AG1-219 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:50
Layland 69 kV
39.5 MW Capacity / 75.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-219 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar; Storage generating facility located in the AEP zone — Fayette County, West Virginia. The installed facilities will have a total capability of 75.0 MW with 39.5 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-219 |
| Project Name | Layland 69 kV |
| Developer Name | Fayette Solar I, LLC |
| State | West Virginia |
| County | Fayette |
| Transmission Owner | AEP |
| MFO | 75.0 MW |
| MWE | 75.0 MW |
| MWC | 39.5 MW |
| Fuel Type | Solar; Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-219 will interconnect on the AEP transmission system at the Layland 69 kV substation.
Summer Peak Analysis
The Queue Project was evaluated as a 75.0 MW (Capacity 39.5 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP |
05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line
247826 to 242564 ckt 1 |
AEP_P4_#14148_05TOWER117 69.0_C
CONTINGENCY 'AEP_P4_#14148_05TOWER117 69.0_C' OPEN BRANCH FROM BUS 244382 TO BUS 244383 CKT Z1 /*05ELMO 69.0 - 05ELMO SS 69.0 OPEN BRANCH FROM BUS 244383 TO BUS 244402 CKT 1 /*05ELMO SS 69.0 - 05FAYETTVL 69.0 OPEN BRANCH FROM BUS 244383 TO BUS 244405 CKT 1 /*05ELMO SS 69.0 - 05GAULEYMT 69.0 OPEN BRANCH FROM BUS 244383 TO BUS 244453 CKT 1 /*05ELMO SS 69.0 - 05TOWER117 69.0 OPEN BRANCH FROM BUS 244384 TO BUS 244387 CKT 1 /*05BROWNSVL 69.0 - 05CARBONDL 69.0 OPEN BRANCH FROM BUS 244384 TO BUS 244405 CKT 1 /*05BROWNSVL 69.0 - 05GAULEYMT 69.0 OPEN BRANCH FROM BUS 244453 TO BUS 247825 CKT 1 /*05TOWER117 69.0 - 05NUTALL 69.0 REMOVE SWSHUNT FROM BUS 244453 /*05TOWER117 69.0 END |
Breaker | AC | 116.0 % | 130.78 % | 167.0 | B | 218.41 | 24.45 | |
| AP |
01NETTIE-01CRUPRN 138.0 kV Ckt 1 line
235376 to 235318 ckt 1 |
AEP_P4_#13045_05BRADLEY 69.0_K
CONTINGENCY 'AEP_P4_#13045_05BRADLEY 69.0_K' OPEN BRANCH FROM BUS 242564 TO BUS 242565 CKT Z1 /*05BRADL1 138.0 - 05BRADL2 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242653 CKT 1 /*05BRADL1 138.0 - 05GRANDV 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242758 CKT 1 /*05BRADL1 138.0 - 05POLEYD 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 244877 CKT 1 /*05BRADL1 138.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 242564 TO BUS 247333 CKT 1 /*05BRADL1 138.0 - 05PAX BRANCH 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 247826 CKT 1 /*05BRADL1 138.0 - 05MOLLYS CRK 138.0 OPEN BRANCH FROM BUS 244380 TO BUS 244442 CKT 1 /*05BRADLEY 69.0 - 05PRINCE 69.0 OPEN BRANCH FROM BUS 244380 TO BUS 244877 CKT 1 /*05BRADLEY 69.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 244420 TO BUS 244442 CKT 1 /*05LAYLAND 69.0 - 05PRINCE 69.0 OPEN BRANCH FROM BUS 244876 TO BUS 244877 CKT 1 /*05BRADLEY 46.0 - 05BRDLEYEQ 999.0 REMOVE SWSHUNT FROM BUS 242564 /*05BRADL1 138.0 END |
Breaker | AC | 111.45 % | 125.64 % | 192.0 | B | 241.22 | 27.83 | |
| AP |
01NETTIE-01CRUPRN 138.0 kV Ckt 1 line
235376 to 235318 ckt 1 |
AEP_P4_#7807_05BRADL1 138_P
CONTINGENCY 'AEP_P4_#7807_05BRADL1 138_P' OPEN BRANCH FROM BUS 242564 TO BUS 242565 CKT Z1 /*05BRADL1 138.0 - 05BRADL2 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242653 CKT 1 /*05BRADL1 138.0 - 05GRANDV 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242758 CKT 1 /*05BRADL1 138.0 - 05POLEYD 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 244877 CKT 1 /*05BRADL1 138.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 242564 TO BUS 247333 CKT 1 /*05BRADL1 138.0 - 05PAX BRANCH 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 247826 CKT 1 /*05BRADL1 138.0 - 05MOLLYS CRK 138.0 OPEN BRANCH FROM BUS 244380 TO BUS 244442 CKT 1 /*05BRADLEY 69.0 - 05PRINCE 69.0 OPEN BRANCH FROM BUS 244380 TO BUS 244877 CKT 1 /*05BRADLEY 69.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 244420 TO BUS 247827 CKT 1 /*05LAYLAND 69.0 - 05MOLLYS CRK 69.0 OPEN BRANCH FROM BUS 244452 TO BUS 247827 CKT 1 /*05THURMOND 69.0 - 05MOLLYS CRK 69.0 OPEN BRANCH FROM BUS 244876 TO BUS 244877 CKT 1 /*05BRADLEY 46.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 247824 TO BUS 247826 CKT 1 /*05NUTALL 138.0 - 05MOLLYS CRK 138.0 OPEN BRANCH FROM BUS 247826 TO BUS 247827 CKT 1 /*05MOLLYS CRK 138.0 - 05MOLLYS CRK 69.0 REMOVE SWSHUNT FROM BUS 242564 /*05BRADL1 138.0 END |
Breaker | AC | 110.54 % | 125.6 % | 192.0 | B | 241.15 | 29.64 | |
| AP |
01NETTIE-01CRUPRN 138.0 kV Ckt 1 line
235376 to 235318 ckt 1 |
AEP_P4_#7803_05BRADL1 138_N
CONTINGENCY 'AEP_P4_#7803_05BRADL1 138_N' OPEN BRANCH FROM BUS 242564 TO BUS 242565 CKT Z1 /*05BRADL1 138.0 - 05BRADL2 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242653 CKT 1 /*05BRADL1 138.0 - 05GRANDV 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242758 CKT 1 /*05BRADL1 138.0 - 05POLEYD 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 244877 CKT 1 /*05BRADL1 138.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 242564 TO BUS 247333 CKT 1 /*05BRADL1 138.0 - 05PAX BRANCH 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 247826 CKT 1 /*05BRADL1 138.0 - 05MOLLYS CRK 138.0 OPEN BRANCH FROM BUS 242565 TO BUS 242618 CKT 1 /*05BRADL2 138.0 - 05DAMERN 138.0 OPEN BRANCH FROM BUS 242565 TO BUS 242695 CKT 1 /*05BRADL2 138.0 - 05KINCAI 138.0 OPEN BRANCH FROM BUS 242618 TO BUS 244395 CKT 1 /*05DAMERN 138.0 - 05DAMERNEQ 999.0 OPEN BRANCH FROM BUS 244380 TO BUS 244442 CKT 1 /*05BRADLEY 69.0 - 05PRINCE 69.0 OPEN BRANCH FROM BUS 244380 TO BUS 244877 CKT 1 /*05BRADLEY 69.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 244395 TO BUS 244396 CKT 1 /*05DAMERNEQ 999.0 - 05DAMERON 46.0 OPEN BRANCH FROM BUS 244876 TO BUS 244877 CKT 1 /*05BRADLEY 46.0 - 05BRDLEYEQ 999.0 REMOVE SWSHUNT FROM BUS 242564 /*05BRADL1 138.0 END |
Breaker | AC | 111.37 % | 125.56 % | 192.0 | B | 241.07 | 27.85 | |
| AP |
01NETTIE-01CRUPRN 138.0 kV Ckt 1 line
235376 to 235318 ckt 1 |
AEP_P4_#7798_05BRADL1 138_C
CONTINGENCY 'AEP_P4_#7798_05BRADL1 138_C' OPEN BRANCH FROM BUS 242564 TO BUS 242565 CKT Z1 /*05BRADL1 138.0 - 05BRADL2 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242653 CKT 1 /*05BRADL1 138.0 - 05GRANDV 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242758 CKT 1 /*05BRADL1 138.0 - 05POLEYD 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 244877 CKT 1 /*05BRADL1 138.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 242564 TO BUS 247333 CKT 1 /*05BRADL1 138.0 - 05PAX BRANCH 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 247826 CKT 1 /*05BRADL1 138.0 - 05MOLLYS CRK 138.0 OPEN BRANCH FROM BUS 242686 TO BUS 242730 CKT 1 /*05JEHU BR SS 138.0 - 05NBECKL 138.0 OPEN BRANCH FROM BUS 242730 TO BUS 242758 CKT 1 /*05NBECKL 138.0 - 05POLEYD 138.0 OPEN BRANCH FROM BUS 244380 TO BUS 244442 CKT 1 /*05BRADLEY 69.0 - 05PRINCE 69.0 OPEN BRANCH FROM BUS 244380 TO BUS 244877 CKT 1 /*05BRADLEY 69.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 244876 TO BUS 244877 CKT 1 /*05BRADLEY 46.0 - 05BRDLEYEQ 999.0 REMOVE SWSHUNT FROM BUS 242564 /*05BRADL1 138.0 END |
Breaker | AC | 111.27 % | 125.45 % | 192.0 | B | 240.86 | 27.83 | |
| AP |
01NETTIE-01CRUPRN 138.0 kV Ckt 1 line
235376 to 235318 ckt 1 |
AEP_P4_#7801_05BRADL1 138_B
CONTINGENCY 'AEP_P4_#7801_05BRADL1 138_B' OPEN BRANCH FROM BUS 242564 TO BUS 242565 CKT Z1 /*05BRADL1 138.0 - 05BRADL2 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242653 CKT 1 /*05BRADL1 138.0 - 05GRANDV 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242758 CKT 1 /*05BRADL1 138.0 - 05POLEYD 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 244877 CKT 1 /*05BRADL1 138.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 242564 TO BUS 247333 CKT 1 /*05BRADL1 138.0 - 05PAX BRANCH 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 247826 CKT 1 /*05BRADL1 138.0 - 05MOLLYS CRK 138.0 OPEN BRANCH FROM BUS 244380 TO BUS 244442 CKT 1 /*05BRADLEY 69.0 - 05PRINCE 69.0 OPEN BRANCH FROM BUS 244380 TO BUS 244877 CKT 1 /*05BRADLEY 69.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 244876 TO BUS 244877 CKT 1 /*05BRADLEY 46.0 - 05BRDLEYEQ 999.0 REMOVE SWSHUNT FROM BUS 242564 /*05BRADL1 138.0 END |
Breaker | AC | 111.1 % | 125.29 % | 192.0 | B | 240.56 | 27.83 | |
| AP |
01GILBOA-01ENONTP 138.0 kV Ckt 1 line
235333 to 235328 ckt 1 |
AEP_P4_#14144_05NUTALL 138_L2
CONTINGENCY 'AEP_P4_#14144_05NUTALL 138_L2' OPEN BRANCH FROM BUS 242564 TO BUS 247826 CKT 1 /*05BRADL1 138.0 - 05MOLLYS CRK 138.0 OPEN BRANCH FROM BUS 244420 TO BUS 247827 CKT 1 /*05LAYLAND 69.0 - 05MOLLYS CRK 69.0 OPEN BRANCH FROM BUS 244452 TO BUS 247827 CKT 1 /*05THURMOND 69.0 - 05MOLLYS CRK 69.0 OPEN BRANCH FROM BUS 247824 TO BUS 247825 CKT 2 /*05NUTALL 138.0 - 05NUTALL 69.0 OPEN BRANCH FROM BUS 247824 TO BUS 247826 CKT 1 /*05NUTALL 138.0 - 05MOLLYS CRK 138.0 OPEN BRANCH FROM BUS 247826 TO BUS 247827 CKT 1 /*05MOLLYS CRK 138.0 - 05MOLLYS CRK 69.0 END |
Breaker | AC | 105.53 % | 106.61 % | 229.0 | B | 244.13 | 2.39 | |
| AP |
01CRUPRN-01COWEN 138.0 kV Ckt 1 line
235318 to 235316 ckt 1 |
FE-P2-3-MP-138-084T
CONTINGENCY 'FE-P2-3-MP-138-084T' DISCONNECT BRANCH FROM BUS 235296 TO BUS 235389 CKT 1 /*01BAYS 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235317 TO BUS 235389 CKT 1 /*01CRAIGV 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235328 TO BUS 235389 CKT 1 /*01ENONTP 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235350 TO BUS 235389 CKT 1 /*01IVYDAL 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235389 TO BUS 236979 CKT 1 /*01POWELM 138.0 - 01POWEL MT 23.0 DISCONNECT BRANCH FROM BUS 247793 TO BUS 235350 CKT 1 /*05LINDEN RD 138.0 - 01IVYDAL 138.0 REDUCE BUS 235389 SHUNT BY 100 PERCENT /*01POWELM 138.0 END |
Breaker | AC | 97.33 % | 101.52 % | 206.0 | B | 209.13 | 8.72 | |
| AP |
01CRUPRN-01COWEN 138.0 kV Ckt 1 line
235318 to 235316 ckt 1 |
FE-P2-3-MP-138-083
CONTINGENCY 'FE-P2-3-MP-138-083' DISCONNECT BRANCH FROM BUS 235296 TO BUS 235389 CKT 1 /*01BAYS 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235317 TO BUS 235389 CKT 1 /*01CRAIGV 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235328 TO BUS 235389 CKT 1 /*01ENONTP 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235350 TO BUS 235389 CKT 1 /*01IVYDAL 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235389 TO BUS 236979 CKT 1 /*01POWELM 138.0 - 01POWEL MT 23.0 REMOVE SWSHUNT FROM BUS 235389 /*01POWELM 138.0 END |
Breaker | AC | 97.33 % | 101.51 % | 206.0 | B | 209.12 | 8.72 | |
| AP |
01CRUPRN-01COWEN 138.0 kV Ckt 1 line
235318 to 235316 ckt 1 |
FE-P2-3-MP-138-082
CONTINGENCY 'FE-P2-3-MP-138-082' DISCONNECT BRANCH FROM BUS 235296 TO BUS 235389 CKT 1 /*01BAYS 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235296 TO BUS 235431 CKT 1 /*01BAYS 138.0 - 01WOLFRN 138.0 DISCONNECT BRANCH FROM BUS 235296 TO BUS 237258 CKT 1 /*01BAYS 138.0 - 01BAYS 66.0 DISCONNECT BRANCH FROM BUS 235317 TO BUS 235389 CKT 1 /*01CRAIGV 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235328 TO BUS 235389 CKT 1 /*01ENONTP 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235350 TO BUS 235389 CKT 1 /*01IVYDAL 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235389 TO BUS 236979 CKT 1 /*01POWELM 138.0 - 01POWEL MT 23.0 DISCONNECT BRANCH FROM BUS 235411 TO BUS 235437 CKT 1 /*01SUTTON 138.0 - 01SUTT T 138.0 DISCONNECT BRANCH FROM BUS 235412 TO BUS 235437 CKT 1 /*01SUTTNH 138.0 - 01SUTT T 138.0 DISCONNECT BRANCH FROM BUS 235412 TO BUS 237289 CKT 1 /*01SUTTNH 138.0 - 01SUTTN H 66.0 DISCONNECT BRANCH FROM BUS 235431 TO BUS 235437 CKT 1 /*01WOLFRN 138.0 - 01SUTT T 138.0 REMOVE SWSHUNT FROM BUS 235389 /*01POWELM 138.0 END |
Breaker | AC | 96.72 % | 100.89 % | 206.0 | B | 207.84 | 8.72 | |
| AP |
01NETTIE-01CRUPRN 138.0 kV Ckt 1 line
235376 to 235318 ckt 1 |
AEP_P2-2_#7801_05BRADL1 138_1
CONTINGENCY 'AEP_P2-2_#7801_05BRADL1 138_1' OPEN BRANCH FROM BUS 242564 TO BUS 242565 CKT Z1 /*05BRADL1 138.0 - 05BRADL2 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242653 CKT 1 /*05BRADL1 138.0 - 05GRANDV 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 242758 CKT 1 /*05BRADL1 138.0 - 05POLEYD 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 244877 CKT 1 /*05BRADL1 138.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 242564 TO BUS 247333 CKT 1 /*05BRADL1 138.0 - 05PAX BRANCH 138.0 OPEN BRANCH FROM BUS 242564 TO BUS 247826 CKT 1 /*05BRADL1 138.0 - 05MOLLYS CRK 138.0 OPEN BRANCH FROM BUS 244380 TO BUS 244442 CKT 1 /*05BRADLEY 69.0 - 05PRINCE 69.0 OPEN BRANCH FROM BUS 244380 TO BUS 244877 CKT 1 /*05BRADLEY 69.0 - 05BRDLEYEQ 999.0 OPEN BRANCH FROM BUS 244876 TO BUS 244877 CKT 1 /*05BRADLEY 46.0 - 05BRDLEYEQ 999.0 REMOVE SWSHUNT FROM BUS 242564 /*05BRADL1 138.0 END |
Bus | AC | 111.12 % | 125.31 % | 192.0 | B | 240.6 | 27.83 | |
| AP |
01CRUPRN-01COWEN 138.0 kV Ckt 1 line
235318 to 235316 ckt 1 |
FE-P2-2-MP-138-024
CONTINGENCY 'FE-P2-2-MP-138-024' DISCONNECT BRANCH FROM BUS 235296 TO BUS 235389 CKT 1 /*01BAYS 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235317 TO BUS 235389 CKT 1 /*01CRAIGV 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235328 TO BUS 235389 CKT 1 /*01ENONTP 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235350 TO BUS 235389 CKT 1 /*01IVYDAL 138.0 - 01POWELM 138.0 DISCONNECT BRANCH FROM BUS 235389 TO BUS 236979 CKT 1 /*01POWELM 138.0 - 01POWEL MT 23.0 REMOVE SWSHUNT FROM BUS 235389 /*01POWELM 138.0 END |
Bus | AC | 97.36 % | 101.55 % | 206.0 | B | 209.2 | 8.72 | |
| Details for 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 963451 | AG1-194 C | 50/50 | 56.02 MW | 56.02 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 963452 | AG1-194 E | 50/50 | 51.72 MW | 51.72 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 963671 | AG1-219 C | 50/50 | 12.88 MW | 12.88 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 963672 | AG1-219 E | 50/50 | 11.57 MW | 11.57 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 960201 | AF2-311 C | 50/50 | 6.37 MW | 6.37 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 960202 | AF2-311 E | 50/50 | 5.21 MW | 5.21 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 960251 | AF2-316 C | 50/50 | 9.59 MW | 9.59 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 960252 | AF2-316 E | 50/50 | 7.8 MW | 7.8 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 235780 | 01BEECHRIDGE | 50/50 | 0.65 MW | 0.65 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 236845 | 01BR_BAT_M24 | 50/50 | 8.07 MW | 8.07 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 244467 | 05SUMMERVL | 50/50 | 7.34 MW | 7.34 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 292981 | N-007 E | Adder | 2.07 MW | 1.76 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 923384 | M24 E | 50/50 | 21.58 MW | 21.58 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 931011 | AB1-150 C | 50/50 | 0.29 MW | 0.29 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 931012 | AB1-150 E | 50/50 | 11.08 MW | 11.08 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 938641 | AE1-086 C | 50/50 | 0.03 MW | 0.03 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 938642 | AE1-086 E | 50/50 | 1.11 MW | 1.11 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | 962403 | AG1-089 BAT | Adder | 2.85 MW | 2.42 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.32 MW | 0.32 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.27 MW | 0.27 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.22 MW | 0.22 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.15 MW | 0.15 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.22 MW | 0.22 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.22 MW | 0.22 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.8 MW | 0.8 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.43 MW | 0.43 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.22 MW | 0.22 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.86 MW | 0.86 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 05MOLLYS CRK-05BRADL1 138.0 kV Ckt 1 line l/o AEP_P4_#14148_05TOWER117 69.0_C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.16 MW | 1.16 MW |
| Details for 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 963451 | AG1-194 C | 50/50 | 36.45 MW | 36.45 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 963452 | AG1-194 E | 50/50 | 33.65 MW | 33.65 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 963671 | AG1-219 C | 50/50 | 14.66 MW | 14.66 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 963672 | AG1-219 E | 50/50 | 13.17 MW | 13.17 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 960201 | AF2-311 C | Adder | 4.37 MW | 3.71 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 960202 | AF2-311 E | Adder | 3.57 MW | 3.04 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 960251 | AF2-316 C | Adder | 6.57 MW | 5.58 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 960252 | AF2-316 E | Adder | 5.35 MW | 4.54 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 235780 | 01BEECHRIDGE | 50/50 | 1.11 MW | 1.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 236845 | 01BR_BAT_M24 | 50/50 | 13.87 MW | 13.87 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 244467 | 05SUMMERVL | 50/50 | 3.92 MW | 3.92 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 923384 | M24 E | 50/50 | 37.05 MW | 37.05 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 931011 | AB1-150 C | 50/50 | 0.49 MW | 0.49 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 931012 | AB1-150 E | 50/50 | 19.02 MW | 19.02 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 938641 | AE1-086 C | 50/50 | 0.04 MW | 0.04 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | 938642 | AE1-086 E | 50/50 | 1.91 MW | 1.91 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.22 MW | 2.22 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.39 MW | 3.39 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.49 MW | 2.49 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.25 MW | 0.25 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.48 MW | 0.48 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.19 MW | 0.19 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.43 MW | 0.43 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.13 MW | 0.13 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.59 MW | 1.59 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.4 MW | 0.4 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#13045_05BRADLEY 69.0_K | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 963451 | AG1-194 C | 50/50 | 36.19 MW | 36.19 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 963452 | AG1-194 E | 50/50 | 33.41 MW | 33.41 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 963671 | AG1-219 C | 50/50 | 15.61 MW | 15.61 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 963672 | AG1-219 E | 50/50 | 14.03 MW | 14.03 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 960201 | AF2-311 C | Adder | 4.38 MW | 3.72 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 960202 | AF2-311 E | Adder | 3.58 MW | 3.05 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 960251 | AF2-316 C | Adder | 6.59 MW | 5.6 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 960252 | AF2-316 E | Adder | 5.36 MW | 4.56 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 235780 | 01BEECHRIDGE | 50/50 | 1.11 MW | 1.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 236845 | 01BR_BAT_M24 | 50/50 | 13.89 MW | 13.89 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 244467 | 05SUMMERVL | 50/50 | 3.89 MW | 3.89 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 923384 | M24 E | 50/50 | 37.1 MW | 37.1 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 931011 | AB1-150 C | 50/50 | 0.49 MW | 0.49 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 931012 | AB1-150 E | 50/50 | 19.05 MW | 19.05 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 938641 | AE1-086 C | 50/50 | 0.04 MW | 0.04 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | 938642 | AE1-086 E | 50/50 | 1.91 MW | 1.91 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.22 MW | 2.22 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.38 MW | 3.38 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.48 MW | 2.48 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.25 MW | 0.25 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.48 MW | 0.48 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.19 MW | 0.19 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.43 MW | 0.43 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.13 MW | 0.13 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.59 MW | 1.59 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.4 MW | 0.4 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7807_05BRADL1 138_P | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 963451 | AG1-194 C | 50/50 | 36.48 MW | 36.48 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 963452 | AG1-194 E | 50/50 | 33.67 MW | 33.67 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 963671 | AG1-219 C | 50/50 | 14.67 MW | 14.67 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 963672 | AG1-219 E | 50/50 | 13.18 MW | 13.18 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 960201 | AF2-311 C | Adder | 4.38 MW | 3.72 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 960202 | AF2-311 E | Adder | 3.58 MW | 3.04 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 960251 | AF2-316 C | Adder | 6.58 MW | 5.59 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 960252 | AF2-316 E | Adder | 5.36 MW | 4.55 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 235780 | 01BEECHRIDGE | 50/50 | 1.11 MW | 1.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 236845 | 01BR_BAT_M24 | 50/50 | 13.87 MW | 13.87 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 244467 | 05SUMMERVL | 50/50 | 3.92 MW | 3.92 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 923384 | M24 E | 50/50 | 37.07 MW | 37.07 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 931011 | AB1-150 C | 50/50 | 0.49 MW | 0.49 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 931012 | AB1-150 E | 50/50 | 19.03 MW | 19.03 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 938641 | AE1-086 C | 50/50 | 0.04 MW | 0.04 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | 938642 | AE1-086 E | 50/50 | 1.91 MW | 1.91 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.21 MW | 2.21 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.38 MW | 3.38 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.48 MW | 2.48 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.25 MW | 0.25 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.48 MW | 0.48 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.19 MW | 0.19 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.43 MW | 0.43 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.13 MW | 0.13 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.59 MW | 1.59 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.4 MW | 0.4 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7803_05BRADL1 138_N | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 963451 | AG1-194 C | 50/50 | 36.45 MW | 36.45 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 963452 | AG1-194 E | 50/50 | 33.65 MW | 33.65 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 963671 | AG1-219 C | 50/50 | 14.66 MW | 14.66 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 963672 | AG1-219 E | 50/50 | 13.17 MW | 13.17 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 960201 | AF2-311 C | Adder | 4.37 MW | 3.71 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 960202 | AF2-311 E | Adder | 3.57 MW | 3.04 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 960251 | AF2-316 C | Adder | 6.57 MW | 5.58 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 960252 | AF2-316 E | Adder | 5.35 MW | 4.54 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 235780 | 01BEECHRIDGE | 50/50 | 1.11 MW | 1.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 236845 | 01BR_BAT_M24 | 50/50 | 13.87 MW | 13.87 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 244467 | 05SUMMERVL | 50/50 | 3.92 MW | 3.92 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 923384 | M24 E | 50/50 | 37.05 MW | 37.05 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 931011 | AB1-150 C | 50/50 | 0.49 MW | 0.49 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 931012 | AB1-150 E | 50/50 | 19.02 MW | 19.02 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 938641 | AE1-086 C | 50/50 | 0.04 MW | 0.04 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | 938642 | AE1-086 E | 50/50 | 1.91 MW | 1.91 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.22 MW | 2.22 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.39 MW | 3.39 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.49 MW | 2.49 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.25 MW | 0.25 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.48 MW | 0.48 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.19 MW | 0.19 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.43 MW | 0.43 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.13 MW | 0.13 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.59 MW | 1.59 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.4 MW | 0.4 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7798_05BRADL1 138_C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 963451 | AG1-194 C | 50/50 | 36.45 MW | 36.45 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 963452 | AG1-194 E | 50/50 | 33.65 MW | 33.65 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 963671 | AG1-219 C | 50/50 | 14.66 MW | 14.66 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 963672 | AG1-219 E | 50/50 | 13.17 MW | 13.17 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 960201 | AF2-311 C | Adder | 4.37 MW | 3.71 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 960202 | AF2-311 E | Adder | 3.57 MW | 3.04 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 960251 | AF2-316 C | Adder | 6.57 MW | 5.58 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 960252 | AF2-316 E | Adder | 5.35 MW | 4.54 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 235780 | 01BEECHRIDGE | 50/50 | 1.11 MW | 1.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 236845 | 01BR_BAT_M24 | 50/50 | 13.87 MW | 13.87 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 244467 | 05SUMMERVL | 50/50 | 3.92 MW | 3.92 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 923384 | M24 E | 50/50 | 37.05 MW | 37.05 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 931011 | AB1-150 C | 50/50 | 0.49 MW | 0.49 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 931012 | AB1-150 E | 50/50 | 19.02 MW | 19.02 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 938641 | AE1-086 C | 50/50 | 0.04 MW | 0.04 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | 938642 | AE1-086 E | 50/50 | 1.91 MW | 1.91 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.22 MW | 2.22 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.39 MW | 3.39 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.49 MW | 2.49 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.25 MW | 0.25 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.48 MW | 0.48 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.19 MW | 0.19 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.43 MW | 0.43 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.13 MW | 0.13 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.59 MW | 1.59 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.4 MW | 0.4 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P4_#7801_05BRADL1 138_B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | 960201 | AF2-311 C | 50/50 | 25.01 MW | 25.01 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | 960202 | AF2-311 E | 50/50 | 20.46 MW | 20.46 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | 960251 | AF2-316 C | 50/50 | 37.6 MW | 37.6 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | 960252 | AF2-316 E | 50/50 | 30.6 MW | 30.6 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | 925971 | AC1-073 C | Adder | -0.38 MW | -0.32 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | 963673 | AG1-219 BAT | 50/50 | 2.39 MW | 2.39 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | 963453 | AG1-194 BAT | 50/50 | 14.94 MW | 14.94 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | 235093 | W2-057 BAT | Adder | 2.1 MW | 1.78 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.22 MW | 0.22 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.76 MW | 4.76 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.5 MW | 6.5 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.9 MW | 4.9 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.24 MW | 0.24 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.41 MW | 0.41 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.96 MW | 0.96 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.37 MW | 0.37 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.83 MW | 0.83 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.21 MW | 0.21 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.64 MW | 2.64 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.8 MW | 0.8 MW |
| 01GILBOA-01ENONTP 138.0 kV Ckt 1 line l/o AEP_P4_#14144_05NUTALL 138_L2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.16 MW | 0.16 MW |
| Details for 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 962401 | AG1-089 C | Adder | 0.61 MW | 0.52 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 962402 | AG1-089 E | Adder | 0.92 MW | 0.78 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 963451 | AG1-194 C | 50/50 | 15.12 MW | 15.12 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 963452 | AG1-194 E | 50/50 | 13.96 MW | 13.96 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 963671 | AG1-219 C | 50/50 | 4.59 MW | 4.59 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 963672 | AG1-219 E | 50/50 | 4.13 MW | 4.13 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 960201 | AF2-311 C | 50/50 | 8.54 MW | 8.54 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 960202 | AF2-311 E | 50/50 | 6.99 MW | 6.99 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 960251 | AF2-316 C | 50/50 | 12.85 MW | 12.85 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 960252 | AF2-316 E | 50/50 | 10.46 MW | 10.46 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 235780 | 01BEECHRIDGE | 50/50 | 0.67 MW | 0.67 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 236845 | 01BR_BAT_M24 | 50/50 | 8.41 MW | 8.41 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 244467 | 05SUMMERVL | 50/50 | 1.74 MW | 1.74 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 923384 | M24 E | 50/50 | 22.47 MW | 22.47 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 931011 | AB1-150 C | 50/50 | 0.3 MW | 0.3 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 931012 | AB1-150 E | 50/50 | 11.54 MW | 11.54 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 938641 | AE1-086 C | 50/50 | 0.03 MW | 0.03 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 938642 | AE1-086 E | 50/50 | 1.16 MW | 1.16 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 939804 | AE1-212 C O1 | Adder | 2.71 MW | 2.3 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 939805 | AE1-212 E O1 | Adder | 1.87 MW | 1.59 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 925971 | AC1-073 C | Adder | -0.55 MW | -0.46 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | 235093 | W2-057 BAT | Adder | 3.04 MW | 2.58 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.18 MW | 0.18 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.23 MW | 0.23 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.29 MW | 5.29 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.89 MW | 6.89 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.25 MW | 5.25 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.27 MW | 0.27 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.46 MW | 0.46 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.04 MW | 1.04 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.39 MW | 0.39 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.88 MW | 0.88 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.93 MW | 2.93 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.86 MW | 0.86 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-084T | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.17 MW | 0.17 MW |
| Details for 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 962401 | AG1-089 C | Adder | 0.61 MW | 0.52 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 962402 | AG1-089 E | Adder | 0.92 MW | 0.78 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 963451 | AG1-194 C | 50/50 | 15.12 MW | 15.12 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 963452 | AG1-194 E | 50/50 | 13.96 MW | 13.96 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 963671 | AG1-219 C | 50/50 | 4.59 MW | 4.59 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 963672 | AG1-219 E | 50/50 | 4.13 MW | 4.13 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 960201 | AF2-311 C | 50/50 | 8.54 MW | 8.54 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 960202 | AF2-311 E | 50/50 | 6.99 MW | 6.99 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 960251 | AF2-316 C | 50/50 | 12.85 MW | 12.85 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 960252 | AF2-316 E | 50/50 | 10.46 MW | 10.46 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 235780 | 01BEECHRIDGE | 50/50 | 0.67 MW | 0.67 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 236845 | 01BR_BAT_M24 | 50/50 | 8.41 MW | 8.41 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 244467 | 05SUMMERVL | 50/50 | 1.74 MW | 1.74 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 923384 | M24 E | 50/50 | 22.47 MW | 22.47 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 931011 | AB1-150 C | 50/50 | 0.3 MW | 0.3 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 931012 | AB1-150 E | 50/50 | 11.54 MW | 11.54 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 938641 | AE1-086 C | 50/50 | 0.03 MW | 0.03 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 938642 | AE1-086 E | 50/50 | 1.16 MW | 1.16 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 939804 | AE1-212 C O1 | Adder | 2.71 MW | 2.3 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 939805 | AE1-212 E O1 | Adder | 1.87 MW | 1.59 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 925971 | AC1-073 C | Adder | -0.55 MW | -0.46 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | 235093 | W2-057 BAT | Adder | 3.04 MW | 2.58 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.18 MW | 0.18 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.23 MW | 0.23 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.29 MW | 5.29 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.89 MW | 6.89 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.25 MW | 5.25 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.27 MW | 0.27 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.46 MW | 0.46 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.04 MW | 1.04 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.39 MW | 0.39 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.88 MW | 0.88 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.93 MW | 2.93 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.86 MW | 0.86 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-083 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.17 MW | 0.17 MW |
| Details for 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 962401 | AG1-089 C | Adder | 0.61 MW | 0.52 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 962402 | AG1-089 E | Adder | 0.92 MW | 0.78 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 963451 | AG1-194 C | 50/50 | 15.11 MW | 15.11 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 963452 | AG1-194 E | 50/50 | 13.95 MW | 13.95 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 963671 | AG1-219 C | 50/50 | 4.59 MW | 4.59 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 963672 | AG1-219 E | 50/50 | 4.13 MW | 4.13 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 960201 | AF2-311 C | 50/50 | 8.54 MW | 8.54 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 960202 | AF2-311 E | 50/50 | 6.99 MW | 6.99 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 960251 | AF2-316 C | 50/50 | 12.84 MW | 12.84 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 960252 | AF2-316 E | 50/50 | 10.45 MW | 10.45 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 235780 | 01BEECHRIDGE | 50/50 | 0.67 MW | 0.67 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 236845 | 01BR_BAT_M24 | 50/50 | 8.4 MW | 8.4 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 244467 | 05SUMMERVL | 50/50 | 1.74 MW | 1.74 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 923384 | M24 E | 50/50 | 22.45 MW | 22.45 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 931011 | AB1-150 C | 50/50 | 0.3 MW | 0.3 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 931012 | AB1-150 E | 50/50 | 11.53 MW | 11.53 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 938641 | AE1-086 C | 50/50 | 0.03 MW | 0.03 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 938642 | AE1-086 E | 50/50 | 1.16 MW | 1.16 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 939804 | AE1-212 C O1 | Adder | 2.71 MW | 2.3 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 939805 | AE1-212 E O1 | Adder | 1.86 MW | 1.58 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 925971 | AC1-073 C | Adder | -0.55 MW | -0.47 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | 235093 | W2-057 BAT | Adder | 3.04 MW | 2.58 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.18 MW | 0.18 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.23 MW | 0.23 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.29 MW | 5.29 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.88 MW | 6.88 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.24 MW | 5.24 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.27 MW | 0.27 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.46 MW | 0.46 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.04 MW | 1.04 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.39 MW | 0.39 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.88 MW | 0.88 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.93 MW | 2.93 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.86 MW | 0.86 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-3-MP-138-082 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.17 MW | 0.17 MW |
| Details for 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 963451 | AG1-194 C | 50/50 | 36.45 MW | 36.45 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 963452 | AG1-194 E | 50/50 | 33.65 MW | 33.65 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 963671 | AG1-219 C | 50/50 | 14.66 MW | 14.66 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 963672 | AG1-219 E | 50/50 | 13.17 MW | 13.17 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 960201 | AF2-311 C | Adder | 4.37 MW | 3.71 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 960202 | AF2-311 E | Adder | 3.57 MW | 3.04 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 960251 | AF2-316 C | Adder | 6.57 MW | 5.58 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 960252 | AF2-316 E | Adder | 5.35 MW | 4.54 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 235780 | 01BEECHRIDGE | 50/50 | 1.11 MW | 1.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 236845 | 01BR_BAT_M24 | 50/50 | 13.87 MW | 13.87 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 244467 | 05SUMMERVL | 50/50 | 3.92 MW | 3.92 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 923384 | M24 E | 50/50 | 37.05 MW | 37.05 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 931011 | AB1-150 C | 50/50 | 0.49 MW | 0.49 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 931012 | AB1-150 E | 50/50 | 19.02 MW | 19.02 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 938641 | AE1-086 C | 50/50 | 0.04 MW | 0.04 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | 938642 | AE1-086 E | 50/50 | 1.91 MW | 1.91 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.22 MW | 2.22 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.39 MW | 3.39 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.49 MW | 2.49 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.25 MW | 0.25 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.48 MW | 0.48 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.19 MW | 0.19 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.43 MW | 0.43 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.13 MW | 0.13 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.59 MW | 1.59 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.4 MW | 0.4 MW |
| 01NETTIE-01CRUPRN 138.0 kV Ckt 1 line l/o AEP_P2-2_#7801_05BRADL1 138_1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 962401 | AG1-089 C | Adder | 0.61 MW | 0.52 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 962402 | AG1-089 E | Adder | 0.92 MW | 0.78 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 963451 | AG1-194 C | 50/50 | 15.12 MW | 15.12 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 963452 | AG1-194 E | 50/50 | 13.96 MW | 13.96 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 963671 | AG1-219 C | 50/50 | 4.59 MW | 4.59 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 963672 | AG1-219 E | 50/50 | 4.13 MW | 4.13 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 960201 | AF2-311 C | 50/50 | 8.54 MW | 8.54 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 960202 | AF2-311 E | 50/50 | 6.99 MW | 6.99 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 960251 | AF2-316 C | 50/50 | 12.85 MW | 12.85 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 960252 | AF2-316 E | 50/50 | 10.46 MW | 10.46 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 235780 | 01BEECHRIDGE | 50/50 | 0.67 MW | 0.67 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 236845 | 01BR_BAT_M24 | 50/50 | 8.41 MW | 8.41 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 244467 | 05SUMMERVL | 50/50 | 1.74 MW | 1.74 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 923384 | M24 E | 50/50 | 22.47 MW | 22.47 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 931011 | AB1-150 C | 50/50 | 0.3 MW | 0.3 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 931012 | AB1-150 E | 50/50 | 11.54 MW | 11.54 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 938641 | AE1-086 C | 50/50 | 0.03 MW | 0.03 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 938642 | AE1-086 E | 50/50 | 1.16 MW | 1.16 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 939804 | AE1-212 C O1 | Adder | 2.71 MW | 2.3 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 939805 | AE1-212 E O1 | Adder | 1.87 MW | 1.59 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 925971 | AC1-073 C | Adder | -0.55 MW | -0.46 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | 235093 | W2-057 BAT | Adder | 3.04 MW | 2.58 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.18 MW | 0.18 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.23 MW | 0.23 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.29 MW | 5.29 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.89 MW | 6.89 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.25 MW | 5.25 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.27 MW | 0.27 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.46 MW | 0.46 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.04 MW | 1.04 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.39 MW | 0.39 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.88 MW | 0.88 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.93 MW | 2.93 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.86 MW | 0.86 MW |
| 01CRUPRN-01COWEN 138.0 kV Ckt 1 line l/o FE-P2-2-MP-138-024 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.17 MW | 0.17 MW |
Light Load Analysis
The Queue Project was evaluated as a 75.0 MW (Capacity 39.5 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| (TBD) | Replace two 138 kV disconnect switches at Crupperneck Substation | $849,000 | |
| n7518 | Reconductor approximately 3.33 miles of 336.4 ACSR 26/7 transmission line from Crupperneck to Nettie with a conductor able to meet or exceed 237 MVA STE. | $13,185,200 | |
| n7517 | Replace (2) 8 Amp thermal relays at Gilboa. | $1,218,220 | |
| n7516 | Replace 4Bradley Sub cond 300 MCM CU 37 Str | $400,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-219 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.