1713 | External Queue | 23.71 MW | 23.71 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 991276 | J1725 | External Queue | 8.35 MW | 8.35 MW |
| Details for 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 274853 | TWINGROVE;U1 | 80/20 | 3.1 MW | 3.1 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 274854 | TWINGROVE;U2 | 80/20 | 3.19 MW | 3.19 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 274880 | RADFORD R;1U | 80/20 | 4.07 MW | 4.07 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 276615 | W2-048 GEN | 80/20 | 7.79 MW | 7.79 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 276621 | X2-022 GEN | 80/20 | 22.17 MW | 22.17 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 290261 | S-027 E | 80/20 | 14.13 MW | 14.13 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 290265 | S-028 E | 80/20 | 14.13 MW | 14.13 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 293798 | W4-005 E | 80/20 | 27.23 MW | 27.23 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 924261 | AB2-070 C O1 | 80/20 | 6.49 MW | 6.49 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 924262 | AB2-070 E O1 | 80/20 | 39.31 MW | 39.31 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 925771 | AC1-053 C | 80/20 | 6.18 MW | 6.18 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 925772 | AC1-053 E | 80/20 | 41.38 MW | 41.38 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 935141 | AD1-148 | 80/20 | 10.42 MW | 10.42 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 937001 | AD2-134 C | Adder | -0.93 MW | -0.79 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 942601 | AE2-276 | 80/20 | 2.89 MW | 2.89 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 944221 | AF1-090 C O1 | 80/20 | 4.79 MW | 4.79 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 944222 | AF1-090 E O1 | 80/20 | 22.45 MW | 22.45 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945391 | AF1-204 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945392 | AF1-204 E O1 | 80/20 | 10.75 MW | 10.75 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945871 | AF1-252 O1 | 80/20 | 10.63 MW | 10.63 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945881 | AF1-253 | 80/20 | 7.36 MW | 7.36 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 959611 | AF2-252 C | 80/20 | 4.46 MW | 4.46 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 959612 | AF2-252 E | 80/20 | 6.69 MW | 6.69 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960141 | AF2-305 | 80/20 | 2.3 MW | 2.3 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960261 | AF2-317 | 80/20 | 3.33 MW | 3.33 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960611 | AF2-352 C | 80/20 | 4.46 MW | 4.46 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960612 | AF2-352 E | 80/20 | 6.69 MW | 6.69 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 963831 | AG1-236 C | 80/20 | 6.18 MW | 6.18 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 963832 | AG1-236 E | 80/20 | 41.38 MW | 41.38 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965092 | AG1-374 E | 80/20 | 16.73 MW | 16.73 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965331 | AG1-398 | 80/20 | 1.83 MW | 1.83 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965341 | AG1-399 C O1 | 80/20 | 9.42 MW | 9.42 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965342 | AG1-399 E O1 | 80/20 | 44.11 MW | 44.11 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965351 | AG1-400 O1 | 80/20 | 33.46 MW | 33.46 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965371 | AG1-402 O1 | 80/20 | 33.46 MW | 33.46 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965391 | AG1-404 O1 | 80/20 | 22.31 MW | 22.31 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965911 | AG1-460 C | 80/20 | 2.33 MW | 2.33 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965912 | AG1-460 E | 80/20 | 3.49 MW | 3.49 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957382 | AF2-032 E | 80/20 | 0.39 MW | 0.39 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 276172 | Z1-108 BAT | 80/20 | 1.39 MW | 1.39 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 920273 | AA2-123 BAT | 80/20 | 1.27 MW | 1.27 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 941732 | AE2-173 BAT | 80/20 | 20.75 MW | 20.75 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 943803 | AF1-048 BAT | 80/20 | 3.3 MW | 3.3 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 944201 | AF1-088 FTIR | 80/20 | 57.85 MW | 57.85 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957141 | AF2-008 FTIR | 80/20 | 28.93 MW | 28.93 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957333 | AF2-027 BAT | 80/20 | 3.49 MW | 3.49 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957373 | AF2-031 BAT | 80/20 | 1.54 MW | 1.54 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957403 | AF2-034 BAT | 80/20 | 0.81 MW | 0.81 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 958013 | AF2-095 BAT | 80/20 | 3.94 MW | 3.94 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 958023 | AF2-096 BAT | 80/20 | 7.67 MW | 7.67 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 959353 | AF2-226 BAT | 80/20 | 2.88 MW | 2.88 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960283 | AF2-319 BAT | 80/20 | 2.88 MW | 2.88 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960382 | AF2-329 BAT | 80/20 | 3.19 MW | 3.19 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960603 | AF2-351 BAT | 80/20 | 1.97 MW | 1.97 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 961503 | AF2-441 BAT | 80/20 | 16.04 MW | 16.04 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 964362 | AG1-298 BAT | 80/20 | 39.65 MW | 39.65 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965063 | AG1-371 BAT | 80/20 | 3.99 MW | 3.99 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965083 | AG1-373 BAT | 80/20 | 1.33 MW | 1.33 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966093 | AG1-478 BAT | 80/20 | 0.86 MW | 0.86 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966433 | AG1-512 BAT | 80/20 | 3.22 MW | 3.22 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966443 | AG1-513 BAT | 80/20 | 0.8 MW | 0.8 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966652 | AG1-535 BAT | 80/20 | 6.54 MW | 6.54 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990056 | J1201 | External Queue | 4.75 MW | 4.75 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990271 | J1263 | External Queue | 32.23 MW | 32.23 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990351 | J1289 C | External Queue | 2.13 MW | 2.13 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990856 | J1408 | External Queue | 14.85 MW | 14.85 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 955402 | J1022 E | External Queue | 34.21 MW | 34.21 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 955711 | J1055 C | External Queue | 1.99 MW | 1.99 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 955712 | J1055 E | External Queue | 10.78 MW | 10.78 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 956281 | J1115 C | External Queue | 6.82 MW | 6.82 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 956282 | J1115 E | External Queue | 36.91 MW | 36.91 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 991236 | J1676 | External Queue | 94.19 MW | 94.19 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 991261 | J1713 | External Queue | 23.71 MW | 23.71 MW |
| 7BROKAW-MCLEAN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 991276 | J1725 | External Queue | 8.35 MW | 8.35 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| (TBD) | replace the limiting MISO substation terminal equipment with 4000A equipment in order to mitigate the constraint. This will include 2 circuit breakers, 5 switches and 1 wavetrap. | $2,500,000 | |
| n7207 | AD1-100 - AE1-172 - Loretto - replace-4-345kV circuit breakers, upgrade a line relay scheme, station conductor upgrades at both terminals | $47,000,000 | |
| n8403 | Construct a new 345kV line from TSS 93 Loretto to TSS 905 Essex (AD1-100 Interconnection Substation) | $127,000,000 | |
| n8404 | Reconductor line, upgrade station conductors and new relay settings | $40,000,000 | |
| n8091 | The upgrade will be to mitigate sag on the line, upgrade station conductor at both terminals and upgrade two 345 kV CBs at Pontiac. | $21,800,000 | |
| (TBD) | Additional ComEd Reinforcement Needed | $0 | |
| n6260.1 | Upgrade of TSS 80 Pontiac 345kV circuit breaker BT 4-5 and 345kV station and bus conductor | $4,000,000 | |
| n6260.2 | Replace a line disconnect switch to upgrade the Pontiac - Loretto 345 kV line. | $500,000 | |
| n6260.3 | ComEd 345kV L8012 SSTE rating is 1846 MVA. Station upgrade and line re-conductoring, ratings will be 1754/2246/2297/2488 MVA (SN/SLTE/SSTE/SLD). | $61,500,000 | |
| n7938 | Construct a new 345kV line from TSS 80 Pontiac to TSS 196 Katydid. New 345kV circuit breakers, relay upgrades and 345kV bus expansion | $127,000,000 | |
| n6261.1 | Mitigate Sag on the Pontiac - AD1-133 Tap 345 kV Line | $12,300,000 | |
| n7941 | Pontiac - Z2-087 (McLean) Sag Mitigation | $10,500,000 | |
| n7941.1 | Pontiac - Z2-087 (McLean) 345 kV line - upgarde station conductor at both stations and upgrade 2-138kV line traps. | $2,200,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-404 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.