AG1-090 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:46
Philipsburg 115 kV
80.0 MW Capacity / 100.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-090 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar; Storage generating facility located in the PENELEC zone — Centre County, Pennsylvania. The installed facilities will have a total capability of 100.0 MW with 80.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-090 |
| Project Name | Philipsburg 115 kV |
| Developer Name | CE-Black Moshannon OZ LLC |
| State | Pennsylvania |
| County | Centre |
| Transmission Owner | PENELEC |
| MFO | 100.0 MW |
| MWE | 100.0 MW |
| MWC | 80.0 MW |
| Fuel Type | Solar; Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
The interconnection of AG1-090 will be accomplished by installing one 115 kV breaker at Philipsburg substation to expand the station from a four breaker to a five breaker ring bus. Philipsburg Substation is planned to be converted to a four breaker ring bus with supplemental project s1919. Changes, deferral, or cancelation of this supplemental project could result in additional scope for AG1-090 to interconnect at Philipsburg Substation.
Summer Peak Analysis
The Queue Project was evaluated as a 100.0 MW (Capacity 80.0 MW) injection in the PENELEC area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| PENELEC |
AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line
938380 to 200520 ckt 1 |
PL:10:P13:100618
CONTINGENCY 'PL:10:P13:100618' DISCONNECT BRANCH FROM BUS 208005 TO BUS 200009 CKT 2 /*JUNI BU2 230.0 - JUNIATA 500.0 DISCONNECT BRANCH FROM BUS 208005 TO BUS 200513 CKT 1 /*JUNI BU2 230.0 - 26LEWISTWN 230.0 DISCONNECT BRANCH FROM BUS 208005 TO BUS 207955 CKT 1 /*JUNI BU2 230.0 - DAUP TR2 230.0 DISCONNECT BRANCH FROM BUS 208005 TO BUS 208004 CKT 1 /*JUNI BU2 230.0 - JUNI BU1 230.0 DISCONNECT BRANCH FROM BUS 208005 TO BUS 209997 CKT 4 /*JUNI BU2 230.0 - JUNI 69.0 REMOVE SHUNT 1 FROM BUS 208005 /*JUNI BU2 230.0 END |
Single | AC | 121.44 % | 124.57 % | 160.0 | B | 199.32 | 5.71 | |
| PENELEC |
AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line
938380 to 200520 ckt 1 |
PN-P1-2-PN-230-103AT
CONTINGENCY 'PN-P1-2-PN-230-103AT' DISCONNECT BRANCH FROM BUS 200513 TO BUS 208005 CKT 1 /*26LEWISTWN 230.0 - JUNI BU2 230.0 END |
Single | AC | 120.05 % | 123.18 % | 160.0 | B | 197.09 | 5.7 | |
| PENELEC |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line
200675 to 200924 ckt 1 |
Base Case | Single | AC | 110.15 % | 110.97 % | 506.0 | A | 561.53 | 5.95 | |
| PENELEC |
26CANYON-26N.MESHPN 230.0 kV Ckt 1 line
200924 to 200706 ckt 1 |
Base Case | Single | AC | 100.81 % | 101.57 % | 546.0 | A | 554.59 | 5.95 | |
| PENELEC |
AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line
938380 to 200520 ckt 1 |
PL:10:P45:102437
CONTINGENCY 'PL:10:P45:102437' DISCONNECT BUS 208004 /*JUNI BU1 230.0 DISCONNECT BUS 208005 /*JUNI BU2 230.0 END |
Breaker | AC | 170.84 % | 174.5 % | 160.0 | B | 279.19 | 7.14 | |
| PENELEC |
26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer
999332 to 200726 ckt 2A |
PN-P2-3-PN-230-21DT
CONTINGENCY 'PN-P2-3-PN-230-21DT' DISCONNECT BRANCH FROM BUS 200665 TO BUS 200710 CKT 1 /*26SHAWVL 3 22.0 - 26SHAWVL 1 230.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 200714 TO BUS 200715 CKT 1A /*26SHAWVL 1 230.0 - 26SHAWVL 1 115.0 - 26SHAWVL 1 18.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 200726 CKT ZB /*26SHAWVL 1 230.0 - 26SHAWVL 2 230.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 944320 CKT 1 /*26SHAWVL 1 230.0 - AF1-100 TAP 230.0 END |
Breaker | AC | 150.84 % | 172.35 % | 149.0 | B | 256.8 | 32.77 | |
| PENELEC |
26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer
999332 to 200726 ckt 2A |
PN-P2-3-PN-115-59A
CONTINGENCY 'PN-P2-3-PN-115-59A' DISCONNECT BRANCH FROM BUS 200597 TO BUS 200713 CKT 1 /*26ROCK MT 34.5 - 26ROCKTON 115.0 DISCONNECT BRANCH FROM BUS 200607 TO BUS 200712 CKT 3 /*26DUBOIS 2 34.5 - 26DUBOIS 115.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 200714 TO BUS 200715 CKT 1A /*26SHAWVL 1 230.0 - 26SHAWVL 1 115.0 - 26SHAWVL 1 18.0 DISCONNECT BRANCH FROM BUS 200712 TO BUS 200713 CKT 1 /*26DUBOIS 115.0 - 26ROCKTON 115.0 DISCONNECT BRANCH FROM BUS 200713 TO BUS 200714 CKT 1 /*26ROCKTON 115.0 - 26SHAWVL 1 115.0 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200555 TO BUS 200913 CKT 14 /*26SHAWVL 1 115.0 - 26SHAW.NO1 34.5 - 26SHAW-D 4.2 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200555 TO BUS 200913 CKT 14 /*26SHAWVL 1 115.0 - 26SHAW.NO1 34.5 - 26SHAW-D 4.2 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200715 CKT 1B /*26SHAWVL 1 115.0 - 26SHAWVL 1 18.0 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200722 CKT 2B /*26SHAWVL 1 115.0 - 26SHAWVL 2 18.0 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200727 CKT ZB /*26SHAWVL 1 115.0 - 26SHAW. 2 115.0 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200872 CKT 1 /*26SHAWVL 1 115.0 - 26BIOEN TP 115.0 END |
Breaker | AC | 107.37 % | 139.73 % | 149.0 | B | 208.2 | 52.03 | |
| PENELEC |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
200767 to 200795 ckt 1 |
PN_P4-500-002F
CONTINGENCY 'PN_P4-500-002F' DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3 /*CONEM-GH 500.0 - 26CONEMAGH 230.0 DISCONNECT BUS 200030 /*CONE G1 22.0 END |
Breaker | AC | 136.0 % | 137.88 % | 923.0 | B | 1272.59 | 20.05 | |
| PENELEC |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
200767 to 200795 ckt 1 |
PN_P4-500-002A
CONTINGENCY 'PN_P4-500-002A' DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3 /*CONEM-GH 500.0 - 26CONEMAGH 230.0 DISCONNECT BUS 200031 /*CONE G2 22.0 END |
Breaker | AC | 135.99 % | 137.87 % | 923.0 | B | 1272.53 | 20.05 | |
| PENELEC |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
200795 to 200810 ckt 1 |
PN_P4-500-002F
CONTINGENCY 'PN_P4-500-002F' DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3 /*CONEM-GH 500.0 - 26CONEMAGH 230.0 DISCONNECT BUS 200030 /*CONE G1 22.0 END |
Breaker | AC | 133.29 % | 135.43 % | 923.0 | B | 1250.03 | 23.16 | |
| PENELEC |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
200795 to 200810 ckt 1 |
PN_P4-500-002A
CONTINGENCY 'PN_P4-500-002A' DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3 /*CONEM-GH 500.0 - 26CONEMAGH 230.0 DISCONNECT BUS 200031 /*CONE G2 22.0 END |
Breaker | AC | 133.28 % | 135.42 % | 923.0 | B | 1249.96 | 23.16 | |
| AP/PENELEC |
AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line
966040 to 200513 ckt 1 |
PN-P2-3-PN-230-17B28
CONTINGENCY 'PN-P2-3-PN-230-17B28' DISCONNECT BRANCH FROM BUS 200677 TO BUS 200706 CKT 3 /*26NO MESHO 115.0 - 26N.MESHPN 230.0 DISCONNECT BRANCH FROM BUS 200706 TO BUS 200708 CKT 1 /*26N.MESHPN 230.0 - 26OXBOW 230.0 DISCONNECT BRANCH FROM BUS 200708 TO BUS 200709 CKT 1 /*26OXBOW 230.0 - 26OXBOW 34.5 DISCONNECT BRANCH FROM BUS 200708 TO BUS 208009 CKT 1 /*26OXBOW 230.0 - LACK 230.0 END |
Breaker | AC | 133.17 % | 136.03 % | 621.0 | B | 844.74 | 18.74 | |
| AP/PENELEC |
AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line
966040 to 200513 ckt 1 |
PN-P2_1-PN-230-997-DRT-063
CONTINGENCY 'PN-P2_1-PN-230-997-DRT-063' DISCONNECT BRANCH FROM BUS 200706 TO BUS 200708 CKT 1 /*26N.MESHPN 230.0 - 26OXBOW 230.0 DISCONNECT BRANCH FROM BUS 200708 TO BUS 200709 CKT 1 /*26OXBOW 230.0 - 26OXBOW 34.5 SET POSTCONTRATING 498 BRANCH FROM BUS 200706 TO BUS 200924 CKT 1 /*26N.MESHPN 230.0 - 26CANYON 230.0 SET PRECONTRATING 498 BRANCH FROM BUS 200706 TO BUS 200924 CKT 1 /*26N.MESHPN 230.0 - 26CANYON 230.0 END |
Breaker | AC | 133.16 % | 136.02 % | 621.0 | B | 844.7 | 18.73 | |
| PENELEC |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
200767 to 200795 ckt 1 |
PN-P2_3-PN-230-0347-2
CONTINGENCY 'PN-P2_3-PN-230-0347-2' OPEN BRANCH FROM BUS 200793 TO BUS 200741 CKT 9 /*26SEWARD 2 230.0 - 26SEWARD 115.0 OPEN BRANCH FROM BUS 200793 TO BUS 200912 CKT 1 /*26SEWARD 2 230.0 - 26CONEMAGH 230.0 END |
Breaker | AC | 133.25 % | 135.09 % | 923.0 | B | 1246.92 | 19.68 | |
| PENELEC |
26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer
999332 to 200726 ckt 2A |
PN-P2-3-PN-115-73-11
CONTINGENCY 'PN-P2-3-PN-115-73-11' DISCONNECT BRANCH FROM BUS 200527 TO BUS 200528 CKT 1 /*26TYRONE N 115.0 - 26WESTFALL 115.0 DISCONNECT BRANCH FROM BUS 200527 TO BUS 200543 CKT 2 /*26TYRONE N 115.0 - 26TYRNE #2 46.0 DISCONNECT BRANCH FROM BUS 200527 TO BUS 200544 CKT 1 /*26TYRONE N 115.0 - 26TYRNE #1 46.0 DISCONNECT BRANCH FROM BUS 200527 TO BUS 200904 CKT 1 /*26TYRONE N 115.0 - 26EAGL VAL 115.0 DISCONNECT BRANCH FROM BUS 200528 TO BUS 200545 CKT 3 /*26WESTFALL 115.0 - 26WESTFALL 46.0 END |
Breaker | AC | 113.97 % | 133.67 % | 149.0 | B | 199.16 | 33.77 | |
| PENELEC |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
200795 to 200810 ckt 1 |
PN-P2_3-PN-230-0347-2
CONTINGENCY 'PN-P2_3-PN-230-0347-2' OPEN BRANCH FROM BUS 200793 TO BUS 200741 CKT 9 /*26SEWARD 2 230.0 - 26SEWARD 115.0 OPEN BRANCH FROM BUS 200793 TO BUS 200912 CKT 1 /*26SEWARD 2 230.0 - 26CONEMAGH 230.0 END |
Breaker | AC | 129.89 % | 132.02 % | 923.0 | B | 1218.55 | 23.02 | |
| PENELEC |
26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line
200522 to 938380 ckt 1 |
PL:10:P45:102437
CONTINGENCY 'PL:10:P45:102437' DISCONNECT BUS 208004 /*JUNI BU1 230.0 DISCONNECT BUS 208005 /*JUNI BU2 230.0 END |
Breaker | AC | 127.09 % | 130.75 % | 160.0 | B | 209.21 | 7.17 | |
| PENELEC |
KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
999338 to 200011 ckt 4 |
PN-P2-3-PN-500-004-DRT-003
CONTINGENCY 'PN-P2-3-PN-500-004-DRT-003' DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 DISCONNECT BUS 200033 /*KEYS G2 20.0 REMOVE MACHINE H FROM BUS 200033 /*KEYS G2 20.0 REMOVE MACHINE L FROM BUS 200033 /*KEYS G2 20.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE 500.0 - 01SOBEND 500.0 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET PRECONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE 500.0 - 01SOBEND 500.0 END |
Breaker | AC | 110.59 % | 112.31 % | 639.0 | B | 717.67 | 12.58 | |
| PENELEC |
KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
999338 to 200011 ckt 4 |
PN-P2-3-PN-500-004-DRT-004
CONTINGENCY 'PN-P2-3-PN-500-004-DRT-004' DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 DISCONNECT BUS 200032 /*KEYS G1 20.0 REMOVE MACHINE H FROM BUS 200032 /*KEYS G1 20.0 REMOVE MACHINE L FROM BUS 200032 /*KEYS G1 20.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE 500.0 - 01SOBEND 500.0 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET PRECONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE 500.0 - 01SOBEND 500.0 END |
Breaker | AC | 110.59 % | 112.31 % | 639.0 | B | 717.67 | 12.58 | |
| PENELEC |
KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
999338 to 200011 ckt 4 |
APS-P2-3-WP-500-DRT27
CONTINGENCY 'APS-P2-3-WP-500-DRT27' OPEN BRANCH FROM BUS 200011 TO BUS 200033 CKT 1 /*KEYSTONE 500.0 - KEYS G2 20.0 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND 500.0 - KEYSTONE 500.0 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET PRECONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND 500.0 - KEYSTONE 500.0 END |
Breaker | AC | 110.59 % | 112.31 % | 639.0 | B | 717.67 | 12.58 | |
| PENELEC |
KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
999338 to 200011 ckt 4 |
APS-P2-3-WP-500-DRT26
CONTINGENCY 'APS-P2-3-WP-500-DRT26' OPEN BRANCH FROM BUS 200011 TO BUS 200032 CKT 1 /*KEYSTONE 500.0 - KEYS G1 20.0 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND 500.0 - KEYSTONE 500.0 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET PRECONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND 500.0 - KEYSTONE 500.0 END |
Breaker | AC | 110.59 % | 112.31 % | 639.0 | B | 717.66 | 12.58 | |
| PENELEC |
26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line
200810 to 999338 ckt 4 |
PN-P2-3-PN-500-004-DRT-003
CONTINGENCY 'PN-P2-3-PN-500-004-DRT-003' DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 DISCONNECT BUS 200033 /*KEYS G2 20.0 REMOVE MACHINE H FROM BUS 200033 /*KEYS G2 20.0 REMOVE MACHINE L FROM BUS 200033 /*KEYS G2 20.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE 500.0 - 01SOBEND 500.0 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET PRECONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE 500.0 - 01SOBEND 500.0 END |
Breaker | AC | 110.66 % | 112.36 % | 639.0 | B | 717.98 | 12.58 | |
| PENELEC |
26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line
200810 to 999338 ckt 4 |
PN-P2-3-PN-500-004-DRT-004
CONTINGENCY 'PN-P2-3-PN-500-004-DRT-004' DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 DISCONNECT BUS 200032 /*KEYS G1 20.0 REMOVE MACHINE H FROM BUS 200032 /*KEYS G1 20.0 REMOVE MACHINE L FROM BUS 200032 /*KEYS G1 20.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE 500.0 - 01SOBEND 500.0 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET PRECONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE 500.0 - 01SOBEND 500.0 END |
Breaker | AC | 110.65 % | 112.36 % | 639.0 | B | 717.97 | 12.58 | |
| PENELEC |
26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line
200810 to 999338 ckt 4 |
APS-P2-3-WP-500-DRT27
CONTINGENCY 'APS-P2-3-WP-500-DRT27' OPEN BRANCH FROM BUS 200011 TO BUS 200033 CKT 1 /*KEYSTONE 500.0 - KEYS G2 20.0 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND 500.0 - KEYSTONE 500.0 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET PRECONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND 500.0 - KEYSTONE 500.0 END |
Breaker | AC | 110.65 % | 112.36 % | 639.0 | B | 717.97 | 12.58 | |
| PENELEC |
26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line
200810 to 999338 ckt 4 |
APS-P2-3-WP-500-DRT26
CONTINGENCY 'APS-P2-3-WP-500-DRT26' OPEN BRANCH FROM BUS 200011 TO BUS 200032 CKT 1 /*KEYSTONE 500.0 - KEYS G1 20.0 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND 500.0 - KEYSTONE 500.0 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE 500.0 - 01CABOT 500.0 SET PRECONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND 500.0 - KEYSTONE 500.0 END |
Breaker | AC | 110.65 % | 112.36 % | 639.0 | B | 717.96 | 12.58 | |
| PENELEC |
AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line
941190 to 200582 ckt 1 |
PN-P2-3-PN-230-8I
CONTINGENCY 'PN-P2-3-PN-230-8I' DISCONNECT BRANCH FROM BUS 200581 TO BUS 200593 CKT 1 /*26FOREST 230.0 - 26GLADE 230.0 DISCONNECT BRANCH FROM BUS 200593 TO BUS 200704 CKT 1 /*26GLADE 230.0 - 26LEWIS RN 230.0 END |
Breaker | AC | 112.56 % | 114.31 % | 160.0 | B | 182.89 | 3.19 | |
| PENELEC |
26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer
999333 to 200710 ckt 1A |
PN-P2-3-PN-230-21AT
CONTINGENCY 'PN-P2-3-PN-230-21AT' DISCONNECT BRANCH FROM BUS 200666 TO BUS 200726 CKT 1 /*26SHAWVL 4 22.0 - 26SHAWVL 2 230.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 200726 CKT ZB /*26SHAWVL 1 230.0 - 26SHAWVL 2 230.0 DISCONNECT BRANCH FROM BUS 200726 TO BUS 200727 TO BUS 200722 CKT 2A /*26SHAWVL 2 230.0 - 26SHAW. 2 115.0 - 26SHAWVL 2 18.0 DISCONNECT BRANCH FROM BUS 200726 TO BUS 235175 CKT 1 /*26SHAWVL 2 230.0 - 01ELKO 230.0 DISCONNECT BRANCH FROM BUS 200726 TO BUS 235248 CKT 1 /*26SHAWVL 2 230.0 - 01SHINGL 230.0 END |
Breaker | AC | 95.69 % | 111.14 % | 201.0 | B | 223.38 | 31.74 | |
| PENELEC |
26GLADE-26WARREN 230.0 kV Ckt 1 line
200593 to 200811 ckt 1 |
PN-P2_3-PN-345-997-DRT-031
CONTINGENCY 'PN-P2_3-PN-345-997-DRT-031' DISCONNECT BRANCH FROM BUS 200595 TO BUS 200598 CKT 2 /*26WAYNE 345.0 - 26WAYNE 115.0 DISCONNECT BRANCH FROM BUS 200595 TO BUS 200826 CKT 1 /*26WAYNE 345.0 - 26HANDSMLK 345.0 SET POSTCONTRATING 1170 BRANCH FROM BUS 200599 TO BUS 200595 CKT 1 /*26ERIE W 345.0 - 26WAYNE 345.0 SET PRECONTRATING 915 BRANCH FROM BUS 200599 TO BUS 200595 CKT 1 /*26ERIE W 345.0 - 26WAYNE 345.0 END |
Breaker | AC | 111.91 % | 113.07 % | 666.0 | B | 753.07 | 9.3 | |
| PENELEC |
26GLADE-26WARREN 230.0 kV Ckt 1 line
200593 to 200811 ckt 1 |
PN-P2-3-PN-345-003A-B45
CONTINGENCY 'PN-P2-3-PN-345-003A-B45' DISCONNECT BRANCH FROM BUS 200826 TO BUS 200595 CKT 1 /*26HANDSMLK 345.0 - 26WAYNE 345.0 OPEN BRANCH FROM BUS 200598 TO BUS 200595 CKT 1 /*26WAYNE 115.0 - 26WAYNE 345.0 SET POSTCONTRATING 1170 BRANCH FROM BUS 200599 TO BUS 200595 CKT 1 /*26ERIE W 345.0 - 26WAYNE 345.0 SET PRECONTRATING 915 BRANCH FROM BUS 200599 TO BUS 200595 CKT 1 /*26ERIE W 345.0 - 26WAYNE 345.0 END |
Breaker | AC | 111.87 % | 113.04 % | 666.0 | B | 752.83 | 9.29 | |
| PENELEC |
26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line
999333 to 200714 ckt 1A |
PN-P2-3-PN-230-21HT
CONTINGENCY 'PN-P2-3-PN-230-21HT' DISCONNECT BRANCH FROM BUS 200666 TO BUS 200726 CKT 1 /*26SHAWVL 4 22.0 - 26SHAWVL 2 230.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 200726 CKT ZB /*26SHAWVL 1 230.0 - 26SHAWVL 2 230.0 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200722 CKT 2B /*26SHAWVL 1 115.0 - 26SHAWVL 2 18.0 DISCONNECT BRANCH FROM BUS 200726 TO BUS 200727 TO BUS 200722 CKT 2A /*26SHAWVL 2 230.0 - 26SHAW. 2 115.0 - 26SHAWVL 2 18.0 DISCONNECT BRANCH FROM BUS 200726 TO BUS 235175 CKT 1 /*26SHAWVL 2 230.0 - 01ELKO 230.0 DISCONNECT BRANCH FROM BUS 200726 TO BUS 235248 CKT 1 /*26SHAWVL 2 230.0 - 01SHINGL 230.0 END |
Breaker | AC | 98.93 % | 108.7 % | 126.0 | B | 136.96 | 11.84 | |
| PENELEC |
26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer
999332 to 200726 ckt 2A |
PN-P2-2-PN-230-013T
CONTINGENCY 'PN-P2-2-PN-230-013T' DISCONNECT BRANCH FROM BUS 200710 TO BUS 200665 CKT 1 /*26SHAWVL 1 230.0 - 26SHAWVL 3 22.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 200726 CKT ZB /*26SHAWVL 1 230.0 - 26SHAWVL 2 230.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 944320 CKT 1 /*26SHAWVL 1 230.0 - AF1-100 TAP 230.0 END |
Bus | AC | 151.62 % | 172.96 % | 149.0 | B | 257.71 | 32.77 | |
| PENELEC |
AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line
938380 to 200520 ckt 1 |
PL:10:P24:100548
CONTINGENCY 'PL:10:P24:100548' DISCONNECT BUS 208004 /*JUNI BU1 230.0 DISCONNECT BUS 208005 /*JUNI BU2 230.0 END |
Bus | AC | 170.84 % | 174.5 % | 160.0 | B | 279.19 | 7.14 | |
| PENELEC |
26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer
999332 to 200726 ckt 2A |
PN-P2-2-PN-115-062T
CONTINGENCY 'PN-P2-2-PN-115-062T' DISCONNECT BRANCH FROM BUS 200555 TO BUS 200714 TO BUS 200913 CKT 14 /*26SHAW.NO1 34.5 - 26SHAWVL 1 115.0 - 26SHAW-D 4.2 DISCONNECT BRANCH FROM BUS 200710 TO BUS 200714 TO BUS 200715 CKT 1A /*26SHAWVL 1 230.0 - 26SHAWVL 1 115.0 - 26SHAWVL 1 18.0 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200713 CKT 1 /*26SHAWVL 1 115.0 - 26ROCKTON 115.0 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200715 CKT 1B /*26SHAWVL 1 115.0 - 26SHAWVL 1 18.0 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200722 CKT 2B /*26SHAWVL 1 115.0 - 26SHAWVL 2 18.0 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200727 CKT ZB /*26SHAWVL 1 115.0 - 26SHAW. 2 115.0 DISCONNECT BRANCH FROM BUS 200714 TO BUS 200872 CKT 1 /*26SHAWVL 1 115.0 - 26BIOEN TP 115.0 REDUCE BUS 200714 SHUNT BY 100 PERCENT /*26SHAWVL 1 115.0 END |
Bus | AC | 108.01 % | 140.37 % | 149.0 | B | 209.15 | 52.03 | |
| PENELEC |
26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line
200522 to 938380 ckt 1 |
PL:10:P24:100548
CONTINGENCY 'PL:10:P24:100548' DISCONNECT BUS 208004 /*JUNI BU1 230.0 DISCONNECT BUS 208005 /*JUNI BU2 230.0 END |
Bus | AC | 127.38 % | 131.02 % | 160.0 | B | 209.63 | 7.17 | |
| PENELEC |
26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer
999333 to 200710 ckt 1A |
PN-P2-2-PN-230-014T
CONTINGENCY 'PN-P2-2-PN-230-014T' DISCONNECT BRANCH FROM BUS 200726 TO BUS 200666 CKT 1 /*26SHAWVL 2 230.0 - 26SHAWVL 4 22.0 DISCONNECT BRANCH FROM BUS 200726 TO BUS 200710 CKT ZB /*26SHAWVL 2 230.0 - 26SHAWVL 1 230.0 DISCONNECT BRANCH FROM BUS 200726 TO BUS 235175 CKT 1 /*26SHAWVL 2 230.0 - 01ELKO 230.0 DISCONNECT BRANCH FROM BUS 200726 TO BUS 235248 CKT 1 /*26SHAWVL 2 230.0 - 01SHINGL 230.0 END |
Bus | AC | 96.25 % | 111.54 % | 201.0 | B | 224.2 | 31.74 | |
| PENELEC |
AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line
941190 to 200582 ckt 1 |
PN-P7-1-PN-230-002A
CONTINGENCY 'PN-P7-1-PN-230-002A' DISCONNECT BRANCH FROM BUS 200593 TO BUS 200581 CKT 1 /*26GLADE 230.0 - 26FOREST 230.0 DISCONNECT BRANCH FROM BUS 200593 TO BUS 200704 CKT 1 /*26GLADE 230.0 - 26LEWIS RN 230.0 END |
Tower | AC | 112.56 % | 114.31 % | 160.0 | B | 182.89 | 3.19 | |
| AP |
01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line
235248 to 966040 ckt 1 |
PN-P2_1-PN-230-997-DRT-063
CONTINGENCY 'PN-P2_1-PN-230-997-DRT-063' DISCONNECT BRANCH FROM BUS 200706 TO BUS 200708 CKT 1 /*26N.MESHPN 230.0 - 26OXBOW 230.0 DISCONNECT BRANCH FROM BUS 200708 TO BUS 200709 CKT 1 /*26OXBOW 230.0 - 26OXBOW 34.5 SET POSTCONTRATING 498 BRANCH FROM BUS 200706 TO BUS 200924 CKT 1 /*26N.MESHPN 230.0 - 26CANYON 230.0 SET PRECONTRATING 498 BRANCH FROM BUS 200706 TO BUS 200924 CKT 1 /*26N.MESHPN 230.0 - 26CANYON 230.0 END |
Breaker | AC | 133.2 % | 136.11 % | 621.0 | B | 845.24 | 18.73 | |
| Details for AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 962411 | AG1-090 C O1 | 80/20 | 5.71 MW | 5.71 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 964031 | AG1-257 C | 80/20 | 1.01 MW | 1.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 964201 | AG1-281 C | 80/20 | 0.68 MW | 0.68 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 964391 | AG1-301 C | 80/20 | 1.26 MW | 1.26 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 965121 | AG1-377 C O1 | 80/20 | 0.86 MW | 0.86 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 965131 | AG1-378 C O1 | 80/20 | 0.86 MW | 0.86 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 966041 | AG1-473 C | 80/20 | 5.0 MW | 5.0 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 934371 | AD1-061 C | Adder | -0.47 MW | -0.4 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 936061 | AD2-009 C | Adder | -3.22 MW | -2.74 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 936991 | AD2-133 C | 80/20 | 1.07 MW | 1.07 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 942121 | AE2-224 C | 80/20 | 3.48 MW | 3.48 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 942351 | AE2-248 C | 80/20 | 1.18 MW | 1.18 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 942491 | AE2-262 C | 80/20 | 4.97 MW | 4.97 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 942501 | AE2-263 C | 80/20 | 4.67 MW | 4.67 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 944311 | AF1-099 C | 80/20 | 6.94 MW | 6.94 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 944321 | AF1-100 C | 80/20 | 12.78 MW | 12.78 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 944471 | AF1-112 C | 80/20 | 1.09 MW | 1.09 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 944691 | AF1-134 C | 80/20 | 0.7 MW | 0.7 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 944771 | AF1-142 C | 80/20 | 11.11 MW | 11.11 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 944881 | AF1-153 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 944901 | AF1-155 C | 80/20 | 0.77 MW | 0.77 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 945161 | AF1-181 | 80/20 | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 945171 | AF1-182 | 80/20 | 0.06 MW | 0.06 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 945181 | AF1-183 | 80/20 | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 945591 | AF1-224 C | Adder | -0.5 MW | -0.43 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 958871 | AF2-178 | Adder | -0.91 MW | -0.78 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 958881 | AF2-179 | Adder | -0.4 MW | -0.34 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 958891 | AF2-180 | Adder | -0.4 MW | -0.34 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 958931 | AF2-184 | Adder | -0.36 MW | -0.3 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 958941 | AF2-185 | Adder | -0.22 MW | -0.19 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 960041 | AF2-295 C | 80/20 | 0.77 MW | 0.77 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 960051 | AF2-296 C | 80/20 | 0.7 MW | 0.7 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 200649 | 26PENNTECH | 80/20 | 0.44 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 200665 | 26SHAWVL 3 | 80/20 | 2.54 MW | 2.54 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 200666 | 26SHAWVL 4 | 80/20 | 2.5 MW | 2.5 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 200715 | 26SHAWVL 1 | 80/20 | 1.68 MW | 1.68 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 200722 | 26SHAWVL 2 | 80/20 | 1.72 MW | 1.72 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 200913 | 26SHAW-D | 80/20 | 0.08 MW | 0.08 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 938384 | AE1-071-C | 80/20 | 6.65 MW | 6.65 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 939591 | AE1-188 C | Adder | -0.8 MW | -0.68 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 940201 | AE2-001 C | 80/20 | 1.43 MW | 1.43 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 940671 | AE2-054 C | Adder | -0.73 MW | -0.62 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 940681 | AE2-055 C | 80/20 | 1.5 MW | 1.5 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 941231 | AE2-117 C | 80/20 | 1.22 MW | 1.22 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 941241 | AE2-118 C | 80/20 | 1.16 MW | 1.16 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 941271 | AE2-121 C | 80/20 | 0.76 MW | 0.76 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 941321 | AE2-126 C | 80/20 | 0.82 MW | 0.82 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 941331 | AE2-129 C | 80/20 | 0.86 MW | 0.86 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 941351 | AE2-131 C | 80/20 | 0.86 MW | 0.86 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 957451 | AF2-039 C | 80/20 | 0.61 MW | 0.61 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 957561 | AF2-050 C | 80/20 | 1.74 MW | 1.74 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 957931 | AF2-087 C | 80/20 | 0.22 MW | 0.22 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 957941 | AF2-088 C | 80/20 | 0.29 MW | 0.29 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 958271 | AF2-121 C | 80/20 | 0.86 MW | 0.86 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 200812 | 26ALY HYDR | 80/20 | 0.44 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 200886 | 26ARWF_N39 | 80/20 | 0.12 MW | 0.12 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 200915 | 26CHSTN_FL | 80/20 | 0.06 MW | 0.06 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 203034 | 26NA_O38_P22 | 80/20 | 0.11 MW | 0.11 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 938751 | AE1-101 C | Adder | -7.14 MW | -6.07 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 964451 | AG1-308 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 946421 | AF2-000A C | 80/20 | 3.36 MW | 3.36 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | 200905 | 26Q36 | 80/20 | 0.1 MW | 0.1 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.17 MW | 0.17 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.05 MW | 0.05 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.89 MW | 0.89 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.06 MW | 2.06 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.42 MW | 0.42 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.11 MW | 0.11 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.02 MW | 0.02 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P13:100618 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 962411 | AG1-090 C O1 | 80/20 | 5.7 MW | 5.7 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 964031 | AG1-257 C | 80/20 | 1.01 MW | 1.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 964201 | AG1-281 C | 80/20 | 0.68 MW | 0.68 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 964391 | AG1-301 C | 80/20 | 1.26 MW | 1.26 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 965121 | AG1-377 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 965131 | AG1-378 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 966041 | AG1-473 C | 80/20 | 5.0 MW | 5.0 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 934371 | AD1-061 C | Adder | -0.47 MW | -0.4 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 936061 | AD2-009 C | Adder | -3.22 MW | -2.74 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 936991 | AD2-133 C | 80/20 | 1.07 MW | 1.07 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 942121 | AE2-224 C | 80/20 | 3.48 MW | 3.48 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 942351 | AE2-248 C | 80/20 | 1.18 MW | 1.18 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 942491 | AE2-262 C | 80/20 | 4.96 MW | 4.96 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 942501 | AE2-263 C | 80/20 | 4.67 MW | 4.67 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 944311 | AF1-099 C | 80/20 | 6.94 MW | 6.94 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 944321 | AF1-100 C | 80/20 | 12.78 MW | 12.78 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 944471 | AF1-112 C | 80/20 | 1.09 MW | 1.09 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 944691 | AF1-134 C | 80/20 | 0.7 MW | 0.7 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 944771 | AF1-142 C | 80/20 | 11.1 MW | 11.1 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 944881 | AF1-153 C O1 | 80/20 | 0.77 MW | 0.77 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 944901 | AF1-155 C | 80/20 | 0.77 MW | 0.77 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 945161 | AF1-181 | 80/20 | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 945171 | AF1-182 | 80/20 | 0.06 MW | 0.06 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 945181 | AF1-183 | 80/20 | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 945591 | AF1-224 C | Adder | -0.5 MW | -0.43 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 958871 | AF2-178 | Adder | -0.91 MW | -0.78 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 958881 | AF2-179 | Adder | -0.4 MW | -0.34 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 958891 | AF2-180 | Adder | -0.4 MW | -0.34 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 958931 | AF2-184 | Adder | -0.36 MW | -0.3 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 960041 | AF2-295 C | 80/20 | 0.77 MW | 0.77 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 960051 | AF2-296 C | 80/20 | 0.7 MW | 0.7 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 200649 | 26PENNTECH | 80/20 | 0.44 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 200665 | 26SHAWVL 3 | 80/20 | 2.54 MW | 2.54 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 200666 | 26SHAWVL 4 | 80/20 | 2.5 MW | 2.5 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 200715 | 26SHAWVL 1 | 80/20 | 1.68 MW | 1.68 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 200722 | 26SHAWVL 2 | 80/20 | 1.71 MW | 1.71 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 200913 | 26SHAW-D | 80/20 | 0.08 MW | 0.08 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 938384 | AE1-071-C | 80/20 | 6.65 MW | 6.65 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 939591 | AE1-188 C | Adder | -0.8 MW | -0.68 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 940201 | AE2-001 C | 80/20 | 1.43 MW | 1.43 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 940671 | AE2-054 C | Adder | -0.73 MW | -0.62 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 940681 | AE2-055 C | 80/20 | 1.5 MW | 1.5 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 941231 | AE2-117 C | 80/20 | 1.22 MW | 1.22 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 941241 | AE2-118 C | 80/20 | 1.16 MW | 1.16 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 941271 | AE2-121 C | 80/20 | 0.76 MW | 0.76 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 941321 | AE2-126 C | 80/20 | 0.81 MW | 0.81 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 941331 | AE2-129 C | 80/20 | 0.85 MW | 0.85 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 941351 | AE2-131 C | 80/20 | 0.85 MW | 0.85 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 957451 | AF2-039 C | 80/20 | 0.61 MW | 0.61 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 957561 | AF2-050 C | 80/20 | 1.74 MW | 1.74 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 957931 | AF2-087 C | 80/20 | 0.22 MW | 0.22 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 957941 | AF2-088 C | 80/20 | 0.29 MW | 0.29 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 958271 | AF2-121 C | 80/20 | 0.85 MW | 0.85 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 200812 | 26ALY HYDR | 80/20 | 0.44 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 200886 | 26ARWF_N39 | 80/20 | 0.12 MW | 0.12 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 200915 | 26CHSTN_FL | 80/20 | 0.06 MW | 0.06 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 203034 | 26NA_O38_P22 | 80/20 | 0.11 MW | 0.11 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 938751 | AE1-101 C | Adder | -7.13 MW | -6.06 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 964451 | AG1-308 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 946421 | AF2-000A C | 80/20 | 3.36 MW | 3.36 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | 200905 | 26Q36 | 80/20 | 0.1 MW | 0.1 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.17 MW | 0.17 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.05 MW | 0.05 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.89 MW | 0.89 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.03 MW | 2.03 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.4 MW | 0.4 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.11 MW | 0.11 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.02 MW | 0.02 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.0 MW | 0.0 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-103AT | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 962411 | AG1-090 C O1 | Adder | 5.95 MW | 5.06 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 964031 | AG1-257 C | Adder | 0.65 MW | 0.55 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 965121 | AG1-377 C O1 | Adder | 0.89 MW | 0.76 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 965131 | AG1-378 C O1 | Adder | 0.89 MW | 0.76 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 965241 | AG1-392C C O | 80/20 | 1.93 MW | 1.93 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 965251 | AG1-392B C O | 80/20 | 1.93 MW | 1.93 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 965261 | AG1-392A C O | 80/20 | 3.86 MW | 3.86 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 965271 | AG1-392 C O1 | 80/20 | 3.86 MW | 3.86 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 942351 | AE2-248 C | Adder | 0.74 MW | 0.63 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 942491 | AE2-262 C | 80/20 | 4.93 MW | 4.93 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 942501 | AE2-263 C | 80/20 | 4.63 MW | 4.63 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 942961 | AE2-316 C | Adder | 3.08 MW | 2.62 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944311 | AF1-099 C | 80/20 | 8.02 MW | 8.02 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944321 | AF1-100 C | 80/20 | 15.39 MW | 15.39 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944411 | AF1-106 O1 | 80/20 | 5.16 MW | 5.16 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944471 | AF1-112 C | Adder | 0.69 MW | 0.59 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944771 | AF1-142 C | 80/20 | 12.84 MW | 12.84 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944881 | AF1-153 C O1 | 80/20 | 1.09 MW | 1.09 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944901 | AF1-155 C | 80/20 | 1.08 MW | 1.08 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 945161 | AF1-181 | 80/20 | 0.01 MW | 0.01 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 945171 | AF1-182 | 80/20 | 0.07 MW | 0.07 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 945181 | AF1-183 | 80/20 | 0.02 MW | 0.02 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 945331 | AF1-198 | 80/20 | 0.11 MW | 0.11 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 959471 | AF2-238 C | 80/20 | 3.16 MW | 3.16 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 960041 | AF2-295 C | 80/20 | 1.08 MW | 1.08 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 961141 | AF2-405 | 80/20 | 2.58 MW | 2.58 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 961151 | AF2-406 | 80/20 | 19.35 MW | 19.35 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 961211 | AF2-412 | 80/20 | 28.31 MW | 28.31 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 961451 | AF2-436 | 80/20 | 0.17 MW | 0.17 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200642 | 26SENECA#1 | 80/20 | 3.5 MW | 3.5 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200643 | 26SENECA#2 | 80/20 | 3.13 MW | 3.13 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200644 | 26SENECA#3 | 80/20 | 0.34 MW | 0.34 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200649 | 26PENNTECH | 80/20 | 0.69 MW | 0.69 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200665 | 26SHAWVL 3 | 80/20 | 2.95 MW | 2.95 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200666 | 26SHAWVL 4 | 80/20 | 2.88 MW | 2.88 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200715 | 26SHAWVL 1 | 80/20 | 1.95 MW | 1.95 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200722 | 26SHAWVL 2 | 80/20 | 1.98 MW | 1.98 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200887 | 26ARMNA MT | 80/20 | 0.66 MW | 0.66 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200913 | 26SHAW-D | 80/20 | 0.09 MW | 0.09 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203261 | 26BLOSSBCT | 80/20 | 0.82 MW | 0.82 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203283 | 26MANOR_T86 | 80/20 | 0.06 MW | 0.06 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203349 | 26Z1-069 C | 80/20 | 0.38 MW | 0.38 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203350 | 26MILZ1-092 | 80/20 | 0.93 MW | 0.93 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203351 | 26GROZ1-110 | 80/20 | 1.13 MW | 1.13 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203352 | 26CANZ2-011 | 80/20 | 1.11 MW | 1.11 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203922 | X1-109 G1 | 80/20 | 25.9 MW | 25.9 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203923 | X1-109 G2 | 80/20 | 25.9 MW | 25.9 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203932 | AA2-133 GEN | 80/20 | 2.27 MW | 2.27 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 931091 | AB1-160 C | 80/20 | 0.11 MW | 0.11 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 940201 | AE2-001 C | 80/20 | 0.97 MW | 0.97 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 940681 | AE2-055 C | Adder | 0.9 MW | 0.77 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 940861 | AE2-074 C | 80/20 | 2.09 MW | 2.09 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941191 | AE2-113 C | 80/20 | 6.38 MW | 6.38 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941271 | AE2-121 C | 80/20 | 0.52 MW | 0.52 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941321 | AE2-126 C | 80/20 | 1.1 MW | 1.1 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941331 | AE2-129 C | Adder | 0.89 MW | 0.76 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941351 | AE2-131 C | Adder | 0.89 MW | 0.76 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941421 | AE2-139 C | 80/20 | 23.54 MW | 23.54 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 946111 | AF1-276 C | 80/20 | 6.58 MW | 6.58 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 946121 | AF1-277 C | 80/20 | 6.58 MW | 6.58 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 946131 | AF1-278 C | 80/20 | 5.25 MW | 5.25 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 946381 | AF1-302 C | Adder | 1.35 MW | 1.14 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 957451 | AF2-039 C | 80/20 | 0.71 MW | 0.71 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 957941 | AF2-088 C | 80/20 | 0.34 MW | 0.34 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 958271 | AF2-121 C | Adder | 0.89 MW | 0.76 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 964451 | AG1-308 C O1 | Adder | 0.62 MW | 0.53 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 946421 | AF2-000A C | 80/20 | 4.75 MW | 4.75 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.28 MW | 0.28 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 3.9 MW | 3.9 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.36 MW | 0.36 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.36 MW | 7.36 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 15.91 MW | 15.91 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.84 MW | 8.84 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.41 MW | 0.41 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.64 MW | 1.64 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.67 MW | 1.67 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.34 MW | 0.34 MW |
| Details for 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 962411 | AG1-090 C O1 | Adder | 5.95 MW | 5.06 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 964031 | AG1-257 C | Adder | 0.65 MW | 0.55 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 965121 | AG1-377 C O1 | Adder | 0.89 MW | 0.76 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 965131 | AG1-378 C O1 | Adder | 0.89 MW | 0.76 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 965241 | AG1-392C C O | 80/20 | 1.93 MW | 1.93 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 965251 | AG1-392B C O | 80/20 | 1.93 MW | 1.93 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 965261 | AG1-392A C O | 80/20 | 3.86 MW | 3.86 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 965271 | AG1-392 C O1 | 80/20 | 3.86 MW | 3.86 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 942351 | AE2-248 C | Adder | 0.74 MW | 0.63 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 942491 | AE2-262 C | 80/20 | 4.93 MW | 4.93 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 942501 | AE2-263 C | 80/20 | 4.63 MW | 4.63 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 942961 | AE2-316 C | Adder | 3.08 MW | 2.62 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 944311 | AF1-099 C | 80/20 | 8.02 MW | 8.02 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 944321 | AF1-100 C | 80/20 | 15.39 MW | 15.39 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 944411 | AF1-106 O1 | 80/20 | 5.16 MW | 5.16 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 944471 | AF1-112 C | Adder | 0.69 MW | 0.59 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 944771 | AF1-142 C | 80/20 | 12.84 MW | 12.84 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 944881 | AF1-153 C O1 | 80/20 | 1.09 MW | 1.09 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 944901 | AF1-155 C | 80/20 | 1.08 MW | 1.08 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 945161 | AF1-181 | 80/20 | 0.01 MW | 0.01 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 945171 | AF1-182 | 80/20 | 0.07 MW | 0.07 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 945181 | AF1-183 | 80/20 | 0.02 MW | 0.02 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 945331 | AF1-198 | 80/20 | 0.11 MW | 0.11 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 959471 | AF2-238 C | 80/20 | 3.16 MW | 3.16 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 960041 | AF2-295 C | 80/20 | 1.08 MW | 1.08 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 961141 | AF2-405 | 80/20 | 2.58 MW | 2.58 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 961151 | AF2-406 | 80/20 | 19.35 MW | 19.35 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 961211 | AF2-412 | 80/20 | 28.31 MW | 28.31 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 961451 | AF2-436 | 80/20 | 0.17 MW | 0.17 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 200642 | 26SENECA#1 | 80/20 | 3.5 MW | 3.5 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 200643 | 26SENECA#2 | 80/20 | 3.13 MW | 3.13 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 200644 | 26SENECA#3 | 80/20 | 0.34 MW | 0.34 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 200649 | 26PENNTECH | 80/20 | 0.69 MW | 0.69 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 200665 | 26SHAWVL 3 | 80/20 | 2.95 MW | 2.95 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 200666 | 26SHAWVL 4 | 80/20 | 2.88 MW | 2.88 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 200715 | 26SHAWVL 1 | 80/20 | 1.95 MW | 1.95 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 200722 | 26SHAWVL 2 | 80/20 | 1.98 MW | 1.98 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 200887 | 26ARMNA MT | 80/20 | 0.66 MW | 0.66 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 200913 | 26SHAW-D | 80/20 | 0.09 MW | 0.09 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 203261 | 26BLOSSBCT | 80/20 | 0.82 MW | 0.82 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 203283 | 26MANOR_T86 | 80/20 | 0.06 MW | 0.06 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 203349 | 26Z1-069 C | 80/20 | 0.38 MW | 0.38 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 203350 | 26MILZ1-092 | 80/20 | 0.93 MW | 0.93 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 203351 | 26GROZ1-110 | 80/20 | 1.13 MW | 1.13 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 203352 | 26CANZ2-011 | 80/20 | 1.11 MW | 1.11 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 203922 | X1-109 G1 | 80/20 | 25.9 MW | 25.9 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 203923 | X1-109 G2 | 80/20 | 25.9 MW | 25.9 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 203932 | AA2-133 GEN | 80/20 | 2.27 MW | 2.27 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 931091 | AB1-160 C | 80/20 | 0.11 MW | 0.11 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 940201 | AE2-001 C | 80/20 | 0.97 MW | 0.97 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 940681 | AE2-055 C | Adder | 0.9 MW | 0.77 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 940861 | AE2-074 C | 80/20 | 2.09 MW | 2.09 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 941191 | AE2-113 C | 80/20 | 6.38 MW | 6.38 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 941271 | AE2-121 C | 80/20 | 0.52 MW | 0.52 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 941321 | AE2-126 C | 80/20 | 1.1 MW | 1.1 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 941331 | AE2-129 C | Adder | 0.89 MW | 0.76 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 941351 | AE2-131 C | Adder | 0.89 MW | 0.76 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 941421 | AE2-139 C | 80/20 | 23.54 MW | 23.54 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 946111 | AF1-276 C | 80/20 | 6.58 MW | 6.58 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 946121 | AF1-277 C | 80/20 | 6.58 MW | 6.58 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 946131 | AF1-278 C | 80/20 | 5.25 MW | 5.25 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 946381 | AF1-302 C | Adder | 1.35 MW | 1.14 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 957451 | AF2-039 C | 80/20 | 0.71 MW | 0.71 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 957941 | AF2-088 C | 80/20 | 0.34 MW | 0.34 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 958271 | AF2-121 C | Adder | 0.89 MW | 0.76 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 964451 | AG1-308 C O1 | Adder | 0.62 MW | 0.53 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | 946421 | AF2-000A C | 80/20 | 4.75 MW | 4.75 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.28 MW | 0.28 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 3.9 MW | 3.9 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.36 MW | 0.36 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.36 MW | 7.36 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 15.91 MW | 15.91 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.84 MW | 8.84 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.41 MW | 0.41 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.64 MW | 1.64 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.67 MW | 1.67 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| 26CANYON-26N.MESHPN 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.34 MW | 0.34 MW |
| Details for AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 962411 | AG1-090 C O1 | Adder | 5.71 MW | 4.86 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 962412 | AG1-090 E O1 | Adder | 1.43 MW | 1.21 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964031 | AG1-257 C | 50/50 | 1.01 MW | 1.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964032 | AG1-257 E | 50/50 | 1.41 MW | 1.41 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964201 | AG1-281 C | Adder | 0.68 MW | 0.58 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964202 | AG1-281 E | Adder | 0.45 MW | 0.39 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964391 | AG1-301 C | 50/50 | 1.26 MW | 1.26 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964392 | AG1-301 E | 50/50 | 0.84 MW | 0.84 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 965121 | AG1-377 C O1 | Adder | 0.86 MW | 0.73 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 965122 | AG1-377 E O1 | Adder | 0.57 MW | 0.49 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 965131 | AG1-378 C O1 | Adder | 0.86 MW | 0.73 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 965132 | AG1-378 E O1 | Adder | 0.57 MW | 0.49 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 966041 | AG1-473 C | 50/50 | 5.0 MW | 5.0 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 966042 | AG1-473 E | 50/50 | 3.33 MW | 3.33 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 290086 | Q-036 E | Adder | 2.85 MW | 2.42 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 934371 | AD1-061 C | Adder | -0.47 MW | -0.4 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 936061 | AD2-009 C | Adder | -3.23 MW | -2.74 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 936991 | AD2-133 C | Adder | 1.07 MW | 0.91 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 936992 | AD2-133 E | Adder | 4.92 MW | 4.18 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942121 | AE2-224 C | Adder | 3.49 MW | 2.96 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942122 | AE2-224 E | Adder | 2.32 MW | 1.98 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942351 | AE2-248 C | 50/50 | 1.18 MW | 1.18 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942352 | AE2-248 E | 50/50 | 0.79 MW | 0.79 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942491 | AE2-262 C | Adder | 4.97 MW | 4.22 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942492 | AE2-262 E | Adder | 3.34 MW | 2.84 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942501 | AE2-263 C | Adder | 4.67 MW | 3.97 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942502 | AE2-263 E | Adder | 3.12 MW | 2.65 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944311 | AF1-099 C | Adder | 6.95 MW | 5.91 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944312 | AF1-099 E | Adder | 4.63 MW | 3.94 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944321 | AF1-100 C | Adder | 12.8 MW | 10.88 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944322 | AF1-100 E | Adder | 8.53 MW | 7.25 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944471 | AF1-112 C | 50/50 | 1.09 MW | 1.09 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944472 | AF1-112 E | 50/50 | 0.75 MW | 0.75 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944691 | AF1-134 C | Adder | 0.7 MW | 0.59 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944692 | AF1-134 E | Adder | 0.46 MW | 0.4 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944771 | AF1-142 C | Adder | 11.12 MW | 9.45 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944772 | AF1-142 E | Adder | 7.41 MW | 6.3 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944881 | AF1-153 C O1 | Adder | 0.78 MW | 0.66 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944882 | AF1-153 E O1 | Adder | 0.52 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944901 | AF1-155 C | Adder | 0.77 MW | 0.66 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944902 | AF1-155 E | Adder | 0.51 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 945591 | AF1-224 C | Adder | -0.5 MW | -0.43 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958871 | AF2-178 | Adder | -0.91 MW | -0.78 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958881 | AF2-179 | Adder | -0.4 MW | -0.34 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958891 | AF2-180 | Adder | -0.4 MW | -0.34 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958931 | AF2-184 | Adder | -0.36 MW | -0.3 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958941 | AF2-185 | Adder | -0.22 MW | -0.19 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 959802 | AF2-271 E | Adder | 0.28 MW | 0.24 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 960022 | AF2-293 E | 50/50 | 0.14 MW | 0.14 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 960041 | AF2-295 C | Adder | 0.77 MW | 0.66 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 960042 | AF2-295 E | Adder | 0.51 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 960051 | AF2-296 C | Adder | 0.7 MW | 0.59 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 960052 | AF2-296 E | Adder | 0.46 MW | 0.4 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 200852 | 26WARR RDG | 50/50 | 0.26 MW | 0.26 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 200883 | Q-053 E | Adder | 1.66 MW | 1.41 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 235003 | AC1-025 E | 50/50 | 0.19 MW | 0.19 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 236828 | 01GRAYMONT | 50/50 | 0.48 MW | 0.48 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 293301 | N-039 E | Adder | 4.28 MW | 3.64 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 294515 | O38_P22 | Adder | 3.74 MW | 3.18 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 938384 | AE1-071-C | 50/50 | 6.65 MW | 6.65 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 939591 | AE1-188 C | Adder | -0.8 MW | -0.68 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 940201 | AE2-001 C | 50/50 | 1.43 MW | 1.43 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 940202 | AE2-001 E | 50/50 | 0.96 MW | 0.96 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 940671 | AE2-054 C | Adder | -0.73 MW | -0.62 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 940681 | AE2-055 C | 50/50 | 1.5 MW | 1.5 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 940682 | AE2-055 E | 50/50 | 1.0 MW | 1.0 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941231 | AE2-117 C | 50/50 | 1.23 MW | 1.23 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941232 | AE2-117 E | 50/50 | 0.82 MW | 0.82 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941241 | AE2-118 C | Adder | 1.16 MW | 0.99 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941242 | AE2-118 E | Adder | 0.78 MW | 0.66 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941271 | AE2-121 C | 50/50 | 0.76 MW | 0.76 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941272 | AE2-121 E | 50/50 | 0.5 MW | 0.5 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941321 | AE2-126 C | Adder | 0.82 MW | 0.69 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941322 | AE2-126 E | Adder | 0.54 MW | 0.46 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941331 | AE2-129 C | Adder | 0.86 MW | 0.73 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941332 | AE2-129 E | Adder | 0.57 MW | 0.49 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941351 | AE2-131 C | Adder | 0.86 MW | 0.73 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941352 | AE2-131 E | Adder | 0.57 MW | 0.49 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957451 | AF2-039 C | Adder | 0.61 MW | 0.52 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957452 | AF2-039 E | Adder | 0.4 MW | 0.34 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957561 | AF2-050 C | Adder | 1.74 MW | 1.48 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957562 | AF2-050 E | Adder | 1.16 MW | 0.99 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957931 | AF2-087 C | Adder | 0.22 MW | 0.19 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957932 | AF2-087 E | Adder | 0.31 MW | 0.26 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957941 | AF2-088 C | Adder | 0.29 MW | 0.25 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957942 | AF2-088 E | Adder | 0.2 MW | 0.17 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958271 | AF2-121 C | Adder | 0.86 MW | 0.73 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958272 | AF2-121 E | Adder | 0.57 MW | 0.49 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 200812 | 26ALY HYDR | 50/50 | 0.44 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 938751 | AE1-101 C | Adder | -7.15 MW | -6.07 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964451 | AG1-308 C O1 | Adder | 0.59 MW | 0.5 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964452 | AG1-308 E O1 | Adder | 0.83 MW | 0.7 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 946421 | AF2-000A C | Adder | 3.37 MW | 2.86 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 946422 | AF2-000A E | Adder | 10.1 MW | 8.59 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 938385 | AE1-071-E | 50/50 | 24.72 MW | 24.72 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 959843 | AF2-275 BAT | Adder | 0.12 MW | 0.1 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 959853 | AF2-276 BAT | Adder | 0.12 MW | 0.1 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 966463 | AG1-515 BAT | Adder | 0.91 MW | 0.77 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.17 MW | 0.17 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.05 MW | 0.05 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.89 MW | 0.89 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.11 MW | 2.11 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.44 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.36 MW | 0.36 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.11 MW | 0.11 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.03 MW | 0.03 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.07 MW | 2.07 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 962411 | AG1-090 C O1 | 50/50 | 26.21 MW | 26.21 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 962412 | AG1-090 E O1 | 50/50 | 6.55 MW | 6.55 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 965121 | AG1-377 C O1 | 50/50 | 3.93 MW | 3.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 965122 | AG1-377 E O1 | 50/50 | 2.62 MW | 2.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 965131 | AG1-378 C O1 | 50/50 | 3.93 MW | 3.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 965132 | AG1-378 E O1 | 50/50 | 2.62 MW | 2.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 290086 | Q-036 E | 50/50 | 10.01 MW | 10.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 936991 | AD2-133 C | 50/50 | 3.77 MW | 3.77 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 936992 | AD2-133 E | 50/50 | 17.27 MW | 17.27 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 944181 | AF1-086 C O1 | 50/50 | 3.39 MW | 3.39 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 944182 | AF1-086 E O1 | 50/50 | 14.74 MW | 14.74 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 944691 | AF1-134 C | 50/50 | 3.36 MW | 3.36 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 944692 | AF1-134 E | 50/50 | 2.24 MW | 2.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 945181 | AF1-183 | 50/50 | 0.07 MW | 0.07 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 959802 | AF2-271 E | Adder | 0.29 MW | 0.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 960051 | AF2-296 C | 50/50 | 3.36 MW | 3.36 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 960052 | AF2-296 E | 50/50 | 2.24 MW | 2.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 200715 | 26SHAWVL 1 | 50/50 | 9.0 MW | 9.0 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 200722 | 26SHAWVL 2 | 50/50 | 13.33 MW | 13.33 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 200883 | Q-053 E | Adder | 2.66 MW | 2.26 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 200913 | 26SHAW-D | 50/50 | 0.44 MW | 0.44 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 236828 | 01GRAYMONT | Adder | -0.34 MW | -0.29 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 293393 | V3-030E | Adder | 2.32 MW | 1.97 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 941321 | AE2-126 C | 50/50 | 2.69 MW | 2.69 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 941322 | AE2-126 E | 50/50 | 1.79 MW | 1.79 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 941331 | AE2-129 C | 50/50 | 3.93 MW | 3.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 941332 | AE2-129 E | 50/50 | 2.62 MW | 2.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 941351 | AE2-131 C | 50/50 | 3.93 MW | 3.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 941352 | AE2-131 E | 50/50 | 2.62 MW | 2.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 957451 | AF2-039 C | 50/50 | 3.51 MW | 3.51 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 957452 | AF2-039 E | 50/50 | 2.34 MW | 2.34 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 957941 | AF2-088 C | 50/50 | 1.69 MW | 1.69 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 957942 | AF2-088 E | 50/50 | 1.12 MW | 1.12 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 958271 | AF2-121 C | 50/50 | 3.93 MW | 3.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 958272 | AF2-121 E | 50/50 | 2.62 MW | 2.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 964451 | AG1-308 C O1 | 50/50 | 2.72 MW | 2.72 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 964452 | AG1-308 E O1 | 50/50 | 3.8 MW | 3.8 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 200905 | 26Q36 | 50/50 | 0.34 MW | 0.34 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 946423 | AF2-000A BAT | Adder | 15.14 MW | 12.87 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 960023 | AF2-293 BAT | Adder | 0.12 MW | 0.1 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 235007 | AC1-025 BAT | Adder | 0.15 MW | 0.13 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.02 MW | 0.02 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.03 MW | 0.03 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.49 MW | 0.49 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.17 MW | 1.17 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.67 MW | 0.67 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.03 MW | 0.03 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.43 MW | 0.43 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.12 MW | 0.12 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.83 MW | 2.83 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.1 MW | 0.1 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 962411 | AG1-090 C O1 | 50/50 | 41.62 MW | 41.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 962412 | AG1-090 E O1 | 50/50 | 10.41 MW | 10.41 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 964391 | AG1-301 C | Adder | 1.02 MW | 0.86 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 964392 | AG1-301 E | Adder | 0.68 MW | 0.58 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 965121 | AG1-377 C O1 | 50/50 | 6.24 MW | 6.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 965122 | AG1-377 E O1 | 50/50 | 4.16 MW | 4.16 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 965131 | AG1-378 C O1 | 50/50 | 6.24 MW | 6.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 965132 | AG1-378 E O1 | 50/50 | 4.16 MW | 4.16 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 290086 | Q-036 E | 50/50 | 15.76 MW | 15.76 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 936991 | AD2-133 C | 50/50 | 5.93 MW | 5.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 936992 | AD2-133 E | 50/50 | 27.17 MW | 27.17 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 959802 | AF2-271 E | 50/50 | 0.47 MW | 0.47 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 200722 | 26SHAWVL 2 | 50/50 | 18.59 MW | 18.59 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 200852 | 26WARR RDG | Adder | 0.21 MW | 0.18 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 200883 | Q-053 E | 50/50 | 3.77 MW | 3.77 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 941231 | AE2-117 C | 50/50 | 1.23 MW | 1.23 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 941232 | AE2-117 E | 50/50 | 0.82 MW | 0.82 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 941331 | AE2-129 C | 50/50 | 6.24 MW | 6.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 941332 | AE2-129 E | 50/50 | 4.16 MW | 4.16 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 941351 | AE2-131 C | 50/50 | 6.24 MW | 6.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 941352 | AE2-131 E | 50/50 | 4.16 MW | 4.16 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 957451 | AF2-039 C | 50/50 | 5.62 MW | 5.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 957452 | AF2-039 E | 50/50 | 3.75 MW | 3.75 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 957931 | AF2-087 C | Adder | 0.27 MW | 0.23 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 957932 | AF2-087 E | Adder | 0.37 MW | 0.31 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 957941 | AF2-088 C | 50/50 | 2.71 MW | 2.71 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 957942 | AF2-088 E | 50/50 | 1.8 MW | 1.8 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 958271 | AF2-121 C | 50/50 | 6.24 MW | 6.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 958272 | AF2-121 E | 50/50 | 4.16 MW | 4.16 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 200915 | 26CHSTN_FL | 50/50 | 0.13 MW | 0.13 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 964451 | AG1-308 C O1 | 50/50 | 4.32 MW | 4.32 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 964452 | AG1-308 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | 200905 | 26Q36 | 50/50 | 0.54 MW | 0.54 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.13 MW | 0.13 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.06 MW | 0.06 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.1 MW | 0.1 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.2 MW | 0.2 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.02 MW | 0.02 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.39 MW | 1.39 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.02 MW | 0.02 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-59A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961971 | AG1-040 C | Adder | 1.7 MW | 1.45 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961972 | AG1-040 E | Adder | 1.14 MW | 0.96 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961981 | AG1-041 C | 50/50 | 2.1 MW | 2.1 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961982 | AG1-041 E | 50/50 | 1.4 MW | 1.4 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962411 | AG1-090 C O1 | Adder | 16.04 MW | 13.64 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962412 | AG1-090 E O1 | Adder | 4.01 MW | 3.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962511 | AG1-100 C | Adder | 1.62 MW | 1.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962512 | AG1-100 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962911 | AG1-140 C | Adder | 0.25 MW | 0.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962912 | AG1-140 E | Adder | 0.13 MW | 0.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963441 | AG1-193 C | Adder | 1.93 MW | 1.64 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963442 | AG1-193 E | Adder | 1.29 MW | 1.09 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963481 | AG1-197 C | Adder | 1.29 MW | 1.1 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963482 | AG1-197 E | Adder | 0.86 MW | 0.73 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963491 | AG1-198 C | Adder | 1.0 MW | 0.85 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963492 | AG1-198 E | Adder | 0.67 MW | 0.57 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963991 | AG1-253 C | Adder | 0.37 MW | 0.32 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963992 | AG1-253 E | Adder | 0.18 MW | 0.15 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964031 | AG1-257 C | Adder | 1.14 MW | 0.97 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964032 | AG1-257 E | Adder | 1.59 MW | 1.35 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964201 | AG1-281 C | 50/50 | 3.31 MW | 3.31 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964202 | AG1-281 E | 50/50 | 2.21 MW | 2.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964391 | AG1-301 C | Adder | 2.58 MW | 2.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964392 | AG1-301 E | Adder | 1.72 MW | 1.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964411 | AG1-303 C O1 | Adder | 4.01 MW | 3.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964412 | AG1-303 E O1 | Adder | 2.67 MW | 2.27 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 966771 | AG1-548 C | Adder | 15.9 MW | 13.51 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 966772 | AG1-548 E | Adder | 4.84 MW | 4.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965121 | AG1-377 C O1 | Adder | 2.41 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965122 | AG1-377 E O1 | Adder | 1.6 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965131 | AG1-378 C O1 | Adder | 2.41 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965132 | AG1-378 E O1 | Adder | 1.6 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965171 | AG1-382 C | 50/50 | 3.35 MW | 3.35 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965172 | AG1-382 E | 50/50 | 2.23 MW | 2.23 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965241 | AG1-392C C O | Adder | 2.58 MW | 2.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965242 | AG1-392C E O | Adder | 1.72 MW | 1.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965251 | AG1-392B C O | Adder | 2.58 MW | 2.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965252 | AG1-392B E O | Adder | 1.72 MW | 1.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965261 | AG1-392A C O | Adder | 5.17 MW | 4.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965262 | AG1-392A E O | Adder | 3.44 MW | 2.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965271 | AG1-392 C O1 | Adder | 5.17 MW | 4.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965272 | AG1-392 E O1 | Adder | 3.44 MW | 2.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965861 | AG1-455 | Adder | 4.54 MW | 3.86 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 966041 | AG1-473 C | Adder | 3.89 MW | 3.31 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 966042 | AG1-473 E | Adder | 2.59 MW | 2.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 290086 | Q-036 E | Adder | 9.26 MW | 7.87 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 296332 | R-032 E | 50/50 | 18.26 MW | 18.26 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 913142 | Y1-033 E OP1 | Adder | 5.94 MW | 5.05 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 936991 | AD2-133 C | Adder | 3.48 MW | 2.96 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 936992 | AD2-133 E | Adder | 15.96 MW | 13.56 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942121 | AE2-224 C | 50/50 | 19.07 MW | 19.07 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942122 | AE2-224 E | 50/50 | 12.71 MW | 12.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942351 | AE2-248 C | Adder | 1.31 MW | 1.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942352 | AE2-248 E | Adder | 0.87 MW | 0.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942361 | AE2-249 C | 50/50 | 2.92 MW | 2.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942362 | AE2-249 E | 50/50 | 1.95 MW | 1.95 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942491 | AE2-262 C | Adder | 7.39 MW | 6.28 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942492 | AE2-262 E | Adder | 4.96 MW | 4.22 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942501 | AE2-263 C | Adder | 6.94 MW | 5.9 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942502 | AE2-263 E | Adder | 4.64 MW | 3.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942811 | AE2-299 C | Adder | 4.4 MW | 3.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942812 | AE2-299 E | Adder | 17.58 MW | 14.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942961 | AE2-316 C | Adder | 6.9 MW | 5.86 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942962 | AE2-316 E | Adder | 8.16 MW | 6.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943151 | AE2-344 C | Adder | 9.42 MW | 8.01 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943152 | AE2-344 E | Adder | 6.28 MW | 5.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943351 | AF1-006 C | Adder | 1.63 MW | 1.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943352 | AF1-006 E | Adder | 0.92 MW | 0.78 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943711 | AF1-039 C O1 | Adder | 1.57 MW | 1.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943712 | AF1-039 E O1 | Adder | 1.05 MW | 0.89 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944181 | AF1-086 C O1 | Adder | 3.79 MW | 3.23 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944182 | AF1-086 E O1 | Adder | 16.5 MW | 14.03 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944261 | AF1-094 C | Adder | 1.67 MW | 1.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944262 | AF1-094 E | Adder | 1.11 MW | 0.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944301 | AF1-098 C | Adder | 6.72 MW | 5.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944302 | AF1-098 E | Adder | 4.48 MW | 3.81 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944311 | AF1-099 C | Adder | 11.5 MW | 9.77 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944312 | AF1-099 E | Adder | 7.67 MW | 6.52 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944321 | AF1-100 C | Adder | 23.56 MW | 20.02 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944322 | AF1-100 E | Adder | 15.7 MW | 13.35 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944391 | AF1-104 O1 | Adder | 2.38 MW | 2.03 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944411 | AF1-106 O1 | Adder | 3.45 MW | 2.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944471 | AF1-112 C | Adder | 1.22 MW | 1.03 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944472 | AF1-112 E | Adder | 0.83 MW | 0.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944691 | AF1-134 C | Adder | 2.16 MW | 1.84 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944692 | AF1-134 E | Adder | 1.44 MW | 1.23 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944751 | AF1-140 C | 50/50 | 2.84 MW | 2.84 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944752 | AF1-140 E | 50/50 | 1.89 MW | 1.89 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944771 | AF1-142 C | Adder | 18.4 MW | 15.64 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944772 | AF1-142 E | Adder | 12.27 MW | 10.43 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944781 | AF1-143 C | 50/50 | 13.87 MW | 13.87 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944782 | AF1-143 E | 50/50 | 7.39 MW | 7.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944881 | AF1-153 C O1 | Adder | 1.96 MW | 1.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944882 | AF1-153 E O1 | Adder | 1.3 MW | 1.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944901 | AF1-155 C | Adder | 1.96 MW | 1.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944902 | AF1-155 E | Adder | 1.3 MW | 1.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945021 | AF1-167 C | Adder | 1.19 MW | 1.01 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945022 | AF1-167 E | Adder | 0.8 MW | 0.68 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945051 | AF1-170 C | Adder | 6.03 MW | 5.12 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945052 | AF1-170 E | Adder | 4.02 MW | 3.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945451 | AF1-210 C | Adder | 1.31 MW | 1.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945452 | AF1-210 E | Adder | 0.87 MW | 0.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945751 | AF1-240 C O1 | Adder | 2.03 MW | 1.72 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945752 | AF1-240 E O1 | Adder | 1.35 MW | 1.15 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958471 | AF2-141 | Adder | 1.85 MW | 1.57 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958731 | AF2-164 C O1 | Adder | 9.57 MW | 8.13 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958732 | AF2-164 E O1 | Adder | 6.38 MW | 5.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958741 | AF2-165 C | Adder | 1.88 MW | 1.6 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958742 | AF2-165 E | Adder | 1.26 MW | 1.07 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958751 | AF2-166 C | Adder | 1.89 MW | 1.6 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958752 | AF2-166 E | Adder | 1.26 MW | 1.07 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959441 | AF2-235 C | Adder | 0.9 MW | 0.77 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959442 | AF2-235 E | Adder | 0.6 MW | 0.51 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959471 | AF2-238 C | Adder | 2.12 MW | 1.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959472 | AF2-238 E | Adder | 1.42 MW | 1.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959521 | AF2-243 C | Adder | 1.41 MW | 1.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959522 | AF2-243 E | Adder | 0.94 MW | 0.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959802 | AF2-271 E | Adder | 0.66 MW | 0.56 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960022 | AF2-293 E | Adder | 0.16 MW | 0.14 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960031 | AF2-294 C | Adder | 1.61 MW | 1.37 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960032 | AF2-294 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960041 | AF2-295 C | Adder | 1.96 MW | 1.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960042 | AF2-295 E | Adder | 1.3 MW | 1.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960051 | AF2-296 C | Adder | 2.16 MW | 1.84 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960052 | AF2-296 E | Adder | 1.44 MW | 1.23 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960451 | AF2-336 C | 50/50 | 3.51 MW | 3.51 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960452 | AF2-336 E | 50/50 | 2.34 MW | 2.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960461 | AF2-337 C | 50/50 | 3.51 MW | 3.51 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960462 | AF2-337 E | 50/50 | 2.34 MW | 2.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961141 | AF2-405 | Adder | 1.72 MW | 1.47 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961151 | AF2-406 | Adder | 12.94 MW | 11.0 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961211 | AF2-412 | Adder | 26.53 MW | 22.55 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961451 | AF2-436 | Adder | 0.19 MW | 0.16 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200503 | 26C.SLOPE | 50/50 | 2.53 MW | 2.53 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200794 | 26CONEMAGH | 50/50 | 0.53 MW | 0.53 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200809 | 26SITHE | 50/50 | 2.68 MW | 2.68 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200834 | 26SW_E13_K22 | 50/50 | 0.04 MW | 0.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200835 | 26ARN_Z1-066 | Adder | 1.85 MW | 1.57 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200837 | 26HOMER C1 | 50/50 | 46.19 MW | 46.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200838 | 26HOMER C2 | 50/50 | 37.95 MW | 37.95 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200839 | 26HOMER C3 | 50/50 | 40.18 MW | 40.18 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200846 | 26FORWARD | 50/50 | 0.17 MW | 0.17 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200852 | 26WARR RDG | Adder | 0.54 MW | 0.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200864 | K-013 E | 50/50 | 7.16 MW | 7.16 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200883 | Q-053 E | 50/50 | 8.61 MW | 8.61 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200888 | 26HIGHLAND | 50/50 | 0.42 MW | 0.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200889 | 26STNY CRK | 50/50 | 0.41 MW | 0.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200890 | 26BF_G21_K23 | 50/50 | 0.2 MW | 0.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200891 | 26CSLMN_L13 | 50/50 | 0.23 MW | 0.23 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200892 | 26LOOKOUT | 50/50 | 0.25 MW | 0.25 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200894 | 26K02 | Adder | 8.16 MW | 6.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200925 | 26R32 | 50/50 | 0.66 MW | 0.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200945 | 26CT_V3-030 | 50/50 | 0.21 MW | 0.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 202225 | 26SCI_S29B | 50/50 | 0.09 MW | 0.09 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 203915 | 26BF_Z2-108 | Adder | 4.16 MW | 3.54 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 203932 | AA2-133 GEN | Adder | 2.51 MW | 2.13 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 203999 | P-047 E | Adder | 15.06 MW | 12.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 235003 | AC1-025 E | Adder | 0.2 MW | 0.17 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 236828 | 01GRAYMONT | Adder | 0.55 MW | 0.47 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 292350 | K-023 | 50/50 | 5.75 MW | 5.75 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 292542 | L-013 1 | 50/50 | 7.39 MW | 7.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293301 | N-039 E | 50/50 | 19.3 MW | 19.3 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293393 | V3-030E | 50/50 | 6.54 MW | 6.54 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293432 | R-040 E | Adder | 0.42 MW | 0.35 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293603 | O-018 E | 50/50 | 15.83 MW | 15.83 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293902 | O-048 E | 50/50 | 6.66 MW | 6.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 294515 | O38_P22 | 50/50 | 16.89 MW | 16.89 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 294903 | P-060 E | 50/50 | 11.94 MW | 11.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 916202 | Z1-069 E | Adder | 12.12 MW | 10.31 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 931092 | AB1-160 E | Adder | 3.46 MW | 2.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 938951 | AE1-123 | Adder | 2.85 MW | 2.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 939291 | AE1-160 C | Adder | 1.91 MW | 1.62 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 939292 | AE1-160 E | Adder | 1.1 MW | 0.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940201 | AE2-001 C | Adder | 1.66 MW | 1.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940202 | AE2-001 E | Adder | 1.1 MW | 0.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940681 | AE2-055 C | Adder | 1.62 MW | 1.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940682 | AE2-055 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940861 | AE2-074 C | Adder | 3.32 MW | 2.82 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940862 | AE2-074 E | Adder | 4.37 MW | 3.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941191 | AE2-113 C | Adder | 12.65 MW | 10.75 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941192 | AE2-113 E | Adder | 11.87 MW | 10.09 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941231 | AE2-117 C | Adder | 2.6 MW | 2.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941232 | AE2-117 E | Adder | 1.73 MW | 1.47 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941241 | AE2-118 C | Adder | 2.74 MW | 2.33 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941242 | AE2-118 E | Adder | 1.83 MW | 1.55 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941271 | AE2-121 C | Adder | 0.88 MW | 0.75 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941272 | AE2-121 E | Adder | 0.59 MW | 0.5 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941321 | AE2-126 C | Adder | 2.12 MW | 1.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941322 | AE2-126 E | Adder | 1.42 MW | 1.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941331 | AE2-129 C | Adder | 2.41 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941332 | AE2-129 E | Adder | 1.6 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941351 | AE2-131 C | Adder | 2.41 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941352 | AE2-131 E | Adder | 1.6 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941421 | AE2-139 C | Adder | 8.46 MW | 7.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941422 | AE2-139 E | Adder | 5.64 MW | 4.79 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946111 | AF1-276 C | Adder | 14.81 MW | 12.59 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946112 | AF1-276 E | Adder | 7.3 MW | 6.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946121 | AF1-277 C | Adder | 14.81 MW | 12.59 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946122 | AF1-277 E | Adder | 7.3 MW | 6.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946131 | AF1-278 C | Adder | 11.81 MW | 10.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946132 | AF1-278 E | Adder | 5.87 MW | 4.99 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946221 | AF1-287 C | Adder | 1.62 MW | 1.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946222 | AF1-287 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946381 | AF1-302 C | Adder | 3.01 MW | 2.56 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946382 | AF1-302 E | Adder | 4.02 MW | 3.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946571 | AF1-321 C O1 | 50/50 | 3.74 MW | 3.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946572 | AF1-321 E O1 | 50/50 | 2.49 MW | 2.49 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946771 | AF1-217 C | Adder | 1.62 MW | 1.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946772 | AF1-217 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957001 | AF2-001 C O1 | 50/50 | 3.74 MW | 3.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957002 | AF2-001 E O1 | 50/50 | 2.49 MW | 2.49 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957011 | AF2-002 C O1 | 50/50 | 1.87 MW | 1.87 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957012 | AF2-002 E O1 | 50/50 | 1.25 MW | 1.25 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957161 | AF2-010 C | Adder | 6.42 MW | 5.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957162 | AF2-010 E | Adder | 4.33 MW | 3.68 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957451 | AF2-039 C | Adder | 1.41 MW | 1.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957452 | AF2-039 E | Adder | 0.94 MW | 0.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957561 | AF2-050 C | 50/50 | 9.54 MW | 9.54 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957562 | AF2-050 E | 50/50 | 6.36 MW | 6.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957931 | AF2-087 C | 50/50 | 0.78 MW | 0.78 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957932 | AF2-087 E | 50/50 | 1.07 MW | 1.07 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957941 | AF2-088 C | Adder | 0.68 MW | 0.58 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957942 | AF2-088 E | Adder | 0.45 MW | 0.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957981 | AF2-092 C | 50/50 | 2.11 MW | 2.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957982 | AF2-092 E | 50/50 | 1.4 MW | 1.4 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958271 | AF2-121 C | Adder | 2.41 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958272 | AF2-121 E | Adder | 1.6 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958361 | AF2-130 C | Adder | 1.89 MW | 1.6 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958362 | AF2-130 E | Adder | 1.26 MW | 1.07 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200833 | 26SEWRDB34 | 50/50 | 32.57 MW | 32.57 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200886 | 26ARWF_N39 | 50/50 | 0.55 MW | 0.55 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200915 | 26CHSTN_FL | 50/50 | 0.3 MW | 0.3 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 203034 | 26NA_O38_P22 | 50/50 | 0.48 MW | 0.48 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959301 | AF2-221 C | 50/50 | 1.97 MW | 1.97 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959302 | AF2-221 E | 50/50 | 2.71 MW | 2.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 292340 | 26SW_E13_K22 | 50/50 | 1.99 MW | 1.99 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964451 | AG1-308 C O1 | Adder | 1.66 MW | 1.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964452 | AG1-308 E O1 | Adder | 2.33 MW | 1.98 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960901 | AG1-000C C | 50/50 | 12.22 MW | 12.22 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960902 | AG1-000C E | 50/50 | 6.02 MW | 6.02 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946421 | AF2-000A C | Adder | 8.18 MW | 6.95 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946422 | AF2-000A E | Adder | 24.53 MW | 20.85 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 966783 | AG1-549 BAT | 50/50 | 7.8 MW | 7.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.6 MW | 0.6 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.71 MW | 0.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.08 MW | 1.08 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.38 MW | 0.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 7.55 MW | 7.55 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.39 MW | 0.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.47 MW | 1.47 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.38 MW | 0.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.33 MW | 0.33 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.53 MW | 0.53 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.7 MW | 1.7 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.61 MW | 1.61 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.34 MW | 0.34 MW |
| Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961971 | AG1-040 C | Adder | 1.7 MW | 1.45 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961972 | AG1-040 E | Adder | 1.14 MW | 0.96 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961981 | AG1-041 C | 50/50 | 2.1 MW | 2.1 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961982 | AG1-041 E | 50/50 | 1.4 MW | 1.4 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962411 | AG1-090 C O1 | Adder | 16.04 MW | 13.64 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962412 | AG1-090 E O1 | Adder | 4.01 MW | 3.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962511 | AG1-100 C | Adder | 1.62 MW | 1.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962512 | AG1-100 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962911 | AG1-140 C | Adder | 0.25 MW | 0.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962912 | AG1-140 E | Adder | 0.13 MW | 0.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963441 | AG1-193 C | Adder | 1.93 MW | 1.64 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963442 | AG1-193 E | Adder | 1.29 MW | 1.09 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963481 | AG1-197 C | Adder | 1.29 MW | 1.1 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963482 | AG1-197 E | Adder | 0.86 MW | 0.73 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963491 | AG1-198 C | Adder | 1.0 MW | 0.85 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963492 | AG1-198 E | Adder | 0.67 MW | 0.57 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963991 | AG1-253 C | Adder | 0.37 MW | 0.32 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963992 | AG1-253 E | Adder | 0.18 MW | 0.15 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964031 | AG1-257 C | Adder | 1.14 MW | 0.97 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964032 | AG1-257 E | Adder | 1.59 MW | 1.35 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964201 | AG1-281 C | 50/50 | 3.31 MW | 3.31 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964202 | AG1-281 E | 50/50 | 2.21 MW | 2.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964391 | AG1-301 C | Adder | 2.58 MW | 2.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964392 | AG1-301 E | Adder | 1.72 MW | 1.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964411 | AG1-303 C O1 | Adder | 4.01 MW | 3.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964412 | AG1-303 E O1 | Adder | 2.67 MW | 2.27 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 966771 | AG1-548 C | Adder | 15.9 MW | 13.51 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 966772 | AG1-548 E | Adder | 4.84 MW | 4.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965121 | AG1-377 C O1 | Adder | 2.41 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965122 | AG1-377 E O1 | Adder | 1.6 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965131 | AG1-378 C O1 | Adder | 2.41 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965132 | AG1-378 E O1 | Adder | 1.6 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965171 | AG1-382 C | 50/50 | 3.35 MW | 3.35 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965172 | AG1-382 E | 50/50 | 2.23 MW | 2.23 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965241 | AG1-392C C O | Adder | 2.58 MW | 2.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965242 | AG1-392C E O | Adder | 1.72 MW | 1.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965251 | AG1-392B C O | Adder | 2.58 MW | 2.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965252 | AG1-392B E O | Adder | 1.72 MW | 1.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965261 | AG1-392A C O | Adder | 5.17 MW | 4.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965262 | AG1-392A E O | Adder | 3.44 MW | 2.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965271 | AG1-392 C O1 | Adder | 5.17 MW | 4.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965272 | AG1-392 E O1 | Adder | 3.44 MW | 2.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965861 | AG1-455 | Adder | 4.54 MW | 3.86 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 966041 | AG1-473 C | Adder | 3.89 MW | 3.31 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 966042 | AG1-473 E | Adder | 2.59 MW | 2.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 290086 | Q-036 E | Adder | 9.26 MW | 7.87 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 296332 | R-032 E | 50/50 | 18.26 MW | 18.26 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 913142 | Y1-033 E OP1 | Adder | 5.94 MW | 5.05 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 936991 | AD2-133 C | Adder | 3.48 MW | 2.96 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 936992 | AD2-133 E | Adder | 15.96 MW | 13.56 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942121 | AE2-224 C | 50/50 | 19.07 MW | 19.07 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942122 | AE2-224 E | 50/50 | 12.71 MW | 12.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942351 | AE2-248 C | Adder | 1.31 MW | 1.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942352 | AE2-248 E | Adder | 0.87 MW | 0.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942361 | AE2-249 C | 50/50 | 2.92 MW | 2.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942362 | AE2-249 E | 50/50 | 1.95 MW | 1.95 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942491 | AE2-262 C | Adder | 7.39 MW | 6.28 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942492 | AE2-262 E | Adder | 4.96 MW | 4.22 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942501 | AE2-263 C | Adder | 6.94 MW | 5.9 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942502 | AE2-263 E | Adder | 4.64 MW | 3.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942811 | AE2-299 C | Adder | 4.4 MW | 3.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942812 | AE2-299 E | Adder | 17.58 MW | 14.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942961 | AE2-316 C | Adder | 6.9 MW | 5.86 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942962 | AE2-316 E | Adder | 8.16 MW | 6.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943151 | AE2-344 C | Adder | 9.42 MW | 8.01 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943152 | AE2-344 E | Adder | 6.28 MW | 5.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943351 | AF1-006 C | Adder | 1.63 MW | 1.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943352 | AF1-006 E | Adder | 0.92 MW | 0.78 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943711 | AF1-039 C O1 | Adder | 1.57 MW | 1.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943712 | AF1-039 E O1 | Adder | 1.05 MW | 0.89 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944181 | AF1-086 C O1 | Adder | 3.79 MW | 3.23 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944182 | AF1-086 E O1 | Adder | 16.5 MW | 14.03 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944261 | AF1-094 C | Adder | 1.67 MW | 1.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944262 | AF1-094 E | Adder | 1.11 MW | 0.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944301 | AF1-098 C | Adder | 6.72 MW | 5.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944302 | AF1-098 E | Adder | 4.48 MW | 3.81 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944311 | AF1-099 C | Adder | 11.5 MW | 9.77 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944312 | AF1-099 E | Adder | 7.67 MW | 6.52 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944321 | AF1-100 C | Adder | 23.56 MW | 20.02 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944322 | AF1-100 E | Adder | 15.7 MW | 13.35 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944391 | AF1-104 O1 | Adder | 2.38 MW | 2.03 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944411 | AF1-106 O1 | Adder | 3.45 MW | 2.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944471 | AF1-112 C | Adder | 1.22 MW | 1.03 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944472 | AF1-112 E | Adder | 0.83 MW | 0.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944691 | AF1-134 C | Adder | 2.16 MW | 1.84 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944692 | AF1-134 E | Adder | 1.44 MW | 1.23 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944751 | AF1-140 C | 50/50 | 2.84 MW | 2.84 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944752 | AF1-140 E | 50/50 | 1.89 MW | 1.89 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944771 | AF1-142 C | Adder | 18.4 MW | 15.64 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944772 | AF1-142 E | Adder | 12.27 MW | 10.43 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944781 | AF1-143 C | 50/50 | 13.87 MW | 13.87 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944782 | AF1-143 E | 50/50 | 7.39 MW | 7.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944881 | AF1-153 C O1 | Adder | 1.96 MW | 1.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944882 | AF1-153 E O1 | Adder | 1.3 MW | 1.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944901 | AF1-155 C | Adder | 1.96 MW | 1.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944902 | AF1-155 E | Adder | 1.3 MW | 1.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945021 | AF1-167 C | Adder | 1.19 MW | 1.01 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945022 | AF1-167 E | Adder | 0.8 MW | 0.68 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945051 | AF1-170 C | Adder | 6.03 MW | 5.12 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945052 | AF1-170 E | Adder | 4.02 MW | 3.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945451 | AF1-210 C | Adder | 1.31 MW | 1.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945452 | AF1-210 E | Adder | 0.87 MW | 0.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945751 | AF1-240 C O1 | Adder | 2.03 MW | 1.72 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945752 | AF1-240 E O1 | Adder | 1.35 MW | 1.15 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958471 | AF2-141 | Adder | 1.85 MW | 1.57 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958731 | AF2-164 C O1 | Adder | 9.57 MW | 8.13 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958732 | AF2-164 E O1 | Adder | 6.38 MW | 5.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958741 | AF2-165 C | Adder | 1.88 MW | 1.6 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958742 | AF2-165 E | Adder | 1.26 MW | 1.07 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958751 | AF2-166 C | Adder | 1.89 MW | 1.6 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958752 | AF2-166 E | Adder | 1.26 MW | 1.07 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959441 | AF2-235 C | Adder | 0.9 MW | 0.77 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959442 | AF2-235 E | Adder | 0.6 MW | 0.51 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959471 | AF2-238 C | Adder | 2.12 MW | 1.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959472 | AF2-238 E | Adder | 1.42 MW | 1.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959521 | AF2-243 C | Adder | 1.41 MW | 1.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959522 | AF2-243 E | Adder | 0.94 MW | 0.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959802 | AF2-271 E | Adder | 0.66 MW | 0.56 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960022 | AF2-293 E | Adder | 0.16 MW | 0.14 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960031 | AF2-294 C | Adder | 1.61 MW | 1.37 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960032 | AF2-294 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960041 | AF2-295 C | Adder | 1.96 MW | 1.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960042 | AF2-295 E | Adder | 1.3 MW | 1.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960051 | AF2-296 C | Adder | 2.16 MW | 1.84 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960052 | AF2-296 E | Adder | 1.44 MW | 1.23 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960451 | AF2-336 C | 50/50 | 3.51 MW | 3.51 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960452 | AF2-336 E | 50/50 | 2.34 MW | 2.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960461 | AF2-337 C | 50/50 | 3.51 MW | 3.51 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960462 | AF2-337 E | 50/50 | 2.34 MW | 2.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961141 | AF2-405 | Adder | 1.72 MW | 1.47 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961151 | AF2-406 | Adder | 12.94 MW | 11.0 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961211 | AF2-412 | Adder | 26.53 MW | 22.55 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961451 | AF2-436 | Adder | 0.19 MW | 0.16 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200503 | 26C.SLOPE | 50/50 | 2.53 MW | 2.53 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200794 | 26CONEMAGH | 50/50 | 0.53 MW | 0.53 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200809 | 26SITHE | 50/50 | 2.68 MW | 2.68 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200834 | 26SW_E13_K22 | 50/50 | 0.04 MW | 0.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200835 | 26ARN_Z1-066 | Adder | 1.85 MW | 1.57 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200837 | 26HOMER C1 | 50/50 | 46.19 MW | 46.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200838 | 26HOMER C2 | 50/50 | 37.95 MW | 37.95 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200839 | 26HOMER C3 | 50/50 | 40.18 MW | 40.18 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200846 | 26FORWARD | 50/50 | 0.17 MW | 0.17 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200852 | 26WARR RDG | Adder | 0.54 MW | 0.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200864 | K-013 E | 50/50 | 7.16 MW | 7.16 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200883 | Q-053 E | 50/50 | 8.61 MW | 8.61 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200888 | 26HIGHLAND | 50/50 | 0.42 MW | 0.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200889 | 26STNY CRK | 50/50 | 0.41 MW | 0.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200890 | 26BF_G21_K23 | 50/50 | 0.2 MW | 0.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200891 | 26CSLMN_L13 | 50/50 | 0.23 MW | 0.23 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200892 | 26LOOKOUT | 50/50 | 0.25 MW | 0.25 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200894 | 26K02 | Adder | 8.16 MW | 6.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200925 | 26R32 | 50/50 | 0.66 MW | 0.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200945 | 26CT_V3-030 | 50/50 | 0.21 MW | 0.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 202225 | 26SCI_S29B | 50/50 | 0.09 MW | 0.09 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 203915 | 26BF_Z2-108 | Adder | 4.16 MW | 3.54 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 203932 | AA2-133 GEN | Adder | 2.51 MW | 2.13 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 203999 | P-047 E | Adder | 15.06 MW | 12.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 235003 | AC1-025 E | Adder | 0.2 MW | 0.17 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 236828 | 01GRAYMONT | Adder | 0.55 MW | 0.47 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 292350 | K-023 | 50/50 | 5.75 MW | 5.75 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 292542 | L-013 1 | 50/50 | 7.39 MW | 7.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293301 | N-039 E | 50/50 | 19.3 MW | 19.3 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293393 | V3-030E | 50/50 | 6.54 MW | 6.54 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293432 | R-040 E | Adder | 0.42 MW | 0.35 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293603 | O-018 E | 50/50 | 15.83 MW | 15.83 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293902 | O-048 E | 50/50 | 6.66 MW | 6.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 294515 | O38_P22 | 50/50 | 16.89 MW | 16.89 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 294903 | P-060 E | 50/50 | 11.94 MW | 11.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 916202 | Z1-069 E | Adder | 12.12 MW | 10.31 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 931092 | AB1-160 E | Adder | 3.46 MW | 2.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 938951 | AE1-123 | Adder | 2.85 MW | 2.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 939291 | AE1-160 C | Adder | 1.91 MW | 1.62 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 939292 | AE1-160 E | Adder | 1.1 MW | 0.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940201 | AE2-001 C | Adder | 1.66 MW | 1.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940202 | AE2-001 E | Adder | 1.1 MW | 0.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940681 | AE2-055 C | Adder | 1.62 MW | 1.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940682 | AE2-055 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940861 | AE2-074 C | Adder | 3.32 MW | 2.82 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940862 | AE2-074 E | Adder | 4.37 MW | 3.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941191 | AE2-113 C | Adder | 12.65 MW | 10.75 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941192 | AE2-113 E | Adder | 11.87 MW | 10.09 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941231 | AE2-117 C | Adder | 2.6 MW | 2.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941232 | AE2-117 E | Adder | 1.73 MW | 1.47 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941241 | AE2-118 C | Adder | 2.74 MW | 2.33 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941242 | AE2-118 E | Adder | 1.83 MW | 1.55 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941271 | AE2-121 C | Adder | 0.88 MW | 0.75 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941272 | AE2-121 E | Adder | 0.59 MW | 0.5 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941321 | AE2-126 C | Adder | 2.12 MW | 1.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941322 | AE2-126 E | Adder | 1.42 MW | 1.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941331 | AE2-129 C | Adder | 2.41 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941332 | AE2-129 E | Adder | 1.6 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941351 | AE2-131 C | Adder | 2.41 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941352 | AE2-131 E | Adder | 1.6 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941421 | AE2-139 C | Adder | 8.46 MW | 7.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941422 | AE2-139 E | Adder | 5.64 MW | 4.79 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946111 | AF1-276 C | Adder | 14.81 MW | 12.59 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946112 | AF1-276 E | Adder | 7.3 MW | 6.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946121 | AF1-277 C | Adder | 14.81 MW | 12.59 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946122 | AF1-277 E | Adder | 7.3 MW | 6.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946131 | AF1-278 C | Adder | 11.81 MW | 10.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946132 | AF1-278 E | Adder | 5.87 MW | 4.99 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946221 | AF1-287 C | Adder | 1.62 MW | 1.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946222 | AF1-287 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946381 | AF1-302 C | Adder | 3.01 MW | 2.56 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946382 | AF1-302 E | Adder | 4.02 MW | 3.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946571 | AF1-321 C O1 | 50/50 | 3.74 MW | 3.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946572 | AF1-321 E O1 | 50/50 | 2.49 MW | 2.49 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946771 | AF1-217 C | Adder | 1.62 MW | 1.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946772 | AF1-217 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957001 | AF2-001 C O1 | 50/50 | 3.74 MW | 3.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957002 | AF2-001 E O1 | 50/50 | 2.49 MW | 2.49 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957011 | AF2-002 C O1 | 50/50 | 1.87 MW | 1.87 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957012 | AF2-002 E O1 | 50/50 | 1.25 MW | 1.25 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957161 | AF2-010 C | Adder | 6.42 MW | 5.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957162 | AF2-010 E | Adder | 4.33 MW | 3.68 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957451 | AF2-039 C | Adder | 1.41 MW | 1.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957452 | AF2-039 E | Adder | 0.94 MW | 0.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957561 | AF2-050 C | 50/50 | 9.54 MW | 9.54 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957562 | AF2-050 E | 50/50 | 6.36 MW | 6.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957931 | AF2-087 C | 50/50 | 0.78 MW | 0.78 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957932 | AF2-087 E | 50/50 | 1.07 MW | 1.07 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957941 | AF2-088 C | Adder | 0.68 MW | 0.58 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957942 | AF2-088 E | Adder | 0.45 MW | 0.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957981 | AF2-092 C | 50/50 | 2.11 MW | 2.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957982 | AF2-092 E | 50/50 | 1.4 MW | 1.4 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958271 | AF2-121 C | Adder | 2.41 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958272 | AF2-121 E | Adder | 1.6 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958361 | AF2-130 C | Adder | 1.89 MW | 1.6 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958362 | AF2-130 E | Adder | 1.26 MW | 1.07 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200833 | 26SEWRDB34 | 50/50 | 32.57 MW | 32.57 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200886 | 26ARWF_N39 | 50/50 | 0.55 MW | 0.55 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200915 | 26CHSTN_FL | 50/50 | 0.3 MW | 0.3 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 203034 | 26NA_O38_P22 | 50/50 | 0.48 MW | 0.48 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959301 | AF2-221 C | 50/50 | 1.97 MW | 1.97 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959302 | AF2-221 E | 50/50 | 2.71 MW | 2.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 292340 | 26SW_E13_K22 | 50/50 | 1.99 MW | 1.99 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964451 | AG1-308 C O1 | Adder | 1.66 MW | 1.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964452 | AG1-308 E O1 | Adder | 2.33 MW | 1.98 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960901 | AG1-000C C | 50/50 | 12.22 MW | 12.22 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960902 | AG1-000C E | 50/50 | 6.02 MW | 6.02 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946421 | AF2-000A C | Adder | 8.18 MW | 6.95 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946422 | AF2-000A E | Adder | 24.53 MW | 20.85 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 966783 | AG1-549 BAT | 50/50 | 7.8 MW | 7.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.6 MW | 0.6 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.71 MW | 0.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.08 MW | 1.08 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.38 MW | 0.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 7.55 MW | 7.55 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.39 MW | 0.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.47 MW | 1.47 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.38 MW | 0.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.33 MW | 0.33 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.53 MW | 0.53 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.7 MW | 1.7 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.61 MW | 1.61 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.34 MW | 0.34 MW |
| Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961971 | AG1-040 C | Adder | 1.81 MW | 1.54 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961972 | AG1-040 E | Adder | 1.21 MW | 1.02 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961981 | AG1-041 C | Adder | 2.34 MW | 1.99 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961982 | AG1-041 E | Adder | 1.56 MW | 1.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962411 | AG1-090 C O1 | Adder | 18.53 MW | 15.75 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962412 | AG1-090 E O1 | Adder | 4.63 MW | 3.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962511 | AG1-100 C | Adder | 1.72 MW | 1.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962512 | AG1-100 E | Adder | 1.14 MW | 0.97 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962911 | AG1-140 C | Adder | 0.26 MW | 0.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 962912 | AG1-140 E | Adder | 0.13 MW | 0.11 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963441 | AG1-193 C | Adder | 2.14 MW | 1.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963442 | AG1-193 E | Adder | 1.43 MW | 1.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963481 | AG1-197 C | Adder | 1.37 MW | 1.17 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963482 | AG1-197 E | Adder | 0.91 MW | 0.78 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963491 | AG1-198 C | Adder | 1.1 MW | 0.93 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963492 | AG1-198 E | Adder | 0.73 MW | 0.62 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963991 | AG1-253 C | Adder | 0.39 MW | 0.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 963992 | AG1-253 E | Adder | 0.19 MW | 0.16 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964031 | AG1-257 C | Adder | 1.25 MW | 1.06 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964032 | AG1-257 E | Adder | 1.75 MW | 1.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964201 | AG1-281 C | Adder | 3.68 MW | 3.12 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964202 | AG1-281 E | Adder | 2.45 MW | 2.08 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964391 | AG1-301 C | Adder | 2.8 MW | 2.38 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964392 | AG1-301 E | Adder | 1.86 MW | 1.58 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964411 | AG1-303 C O1 | Adder | 4.27 MW | 3.63 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964412 | AG1-303 E O1 | Adder | 2.85 MW | 2.42 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 966771 | AG1-548 C | Adder | 17.34 MW | 14.74 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 966772 | AG1-548 E | Adder | 5.28 MW | 4.49 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965121 | AG1-377 C O1 | Adder | 2.78 MW | 2.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965122 | AG1-377 E O1 | Adder | 1.85 MW | 1.57 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965131 | AG1-378 C O1 | Adder | 2.78 MW | 2.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965132 | AG1-378 E O1 | Adder | 1.85 MW | 1.57 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965171 | AG1-382 C | Adder | 3.92 MW | 3.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965172 | AG1-382 E | Adder | 2.61 MW | 2.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965241 | AG1-392C C O | Adder | 2.61 MW | 2.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965242 | AG1-392C E O | Adder | 1.74 MW | 1.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965251 | AG1-392B C O | Adder | 2.61 MW | 2.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965252 | AG1-392B E O | Adder | 1.74 MW | 1.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965261 | AG1-392A C O | Adder | 5.23 MW | 4.44 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965262 | AG1-392A E O | Adder | 3.49 MW | 2.96 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965271 | AG1-392 C O1 | Adder | 5.23 MW | 4.44 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965272 | AG1-392 E O1 | Adder | 3.49 MW | 2.96 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 965861 | AG1-455 | Adder | 4.8 MW | 4.08 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 966041 | AG1-473 C | Adder | 4.22 MW | 3.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 966042 | AG1-473 E | Adder | 2.82 MW | 2.39 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 290086 | Q-036 E | Adder | 10.55 MW | 8.97 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 296332 | R-032 E | 50/50 | 20.3 MW | 20.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 913142 | Y1-033 E OP1 | Adder | 6.59 MW | 5.61 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 936991 | AD2-133 C | Adder | 3.97 MW | 3.38 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 936992 | AD2-133 E | Adder | 18.19 MW | 15.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942121 | AE2-224 C | Adder | 19.88 MW | 16.9 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942122 | AE2-224 E | Adder | 13.25 MW | 11.27 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942351 | AE2-248 C | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942352 | AE2-248 E | Adder | 0.96 MW | 0.81 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942361 | AE2-249 C | Adder | 3.24 MW | 2.75 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942362 | AE2-249 E | Adder | 2.16 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942491 | AE2-262 C | Adder | 8.14 MW | 6.92 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942492 | AE2-262 E | Adder | 5.47 MW | 4.65 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942501 | AE2-263 C | Adder | 7.65 MW | 6.5 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942502 | AE2-263 E | Adder | 5.11 MW | 4.34 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942811 | AE2-299 C | Adder | 4.6 MW | 3.91 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942812 | AE2-299 E | Adder | 18.41 MW | 15.65 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942961 | AE2-316 C | Adder | 7.54 MW | 6.41 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942962 | AE2-316 E | Adder | 8.93 MW | 7.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943151 | AE2-344 C | Adder | 9.98 MW | 8.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943152 | AE2-344 E | Adder | 6.65 MW | 5.65 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943351 | AF1-006 C | Adder | 1.72 MW | 1.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943352 | AF1-006 E | Adder | 0.97 MW | 0.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943711 | AF1-039 C O1 | Adder | 1.74 MW | 1.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943712 | AF1-039 E O1 | Adder | 1.16 MW | 0.99 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944181 | AF1-086 C O1 | Adder | 5.92 MW | 5.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944182 | AF1-086 E O1 | Adder | 25.74 MW | 21.88 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944261 | AF1-094 C | Adder | 1.83 MW | 1.55 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944262 | AF1-094 E | Adder | 1.22 MW | 1.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944301 | AF1-098 C | Adder | 7.08 MW | 6.02 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944302 | AF1-098 E | Adder | 4.72 MW | 4.01 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944311 | AF1-099 C | Adder | 12.68 MW | 10.78 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944312 | AF1-099 E | Adder | 8.45 MW | 7.19 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944321 | AF1-100 C | Adder | 26.26 MW | 22.32 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944322 | AF1-100 E | Adder | 17.51 MW | 14.88 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944411 | AF1-106 O1 | Adder | 3.47 MW | 2.95 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944471 | AF1-112 C | Adder | 1.34 MW | 1.14 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944472 | AF1-112 E | Adder | 0.92 MW | 0.78 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944691 | AF1-134 C | Adder | 3.03 MW | 2.58 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944692 | AF1-134 E | Adder | 2.02 MW | 1.72 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944751 | AF1-140 C | Adder | 3.17 MW | 2.69 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944752 | AF1-140 E | Adder | 2.11 MW | 1.8 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944771 | AF1-142 C | Adder | 20.29 MW | 17.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944772 | AF1-142 E | Adder | 13.53 MW | 11.5 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944781 | AF1-143 C | Adder | 15.31 MW | 13.02 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944782 | AF1-143 E | Adder | 8.17 MW | 6.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944881 | AF1-153 C O1 | Adder | 2.16 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944882 | AF1-153 E O1 | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944901 | AF1-155 C | Adder | 2.16 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944902 | AF1-155 E | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945021 | AF1-167 C | Adder | 1.39 MW | 1.19 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945022 | AF1-167 E | Adder | 0.93 MW | 0.79 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945051 | AF1-170 C | Adder | 6.38 MW | 5.42 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945052 | AF1-170 E | Adder | 4.25 MW | 3.61 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945451 | AF1-210 C | Adder | 1.53 MW | 1.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945452 | AF1-210 E | Adder | 1.02 MW | 0.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945751 | AF1-240 C O1 | Adder | 3.02 MW | 2.56 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945752 | AF1-240 E O1 | Adder | 2.01 MW | 1.71 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958471 | AF2-141 | Adder | 2.04 MW | 1.74 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958731 | AF2-164 C O1 | Adder | 9.85 MW | 8.37 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958732 | AF2-164 E O1 | Adder | 6.56 MW | 5.58 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958741 | AF2-165 C | Adder | 2.21 MW | 1.88 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958742 | AF2-165 E | Adder | 1.47 MW | 1.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958751 | AF2-166 C | Adder | 2.3 MW | 1.96 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958752 | AF2-166 E | Adder | 1.54 MW | 1.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959441 | AF2-235 C | Adder | 1.04 MW | 0.88 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959442 | AF2-235 E | Adder | 0.69 MW | 0.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959471 | AF2-238 C | Adder | 2.14 MW | 1.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959472 | AF2-238 E | Adder | 1.43 MW | 1.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959521 | AF2-243 C | Adder | 1.65 MW | 1.41 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959522 | AF2-243 E | Adder | 1.1 MW | 0.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959802 | AF2-271 E | Adder | 0.73 MW | 0.62 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960022 | AF2-293 E | Adder | 0.18 MW | 0.15 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960031 | AF2-294 C | Adder | 1.62 MW | 1.38 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960032 | AF2-294 E | Adder | 1.08 MW | 0.92 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960041 | AF2-295 C | Adder | 2.16 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960042 | AF2-295 E | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960051 | AF2-296 C | Adder | 3.03 MW | 2.58 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960052 | AF2-296 E | Adder | 2.02 MW | 1.72 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960451 | AF2-336 C | Adder | 3.9 MW | 3.32 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960452 | AF2-336 E | Adder | 2.6 MW | 2.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960461 | AF2-337 C | Adder | 3.9 MW | 3.32 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960462 | AF2-337 E | Adder | 2.6 MW | 2.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961141 | AF2-405 | Adder | 1.73 MW | 1.47 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961151 | AF2-406 | Adder | 13.0 MW | 11.05 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961211 | AF2-412 | Adder | 26.57 MW | 22.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200636 | 26IUP CO-G | 50/50 | 0.82 MW | 0.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200794 | 26CONEMAGH | 50/50 | 0.65 MW | 0.65 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200809 | 26SITHE | 50/50 | 2.6 MW | 2.6 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200835 | 26ARN_Z1-066 | Adder | 2.04 MW | 1.74 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200837 | 26HOMER C1 | 50/50 | 44.79 MW | 44.79 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200838 | 26HOMER C2 | 50/50 | 37.23 MW | 37.23 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200839 | 26HOMER C3 | 50/50 | 39.41 MW | 39.41 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200846 | 26FORWARD | 50/50 | 0.18 MW | 0.18 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200852 | 26WARR RDG | Adder | 0.58 MW | 0.49 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200864 | K-013 E | 50/50 | 7.87 MW | 7.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200883 | Q-053 E | Adder | 9.7 MW | 8.24 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200888 | 26HIGHLAND | 50/50 | 0.47 MW | 0.47 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200894 | 26K02 | Adder | 8.51 MW | 7.23 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200925 | 26R32 | 50/50 | 0.73 MW | 0.73 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 202158 | 26CON.GEN1 | 50/50 | 0.14 MW | 0.14 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 203915 | 26BF_Z2-108 | Adder | 4.59 MW | 3.9 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 203999 | P-047 E | Adder | 15.11 MW | 12.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 235003 | AC1-025 E | Adder | 0.22 MW | 0.19 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 236828 | 01GRAYMONT | Adder | 0.61 MW | 0.52 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 292350 | K-023 | Adder | 6.36 MW | 5.4 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 292542 | L-013 1 | Adder | 8.17 MW | 6.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293301 | N-039 E | Adder | 20.17 MW | 17.15 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293393 | V3-030E | Adder | 8.84 MW | 7.51 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293432 | R-040 E | Adder | 0.46 MW | 0.39 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293603 | O-018 E | 50/50 | 17.59 MW | 17.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293902 | O-048 E | Adder | 7.35 MW | 6.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 294515 | O38_P22 | Adder | 17.65 MW | 15.01 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 294903 | P-060 E | Adder | 13.19 MW | 11.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 916202 | Z1-069 E | Adder | 12.26 MW | 10.42 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 931092 | AB1-160 E | Adder | 3.5 MW | 2.98 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 938951 | AE1-123 | Adder | 3.59 MW | 3.05 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 939291 | AE1-160 C | Adder | 2.2 MW | 1.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 939292 | AE1-160 E | Adder | 1.26 MW | 1.07 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940201 | AE2-001 C | Adder | 1.82 MW | 1.55 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940202 | AE2-001 E | Adder | 1.21 MW | 1.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940681 | AE2-055 C | Adder | 1.78 MW | 1.51 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940682 | AE2-055 E | Adder | 1.19 MW | 1.01 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940861 | AE2-074 C | Adder | 3.37 MW | 2.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940862 | AE2-074 E | Adder | 4.44 MW | 3.77 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941191 | AE2-113 C | Adder | 13.24 MW | 11.26 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941192 | AE2-113 E | Adder | 12.43 MW | 10.56 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941231 | AE2-117 C | Adder | 2.83 MW | 2.4 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941232 | AE2-117 E | Adder | 1.88 MW | 1.6 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941241 | AE2-118 C | Adder | 2.97 MW | 2.53 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941242 | AE2-118 E | Adder | 1.98 MW | 1.68 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941271 | AE2-121 C | Adder | 0.97 MW | 0.83 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941272 | AE2-121 E | Adder | 0.65 MW | 0.55 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941321 | AE2-126 C | Adder | 2.4 MW | 2.04 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941322 | AE2-126 E | Adder | 1.6 MW | 1.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941331 | AE2-129 C | Adder | 2.78 MW | 2.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941332 | AE2-129 E | Adder | 1.85 MW | 1.57 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941351 | AE2-131 C | Adder | 2.78 MW | 2.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941352 | AE2-131 E | Adder | 1.85 MW | 1.57 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941421 | AE2-139 C | Adder | 8.58 MW | 7.29 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941422 | AE2-139 E | Adder | 5.72 MW | 4.86 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946071 | AF1-272 C O1 | 50/50 | 25.67 MW | 25.67 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946072 | AF1-272 E O1 | 50/50 | 17.12 MW | 17.12 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946111 | AF1-276 C | Adder | 15.12 MW | 12.85 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946112 | AF1-276 E | Adder | 7.45 MW | 6.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946121 | AF1-277 C | Adder | 15.12 MW | 12.85 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946122 | AF1-277 E | Adder | 7.45 MW | 6.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946131 | AF1-278 C | Adder | 12.06 MW | 10.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946132 | AF1-278 E | Adder | 5.99 MW | 5.09 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946221 | AF1-287 C | Adder | 1.72 MW | 1.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946222 | AF1-287 E | Adder | 1.15 MW | 0.97 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946381 | AF1-302 C | Adder | 3.3 MW | 2.8 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946382 | AF1-302 E | Adder | 4.39 MW | 3.73 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946571 | AF1-321 C O1 | 50/50 | 4.11 MW | 4.11 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946572 | AF1-321 E O1 | 50/50 | 2.74 MW | 2.74 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946771 | AF1-217 C | Adder | 1.72 MW | 1.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946772 | AF1-217 E | Adder | 1.15 MW | 0.97 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957001 | AF2-001 C O1 | 50/50 | 4.11 MW | 4.11 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957002 | AF2-001 E O1 | 50/50 | 2.74 MW | 2.74 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957011 | AF2-002 C O1 | 50/50 | 2.05 MW | 2.05 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957012 | AF2-002 E O1 | 50/50 | 1.37 MW | 1.37 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957161 | AF2-010 C | Adder | 7.05 MW | 5.99 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957162 | AF2-010 E | Adder | 4.75 MW | 4.04 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957451 | AF2-039 C | Adder | 1.66 MW | 1.41 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957452 | AF2-039 E | Adder | 1.11 MW | 0.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957561 | AF2-050 C | Adder | 9.94 MW | 8.45 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957562 | AF2-050 E | Adder | 6.63 MW | 5.63 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957931 | AF2-087 C | Adder | 0.86 MW | 0.73 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957932 | AF2-087 E | Adder | 1.18 MW | 1.01 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957941 | AF2-088 C | Adder | 0.8 MW | 0.68 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957942 | AF2-088 E | Adder | 0.53 MW | 0.45 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957981 | AF2-092 C | Adder | 2.34 MW | 1.99 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957982 | AF2-092 E | Adder | 1.56 MW | 1.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958271 | AF2-121 C | Adder | 2.78 MW | 2.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958272 | AF2-121 E | Adder | 1.85 MW | 1.57 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958361 | AF2-130 C | Adder | 2.3 MW | 1.96 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958362 | AF2-130 E | Adder | 1.54 MW | 1.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200833 | 26SEWRDB34 | 50/50 | 34.08 MW | 34.08 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959301 | AF2-221 C | 50/50 | 2.17 MW | 2.17 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959302 | AF2-221 E | 50/50 | 3.0 MW | 3.0 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 292340 | 26SW_E13_K22 | Adder | 2.19 MW | 1.86 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964451 | AG1-308 C O1 | Adder | 1.92 MW | 1.63 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 964452 | AG1-308 E O1 | Adder | 2.69 MW | 2.28 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960901 | AG1-000C C | Adder | 13.48 MW | 11.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960902 | AG1-000C E | Adder | 6.64 MW | 5.64 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946421 | AF2-000A C | Adder | 8.95 MW | 7.61 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946422 | AF2-000A E | Adder | 26.84 MW | 22.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 966783 | AG1-549 BAT | 50/50 | 9.17 MW | 9.17 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.48 MW | 0.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.67 MW | 0.67 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.86 MW | 0.86 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.34 MW | 0.34 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.28 MW | 0.28 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 7.36 MW | 7.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.34 MW | 0.34 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.25 MW | 1.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.66 MW | 0.66 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.49 MW | 0.49 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.51 MW | 3.51 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.31 MW | 1.31 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.28 MW | 0.28 MW |
| Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961971 | AG1-040 C | Adder | 1.81 MW | 1.54 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961972 | AG1-040 E | Adder | 1.21 MW | 1.02 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961981 | AG1-041 C | Adder | 2.34 MW | 1.99 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961982 | AG1-041 E | Adder | 1.56 MW | 1.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962411 | AG1-090 C O1 | Adder | 18.53 MW | 15.75 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962412 | AG1-090 E O1 | Adder | 4.63 MW | 3.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962511 | AG1-100 C | Adder | 1.72 MW | 1.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962512 | AG1-100 E | Adder | 1.14 MW | 0.97 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962911 | AG1-140 C | Adder | 0.26 MW | 0.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 962912 | AG1-140 E | Adder | 0.13 MW | 0.11 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963441 | AG1-193 C | Adder | 2.14 MW | 1.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963442 | AG1-193 E | Adder | 1.43 MW | 1.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963481 | AG1-197 C | Adder | 1.37 MW | 1.17 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963482 | AG1-197 E | Adder | 0.91 MW | 0.78 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963491 | AG1-198 C | Adder | 1.1 MW | 0.93 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963492 | AG1-198 E | Adder | 0.73 MW | 0.62 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963991 | AG1-253 C | Adder | 0.39 MW | 0.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 963992 | AG1-253 E | Adder | 0.19 MW | 0.16 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964031 | AG1-257 C | Adder | 1.25 MW | 1.06 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964032 | AG1-257 E | Adder | 1.75 MW | 1.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964201 | AG1-281 C | Adder | 3.68 MW | 3.12 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964202 | AG1-281 E | Adder | 2.45 MW | 2.08 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964391 | AG1-301 C | Adder | 2.8 MW | 2.38 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964392 | AG1-301 E | Adder | 1.86 MW | 1.58 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964411 | AG1-303 C O1 | Adder | 4.27 MW | 3.63 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964412 | AG1-303 E O1 | Adder | 2.85 MW | 2.42 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 966771 | AG1-548 C | Adder | 17.34 MW | 14.74 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 966772 | AG1-548 E | Adder | 5.28 MW | 4.49 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965121 | AG1-377 C O1 | Adder | 2.78 MW | 2.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965122 | AG1-377 E O1 | Adder | 1.85 MW | 1.57 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965131 | AG1-378 C O1 | Adder | 2.78 MW | 2.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965132 | AG1-378 E O1 | Adder | 1.85 MW | 1.57 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965171 | AG1-382 C | Adder | 3.92 MW | 3.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965172 | AG1-382 E | Adder | 2.61 MW | 2.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965241 | AG1-392C C O | Adder | 2.61 MW | 2.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965242 | AG1-392C E O | Adder | 1.74 MW | 1.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965251 | AG1-392B C O | Adder | 2.61 MW | 2.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965252 | AG1-392B E O | Adder | 1.74 MW | 1.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965261 | AG1-392A C O | Adder | 5.23 MW | 4.44 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965262 | AG1-392A E O | Adder | 3.49 MW | 2.96 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965271 | AG1-392 C O1 | Adder | 5.23 MW | 4.44 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965272 | AG1-392 E O1 | Adder | 3.49 MW | 2.96 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 965861 | AG1-455 | Adder | 4.8 MW | 4.08 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 966041 | AG1-473 C | Adder | 4.22 MW | 3.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 966042 | AG1-473 E | Adder | 2.82 MW | 2.39 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 290086 | Q-036 E | Adder | 10.55 MW | 8.97 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 296332 | R-032 E | 50/50 | 20.3 MW | 20.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 913142 | Y1-033 E OP1 | Adder | 6.59 MW | 5.61 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 936991 | AD2-133 C | Adder | 3.97 MW | 3.38 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 936992 | AD2-133 E | Adder | 18.19 MW | 15.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942121 | AE2-224 C | Adder | 19.88 MW | 16.9 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942122 | AE2-224 E | Adder | 13.25 MW | 11.27 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942351 | AE2-248 C | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942352 | AE2-248 E | Adder | 0.96 MW | 0.81 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942361 | AE2-249 C | Adder | 3.24 MW | 2.75 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942362 | AE2-249 E | Adder | 2.16 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942491 | AE2-262 C | Adder | 8.14 MW | 6.92 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942492 | AE2-262 E | Adder | 5.47 MW | 4.65 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942501 | AE2-263 C | Adder | 7.65 MW | 6.5 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942502 | AE2-263 E | Adder | 5.11 MW | 4.34 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942811 | AE2-299 C | Adder | 4.6 MW | 3.91 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942812 | AE2-299 E | Adder | 18.41 MW | 15.65 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942961 | AE2-316 C | Adder | 7.54 MW | 6.41 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942962 | AE2-316 E | Adder | 8.93 MW | 7.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943151 | AE2-344 C | Adder | 9.98 MW | 8.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943152 | AE2-344 E | Adder | 6.65 MW | 5.65 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943351 | AF1-006 C | Adder | 1.72 MW | 1.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943352 | AF1-006 E | Adder | 0.97 MW | 0.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943711 | AF1-039 C O1 | Adder | 1.74 MW | 1.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943712 | AF1-039 E O1 | Adder | 1.16 MW | 0.99 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944181 | AF1-086 C O1 | Adder | 5.92 MW | 5.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944182 | AF1-086 E O1 | Adder | 25.74 MW | 21.88 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944261 | AF1-094 C | Adder | 1.83 MW | 1.55 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944262 | AF1-094 E | Adder | 1.22 MW | 1.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944301 | AF1-098 C | Adder | 7.08 MW | 6.02 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944302 | AF1-098 E | Adder | 4.72 MW | 4.01 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944311 | AF1-099 C | Adder | 12.68 MW | 10.78 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944312 | AF1-099 E | Adder | 8.45 MW | 7.19 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944321 | AF1-100 C | Adder | 26.26 MW | 22.32 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944322 | AF1-100 E | Adder | 17.51 MW | 14.88 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944411 | AF1-106 O1 | Adder | 3.47 MW | 2.95 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944471 | AF1-112 C | Adder | 1.34 MW | 1.14 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944472 | AF1-112 E | Adder | 0.92 MW | 0.78 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944691 | AF1-134 C | Adder | 3.03 MW | 2.58 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944692 | AF1-134 E | Adder | 2.02 MW | 1.72 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944751 | AF1-140 C | Adder | 3.17 MW | 2.69 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944752 | AF1-140 E | Adder | 2.11 MW | 1.8 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944771 | AF1-142 C | Adder | 20.29 MW | 17.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944772 | AF1-142 E | Adder | 13.53 MW | 11.5 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944781 | AF1-143 C | Adder | 15.31 MW | 13.02 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944782 | AF1-143 E | Adder | 8.17 MW | 6.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944881 | AF1-153 C O1 | Adder | 2.16 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944882 | AF1-153 E O1 | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944901 | AF1-155 C | Adder | 2.16 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944902 | AF1-155 E | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945021 | AF1-167 C | Adder | 1.39 MW | 1.19 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945022 | AF1-167 E | Adder | 0.93 MW | 0.79 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945051 | AF1-170 C | Adder | 6.38 MW | 5.42 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945052 | AF1-170 E | Adder | 4.25 MW | 3.61 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945451 | AF1-210 C | Adder | 1.53 MW | 1.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945452 | AF1-210 E | Adder | 1.02 MW | 0.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945751 | AF1-240 C O1 | Adder | 3.02 MW | 2.56 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945752 | AF1-240 E O1 | Adder | 2.01 MW | 1.71 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958471 | AF2-141 | Adder | 2.04 MW | 1.74 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958731 | AF2-164 C O1 | Adder | 9.85 MW | 8.37 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958732 | AF2-164 E O1 | Adder | 6.56 MW | 5.58 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958741 | AF2-165 C | Adder | 2.21 MW | 1.88 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958742 | AF2-165 E | Adder | 1.47 MW | 1.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958751 | AF2-166 C | Adder | 2.3 MW | 1.96 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958752 | AF2-166 E | Adder | 1.54 MW | 1.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959441 | AF2-235 C | Adder | 1.04 MW | 0.88 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959442 | AF2-235 E | Adder | 0.69 MW | 0.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959471 | AF2-238 C | Adder | 2.14 MW | 1.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959472 | AF2-238 E | Adder | 1.43 MW | 1.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959521 | AF2-243 C | Adder | 1.65 MW | 1.41 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959522 | AF2-243 E | Adder | 1.1 MW | 0.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959802 | AF2-271 E | Adder | 0.73 MW | 0.62 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960022 | AF2-293 E | Adder | 0.18 MW | 0.15 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960031 | AF2-294 C | Adder | 1.62 MW | 1.38 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960032 | AF2-294 E | Adder | 1.08 MW | 0.92 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960041 | AF2-295 C | Adder | 2.16 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960042 | AF2-295 E | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960051 | AF2-296 C | Adder | 3.03 MW | 2.58 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960052 | AF2-296 E | Adder | 2.02 MW | 1.72 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960451 | AF2-336 C | Adder | 3.9 MW | 3.32 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960452 | AF2-336 E | Adder | 2.6 MW | 2.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960461 | AF2-337 C | Adder | 3.9 MW | 3.32 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960462 | AF2-337 E | Adder | 2.6 MW | 2.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961141 | AF2-405 | Adder | 1.73 MW | 1.47 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961151 | AF2-406 | Adder | 13.0 MW | 11.05 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961211 | AF2-412 | Adder | 26.57 MW | 22.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200636 | 26IUP CO-G | 50/50 | 0.82 MW | 0.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200794 | 26CONEMAGH | 50/50 | 0.65 MW | 0.65 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200809 | 26SITHE | 50/50 | 2.6 MW | 2.6 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200835 | 26ARN_Z1-066 | Adder | 2.04 MW | 1.74 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200837 | 26HOMER C1 | 50/50 | 44.79 MW | 44.79 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200838 | 26HOMER C2 | 50/50 | 37.23 MW | 37.23 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200839 | 26HOMER C3 | 50/50 | 39.41 MW | 39.41 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200846 | 26FORWARD | 50/50 | 0.18 MW | 0.18 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200852 | 26WARR RDG | Adder | 0.58 MW | 0.49 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200864 | K-013 E | 50/50 | 7.87 MW | 7.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200883 | Q-053 E | Adder | 9.7 MW | 8.24 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200888 | 26HIGHLAND | 50/50 | 0.47 MW | 0.47 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200894 | 26K02 | Adder | 8.51 MW | 7.23 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200925 | 26R32 | 50/50 | 0.73 MW | 0.73 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 202158 | 26CON.GEN1 | 50/50 | 0.14 MW | 0.14 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 203915 | 26BF_Z2-108 | Adder | 4.59 MW | 3.9 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 203999 | P-047 E | Adder | 15.11 MW | 12.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 235003 | AC1-025 E | Adder | 0.22 MW | 0.19 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 236828 | 01GRAYMONT | Adder | 0.61 MW | 0.52 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 292350 | K-023 | Adder | 6.36 MW | 5.4 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 292542 | L-013 1 | Adder | 8.17 MW | 6.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293301 | N-039 E | Adder | 20.17 MW | 17.15 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293393 | V3-030E | Adder | 8.84 MW | 7.51 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293432 | R-040 E | Adder | 0.46 MW | 0.39 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293603 | O-018 E | 50/50 | 17.59 MW | 17.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293902 | O-048 E | Adder | 7.35 MW | 6.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 294515 | O38_P22 | Adder | 17.65 MW | 15.01 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 294903 | P-060 E | Adder | 13.19 MW | 11.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 916202 | Z1-069 E | Adder | 12.26 MW | 10.42 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 931092 | AB1-160 E | Adder | 3.5 MW | 2.98 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 938951 | AE1-123 | Adder | 3.59 MW | 3.05 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 939291 | AE1-160 C | Adder | 2.2 MW | 1.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 939292 | AE1-160 E | Adder | 1.26 MW | 1.07 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940201 | AE2-001 C | Adder | 1.82 MW | 1.55 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940202 | AE2-001 E | Adder | 1.21 MW | 1.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940681 | AE2-055 C | Adder | 1.78 MW | 1.51 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940682 | AE2-055 E | Adder | 1.19 MW | 1.01 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940861 | AE2-074 C | Adder | 3.37 MW | 2.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940862 | AE2-074 E | Adder | 4.44 MW | 3.77 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941191 | AE2-113 C | Adder | 13.24 MW | 11.26 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941192 | AE2-113 E | Adder | 12.43 MW | 10.56 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941231 | AE2-117 C | Adder | 2.83 MW | 2.4 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941232 | AE2-117 E | Adder | 1.88 MW | 1.6 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941241 | AE2-118 C | Adder | 2.97 MW | 2.53 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941242 | AE2-118 E | Adder | 1.98 MW | 1.68 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941271 | AE2-121 C | Adder | 0.97 MW | 0.83 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941272 | AE2-121 E | Adder | 0.65 MW | 0.55 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941321 | AE2-126 C | Adder | 2.4 MW | 2.04 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941322 | AE2-126 E | Adder | 1.6 MW | 1.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941331 | AE2-129 C | Adder | 2.78 MW | 2.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941332 | AE2-129 E | Adder | 1.85 MW | 1.57 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941351 | AE2-131 C | Adder | 2.78 MW | 2.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941352 | AE2-131 E | Adder | 1.85 MW | 1.57 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941421 | AE2-139 C | Adder | 8.58 MW | 7.29 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941422 | AE2-139 E | Adder | 5.72 MW | 4.86 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946071 | AF1-272 C O1 | 50/50 | 25.67 MW | 25.67 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946072 | AF1-272 E O1 | 50/50 | 17.12 MW | 17.12 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946111 | AF1-276 C | Adder | 15.12 MW | 12.85 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946112 | AF1-276 E | Adder | 7.45 MW | 6.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946121 | AF1-277 C | Adder | 15.12 MW | 12.85 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946122 | AF1-277 E | Adder | 7.45 MW | 6.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946131 | AF1-278 C | Adder | 12.06 MW | 10.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946132 | AF1-278 E | Adder | 5.99 MW | 5.09 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946221 | AF1-287 C | Adder | 1.72 MW | 1.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946222 | AF1-287 E | Adder | 1.15 MW | 0.97 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946381 | AF1-302 C | Adder | 3.3 MW | 2.8 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946382 | AF1-302 E | Adder | 4.39 MW | 3.73 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946571 | AF1-321 C O1 | 50/50 | 4.11 MW | 4.11 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946572 | AF1-321 E O1 | 50/50 | 2.74 MW | 2.74 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946771 | AF1-217 C | Adder | 1.72 MW | 1.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946772 | AF1-217 E | Adder | 1.15 MW | 0.97 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957001 | AF2-001 C O1 | 50/50 | 4.11 MW | 4.11 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957002 | AF2-001 E O1 | 50/50 | 2.74 MW | 2.74 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957011 | AF2-002 C O1 | 50/50 | 2.05 MW | 2.05 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957012 | AF2-002 E O1 | 50/50 | 1.37 MW | 1.37 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957161 | AF2-010 C | Adder | 7.05 MW | 5.99 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957162 | AF2-010 E | Adder | 4.75 MW | 4.04 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957451 | AF2-039 C | Adder | 1.66 MW | 1.41 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957452 | AF2-039 E | Adder | 1.11 MW | 0.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957561 | AF2-050 C | Adder | 9.94 MW | 8.45 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957562 | AF2-050 E | Adder | 6.63 MW | 5.63 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957931 | AF2-087 C | Adder | 0.86 MW | 0.73 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957932 | AF2-087 E | Adder | 1.18 MW | 1.01 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957941 | AF2-088 C | Adder | 0.8 MW | 0.68 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957942 | AF2-088 E | Adder | 0.53 MW | 0.45 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957981 | AF2-092 C | Adder | 2.34 MW | 1.99 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957982 | AF2-092 E | Adder | 1.56 MW | 1.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958271 | AF2-121 C | Adder | 2.78 MW | 2.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958272 | AF2-121 E | Adder | 1.85 MW | 1.57 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958361 | AF2-130 C | Adder | 2.3 MW | 1.96 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958362 | AF2-130 E | Adder | 1.54 MW | 1.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200833 | 26SEWRDB34 | 50/50 | 34.08 MW | 34.08 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959301 | AF2-221 C | 50/50 | 2.17 MW | 2.17 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959302 | AF2-221 E | 50/50 | 3.0 MW | 3.0 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 292340 | 26SW_E13_K22 | Adder | 2.19 MW | 1.86 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964451 | AG1-308 C O1 | Adder | 1.92 MW | 1.63 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 964452 | AG1-308 E O1 | Adder | 2.69 MW | 2.28 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960901 | AG1-000C C | Adder | 13.48 MW | 11.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960902 | AG1-000C E | Adder | 6.64 MW | 5.64 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946421 | AF2-000A C | Adder | 8.95 MW | 7.61 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946422 | AF2-000A E | Adder | 26.84 MW | 22.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 966783 | AG1-549 BAT | 50/50 | 9.17 MW | 9.17 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.48 MW | 0.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.67 MW | 0.67 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.86 MW | 0.86 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.34 MW | 0.34 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.28 MW | 0.28 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 7.36 MW | 7.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.34 MW | 0.34 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.25 MW | 1.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.66 MW | 0.66 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.49 MW | 0.49 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.51 MW | 3.51 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.31 MW | 1.31 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.28 MW | 0.28 MW |
| Details for AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 962411 | AG1-090 C O1 | 50/50 | 14.99 MW | 14.99 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 962412 | AG1-090 E O1 | 50/50 | 3.75 MW | 3.75 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 964031 | AG1-257 C | 50/50 | 4.19 MW | 4.19 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 964032 | AG1-257 E | 50/50 | 5.86 MW | 5.86 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965121 | AG1-377 C O1 | 50/50 | 2.25 MW | 2.25 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965122 | AG1-377 E O1 | 50/50 | 1.5 MW | 1.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965131 | AG1-378 C O1 | 50/50 | 2.25 MW | 2.25 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965132 | AG1-378 E O1 | 50/50 | 1.5 MW | 1.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965241 | AG1-392C C O | Adder | 1.46 MW | 1.24 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965242 | AG1-392C E O | Adder | 0.98 MW | 0.83 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965251 | AG1-392B C O | Adder | 1.46 MW | 1.24 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965252 | AG1-392B E O | Adder | 0.98 MW | 0.83 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965261 | AG1-392A C O | Adder | 2.92 MW | 2.49 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965262 | AG1-392A E O | Adder | 1.95 MW | 1.66 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965271 | AG1-392 C O1 | Adder | 2.92 MW | 2.49 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 965272 | AG1-392 E O1 | Adder | 1.95 MW | 1.66 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 966041 | AG1-473 C | 50/50 | 21.31 MW | 21.31 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 966042 | AG1-473 E | 50/50 | 14.21 MW | 14.21 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 290086 | Q-036 E | Adder | 5.4 MW | 4.59 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 936991 | AD2-133 C | Adder | 2.03 MW | 1.73 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 936992 | AD2-133 E | Adder | 9.3 MW | 7.91 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 942351 | AE2-248 C | 50/50 | 4.9 MW | 4.9 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 942352 | AE2-248 E | 50/50 | 3.27 MW | 3.27 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 942491 | AE2-262 C | 50/50 | 20.1 MW | 20.1 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 942492 | AE2-262 E | 50/50 | 13.51 MW | 13.51 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 942501 | AE2-263 C | 50/50 | 18.89 MW | 18.89 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 942502 | AE2-263 E | 50/50 | 12.62 MW | 12.62 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 942961 | AE2-316 C | 50/50 | 7.2 MW | 7.2 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 942962 | AE2-316 E | 50/50 | 8.52 MW | 8.52 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944181 | AF1-086 C O1 | Adder | 2.28 MW | 1.94 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944182 | AF1-086 E O1 | Adder | 9.9 MW | 8.42 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944311 | AF1-099 C | 50/50 | 27.75 MW | 27.75 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944312 | AF1-099 E | 50/50 | 18.5 MW | 18.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944321 | AF1-100 C | 50/50 | 49.8 MW | 49.8 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944322 | AF1-100 E | 50/50 | 33.2 MW | 33.2 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944411 | AF1-106 O1 | Adder | 2.37 MW | 2.01 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944471 | AF1-112 C | 50/50 | 4.52 MW | 4.52 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944472 | AF1-112 E | 50/50 | 3.1 MW | 3.1 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944691 | AF1-134 C | 50/50 | 2.09 MW | 2.09 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944692 | AF1-134 E | 50/50 | 1.39 MW | 1.39 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944771 | AF1-142 C | 50/50 | 44.4 MW | 44.4 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944772 | AF1-142 E | 50/50 | 29.6 MW | 29.6 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944881 | AF1-153 C O1 | 50/50 | 2.89 MW | 2.89 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944882 | AF1-153 E O1 | 50/50 | 1.93 MW | 1.93 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944901 | AF1-155 C | 50/50 | 2.87 MW | 2.87 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 944902 | AF1-155 E | 50/50 | 1.91 MW | 1.91 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 945161 | AF1-181 | 50/50 | 0.04 MW | 0.04 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 945171 | AF1-182 | 50/50 | 0.23 MW | 0.23 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 945181 | AF1-183 | 50/50 | 0.05 MW | 0.05 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 959471 | AF2-238 C | Adder | 1.52 MW | 1.29 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 959472 | AF2-238 E | Adder | 1.01 MW | 0.86 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 960022 | AF2-293 E | 50/50 | 0.57 MW | 0.57 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 960031 | AF2-294 C | Adder | 1.14 MW | 0.97 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 960032 | AF2-294 E | Adder | 0.76 MW | 0.64 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 960041 | AF2-295 C | 50/50 | 2.87 MW | 2.87 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 960042 | AF2-295 E | 50/50 | 1.91 MW | 1.91 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 960051 | AF2-296 C | 50/50 | 2.09 MW | 2.09 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 960052 | AF2-296 E | 50/50 | 1.39 MW | 1.39 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 961141 | AF2-405 | Adder | 1.18 MW | 1.0 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 961151 | AF2-406 | Adder | 8.87 MW | 7.54 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 961211 | AF2-412 | Adder | 14.43 MW | 12.26 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 961451 | AF2-436 | Adder | 0.18 MW | 0.16 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 200649 | 26PENNTECH | 50/50 | 1.61 MW | 1.61 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 200665 | 26SHAWVL 3 | 50/50 | 9.87 MW | 9.87 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 200666 | 26SHAWVL 4 | 50/50 | 9.71 MW | 9.71 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 200715 | 26SHAWVL 1 | 50/50 | 6.18 MW | 6.18 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 200722 | 26SHAWVL 2 | 50/50 | 6.32 MW | 6.32 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 200823 | 26MHP_X3-003 | Adder | 7.13 MW | 6.06 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 200894 | 26K02 | 50/50 | 11.12 MW | 11.12 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 200913 | 26SHAW-D | 50/50 | 0.26 MW | 0.26 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 203932 | AA2-133 GEN | Adder | 2.43 MW | 2.07 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 203999 | P-047 E | Adder | 9.42 MW | 8.0 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 235003 | AC1-025 E | 50/50 | 0.77 MW | 0.77 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 236828 | 01GRAYMONT | 50/50 | 1.98 MW | 1.98 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 294573 | P-028 E | Adder | 13.79 MW | 11.72 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 916202 | Z1-069 E | Adder | 6.84 MW | 5.81 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 931092 | AB1-160 E | Adder | 1.95 MW | 1.66 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 940201 | AE2-001 C | 50/50 | 5.93 MW | 5.93 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 940202 | AE2-001 E | 50/50 | 3.96 MW | 3.96 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 940681 | AE2-055 C | 50/50 | 6.26 MW | 6.26 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 940682 | AE2-055 E | 50/50 | 4.17 MW | 4.17 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 940861 | AE2-074 C | Adder | 1.9 MW | 1.62 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 940862 | AE2-074 E | Adder | 2.5 MW | 2.13 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941191 | AE2-113 C | 50/50 | 10.74 MW | 10.74 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941192 | AE2-113 E | 50/50 | 10.08 MW | 10.08 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941271 | AE2-121 C | 50/50 | 3.12 MW | 3.12 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941272 | AE2-121 E | 50/50 | 2.09 MW | 2.09 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941321 | AE2-126 C | 50/50 | 2.88 MW | 2.88 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941322 | AE2-126 E | 50/50 | 1.92 MW | 1.92 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941331 | AE2-129 C | 50/50 | 2.25 MW | 2.25 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941332 | AE2-129 E | 50/50 | 1.5 MW | 1.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941351 | AE2-131 C | 50/50 | 2.25 MW | 2.25 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941352 | AE2-131 E | 50/50 | 1.5 MW | 1.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941421 | AE2-139 C | Adder | 8.38 MW | 7.12 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 941422 | AE2-139 E | Adder | 5.59 MW | 4.75 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 946111 | AF1-276 C | Adder | 8.42 MW | 7.15 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 946112 | AF1-276 E | Adder | 4.15 MW | 3.52 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 946121 | AF1-277 C | Adder | 8.42 MW | 7.15 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 946122 | AF1-277 E | Adder | 4.15 MW | 3.52 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 946131 | AF1-278 C | Adder | 6.71 MW | 5.71 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 946132 | AF1-278 E | Adder | 3.34 MW | 2.84 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 946381 | AF1-302 C | 50/50 | 3.14 MW | 3.14 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 946382 | AF1-302 E | 50/50 | 4.19 MW | 4.19 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 957451 | AF2-039 C | 50/50 | 2.09 MW | 2.09 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 957452 | AF2-039 E | 50/50 | 1.4 MW | 1.4 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 957941 | AF2-088 C | 50/50 | 1.01 MW | 1.01 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 957942 | AF2-088 E | 50/50 | 0.67 MW | 0.67 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 958271 | AF2-121 C | 50/50 | 2.25 MW | 2.25 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 958272 | AF2-121 E | 50/50 | 1.5 MW | 1.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 964451 | AG1-308 C O1 | 50/50 | 1.55 MW | 1.55 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 964452 | AG1-308 E O1 | 50/50 | 2.17 MW | 2.17 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 946421 | AF2-000A C | 50/50 | 12.69 MW | 12.69 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | 946422 | AF2-000A E | 50/50 | 38.05 MW | 38.05 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 2.42 MW | 2.42 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.73 MW | 2.73 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.68 MW | 10.68 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.24 MW | 5.24 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.1 MW | 0.1 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.22 MW | 2.22 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.05 MW | 1.05 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 14.21 MW | 14.21 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.72 MW | 0.72 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-230-17B28 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
| Details for AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 962411 | AG1-090 C O1 | 50/50 | 14.98 MW | 14.98 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 962412 | AG1-090 E O1 | 50/50 | 3.75 MW | 3.75 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 964031 | AG1-257 C | 50/50 | 4.19 MW | 4.19 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 964032 | AG1-257 E | 50/50 | 5.86 MW | 5.86 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965121 | AG1-377 C O1 | 50/50 | 2.25 MW | 2.25 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965122 | AG1-377 E O1 | 50/50 | 1.5 MW | 1.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965131 | AG1-378 C O1 | 50/50 | 2.25 MW | 2.25 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965132 | AG1-378 E O1 | 50/50 | 1.5 MW | 1.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965241 | AG1-392C C O | Adder | 1.46 MW | 1.24 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965242 | AG1-392C E O | Adder | 0.98 MW | 0.83 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965251 | AG1-392B C O | Adder | 1.46 MW | 1.24 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965252 | AG1-392B E O | Adder | 0.98 MW | 0.83 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965261 | AG1-392A C O | Adder | 2.92 MW | 2.49 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965262 | AG1-392A E O | Adder | 1.95 MW | 1.66 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965271 | AG1-392 C O1 | Adder | 2.92 MW | 2.49 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965272 | AG1-392 E O1 | Adder | 1.95 MW | 1.66 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 966041 | AG1-473 C | 50/50 | 21.31 MW | 21.31 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 966042 | AG1-473 E | 50/50 | 14.21 MW | 14.21 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 290086 | Q-036 E | Adder | 5.39 MW | 4.58 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 936991 | AD2-133 C | Adder | 2.03 MW | 1.73 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 936992 | AD2-133 E | Adder | 9.3 MW | 7.91 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942351 | AE2-248 C | 50/50 | 4.9 MW | 4.9 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942352 | AE2-248 E | 50/50 | 3.27 MW | 3.27 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942491 | AE2-262 C | 50/50 | 20.1 MW | 20.1 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942492 | AE2-262 E | 50/50 | 13.51 MW | 13.51 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942501 | AE2-263 C | 50/50 | 18.89 MW | 18.89 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942502 | AE2-263 E | 50/50 | 12.61 MW | 12.61 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942961 | AE2-316 C | 50/50 | 7.19 MW | 7.19 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942962 | AE2-316 E | 50/50 | 8.52 MW | 8.52 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944181 | AF1-086 C O1 | Adder | 2.28 MW | 1.94 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944182 | AF1-086 E O1 | Adder | 9.9 MW | 8.42 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944311 | AF1-099 C | 50/50 | 27.75 MW | 27.75 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944312 | AF1-099 E | 50/50 | 18.5 MW | 18.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944321 | AF1-100 C | 50/50 | 49.79 MW | 49.79 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944322 | AF1-100 E | 50/50 | 33.19 MW | 33.19 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944411 | AF1-106 O1 | Adder | 2.37 MW | 2.01 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944471 | AF1-112 C | 50/50 | 4.52 MW | 4.52 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944472 | AF1-112 E | 50/50 | 3.1 MW | 3.1 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944691 | AF1-134 C | 50/50 | 2.09 MW | 2.09 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944692 | AF1-134 E | 50/50 | 1.39 MW | 1.39 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944771 | AF1-142 C | 50/50 | 44.39 MW | 44.39 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944772 | AF1-142 E | 50/50 | 29.59 MW | 29.59 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944881 | AF1-153 C O1 | 50/50 | 2.89 MW | 2.89 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944882 | AF1-153 E O1 | 50/50 | 1.93 MW | 1.93 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944901 | AF1-155 C | 50/50 | 2.87 MW | 2.87 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944902 | AF1-155 E | 50/50 | 1.91 MW | 1.91 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 945161 | AF1-181 | 50/50 | 0.04 MW | 0.04 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 945171 | AF1-182 | 50/50 | 0.23 MW | 0.23 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 945181 | AF1-183 | 50/50 | 0.05 MW | 0.05 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 959471 | AF2-238 C | Adder | 1.52 MW | 1.29 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 959472 | AF2-238 E | Adder | 1.01 MW | 0.86 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960022 | AF2-293 E | 50/50 | 0.57 MW | 0.57 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960031 | AF2-294 C | Adder | 1.15 MW | 0.98 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960032 | AF2-294 E | Adder | 0.77 MW | 0.65 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960041 | AF2-295 C | 50/50 | 2.87 MW | 2.87 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960042 | AF2-295 E | 50/50 | 1.91 MW | 1.91 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960051 | AF2-296 C | 50/50 | 2.09 MW | 2.09 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960052 | AF2-296 E | 50/50 | 1.39 MW | 1.39 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 961141 | AF2-405 | Adder | 1.18 MW | 1.01 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 961151 | AF2-406 | Adder | 8.88 MW | 7.54 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 961211 | AF2-412 | Adder | 14.43 MW | 12.27 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 961451 | AF2-436 | Adder | 0.19 MW | 0.16 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200649 | 26PENNTECH | 50/50 | 1.61 MW | 1.61 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200665 | 26SHAWVL 3 | 50/50 | 9.87 MW | 9.87 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200666 | 26SHAWVL 4 | 50/50 | 9.71 MW | 9.71 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200715 | 26SHAWVL 1 | 50/50 | 6.18 MW | 6.18 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200722 | 26SHAWVL 2 | 50/50 | 6.32 MW | 6.32 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200823 | 26MHP_X3-003 | Adder | 7.34 MW | 6.24 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200894 | 26K02 | 50/50 | 11.1 MW | 11.1 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200913 | 26SHAW-D | 50/50 | 0.26 MW | 0.26 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 203932 | AA2-133 GEN | Adder | 2.46 MW | 2.09 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 203999 | P-047 E | Adder | 9.42 MW | 8.01 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 235003 | AC1-025 E | 50/50 | 0.77 MW | 0.77 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 236828 | 01GRAYMONT | 50/50 | 1.98 MW | 1.98 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 294573 | P-028 E | Adder | 14.2 MW | 12.07 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 916202 | Z1-069 E | Adder | 6.84 MW | 5.81 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 931092 | AB1-160 E | Adder | 1.95 MW | 1.66 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940201 | AE2-001 C | 50/50 | 5.93 MW | 5.93 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940202 | AE2-001 E | 50/50 | 3.96 MW | 3.96 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940681 | AE2-055 C | 50/50 | 6.26 MW | 6.26 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940682 | AE2-055 E | 50/50 | 4.17 MW | 4.17 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940861 | AE2-074 C | Adder | 1.9 MW | 1.62 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940862 | AE2-074 E | Adder | 2.5 MW | 2.13 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941191 | AE2-113 C | 50/50 | 10.74 MW | 10.74 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941192 | AE2-113 E | 50/50 | 10.08 MW | 10.08 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941271 | AE2-121 C | 50/50 | 3.12 MW | 3.12 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941272 | AE2-121 E | 50/50 | 2.09 MW | 2.09 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941321 | AE2-126 C | 50/50 | 2.88 MW | 2.88 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941322 | AE2-126 E | 50/50 | 1.92 MW | 1.92 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941331 | AE2-129 C | 50/50 | 2.25 MW | 2.25 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941332 | AE2-129 E | 50/50 | 1.5 MW | 1.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941351 | AE2-131 C | 50/50 | 2.25 MW | 2.25 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941352 | AE2-131 E | 50/50 | 1.5 MW | 1.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941421 | AE2-139 C | Adder | 8.36 MW | 7.1 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941422 | AE2-139 E | Adder | 5.57 MW | 4.74 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946111 | AF1-276 C | Adder | 8.42 MW | 7.16 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946112 | AF1-276 E | Adder | 4.15 MW | 3.52 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946121 | AF1-277 C | Adder | 8.42 MW | 7.16 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946122 | AF1-277 E | Adder | 4.15 MW | 3.52 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946131 | AF1-278 C | Adder | 6.71 MW | 5.71 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946132 | AF1-278 E | Adder | 3.34 MW | 2.84 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946381 | AF1-302 C | 50/50 | 3.14 MW | 3.14 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946382 | AF1-302 E | 50/50 | 4.19 MW | 4.19 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 957451 | AF2-039 C | 50/50 | 2.09 MW | 2.09 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 957452 | AF2-039 E | 50/50 | 1.4 MW | 1.4 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 957941 | AF2-088 C | 50/50 | 1.01 MW | 1.01 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 957942 | AF2-088 E | 50/50 | 0.67 MW | 0.67 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 958271 | AF2-121 C | 50/50 | 2.25 MW | 2.25 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 958272 | AF2-121 E | 50/50 | 1.5 MW | 1.5 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 964451 | AG1-308 C O1 | 50/50 | 1.55 MW | 1.55 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 964452 | AG1-308 E O1 | 50/50 | 2.17 MW | 2.17 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946421 | AF2-000A C | 50/50 | 12.68 MW | 12.68 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946422 | AF2-000A E | 50/50 | 38.05 MW | 38.05 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 2.43 MW | 2.43 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.72 MW | 2.72 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.67 MW | 10.67 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.24 MW | 5.24 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.1 MW | 0.1 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.22 MW | 2.22 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.05 MW | 1.05 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 14.21 MW | 14.21 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.72 MW | 0.72 MW |
| AG1-473 TAP-26LEWISTWN 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
| Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961971 | AG1-040 C | Adder | 1.71 MW | 1.45 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961972 | AG1-040 E | Adder | 1.14 MW | 0.97 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961981 | AG1-041 C | 50/50 | 2.04 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961982 | AG1-041 E | 50/50 | 1.36 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962411 | AG1-090 C O1 | Adder | 15.74 MW | 13.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962412 | AG1-090 E O1 | Adder | 3.94 MW | 3.35 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962511 | AG1-100 C | Adder | 1.63 MW | 1.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962512 | AG1-100 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962911 | AG1-140 C | Adder | 0.25 MW | 0.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962912 | AG1-140 E | Adder | 0.13 MW | 0.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963441 | AG1-193 C | Adder | 1.92 MW | 1.64 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963442 | AG1-193 E | Adder | 1.28 MW | 1.09 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963481 | AG1-197 C | Adder | 1.29 MW | 1.1 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963482 | AG1-197 E | Adder | 0.86 MW | 0.73 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963491 | AG1-198 C | Adder | 1.0 MW | 0.85 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963492 | AG1-198 E | Adder | 0.67 MW | 0.57 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963991 | AG1-253 C | Adder | 0.37 MW | 0.32 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963992 | AG1-253 E | Adder | 0.18 MW | 0.15 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964031 | AG1-257 C | Adder | 1.14 MW | 0.97 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964032 | AG1-257 E | Adder | 1.59 MW | 1.35 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964201 | AG1-281 C | 50/50 | 3.24 MW | 3.24 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964202 | AG1-281 E | 50/50 | 2.16 MW | 2.16 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964391 | AG1-301 C | Adder | 2.58 MW | 2.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964392 | AG1-301 E | Adder | 1.72 MW | 1.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964411 | AG1-303 C O1 | Adder | 4.02 MW | 3.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964412 | AG1-303 E O1 | Adder | 2.68 MW | 2.28 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 966771 | AG1-548 C | Adder | 15.89 MW | 13.5 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 966772 | AG1-548 E | Adder | 4.84 MW | 4.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965121 | AG1-377 C O1 | Adder | 2.36 MW | 2.01 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965122 | AG1-377 E O1 | Adder | 1.57 MW | 1.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965131 | AG1-378 C O1 | Adder | 2.36 MW | 2.01 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965132 | AG1-378 E O1 | Adder | 1.57 MW | 1.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965171 | AG1-382 C | 50/50 | 3.21 MW | 3.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965172 | AG1-382 E | 50/50 | 2.14 MW | 2.14 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965241 | AG1-392C C O | Adder | 2.6 MW | 2.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965242 | AG1-392C E O | Adder | 1.74 MW | 1.48 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965251 | AG1-392B C O | Adder | 2.6 MW | 2.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965252 | AG1-392B E O | Adder | 1.74 MW | 1.48 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965261 | AG1-392A C O | Adder | 5.21 MW | 4.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965262 | AG1-392A E O | Adder | 3.47 MW | 2.95 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965271 | AG1-392 C O1 | Adder | 5.21 MW | 4.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965272 | AG1-392 E O1 | Adder | 3.47 MW | 2.95 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965861 | AG1-455 | Adder | 4.55 MW | 3.87 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 966041 | AG1-473 C | Adder | 3.9 MW | 3.31 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 966042 | AG1-473 E | Adder | 2.6 MW | 2.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 290086 | Q-036 E | Adder | 9.07 MW | 7.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 296332 | R-032 E | 50/50 | 17.74 MW | 17.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 913142 | Y1-033 E OP1 | Adder | 5.73 MW | 4.87 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 936991 | AD2-133 C | Adder | 3.42 MW | 2.9 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 936992 | AD2-133 E | Adder | 15.64 MW | 13.29 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942121 | AE2-224 C | 50/50 | 19.43 MW | 19.43 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942122 | AE2-224 E | 50/50 | 12.95 MW | 12.95 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942351 | AE2-248 C | Adder | 1.31 MW | 1.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942352 | AE2-248 E | Adder | 0.87 MW | 0.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942361 | AE2-249 C | 50/50 | 2.83 MW | 2.83 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942362 | AE2-249 E | 50/50 | 1.89 MW | 1.89 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942491 | AE2-262 C | Adder | 7.37 MW | 6.26 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942492 | AE2-262 E | Adder | 4.95 MW | 4.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942501 | AE2-263 C | Adder | 6.92 MW | 5.88 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942502 | AE2-263 E | Adder | 4.62 MW | 3.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942811 | AE2-299 C | Adder | 4.42 MW | 3.75 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942812 | AE2-299 E | Adder | 17.66 MW | 15.01 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942961 | AE2-316 C | Adder | 6.89 MW | 5.86 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942962 | AE2-316 E | Adder | 8.16 MW | 6.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943151 | AE2-344 C | Adder | 9.45 MW | 8.03 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943152 | AE2-344 E | Adder | 6.3 MW | 5.35 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943351 | AF1-006 C | Adder | 1.64 MW | 1.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943352 | AF1-006 E | Adder | 0.92 MW | 0.78 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943711 | AF1-039 C O1 | Adder | 1.52 MW | 1.29 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943712 | AF1-039 E O1 | Adder | 1.01 MW | 0.86 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944181 | AF1-086 C O1 | Adder | 3.54 MW | 3.01 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944182 | AF1-086 E O1 | Adder | 15.42 MW | 13.1 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944261 | AF1-094 C | Adder | 1.67 MW | 1.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944262 | AF1-094 E | Adder | 1.11 MW | 0.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944301 | AF1-098 C | Adder | 6.75 MW | 5.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944302 | AF1-098 E | Adder | 4.5 MW | 3.83 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944311 | AF1-099 C | Adder | 11.46 MW | 9.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944312 | AF1-099 E | Adder | 7.64 MW | 6.5 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944321 | AF1-100 C | Adder | 23.43 MW | 19.91 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944322 | AF1-100 E | Adder | 15.62 MW | 13.27 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944391 | AF1-104 O1 | Adder | 2.4 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944411 | AF1-106 O1 | Adder | 3.48 MW | 2.96 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944471 | AF1-112 C | Adder | 1.22 MW | 1.03 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944472 | AF1-112 E | Adder | 0.83 MW | 0.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944691 | AF1-134 C | Adder | 2.06 MW | 1.75 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944692 | AF1-134 E | Adder | 1.38 MW | 1.17 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944751 | AF1-140 C | 50/50 | 2.75 MW | 2.75 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944752 | AF1-140 E | 50/50 | 1.83 MW | 1.83 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944771 | AF1-142 C | Adder | 18.34 MW | 15.59 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944772 | AF1-142 E | Adder | 12.22 MW | 10.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944781 | AF1-143 C | 50/50 | 13.38 MW | 13.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944782 | AF1-143 E | 50/50 | 7.14 MW | 7.14 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944881 | AF1-153 C O1 | Adder | 1.95 MW | 1.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944882 | AF1-153 E O1 | Adder | 1.3 MW | 1.1 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944901 | AF1-155 C | Adder | 1.95 MW | 1.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944902 | AF1-155 E | Adder | 1.3 MW | 1.1 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945021 | AF1-167 C | Adder | 1.18 MW | 1.0 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945022 | AF1-167 E | Adder | 0.79 MW | 0.67 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945051 | AF1-170 C | Adder | 6.05 MW | 5.14 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945052 | AF1-170 E | Adder | 4.03 MW | 3.43 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945451 | AF1-210 C | Adder | 1.3 MW | 1.1 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945452 | AF1-210 E | Adder | 0.86 MW | 0.73 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945751 | AF1-240 C O1 | Adder | 1.92 MW | 1.63 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945752 | AF1-240 E O1 | Adder | 1.28 MW | 1.09 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958471 | AF2-141 | Adder | 1.78 MW | 1.52 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958731 | AF2-164 C O1 | Adder | 9.63 MW | 8.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958732 | AF2-164 E O1 | Adder | 6.42 MW | 5.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958741 | AF2-165 C | Adder | 1.86 MW | 1.58 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958742 | AF2-165 E | Adder | 1.24 MW | 1.06 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958751 | AF2-166 C | Adder | 1.85 MW | 1.58 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958752 | AF2-166 E | Adder | 1.24 MW | 1.05 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959441 | AF2-235 C | Adder | 0.9 MW | 0.76 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959442 | AF2-235 E | Adder | 0.6 MW | 0.51 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959471 | AF2-238 C | Adder | 2.14 MW | 1.82 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959472 | AF2-238 E | Adder | 1.43 MW | 1.21 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959521 | AF2-243 C | Adder | 1.4 MW | 1.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959522 | AF2-243 E | Adder | 0.93 MW | 0.79 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959802 | AF2-271 E | Adder | 0.66 MW | 0.56 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960022 | AF2-293 E | Adder | 0.16 MW | 0.14 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960031 | AF2-294 C | Adder | 1.63 MW | 1.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960032 | AF2-294 E | Adder | 1.09 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960041 | AF2-295 C | Adder | 1.95 MW | 1.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960042 | AF2-295 E | Adder | 1.3 MW | 1.1 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960051 | AF2-296 C | Adder | 2.06 MW | 1.75 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960052 | AF2-296 E | Adder | 1.38 MW | 1.17 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960451 | AF2-336 C | 50/50 | 3.4 MW | 3.4 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960452 | AF2-336 E | 50/50 | 2.27 MW | 2.27 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960461 | AF2-337 C | 50/50 | 3.4 MW | 3.4 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960462 | AF2-337 E | 50/50 | 2.27 MW | 2.27 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961141 | AF2-405 | Adder | 1.74 MW | 1.48 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961151 | AF2-406 | Adder | 13.05 MW | 11.1 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961211 | AF2-412 | Adder | 26.78 MW | 22.76 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961451 | AF2-436 | Adder | 0.19 MW | 0.16 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200503 | 26C.SLOPE | 50/50 | 2.44 MW | 2.44 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200794 | 26CONEMAGH | 50/50 | 0.48 MW | 0.48 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200809 | 26SITHE | 50/50 | 2.72 MW | 2.72 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200834 | 26SW_E13_K22 | 50/50 | 0.04 MW | 0.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200835 | 26ARN_Z1-066 | Adder | 1.78 MW | 1.52 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200837 | 26HOMER C1 | 50/50 | 46.77 MW | 46.77 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200838 | 26HOMER C2 | 50/50 | 38.38 MW | 38.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200839 | 26HOMER C3 | 50/50 | 40.64 MW | 40.64 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200846 | 26FORWARD | 50/50 | 0.16 MW | 0.16 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200852 | 26WARR RDG | Adder | 0.54 MW | 0.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200864 | K-013 E | 50/50 | 6.91 MW | 6.91 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200883 | Q-053 E | 50/50 | 8.38 MW | 8.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200888 | 26HIGHLAND | 50/50 | 0.41 MW | 0.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200889 | 26STNY CRK | 50/50 | 0.4 MW | 0.4 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200890 | 26BF_G21_K23 | 50/50 | 0.19 MW | 0.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200891 | 26CSLMN_L13 | 50/50 | 0.23 MW | 0.23 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200892 | 26LOOKOUT | 50/50 | 0.24 MW | 0.24 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200894 | 26K02 | Adder | 8.19 MW | 6.96 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200925 | 26R32 | 50/50 | 0.64 MW | 0.64 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 202225 | 26SCI_S29B | 50/50 | 0.08 MW | 0.08 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 203915 | 26BF_Z2-108 | Adder | 4.02 MW | 3.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 203932 | AA2-133 GEN | Adder | 2.54 MW | 2.15 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 203999 | P-047 E | Adder | 15.19 MW | 12.91 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 235003 | AC1-025 E | Adder | 0.2 MW | 0.17 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 236828 | 01GRAYMONT | Adder | 0.55 MW | 0.47 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 292350 | K-023 | 50/50 | 5.55 MW | 5.55 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 292542 | L-013 1 | 50/50 | 7.14 MW | 7.14 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 293301 | N-039 E | 50/50 | 19.64 MW | 19.64 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 293393 | V3-030E | Adder | 6.2 MW | 5.27 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 293432 | R-040 E | Adder | 0.4 MW | 0.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 293603 | O-018 E | 50/50 | 15.37 MW | 15.37 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 293902 | O-048 E | 50/50 | 6.42 MW | 6.42 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 294515 | O38_P22 | 50/50 | 17.18 MW | 17.18 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 294903 | P-060 E | 50/50 | 11.54 MW | 11.54 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 916202 | Z1-069 E | Adder | 12.22 MW | 10.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 931092 | AB1-160 E | Adder | 3.49 MW | 2.97 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 938951 | AE1-123 | Adder | 2.78 MW | 2.37 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 939291 | AE1-160 C | Adder | 1.9 MW | 1.61 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 939292 | AE1-160 E | Adder | 1.09 MW | 0.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940201 | AE2-001 C | Adder | 1.66 MW | 1.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940202 | AE2-001 E | Adder | 1.1 MW | 0.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940681 | AE2-055 C | Adder | 1.62 MW | 1.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940682 | AE2-055 E | Adder | 1.08 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940861 | AE2-074 C | Adder | 3.34 MW | 2.84 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940862 | AE2-074 E | Adder | 4.4 MW | 3.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941191 | AE2-113 C | Adder | 12.69 MW | 10.79 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941192 | AE2-113 E | Adder | 11.91 MW | 10.12 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941231 | AE2-117 C | Adder | 2.59 MW | 2.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941232 | AE2-117 E | Adder | 1.73 MW | 1.47 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941241 | AE2-118 C | 50/50 | 2.74 MW | 2.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941242 | AE2-118 E | 50/50 | 1.82 MW | 1.82 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941271 | AE2-121 C | Adder | 0.88 MW | 0.75 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941272 | AE2-121 E | Adder | 0.59 MW | 0.5 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941321 | AE2-126 C | Adder | 2.1 MW | 1.79 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941322 | AE2-126 E | Adder | 1.4 MW | 1.19 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941331 | AE2-129 C | Adder | 2.36 MW | 2.01 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941332 | AE2-129 E | Adder | 1.57 MW | 1.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941351 | AE2-131 C | Adder | 2.36 MW | 2.01 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941352 | AE2-131 E | Adder | 1.57 MW | 1.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941421 | AE2-139 C | Adder | 8.53 MW | 7.25 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941422 | AE2-139 E | Adder | 5.68 MW | 4.83 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946111 | AF1-276 C | Adder | 14.91 MW | 12.67 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946112 | AF1-276 E | Adder | 7.34 MW | 6.24 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946121 | AF1-277 C | Adder | 14.91 MW | 12.67 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946122 | AF1-277 E | Adder | 7.34 MW | 6.24 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946131 | AF1-278 C | Adder | 11.89 MW | 10.11 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946132 | AF1-278 E | Adder | 5.91 MW | 5.02 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946221 | AF1-287 C | Adder | 1.63 MW | 1.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946222 | AF1-287 E | Adder | 1.09 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946381 | AF1-302 C | Adder | 3.01 MW | 2.56 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946382 | AF1-302 E | Adder | 4.01 MW | 3.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946571 | AF1-321 C O1 | 50/50 | 3.61 MW | 3.61 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946572 | AF1-321 E O1 | 50/50 | 2.41 MW | 2.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946771 | AF1-217 C | Adder | 1.63 MW | 1.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946772 | AF1-217 E | Adder | 1.09 MW | 0.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957001 | AF2-001 C O1 | 50/50 | 3.61 MW | 3.61 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957002 | AF2-001 E O1 | 50/50 | 2.41 MW | 2.41 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957011 | AF2-002 C O1 | 50/50 | 1.8 MW | 1.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957012 | AF2-002 E O1 | 50/50 | 1.2 MW | 1.2 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957161 | AF2-010 C | Adder | 6.41 MW | 5.45 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957162 | AF2-010 E | Adder | 4.32 MW | 3.67 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957451 | AF2-039 C | Adder | 1.39 MW | 1.18 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957452 | AF2-039 E | Adder | 0.92 MW | 0.79 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957561 | AF2-050 C | 50/50 | 9.71 MW | 9.71 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957562 | AF2-050 E | 50/50 | 6.48 MW | 6.48 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957931 | AF2-087 C | 50/50 | 0.77 MW | 0.77 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957932 | AF2-087 E | 50/50 | 1.06 MW | 1.06 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957941 | AF2-088 C | Adder | 0.67 MW | 0.57 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957942 | AF2-088 E | Adder | 0.45 MW | 0.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957981 | AF2-092 C | 50/50 | 2.04 MW | 2.04 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957982 | AF2-092 E | 50/50 | 1.36 MW | 1.36 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958271 | AF2-121 C | Adder | 2.36 MW | 2.01 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958272 | AF2-121 E | Adder | 1.57 MW | 1.34 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958361 | AF2-130 C | Adder | 1.85 MW | 1.58 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958362 | AF2-130 E | Adder | 1.24 MW | 1.05 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200833 | 26SEWRDB34 | 50/50 | 33.86 MW | 33.86 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200886 | 26ARWF_N39 | 50/50 | 0.56 MW | 0.56 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200915 | 26CHSTN_FL | 50/50 | 0.29 MW | 0.29 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 203034 | 26NA_O38_P22 | 50/50 | 0.49 MW | 0.49 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959301 | AF2-221 C | 50/50 | 1.9 MW | 1.9 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959302 | AF2-221 E | 50/50 | 2.63 MW | 2.63 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 292340 | 26SW_E13_K22 | 50/50 | 1.92 MW | 1.92 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964451 | AG1-308 C O1 | Adder | 1.63 MW | 1.39 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964452 | AG1-308 E O1 | Adder | 2.28 MW | 1.94 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960901 | AG1-000C C | 50/50 | 11.81 MW | 11.81 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960902 | AG1-000C E | 50/50 | 5.82 MW | 5.82 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946421 | AF2-000A C | Adder | 8.16 MW | 6.93 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946422 | AF2-000A E | Adder | 24.47 MW | 20.8 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 966783 | AG1-549 BAT | 50/50 | 7.74 MW | 7.74 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.59 MW | 0.59 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.7 MW | 0.7 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.06 MW | 1.06 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.38 MW | 0.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.3 MW | 0.3 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 7.66 MW | 7.66 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.46 MW | 1.46 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.33 MW | 0.33 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.32 MW | 0.32 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.52 MW | 0.52 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.38 MW | 1.38 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.59 MW | 1.59 MW |
| 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.34 MW | 0.34 MW |
| Details for 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 962411 | AG1-090 C O1 | 50/50 | 27.01 MW | 27.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 962412 | AG1-090 E O1 | 50/50 | 6.75 MW | 6.75 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 965121 | AG1-377 C O1 | 50/50 | 4.05 MW | 4.05 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 965122 | AG1-377 E O1 | 50/50 | 2.7 MW | 2.7 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 965131 | AG1-378 C O1 | 50/50 | 4.05 MW | 4.05 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 965132 | AG1-378 E O1 | 50/50 | 2.7 MW | 2.7 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 290086 | Q-036 E | 50/50 | 14.08 MW | 14.08 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 936991 | AD2-133 C | 50/50 | 5.3 MW | 5.3 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 936992 | AD2-133 E | 50/50 | 24.28 MW | 24.28 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 944181 | AF1-086 C O1 | 50/50 | 2.49 MW | 2.49 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 944182 | AF1-086 E O1 | 50/50 | 10.85 MW | 10.85 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 944691 | AF1-134 C | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 944692 | AF1-134 E | 50/50 | 1.7 MW | 1.7 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 945181 | AF1-183 | 50/50 | 0.02 MW | 0.02 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 960051 | AF2-296 C | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 960052 | AF2-296 E | 50/50 | 1.7 MW | 1.7 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 200715 | 26SHAWVL 1 | 50/50 | 2.6 MW | 2.6 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 200722 | 26SHAWVL 2 | 50/50 | 13.68 MW | 13.68 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 200913 | 26SHAW-D | 50/50 | 0.34 MW | 0.34 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 941321 | AE2-126 C | 50/50 | 2.17 MW | 2.17 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 941322 | AE2-126 E | 50/50 | 1.45 MW | 1.45 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 941331 | AE2-129 C | 50/50 | 4.05 MW | 4.05 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 941332 | AE2-129 E | 50/50 | 2.7 MW | 2.7 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 941351 | AE2-131 C | 50/50 | 4.05 MW | 4.05 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 941352 | AE2-131 E | 50/50 | 2.7 MW | 2.7 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 957451 | AF2-039 C | 50/50 | 2.7 MW | 2.7 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 957452 | AF2-039 E | 50/50 | 1.8 MW | 1.8 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 957941 | AF2-088 C | 50/50 | 1.3 MW | 1.3 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 957942 | AF2-088 E | 50/50 | 0.87 MW | 0.87 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 958271 | AF2-121 C | 50/50 | 4.05 MW | 4.05 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 958272 | AF2-121 E | 50/50 | 2.7 MW | 2.7 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 964451 | AG1-308 C O1 | 50/50 | 2.8 MW | 2.8 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 964452 | AG1-308 E O1 | 50/50 | 3.92 MW | 3.92 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | 200905 | 26Q36 | 50/50 | 0.48 MW | 0.48 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.21 MW | 0.21 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.73 MW | 0.73 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.38 MW | 0.38 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.27 MW | 0.27 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.07 MW | 0.07 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.03 MW | 0.03 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.79 MW | 1.79 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.05 MW | 0.05 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-115-73-11 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961971 | AG1-040 C | Adder | 1.81 MW | 1.54 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961972 | AG1-040 E | Adder | 1.21 MW | 1.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961981 | AG1-041 C | Adder | 2.31 MW | 1.97 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961982 | AG1-041 E | Adder | 1.54 MW | 1.31 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962411 | AG1-090 C O1 | Adder | 18.42 MW | 15.65 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962412 | AG1-090 E O1 | Adder | 4.6 MW | 3.91 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962511 | AG1-100 C | Adder | 1.72 MW | 1.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962512 | AG1-100 E | Adder | 1.15 MW | 0.98 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962911 | AG1-140 C | Adder | 0.26 MW | 0.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 962912 | AG1-140 E | Adder | 0.13 MW | 0.11 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963441 | AG1-193 C | Adder | 2.14 MW | 1.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963442 | AG1-193 E | Adder | 1.43 MW | 1.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963481 | AG1-197 C | Adder | 1.38 MW | 1.17 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963482 | AG1-197 E | Adder | 0.92 MW | 0.78 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963491 | AG1-198 C | Adder | 1.1 MW | 0.93 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963492 | AG1-198 E | Adder | 0.73 MW | 0.62 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963991 | AG1-253 C | Adder | 0.39 MW | 0.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 963992 | AG1-253 E | Adder | 0.19 MW | 0.16 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964031 | AG1-257 C | Adder | 1.25 MW | 1.06 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964032 | AG1-257 E | Adder | 1.75 MW | 1.49 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964201 | AG1-281 C | Adder | 3.65 MW | 3.1 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964202 | AG1-281 E | Adder | 2.43 MW | 2.07 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964391 | AG1-301 C | Adder | 2.8 MW | 2.38 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964392 | AG1-301 E | Adder | 1.86 MW | 1.58 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964411 | AG1-303 C O1 | Adder | 4.28 MW | 3.64 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964412 | AG1-303 E O1 | Adder | 2.86 MW | 2.43 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 966771 | AG1-548 C | Adder | 17.35 MW | 14.75 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 966772 | AG1-548 E | Adder | 5.28 MW | 4.49 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965121 | AG1-377 C O1 | Adder | 2.76 MW | 2.35 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965122 | AG1-377 E O1 | Adder | 1.84 MW | 1.56 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965131 | AG1-378 C O1 | Adder | 2.76 MW | 2.35 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965132 | AG1-378 E O1 | Adder | 1.84 MW | 1.56 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965171 | AG1-382 C | Adder | 3.86 MW | 3.29 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965172 | AG1-382 E | Adder | 2.58 MW | 2.19 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965241 | AG1-392C C O | Adder | 2.62 MW | 2.23 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965242 | AG1-392C E O | Adder | 1.75 MW | 1.49 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965251 | AG1-392B C O | Adder | 2.62 MW | 2.23 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965252 | AG1-392B E O | Adder | 1.75 MW | 1.49 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965261 | AG1-392A C O | Adder | 5.25 MW | 4.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965262 | AG1-392A E O | Adder | 3.5 MW | 2.98 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965271 | AG1-392 C O1 | Adder | 5.25 MW | 4.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965272 | AG1-392 E O1 | Adder | 3.5 MW | 2.98 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 965861 | AG1-455 | Adder | 4.81 MW | 4.09 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 966041 | AG1-473 C | Adder | 4.23 MW | 3.6 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 966042 | AG1-473 E | Adder | 2.82 MW | 2.4 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 290086 | Q-036 E | Adder | 10.48 MW | 8.91 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 296332 | R-032 E | 50/50 | 20.09 MW | 20.09 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 913142 | Y1-033 E OP1 | Adder | 6.51 MW | 5.54 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 936991 | AD2-133 C | Adder | 3.95 MW | 3.35 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 936992 | AD2-133 E | Adder | 18.07 MW | 15.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942121 | AE2-224 C | 50/50 | 20.04 MW | 20.04 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942122 | AE2-224 E | 50/50 | 13.36 MW | 13.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942351 | AE2-248 C | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942352 | AE2-248 E | Adder | 0.96 MW | 0.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942361 | AE2-249 C | Adder | 3.2 MW | 2.72 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942362 | AE2-249 E | Adder | 2.14 MW | 1.81 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942491 | AE2-262 C | Adder | 8.14 MW | 6.92 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942492 | AE2-262 E | Adder | 5.47 MW | 4.65 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942501 | AE2-263 C | Adder | 7.65 MW | 6.5 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942502 | AE2-263 E | Adder | 5.11 MW | 4.34 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942811 | AE2-299 C | Adder | 4.62 MW | 3.92 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942812 | AE2-299 E | Adder | 18.47 MW | 15.7 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942961 | AE2-316 C | Adder | 7.55 MW | 6.42 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 942962 | AE2-316 E | Adder | 8.94 MW | 7.6 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943151 | AE2-344 C | Adder | 10.0 MW | 8.5 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943152 | AE2-344 E | Adder | 6.67 MW | 5.67 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943351 | AF1-006 C | Adder | 1.72 MW | 1.47 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943352 | AF1-006 E | Adder | 0.97 MW | 0.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943711 | AF1-039 C O1 | Adder | 1.72 MW | 1.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 943712 | AF1-039 E O1 | Adder | 1.15 MW | 0.98 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944181 | AF1-086 C O1 | Adder | 5.82 MW | 4.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944182 | AF1-086 E O1 | Adder | 25.3 MW | 21.51 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944261 | AF1-094 C | Adder | 1.83 MW | 1.55 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944262 | AF1-094 E | Adder | 1.22 MW | 1.04 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944301 | AF1-098 C | Adder | 7.1 MW | 6.04 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944302 | AF1-098 E | Adder | 4.74 MW | 4.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944311 | AF1-099 C | Adder | 12.68 MW | 10.78 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944312 | AF1-099 E | Adder | 8.45 MW | 7.18 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944321 | AF1-100 C | Adder | 26.23 MW | 22.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944322 | AF1-100 E | Adder | 17.49 MW | 14.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944411 | AF1-106 O1 | Adder | 3.48 MW | 2.96 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944471 | AF1-112 C | Adder | 1.34 MW | 1.14 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944472 | AF1-112 E | Adder | 0.92 MW | 0.78 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944691 | AF1-134 C | Adder | 2.99 MW | 2.54 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944692 | AF1-134 E | Adder | 1.99 MW | 1.7 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944751 | AF1-140 C | Adder | 3.14 MW | 2.67 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944752 | AF1-140 E | Adder | 2.09 MW | 1.78 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944771 | AF1-142 C | Adder | 20.29 MW | 17.24 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944772 | AF1-142 E | Adder | 13.52 MW | 11.5 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944781 | AF1-143 C | Adder | 15.12 MW | 12.85 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944782 | AF1-143 E | Adder | 8.07 MW | 6.86 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944881 | AF1-153 C O1 | Adder | 2.16 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944882 | AF1-153 E O1 | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944901 | AF1-155 C | Adder | 2.16 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 944902 | AF1-155 E | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945021 | AF1-167 C | Adder | 1.39 MW | 1.18 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945022 | AF1-167 E | Adder | 0.93 MW | 0.79 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945051 | AF1-170 C | Adder | 6.39 MW | 5.43 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945052 | AF1-170 E | Adder | 4.26 MW | 3.62 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945451 | AF1-210 C | Adder | 1.53 MW | 1.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945452 | AF1-210 E | Adder | 1.02 MW | 0.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945751 | AF1-240 C O1 | Adder | 2.97 MW | 2.53 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 945752 | AF1-240 E O1 | Adder | 1.98 MW | 1.69 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958471 | AF2-141 | Adder | 2.02 MW | 1.71 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958731 | AF2-164 C O1 | Adder | 9.88 MW | 8.4 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958732 | AF2-164 E O1 | Adder | 6.59 MW | 5.6 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958741 | AF2-165 C | Adder | 2.2 MW | 1.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958742 | AF2-165 E | Adder | 1.47 MW | 1.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958751 | AF2-166 C | Adder | 2.29 MW | 1.95 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958752 | AF2-166 E | Adder | 1.53 MW | 1.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959441 | AF2-235 C | Adder | 1.04 MW | 0.88 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959442 | AF2-235 E | Adder | 0.69 MW | 0.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959471 | AF2-238 C | Adder | 2.15 MW | 1.83 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959472 | AF2-238 E | Adder | 1.43 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959521 | AF2-243 C | Adder | 1.65 MW | 1.4 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959522 | AF2-243 E | Adder | 1.1 MW | 0.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959802 | AF2-271 E | Adder | 0.73 MW | 0.62 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960022 | AF2-293 E | Adder | 0.18 MW | 0.15 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960031 | AF2-294 C | Adder | 1.63 MW | 1.38 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960032 | AF2-294 E | Adder | 1.08 MW | 0.92 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960041 | AF2-295 C | Adder | 2.16 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960042 | AF2-295 E | Adder | 1.44 MW | 1.22 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960051 | AF2-296 C | Adder | 2.99 MW | 2.54 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960052 | AF2-296 E | Adder | 1.99 MW | 1.7 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960451 | AF2-336 C | Adder | 3.86 MW | 3.28 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960452 | AF2-336 E | Adder | 2.57 MW | 2.19 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960461 | AF2-337 C | Adder | 3.86 MW | 3.28 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960462 | AF2-337 E | Adder | 2.57 MW | 2.19 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961141 | AF2-405 | Adder | 1.74 MW | 1.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961151 | AF2-406 | Adder | 13.06 MW | 11.1 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961211 | AF2-412 | Adder | 26.7 MW | 22.69 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 961451 | AF2-436 | Adder | 0.19 MW | 0.16 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200636 | 26IUP CO-G | 50/50 | 0.81 MW | 0.81 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200794 | 26CONEMAGH | 50/50 | 0.63 MW | 0.63 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200809 | 26SITHE | 50/50 | 2.62 MW | 2.62 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200835 | 26ARN_Z1-066 | Adder | 2.02 MW | 1.71 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200837 | 26HOMER C1 | 50/50 | 45.05 MW | 45.05 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200838 | 26HOMER C2 | 50/50 | 37.43 MW | 37.43 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200839 | 26HOMER C3 | 50/50 | 39.62 MW | 39.62 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200846 | 26FORWARD | 50/50 | 0.18 MW | 0.18 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200852 | 26WARR RDG | Adder | 0.58 MW | 0.49 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200864 | K-013 E | 50/50 | 7.78 MW | 7.78 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200883 | Q-053 E | Adder | 9.61 MW | 8.17 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200888 | 26HIGHLAND | 50/50 | 0.46 MW | 0.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200894 | 26K02 | Adder | 8.53 MW | 7.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200925 | 26R32 | 50/50 | 0.73 MW | 0.73 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 202158 | 26CON.GEN1 | 50/50 | 0.14 MW | 0.14 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 203915 | 26BF_Z2-108 | Adder | 4.54 MW | 3.86 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 203932 | AA2-133 GEN | Adder | 2.54 MW | 2.16 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 203999 | P-047 E | Adder | 15.18 MW | 12.9 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 235003 | AC1-025 E | Adder | 0.22 MW | 0.19 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 236828 | 01GRAYMONT | Adder | 0.61 MW | 0.52 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 292350 | K-023 | Adder | 6.28 MW | 5.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 292542 | L-013 1 | Adder | 8.07 MW | 6.86 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 293301 | N-039 E | Adder | 20.33 MW | 17.28 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 293393 | V3-030E | Adder | 8.7 MW | 7.39 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 293432 | R-040 E | Adder | 0.45 MW | 0.39 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 293603 | O-018 E | 50/50 | 17.41 MW | 17.41 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 293902 | O-048 E | Adder | 7.26 MW | 6.17 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 294515 | O38_P22 | Adder | 17.79 MW | 15.12 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 294903 | P-060 E | Adder | 13.04 MW | 11.08 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 916202 | Z1-069 E | Adder | 12.31 MW | 10.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 931092 | AB1-160 E | Adder | 3.52 MW | 2.99 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 938951 | AE1-123 | Adder | 3.57 MW | 3.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 939291 | AE1-160 C | Adder | 2.2 MW | 1.87 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 939292 | AE1-160 E | Adder | 1.26 MW | 1.07 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940201 | AE2-001 C | Adder | 1.82 MW | 1.55 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940202 | AE2-001 E | Adder | 1.21 MW | 1.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940681 | AE2-055 C | Adder | 1.78 MW | 1.52 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940682 | AE2-055 E | Adder | 1.19 MW | 1.01 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940861 | AE2-074 C | Adder | 3.39 MW | 2.88 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 940862 | AE2-074 E | Adder | 4.46 MW | 3.79 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941191 | AE2-113 C | Adder | 13.27 MW | 11.28 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941192 | AE2-113 E | Adder | 12.46 MW | 10.59 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941231 | AE2-117 C | Adder | 2.83 MW | 2.4 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941232 | AE2-117 E | Adder | 1.88 MW | 1.6 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941241 | AE2-118 C | Adder | 2.97 MW | 2.53 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941242 | AE2-118 E | Adder | 1.98 MW | 1.68 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941271 | AE2-121 C | Adder | 0.97 MW | 0.83 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941272 | AE2-121 E | Adder | 0.65 MW | 0.55 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941321 | AE2-126 C | Adder | 2.39 MW | 2.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941322 | AE2-126 E | Adder | 1.6 MW | 1.36 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941331 | AE2-129 C | Adder | 2.76 MW | 2.35 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941332 | AE2-129 E | Adder | 1.84 MW | 1.56 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941351 | AE2-131 C | Adder | 2.76 MW | 2.35 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941352 | AE2-131 E | Adder | 1.84 MW | 1.56 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941421 | AE2-139 C | Adder | 8.62 MW | 7.32 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 941422 | AE2-139 E | Adder | 5.74 MW | 4.88 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946071 | AF1-272 C O1 | 50/50 | 25.42 MW | 25.42 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946072 | AF1-272 E O1 | 50/50 | 16.95 MW | 16.95 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946111 | AF1-276 C | Adder | 15.18 MW | 12.9 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946112 | AF1-276 E | Adder | 7.48 MW | 6.35 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946121 | AF1-277 C | Adder | 15.18 MW | 12.9 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946122 | AF1-277 E | Adder | 7.48 MW | 6.35 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946131 | AF1-278 C | Adder | 12.1 MW | 10.29 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946132 | AF1-278 E | Adder | 6.02 MW | 5.11 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946221 | AF1-287 C | Adder | 1.72 MW | 1.47 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946222 | AF1-287 E | Adder | 1.15 MW | 0.98 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946381 | AF1-302 C | Adder | 3.3 MW | 2.8 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946382 | AF1-302 E | Adder | 4.4 MW | 3.74 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946571 | AF1-321 C O1 | 50/50 | 4.05 MW | 4.05 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946572 | AF1-321 E O1 | 50/50 | 2.7 MW | 2.7 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946771 | AF1-217 C | Adder | 1.72 MW | 1.47 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946772 | AF1-217 E | Adder | 1.15 MW | 0.98 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957001 | AF2-001 C O1 | 50/50 | 4.05 MW | 4.05 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957002 | AF2-001 E O1 | 50/50 | 2.7 MW | 2.7 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957011 | AF2-002 C O1 | 50/50 | 2.03 MW | 2.03 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957012 | AF2-002 E O1 | 50/50 | 1.35 MW | 1.35 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957161 | AF2-010 C | Adder | 7.05 MW | 5.99 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957162 | AF2-010 E | Adder | 4.75 MW | 4.04 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957451 | AF2-039 C | Adder | 1.66 MW | 1.41 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957452 | AF2-039 E | Adder | 1.1 MW | 0.94 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957561 | AF2-050 C | 50/50 | 10.02 MW | 10.02 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957562 | AF2-050 E | 50/50 | 6.68 MW | 6.68 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957931 | AF2-087 C | Adder | 0.86 MW | 0.73 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957932 | AF2-087 E | Adder | 1.18 MW | 1.0 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957941 | AF2-088 C | Adder | 0.8 MW | 0.68 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957942 | AF2-088 E | Adder | 0.53 MW | 0.45 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957981 | AF2-092 C | Adder | 2.31 MW | 1.97 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 957982 | AF2-092 E | Adder | 1.54 MW | 1.31 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958271 | AF2-121 C | Adder | 2.76 MW | 2.35 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958272 | AF2-121 E | Adder | 1.84 MW | 1.56 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958361 | AF2-130 C | Adder | 2.29 MW | 1.95 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 958362 | AF2-130 E | Adder | 1.53 MW | 1.3 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 200833 | 26SEWRDB34 | 50/50 | 34.63 MW | 34.63 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959301 | AF2-221 C | 50/50 | 2.14 MW | 2.14 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 959302 | AF2-221 E | 50/50 | 2.96 MW | 2.96 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 292340 | 26SW_E13_K22 | Adder | 2.17 MW | 1.84 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964451 | AG1-308 C O1 | Adder | 1.91 MW | 1.62 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 964452 | AG1-308 E O1 | Adder | 2.67 MW | 2.27 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960901 | AG1-000C C | Adder | 13.32 MW | 11.32 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 960902 | AG1-000C E | Adder | 6.56 MW | 5.58 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946421 | AF2-000A C | Adder | 8.95 MW | 7.61 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 946422 | AF2-000A E | Adder | 26.85 MW | 22.82 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | 966783 | AG1-549 BAT | 50/50 | 9.14 MW | 9.14 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.46 MW | 0.46 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.83 MW | 0.83 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.32 MW | 0.32 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.27 MW | 0.27 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 7.43 MW | 7.43 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.33 MW | 0.33 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.21 MW | 1.21 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.62 MW | 0.62 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.25 MW | 0.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.48 MW | 0.48 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.25 MW | 3.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.25 MW | 1.25 MW |
| 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN-P2_3-PN-230-0347-2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.27 MW | 0.27 MW |
| Details for 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 962411 | AG1-090 C O1 | Adder | 5.74 MW | 4.88 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 962412 | AG1-090 E O1 | Adder | 1.44 MW | 1.22 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964031 | AG1-257 C | 50/50 | 1.01 MW | 1.01 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964032 | AG1-257 E | 50/50 | 1.42 MW | 1.42 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964201 | AG1-281 C | Adder | 0.68 MW | 0.58 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964202 | AG1-281 E | Adder | 0.46 MW | 0.39 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964391 | AG1-301 C | 50/50 | 1.27 MW | 1.27 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964392 | AG1-301 E | 50/50 | 0.84 MW | 0.84 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 965121 | AG1-377 C O1 | Adder | 0.86 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 965122 | AG1-377 E O1 | Adder | 0.57 MW | 0.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 965131 | AG1-378 C O1 | Adder | 0.86 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 965132 | AG1-378 E O1 | Adder | 0.57 MW | 0.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 966041 | AG1-473 C | 50/50 | 5.01 MW | 5.01 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 966042 | AG1-473 E | 50/50 | 3.34 MW | 3.34 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 290086 | Q-036 E | Adder | 2.87 MW | 2.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 934371 | AD1-061 C | Adder | -0.47 MW | -0.4 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 936061 | AD2-009 C | Adder | -3.21 MW | -2.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 936991 | AD2-133 C | Adder | 1.08 MW | 0.92 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 936992 | AD2-133 E | Adder | 4.94 MW | 4.2 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942121 | AE2-224 C | Adder | 3.51 MW | 2.98 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942122 | AE2-224 E | Adder | 2.34 MW | 1.99 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942351 | AE2-248 C | 50/50 | 1.18 MW | 1.18 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942352 | AE2-248 E | 50/50 | 0.79 MW | 0.79 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942491 | AE2-262 C | Adder | 4.99 MW | 4.24 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942492 | AE2-262 E | Adder | 3.35 MW | 2.85 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942501 | AE2-263 C | Adder | 4.69 MW | 3.98 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942502 | AE2-263 E | Adder | 3.13 MW | 2.66 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942961 | AE2-316 C | Adder | 2.07 MW | 1.76 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 942962 | AE2-316 E | Adder | 2.45 MW | 2.08 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944311 | AF1-099 C | Adder | 6.97 MW | 5.93 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944312 | AF1-099 E | Adder | 4.65 MW | 3.95 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944321 | AF1-100 C | Adder | 12.84 MW | 10.92 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944322 | AF1-100 E | Adder | 8.56 MW | 7.28 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944471 | AF1-112 C | 50/50 | 1.09 MW | 1.09 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944472 | AF1-112 E | 50/50 | 0.75 MW | 0.75 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944691 | AF1-134 C | Adder | 0.7 MW | 0.6 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944692 | AF1-134 E | Adder | 0.47 MW | 0.4 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944771 | AF1-142 C | Adder | 11.16 MW | 9.48 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944772 | AF1-142 E | Adder | 7.44 MW | 6.32 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944881 | AF1-153 C O1 | Adder | 0.78 MW | 0.66 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944882 | AF1-153 E O1 | Adder | 0.52 MW | 0.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944901 | AF1-155 C | Adder | 0.78 MW | 0.66 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 944902 | AF1-155 E | Adder | 0.52 MW | 0.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 945591 | AF1-224 C | Adder | -0.5 MW | -0.43 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958871 | AF2-178 | Adder | -0.91 MW | -0.78 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958881 | AF2-179 | Adder | -0.39 MW | -0.34 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958891 | AF2-180 | Adder | -0.39 MW | -0.34 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958931 | AF2-184 | Adder | -0.36 MW | -0.3 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 959802 | AF2-271 E | Adder | 0.28 MW | 0.24 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 960022 | AF2-293 E | 50/50 | 0.14 MW | 0.14 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 960041 | AF2-295 C | Adder | 0.78 MW | 0.66 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 960042 | AF2-295 E | Adder | 0.52 MW | 0.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 960051 | AF2-296 C | Adder | 0.7 MW | 0.6 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 960052 | AF2-296 E | Adder | 0.47 MW | 0.4 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 200852 | 26WARR RDG | 50/50 | 0.26 MW | 0.26 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 200883 | Q-053 E | Adder | 1.67 MW | 1.42 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 235003 | AC1-025 E | 50/50 | 0.19 MW | 0.19 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 236828 | 01GRAYMONT | 50/50 | 0.48 MW | 0.48 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 293301 | N-039 E | Adder | 4.3 MW | 3.65 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 294515 | O38_P22 | Adder | 3.76 MW | 3.2 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 939591 | AE1-188 C | Adder | -0.8 MW | -0.68 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 940201 | AE2-001 C | 50/50 | 1.44 MW | 1.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 940202 | AE2-001 E | 50/50 | 0.96 MW | 0.96 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 940671 | AE2-054 C | Adder | -0.73 MW | -0.62 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 940681 | AE2-055 C | 50/50 | 1.51 MW | 1.51 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 940682 | AE2-055 E | 50/50 | 1.0 MW | 1.0 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941191 | AE2-113 C | Adder | 3.11 MW | 2.64 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941192 | AE2-113 E | Adder | 2.92 MW | 2.48 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941231 | AE2-117 C | 50/50 | 1.23 MW | 1.23 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941232 | AE2-117 E | 50/50 | 0.82 MW | 0.82 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941241 | AE2-118 C | Adder | 1.17 MW | 0.99 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941242 | AE2-118 E | Adder | 0.78 MW | 0.66 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941271 | AE2-121 C | 50/50 | 0.76 MW | 0.76 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941272 | AE2-121 E | 50/50 | 0.51 MW | 0.51 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941321 | AE2-126 C | Adder | 0.82 MW | 0.7 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941322 | AE2-126 E | Adder | 0.55 MW | 0.47 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941331 | AE2-129 C | Adder | 0.86 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941332 | AE2-129 E | Adder | 0.57 MW | 0.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941351 | AE2-131 C | Adder | 0.86 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 941352 | AE2-131 E | Adder | 0.57 MW | 0.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 946381 | AF1-302 C | Adder | 0.9 MW | 0.77 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 946382 | AF1-302 E | Adder | 1.21 MW | 1.02 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957451 | AF2-039 C | Adder | 0.61 MW | 0.52 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957452 | AF2-039 E | Adder | 0.41 MW | 0.35 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957561 | AF2-050 C | Adder | 1.75 MW | 1.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957562 | AF2-050 E | Adder | 1.17 MW | 0.99 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957931 | AF2-087 C | Adder | 0.23 MW | 0.19 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957932 | AF2-087 E | Adder | 0.31 MW | 0.26 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957941 | AF2-088 C | Adder | 0.29 MW | 0.25 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 957942 | AF2-088 E | Adder | 0.2 MW | 0.17 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958271 | AF2-121 C | Adder | 0.86 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 958272 | AF2-121 E | Adder | 0.57 MW | 0.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 200812 | 26ALY HYDR | 50/50 | 0.44 MW | 0.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 938751 | AE1-101 C | Adder | -7.11 MW | -6.05 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964451 | AG1-308 C O1 | Adder | 0.6 MW | 0.51 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 964452 | AG1-308 E O1 | Adder | 0.83 MW | 0.71 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 946421 | AF2-000A C | Adder | 3.38 MW | 2.88 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 946422 | AF2-000A E | Adder | 10.15 MW | 8.62 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 959843 | AF2-275 BAT | Adder | 0.12 MW | 0.1 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 959853 | AF2-276 BAT | Adder | 0.12 MW | 0.1 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | 966463 | AG1-515 BAT | Adder | 0.9 MW | 0.77 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.15 MW | 0.15 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.93 MW | 0.93 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.57 MW | 2.57 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.73 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.09 MW | 0.09 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.08 MW | 0.08 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.08 MW | 0.08 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.2 MW | 0.2 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.85 MW | 1.85 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.05 MW | 0.05 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P45:102437 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 961971 | AG1-040 C | Adder | 1.04 MW | 0.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 961972 | AG1-040 E | Adder | 0.69 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 961981 | AG1-041 C | Adder | 1.24 MW | 1.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 961982 | AG1-041 E | Adder | 0.82 MW | 0.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 962411 | AG1-090 C O1 | Adder | 10.06 MW | 8.55 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 962412 | AG1-090 E O1 | Adder | 2.52 MW | 2.14 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 962511 | AG1-100 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 962512 | AG1-100 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 962911 | AG1-140 C | Adder | 0.15 MW | 0.13 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 962912 | AG1-140 E | Adder | 0.08 MW | 0.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 963441 | AG1-193 C | Adder | 1.22 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 963442 | AG1-193 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 963481 | AG1-197 C | Adder | 0.79 MW | 0.67 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 963482 | AG1-197 E | Adder | 0.52 MW | 0.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 963491 | AG1-198 C | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 963492 | AG1-198 E | Adder | 0.42 MW | 0.35 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 963991 | AG1-253 C | Adder | 0.22 MW | 0.19 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 963992 | AG1-253 E | Adder | 0.11 MW | 0.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 964031 | AG1-257 C | Adder | 0.7 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 964032 | AG1-257 E | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 964201 | AG1-281 C | Adder | 1.92 MW | 1.64 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 964202 | AG1-281 E | Adder | 1.28 MW | 1.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 964391 | AG1-301 C | Adder | 1.47 MW | 1.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 964392 | AG1-301 E | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 964411 | AG1-303 C O1 | Adder | 2.45 MW | 2.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 964412 | AG1-303 E O1 | Adder | 1.64 MW | 1.39 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 966771 | AG1-548 C | Adder | 9.9 MW | 8.41 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 966772 | AG1-548 E | Adder | 3.01 MW | 2.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 966781 | AG1-549 C O1 | 50/50 | 37.22 MW | 37.22 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 966782 | AG1-549 E O1 | 50/50 | 6.57 MW | 6.57 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965121 | AG1-377 C O1 | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965122 | AG1-377 E O1 | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965131 | AG1-378 C O1 | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965132 | AG1-378 E O1 | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965171 | AG1-382 C | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965172 | AG1-382 E | Adder | 1.36 MW | 1.16 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965241 | AG1-392C C O | Adder | 1.53 MW | 1.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965242 | AG1-392C E O | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965251 | AG1-392B C O | Adder | 1.53 MW | 1.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965252 | AG1-392B E O | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965261 | AG1-392A C O | Adder | 3.06 MW | 2.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965262 | AG1-392A E O | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965271 | AG1-392 C O1 | Adder | 3.06 MW | 2.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965272 | AG1-392 E O1 | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 965861 | AG1-455 | Adder | 2.74 MW | 2.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 290086 | Q-036 E | Adder | 5.65 MW | 4.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 296332 | R-032 E | 50/50 | 10.62 MW | 10.62 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 913142 | Y1-033 E OP1 | Adder | 3.51 MW | 2.98 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 936991 | AD2-133 C | Adder | 2.13 MW | 1.81 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 936992 | AD2-133 E | Adder | 9.74 MW | 8.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942121 | AE2-224 C | Adder | 10.18 MW | 8.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942122 | AE2-224 E | Adder | 6.79 MW | 5.77 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942351 | AE2-248 C | Adder | 0.8 MW | 0.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942361 | AE2-249 C | Adder | 1.72 MW | 1.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942362 | AE2-249 E | Adder | 1.15 MW | 0.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942491 | AE2-262 C | Adder | 4.58 MW | 3.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942492 | AE2-262 E | Adder | 3.07 MW | 2.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942501 | AE2-263 C | Adder | 4.3 MW | 3.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942502 | AE2-263 E | Adder | 2.87 MW | 2.44 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942811 | AE2-299 C | Adder | 2.64 MW | 2.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942812 | AE2-299 E | Adder | 10.56 MW | 8.98 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942961 | AE2-316 C | Adder | 4.3 MW | 3.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 942962 | AE2-316 E | Adder | 5.1 MW | 4.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 943151 | AE2-344 C | Adder | 5.71 MW | 4.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 943152 | AE2-344 E | Adder | 3.81 MW | 3.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 943351 | AF1-006 C | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 943352 | AF1-006 E | Adder | 0.55 MW | 0.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 943711 | AF1-039 C O1 | Adder | 0.93 MW | 0.79 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 943712 | AF1-039 E O1 | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944181 | AF1-086 C O1 | Adder | 3.25 MW | 2.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944182 | AF1-086 E O1 | Adder | 14.13 MW | 12.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944261 | AF1-094 C | Adder | 1.04 MW | 0.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944262 | AF1-094 E | Adder | 0.7 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944301 | AF1-098 C | Adder | 4.06 MW | 3.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944302 | AF1-098 E | Adder | 2.71 MW | 2.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944311 | AF1-099 C | Adder | 7.14 MW | 6.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944312 | AF1-099 E | Adder | 4.76 MW | 4.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944321 | AF1-100 C | Adder | 14.77 MW | 12.55 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944322 | AF1-100 E | Adder | 9.85 MW | 8.37 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944411 | AF1-106 O1 | Adder | 2.05 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944472 | AF1-112 E | Adder | 0.51 MW | 0.43 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944691 | AF1-134 C | Adder | 1.67 MW | 1.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944692 | AF1-134 E | Adder | 1.11 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944751 | AF1-140 C | Adder | 1.66 MW | 1.41 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944752 | AF1-140 E | Adder | 1.11 MW | 0.94 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944771 | AF1-142 C | Adder | 11.43 MW | 9.72 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944772 | AF1-142 E | Adder | 7.62 MW | 6.48 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944781 | AF1-143 C | Adder | 8.19 MW | 6.96 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944782 | AF1-143 E | Adder | 4.37 MW | 3.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 945021 | AF1-167 C | Adder | 0.79 MW | 0.67 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 945022 | AF1-167 E | Adder | 0.53 MW | 0.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 945051 | AF1-170 C | Adder | 3.64 MW | 3.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 945052 | AF1-170 E | Adder | 2.43 MW | 2.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 945451 | AF1-210 C | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 945452 | AF1-210 E | Adder | 0.58 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 945751 | AF1-240 C O1 | Adder | 1.68 MW | 1.43 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 945752 | AF1-240 E O1 | Adder | 1.12 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 958471 | AF2-141 | Adder | 1.09 MW | 0.93 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 958731 | AF2-164 C O1 | Adder | 5.72 MW | 4.86 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 958732 | AF2-164 E O1 | Adder | 3.81 MW | 3.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 958741 | AF2-165 C | Adder | 1.25 MW | 1.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 958742 | AF2-165 E | Adder | 0.84 MW | 0.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 958751 | AF2-166 C | Adder | 1.3 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 958752 | AF2-166 E | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 959441 | AF2-235 C | Adder | 0.59 MW | 0.5 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 959442 | AF2-235 E | Adder | 0.39 MW | 0.34 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 959471 | AF2-238 C | Adder | 1.26 MW | 1.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 959472 | AF2-238 E | Adder | 0.84 MW | 0.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 959521 | AF2-243 C | Adder | 0.94 MW | 0.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 959522 | AF2-243 E | Adder | 0.63 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 959802 | AF2-271 E | Adder | 0.38 MW | 0.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960022 | AF2-293 E | Adder | 0.1 MW | 0.08 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960031 | AF2-294 C | Adder | 0.96 MW | 0.81 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960032 | AF2-294 E | Adder | 0.64 MW | 0.54 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960051 | AF2-296 C | Adder | 1.67 MW | 1.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960052 | AF2-296 E | Adder | 1.11 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960451 | AF2-336 C | Adder | 2.07 MW | 1.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960452 | AF2-336 E | Adder | 1.38 MW | 1.17 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960461 | AF2-337 C | Adder | 2.07 MW | 1.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960462 | AF2-337 E | Adder | 1.38 MW | 1.17 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 961141 | AF2-405 | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 961151 | AF2-406 | Adder | 7.68 MW | 6.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 961211 | AF2-412 | Adder | 15.67 MW | 13.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 961451 | AF2-436 | Adder | 0.11 MW | 0.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200636 | 26IUP CO-G | 50/50 | 0.49 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200794 | 26CONEMAGH | 50/50 | 0.33 MW | 0.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200809 | 26SITHE | 50/50 | 1.54 MW | 1.54 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200835 | 26ARN_Z1-066 | Adder | 1.09 MW | 0.93 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200837 | 26HOMER C1 | 50/50 | 26.57 MW | 26.57 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200838 | 26HOMER C2 | 50/50 | 22.01 MW | 22.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200839 | 26HOMER C3 | 50/50 | 23.3 MW | 23.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200846 | 26FORWARD | 50/50 | 0.1 MW | 0.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200852 | 26WARR RDG | Adder | 0.31 MW | 0.26 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200864 | K-013 E | 50/50 | 4.23 MW | 4.23 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200883 | Q-053 E | Adder | 5.08 MW | 4.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200888 | 26HIGHLAND | 50/50 | 0.24 MW | 0.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200894 | 26K02 | Adder | 4.95 MW | 4.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200925 | 26R32 | 50/50 | 0.38 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 203915 | 26BF_Z2-108 | Adder | 2.46 MW | 2.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 203932 | AA2-133 GEN | Adder | 1.5 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 203999 | P-047 E | Adder | 8.92 MW | 7.58 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 235003 | AC1-025 E | Adder | 0.12 MW | 0.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 292350 | K-023 | Adder | 3.4 MW | 2.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 292542 | L-013 1 | Adder | 4.37 MW | 3.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 293301 | N-039 E | Adder | 10.36 MW | 8.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 293393 | V3-030E | Adder | 4.72 MW | 4.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 293603 | O-018 E | 50/50 | 9.21 MW | 9.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 293902 | O-048 E | Adder | 3.93 MW | 3.34 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 294515 | O38_P22 | Adder | 9.06 MW | 7.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 294903 | P-060 E | Adder | 7.04 MW | 5.99 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 916202 | Z1-069 E | Adder | 7.19 MW | 6.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 931092 | AB1-160 E | Adder | 2.05 MW | 1.75 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 938951 | AE1-123 | Adder | 2.02 MW | 1.72 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 939291 | AE1-160 C | Adder | 1.25 MW | 1.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 939292 | AE1-160 E | Adder | 0.72 MW | 0.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 940201 | AE2-001 C | Adder | 1.02 MW | 0.86 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 940202 | AE2-001 E | Adder | 0.68 MW | 0.58 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 940681 | AE2-055 C | Adder | 0.99 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 940682 | AE2-055 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 940861 | AE2-074 C | Adder | 1.97 MW | 1.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 940862 | AE2-074 E | Adder | 2.59 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941191 | AE2-113 C | Adder | 7.64 MW | 6.5 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941192 | AE2-113 E | Adder | 7.18 MW | 6.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941231 | AE2-117 C | Adder | 1.49 MW | 1.26 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941232 | AE2-117 E | Adder | 0.99 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941241 | AE2-118 C | Adder | 1.56 MW | 1.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941242 | AE2-118 E | Adder | 1.04 MW | 0.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941271 | AE2-121 C | Adder | 0.54 MW | 0.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941272 | AE2-121 E | Adder | 0.36 MW | 0.31 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941331 | AE2-129 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941332 | AE2-129 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941351 | AE2-131 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941352 | AE2-131 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941421 | AE2-139 C | Adder | 5.07 MW | 4.31 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 941422 | AE2-139 E | Adder | 3.38 MW | 2.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946071 | AF1-272 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946072 | AF1-272 E O1 | 50/50 | 10.45 MW | 10.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946111 | AF1-276 C | Adder | 8.81 MW | 7.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946112 | AF1-276 E | Adder | 4.34 MW | 3.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946121 | AF1-277 C | Adder | 8.81 MW | 7.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946122 | AF1-277 E | Adder | 4.34 MW | 3.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946131 | AF1-278 C | Adder | 7.02 MW | 5.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946132 | AF1-278 E | Adder | 3.49 MW | 2.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946221 | AF1-287 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946222 | AF1-287 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946381 | AF1-302 C | Adder | 1.88 MW | 1.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946382 | AF1-302 E | Adder | 2.51 MW | 2.13 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946571 | AF1-321 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946572 | AF1-321 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946771 | AF1-217 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946772 | AF1-217 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957001 | AF2-001 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957002 | AF2-001 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957011 | AF2-002 C O1 | 50/50 | 1.11 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957012 | AF2-002 E O1 | 50/50 | 0.74 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957161 | AF2-010 C | Adder | 4.02 MW | 3.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957162 | AF2-010 E | Adder | 2.71 MW | 2.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957451 | AF2-039 C | Adder | 0.92 MW | 0.79 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957452 | AF2-039 E | Adder | 0.62 MW | 0.52 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957561 | AF2-050 C | Adder | 5.09 MW | 4.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957562 | AF2-050 E | Adder | 3.39 MW | 2.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957931 | AF2-087 C | Adder | 0.45 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957932 | AF2-087 E | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957941 | AF2-088 C | Adder | 0.44 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957942 | AF2-088 E | Adder | 0.3 MW | 0.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957981 | AF2-092 C | Adder | 1.24 MW | 1.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 957982 | AF2-092 E | Adder | 0.83 MW | 0.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 958271 | AF2-121 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 958272 | AF2-121 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 958361 | AF2-130 C | Adder | 1.3 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 958362 | AF2-130 E | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200833 | 26SEWRDB34 | 50/50 | 16.03 MW | 16.03 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 200906 | 26KEYSTN#3 | 50/50 | 0.82 MW | 0.82 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 959301 | AF2-221 C | 50/50 | 1.15 MW | 1.15 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 959302 | AF2-221 E | 50/50 | 1.59 MW | 1.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 292340 | 26SW_E13_K22 | Adder | 1.18 MW | 1.0 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 964451 | AG1-308 C O1 | Adder | 1.04 MW | 0.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 964452 | AG1-308 E O1 | Adder | 1.46 MW | 1.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960901 | AG1-000C C | 50/50 | 7.22 MW | 7.22 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 960902 | AG1-000C E | 50/50 | 3.56 MW | 3.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946421 | AF2-000A C | Adder | 5.08 MW | 4.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | 946422 | AF2-000A E | Adder | 15.24 MW | 12.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.49 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.47 MW | 0.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.87 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 4.61 MW | 4.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.12 MW | 1.12 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.27 MW | 0.27 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.29 MW | 1.29 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.1 MW | 0.1 MW |
| Details for KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 961971 | AG1-040 C | Adder | 1.04 MW | 0.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 961972 | AG1-040 E | Adder | 0.69 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 961981 | AG1-041 C | Adder | 1.24 MW | 1.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 961982 | AG1-041 E | Adder | 0.82 MW | 0.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 962411 | AG1-090 C O1 | Adder | 10.06 MW | 8.55 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 962412 | AG1-090 E O1 | Adder | 2.52 MW | 2.14 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 962511 | AG1-100 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 962512 | AG1-100 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 962911 | AG1-140 C | Adder | 0.15 MW | 0.13 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 962912 | AG1-140 E | Adder | 0.08 MW | 0.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 963441 | AG1-193 C | Adder | 1.22 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 963442 | AG1-193 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 963481 | AG1-197 C | Adder | 0.79 MW | 0.67 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 963482 | AG1-197 E | Adder | 0.52 MW | 0.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 963491 | AG1-198 C | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 963492 | AG1-198 E | Adder | 0.42 MW | 0.35 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 963991 | AG1-253 C | Adder | 0.22 MW | 0.19 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 963992 | AG1-253 E | Adder | 0.11 MW | 0.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 964031 | AG1-257 C | Adder | 0.7 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 964032 | AG1-257 E | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 964201 | AG1-281 C | Adder | 1.92 MW | 1.64 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 964202 | AG1-281 E | Adder | 1.28 MW | 1.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 964391 | AG1-301 C | Adder | 1.47 MW | 1.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 964392 | AG1-301 E | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 964411 | AG1-303 C O1 | Adder | 2.45 MW | 2.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 964412 | AG1-303 E O1 | Adder | 1.64 MW | 1.39 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 966771 | AG1-548 C | Adder | 9.9 MW | 8.41 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 966772 | AG1-548 E | Adder | 3.01 MW | 2.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 966781 | AG1-549 C O1 | 50/50 | 37.22 MW | 37.22 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 966782 | AG1-549 E O1 | 50/50 | 6.57 MW | 6.57 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965121 | AG1-377 C O1 | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965122 | AG1-377 E O1 | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965131 | AG1-378 C O1 | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965132 | AG1-378 E O1 | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965171 | AG1-382 C | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965172 | AG1-382 E | Adder | 1.36 MW | 1.16 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965241 | AG1-392C C O | Adder | 1.53 MW | 1.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965242 | AG1-392C E O | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965251 | AG1-392B C O | Adder | 1.53 MW | 1.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965252 | AG1-392B E O | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965261 | AG1-392A C O | Adder | 3.06 MW | 2.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965262 | AG1-392A E O | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965271 | AG1-392 C O1 | Adder | 3.06 MW | 2.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965272 | AG1-392 E O1 | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 965861 | AG1-455 | Adder | 2.74 MW | 2.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 290086 | Q-036 E | Adder | 5.65 MW | 4.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 296332 | R-032 E | 50/50 | 10.62 MW | 10.62 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 913142 | Y1-033 E OP1 | Adder | 3.51 MW | 2.98 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 936991 | AD2-133 C | Adder | 2.13 MW | 1.81 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 936992 | AD2-133 E | Adder | 9.74 MW | 8.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942121 | AE2-224 C | Adder | 10.18 MW | 8.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942122 | AE2-224 E | Adder | 6.79 MW | 5.77 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942351 | AE2-248 C | Adder | 0.8 MW | 0.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942361 | AE2-249 C | Adder | 1.72 MW | 1.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942362 | AE2-249 E | Adder | 1.15 MW | 0.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942491 | AE2-262 C | Adder | 4.58 MW | 3.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942492 | AE2-262 E | Adder | 3.07 MW | 2.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942501 | AE2-263 C | Adder | 4.3 MW | 3.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942502 | AE2-263 E | Adder | 2.87 MW | 2.44 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942811 | AE2-299 C | Adder | 2.64 MW | 2.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942812 | AE2-299 E | Adder | 10.56 MW | 8.98 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942961 | AE2-316 C | Adder | 4.3 MW | 3.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 942962 | AE2-316 E | Adder | 5.1 MW | 4.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 943151 | AE2-344 C | Adder | 5.71 MW | 4.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 943152 | AE2-344 E | Adder | 3.81 MW | 3.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 943351 | AF1-006 C | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 943352 | AF1-006 E | Adder | 0.55 MW | 0.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 943711 | AF1-039 C O1 | Adder | 0.93 MW | 0.79 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 943712 | AF1-039 E O1 | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944181 | AF1-086 C O1 | Adder | 3.25 MW | 2.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944182 | AF1-086 E O1 | Adder | 14.13 MW | 12.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944261 | AF1-094 C | Adder | 1.04 MW | 0.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944262 | AF1-094 E | Adder | 0.7 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944301 | AF1-098 C | Adder | 4.06 MW | 3.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944302 | AF1-098 E | Adder | 2.71 MW | 2.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944311 | AF1-099 C | Adder | 7.14 MW | 6.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944312 | AF1-099 E | Adder | 4.76 MW | 4.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944321 | AF1-100 C | Adder | 14.77 MW | 12.55 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944322 | AF1-100 E | Adder | 9.85 MW | 8.37 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944411 | AF1-106 O1 | Adder | 2.05 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944472 | AF1-112 E | Adder | 0.51 MW | 0.43 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944691 | AF1-134 C | Adder | 1.67 MW | 1.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944692 | AF1-134 E | Adder | 1.11 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944751 | AF1-140 C | Adder | 1.66 MW | 1.41 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944752 | AF1-140 E | Adder | 1.11 MW | 0.94 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944771 | AF1-142 C | Adder | 11.43 MW | 9.72 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944772 | AF1-142 E | Adder | 7.62 MW | 6.48 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944781 | AF1-143 C | Adder | 8.19 MW | 6.96 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944782 | AF1-143 E | Adder | 4.37 MW | 3.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 945021 | AF1-167 C | Adder | 0.79 MW | 0.67 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 945022 | AF1-167 E | Adder | 0.53 MW | 0.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 945051 | AF1-170 C | Adder | 3.64 MW | 3.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 945052 | AF1-170 E | Adder | 2.43 MW | 2.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 945451 | AF1-210 C | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 945452 | AF1-210 E | Adder | 0.58 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 945751 | AF1-240 C O1 | Adder | 1.68 MW | 1.43 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 945752 | AF1-240 E O1 | Adder | 1.12 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 958471 | AF2-141 | Adder | 1.09 MW | 0.93 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 958731 | AF2-164 C O1 | Adder | 5.72 MW | 4.86 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 958732 | AF2-164 E O1 | Adder | 3.81 MW | 3.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 958741 | AF2-165 C | Adder | 1.25 MW | 1.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 958742 | AF2-165 E | Adder | 0.84 MW | 0.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 958751 | AF2-166 C | Adder | 1.3 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 958752 | AF2-166 E | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 959441 | AF2-235 C | Adder | 0.59 MW | 0.5 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 959442 | AF2-235 E | Adder | 0.39 MW | 0.34 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 959471 | AF2-238 C | Adder | 1.26 MW | 1.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 959472 | AF2-238 E | Adder | 0.84 MW | 0.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 959521 | AF2-243 C | Adder | 0.94 MW | 0.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 959522 | AF2-243 E | Adder | 0.63 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 959802 | AF2-271 E | Adder | 0.38 MW | 0.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960022 | AF2-293 E | Adder | 0.1 MW | 0.08 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960031 | AF2-294 C | Adder | 0.96 MW | 0.81 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960032 | AF2-294 E | Adder | 0.64 MW | 0.54 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960051 | AF2-296 C | Adder | 1.67 MW | 1.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960052 | AF2-296 E | Adder | 1.11 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960451 | AF2-336 C | Adder | 2.07 MW | 1.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960452 | AF2-336 E | Adder | 1.38 MW | 1.17 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960461 | AF2-337 C | Adder | 2.07 MW | 1.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960462 | AF2-337 E | Adder | 1.38 MW | 1.17 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 961141 | AF2-405 | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 961151 | AF2-406 | Adder | 7.68 MW | 6.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 961211 | AF2-412 | Adder | 15.67 MW | 13.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 961451 | AF2-436 | Adder | 0.11 MW | 0.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200636 | 26IUP CO-G | 50/50 | 0.49 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200794 | 26CONEMAGH | 50/50 | 0.33 MW | 0.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200809 | 26SITHE | 50/50 | 1.54 MW | 1.54 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200835 | 26ARN_Z1-066 | Adder | 1.09 MW | 0.93 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200837 | 26HOMER C1 | 50/50 | 26.57 MW | 26.57 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200838 | 26HOMER C2 | 50/50 | 22.01 MW | 22.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200839 | 26HOMER C3 | 50/50 | 23.3 MW | 23.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200846 | 26FORWARD | 50/50 | 0.1 MW | 0.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200852 | 26WARR RDG | Adder | 0.31 MW | 0.26 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200864 | K-013 E | 50/50 | 4.23 MW | 4.23 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200883 | Q-053 E | Adder | 5.08 MW | 4.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200888 | 26HIGHLAND | 50/50 | 0.24 MW | 0.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200894 | 26K02 | Adder | 4.95 MW | 4.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200925 | 26R32 | 50/50 | 0.38 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 203915 | 26BF_Z2-108 | Adder | 2.46 MW | 2.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 203932 | AA2-133 GEN | Adder | 1.5 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 203999 | P-047 E | Adder | 8.92 MW | 7.58 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 235003 | AC1-025 E | Adder | 0.12 MW | 0.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 292350 | K-023 | Adder | 3.4 MW | 2.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 292542 | L-013 1 | Adder | 4.37 MW | 3.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 293301 | N-039 E | Adder | 10.36 MW | 8.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 293393 | V3-030E | Adder | 4.72 MW | 4.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 293603 | O-018 E | 50/50 | 9.21 MW | 9.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 293902 | O-048 E | Adder | 3.93 MW | 3.34 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 294515 | O38_P22 | Adder | 9.06 MW | 7.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 294903 | P-060 E | Adder | 7.04 MW | 5.99 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 916202 | Z1-069 E | Adder | 7.19 MW | 6.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 931092 | AB1-160 E | Adder | 2.05 MW | 1.75 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 938951 | AE1-123 | Adder | 2.02 MW | 1.72 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 939291 | AE1-160 C | Adder | 1.25 MW | 1.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 939292 | AE1-160 E | Adder | 0.72 MW | 0.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 940201 | AE2-001 C | Adder | 1.02 MW | 0.86 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 940202 | AE2-001 E | Adder | 0.68 MW | 0.58 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 940681 | AE2-055 C | Adder | 0.99 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 940682 | AE2-055 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 940861 | AE2-074 C | Adder | 1.97 MW | 1.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 940862 | AE2-074 E | Adder | 2.59 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941191 | AE2-113 C | Adder | 7.64 MW | 6.5 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941192 | AE2-113 E | Adder | 7.18 MW | 6.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941231 | AE2-117 C | Adder | 1.49 MW | 1.26 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941232 | AE2-117 E | Adder | 0.99 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941241 | AE2-118 C | Adder | 1.56 MW | 1.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941242 | AE2-118 E | Adder | 1.04 MW | 0.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941271 | AE2-121 C | Adder | 0.54 MW | 0.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941272 | AE2-121 E | Adder | 0.36 MW | 0.31 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941331 | AE2-129 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941332 | AE2-129 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941351 | AE2-131 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941352 | AE2-131 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941421 | AE2-139 C | Adder | 5.07 MW | 4.31 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 941422 | AE2-139 E | Adder | 3.38 MW | 2.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946071 | AF1-272 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946072 | AF1-272 E O1 | 50/50 | 10.45 MW | 10.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946111 | AF1-276 C | Adder | 8.81 MW | 7.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946112 | AF1-276 E | Adder | 4.34 MW | 3.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946121 | AF1-277 C | Adder | 8.81 MW | 7.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946122 | AF1-277 E | Adder | 4.34 MW | 3.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946131 | AF1-278 C | Adder | 7.02 MW | 5.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946132 | AF1-278 E | Adder | 3.49 MW | 2.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946221 | AF1-287 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946222 | AF1-287 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946381 | AF1-302 C | Adder | 1.88 MW | 1.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946382 | AF1-302 E | Adder | 2.51 MW | 2.13 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946571 | AF1-321 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946572 | AF1-321 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946771 | AF1-217 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946772 | AF1-217 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957001 | AF2-001 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957002 | AF2-001 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957011 | AF2-002 C O1 | 50/50 | 1.11 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957012 | AF2-002 E O1 | 50/50 | 0.74 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957161 | AF2-010 C | Adder | 4.02 MW | 3.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957162 | AF2-010 E | Adder | 2.71 MW | 2.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957451 | AF2-039 C | Adder | 0.92 MW | 0.79 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957452 | AF2-039 E | Adder | 0.62 MW | 0.52 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957561 | AF2-050 C | Adder | 5.09 MW | 4.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957562 | AF2-050 E | Adder | 3.39 MW | 2.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957931 | AF2-087 C | Adder | 0.45 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957932 | AF2-087 E | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957941 | AF2-088 C | Adder | 0.44 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957942 | AF2-088 E | Adder | 0.3 MW | 0.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957981 | AF2-092 C | Adder | 1.24 MW | 1.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 957982 | AF2-092 E | Adder | 0.83 MW | 0.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 958271 | AF2-121 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 958272 | AF2-121 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 958361 | AF2-130 C | Adder | 1.3 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 958362 | AF2-130 E | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200833 | 26SEWRDB34 | 50/50 | 16.03 MW | 16.03 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 200906 | 26KEYSTN#3 | 50/50 | 0.82 MW | 0.82 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 959301 | AF2-221 C | 50/50 | 1.15 MW | 1.15 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 959302 | AF2-221 E | 50/50 | 1.59 MW | 1.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 292340 | 26SW_E13_K22 | Adder | 1.18 MW | 1.0 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 964451 | AG1-308 C O1 | Adder | 1.04 MW | 0.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 964452 | AG1-308 E O1 | Adder | 1.46 MW | 1.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960901 | AG1-000C C | 50/50 | 7.22 MW | 7.22 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 960902 | AG1-000C E | 50/50 | 3.56 MW | 3.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946421 | AF2-000A C | Adder | 5.08 MW | 4.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | 946422 | AF2-000A E | Adder | 15.24 MW | 12.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.49 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.47 MW | 0.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.87 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 4.61 MW | 4.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.12 MW | 1.12 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.27 MW | 0.27 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.29 MW | 1.29 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.1 MW | 0.1 MW |
| Details for KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 961971 | AG1-040 C | Adder | 1.04 MW | 0.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 961972 | AG1-040 E | Adder | 0.69 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 961981 | AG1-041 C | Adder | 1.24 MW | 1.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 961982 | AG1-041 E | Adder | 0.82 MW | 0.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 962411 | AG1-090 C O1 | Adder | 10.06 MW | 8.55 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 962412 | AG1-090 E O1 | Adder | 2.52 MW | 2.14 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 962511 | AG1-100 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 962512 | AG1-100 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 962911 | AG1-140 C | Adder | 0.15 MW | 0.13 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 962912 | AG1-140 E | Adder | 0.08 MW | 0.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 963441 | AG1-193 C | Adder | 1.22 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 963442 | AG1-193 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 963481 | AG1-197 C | Adder | 0.79 MW | 0.67 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 963482 | AG1-197 E | Adder | 0.52 MW | 0.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 963491 | AG1-198 C | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 963492 | AG1-198 E | Adder | 0.42 MW | 0.35 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 963991 | AG1-253 C | Adder | 0.22 MW | 0.19 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 963992 | AG1-253 E | Adder | 0.11 MW | 0.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 964031 | AG1-257 C | Adder | 0.7 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 964032 | AG1-257 E | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 964201 | AG1-281 C | Adder | 1.92 MW | 1.64 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 964202 | AG1-281 E | Adder | 1.28 MW | 1.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 964391 | AG1-301 C | Adder | 1.47 MW | 1.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 964392 | AG1-301 E | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 964411 | AG1-303 C O1 | Adder | 2.45 MW | 2.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 964412 | AG1-303 E O1 | Adder | 1.64 MW | 1.39 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 966771 | AG1-548 C | Adder | 9.9 MW | 8.41 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 966772 | AG1-548 E | Adder | 3.01 MW | 2.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 966781 | AG1-549 C O1 | 50/50 | 37.22 MW | 37.22 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 966782 | AG1-549 E O1 | 50/50 | 6.57 MW | 6.57 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965121 | AG1-377 C O1 | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965122 | AG1-377 E O1 | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965131 | AG1-378 C O1 | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965132 | AG1-378 E O1 | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965171 | AG1-382 C | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965172 | AG1-382 E | Adder | 1.36 MW | 1.16 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965241 | AG1-392C C O | Adder | 1.53 MW | 1.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965242 | AG1-392C E O | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965251 | AG1-392B C O | Adder | 1.53 MW | 1.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965252 | AG1-392B E O | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965261 | AG1-392A C O | Adder | 3.06 MW | 2.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965262 | AG1-392A E O | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965271 | AG1-392 C O1 | Adder | 3.06 MW | 2.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965272 | AG1-392 E O1 | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 965861 | AG1-455 | Adder | 2.74 MW | 2.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 290086 | Q-036 E | Adder | 5.65 MW | 4.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 296332 | R-032 E | 50/50 | 10.62 MW | 10.62 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 913142 | Y1-033 E OP1 | Adder | 3.51 MW | 2.98 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 936991 | AD2-133 C | Adder | 2.13 MW | 1.81 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 936992 | AD2-133 E | Adder | 9.74 MW | 8.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942121 | AE2-224 C | Adder | 10.18 MW | 8.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942122 | AE2-224 E | Adder | 6.79 MW | 5.77 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942351 | AE2-248 C | Adder | 0.8 MW | 0.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942361 | AE2-249 C | Adder | 1.72 MW | 1.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942362 | AE2-249 E | Adder | 1.15 MW | 0.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942491 | AE2-262 C | Adder | 4.58 MW | 3.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942492 | AE2-262 E | Adder | 3.07 MW | 2.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942501 | AE2-263 C | Adder | 4.3 MW | 3.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942502 | AE2-263 E | Adder | 2.87 MW | 2.44 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942811 | AE2-299 C | Adder | 2.64 MW | 2.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942812 | AE2-299 E | Adder | 10.56 MW | 8.98 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942961 | AE2-316 C | Adder | 4.3 MW | 3.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 942962 | AE2-316 E | Adder | 5.1 MW | 4.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 943151 | AE2-344 C | Adder | 5.71 MW | 4.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 943152 | AE2-344 E | Adder | 3.81 MW | 3.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 943351 | AF1-006 C | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 943352 | AF1-006 E | Adder | 0.55 MW | 0.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 943711 | AF1-039 C O1 | Adder | 0.93 MW | 0.79 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 943712 | AF1-039 E O1 | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944181 | AF1-086 C O1 | Adder | 3.25 MW | 2.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944182 | AF1-086 E O1 | Adder | 14.13 MW | 12.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944261 | AF1-094 C | Adder | 1.04 MW | 0.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944262 | AF1-094 E | Adder | 0.7 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944301 | AF1-098 C | Adder | 4.06 MW | 3.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944302 | AF1-098 E | Adder | 2.71 MW | 2.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944311 | AF1-099 C | Adder | 7.14 MW | 6.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944312 | AF1-099 E | Adder | 4.76 MW | 4.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944321 | AF1-100 C | Adder | 14.77 MW | 12.55 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944322 | AF1-100 E | Adder | 9.85 MW | 8.37 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944411 | AF1-106 O1 | Adder | 2.05 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944472 | AF1-112 E | Adder | 0.51 MW | 0.43 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944691 | AF1-134 C | Adder | 1.67 MW | 1.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944692 | AF1-134 E | Adder | 1.11 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944751 | AF1-140 C | Adder | 1.66 MW | 1.41 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944752 | AF1-140 E | Adder | 1.11 MW | 0.94 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944771 | AF1-142 C | Adder | 11.43 MW | 9.72 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944772 | AF1-142 E | Adder | 7.62 MW | 6.48 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944781 | AF1-143 C | Adder | 8.19 MW | 6.96 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944782 | AF1-143 E | Adder | 4.37 MW | 3.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 945021 | AF1-167 C | Adder | 0.79 MW | 0.67 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 945022 | AF1-167 E | Adder | 0.53 MW | 0.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 945051 | AF1-170 C | Adder | 3.64 MW | 3.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 945052 | AF1-170 E | Adder | 2.43 MW | 2.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 945451 | AF1-210 C | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 945452 | AF1-210 E | Adder | 0.58 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 945751 | AF1-240 C O1 | Adder | 1.68 MW | 1.43 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 945752 | AF1-240 E O1 | Adder | 1.12 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 958471 | AF2-141 | Adder | 1.09 MW | 0.93 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 958731 | AF2-164 C O1 | Adder | 5.72 MW | 4.86 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 958732 | AF2-164 E O1 | Adder | 3.81 MW | 3.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 958741 | AF2-165 C | Adder | 1.25 MW | 1.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 958742 | AF2-165 E | Adder | 0.84 MW | 0.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 958751 | AF2-166 C | Adder | 1.3 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 958752 | AF2-166 E | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 959441 | AF2-235 C | Adder | 0.59 MW | 0.5 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 959442 | AF2-235 E | Adder | 0.39 MW | 0.34 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 959471 | AF2-238 C | Adder | 1.26 MW | 1.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 959472 | AF2-238 E | Adder | 0.84 MW | 0.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 959521 | AF2-243 C | Adder | 0.94 MW | 0.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 959522 | AF2-243 E | Adder | 0.63 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 959802 | AF2-271 E | Adder | 0.38 MW | 0.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960022 | AF2-293 E | Adder | 0.1 MW | 0.08 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960031 | AF2-294 C | Adder | 0.96 MW | 0.81 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960032 | AF2-294 E | Adder | 0.64 MW | 0.54 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960051 | AF2-296 C | Adder | 1.67 MW | 1.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960052 | AF2-296 E | Adder | 1.11 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960451 | AF2-336 C | Adder | 2.07 MW | 1.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960452 | AF2-336 E | Adder | 1.38 MW | 1.17 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960461 | AF2-337 C | Adder | 2.07 MW | 1.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960462 | AF2-337 E | Adder | 1.38 MW | 1.17 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 961141 | AF2-405 | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 961151 | AF2-406 | Adder | 7.68 MW | 6.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 961211 | AF2-412 | Adder | 15.67 MW | 13.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 961451 | AF2-436 | Adder | 0.11 MW | 0.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200636 | 26IUP CO-G | 50/50 | 0.49 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200794 | 26CONEMAGH | 50/50 | 0.33 MW | 0.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200809 | 26SITHE | 50/50 | 1.54 MW | 1.54 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200835 | 26ARN_Z1-066 | Adder | 1.09 MW | 0.93 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200837 | 26HOMER C1 | 50/50 | 26.57 MW | 26.57 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200838 | 26HOMER C2 | 50/50 | 22.01 MW | 22.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200839 | 26HOMER C3 | 50/50 | 23.3 MW | 23.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200846 | 26FORWARD | 50/50 | 0.1 MW | 0.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200852 | 26WARR RDG | Adder | 0.31 MW | 0.26 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200864 | K-013 E | 50/50 | 4.23 MW | 4.23 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200883 | Q-053 E | Adder | 5.08 MW | 4.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200888 | 26HIGHLAND | 50/50 | 0.24 MW | 0.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200894 | 26K02 | Adder | 4.95 MW | 4.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200925 | 26R32 | 50/50 | 0.38 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 203915 | 26BF_Z2-108 | Adder | 2.46 MW | 2.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 203932 | AA2-133 GEN | Adder | 1.5 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 203999 | P-047 E | Adder | 8.92 MW | 7.58 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 235003 | AC1-025 E | Adder | 0.12 MW | 0.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 292350 | K-023 | Adder | 3.4 MW | 2.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 292542 | L-013 1 | Adder | 4.37 MW | 3.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 293301 | N-039 E | Adder | 10.36 MW | 8.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 293393 | V3-030E | Adder | 4.72 MW | 4.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 293603 | O-018 E | 50/50 | 9.21 MW | 9.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 293902 | O-048 E | Adder | 3.93 MW | 3.34 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 294515 | O38_P22 | Adder | 9.06 MW | 7.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 294903 | P-060 E | Adder | 7.04 MW | 5.99 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 916202 | Z1-069 E | Adder | 7.19 MW | 6.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 931092 | AB1-160 E | Adder | 2.05 MW | 1.75 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 938951 | AE1-123 | Adder | 2.02 MW | 1.72 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 939291 | AE1-160 C | Adder | 1.25 MW | 1.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 939292 | AE1-160 E | Adder | 0.72 MW | 0.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 940201 | AE2-001 C | Adder | 1.02 MW | 0.86 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 940202 | AE2-001 E | Adder | 0.68 MW | 0.58 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 940681 | AE2-055 C | Adder | 0.99 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 940682 | AE2-055 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 940861 | AE2-074 C | Adder | 1.97 MW | 1.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 940862 | AE2-074 E | Adder | 2.59 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941191 | AE2-113 C | Adder | 7.64 MW | 6.5 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941192 | AE2-113 E | Adder | 7.18 MW | 6.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941231 | AE2-117 C | Adder | 1.49 MW | 1.26 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941232 | AE2-117 E | Adder | 0.99 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941241 | AE2-118 C | Adder | 1.56 MW | 1.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941242 | AE2-118 E | Adder | 1.04 MW | 0.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941271 | AE2-121 C | Adder | 0.54 MW | 0.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941272 | AE2-121 E | Adder | 0.36 MW | 0.31 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941331 | AE2-129 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941332 | AE2-129 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941351 | AE2-131 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941352 | AE2-131 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941421 | AE2-139 C | Adder | 5.07 MW | 4.31 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 941422 | AE2-139 E | Adder | 3.38 MW | 2.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946071 | AF1-272 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946072 | AF1-272 E O1 | 50/50 | 10.45 MW | 10.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946111 | AF1-276 C | Adder | 8.81 MW | 7.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946112 | AF1-276 E | Adder | 4.34 MW | 3.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946121 | AF1-277 C | Adder | 8.81 MW | 7.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946122 | AF1-277 E | Adder | 4.34 MW | 3.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946131 | AF1-278 C | Adder | 7.02 MW | 5.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946132 | AF1-278 E | Adder | 3.49 MW | 2.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946221 | AF1-287 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946222 | AF1-287 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946381 | AF1-302 C | Adder | 1.88 MW | 1.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946382 | AF1-302 E | Adder | 2.51 MW | 2.13 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946571 | AF1-321 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946572 | AF1-321 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946771 | AF1-217 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946772 | AF1-217 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957001 | AF2-001 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957002 | AF2-001 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957011 | AF2-002 C O1 | 50/50 | 1.11 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957012 | AF2-002 E O1 | 50/50 | 0.74 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957161 | AF2-010 C | Adder | 4.02 MW | 3.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957162 | AF2-010 E | Adder | 2.71 MW | 2.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957451 | AF2-039 C | Adder | 0.92 MW | 0.79 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957452 | AF2-039 E | Adder | 0.62 MW | 0.52 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957561 | AF2-050 C | Adder | 5.09 MW | 4.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957562 | AF2-050 E | Adder | 3.39 MW | 2.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957931 | AF2-087 C | Adder | 0.45 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957932 | AF2-087 E | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957941 | AF2-088 C | Adder | 0.44 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957942 | AF2-088 E | Adder | 0.3 MW | 0.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957981 | AF2-092 C | Adder | 1.24 MW | 1.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 957982 | AF2-092 E | Adder | 0.83 MW | 0.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 958271 | AF2-121 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 958272 | AF2-121 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 958361 | AF2-130 C | Adder | 1.3 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 958362 | AF2-130 E | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200833 | 26SEWRDB34 | 50/50 | 16.03 MW | 16.03 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 200906 | 26KEYSTN#3 | 50/50 | 0.82 MW | 0.82 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 959301 | AF2-221 C | 50/50 | 1.15 MW | 1.15 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 959302 | AF2-221 E | 50/50 | 1.59 MW | 1.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 292340 | 26SW_E13_K22 | Adder | 1.18 MW | 1.0 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 964451 | AG1-308 C O1 | Adder | 1.04 MW | 0.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 964452 | AG1-308 E O1 | Adder | 1.46 MW | 1.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960901 | AG1-000C C | 50/50 | 7.22 MW | 7.22 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 960902 | AG1-000C E | 50/50 | 3.56 MW | 3.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946421 | AF2-000A C | Adder | 5.08 MW | 4.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | 946422 | AF2-000A E | Adder | 15.24 MW | 12.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.49 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.47 MW | 0.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.87 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 4.61 MW | 4.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.12 MW | 1.12 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.27 MW | 0.27 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.29 MW | 1.29 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT27 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.1 MW | 0.1 MW |
| Details for KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 961971 | AG1-040 C | Adder | 1.04 MW | 0.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 961972 | AG1-040 E | Adder | 0.69 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 961981 | AG1-041 C | Adder | 1.24 MW | 1.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 961982 | AG1-041 E | Adder | 0.82 MW | 0.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 962411 | AG1-090 C O1 | Adder | 10.06 MW | 8.55 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 962412 | AG1-090 E O1 | Adder | 2.52 MW | 2.14 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 962511 | AG1-100 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 962512 | AG1-100 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 962911 | AG1-140 C | Adder | 0.15 MW | 0.13 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 962912 | AG1-140 E | Adder | 0.08 MW | 0.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 963441 | AG1-193 C | Adder | 1.22 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 963442 | AG1-193 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 963481 | AG1-197 C | Adder | 0.79 MW | 0.67 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 963482 | AG1-197 E | Adder | 0.52 MW | 0.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 963491 | AG1-198 C | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 963492 | AG1-198 E | Adder | 0.42 MW | 0.35 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 963991 | AG1-253 C | Adder | 0.22 MW | 0.19 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 963992 | AG1-253 E | Adder | 0.11 MW | 0.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 964031 | AG1-257 C | Adder | 0.7 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 964032 | AG1-257 E | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 964201 | AG1-281 C | Adder | 1.92 MW | 1.64 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 964202 | AG1-281 E | Adder | 1.28 MW | 1.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 964391 | AG1-301 C | Adder | 1.47 MW | 1.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 964392 | AG1-301 E | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 964411 | AG1-303 C O1 | Adder | 2.45 MW | 2.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 964412 | AG1-303 E O1 | Adder | 1.64 MW | 1.39 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 966771 | AG1-548 C | Adder | 9.9 MW | 8.41 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 966772 | AG1-548 E | Adder | 3.01 MW | 2.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 966781 | AG1-549 C O1 | 50/50 | 37.22 MW | 37.22 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 966782 | AG1-549 E O1 | 50/50 | 6.57 MW | 6.57 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965121 | AG1-377 C O1 | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965122 | AG1-377 E O1 | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965131 | AG1-378 C O1 | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965132 | AG1-378 E O1 | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965171 | AG1-382 C | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965172 | AG1-382 E | Adder | 1.36 MW | 1.16 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965241 | AG1-392C C O | Adder | 1.53 MW | 1.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965242 | AG1-392C E O | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965251 | AG1-392B C O | Adder | 1.53 MW | 1.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965252 | AG1-392B E O | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965261 | AG1-392A C O | Adder | 3.06 MW | 2.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965262 | AG1-392A E O | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965271 | AG1-392 C O1 | Adder | 3.06 MW | 2.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965272 | AG1-392 E O1 | Adder | 2.04 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 965861 | AG1-455 | Adder | 2.74 MW | 2.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 290086 | Q-036 E | Adder | 5.65 MW | 4.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 296332 | R-032 E | 50/50 | 10.62 MW | 10.62 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 913142 | Y1-033 E OP1 | Adder | 3.51 MW | 2.98 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 936991 | AD2-133 C | Adder | 2.13 MW | 1.81 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 936992 | AD2-133 E | Adder | 9.74 MW | 8.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942121 | AE2-224 C | Adder | 10.18 MW | 8.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942122 | AE2-224 E | Adder | 6.79 MW | 5.77 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942351 | AE2-248 C | Adder | 0.8 MW | 0.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942361 | AE2-249 C | Adder | 1.72 MW | 1.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942362 | AE2-249 E | Adder | 1.15 MW | 0.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942491 | AE2-262 C | Adder | 4.58 MW | 3.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942492 | AE2-262 E | Adder | 3.07 MW | 2.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942501 | AE2-263 C | Adder | 4.3 MW | 3.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942502 | AE2-263 E | Adder | 2.87 MW | 2.44 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942811 | AE2-299 C | Adder | 2.64 MW | 2.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942812 | AE2-299 E | Adder | 10.56 MW | 8.98 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942961 | AE2-316 C | Adder | 4.3 MW | 3.66 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 942962 | AE2-316 E | Adder | 5.1 MW | 4.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 943151 | AE2-344 C | Adder | 5.71 MW | 4.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 943152 | AE2-344 E | Adder | 3.81 MW | 3.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 943351 | AF1-006 C | Adder | 0.98 MW | 0.83 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 943352 | AF1-006 E | Adder | 0.55 MW | 0.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 943711 | AF1-039 C O1 | Adder | 0.93 MW | 0.79 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 943712 | AF1-039 E O1 | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944181 | AF1-086 C O1 | Adder | 3.25 MW | 2.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944182 | AF1-086 E O1 | Adder | 14.13 MW | 12.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944261 | AF1-094 C | Adder | 1.04 MW | 0.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944262 | AF1-094 E | Adder | 0.7 MW | 0.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944301 | AF1-098 C | Adder | 4.06 MW | 3.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944302 | AF1-098 E | Adder | 2.71 MW | 2.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944311 | AF1-099 C | Adder | 7.14 MW | 6.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944312 | AF1-099 E | Adder | 4.76 MW | 4.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944321 | AF1-100 C | Adder | 14.77 MW | 12.55 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944322 | AF1-100 E | Adder | 9.85 MW | 8.37 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944411 | AF1-106 O1 | Adder | 2.05 MW | 1.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944472 | AF1-112 E | Adder | 0.51 MW | 0.43 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944691 | AF1-134 C | Adder | 1.67 MW | 1.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944692 | AF1-134 E | Adder | 1.11 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944751 | AF1-140 C | Adder | 1.66 MW | 1.41 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944752 | AF1-140 E | Adder | 1.11 MW | 0.94 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944771 | AF1-142 C | Adder | 11.43 MW | 9.72 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944772 | AF1-142 E | Adder | 7.62 MW | 6.48 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944781 | AF1-143 C | Adder | 8.19 MW | 6.96 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944782 | AF1-143 E | Adder | 4.37 MW | 3.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 945021 | AF1-167 C | Adder | 0.79 MW | 0.67 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 945022 | AF1-167 E | Adder | 0.53 MW | 0.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 945051 | AF1-170 C | Adder | 3.64 MW | 3.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 945052 | AF1-170 E | Adder | 2.43 MW | 2.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 945451 | AF1-210 C | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 945452 | AF1-210 E | Adder | 0.58 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 945751 | AF1-240 C O1 | Adder | 1.68 MW | 1.43 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 945752 | AF1-240 E O1 | Adder | 1.12 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 958471 | AF2-141 | Adder | 1.09 MW | 0.93 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 958731 | AF2-164 C O1 | Adder | 5.72 MW | 4.86 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 958732 | AF2-164 E O1 | Adder | 3.81 MW | 3.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 958741 | AF2-165 C | Adder | 1.25 MW | 1.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 958742 | AF2-165 E | Adder | 0.84 MW | 0.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 958751 | AF2-166 C | Adder | 1.3 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 958752 | AF2-166 E | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 959441 | AF2-235 C | Adder | 0.59 MW | 0.5 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 959442 | AF2-235 E | Adder | 0.39 MW | 0.34 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 959471 | AF2-238 C | Adder | 1.26 MW | 1.07 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 959472 | AF2-238 E | Adder | 0.84 MW | 0.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 959521 | AF2-243 C | Adder | 0.94 MW | 0.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 959522 | AF2-243 E | Adder | 0.63 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 959802 | AF2-271 E | Adder | 0.38 MW | 0.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960022 | AF2-293 E | Adder | 0.1 MW | 0.08 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960031 | AF2-294 C | Adder | 0.96 MW | 0.81 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960032 | AF2-294 E | Adder | 0.64 MW | 0.54 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960051 | AF2-296 C | Adder | 1.67 MW | 1.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960052 | AF2-296 E | Adder | 1.11 MW | 0.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960451 | AF2-336 C | Adder | 2.07 MW | 1.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960452 | AF2-336 E | Adder | 1.38 MW | 1.17 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960461 | AF2-337 C | Adder | 2.07 MW | 1.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960462 | AF2-337 E | Adder | 1.38 MW | 1.17 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 961141 | AF2-405 | Adder | 1.02 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 961151 | AF2-406 | Adder | 7.68 MW | 6.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 961211 | AF2-412 | Adder | 15.67 MW | 13.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 961451 | AF2-436 | Adder | 0.11 MW | 0.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200636 | 26IUP CO-G | 50/50 | 0.49 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200794 | 26CONEMAGH | 50/50 | 0.33 MW | 0.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200809 | 26SITHE | 50/50 | 1.54 MW | 1.54 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200835 | 26ARN_Z1-066 | Adder | 1.09 MW | 0.93 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200837 | 26HOMER C1 | 50/50 | 26.57 MW | 26.57 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200838 | 26HOMER C2 | 50/50 | 22.01 MW | 22.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200839 | 26HOMER C3 | 50/50 | 23.3 MW | 23.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200846 | 26FORWARD | 50/50 | 0.1 MW | 0.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200852 | 26WARR RDG | Adder | 0.31 MW | 0.26 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200864 | K-013 E | 50/50 | 4.23 MW | 4.23 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200883 | Q-053 E | Adder | 5.08 MW | 4.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200888 | 26HIGHLAND | 50/50 | 0.24 MW | 0.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200894 | 26K02 | Adder | 4.95 MW | 4.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200925 | 26R32 | 50/50 | 0.38 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 203915 | 26BF_Z2-108 | Adder | 2.46 MW | 2.09 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 203932 | AA2-133 GEN | Adder | 1.5 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 203999 | P-047 E | Adder | 8.92 MW | 7.58 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 235003 | AC1-025 E | Adder | 0.12 MW | 0.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 292350 | K-023 | Adder | 3.4 MW | 2.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 292542 | L-013 1 | Adder | 4.37 MW | 3.71 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 293301 | N-039 E | Adder | 10.36 MW | 8.8 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 293393 | V3-030E | Adder | 4.72 MW | 4.01 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 293603 | O-018 E | 50/50 | 9.21 MW | 9.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 293902 | O-048 E | Adder | 3.93 MW | 3.34 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 294515 | O38_P22 | Adder | 9.06 MW | 7.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 294903 | P-060 E | Adder | 7.04 MW | 5.99 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 916202 | Z1-069 E | Adder | 7.19 MW | 6.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 931092 | AB1-160 E | Adder | 2.05 MW | 1.75 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 938951 | AE1-123 | Adder | 2.02 MW | 1.72 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 939291 | AE1-160 C | Adder | 1.25 MW | 1.06 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 939292 | AE1-160 E | Adder | 0.72 MW | 0.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 940201 | AE2-001 C | Adder | 1.02 MW | 0.86 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 940202 | AE2-001 E | Adder | 0.68 MW | 0.58 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 940681 | AE2-055 C | Adder | 0.99 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 940682 | AE2-055 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 940861 | AE2-074 C | Adder | 1.97 MW | 1.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 940862 | AE2-074 E | Adder | 2.59 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941191 | AE2-113 C | Adder | 7.64 MW | 6.5 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941192 | AE2-113 E | Adder | 7.18 MW | 6.1 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941231 | AE2-117 C | Adder | 1.49 MW | 1.26 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941232 | AE2-117 E | Adder | 0.99 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941241 | AE2-118 C | Adder | 1.56 MW | 1.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941242 | AE2-118 E | Adder | 1.04 MW | 0.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941271 | AE2-121 C | Adder | 0.54 MW | 0.46 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941272 | AE2-121 E | Adder | 0.36 MW | 0.31 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941331 | AE2-129 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941332 | AE2-129 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941351 | AE2-131 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941352 | AE2-131 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941421 | AE2-139 C | Adder | 5.07 MW | 4.31 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 941422 | AE2-139 E | Adder | 3.38 MW | 2.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946071 | AF1-272 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946072 | AF1-272 E O1 | 50/50 | 10.45 MW | 10.45 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946111 | AF1-276 C | Adder | 8.81 MW | 7.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946112 | AF1-276 E | Adder | 4.34 MW | 3.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946121 | AF1-277 C | Adder | 8.81 MW | 7.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946122 | AF1-277 E | Adder | 4.34 MW | 3.69 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946131 | AF1-278 C | Adder | 7.02 MW | 5.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946132 | AF1-278 E | Adder | 3.49 MW | 2.97 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946221 | AF1-287 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946222 | AF1-287 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946381 | AF1-302 C | Adder | 1.88 MW | 1.6 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946382 | AF1-302 E | Adder | 2.51 MW | 2.13 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946571 | AF1-321 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946572 | AF1-321 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946771 | AF1-217 C | Adder | 0.98 MW | 0.84 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946772 | AF1-217 E | Adder | 0.66 MW | 0.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957001 | AF2-001 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957002 | AF2-001 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957011 | AF2-002 C O1 | 50/50 | 1.11 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957012 | AF2-002 E O1 | 50/50 | 0.74 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957161 | AF2-010 C | Adder | 4.02 MW | 3.42 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957162 | AF2-010 E | Adder | 2.71 MW | 2.3 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957451 | AF2-039 C | Adder | 0.92 MW | 0.79 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957452 | AF2-039 E | Adder | 0.62 MW | 0.52 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957561 | AF2-050 C | Adder | 5.09 MW | 4.33 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957562 | AF2-050 E | Adder | 3.39 MW | 2.88 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957931 | AF2-087 C | Adder | 0.45 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957932 | AF2-087 E | Adder | 0.62 MW | 0.53 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957941 | AF2-088 C | Adder | 0.44 MW | 0.38 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957942 | AF2-088 E | Adder | 0.3 MW | 0.25 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957981 | AF2-092 C | Adder | 1.24 MW | 1.05 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 957982 | AF2-092 E | Adder | 0.83 MW | 0.7 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 958271 | AF2-121 C | Adder | 1.51 MW | 1.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 958272 | AF2-121 E | Adder | 1.01 MW | 0.85 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 958361 | AF2-130 C | Adder | 1.3 MW | 1.11 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 958362 | AF2-130 E | Adder | 0.87 MW | 0.74 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200833 | 26SEWRDB34 | 50/50 | 16.03 MW | 16.03 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 200906 | 26KEYSTN#3 | 50/50 | 0.82 MW | 0.82 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 959301 | AF2-221 C | 50/50 | 1.15 MW | 1.15 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 959302 | AF2-221 E | 50/50 | 1.59 MW | 1.59 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 292340 | 26SW_E13_K22 | Adder | 1.18 MW | 1.0 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 964451 | AG1-308 C O1 | Adder | 1.04 MW | 0.89 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 964452 | AG1-308 E O1 | Adder | 1.46 MW | 1.24 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960901 | AG1-000C C | 50/50 | 7.22 MW | 7.22 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 960902 | AG1-000C E | 50/50 | 3.56 MW | 3.56 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946421 | AF2-000A C | Adder | 5.08 MW | 4.32 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | 946422 | AF2-000A E | Adder | 15.24 MW | 12.95 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.49 MW | 0.49 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.47 MW | 0.47 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.87 MW | 0.87 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 4.61 MW | 4.61 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.12 MW | 1.12 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.27 MW | 0.27 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.29 MW | 1.29 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.28 MW | 0.28 MW |
| KEYSTONE-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o APS-P2-3-WP-500-DRT26 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.1 MW | 0.1 MW |
| Details for 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 961971 | AG1-040 C | Adder | 1.04 MW | 0.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 961972 | AG1-040 E | Adder | 0.69 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 961981 | AG1-041 C | Adder | 1.24 MW | 1.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 961982 | AG1-041 E | Adder | 0.82 MW | 0.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 962411 | AG1-090 C O1 | Adder | 10.06 MW | 8.55 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 962412 | AG1-090 E O1 | Adder | 2.52 MW | 2.14 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 962511 | AG1-100 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 962512 | AG1-100 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 962911 | AG1-140 C | Adder | 0.15 MW | 0.13 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 962912 | AG1-140 E | Adder | 0.08 MW | 0.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 963441 | AG1-193 C | Adder | 1.22 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 963442 | AG1-193 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 963481 | AG1-197 C | Adder | 0.79 MW | 0.67 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 963482 | AG1-197 E | Adder | 0.52 MW | 0.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 963491 | AG1-198 C | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 963492 | AG1-198 E | Adder | 0.42 MW | 0.35 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 963991 | AG1-253 C | Adder | 0.22 MW | 0.19 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 963992 | AG1-253 E | Adder | 0.11 MW | 0.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 964031 | AG1-257 C | Adder | 0.7 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 964032 | AG1-257 E | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 964201 | AG1-281 C | Adder | 1.92 MW | 1.64 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 964202 | AG1-281 E | Adder | 1.28 MW | 1.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 964391 | AG1-301 C | Adder | 1.47 MW | 1.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 964392 | AG1-301 E | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 964411 | AG1-303 C O1 | Adder | 2.45 MW | 2.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 964412 | AG1-303 E O1 | Adder | 1.64 MW | 1.39 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 966771 | AG1-548 C | Adder | 9.9 MW | 8.41 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 966772 | AG1-548 E | Adder | 3.01 MW | 2.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 966781 | AG1-549 C O1 | 50/50 | 37.22 MW | 37.22 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 966782 | AG1-549 E O1 | 50/50 | 6.57 MW | 6.57 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965121 | AG1-377 C O1 | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965122 | AG1-377 E O1 | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965131 | AG1-378 C O1 | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965132 | AG1-378 E O1 | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965171 | AG1-382 C | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965172 | AG1-382 E | Adder | 1.36 MW | 1.16 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965241 | AG1-392C C O | Adder | 1.53 MW | 1.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965242 | AG1-392C E O | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965251 | AG1-392B C O | Adder | 1.53 MW | 1.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965252 | AG1-392B E O | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965261 | AG1-392A C O | Adder | 3.06 MW | 2.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965262 | AG1-392A E O | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965271 | AG1-392 C O1 | Adder | 3.06 MW | 2.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965272 | AG1-392 E O1 | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 965861 | AG1-455 | Adder | 2.74 MW | 2.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 290086 | Q-036 E | Adder | 5.65 MW | 4.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 296332 | R-032 E | 50/50 | 10.62 MW | 10.62 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 913142 | Y1-033 E OP1 | Adder | 3.51 MW | 2.98 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 936991 | AD2-133 C | Adder | 2.13 MW | 1.81 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 936992 | AD2-133 E | Adder | 9.74 MW | 8.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942121 | AE2-224 C | Adder | 10.18 MW | 8.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942122 | AE2-224 E | Adder | 6.79 MW | 5.77 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942351 | AE2-248 C | Adder | 0.8 MW | 0.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942361 | AE2-249 C | Adder | 1.72 MW | 1.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942362 | AE2-249 E | Adder | 1.15 MW | 0.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942491 | AE2-262 C | Adder | 4.58 MW | 3.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942492 | AE2-262 E | Adder | 3.07 MW | 2.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942501 | AE2-263 C | Adder | 4.3 MW | 3.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942502 | AE2-263 E | Adder | 2.87 MW | 2.44 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942811 | AE2-299 C | Adder | 2.64 MW | 2.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942812 | AE2-299 E | Adder | 10.56 MW | 8.98 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942961 | AE2-316 C | Adder | 4.3 MW | 3.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 942962 | AE2-316 E | Adder | 5.1 MW | 4.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 943151 | AE2-344 C | Adder | 5.71 MW | 4.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 943152 | AE2-344 E | Adder | 3.81 MW | 3.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 943351 | AF1-006 C | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 943352 | AF1-006 E | Adder | 0.55 MW | 0.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 943711 | AF1-039 C O1 | Adder | 0.93 MW | 0.79 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 943712 | AF1-039 E O1 | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944181 | AF1-086 C O1 | Adder | 3.25 MW | 2.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944182 | AF1-086 E O1 | Adder | 14.13 MW | 12.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944261 | AF1-094 C | Adder | 1.04 MW | 0.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944262 | AF1-094 E | Adder | 0.7 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944301 | AF1-098 C | Adder | 4.06 MW | 3.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944302 | AF1-098 E | Adder | 2.71 MW | 2.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944311 | AF1-099 C | Adder | 7.14 MW | 6.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944312 | AF1-099 E | Adder | 4.76 MW | 4.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944321 | AF1-100 C | Adder | 14.77 MW | 12.55 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944322 | AF1-100 E | Adder | 9.85 MW | 8.37 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944411 | AF1-106 O1 | Adder | 2.05 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944472 | AF1-112 E | Adder | 0.51 MW | 0.43 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944691 | AF1-134 C | Adder | 1.67 MW | 1.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944692 | AF1-134 E | Adder | 1.11 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944751 | AF1-140 C | Adder | 1.66 MW | 1.41 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944752 | AF1-140 E | Adder | 1.11 MW | 0.94 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944771 | AF1-142 C | Adder | 11.43 MW | 9.72 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944772 | AF1-142 E | Adder | 7.62 MW | 6.48 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944781 | AF1-143 C | Adder | 8.19 MW | 6.96 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944782 | AF1-143 E | Adder | 4.37 MW | 3.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 945021 | AF1-167 C | Adder | 0.79 MW | 0.67 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 945022 | AF1-167 E | Adder | 0.53 MW | 0.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 945051 | AF1-170 C | Adder | 3.64 MW | 3.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 945052 | AF1-170 E | Adder | 2.43 MW | 2.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 945451 | AF1-210 C | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 945452 | AF1-210 E | Adder | 0.58 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 945751 | AF1-240 C O1 | Adder | 1.68 MW | 1.43 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 945752 | AF1-240 E O1 | Adder | 1.12 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 958471 | AF2-141 | Adder | 1.09 MW | 0.93 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 958731 | AF2-164 C O1 | Adder | 5.72 MW | 4.86 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 958732 | AF2-164 E O1 | Adder | 3.81 MW | 3.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 958741 | AF2-165 C | Adder | 1.25 MW | 1.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 958742 | AF2-165 E | Adder | 0.84 MW | 0.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 958751 | AF2-166 C | Adder | 1.3 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 958752 | AF2-166 E | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 959441 | AF2-235 C | Adder | 0.59 MW | 0.5 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 959442 | AF2-235 E | Adder | 0.39 MW | 0.34 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 959471 | AF2-238 C | Adder | 1.26 MW | 1.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 959472 | AF2-238 E | Adder | 0.84 MW | 0.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 959521 | AF2-243 C | Adder | 0.94 MW | 0.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 959522 | AF2-243 E | Adder | 0.63 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 959802 | AF2-271 E | Adder | 0.38 MW | 0.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960022 | AF2-293 E | Adder | 0.1 MW | 0.08 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960031 | AF2-294 C | Adder | 0.96 MW | 0.81 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960032 | AF2-294 E | Adder | 0.64 MW | 0.54 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960051 | AF2-296 C | Adder | 1.67 MW | 1.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960052 | AF2-296 E | Adder | 1.11 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960451 | AF2-336 C | Adder | 2.07 MW | 1.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960452 | AF2-336 E | Adder | 1.38 MW | 1.17 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960461 | AF2-337 C | Adder | 2.07 MW | 1.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960462 | AF2-337 E | Adder | 1.38 MW | 1.17 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 961141 | AF2-405 | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 961151 | AF2-406 | Adder | 7.68 MW | 6.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 961211 | AF2-412 | Adder | 15.67 MW | 13.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 961451 | AF2-436 | Adder | 0.11 MW | 0.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200636 | 26IUP CO-G | 50/50 | 0.49 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200794 | 26CONEMAGH | 50/50 | 0.33 MW | 0.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200809 | 26SITHE | 50/50 | 1.54 MW | 1.54 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200835 | 26ARN_Z1-066 | Adder | 1.09 MW | 0.93 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200837 | 26HOMER C1 | 50/50 | 26.57 MW | 26.57 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200838 | 26HOMER C2 | 50/50 | 22.01 MW | 22.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200839 | 26HOMER C3 | 50/50 | 23.3 MW | 23.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200846 | 26FORWARD | 50/50 | 0.1 MW | 0.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200852 | 26WARR RDG | Adder | 0.31 MW | 0.26 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200864 | K-013 E | 50/50 | 4.23 MW | 4.23 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200883 | Q-053 E | Adder | 5.08 MW | 4.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200888 | 26HIGHLAND | 50/50 | 0.24 MW | 0.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200894 | 26K02 | Adder | 4.95 MW | 4.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200925 | 26R32 | 50/50 | 0.38 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 203915 | 26BF_Z2-108 | Adder | 2.46 MW | 2.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 203932 | AA2-133 GEN | Adder | 1.5 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 203999 | P-047 E | Adder | 8.92 MW | 7.58 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 235003 | AC1-025 E | Adder | 0.12 MW | 0.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 292350 | K-023 | Adder | 3.4 MW | 2.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 292542 | L-013 1 | Adder | 4.37 MW | 3.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 293301 | N-039 E | Adder | 10.36 MW | 8.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 293393 | V3-030E | Adder | 4.72 MW | 4.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 293603 | O-018 E | 50/50 | 9.21 MW | 9.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 293902 | O-048 E | Adder | 3.93 MW | 3.34 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 294515 | O38_P22 | Adder | 9.06 MW | 7.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 294903 | P-060 E | Adder | 7.04 MW | 5.99 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 916202 | Z1-069 E | Adder | 7.19 MW | 6.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 931092 | AB1-160 E | Adder | 2.05 MW | 1.75 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 938951 | AE1-123 | Adder | 2.02 MW | 1.72 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 939291 | AE1-160 C | Adder | 1.25 MW | 1.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 939292 | AE1-160 E | Adder | 0.72 MW | 0.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 940201 | AE2-001 C | Adder | 1.02 MW | 0.86 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 940202 | AE2-001 E | Adder | 0.68 MW | 0.58 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 940681 | AE2-055 C | Adder | 0.99 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 940682 | AE2-055 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 940861 | AE2-074 C | Adder | 1.97 MW | 1.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 940862 | AE2-074 E | Adder | 2.59 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941191 | AE2-113 C | Adder | 7.64 MW | 6.5 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941192 | AE2-113 E | Adder | 7.18 MW | 6.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941231 | AE2-117 C | Adder | 1.49 MW | 1.26 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941232 | AE2-117 E | Adder | 0.99 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941241 | AE2-118 C | Adder | 1.56 MW | 1.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941242 | AE2-118 E | Adder | 1.04 MW | 0.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941271 | AE2-121 C | Adder | 0.54 MW | 0.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941272 | AE2-121 E | Adder | 0.36 MW | 0.31 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941331 | AE2-129 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941332 | AE2-129 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941351 | AE2-131 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941352 | AE2-131 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941421 | AE2-139 C | Adder | 5.07 MW | 4.31 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 941422 | AE2-139 E | Adder | 3.38 MW | 2.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946071 | AF1-272 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946072 | AF1-272 E O1 | 50/50 | 10.45 MW | 10.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946111 | AF1-276 C | Adder | 8.81 MW | 7.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946112 | AF1-276 E | Adder | 4.34 MW | 3.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946121 | AF1-277 C | Adder | 8.81 MW | 7.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946122 | AF1-277 E | Adder | 4.34 MW | 3.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946131 | AF1-278 C | Adder | 7.02 MW | 5.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946132 | AF1-278 E | Adder | 3.49 MW | 2.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946221 | AF1-287 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946222 | AF1-287 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946381 | AF1-302 C | Adder | 1.88 MW | 1.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946382 | AF1-302 E | Adder | 2.51 MW | 2.13 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946571 | AF1-321 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946572 | AF1-321 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946771 | AF1-217 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946772 | AF1-217 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957001 | AF2-001 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957002 | AF2-001 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957011 | AF2-002 C O1 | 50/50 | 1.11 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957012 | AF2-002 E O1 | 50/50 | 0.74 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957161 | AF2-010 C | Adder | 4.02 MW | 3.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957162 | AF2-010 E | Adder | 2.71 MW | 2.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957451 | AF2-039 C | Adder | 0.92 MW | 0.79 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957452 | AF2-039 E | Adder | 0.62 MW | 0.52 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957561 | AF2-050 C | Adder | 5.09 MW | 4.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957562 | AF2-050 E | Adder | 3.39 MW | 2.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957931 | AF2-087 C | Adder | 0.45 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957932 | AF2-087 E | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957941 | AF2-088 C | Adder | 0.44 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957942 | AF2-088 E | Adder | 0.3 MW | 0.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957981 | AF2-092 C | Adder | 1.24 MW | 1.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 957982 | AF2-092 E | Adder | 0.83 MW | 0.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 958271 | AF2-121 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 958272 | AF2-121 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 958361 | AF2-130 C | Adder | 1.3 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 958362 | AF2-130 E | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200833 | 26SEWRDB34 | 50/50 | 16.03 MW | 16.03 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 200906 | 26KEYSTN#3 | 50/50 | 0.82 MW | 0.82 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 959301 | AF2-221 C | 50/50 | 1.15 MW | 1.15 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 959302 | AF2-221 E | 50/50 | 1.59 MW | 1.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 292340 | 26SW_E13_K22 | Adder | 1.18 MW | 1.0 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 964451 | AG1-308 C O1 | Adder | 1.04 MW | 0.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 964452 | AG1-308 E O1 | Adder | 1.46 MW | 1.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960901 | AG1-000C C | 50/50 | 7.22 MW | 7.22 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 960902 | AG1-000C E | 50/50 | 3.56 MW | 3.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946421 | AF2-000A C | Adder | 5.08 MW | 4.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | 946422 | AF2-000A E | Adder | 15.24 MW | 12.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.49 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.47 MW | 0.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.87 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 4.61 MW | 4.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.12 MW | 1.12 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.27 MW | 0.27 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.29 MW | 1.29 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-003 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.1 MW | 0.1 MW |
| Details for 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 961971 | AG1-040 C | Adder | 1.04 MW | 0.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 961972 | AG1-040 E | Adder | 0.69 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 961981 | AG1-041 C | Adder | 1.24 MW | 1.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 961982 | AG1-041 E | Adder | 0.82 MW | 0.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 962411 | AG1-090 C O1 | Adder | 10.06 MW | 8.55 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 962412 | AG1-090 E O1 | Adder | 2.52 MW | 2.14 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 962511 | AG1-100 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 962512 | AG1-100 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 962911 | AG1-140 C | Adder | 0.15 MW | 0.13 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 962912 | AG1-140 E | Adder | 0.08 MW | 0.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 963441 | AG1-193 C | Adder | 1.22 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 963442 | AG1-193 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 963481 | AG1-197 C | Adder | 0.79 MW | 0.67 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 963482 | AG1-197 E | Adder | 0.52 MW | 0.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 963491 | AG1-198 C | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 963492 | AG1-198 E | Adder | 0.42 MW | 0.35 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 963991 | AG1-253 C | Adder | 0.22 MW | 0.19 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 963992 | AG1-253 E | Adder | 0.11 MW | 0.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 964031 | AG1-257 C | Adder | 0.7 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 964032 | AG1-257 E | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 964201 | AG1-281 C | Adder | 1.92 MW | 1.64 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 964202 | AG1-281 E | Adder | 1.28 MW | 1.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 964391 | AG1-301 C | Adder | 1.47 MW | 1.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 964392 | AG1-301 E | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 964411 | AG1-303 C O1 | Adder | 2.45 MW | 2.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 964412 | AG1-303 E O1 | Adder | 1.64 MW | 1.39 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 966771 | AG1-548 C | Adder | 9.9 MW | 8.41 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 966772 | AG1-548 E | Adder | 3.01 MW | 2.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 966781 | AG1-549 C O1 | 50/50 | 37.22 MW | 37.22 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 966782 | AG1-549 E O1 | 50/50 | 6.57 MW | 6.57 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965121 | AG1-377 C O1 | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965122 | AG1-377 E O1 | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965131 | AG1-378 C O1 | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965132 | AG1-378 E O1 | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965171 | AG1-382 C | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965172 | AG1-382 E | Adder | 1.36 MW | 1.16 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965241 | AG1-392C C O | Adder | 1.53 MW | 1.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965242 | AG1-392C E O | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965251 | AG1-392B C O | Adder | 1.53 MW | 1.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965252 | AG1-392B E O | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965261 | AG1-392A C O | Adder | 3.06 MW | 2.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965262 | AG1-392A E O | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965271 | AG1-392 C O1 | Adder | 3.06 MW | 2.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965272 | AG1-392 E O1 | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 965861 | AG1-455 | Adder | 2.74 MW | 2.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 290086 | Q-036 E | Adder | 5.65 MW | 4.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 296332 | R-032 E | 50/50 | 10.62 MW | 10.62 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 913142 | Y1-033 E OP1 | Adder | 3.51 MW | 2.98 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 936991 | AD2-133 C | Adder | 2.13 MW | 1.81 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 936992 | AD2-133 E | Adder | 9.74 MW | 8.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942121 | AE2-224 C | Adder | 10.18 MW | 8.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942122 | AE2-224 E | Adder | 6.79 MW | 5.77 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942351 | AE2-248 C | Adder | 0.8 MW | 0.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942361 | AE2-249 C | Adder | 1.72 MW | 1.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942362 | AE2-249 E | Adder | 1.15 MW | 0.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942491 | AE2-262 C | Adder | 4.58 MW | 3.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942492 | AE2-262 E | Adder | 3.07 MW | 2.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942501 | AE2-263 C | Adder | 4.3 MW | 3.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942502 | AE2-263 E | Adder | 2.87 MW | 2.44 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942811 | AE2-299 C | Adder | 2.64 MW | 2.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942812 | AE2-299 E | Adder | 10.56 MW | 8.98 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942961 | AE2-316 C | Adder | 4.3 MW | 3.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 942962 | AE2-316 E | Adder | 5.1 MW | 4.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 943151 | AE2-344 C | Adder | 5.71 MW | 4.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 943152 | AE2-344 E | Adder | 3.81 MW | 3.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 943351 | AF1-006 C | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 943352 | AF1-006 E | Adder | 0.55 MW | 0.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 943711 | AF1-039 C O1 | Adder | 0.93 MW | 0.79 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 943712 | AF1-039 E O1 | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944181 | AF1-086 C O1 | Adder | 3.25 MW | 2.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944182 | AF1-086 E O1 | Adder | 14.13 MW | 12.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944261 | AF1-094 C | Adder | 1.04 MW | 0.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944262 | AF1-094 E | Adder | 0.7 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944301 | AF1-098 C | Adder | 4.06 MW | 3.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944302 | AF1-098 E | Adder | 2.71 MW | 2.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944311 | AF1-099 C | Adder | 7.14 MW | 6.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944312 | AF1-099 E | Adder | 4.76 MW | 4.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944321 | AF1-100 C | Adder | 14.77 MW | 12.55 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944322 | AF1-100 E | Adder | 9.85 MW | 8.37 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944411 | AF1-106 O1 | Adder | 2.05 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944472 | AF1-112 E | Adder | 0.51 MW | 0.43 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944691 | AF1-134 C | Adder | 1.67 MW | 1.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944692 | AF1-134 E | Adder | 1.11 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944751 | AF1-140 C | Adder | 1.66 MW | 1.41 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944752 | AF1-140 E | Adder | 1.11 MW | 0.94 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944771 | AF1-142 C | Adder | 11.43 MW | 9.72 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944772 | AF1-142 E | Adder | 7.62 MW | 6.48 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944781 | AF1-143 C | Adder | 8.19 MW | 6.96 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944782 | AF1-143 E | Adder | 4.37 MW | 3.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 945021 | AF1-167 C | Adder | 0.79 MW | 0.67 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 945022 | AF1-167 E | Adder | 0.53 MW | 0.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 945051 | AF1-170 C | Adder | 3.64 MW | 3.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 945052 | AF1-170 E | Adder | 2.43 MW | 2.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 945451 | AF1-210 C | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 945452 | AF1-210 E | Adder | 0.58 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 945751 | AF1-240 C O1 | Adder | 1.68 MW | 1.43 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 945752 | AF1-240 E O1 | Adder | 1.12 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 958471 | AF2-141 | Adder | 1.09 MW | 0.93 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 958731 | AF2-164 C O1 | Adder | 5.72 MW | 4.86 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 958732 | AF2-164 E O1 | Adder | 3.81 MW | 3.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 958741 | AF2-165 C | Adder | 1.25 MW | 1.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 958742 | AF2-165 E | Adder | 0.84 MW | 0.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 958751 | AF2-166 C | Adder | 1.3 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 958752 | AF2-166 E | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 959441 | AF2-235 C | Adder | 0.59 MW | 0.5 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 959442 | AF2-235 E | Adder | 0.39 MW | 0.34 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 959471 | AF2-238 C | Adder | 1.26 MW | 1.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 959472 | AF2-238 E | Adder | 0.84 MW | 0.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 959521 | AF2-243 C | Adder | 0.94 MW | 0.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 959522 | AF2-243 E | Adder | 0.63 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 959802 | AF2-271 E | Adder | 0.38 MW | 0.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960022 | AF2-293 E | Adder | 0.1 MW | 0.08 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960031 | AF2-294 C | Adder | 0.96 MW | 0.81 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960032 | AF2-294 E | Adder | 0.64 MW | 0.54 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960051 | AF2-296 C | Adder | 1.67 MW | 1.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960052 | AF2-296 E | Adder | 1.11 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960451 | AF2-336 C | Adder | 2.07 MW | 1.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960452 | AF2-336 E | Adder | 1.38 MW | 1.17 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960461 | AF2-337 C | Adder | 2.07 MW | 1.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960462 | AF2-337 E | Adder | 1.38 MW | 1.17 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 961141 | AF2-405 | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 961151 | AF2-406 | Adder | 7.68 MW | 6.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 961211 | AF2-412 | Adder | 15.67 MW | 13.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 961451 | AF2-436 | Adder | 0.11 MW | 0.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200636 | 26IUP CO-G | 50/50 | 0.49 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200794 | 26CONEMAGH | 50/50 | 0.33 MW | 0.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200809 | 26SITHE | 50/50 | 1.54 MW | 1.54 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200835 | 26ARN_Z1-066 | Adder | 1.09 MW | 0.93 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200837 | 26HOMER C1 | 50/50 | 26.57 MW | 26.57 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200838 | 26HOMER C2 | 50/50 | 22.01 MW | 22.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200839 | 26HOMER C3 | 50/50 | 23.3 MW | 23.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200846 | 26FORWARD | 50/50 | 0.1 MW | 0.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200852 | 26WARR RDG | Adder | 0.31 MW | 0.26 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200864 | K-013 E | 50/50 | 4.23 MW | 4.23 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200883 | Q-053 E | Adder | 5.08 MW | 4.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200888 | 26HIGHLAND | 50/50 | 0.24 MW | 0.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200894 | 26K02 | Adder | 4.95 MW | 4.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200925 | 26R32 | 50/50 | 0.38 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 203915 | 26BF_Z2-108 | Adder | 2.46 MW | 2.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 203932 | AA2-133 GEN | Adder | 1.5 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 203999 | P-047 E | Adder | 8.92 MW | 7.58 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 235003 | AC1-025 E | Adder | 0.12 MW | 0.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 292350 | K-023 | Adder | 3.4 MW | 2.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 292542 | L-013 1 | Adder | 4.37 MW | 3.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 293301 | N-039 E | Adder | 10.36 MW | 8.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 293393 | V3-030E | Adder | 4.72 MW | 4.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 293603 | O-018 E | 50/50 | 9.21 MW | 9.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 293902 | O-048 E | Adder | 3.93 MW | 3.34 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 294515 | O38_P22 | Adder | 9.06 MW | 7.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 294903 | P-060 E | Adder | 7.04 MW | 5.99 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 916202 | Z1-069 E | Adder | 7.19 MW | 6.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 931092 | AB1-160 E | Adder | 2.05 MW | 1.75 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 938951 | AE1-123 | Adder | 2.02 MW | 1.72 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 939291 | AE1-160 C | Adder | 1.25 MW | 1.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 939292 | AE1-160 E | Adder | 0.72 MW | 0.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 940201 | AE2-001 C | Adder | 1.02 MW | 0.86 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 940202 | AE2-001 E | Adder | 0.68 MW | 0.58 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 940681 | AE2-055 C | Adder | 0.99 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 940682 | AE2-055 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 940861 | AE2-074 C | Adder | 1.97 MW | 1.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 940862 | AE2-074 E | Adder | 2.59 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941191 | AE2-113 C | Adder | 7.64 MW | 6.5 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941192 | AE2-113 E | Adder | 7.18 MW | 6.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941231 | AE2-117 C | Adder | 1.49 MW | 1.26 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941232 | AE2-117 E | Adder | 0.99 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941241 | AE2-118 C | Adder | 1.56 MW | 1.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941242 | AE2-118 E | Adder | 1.04 MW | 0.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941271 | AE2-121 C | Adder | 0.54 MW | 0.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941272 | AE2-121 E | Adder | 0.36 MW | 0.31 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941331 | AE2-129 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941332 | AE2-129 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941351 | AE2-131 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941352 | AE2-131 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941421 | AE2-139 C | Adder | 5.07 MW | 4.31 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 941422 | AE2-139 E | Adder | 3.38 MW | 2.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946071 | AF1-272 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946072 | AF1-272 E O1 | 50/50 | 10.45 MW | 10.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946111 | AF1-276 C | Adder | 8.81 MW | 7.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946112 | AF1-276 E | Adder | 4.34 MW | 3.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946121 | AF1-277 C | Adder | 8.81 MW | 7.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946122 | AF1-277 E | Adder | 4.34 MW | 3.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946131 | AF1-278 C | Adder | 7.02 MW | 5.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946132 | AF1-278 E | Adder | 3.49 MW | 2.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946221 | AF1-287 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946222 | AF1-287 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946381 | AF1-302 C | Adder | 1.88 MW | 1.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946382 | AF1-302 E | Adder | 2.51 MW | 2.13 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946571 | AF1-321 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946572 | AF1-321 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946771 | AF1-217 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946772 | AF1-217 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957001 | AF2-001 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957002 | AF2-001 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957011 | AF2-002 C O1 | 50/50 | 1.11 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957012 | AF2-002 E O1 | 50/50 | 0.74 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957161 | AF2-010 C | Adder | 4.02 MW | 3.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957162 | AF2-010 E | Adder | 2.71 MW | 2.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957451 | AF2-039 C | Adder | 0.92 MW | 0.79 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957452 | AF2-039 E | Adder | 0.62 MW | 0.52 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957561 | AF2-050 C | Adder | 5.09 MW | 4.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957562 | AF2-050 E | Adder | 3.39 MW | 2.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957931 | AF2-087 C | Adder | 0.45 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957932 | AF2-087 E | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957941 | AF2-088 C | Adder | 0.44 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957942 | AF2-088 E | Adder | 0.3 MW | 0.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957981 | AF2-092 C | Adder | 1.24 MW | 1.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 957982 | AF2-092 E | Adder | 0.83 MW | 0.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 958271 | AF2-121 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 958272 | AF2-121 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 958361 | AF2-130 C | Adder | 1.3 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 958362 | AF2-130 E | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200833 | 26SEWRDB34 | 50/50 | 16.03 MW | 16.03 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 200906 | 26KEYSTN#3 | 50/50 | 0.82 MW | 0.82 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 959301 | AF2-221 C | 50/50 | 1.15 MW | 1.15 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 959302 | AF2-221 E | 50/50 | 1.59 MW | 1.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 292340 | 26SW_E13_K22 | Adder | 1.18 MW | 1.0 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 964451 | AG1-308 C O1 | Adder | 1.04 MW | 0.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 964452 | AG1-308 E O1 | Adder | 1.46 MW | 1.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960901 | AG1-000C C | 50/50 | 7.22 MW | 7.22 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 960902 | AG1-000C E | 50/50 | 3.56 MW | 3.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946421 | AF2-000A C | Adder | 5.08 MW | 4.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | 946422 | AF2-000A E | Adder | 15.24 MW | 12.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.49 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.47 MW | 0.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.87 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 4.61 MW | 4.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.12 MW | 1.12 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.27 MW | 0.27 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.29 MW | 1.29 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o PN-P2-3-PN-500-004-DRT-004 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.1 MW | 0.1 MW |
| Details for 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 961971 | AG1-040 C | Adder | 1.04 MW | 0.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 961972 | AG1-040 E | Adder | 0.69 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 961981 | AG1-041 C | Adder | 1.24 MW | 1.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 961982 | AG1-041 E | Adder | 0.82 MW | 0.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 962411 | AG1-090 C O1 | Adder | 10.06 MW | 8.55 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 962412 | AG1-090 E O1 | Adder | 2.52 MW | 2.14 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 962511 | AG1-100 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 962512 | AG1-100 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 962911 | AG1-140 C | Adder | 0.15 MW | 0.13 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 962912 | AG1-140 E | Adder | 0.08 MW | 0.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 963441 | AG1-193 C | Adder | 1.22 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 963442 | AG1-193 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 963481 | AG1-197 C | Adder | 0.79 MW | 0.67 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 963482 | AG1-197 E | Adder | 0.52 MW | 0.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 963491 | AG1-198 C | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 963492 | AG1-198 E | Adder | 0.42 MW | 0.35 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 963991 | AG1-253 C | Adder | 0.22 MW | 0.19 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 963992 | AG1-253 E | Adder | 0.11 MW | 0.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 964031 | AG1-257 C | Adder | 0.7 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 964032 | AG1-257 E | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 964201 | AG1-281 C | Adder | 1.92 MW | 1.64 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 964202 | AG1-281 E | Adder | 1.28 MW | 1.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 964391 | AG1-301 C | Adder | 1.47 MW | 1.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 964392 | AG1-301 E | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 964411 | AG1-303 C O1 | Adder | 2.45 MW | 2.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 964412 | AG1-303 E O1 | Adder | 1.64 MW | 1.39 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 966771 | AG1-548 C | Adder | 9.9 MW | 8.41 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 966772 | AG1-548 E | Adder | 3.01 MW | 2.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 966781 | AG1-549 C O1 | 50/50 | 37.22 MW | 37.22 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 966782 | AG1-549 E O1 | 50/50 | 6.57 MW | 6.57 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965121 | AG1-377 C O1 | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965122 | AG1-377 E O1 | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965131 | AG1-378 C O1 | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965132 | AG1-378 E O1 | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965171 | AG1-382 C | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965172 | AG1-382 E | Adder | 1.36 MW | 1.16 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965241 | AG1-392C C O | Adder | 1.53 MW | 1.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965242 | AG1-392C E O | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965251 | AG1-392B C O | Adder | 1.53 MW | 1.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965252 | AG1-392B E O | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965261 | AG1-392A C O | Adder | 3.06 MW | 2.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965262 | AG1-392A E O | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965271 | AG1-392 C O1 | Adder | 3.06 MW | 2.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965272 | AG1-392 E O1 | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 965861 | AG1-455 | Adder | 2.74 MW | 2.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 290086 | Q-036 E | Adder | 5.65 MW | 4.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 296332 | R-032 E | 50/50 | 10.62 MW | 10.62 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 913142 | Y1-033 E OP1 | Adder | 3.51 MW | 2.98 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 936991 | AD2-133 C | Adder | 2.13 MW | 1.81 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 936992 | AD2-133 E | Adder | 9.74 MW | 8.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942121 | AE2-224 C | Adder | 10.18 MW | 8.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942122 | AE2-224 E | Adder | 6.79 MW | 5.77 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942351 | AE2-248 C | Adder | 0.8 MW | 0.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942361 | AE2-249 C | Adder | 1.72 MW | 1.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942362 | AE2-249 E | Adder | 1.15 MW | 0.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942491 | AE2-262 C | Adder | 4.58 MW | 3.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942492 | AE2-262 E | Adder | 3.07 MW | 2.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942501 | AE2-263 C | Adder | 4.3 MW | 3.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942502 | AE2-263 E | Adder | 2.87 MW | 2.44 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942811 | AE2-299 C | Adder | 2.64 MW | 2.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942812 | AE2-299 E | Adder | 10.56 MW | 8.98 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942961 | AE2-316 C | Adder | 4.3 MW | 3.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 942962 | AE2-316 E | Adder | 5.1 MW | 4.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 943151 | AE2-344 C | Adder | 5.71 MW | 4.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 943152 | AE2-344 E | Adder | 3.81 MW | 3.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 943351 | AF1-006 C | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 943352 | AF1-006 E | Adder | 0.55 MW | 0.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 943711 | AF1-039 C O1 | Adder | 0.93 MW | 0.79 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 943712 | AF1-039 E O1 | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944181 | AF1-086 C O1 | Adder | 3.25 MW | 2.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944182 | AF1-086 E O1 | Adder | 14.13 MW | 12.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944261 | AF1-094 C | Adder | 1.04 MW | 0.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944262 | AF1-094 E | Adder | 0.7 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944301 | AF1-098 C | Adder | 4.06 MW | 3.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944302 | AF1-098 E | Adder | 2.71 MW | 2.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944311 | AF1-099 C | Adder | 7.14 MW | 6.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944312 | AF1-099 E | Adder | 4.76 MW | 4.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944321 | AF1-100 C | Adder | 14.77 MW | 12.55 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944322 | AF1-100 E | Adder | 9.85 MW | 8.37 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944411 | AF1-106 O1 | Adder | 2.05 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944472 | AF1-112 E | Adder | 0.51 MW | 0.43 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944691 | AF1-134 C | Adder | 1.67 MW | 1.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944692 | AF1-134 E | Adder | 1.11 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944751 | AF1-140 C | Adder | 1.66 MW | 1.41 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944752 | AF1-140 E | Adder | 1.11 MW | 0.94 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944771 | AF1-142 C | Adder | 11.43 MW | 9.72 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944772 | AF1-142 E | Adder | 7.62 MW | 6.48 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944781 | AF1-143 C | Adder | 8.19 MW | 6.96 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944782 | AF1-143 E | Adder | 4.37 MW | 3.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 945021 | AF1-167 C | Adder | 0.79 MW | 0.67 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 945022 | AF1-167 E | Adder | 0.53 MW | 0.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 945051 | AF1-170 C | Adder | 3.64 MW | 3.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 945052 | AF1-170 E | Adder | 2.43 MW | 2.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 945451 | AF1-210 C | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 945452 | AF1-210 E | Adder | 0.58 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 945751 | AF1-240 C O1 | Adder | 1.68 MW | 1.43 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 945752 | AF1-240 E O1 | Adder | 1.12 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 958471 | AF2-141 | Adder | 1.09 MW | 0.93 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 958731 | AF2-164 C O1 | Adder | 5.72 MW | 4.86 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 958732 | AF2-164 E O1 | Adder | 3.81 MW | 3.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 958741 | AF2-165 C | Adder | 1.25 MW | 1.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 958742 | AF2-165 E | Adder | 0.84 MW | 0.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 958751 | AF2-166 C | Adder | 1.3 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 958752 | AF2-166 E | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 959441 | AF2-235 C | Adder | 0.59 MW | 0.5 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 959442 | AF2-235 E | Adder | 0.39 MW | 0.34 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 959471 | AF2-238 C | Adder | 1.26 MW | 1.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 959472 | AF2-238 E | Adder | 0.84 MW | 0.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 959521 | AF2-243 C | Adder | 0.94 MW | 0.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 959522 | AF2-243 E | Adder | 0.63 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 959802 | AF2-271 E | Adder | 0.38 MW | 0.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960022 | AF2-293 E | Adder | 0.1 MW | 0.08 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960031 | AF2-294 C | Adder | 0.96 MW | 0.81 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960032 | AF2-294 E | Adder | 0.64 MW | 0.54 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960051 | AF2-296 C | Adder | 1.67 MW | 1.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960052 | AF2-296 E | Adder | 1.11 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960451 | AF2-336 C | Adder | 2.07 MW | 1.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960452 | AF2-336 E | Adder | 1.38 MW | 1.17 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960461 | AF2-337 C | Adder | 2.07 MW | 1.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960462 | AF2-337 E | Adder | 1.38 MW | 1.17 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 961141 | AF2-405 | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 961151 | AF2-406 | Adder | 7.68 MW | 6.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 961211 | AF2-412 | Adder | 15.67 MW | 13.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 961451 | AF2-436 | Adder | 0.11 MW | 0.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200636 | 26IUP CO-G | 50/50 | 0.49 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200794 | 26CONEMAGH | 50/50 | 0.33 MW | 0.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200809 | 26SITHE | 50/50 | 1.54 MW | 1.54 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200835 | 26ARN_Z1-066 | Adder | 1.09 MW | 0.93 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200837 | 26HOMER C1 | 50/50 | 26.57 MW | 26.57 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200838 | 26HOMER C2 | 50/50 | 22.01 MW | 22.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200839 | 26HOMER C3 | 50/50 | 23.3 MW | 23.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200846 | 26FORWARD | 50/50 | 0.1 MW | 0.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200852 | 26WARR RDG | Adder | 0.31 MW | 0.26 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200864 | K-013 E | 50/50 | 4.23 MW | 4.23 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200883 | Q-053 E | Adder | 5.08 MW | 4.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200888 | 26HIGHLAND | 50/50 | 0.24 MW | 0.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200894 | 26K02 | Adder | 4.95 MW | 4.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200925 | 26R32 | 50/50 | 0.38 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 203915 | 26BF_Z2-108 | Adder | 2.46 MW | 2.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 203932 | AA2-133 GEN | Adder | 1.5 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 203999 | P-047 E | Adder | 8.92 MW | 7.58 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 235003 | AC1-025 E | Adder | 0.12 MW | 0.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 292350 | K-023 | Adder | 3.4 MW | 2.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 292542 | L-013 1 | Adder | 4.37 MW | 3.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 293301 | N-039 E | Adder | 10.36 MW | 8.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 293393 | V3-030E | Adder | 4.72 MW | 4.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 293603 | O-018 E | 50/50 | 9.21 MW | 9.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 293902 | O-048 E | Adder | 3.93 MW | 3.34 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 294515 | O38_P22 | Adder | 9.06 MW | 7.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 294903 | P-060 E | Adder | 7.04 MW | 5.99 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 916202 | Z1-069 E | Adder | 7.19 MW | 6.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 931092 | AB1-160 E | Adder | 2.05 MW | 1.75 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 938951 | AE1-123 | Adder | 2.02 MW | 1.72 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 939291 | AE1-160 C | Adder | 1.25 MW | 1.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 939292 | AE1-160 E | Adder | 0.72 MW | 0.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 940201 | AE2-001 C | Adder | 1.02 MW | 0.86 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 940202 | AE2-001 E | Adder | 0.68 MW | 0.58 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 940681 | AE2-055 C | Adder | 0.99 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 940682 | AE2-055 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 940861 | AE2-074 C | Adder | 1.97 MW | 1.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 940862 | AE2-074 E | Adder | 2.59 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941191 | AE2-113 C | Adder | 7.64 MW | 6.5 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941192 | AE2-113 E | Adder | 7.18 MW | 6.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941231 | AE2-117 C | Adder | 1.49 MW | 1.26 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941232 | AE2-117 E | Adder | 0.99 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941241 | AE2-118 C | Adder | 1.56 MW | 1.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941242 | AE2-118 E | Adder | 1.04 MW | 0.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941271 | AE2-121 C | Adder | 0.54 MW | 0.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941272 | AE2-121 E | Adder | 0.36 MW | 0.31 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941331 | AE2-129 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941332 | AE2-129 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941351 | AE2-131 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941352 | AE2-131 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941421 | AE2-139 C | Adder | 5.07 MW | 4.31 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 941422 | AE2-139 E | Adder | 3.38 MW | 2.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946071 | AF1-272 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946072 | AF1-272 E O1 | 50/50 | 10.45 MW | 10.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946111 | AF1-276 C | Adder | 8.81 MW | 7.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946112 | AF1-276 E | Adder | 4.34 MW | 3.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946121 | AF1-277 C | Adder | 8.81 MW | 7.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946122 | AF1-277 E | Adder | 4.34 MW | 3.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946131 | AF1-278 C | Adder | 7.02 MW | 5.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946132 | AF1-278 E | Adder | 3.49 MW | 2.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946221 | AF1-287 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946222 | AF1-287 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946381 | AF1-302 C | Adder | 1.88 MW | 1.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946382 | AF1-302 E | Adder | 2.51 MW | 2.13 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946571 | AF1-321 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946572 | AF1-321 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946771 | AF1-217 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946772 | AF1-217 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957001 | AF2-001 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957002 | AF2-001 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957011 | AF2-002 C O1 | 50/50 | 1.11 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957012 | AF2-002 E O1 | 50/50 | 0.74 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957161 | AF2-010 C | Adder | 4.02 MW | 3.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957162 | AF2-010 E | Adder | 2.71 MW | 2.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957451 | AF2-039 C | Adder | 0.92 MW | 0.79 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957452 | AF2-039 E | Adder | 0.62 MW | 0.52 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957561 | AF2-050 C | Adder | 5.09 MW | 4.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957562 | AF2-050 E | Adder | 3.39 MW | 2.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957931 | AF2-087 C | Adder | 0.45 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957932 | AF2-087 E | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957941 | AF2-088 C | Adder | 0.44 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957942 | AF2-088 E | Adder | 0.3 MW | 0.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957981 | AF2-092 C | Adder | 1.24 MW | 1.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 957982 | AF2-092 E | Adder | 0.83 MW | 0.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 958271 | AF2-121 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 958272 | AF2-121 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 958361 | AF2-130 C | Adder | 1.3 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 958362 | AF2-130 E | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200833 | 26SEWRDB34 | 50/50 | 16.03 MW | 16.03 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 200906 | 26KEYSTN#3 | 50/50 | 0.82 MW | 0.82 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 959301 | AF2-221 C | 50/50 | 1.15 MW | 1.15 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 959302 | AF2-221 E | 50/50 | 1.59 MW | 1.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 292340 | 26SW_E13_K22 | Adder | 1.18 MW | 1.0 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 964451 | AG1-308 C O1 | Adder | 1.04 MW | 0.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 964452 | AG1-308 E O1 | Adder | 1.46 MW | 1.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960901 | AG1-000C C | 50/50 | 7.22 MW | 7.22 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 960902 | AG1-000C E | 50/50 | 3.56 MW | 3.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946421 | AF2-000A C | Adder | 5.08 MW | 4.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | 946422 | AF2-000A E | Adder | 15.24 MW | 12.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.49 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.47 MW | 0.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.87 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 4.61 MW | 4.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.12 MW | 1.12 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.27 MW | 0.27 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.29 MW | 1.29 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT27 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.1 MW | 0.1 MW |
| Details for 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 961971 | AG1-040 C | Adder | 1.04 MW | 0.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 961972 | AG1-040 E | Adder | 0.69 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 961981 | AG1-041 C | Adder | 1.24 MW | 1.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 961982 | AG1-041 E | Adder | 0.82 MW | 0.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 962411 | AG1-090 C O1 | Adder | 10.06 MW | 8.55 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 962412 | AG1-090 E O1 | Adder | 2.52 MW | 2.14 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 962511 | AG1-100 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 962512 | AG1-100 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 962911 | AG1-140 C | Adder | 0.15 MW | 0.13 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 962912 | AG1-140 E | Adder | 0.08 MW | 0.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 963441 | AG1-193 C | Adder | 1.22 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 963442 | AG1-193 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 963481 | AG1-197 C | Adder | 0.79 MW | 0.67 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 963482 | AG1-197 E | Adder | 0.52 MW | 0.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 963491 | AG1-198 C | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 963492 | AG1-198 E | Adder | 0.42 MW | 0.35 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 963991 | AG1-253 C | Adder | 0.22 MW | 0.19 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 963992 | AG1-253 E | Adder | 0.11 MW | 0.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 964031 | AG1-257 C | Adder | 0.7 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 964032 | AG1-257 E | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 964201 | AG1-281 C | Adder | 1.92 MW | 1.64 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 964202 | AG1-281 E | Adder | 1.28 MW | 1.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 964391 | AG1-301 C | Adder | 1.47 MW | 1.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 964392 | AG1-301 E | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 964411 | AG1-303 C O1 | Adder | 2.45 MW | 2.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 964412 | AG1-303 E O1 | Adder | 1.64 MW | 1.39 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 966771 | AG1-548 C | Adder | 9.9 MW | 8.41 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 966772 | AG1-548 E | Adder | 3.01 MW | 2.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 966781 | AG1-549 C O1 | 50/50 | 37.22 MW | 37.22 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 966782 | AG1-549 E O1 | 50/50 | 6.57 MW | 6.57 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965121 | AG1-377 C O1 | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965122 | AG1-377 E O1 | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965131 | AG1-378 C O1 | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965132 | AG1-378 E O1 | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965171 | AG1-382 C | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965172 | AG1-382 E | Adder | 1.36 MW | 1.16 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965241 | AG1-392C C O | Adder | 1.53 MW | 1.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965242 | AG1-392C E O | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965251 | AG1-392B C O | Adder | 1.53 MW | 1.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965252 | AG1-392B E O | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965261 | AG1-392A C O | Adder | 3.06 MW | 2.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965262 | AG1-392A E O | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965271 | AG1-392 C O1 | Adder | 3.06 MW | 2.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965272 | AG1-392 E O1 | Adder | 2.04 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 965861 | AG1-455 | Adder | 2.74 MW | 2.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 290086 | Q-036 E | Adder | 5.65 MW | 4.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 296332 | R-032 E | 50/50 | 10.62 MW | 10.62 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 913142 | Y1-033 E OP1 | Adder | 3.51 MW | 2.98 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 936991 | AD2-133 C | Adder | 2.13 MW | 1.81 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 936992 | AD2-133 E | Adder | 9.74 MW | 8.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942121 | AE2-224 C | Adder | 10.18 MW | 8.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942122 | AE2-224 E | Adder | 6.79 MW | 5.77 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942351 | AE2-248 C | Adder | 0.8 MW | 0.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942361 | AE2-249 C | Adder | 1.72 MW | 1.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942362 | AE2-249 E | Adder | 1.15 MW | 0.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942491 | AE2-262 C | Adder | 4.58 MW | 3.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942492 | AE2-262 E | Adder | 3.07 MW | 2.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942501 | AE2-263 C | Adder | 4.3 MW | 3.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942502 | AE2-263 E | Adder | 2.87 MW | 2.44 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942811 | AE2-299 C | Adder | 2.64 MW | 2.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942812 | AE2-299 E | Adder | 10.56 MW | 8.98 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942961 | AE2-316 C | Adder | 4.3 MW | 3.66 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 942962 | AE2-316 E | Adder | 5.1 MW | 4.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 943151 | AE2-344 C | Adder | 5.71 MW | 4.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 943152 | AE2-344 E | Adder | 3.81 MW | 3.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 943351 | AF1-006 C | Adder | 0.98 MW | 0.83 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 943352 | AF1-006 E | Adder | 0.55 MW | 0.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 943711 | AF1-039 C O1 | Adder | 0.93 MW | 0.79 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 943712 | AF1-039 E O1 | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944181 | AF1-086 C O1 | Adder | 3.25 MW | 2.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944182 | AF1-086 E O1 | Adder | 14.13 MW | 12.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944261 | AF1-094 C | Adder | 1.04 MW | 0.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944262 | AF1-094 E | Adder | 0.7 MW | 0.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944301 | AF1-098 C | Adder | 4.06 MW | 3.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944302 | AF1-098 E | Adder | 2.71 MW | 2.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944311 | AF1-099 C | Adder | 7.14 MW | 6.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944312 | AF1-099 E | Adder | 4.76 MW | 4.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944321 | AF1-100 C | Adder | 14.77 MW | 12.55 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944322 | AF1-100 E | Adder | 9.85 MW | 8.37 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944411 | AF1-106 O1 | Adder | 2.05 MW | 1.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944472 | AF1-112 E | Adder | 0.51 MW | 0.43 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944691 | AF1-134 C | Adder | 1.67 MW | 1.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944692 | AF1-134 E | Adder | 1.11 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944751 | AF1-140 C | Adder | 1.66 MW | 1.41 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944752 | AF1-140 E | Adder | 1.11 MW | 0.94 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944771 | AF1-142 C | Adder | 11.43 MW | 9.72 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944772 | AF1-142 E | Adder | 7.62 MW | 6.48 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944781 | AF1-143 C | Adder | 8.19 MW | 6.96 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944782 | AF1-143 E | Adder | 4.37 MW | 3.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 945021 | AF1-167 C | Adder | 0.79 MW | 0.67 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 945022 | AF1-167 E | Adder | 0.53 MW | 0.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 945051 | AF1-170 C | Adder | 3.64 MW | 3.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 945052 | AF1-170 E | Adder | 2.43 MW | 2.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 945451 | AF1-210 C | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 945452 | AF1-210 E | Adder | 0.58 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 945751 | AF1-240 C O1 | Adder | 1.68 MW | 1.43 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 945752 | AF1-240 E O1 | Adder | 1.12 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 958471 | AF2-141 | Adder | 1.09 MW | 0.93 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 958731 | AF2-164 C O1 | Adder | 5.72 MW | 4.86 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 958732 | AF2-164 E O1 | Adder | 3.81 MW | 3.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 958741 | AF2-165 C | Adder | 1.25 MW | 1.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 958742 | AF2-165 E | Adder | 0.84 MW | 0.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 958751 | AF2-166 C | Adder | 1.3 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 958752 | AF2-166 E | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 959441 | AF2-235 C | Adder | 0.59 MW | 0.5 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 959442 | AF2-235 E | Adder | 0.39 MW | 0.34 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 959471 | AF2-238 C | Adder | 1.26 MW | 1.07 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 959472 | AF2-238 E | Adder | 0.84 MW | 0.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 959521 | AF2-243 C | Adder | 0.94 MW | 0.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 959522 | AF2-243 E | Adder | 0.63 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 959802 | AF2-271 E | Adder | 0.38 MW | 0.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960022 | AF2-293 E | Adder | 0.1 MW | 0.08 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960031 | AF2-294 C | Adder | 0.96 MW | 0.81 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960032 | AF2-294 E | Adder | 0.64 MW | 0.54 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960051 | AF2-296 C | Adder | 1.67 MW | 1.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960052 | AF2-296 E | Adder | 1.11 MW | 0.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960451 | AF2-336 C | Adder | 2.07 MW | 1.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960452 | AF2-336 E | Adder | 1.38 MW | 1.17 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960461 | AF2-337 C | Adder | 2.07 MW | 1.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960462 | AF2-337 E | Adder | 1.38 MW | 1.17 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 961141 | AF2-405 | Adder | 1.02 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 961151 | AF2-406 | Adder | 7.68 MW | 6.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 961211 | AF2-412 | Adder | 15.67 MW | 13.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 961451 | AF2-436 | Adder | 0.11 MW | 0.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200636 | 26IUP CO-G | 50/50 | 0.49 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200794 | 26CONEMAGH | 50/50 | 0.33 MW | 0.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200809 | 26SITHE | 50/50 | 1.54 MW | 1.54 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200835 | 26ARN_Z1-066 | Adder | 1.09 MW | 0.93 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200837 | 26HOMER C1 | 50/50 | 26.57 MW | 26.57 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200838 | 26HOMER C2 | 50/50 | 22.01 MW | 22.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200839 | 26HOMER C3 | 50/50 | 23.3 MW | 23.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200846 | 26FORWARD | 50/50 | 0.1 MW | 0.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200852 | 26WARR RDG | Adder | 0.31 MW | 0.26 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200864 | K-013 E | 50/50 | 4.23 MW | 4.23 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200883 | Q-053 E | Adder | 5.08 MW | 4.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200888 | 26HIGHLAND | 50/50 | 0.24 MW | 0.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200894 | 26K02 | Adder | 4.95 MW | 4.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200925 | 26R32 | 50/50 | 0.38 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 203915 | 26BF_Z2-108 | Adder | 2.46 MW | 2.09 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 203932 | AA2-133 GEN | Adder | 1.5 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 203999 | P-047 E | Adder | 8.92 MW | 7.58 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 235003 | AC1-025 E | Adder | 0.12 MW | 0.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 292350 | K-023 | Adder | 3.4 MW | 2.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 292542 | L-013 1 | Adder | 4.37 MW | 3.71 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 293301 | N-039 E | Adder | 10.36 MW | 8.8 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 293393 | V3-030E | Adder | 4.72 MW | 4.01 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 293603 | O-018 E | 50/50 | 9.21 MW | 9.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 293902 | O-048 E | Adder | 3.93 MW | 3.34 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 294515 | O38_P22 | Adder | 9.06 MW | 7.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 294903 | P-060 E | Adder | 7.04 MW | 5.99 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 916202 | Z1-069 E | Adder | 7.19 MW | 6.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 931092 | AB1-160 E | Adder | 2.05 MW | 1.75 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 938951 | AE1-123 | Adder | 2.02 MW | 1.72 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 939291 | AE1-160 C | Adder | 1.25 MW | 1.06 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 939292 | AE1-160 E | Adder | 0.72 MW | 0.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 940201 | AE2-001 C | Adder | 1.02 MW | 0.86 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 940202 | AE2-001 E | Adder | 0.68 MW | 0.58 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 940681 | AE2-055 C | Adder | 0.99 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 940682 | AE2-055 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 940861 | AE2-074 C | Adder | 1.97 MW | 1.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 940862 | AE2-074 E | Adder | 2.59 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941191 | AE2-113 C | Adder | 7.64 MW | 6.5 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941192 | AE2-113 E | Adder | 7.18 MW | 6.1 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941231 | AE2-117 C | Adder | 1.49 MW | 1.26 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941232 | AE2-117 E | Adder | 0.99 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941241 | AE2-118 C | Adder | 1.56 MW | 1.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941242 | AE2-118 E | Adder | 1.04 MW | 0.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941271 | AE2-121 C | Adder | 0.54 MW | 0.46 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941272 | AE2-121 E | Adder | 0.36 MW | 0.31 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941331 | AE2-129 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941332 | AE2-129 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941351 | AE2-131 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941352 | AE2-131 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941421 | AE2-139 C | Adder | 5.07 MW | 4.31 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 941422 | AE2-139 E | Adder | 3.38 MW | 2.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946071 | AF1-272 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946072 | AF1-272 E O1 | 50/50 | 10.45 MW | 10.45 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946111 | AF1-276 C | Adder | 8.81 MW | 7.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946112 | AF1-276 E | Adder | 4.34 MW | 3.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946121 | AF1-277 C | Adder | 8.81 MW | 7.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946122 | AF1-277 E | Adder | 4.34 MW | 3.69 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946131 | AF1-278 C | Adder | 7.02 MW | 5.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946132 | AF1-278 E | Adder | 3.49 MW | 2.97 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946221 | AF1-287 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946222 | AF1-287 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946381 | AF1-302 C | Adder | 1.88 MW | 1.6 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946382 | AF1-302 E | Adder | 2.51 MW | 2.13 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946571 | AF1-321 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946572 | AF1-321 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946771 | AF1-217 C | Adder | 0.98 MW | 0.84 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946772 | AF1-217 E | Adder | 0.66 MW | 0.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957001 | AF2-001 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957002 | AF2-001 E O1 | 50/50 | 1.47 MW | 1.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957011 | AF2-002 C O1 | 50/50 | 1.11 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957012 | AF2-002 E O1 | 50/50 | 0.74 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957161 | AF2-010 C | Adder | 4.02 MW | 3.42 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957162 | AF2-010 E | Adder | 2.71 MW | 2.3 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957451 | AF2-039 C | Adder | 0.92 MW | 0.79 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957452 | AF2-039 E | Adder | 0.62 MW | 0.52 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957561 | AF2-050 C | Adder | 5.09 MW | 4.33 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957562 | AF2-050 E | Adder | 3.39 MW | 2.88 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957931 | AF2-087 C | Adder | 0.45 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957932 | AF2-087 E | Adder | 0.62 MW | 0.53 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957941 | AF2-088 C | Adder | 0.44 MW | 0.38 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957942 | AF2-088 E | Adder | 0.3 MW | 0.25 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957981 | AF2-092 C | Adder | 1.24 MW | 1.05 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 957982 | AF2-092 E | Adder | 0.83 MW | 0.7 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 958271 | AF2-121 C | Adder | 1.51 MW | 1.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 958272 | AF2-121 E | Adder | 1.01 MW | 0.85 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 958361 | AF2-130 C | Adder | 1.3 MW | 1.11 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 958362 | AF2-130 E | Adder | 0.87 MW | 0.74 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200833 | 26SEWRDB34 | 50/50 | 16.03 MW | 16.03 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 200906 | 26KEYSTN#3 | 50/50 | 0.82 MW | 0.82 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 959301 | AF2-221 C | 50/50 | 1.15 MW | 1.15 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 959302 | AF2-221 E | 50/50 | 1.59 MW | 1.59 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 292340 | 26SW_E13_K22 | Adder | 1.18 MW | 1.0 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 964451 | AG1-308 C O1 | Adder | 1.04 MW | 0.89 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 964452 | AG1-308 E O1 | Adder | 1.46 MW | 1.24 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960901 | AG1-000C C | 50/50 | 7.22 MW | 7.22 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 960902 | AG1-000C E | 50/50 | 3.56 MW | 3.56 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946421 | AF2-000A C | Adder | 5.08 MW | 4.32 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | 946422 | AF2-000A E | Adder | 15.24 MW | 12.95 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.49 MW | 0.49 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.47 MW | 0.47 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.87 MW | 0.87 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 4.61 MW | 4.61 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.12 MW | 1.12 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.27 MW | 0.27 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.29 MW | 1.29 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.28 MW | 0.28 MW |
| 26KEYSTONE-KEYSTONE 230.0 kV Ckt 4 line l/o APS-P2-3-WP-500-DRT26 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.1 MW | 0.1 MW |
| Details for AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 965241 | AG1-392C C O | 50/50 | 1.63 MW | 1.63 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 965242 | AG1-392C E O | 50/50 | 1.09 MW | 1.09 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 965251 | AG1-392B C O | 50/50 | 1.63 MW | 1.63 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 965252 | AG1-392B E O | 50/50 | 1.09 MW | 1.09 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 965261 | AG1-392A C O | 50/50 | 3.26 MW | 3.26 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 965262 | AG1-392A E O | 50/50 | 2.17 MW | 2.17 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 965271 | AG1-392 C O1 | 50/50 | 3.26 MW | 3.26 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 965272 | AG1-392 E O1 | 50/50 | 2.17 MW | 2.17 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 203349 | 26Z1-069 C | 50/50 | 0.28 MW | 0.28 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 236828 | 01GRAYMONT | Adder | -0.24 MW | -0.2 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 916202 | Z1-069 E | 50/50 | 7.08 MW | 7.08 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 931091 | AB1-160 C | 50/50 | 0.08 MW | 0.08 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 931092 | AB1-160 E | 50/50 | 2.02 MW | 2.02 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 940861 | AE2-074 C | 50/50 | 2.59 MW | 2.59 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 940862 | AE2-074 E | 50/50 | 3.41 MW | 3.41 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 941191 | AE2-113 C | 50/50 | 29.44 MW | 29.44 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 941192 | AE2-113 E | 50/50 | 27.64 MW | 27.64 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 941321 | AE2-126 C | Adder | -1.87 MW | -1.59 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 941331 | AE2-129 C | Adder | -0.76 MW | -0.65 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 946111 | AF1-276 C | 50/50 | 8.83 MW | 8.83 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 946112 | AF1-276 E | 50/50 | 4.35 MW | 4.35 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 946121 | AF1-277 C | 50/50 | 8.83 MW | 8.83 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 946122 | AF1-277 E | 50/50 | 4.35 MW | 4.35 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 946131 | AF1-278 C | 50/50 | 7.05 MW | 7.05 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 946132 | AF1-278 E | 50/50 | 3.5 MW | 3.5 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 962413 | AG1-090 BAT | Adder | 3.75 MW | 3.19 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 946423 | AF2-000A BAT | 50/50 | 21.83 MW | 21.83 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 960023 | AF2-293 BAT | Adder | 0.08 MW | 0.07 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | 235007 | AC1-025 BAT | Adder | 0.1 MW | 0.09 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.01 MW | 0.01 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 1.42 MW | 1.42 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.03 MW | 0.03 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.43 MW | 0.43 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.3 MW | 1.3 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.66 MW | 0.66 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.02 MW | 0.02 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.14 MW | 0.14 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.12 MW | 0.12 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.84 MW | 0.84 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.09 MW | 0.09 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-8I | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 962411 | AG1-090 C O1 | 50/50 | 25.39 MW | 25.39 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 962412 | AG1-090 E O1 | 50/50 | 6.35 MW | 6.35 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 965121 | AG1-377 C O1 | 50/50 | 3.81 MW | 3.81 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 965122 | AG1-377 E O1 | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 965131 | AG1-378 C O1 | 50/50 | 3.81 MW | 3.81 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 965132 | AG1-378 E O1 | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 290086 | Q-036 E | 50/50 | 9.72 MW | 9.72 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 936991 | AD2-133 C | 50/50 | 3.66 MW | 3.66 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 936992 | AD2-133 E | 50/50 | 16.76 MW | 16.76 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 944181 | AF1-086 C O1 | 50/50 | 3.31 MW | 3.31 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 944182 | AF1-086 E O1 | 50/50 | 14.4 MW | 14.4 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 944691 | AF1-134 C | 50/50 | 3.27 MW | 3.27 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 944692 | AF1-134 E | 50/50 | 2.18 MW | 2.18 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 945181 | AF1-183 | 50/50 | 0.1 MW | 0.1 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 959802 | AF2-271 E | Adder | 0.28 MW | 0.24 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 960051 | AF2-296 C | 50/50 | 3.27 MW | 3.27 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 960052 | AF2-296 E | 50/50 | 2.18 MW | 2.18 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 200715 | 26SHAWVL 1 | 50/50 | 12.7 MW | 12.7 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 200722 | 26SHAWVL 2 | 50/50 | 8.97 MW | 8.97 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 200883 | Q-053 E | Adder | 2.61 MW | 2.22 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 200913 | 26SHAW-D | 50/50 | 0.43 MW | 0.43 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 236828 | 01GRAYMONT | Adder | -0.34 MW | -0.29 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 293393 | V3-030E | Adder | 2.27 MW | 1.93 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 941321 | AE2-126 C | 50/50 | 2.65 MW | 2.65 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 941322 | AE2-126 E | 50/50 | 1.77 MW | 1.77 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 941331 | AE2-129 C | 50/50 | 3.81 MW | 3.81 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 941332 | AE2-129 E | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 941351 | AE2-131 C | 50/50 | 3.81 MW | 3.81 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 941352 | AE2-131 E | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 957451 | AF2-039 C | 50/50 | 3.41 MW | 3.41 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 957452 | AF2-039 E | 50/50 | 2.27 MW | 2.27 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 957941 | AF2-088 C | 50/50 | 1.64 MW | 1.64 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 957942 | AF2-088 E | 50/50 | 1.09 MW | 1.09 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 958271 | AF2-121 C | 50/50 | 3.81 MW | 3.81 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 958272 | AF2-121 E | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 964451 | AG1-308 C O1 | 50/50 | 2.63 MW | 2.63 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 964452 | AG1-308 E O1 | 50/50 | 3.68 MW | 3.68 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 200905 | 26Q36 | 50/50 | 0.33 MW | 0.33 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 960023 | AF2-293 BAT | Adder | 0.12 MW | 0.1 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | 235007 | AC1-025 BAT | Adder | 0.14 MW | 0.12 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.03 MW | 0.03 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.79 MW | 0.79 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.59 MW | 1.59 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.94 MW | 0.94 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.04 MW | 0.04 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.47 MW | 0.47 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.17 MW | 0.17 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.07 MW | 0.07 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.17 MW | 0.17 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.46 MW | 0.46 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.16 MW | 3.16 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.14 MW | 0.14 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-3-PN-230-21AT | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 962411 | AG1-090 C O1 | Adder | 7.44 MW | 6.33 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 962412 | AG1-090 E O1 | Adder | 1.86 MW | 1.58 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 962911 | AG1-140 C | Adder | -0.33 MW | -0.28 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 963991 | AG1-253 C | Adder | -0.5 MW | -0.42 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 964031 | AG1-257 C | Adder | 0.8 MW | 0.68 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 964032 | AG1-257 E | Adder | 1.11 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965121 | AG1-377 C O1 | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965122 | AG1-377 E O1 | Adder | 0.74 MW | 0.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965131 | AG1-378 C O1 | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965132 | AG1-378 E O1 | Adder | 0.74 MW | 0.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965241 | AG1-392C C O | 50/50 | 1.5 MW | 1.5 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965242 | AG1-392C E O | 50/50 | 1.0 MW | 1.0 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965251 | AG1-392B C O | 50/50 | 1.5 MW | 1.5 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965252 | AG1-392B E O | 50/50 | 1.0 MW | 1.0 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965261 | AG1-392A C O | 50/50 | 2.99 MW | 2.99 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965262 | AG1-392A E O | 50/50 | 2.0 MW | 2.0 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965271 | AG1-392 C O1 | 50/50 | 2.99 MW | 2.99 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965272 | AG1-392 E O1 | 50/50 | 2.0 MW | 2.0 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 966041 | AG1-473 C | Adder | 2.35 MW | 2.0 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 966042 | AG1-473 E | Adder | 1.57 MW | 1.33 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 290086 | Q-036 E | Adder | 3.23 MW | 2.75 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 936991 | AD2-133 C | Adder | 1.22 MW | 1.03 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 936992 | AD2-133 E | Adder | 5.57 MW | 4.73 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 942351 | AE2-248 C | Adder | 0.91 MW | 0.78 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 942352 | AE2-248 E | Adder | 0.61 MW | 0.52 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 942491 | AE2-262 C | Adder | 5.58 MW | 4.74 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 942492 | AE2-262 E | Adder | 3.75 MW | 3.19 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 942501 | AE2-263 C | Adder | 5.24 MW | 4.46 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 942502 | AE2-263 E | Adder | 3.5 MW | 2.98 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 942961 | AE2-316 C | Adder | 4.23 MW | 3.6 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 942962 | AE2-316 E | Adder | 5.01 MW | 4.26 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944311 | AF1-099 C | Adder | 8.89 MW | 7.55 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944312 | AF1-099 E | Adder | 5.92 MW | 5.04 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944321 | AF1-100 C | 50/50 | 18.27 MW | 18.27 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944322 | AF1-100 E | 50/50 | 12.18 MW | 12.18 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944471 | AF1-112 C | Adder | 0.85 MW | 0.72 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944472 | AF1-112 E | Adder | 0.58 MW | 0.49 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944691 | AF1-134 C | Adder | 0.95 MW | 0.81 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944692 | AF1-134 E | Adder | 0.64 MW | 0.54 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944771 | AF1-142 C | Adder | 14.22 MW | 12.09 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944772 | AF1-142 E | Adder | 9.48 MW | 8.06 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944881 | AF1-153 C O1 | 50/50 | 1.63 MW | 1.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944882 | AF1-153 E O1 | 50/50 | 1.09 MW | 1.09 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944901 | AF1-155 C | 50/50 | 1.62 MW | 1.62 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944902 | AF1-155 E | 50/50 | 1.08 MW | 1.08 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 945161 | AF1-181 | 50/50 | 0.02 MW | 0.02 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 945171 | AF1-182 | 50/50 | 0.08 MW | 0.08 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 960022 | AF2-293 E | Adder | 0.11 MW | 0.1 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 960041 | AF2-295 C | 50/50 | 1.62 MW | 1.62 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 960042 | AF2-295 E | 50/50 | 1.08 MW | 1.08 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 960051 | AF2-296 C | Adder | 0.95 MW | 0.81 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 960052 | AF2-296 E | Adder | 0.64 MW | 0.54 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 961211 | AF2-412 | Adder | 9.23 MW | 7.85 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 200642 | 26SENECA#1 | 50/50 | 13.84 MW | 13.84 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 200643 | 26SENECA#2 | 50/50 | 12.38 MW | 12.38 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 200644 | 26SENECA#3 | 50/50 | 1.33 MW | 1.33 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 200649 | 26PENNTECH | 50/50 | 1.29 MW | 1.29 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 200665 | 26SHAWVL 3 | 50/50 | 3.62 MW | 3.62 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 200666 | 26SHAWVL 4 | 50/50 | 3.55 MW | 3.55 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 200722 | 26SHAWVL 2 | 50/50 | 2.49 MW | 2.49 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 200894 | 26K02 | Adder | 4.48 MW | 3.8 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 203349 | 26Z1-069 C | 50/50 | 0.27 MW | 0.27 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 235003 | AC1-025 E | Adder | 0.14 MW | 0.12 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 236828 | 01GRAYMONT | Adder | 0.39 MW | 0.33 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 916202 | Z1-069 E | 50/50 | 6.71 MW | 6.71 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 931091 | AB1-160 C | 50/50 | 0.08 MW | 0.08 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 931092 | AB1-160 E | 50/50 | 1.92 MW | 1.92 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 940201 | AE2-001 C | Adder | 1.17 MW | 0.99 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 940202 | AE2-001 E | Adder | 0.78 MW | 0.66 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 940681 | AE2-055 C | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 940682 | AE2-055 E | Adder | 0.75 MW | 0.64 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 940861 | AE2-074 C | 50/50 | 2.2 MW | 2.2 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 940862 | AE2-074 E | 50/50 | 2.89 MW | 2.89 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 941191 | AE2-113 C | 50/50 | 10.87 MW | 10.87 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 941192 | AE2-113 E | 50/50 | 10.2 MW | 10.2 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 941271 | AE2-121 C | Adder | 0.63 MW | 0.53 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 941272 | AE2-121 E | Adder | 0.42 MW | 0.36 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 941321 | AE2-126 C | 50/50 | 1.76 MW | 1.76 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 941322 | AE2-126 E | 50/50 | 1.17 MW | 1.17 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 941331 | AE2-129 C | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 941332 | AE2-129 E | Adder | 0.74 MW | 0.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 941351 | AE2-131 C | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 941352 | AE2-131 E | Adder | 0.74 MW | 0.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 946111 | AF1-276 C | 50/50 | 15.21 MW | 15.21 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 946112 | AF1-276 E | 50/50 | 7.49 MW | 7.49 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 946121 | AF1-277 C | 50/50 | 15.21 MW | 15.21 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 946122 | AF1-277 E | 50/50 | 7.49 MW | 7.49 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 946131 | AF1-278 C | 50/50 | 12.13 MW | 12.13 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 946132 | AF1-278 E | 50/50 | 6.03 MW | 6.03 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 946221 | AF1-287 C | Adder | -2.04 MW | -1.73 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 946381 | AF1-302 C | Adder | 1.85 MW | 1.57 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 946382 | AF1-302 E | Adder | 2.47 MW | 2.1 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 957451 | AF2-039 C | Adder | 0.91 MW | 0.77 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 957452 | AF2-039 E | Adder | 0.61 MW | 0.52 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 957941 | AF2-088 C | Adder | 0.44 MW | 0.37 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 957942 | AF2-088 E | Adder | 0.29 MW | 0.25 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 958271 | AF2-121 C | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 958272 | AF2-121 E | Adder | 0.74 MW | 0.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 964451 | AG1-308 C O1 | Adder | 0.77 MW | 0.66 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 964452 | AG1-308 E O1 | Adder | 1.08 MW | 0.92 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 946421 | AF2-000A C | 50/50 | 8.03 MW | 8.03 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 946422 | AF2-000A E | 50/50 | 24.1 MW | 24.1 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 944392 | AF1-104 BAT | 50/50 | 3.08 MW | 3.08 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 965862 | AG1-455 BAT | 50/50 | 5.61 MW | 5.61 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 966773 | AG1-548 BAT | 50/50 | 4.17 MW | 4.17 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | 942813 | AE2-299 BAT | 50/50 | 29.66 MW | 29.66 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.33 MW | 1.33 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.48 MW | 0.48 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.29 MW | 2.29 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.51 MW | 0.51 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.28 MW | 0.28 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 3.83 MW | 3.83 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.51 MW | 0.51 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.4 MW | 2.4 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 4.14 MW | 4.14 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.73 MW | 0.73 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.41 MW | 0.41 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.32 MW | 3.32 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.73 MW | 0.73 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2_3-PN-345-997-DRT-031 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 11.33 MW | 11.33 MW |
| Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 962411 | AG1-090 C O1 | Adder | 7.44 MW | 6.32 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 962412 | AG1-090 E O1 | Adder | 1.86 MW | 1.58 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 962911 | AG1-140 C | Adder | -0.33 MW | -0.28 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 963991 | AG1-253 C | Adder | -0.5 MW | -0.42 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 964031 | AG1-257 C | Adder | 0.8 MW | 0.68 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 964032 | AG1-257 E | Adder | 1.11 MW | 0.94 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965121 | AG1-377 C O1 | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965122 | AG1-377 E O1 | Adder | 0.74 MW | 0.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965131 | AG1-378 C O1 | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965132 | AG1-378 E O1 | Adder | 0.74 MW | 0.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965241 | AG1-392C C O | 50/50 | 1.5 MW | 1.5 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965242 | AG1-392C E O | 50/50 | 1.0 MW | 1.0 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965251 | AG1-392B C O | 50/50 | 1.5 MW | 1.5 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965252 | AG1-392B E O | 50/50 | 1.0 MW | 1.0 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965261 | AG1-392A C O | 50/50 | 2.99 MW | 2.99 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965262 | AG1-392A E O | 50/50 | 2.0 MW | 2.0 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965271 | AG1-392 C O1 | 50/50 | 2.99 MW | 2.99 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965272 | AG1-392 E O1 | 50/50 | 2.0 MW | 2.0 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 966041 | AG1-473 C | Adder | 2.35 MW | 2.0 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 966042 | AG1-473 E | Adder | 1.57 MW | 1.33 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 290086 | Q-036 E | Adder | 3.23 MW | 2.74 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 936991 | AD2-133 C | Adder | 1.22 MW | 1.03 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 936992 | AD2-133 E | Adder | 5.56 MW | 4.73 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942351 | AE2-248 C | Adder | 0.91 MW | 0.78 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942352 | AE2-248 E | Adder | 0.61 MW | 0.52 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942491 | AE2-262 C | Adder | 5.58 MW | 4.74 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942492 | AE2-262 E | Adder | 3.75 MW | 3.19 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942501 | AE2-263 C | Adder | 5.24 MW | 4.46 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942502 | AE2-263 E | Adder | 3.5 MW | 2.97 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942961 | AE2-316 C | Adder | 4.23 MW | 3.6 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942962 | AE2-316 E | Adder | 5.01 MW | 4.26 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944311 | AF1-099 C | Adder | 8.88 MW | 7.55 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944312 | AF1-099 E | Adder | 5.92 MW | 5.03 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944321 | AF1-100 C | 50/50 | 18.27 MW | 18.27 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944322 | AF1-100 E | 50/50 | 12.18 MW | 12.18 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944471 | AF1-112 C | Adder | 0.85 MW | 0.72 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944472 | AF1-112 E | Adder | 0.58 MW | 0.49 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944691 | AF1-134 C | Adder | 0.95 MW | 0.81 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944692 | AF1-134 E | Adder | 0.64 MW | 0.54 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944771 | AF1-142 C | Adder | 14.21 MW | 12.08 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944772 | AF1-142 E | Adder | 9.48 MW | 8.05 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944881 | AF1-153 C O1 | 50/50 | 1.63 MW | 1.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944882 | AF1-153 E O1 | 50/50 | 1.09 MW | 1.09 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944901 | AF1-155 C | 50/50 | 1.62 MW | 1.62 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944902 | AF1-155 E | 50/50 | 1.08 MW | 1.08 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 945161 | AF1-181 | 50/50 | 0.02 MW | 0.02 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 945171 | AF1-182 | 50/50 | 0.08 MW | 0.08 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 960022 | AF2-293 E | Adder | 0.11 MW | 0.1 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 960041 | AF2-295 C | 50/50 | 1.62 MW | 1.62 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 960042 | AF2-295 E | 50/50 | 1.08 MW | 1.08 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 960051 | AF2-296 C | Adder | 0.95 MW | 0.81 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 960052 | AF2-296 E | Adder | 0.64 MW | 0.54 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 961211 | AF2-412 | Adder | 9.23 MW | 7.84 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200642 | 26SENECA#1 | 50/50 | 13.84 MW | 13.84 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200643 | 26SENECA#2 | 50/50 | 12.38 MW | 12.38 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200644 | 26SENECA#3 | 50/50 | 1.33 MW | 1.33 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200649 | 26PENNTECH | 50/50 | 1.29 MW | 1.29 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200665 | 26SHAWVL 3 | 50/50 | 3.62 MW | 3.62 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200666 | 26SHAWVL 4 | 50/50 | 3.55 MW | 3.55 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200722 | 26SHAWVL 2 | 50/50 | 2.49 MW | 2.49 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200894 | 26K02 | Adder | 4.47 MW | 3.8 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 203349 | 26Z1-069 C | 50/50 | 0.27 MW | 0.27 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 235003 | AC1-025 E | Adder | 0.14 MW | 0.12 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 236828 | 01GRAYMONT | Adder | 0.39 MW | 0.33 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 916202 | Z1-069 E | 50/50 | 6.71 MW | 6.71 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 931091 | AB1-160 C | 50/50 | 0.08 MW | 0.08 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 931092 | AB1-160 E | 50/50 | 1.92 MW | 1.92 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940201 | AE2-001 C | Adder | 1.17 MW | 0.99 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940202 | AE2-001 E | Adder | 0.78 MW | 0.66 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940681 | AE2-055 C | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940682 | AE2-055 E | Adder | 0.75 MW | 0.64 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940861 | AE2-074 C | 50/50 | 2.2 MW | 2.2 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940862 | AE2-074 E | 50/50 | 2.89 MW | 2.89 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941191 | AE2-113 C | 50/50 | 10.87 MW | 10.87 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941192 | AE2-113 E | 50/50 | 10.2 MW | 10.2 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941271 | AE2-121 C | Adder | 0.63 MW | 0.53 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941272 | AE2-121 E | Adder | 0.42 MW | 0.36 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941321 | AE2-126 C | 50/50 | 1.76 MW | 1.76 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941322 | AE2-126 E | 50/50 | 1.17 MW | 1.17 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941331 | AE2-129 C | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941332 | AE2-129 E | Adder | 0.74 MW | 0.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941351 | AE2-131 C | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941352 | AE2-131 E | Adder | 0.74 MW | 0.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946111 | AF1-276 C | 50/50 | 15.21 MW | 15.21 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946112 | AF1-276 E | 50/50 | 7.49 MW | 7.49 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946121 | AF1-277 C | 50/50 | 15.21 MW | 15.21 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946122 | AF1-277 E | 50/50 | 7.49 MW | 7.49 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946131 | AF1-278 C | 50/50 | 12.13 MW | 12.13 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946132 | AF1-278 E | 50/50 | 6.03 MW | 6.03 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946221 | AF1-287 C | Adder | -2.04 MW | -1.74 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946381 | AF1-302 C | Adder | 1.85 MW | 1.57 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946382 | AF1-302 E | Adder | 2.46 MW | 2.09 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 957451 | AF2-039 C | Adder | 0.91 MW | 0.77 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 957452 | AF2-039 E | Adder | 0.6 MW | 0.51 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 957941 | AF2-088 C | Adder | 0.44 MW | 0.37 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 957942 | AF2-088 E | Adder | 0.29 MW | 0.25 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 958271 | AF2-121 C | Adder | 1.12 MW | 0.95 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 958272 | AF2-121 E | Adder | 0.74 MW | 0.63 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 964451 | AG1-308 C O1 | Adder | 0.77 MW | 0.66 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 964452 | AG1-308 E O1 | Adder | 1.08 MW | 0.92 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946421 | AF2-000A C | 50/50 | 8.03 MW | 8.03 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946422 | AF2-000A E | 50/50 | 24.09 MW | 24.09 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944392 | AF1-104 BAT | 50/50 | 3.08 MW | 3.08 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 965862 | AG1-455 BAT | 50/50 | 5.62 MW | 5.62 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 966773 | AG1-548 BAT | 50/50 | 4.18 MW | 4.18 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942813 | AE2-299 BAT | 50/50 | 29.64 MW | 29.64 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.33 MW | 1.33 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.48 MW | 0.48 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.29 MW | 2.29 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.51 MW | 0.51 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.28 MW | 0.28 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 3.83 MW | 3.83 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.51 MW | 0.51 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.4 MW | 2.4 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 4.13 MW | 4.13 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.73 MW | 0.73 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.41 MW | 0.41 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.31 MW | 3.31 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.73 MW | 0.73 MW |
| 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 11.32 MW | 11.32 MW |
| Details for 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 964031 | AG1-257 C | Adder | 0.5 MW | 0.42 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 964032 | AG1-257 E | Adder | 0.7 MW | 0.59 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 936991 | AD2-133 C | Adder | -2.73 MW | -2.32 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 942351 | AE2-248 C | Adder | 0.56 MW | 0.48 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 942352 | AE2-248 E | Adder | 0.37 MW | 0.32 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 942491 | AE2-262 C | Adder | 4.33 MW | 3.68 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 942492 | AE2-262 E | Adder | 2.91 MW | 2.47 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 942501 | AE2-263 C | Adder | 4.07 MW | 3.46 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 942502 | AE2-263 E | Adder | 2.72 MW | 2.31 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 944311 | AF1-099 C | Adder | 7.29 MW | 6.19 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 944312 | AF1-099 E | Adder | 4.86 MW | 4.13 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 944321 | AF1-100 C | 50/50 | 22.06 MW | 22.06 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 944322 | AF1-100 E | 50/50 | 14.71 MW | 14.71 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 944471 | AF1-112 C | Adder | 0.53 MW | 0.45 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 944472 | AF1-112 E | Adder | 0.36 MW | 0.31 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 944771 | AF1-142 C | Adder | 11.66 MW | 9.91 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 944772 | AF1-142 E | Adder | 7.77 MW | 6.61 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 945161 | AF1-181 | 50/50 | 0.02 MW | 0.02 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 960022 | AF2-293 E | Adder | 0.07 MW | 0.06 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 200665 | 26SHAWVL 3 | 50/50 | 4.79 MW | 4.79 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 235003 | AC1-025 E | Adder | 0.09 MW | 0.07 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 236828 | 01GRAYMONT | Adder | 0.25 MW | 0.21 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 940201 | AE2-001 C | Adder | 0.75 MW | 0.64 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 940202 | AE2-001 E | Adder | 0.5 MW | 0.43 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 940681 | AE2-055 C | Adder | 0.67 MW | 0.57 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 940682 | AE2-055 E | Adder | 0.44 MW | 0.38 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 941271 | AE2-121 C | Adder | 0.41 MW | 0.35 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 941272 | AE2-121 E | Adder | 0.27 MW | 0.23 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 941321 | AE2-126 C | Adder | -1.98 MW | -1.68 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 941331 | AE2-129 C | Adder | -2.84 MW | -2.42 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 959803 | AF2-271 BAT | Adder | 0.13 MW | 0.11 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | 962413 | AG1-090 BAT | 50/50 | 11.84 MW | 11.84 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.14 MW | 0.14 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.07 MW | 0.07 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.24 MW | 0.24 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.67 MW | 0.67 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.27 MW | 0.27 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.67 MW | 0.67 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.06 MW | 0.06 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.34 MW | 0.34 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.08 MW | 0.08 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0 kV Ckt 1A line l/o PN-P2-3-PN-230-21HT | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.88 MW | 1.88 MW |
| Details for 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 962411 | AG1-090 C O1 | 50/50 | 26.21 MW | 26.21 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 962412 | AG1-090 E O1 | 50/50 | 6.55 MW | 6.55 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 965121 | AG1-377 C O1 | 50/50 | 3.93 MW | 3.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 965122 | AG1-377 E O1 | 50/50 | 2.62 MW | 2.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 965131 | AG1-378 C O1 | 50/50 | 3.93 MW | 3.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 965132 | AG1-378 E O1 | 50/50 | 2.62 MW | 2.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 290086 | Q-036 E | 50/50 | 10.01 MW | 10.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 936991 | AD2-133 C | 50/50 | 3.77 MW | 3.77 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 936992 | AD2-133 E | 50/50 | 17.27 MW | 17.27 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 944181 | AF1-086 C O1 | 50/50 | 3.39 MW | 3.39 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 944182 | AF1-086 E O1 | 50/50 | 14.74 MW | 14.74 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 944691 | AF1-134 C | 50/50 | 3.36 MW | 3.36 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 944692 | AF1-134 E | 50/50 | 2.24 MW | 2.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 945181 | AF1-183 | 50/50 | 0.07 MW | 0.07 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 959802 | AF2-271 E | Adder | 0.29 MW | 0.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 960051 | AF2-296 C | 50/50 | 3.36 MW | 3.36 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 960052 | AF2-296 E | 50/50 | 2.24 MW | 2.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 200715 | 26SHAWVL 1 | 50/50 | 9.0 MW | 9.0 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 200722 | 26SHAWVL 2 | 50/50 | 13.33 MW | 13.33 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 200883 | Q-053 E | Adder | 2.66 MW | 2.26 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 200913 | 26SHAW-D | 50/50 | 0.44 MW | 0.44 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 236828 | 01GRAYMONT | Adder | -0.34 MW | -0.29 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 293393 | V3-030E | Adder | 2.32 MW | 1.97 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 941321 | AE2-126 C | 50/50 | 2.69 MW | 2.69 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 941322 | AE2-126 E | 50/50 | 1.79 MW | 1.79 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 941331 | AE2-129 C | 50/50 | 3.93 MW | 3.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 941332 | AE2-129 E | 50/50 | 2.62 MW | 2.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 941351 | AE2-131 C | 50/50 | 3.93 MW | 3.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 941352 | AE2-131 E | 50/50 | 2.62 MW | 2.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 957451 | AF2-039 C | 50/50 | 3.51 MW | 3.51 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 957452 | AF2-039 E | 50/50 | 2.34 MW | 2.34 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 957941 | AF2-088 C | 50/50 | 1.69 MW | 1.69 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 957942 | AF2-088 E | 50/50 | 1.12 MW | 1.12 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 958271 | AF2-121 C | 50/50 | 3.93 MW | 3.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 958272 | AF2-121 E | 50/50 | 2.62 MW | 2.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 964451 | AG1-308 C O1 | 50/50 | 2.72 MW | 2.72 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 964452 | AG1-308 E O1 | 50/50 | 3.8 MW | 3.8 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 200905 | 26Q36 | 50/50 | 0.34 MW | 0.34 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 946423 | AF2-000A BAT | Adder | 15.14 MW | 12.87 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 960023 | AF2-293 BAT | Adder | 0.12 MW | 0.1 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 235007 | AC1-025 BAT | Adder | 0.15 MW | 0.13 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.02 MW | 0.02 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.03 MW | 0.03 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.49 MW | 0.49 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.17 MW | 1.17 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.67 MW | 0.67 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.03 MW | 0.03 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.43 MW | 0.43 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.12 MW | 0.12 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.83 MW | 2.83 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.1 MW | 0.1 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 962411 | AG1-090 C O1 | Adder | 5.71 MW | 4.86 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 962412 | AG1-090 E O1 | Adder | 1.43 MW | 1.21 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964031 | AG1-257 C | 50/50 | 1.01 MW | 1.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964032 | AG1-257 E | 50/50 | 1.41 MW | 1.41 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964201 | AG1-281 C | Adder | 0.68 MW | 0.58 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964202 | AG1-281 E | Adder | 0.45 MW | 0.39 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964391 | AG1-301 C | 50/50 | 1.26 MW | 1.26 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964392 | AG1-301 E | 50/50 | 0.84 MW | 0.84 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 965121 | AG1-377 C O1 | Adder | 0.86 MW | 0.73 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 965122 | AG1-377 E O1 | Adder | 0.57 MW | 0.49 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 965131 | AG1-378 C O1 | Adder | 0.86 MW | 0.73 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 965132 | AG1-378 E O1 | Adder | 0.57 MW | 0.49 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 966041 | AG1-473 C | 50/50 | 5.0 MW | 5.0 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 966042 | AG1-473 E | 50/50 | 3.33 MW | 3.33 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 290086 | Q-036 E | Adder | 2.85 MW | 2.42 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 934371 | AD1-061 C | Adder | -0.47 MW | -0.4 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 936061 | AD2-009 C | Adder | -3.23 MW | -2.74 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 936991 | AD2-133 C | Adder | 1.07 MW | 0.91 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 936992 | AD2-133 E | Adder | 4.92 MW | 4.18 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942121 | AE2-224 C | Adder | 3.49 MW | 2.96 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942122 | AE2-224 E | Adder | 2.32 MW | 1.98 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942351 | AE2-248 C | 50/50 | 1.18 MW | 1.18 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942352 | AE2-248 E | 50/50 | 0.79 MW | 0.79 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942491 | AE2-262 C | Adder | 4.97 MW | 4.22 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942492 | AE2-262 E | Adder | 3.34 MW | 2.84 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942501 | AE2-263 C | Adder | 4.67 MW | 3.97 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942502 | AE2-263 E | Adder | 3.12 MW | 2.65 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944311 | AF1-099 C | Adder | 6.95 MW | 5.91 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944312 | AF1-099 E | Adder | 4.63 MW | 3.94 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944321 | AF1-100 C | Adder | 12.8 MW | 10.88 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944322 | AF1-100 E | Adder | 8.53 MW | 7.25 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944471 | AF1-112 C | 50/50 | 1.09 MW | 1.09 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944472 | AF1-112 E | 50/50 | 0.75 MW | 0.75 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944691 | AF1-134 C | Adder | 0.7 MW | 0.59 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944692 | AF1-134 E | Adder | 0.46 MW | 0.4 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944771 | AF1-142 C | Adder | 11.12 MW | 9.45 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944772 | AF1-142 E | Adder | 7.41 MW | 6.3 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944881 | AF1-153 C O1 | Adder | 0.78 MW | 0.66 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944882 | AF1-153 E O1 | Adder | 0.52 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944901 | AF1-155 C | Adder | 0.77 MW | 0.66 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944902 | AF1-155 E | Adder | 0.51 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 945591 | AF1-224 C | Adder | -0.5 MW | -0.43 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958871 | AF2-178 | Adder | -0.91 MW | -0.78 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958881 | AF2-179 | Adder | -0.4 MW | -0.34 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958891 | AF2-180 | Adder | -0.4 MW | -0.34 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958931 | AF2-184 | Adder | -0.36 MW | -0.3 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958941 | AF2-185 | Adder | -0.22 MW | -0.19 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 959802 | AF2-271 E | Adder | 0.28 MW | 0.24 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 960022 | AF2-293 E | 50/50 | 0.14 MW | 0.14 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 960041 | AF2-295 C | Adder | 0.77 MW | 0.66 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 960042 | AF2-295 E | Adder | 0.51 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 960051 | AF2-296 C | Adder | 0.7 MW | 0.59 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 960052 | AF2-296 E | Adder | 0.46 MW | 0.4 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 200852 | 26WARR RDG | 50/50 | 0.26 MW | 0.26 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 200883 | Q-053 E | Adder | 1.66 MW | 1.41 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 235003 | AC1-025 E | 50/50 | 0.19 MW | 0.19 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 236828 | 01GRAYMONT | 50/50 | 0.48 MW | 0.48 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 293301 | N-039 E | Adder | 4.28 MW | 3.64 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 294515 | O38_P22 | Adder | 3.74 MW | 3.18 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 938384 | AE1-071-C | 50/50 | 6.65 MW | 6.65 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 939591 | AE1-188 C | Adder | -0.8 MW | -0.68 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 940201 | AE2-001 C | 50/50 | 1.43 MW | 1.43 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 940202 | AE2-001 E | 50/50 | 0.96 MW | 0.96 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 940671 | AE2-054 C | Adder | -0.73 MW | -0.62 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 940681 | AE2-055 C | 50/50 | 1.5 MW | 1.5 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 940682 | AE2-055 E | 50/50 | 1.0 MW | 1.0 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941231 | AE2-117 C | 50/50 | 1.23 MW | 1.23 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941232 | AE2-117 E | 50/50 | 0.82 MW | 0.82 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941241 | AE2-118 C | Adder | 1.16 MW | 0.99 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941242 | AE2-118 E | Adder | 0.78 MW | 0.66 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941271 | AE2-121 C | 50/50 | 0.76 MW | 0.76 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941272 | AE2-121 E | 50/50 | 0.5 MW | 0.5 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941321 | AE2-126 C | Adder | 0.82 MW | 0.69 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941322 | AE2-126 E | Adder | 0.54 MW | 0.46 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941331 | AE2-129 C | Adder | 0.86 MW | 0.73 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941332 | AE2-129 E | Adder | 0.57 MW | 0.49 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941351 | AE2-131 C | Adder | 0.86 MW | 0.73 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941352 | AE2-131 E | Adder | 0.57 MW | 0.49 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957451 | AF2-039 C | Adder | 0.61 MW | 0.52 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957452 | AF2-039 E | Adder | 0.4 MW | 0.34 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957561 | AF2-050 C | Adder | 1.74 MW | 1.48 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957562 | AF2-050 E | Adder | 1.16 MW | 0.99 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957931 | AF2-087 C | Adder | 0.22 MW | 0.19 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957932 | AF2-087 E | Adder | 0.31 MW | 0.26 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957941 | AF2-088 C | Adder | 0.29 MW | 0.25 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957942 | AF2-088 E | Adder | 0.2 MW | 0.17 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958271 | AF2-121 C | Adder | 0.86 MW | 0.73 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958272 | AF2-121 E | Adder | 0.57 MW | 0.49 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 200812 | 26ALY HYDR | 50/50 | 0.44 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 938751 | AE1-101 C | Adder | -7.15 MW | -6.07 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964451 | AG1-308 C O1 | Adder | 0.59 MW | 0.5 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964452 | AG1-308 E O1 | Adder | 0.83 MW | 0.7 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 946421 | AF2-000A C | Adder | 3.37 MW | 2.86 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 946422 | AF2-000A E | Adder | 10.1 MW | 8.59 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 938385 | AE1-071-E | 50/50 | 24.72 MW | 24.72 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 959843 | AF2-275 BAT | Adder | 0.12 MW | 0.1 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 959853 | AF2-276 BAT | Adder | 0.12 MW | 0.1 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 966463 | AG1-515 BAT | Adder | 0.91 MW | 0.77 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.17 MW | 0.17 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.05 MW | 0.05 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.89 MW | 0.89 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.11 MW | 2.11 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.44 MW | 0.44 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.36 MW | 0.36 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.11 MW | 0.11 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.03 MW | 0.03 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.07 MW | 2.07 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| AE1-071-POI-26ROXBURY 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 962411 | AG1-090 C O1 | 50/50 | 41.62 MW | 41.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 962412 | AG1-090 E O1 | 50/50 | 10.41 MW | 10.41 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 964391 | AG1-301 C | Adder | 1.02 MW | 0.86 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 964392 | AG1-301 E | Adder | 0.68 MW | 0.58 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 965121 | AG1-377 C O1 | 50/50 | 6.24 MW | 6.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 965122 | AG1-377 E O1 | 50/50 | 4.16 MW | 4.16 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 965131 | AG1-378 C O1 | 50/50 | 6.24 MW | 6.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 965132 | AG1-378 E O1 | 50/50 | 4.16 MW | 4.16 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 290086 | Q-036 E | 50/50 | 15.76 MW | 15.76 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 936991 | AD2-133 C | 50/50 | 5.93 MW | 5.93 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 936992 | AD2-133 E | 50/50 | 27.17 MW | 27.17 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 959802 | AF2-271 E | 50/50 | 0.47 MW | 0.47 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 200722 | 26SHAWVL 2 | 50/50 | 18.59 MW | 18.59 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 200852 | 26WARR RDG | Adder | 0.21 MW | 0.18 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 200883 | Q-053 E | 50/50 | 3.77 MW | 3.77 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 941231 | AE2-117 C | 50/50 | 1.23 MW | 1.23 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 941232 | AE2-117 E | 50/50 | 0.82 MW | 0.82 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 941331 | AE2-129 C | 50/50 | 6.24 MW | 6.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 941332 | AE2-129 E | 50/50 | 4.16 MW | 4.16 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 941351 | AE2-131 C | 50/50 | 6.24 MW | 6.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 941352 | AE2-131 E | 50/50 | 4.16 MW | 4.16 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 957451 | AF2-039 C | 50/50 | 5.62 MW | 5.62 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 957452 | AF2-039 E | 50/50 | 3.75 MW | 3.75 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 957931 | AF2-087 C | Adder | 0.27 MW | 0.23 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 957932 | AF2-087 E | Adder | 0.37 MW | 0.31 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 957941 | AF2-088 C | 50/50 | 2.71 MW | 2.71 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 957942 | AF2-088 E | 50/50 | 1.8 MW | 1.8 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 958271 | AF2-121 C | 50/50 | 6.24 MW | 6.24 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 958272 | AF2-121 E | 50/50 | 4.16 MW | 4.16 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 200915 | 26CHSTN_FL | 50/50 | 0.13 MW | 0.13 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 964451 | AG1-308 C O1 | 50/50 | 4.32 MW | 4.32 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 964452 | AG1-308 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | 200905 | 26Q36 | 50/50 | 0.54 MW | 0.54 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.13 MW | 0.13 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.06 MW | 0.06 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.1 MW | 0.1 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.2 MW | 0.2 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.02 MW | 0.02 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.39 MW | 1.39 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.02 MW | 0.02 MW |
| 26SHAWVL 2-26SHAWVL 2 115.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-115-062T | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 962411 | AG1-090 C O1 | Adder | 5.74 MW | 4.88 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 962412 | AG1-090 E O1 | Adder | 1.44 MW | 1.22 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964031 | AG1-257 C | 50/50 | 1.01 MW | 1.01 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964032 | AG1-257 E | 50/50 | 1.42 MW | 1.42 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964201 | AG1-281 C | Adder | 0.68 MW | 0.58 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964202 | AG1-281 E | Adder | 0.46 MW | 0.39 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964391 | AG1-301 C | 50/50 | 1.27 MW | 1.27 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964392 | AG1-301 E | 50/50 | 0.84 MW | 0.84 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 965121 | AG1-377 C O1 | Adder | 0.86 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 965122 | AG1-377 E O1 | Adder | 0.57 MW | 0.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 965131 | AG1-378 C O1 | Adder | 0.86 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 965132 | AG1-378 E O1 | Adder | 0.57 MW | 0.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 966041 | AG1-473 C | 50/50 | 5.01 MW | 5.01 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 966042 | AG1-473 E | 50/50 | 3.34 MW | 3.34 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 290086 | Q-036 E | Adder | 2.87 MW | 2.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 934371 | AD1-061 C | Adder | -0.47 MW | -0.4 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 936061 | AD2-009 C | Adder | -3.21 MW | -2.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 936991 | AD2-133 C | Adder | 1.08 MW | 0.92 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 936992 | AD2-133 E | Adder | 4.94 MW | 4.2 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942121 | AE2-224 C | Adder | 3.51 MW | 2.98 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942122 | AE2-224 E | Adder | 2.34 MW | 1.99 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942351 | AE2-248 C | 50/50 | 1.18 MW | 1.18 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942352 | AE2-248 E | 50/50 | 0.79 MW | 0.79 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942491 | AE2-262 C | Adder | 4.99 MW | 4.24 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942492 | AE2-262 E | Adder | 3.35 MW | 2.85 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942501 | AE2-263 C | Adder | 4.69 MW | 3.98 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942502 | AE2-263 E | Adder | 3.13 MW | 2.66 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942961 | AE2-316 C | Adder | 2.07 MW | 1.76 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 942962 | AE2-316 E | Adder | 2.45 MW | 2.08 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944311 | AF1-099 C | Adder | 6.97 MW | 5.93 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944312 | AF1-099 E | Adder | 4.65 MW | 3.95 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944321 | AF1-100 C | Adder | 12.84 MW | 10.92 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944322 | AF1-100 E | Adder | 8.56 MW | 7.28 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944471 | AF1-112 C | 50/50 | 1.09 MW | 1.09 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944472 | AF1-112 E | 50/50 | 0.75 MW | 0.75 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944691 | AF1-134 C | Adder | 0.7 MW | 0.6 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944692 | AF1-134 E | Adder | 0.47 MW | 0.4 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944771 | AF1-142 C | Adder | 11.16 MW | 9.48 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944772 | AF1-142 E | Adder | 7.44 MW | 6.32 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944881 | AF1-153 C O1 | Adder | 0.78 MW | 0.66 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944882 | AF1-153 E O1 | Adder | 0.52 MW | 0.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944901 | AF1-155 C | Adder | 0.78 MW | 0.66 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 944902 | AF1-155 E | Adder | 0.52 MW | 0.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 945591 | AF1-224 C | Adder | -0.5 MW | -0.43 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958871 | AF2-178 | Adder | -0.91 MW | -0.78 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958881 | AF2-179 | Adder | -0.39 MW | -0.34 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958891 | AF2-180 | Adder | -0.39 MW | -0.34 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958931 | AF2-184 | Adder | -0.36 MW | -0.3 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 959802 | AF2-271 E | Adder | 0.28 MW | 0.24 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 960022 | AF2-293 E | 50/50 | 0.14 MW | 0.14 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 960041 | AF2-295 C | Adder | 0.78 MW | 0.66 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 960042 | AF2-295 E | Adder | 0.52 MW | 0.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 960051 | AF2-296 C | Adder | 0.7 MW | 0.6 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 960052 | AF2-296 E | Adder | 0.47 MW | 0.4 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 200852 | 26WARR RDG | 50/50 | 0.26 MW | 0.26 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 200883 | Q-053 E | Adder | 1.67 MW | 1.42 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 235003 | AC1-025 E | 50/50 | 0.19 MW | 0.19 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 236828 | 01GRAYMONT | 50/50 | 0.48 MW | 0.48 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 293301 | N-039 E | Adder | 4.3 MW | 3.65 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 294515 | O38_P22 | Adder | 3.76 MW | 3.2 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 939591 | AE1-188 C | Adder | -0.8 MW | -0.68 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 940201 | AE2-001 C | 50/50 | 1.44 MW | 1.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 940202 | AE2-001 E | 50/50 | 0.96 MW | 0.96 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 940671 | AE2-054 C | Adder | -0.73 MW | -0.62 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 940681 | AE2-055 C | 50/50 | 1.51 MW | 1.51 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 940682 | AE2-055 E | 50/50 | 1.0 MW | 1.0 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941191 | AE2-113 C | Adder | 3.11 MW | 2.64 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941192 | AE2-113 E | Adder | 2.92 MW | 2.48 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941231 | AE2-117 C | 50/50 | 1.23 MW | 1.23 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941232 | AE2-117 E | 50/50 | 0.82 MW | 0.82 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941241 | AE2-118 C | Adder | 1.17 MW | 0.99 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941242 | AE2-118 E | Adder | 0.78 MW | 0.66 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941271 | AE2-121 C | 50/50 | 0.76 MW | 0.76 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941272 | AE2-121 E | 50/50 | 0.51 MW | 0.51 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941321 | AE2-126 C | Adder | 0.82 MW | 0.7 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941322 | AE2-126 E | Adder | 0.55 MW | 0.47 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941331 | AE2-129 C | Adder | 0.86 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941332 | AE2-129 E | Adder | 0.57 MW | 0.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941351 | AE2-131 C | Adder | 0.86 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 941352 | AE2-131 E | Adder | 0.57 MW | 0.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 946381 | AF1-302 C | Adder | 0.9 MW | 0.77 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 946382 | AF1-302 E | Adder | 1.21 MW | 1.02 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957451 | AF2-039 C | Adder | 0.61 MW | 0.52 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957452 | AF2-039 E | Adder | 0.41 MW | 0.35 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957561 | AF2-050 C | Adder | 1.75 MW | 1.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957562 | AF2-050 E | Adder | 1.17 MW | 0.99 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957931 | AF2-087 C | Adder | 0.23 MW | 0.19 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957932 | AF2-087 E | Adder | 0.31 MW | 0.26 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957941 | AF2-088 C | Adder | 0.29 MW | 0.25 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 957942 | AF2-088 E | Adder | 0.2 MW | 0.17 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958271 | AF2-121 C | Adder | 0.86 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 958272 | AF2-121 E | Adder | 0.57 MW | 0.49 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 200812 | 26ALY HYDR | 50/50 | 0.44 MW | 0.44 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 938751 | AE1-101 C | Adder | -7.11 MW | -6.05 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964451 | AG1-308 C O1 | Adder | 0.6 MW | 0.51 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 964452 | AG1-308 E O1 | Adder | 0.83 MW | 0.71 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 946421 | AF2-000A C | Adder | 3.38 MW | 2.88 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 946422 | AF2-000A E | Adder | 10.15 MW | 8.62 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 959843 | AF2-275 BAT | Adder | 0.12 MW | 0.1 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 959853 | AF2-276 BAT | Adder | 0.12 MW | 0.1 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | 966463 | AG1-515 BAT | Adder | 0.9 MW | 0.77 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.15 MW | 0.15 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.93 MW | 0.93 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.57 MW | 2.57 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.73 MW | 0.73 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.09 MW | 0.09 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.08 MW | 0.08 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.08 MW | 0.08 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.2 MW | 0.2 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.85 MW | 1.85 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.05 MW | 0.05 MW |
| 26SHADE GP-AE1-071-POI 115.0 kV Ckt 1 line l/o PL:10:P24:100548 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 962411 | AG1-090 C O1 | 50/50 | 25.39 MW | 25.39 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 962412 | AG1-090 E O1 | 50/50 | 6.35 MW | 6.35 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 965121 | AG1-377 C O1 | 50/50 | 3.81 MW | 3.81 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 965122 | AG1-377 E O1 | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 965131 | AG1-378 C O1 | 50/50 | 3.81 MW | 3.81 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 965132 | AG1-378 E O1 | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 290086 | Q-036 E | 50/50 | 9.72 MW | 9.72 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 936991 | AD2-133 C | 50/50 | 3.66 MW | 3.66 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 936992 | AD2-133 E | 50/50 | 16.76 MW | 16.76 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 944181 | AF1-086 C O1 | 50/50 | 3.31 MW | 3.31 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 944182 | AF1-086 E O1 | 50/50 | 14.4 MW | 14.4 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 944691 | AF1-134 C | 50/50 | 3.27 MW | 3.27 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 944692 | AF1-134 E | 50/50 | 2.18 MW | 2.18 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 945181 | AF1-183 | 50/50 | 0.1 MW | 0.1 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 959802 | AF2-271 E | Adder | 0.28 MW | 0.24 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 960051 | AF2-296 C | 50/50 | 3.27 MW | 3.27 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 960052 | AF2-296 E | 50/50 | 2.18 MW | 2.18 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 200715 | 26SHAWVL 1 | 50/50 | 12.7 MW | 12.7 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 200722 | 26SHAWVL 2 | 50/50 | 8.96 MW | 8.96 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 200883 | Q-053 E | Adder | 2.61 MW | 2.22 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 200913 | 26SHAW-D | 50/50 | 0.43 MW | 0.43 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 236828 | 01GRAYMONT | Adder | -0.34 MW | -0.29 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 293393 | V3-030E | Adder | 2.27 MW | 1.93 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 941321 | AE2-126 C | 50/50 | 2.65 MW | 2.65 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 941322 | AE2-126 E | 50/50 | 1.77 MW | 1.77 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 941331 | AE2-129 C | 50/50 | 3.81 MW | 3.81 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 941332 | AE2-129 E | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 941351 | AE2-131 C | 50/50 | 3.81 MW | 3.81 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 941352 | AE2-131 E | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 957451 | AF2-039 C | 50/50 | 3.41 MW | 3.41 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 957452 | AF2-039 E | 50/50 | 2.27 MW | 2.27 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 957941 | AF2-088 C | 50/50 | 1.64 MW | 1.64 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 957942 | AF2-088 E | 50/50 | 1.09 MW | 1.09 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 958271 | AF2-121 C | 50/50 | 3.81 MW | 3.81 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 958272 | AF2-121 E | 50/50 | 2.54 MW | 2.54 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 964451 | AG1-308 C O1 | 50/50 | 2.63 MW | 2.63 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 964452 | AG1-308 E O1 | 50/50 | 3.68 MW | 3.68 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 200905 | 26Q36 | 50/50 | 0.33 MW | 0.33 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 960023 | AF2-293 BAT | Adder | 0.12 MW | 0.1 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | 235007 | AC1-025 BAT | Adder | 0.14 MW | 0.12 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.03 MW | 0.03 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.79 MW | 0.79 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.59 MW | 1.59 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.94 MW | 0.94 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.04 MW | 0.04 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.47 MW | 0.47 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.17 MW | 0.17 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.07 MW | 0.07 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.17 MW | 0.17 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.46 MW | 0.46 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.16 MW | 3.16 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.14 MW | 0.14 MW |
| 26SHAWVL 1-26SHAWVL 1 115.0/230.0 kV Ckt 1A transformer l/o PN-P2-2-PN-230-014T | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 965241 | AG1-392C C O | 50/50 | 1.63 MW | 1.63 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 965242 | AG1-392C E O | 50/50 | 1.09 MW | 1.09 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 965251 | AG1-392B C O | 50/50 | 1.63 MW | 1.63 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 965252 | AG1-392B E O | 50/50 | 1.09 MW | 1.09 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 965261 | AG1-392A C O | 50/50 | 3.26 MW | 3.26 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 965262 | AG1-392A E O | 50/50 | 2.17 MW | 2.17 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 965271 | AG1-392 C O1 | 50/50 | 3.26 MW | 3.26 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 965272 | AG1-392 E O1 | 50/50 | 2.17 MW | 2.17 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 203349 | 26Z1-069 C | 50/50 | 0.28 MW | 0.28 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 236828 | 01GRAYMONT | Adder | -0.24 MW | -0.2 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 916202 | Z1-069 E | 50/50 | 7.08 MW | 7.08 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 931091 | AB1-160 C | 50/50 | 0.08 MW | 0.08 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 931092 | AB1-160 E | 50/50 | 2.02 MW | 2.02 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 940861 | AE2-074 C | 50/50 | 2.59 MW | 2.59 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 940862 | AE2-074 E | 50/50 | 3.41 MW | 3.41 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 941191 | AE2-113 C | 50/50 | 29.44 MW | 29.44 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 941192 | AE2-113 E | 50/50 | 27.64 MW | 27.64 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 941321 | AE2-126 C | Adder | -1.87 MW | -1.59 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 941331 | AE2-129 C | Adder | -0.76 MW | -0.65 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 946111 | AF1-276 C | 50/50 | 8.83 MW | 8.83 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 946112 | AF1-276 E | 50/50 | 4.35 MW | 4.35 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 946121 | AF1-277 C | 50/50 | 8.83 MW | 8.83 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 946122 | AF1-277 E | 50/50 | 4.35 MW | 4.35 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 946131 | AF1-278 C | 50/50 | 7.05 MW | 7.05 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 946132 | AF1-278 E | 50/50 | 3.5 MW | 3.5 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 962413 | AG1-090 BAT | Adder | 3.75 MW | 3.19 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 946423 | AF2-000A BAT | 50/50 | 21.83 MW | 21.83 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 960023 | AF2-293 BAT | Adder | 0.08 MW | 0.07 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | 235007 | AC1-025 BAT | Adder | 0.1 MW | 0.09 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.01 MW | 0.01 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 1.42 MW | 1.42 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.03 MW | 0.03 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.43 MW | 0.43 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.3 MW | 1.3 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.66 MW | 0.66 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.02 MW | 0.02 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.14 MW | 0.14 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.12 MW | 0.12 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.84 MW | 0.84 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.09 MW | 0.09 MW |
| AE2-113 TAP-26RIDGWAY 115.0 kV Ckt 1 line l/o PN-P7-1-PN-230-002A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 962411 | AG1-090 C O1 | 50/50 | 14.98 MW | 14.98 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 962412 | AG1-090 E O1 | 50/50 | 3.75 MW | 3.75 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 964031 | AG1-257 C | 50/50 | 4.19 MW | 4.19 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 964032 | AG1-257 E | 50/50 | 5.86 MW | 5.86 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965121 | AG1-377 C O1 | 50/50 | 2.25 MW | 2.25 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965122 | AG1-377 E O1 | 50/50 | 1.5 MW | 1.5 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965131 | AG1-378 C O1 | 50/50 | 2.25 MW | 2.25 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965132 | AG1-378 E O1 | 50/50 | 1.5 MW | 1.5 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965241 | AG1-392C C O | Adder | 1.46 MW | 1.24 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965242 | AG1-392C E O | Adder | 0.98 MW | 0.83 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965251 | AG1-392B C O | Adder | 1.46 MW | 1.24 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965252 | AG1-392B E O | Adder | 0.98 MW | 0.83 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965261 | AG1-392A C O | Adder | 2.92 MW | 2.49 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965262 | AG1-392A E O | Adder | 1.95 MW | 1.66 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965271 | AG1-392 C O1 | Adder | 2.92 MW | 2.49 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 965272 | AG1-392 E O1 | Adder | 1.95 MW | 1.66 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 290086 | Q-036 E | Adder | 5.39 MW | 4.58 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 936991 | AD2-133 C | Adder | 2.03 MW | 1.73 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 936992 | AD2-133 E | Adder | 9.3 MW | 7.91 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942351 | AE2-248 C | 50/50 | 4.9 MW | 4.9 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942352 | AE2-248 E | 50/50 | 3.27 MW | 3.27 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942491 | AE2-262 C | 50/50 | 20.1 MW | 20.1 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942492 | AE2-262 E | 50/50 | 13.51 MW | 13.51 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942501 | AE2-263 C | 50/50 | 18.89 MW | 18.89 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942502 | AE2-263 E | 50/50 | 12.61 MW | 12.61 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942961 | AE2-316 C | 50/50 | 7.19 MW | 7.19 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 942962 | AE2-316 E | 50/50 | 8.52 MW | 8.52 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944181 | AF1-086 C O1 | Adder | 2.28 MW | 1.94 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944182 | AF1-086 E O1 | Adder | 9.9 MW | 8.42 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944311 | AF1-099 C | 50/50 | 27.75 MW | 27.75 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944312 | AF1-099 E | 50/50 | 18.5 MW | 18.5 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944321 | AF1-100 C | 50/50 | 49.79 MW | 49.79 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944322 | AF1-100 E | 50/50 | 33.19 MW | 33.19 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944411 | AF1-106 O1 | Adder | 2.37 MW | 2.01 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944471 | AF1-112 C | 50/50 | 4.52 MW | 4.52 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944472 | AF1-112 E | 50/50 | 3.1 MW | 3.1 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944691 | AF1-134 C | 50/50 | 2.09 MW | 2.09 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944692 | AF1-134 E | 50/50 | 1.39 MW | 1.39 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944771 | AF1-142 C | 50/50 | 44.39 MW | 44.39 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944772 | AF1-142 E | 50/50 | 29.59 MW | 29.59 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944881 | AF1-153 C O1 | 50/50 | 2.89 MW | 2.89 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944882 | AF1-153 E O1 | 50/50 | 1.93 MW | 1.93 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944901 | AF1-155 C | 50/50 | 2.87 MW | 2.87 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 944902 | AF1-155 E | 50/50 | 1.91 MW | 1.91 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 945161 | AF1-181 | 50/50 | 0.04 MW | 0.04 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 945171 | AF1-182 | 50/50 | 0.23 MW | 0.23 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 945181 | AF1-183 | 50/50 | 0.05 MW | 0.05 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 959471 | AF2-238 C | Adder | 1.52 MW | 1.29 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 959472 | AF2-238 E | Adder | 1.01 MW | 0.86 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960022 | AF2-293 E | 50/50 | 0.57 MW | 0.57 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960031 | AF2-294 C | Adder | 1.15 MW | 0.98 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960032 | AF2-294 E | Adder | 0.77 MW | 0.65 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960041 | AF2-295 C | 50/50 | 2.87 MW | 2.87 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960042 | AF2-295 E | 50/50 | 1.91 MW | 1.91 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960051 | AF2-296 C | 50/50 | 2.09 MW | 2.09 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 960052 | AF2-296 E | 50/50 | 1.39 MW | 1.39 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 961141 | AF2-405 | Adder | 1.18 MW | 1.01 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 961151 | AF2-406 | Adder | 8.88 MW | 7.54 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 961211 | AF2-412 | Adder | 14.43 MW | 12.27 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 961451 | AF2-436 | Adder | 0.19 MW | 0.16 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200649 | 26PENNTECH | 50/50 | 1.61 MW | 1.61 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200665 | 26SHAWVL 3 | 50/50 | 9.87 MW | 9.87 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200666 | 26SHAWVL 4 | 50/50 | 9.71 MW | 9.71 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200715 | 26SHAWVL 1 | 50/50 | 6.18 MW | 6.18 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200722 | 26SHAWVL 2 | 50/50 | 6.32 MW | 6.32 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200823 | 26MHP_X3-003 | Adder | 7.34 MW | 6.24 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200894 | 26K02 | 50/50 | 11.1 MW | 11.1 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 200913 | 26SHAW-D | 50/50 | 0.26 MW | 0.26 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 203932 | AA2-133 GEN | Adder | 2.46 MW | 2.09 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 203999 | P-047 E | Adder | 9.42 MW | 8.01 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 235003 | AC1-025 E | 50/50 | 0.77 MW | 0.77 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 236828 | 01GRAYMONT | 50/50 | 1.98 MW | 1.98 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 294573 | P-028 E | Adder | 14.2 MW | 12.07 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 916202 | Z1-069 E | Adder | 6.84 MW | 5.81 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 931092 | AB1-160 E | Adder | 1.95 MW | 1.66 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940201 | AE2-001 C | 50/50 | 5.93 MW | 5.93 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940202 | AE2-001 E | 50/50 | 3.96 MW | 3.96 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940681 | AE2-055 C | 50/50 | 6.26 MW | 6.26 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940682 | AE2-055 E | 50/50 | 4.17 MW | 4.17 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940861 | AE2-074 C | Adder | 1.9 MW | 1.62 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 940862 | AE2-074 E | Adder | 2.5 MW | 2.13 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941191 | AE2-113 C | 50/50 | 10.74 MW | 10.74 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941192 | AE2-113 E | 50/50 | 10.08 MW | 10.08 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941271 | AE2-121 C | 50/50 | 3.12 MW | 3.12 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941272 | AE2-121 E | 50/50 | 2.09 MW | 2.09 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941321 | AE2-126 C | 50/50 | 2.88 MW | 2.88 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941322 | AE2-126 E | 50/50 | 1.92 MW | 1.92 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941331 | AE2-129 C | 50/50 | 2.25 MW | 2.25 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941332 | AE2-129 E | 50/50 | 1.5 MW | 1.5 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941351 | AE2-131 C | 50/50 | 2.25 MW | 2.25 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941352 | AE2-131 E | 50/50 | 1.5 MW | 1.5 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941421 | AE2-139 C | Adder | 8.36 MW | 7.1 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 941422 | AE2-139 E | Adder | 5.57 MW | 4.74 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946111 | AF1-276 C | Adder | 8.42 MW | 7.16 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946112 | AF1-276 E | Adder | 4.15 MW | 3.52 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946121 | AF1-277 C | Adder | 8.42 MW | 7.16 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946122 | AF1-277 E | Adder | 4.15 MW | 3.52 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946131 | AF1-278 C | Adder | 6.71 MW | 5.71 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946132 | AF1-278 E | Adder | 3.34 MW | 2.84 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946381 | AF1-302 C | 50/50 | 3.14 MW | 3.14 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946382 | AF1-302 E | 50/50 | 4.19 MW | 4.19 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 957451 | AF2-039 C | 50/50 | 2.09 MW | 2.09 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 957452 | AF2-039 E | 50/50 | 1.4 MW | 1.4 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 957941 | AF2-088 C | 50/50 | 1.01 MW | 1.01 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 957942 | AF2-088 E | 50/50 | 0.67 MW | 0.67 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 958271 | AF2-121 C | 50/50 | 2.25 MW | 2.25 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 958272 | AF2-121 E | 50/50 | 1.5 MW | 1.5 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 964451 | AG1-308 C O1 | 50/50 | 1.55 MW | 1.55 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 964452 | AG1-308 E O1 | 50/50 | 2.17 MW | 2.17 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946421 | AF2-000A C | 50/50 | 12.68 MW | 12.68 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | 946422 | AF2-000A E | 50/50 | 38.05 MW | 38.05 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 2.43 MW | 2.43 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.72 MW | 2.72 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.67 MW | 10.67 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.24 MW | 5.24 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.1 MW | 0.1 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.22 MW | 2.22 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.05 MW | 1.05 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 14.21 MW | 14.21 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.72 MW | 0.72 MW |
| 01SHINGL-AG1-473 TAP 230.0 kV Ckt 1 line l/o PN-P2_1-PN-230-997-DRT-063 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
Light Load Analysis
The Queue Project was evaluated as a 100.0 MW (Capacity 80.0 MW) injection in the PENELEC area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| PENELEC |
26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer
999332 to 200726 ckt 2A |
PN-P2-2-PN-230-013T
CONTINGENCY 'PN-P2-2-PN-230-013T' DISCONNECT BRANCH FROM BUS 200710 TO BUS 200665 CKT 1 /*26SHAWVL 1 230.0 - 26SHAWVL 3 22.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 200726 CKT ZB /*26SHAWVL 1 230.0 - 26SHAWVL 2 230.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 944320 CKT 1 /*26SHAWVL 1 230.0 - AF1-100 TAP 230.0 END |
Bus | AC | 89.46 % | 100.38 % | 149.0 | B | 149.57 | 16.38 | |
| PENELEC |
26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer
999332 to 200726 ckt 2A |
PN-P2-3-PN-230-21DT
CONTINGENCY 'PN-P2-3-PN-230-21DT' DISCONNECT BRANCH FROM BUS 200665 TO BUS 200710 CKT 1 /*26SHAWVL 3 22.0 - 26SHAWVL 1 230.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 200714 TO BUS 200715 CKT 1A /*26SHAWVL 1 230.0 - 26SHAWVL 1 115.0 - 26SHAWVL 1 18.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 200726 CKT ZB /*26SHAWVL 1 230.0 - 26SHAWVL 2 230.0 DISCONNECT BRANCH FROM BUS 200710 TO BUS 944320 CKT 1 /*26SHAWVL 1 230.0 - AF1-100 TAP 230.0 END |
Breaker | AC | 89.43 % | 100.36 % | 149.0 | B | 149.54 | 16.38 | |
| Details for 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 200666 | 26SHAWVL 4 | Adder | -14.99 MW | -12.74 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 200715 | 26SHAWVL 1 | 50/50 | 23.74 MW | 23.74 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 200722 | 26SHAWVL 2 | 50/50 | 35.14 MW | 35.14 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 936991 | AD2-133 C | 50/50 | 3.02 MW | 3.02 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 936992 | AD2-133 E | 50/50 | 13.82 MW | 13.82 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 959802 | AF2-271 E | Adder | 0.14 MW | 0.12 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 962411 | AG1-090 C O1 | 50/50 | 6.55 MW | 6.55 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 962412 | AG1-090 E O1 | 50/50 | 9.83 MW | 9.83 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 200805 | 26COLVER13 | Adder | 3.15 MW | 2.68 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 200905 | 26Q36 | 50/50 | 0.8 MW | 0.8 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 290086 | Q-036 E | 50/50 | 4.17 MW | 4.17 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 944181 | AF1-086 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-2-PN-230-013T | 944182 | AF1-086 E O1 | 50/50 | 11.8 MW | 11.8 MW |
| Details for 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 200666 | 26SHAWVL 4 | Adder | -14.99 MW | -12.74 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 200715 | 26SHAWVL 1 | 50/50 | 23.74 MW | 23.74 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 200722 | 26SHAWVL 2 | 50/50 | 35.14 MW | 35.14 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 936991 | AD2-133 C | 50/50 | 3.02 MW | 3.02 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 936992 | AD2-133 E | 50/50 | 13.82 MW | 13.82 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 959802 | AF2-271 E | Adder | 0.14 MW | 0.12 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 962411 | AG1-090 C O1 | 50/50 | 6.55 MW | 6.55 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 962412 | AG1-090 E O1 | 50/50 | 9.83 MW | 9.83 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 200805 | 26COLVER13 | Adder | 3.15 MW | 2.68 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 200905 | 26Q36 | 50/50 | 0.8 MW | 0.8 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 290086 | Q-036 E | 50/50 | 4.17 MW | 4.17 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 944181 | AF1-086 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 26SHAWVL 2-26SHAWVL 2 1.0/230.0 kV Ckt 2A transformer l/o PN-P2-3-PN-230-21DT | 944182 | AF1-086 E O1 | 50/50 | 11.8 MW | 11.8 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n6823.1 | Replace 1033.5 ACSR 54/7 SCCIR (Bus taps, bus & line side disconnect leads, line risers) at Shingletown substation. | $330,000 | |
| n6823.2 | Replace circuit breaker and its CTs at Shingletown Substation. | $610,000 | |
| n6823.3 | Replace 1200 A bus & line side disconnect switches at Shingletown substation. | $720,000 | |
| n6823.4 | Replace 2.00 IPS AL Pipe SCCIR (Line & bus side breaker risers) at Shingletown substation. | $162,816 | |
| n6823.5 | Replace ZR relays at Shingletown substation. | $1,628,156 | |
| b3665 | Replace several pieces of 1033.5 AAC substation conductor at East Towanda 230 kV | $407,700 | |
| n7127.2 | Reconductor 13.01 miles of the East Towanda - Canyon 230 kV Line. Replace transmission line drop at East Towanda. | $55,735,000 | |
| n7127.3 | Replace disconnect switch at Canyon | $275,000 | |
| n6855.1 | Replace substation conductor at Warren and Glade substations | $350,000 | |
| n6855.2 | Rebuild 11.53 miles of transmission line between Warren and Glade. | $42,390,000 | |
| n6855.3 | Replace line trap at Glade | $230,000 | |
| s2279.3 | Replace line trap at Homer City on the Homer City - Shelocta 230 kV Line. | $200,000 | |
| n8112 | Reconductor/rebuild the Homer City - Shelocta 230 kV (~11 miles) | $50,929,813 | |
| n8112.1 | Adjust/replace relays at Homer City and Shelocta substations. | $2,668,506 | |
| n8112.2 | Replace disconnect switches and substation conductor at Homer City Substation. | $3,333,312 | |
| n8112.3 | Replace disconnect switches and leads at Shelocta Substation | $1,744,708 | |
| n6823.6 | Replace wave traps at Shingletown & Lewistown substations (APS/Penelec) | $800,000 | |
| n8219 | Reconductor 13.9 miles of transmission line on the AG1-473 (Shingletown) - Lewistown 230 kV Line. | $59,794,920 | |
| n6822.2 | Adjust relay settings at Lewistown | $1,528,500 | |
| n7605 | Reconductor 9.24 miles of the Canyon - North Meshoppen 230 kV Line | $39,640,000 | |
| n7606 | Replace disconnect switch at Canyon | $275,000 | |
| n8229 | Reconductor 18.7 miles the AE2-113 (Farmers Valley) - Ridgway 115 kV Line | $59,697,096 | |
| b3751 | Rebuild 6.4 miles of the Roxbury - Shade Gap 115 kV line from Roxbury to the AE1-071 115 kV ring bus with single circuit 115 kV construction | $15,030,000 | |
| b3752 | Rebuild 7.2 miles of the Shade Gap - AE1-071 115 kV line section of the Roxbury - Shade Gap 115 kV line | $17,430,000 | |
| n7654 | Replace Shawville 230/115-17.2 kV transformer 1A with a larger unit. | $5,600,000 | |
| b3708 | Install a new 230/115 kV transformer and associated facilities at Shawville. (Projected ISD 6/1/2026) | $8,775,000 | |
| n8192.1 | Adjust/replace relaying at Keystone and Shelocta substations. | $2,668,506 | |
| s2279.2 | Replace line trap at Keystone on the Keystone – Shelocta 230 kV Line. | $200,000 | |
| n8192 | Reconductor/rebuild the Shelocta - Keystone 230 kV line (~2.5 miles) | $13,311,228 | |
| n8192.2 | Replace substation conductor at Keystone substation | $1,142,812 | |
| n8192.3 | Replace line drops at Keystone Substation | $430,625 | |
| n8192.4 | Replace bus conductor at Keystone Substation | $1,142,812 | |
| n8192.5 | Replace disconnect switches at Keystone Substation | $2,629,706 | |
| n8192.6 | Replace breaker leads at Keystone Substation | $430,625 | |
| n8192.7 | Replace disconnect switches and leads at Shelocta Substation | $1,744,708 | |
| n8281 | Replace the Keystone #4 500/230 kV transformer with a larger unit and install a high side breaker | $41,580,000 | |
Attachments
Download all tables in report
| Uprate Chain | |||||
|---|---|---|---|---|---|
| Project | Project Status | MFO | MWE | MWC | Disposition |
| AG1-090 | Active | 100.0 | 100.0 | 80.0 | Transition Cycle 1 |
| AG1-377 | Active | 120.0 | 20.0 | 12.0 | Transition Cycle 1 |
| AG1-378 | Active | 140.0 | 20.0 | 12.0 | Transition Cycle 1 |
Conclusion
The Transition Sort load flow retool results indicate that AG1-090 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.