AF2-222 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:03
Madisonville DP-Twitty's Creek 115 kV
100.0 MW Capacity / 167.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF2-222 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the Dominion zone — Charlotte County, Virginia. The installed facilities will have a total capability of 167.0 MW with 100.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AF2-222 |
| Project Name | Madisonville DP-Twitty's Creek 115 kV |
| Developer Name | Virginia Electric and Power Company |
| State | Virginia |
| County | Charlotte |
| Transmission Owner | Dominion |
| MFO | 167.0 MW |
| MWE | 167.0 MW |
| MWC | 100.0 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2023 |
Point of Interconnection
AF2-222 will interconnect with the Dominion transmission system. The POI is a single line tap between Madisonville DP 115 kV substation and Twitty’s Creek 115 kV substation.
Summer Peak Analysis
The Queue Project was evaluated as a 167.0 MW (Capacity 100.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P7-1: LN 22-90-A
CONTINGENCY 'DVP_P7-1: LN 22-90-A' OPEN BRANCH FROM BUS 314265 TO BUS 314584 CKT 1 /*3FIVEFORKSDP 115.0 - 3LITTLTN 115.0 OPEN BRANCH FROM BUS 314265 TO BUS 314673 CKT 1 /*3FIVEFORKSDP 115.0 - 3PALMERSPRNG 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314571 TO BUS 925780 CKT 1 /*3EATON F 115.0 - AC1-054 TAP 115.0 OPEN BRANCH FROM BUS 314584 TO BUS 314585 CKT 1 /*3LITTLTN 115.0 - 3L GASTN 115.0 OPEN BUS 314265 /*3FIVEFORKSDP 115.0 OPEN BUS 314571 /*3EATON F 115.0 OPEN BUS 314584 /*3LITTLTN 115.0 OPEN BUS 314585 /*3L GASTN 115.0 END |
Tower | AC | 98.02 % | 110.25 % | 199.0 | B | 219.4 | 24.94 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P7-1: LN 22-90-B
CONTINGENCY 'DVP_P7-1: LN 22-90-B' OPEN BRANCH FROM BUS 314265 TO BUS 314584 CKT 1 /*3FIVEFORKSDP 115.0 - 3LITTLTN 115.0 OPEN BRANCH FROM BUS 314265 TO BUS 314673 CKT 1 /*3FIVEFORKSDP 115.0 - 3PALMERSPRNG 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314584 TO BUS 314585 CKT 1 /*3LITTLTN 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 925780 TO BUS 314702 CKT 1 /*AC1-054 TAP 115.0 - 3KERR 115.0 OPEN BUS 314265 /*3FIVEFORKSDP 115.0 OPEN BUS 314584 /*3LITTLTN 115.0 OPEN BUS 314585 /*3L GASTN 115.0 END |
Tower | AC | 88.1 % | 100.3 % | 199.0 | B | 199.6 | 24.94 | |
| DVP |
3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line
314679 to 314681 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314701 TO BUS 314707 CKT 1 /*3LONEPN 115.0 - 3MORAN 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | AC | 120.85 % | 195.09 % | 239.0 | C | 466.27 | 167.0 | |
| DVP |
3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line
314679 to 314681 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 END |
Breaker | AC | 120.84 % | 195.06 % | 239.0 | C | 466.19 | 167.0 | |
| DVP |
3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line
314679 to 314681 ckt 1 |
DVP_P4-2: 8442
CONTINGENCY 'DVP_P4-2: 8442' CHANGE BUS 314713 LOAD BY -100 PERCENT /*3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 76.07 % | 144.63 % | 239.0 | C | 345.67 | 167.0 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924021 /*AB2-043 C O1 115.0 OPEN BUS 924022 /*AB2-043 E O1 115.0 END |
Breaker | AC | 134.67 % | 182.38 % | 208.7 | C | 380.63 | 92.46 | |
| DVP |
6CARSON-6CHRL249 230.0 kV Ckt 1 line
314282 to 314285 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 154.2 % | 155.51 % | 684.0 | C | 1063.69 | 10.38 | |
| DVP |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line
314285 to 314316 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 151.36 % | 152.68 % | 684.0 | C | 1044.33 | 10.38 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 133.6 % | 141.9 % | 684.0 | C | 970.6 | 55.76 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 556T591-A
CONTINGENCY 'DVP_P4-2: 556T591-A' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 945810 TO BUS 314936 CKT 1 /*AF1-246 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 133.6 % | 141.9 % | 684.0 | C | 970.6 | 55.76 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 132.2 % | 140.3 % | 699.0 | C | 980.7 | 55.75 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 556T591-A
CONTINGENCY 'DVP_P4-2: 556T591-A' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 945810 TO BUS 314936 CKT 1 /*AF1-246 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 132.12 % | 140.21 % | 699.0 | C | 980.07 | 55.75 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924021 /*AB2-043 C O1 115.0 OPEN BUS 924022 /*AB2-043 E O1 115.0 END |
Breaker | AC | 102.26 % | 138.49 % | 221.4 | C | 306.62 | 74.47 | |
| DVP |
3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line
314722 to 314679 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314701 TO BUS 314707 CKT 1 /*3LONEPN 115.0 - 3MORAN 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | AC | 83.56 % | 134.4 % | 349.0 | C | 469.06 | 167.0 | |
| DVP |
3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line
314722 to 314679 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 END |
Breaker | AC | 83.55 % | 134.38 % | 349.0 | C | 468.99 | 167.0 | |
| DVP |
AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line
959310 to 314722 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314701 TO BUS 314707 CKT 1 /*3LONEPN 115.0 - 3MORAN 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | AC | 68.82 % | 111.99 % | 406.0 | C | 454.68 | 167.0 | |
| DVP |
AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line
959310 to 314722 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 END |
Breaker | AC | 68.82 % | 111.98 % | 406.0 | C | 454.64 | 167.0 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 END |
Breaker | AC | 95.37 % | 109.77 % | 199.0 | B | 218.44 | 30.86 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314701 TO BUS 314707 CKT 1 /*3LONEPN 115.0 - 3MORAN 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | AC | 94.47 % | 108.82 % | 199.0 | B | 216.55 | 30.81 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-6: CAROLIN T122
CONTINGENCY 'DVP_P4-6: CAROLIN T122' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314259 TO BUS 314559 CKT Z1 /*3CAROL56_1 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314578 CKT 1 /*3CAROLNA 115.0 - 3HORNRTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 315126 CKT 1 /*3CAROLNA 115.0 - 1ROARAP2 14.4 OPEN BRANCH FROM BUS 314559 TO BUS 315128 CKT 1 /*3CAROLNA 115.0 - 1ROARAP4 14.4 OPEN BUS 314559 /*3CAROLNA 115.0 OPEN BUS 315126 /*1ROARAP2 14.4 OPEN BUS 315128 /*1ROARAP4 14.4 END |
Breaker | AC | 92.19 % | 104.54 % | 199.0 | B | 208.03 | 25.23 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 8432
CONTINGENCY 'DVP_P4-2: 8432' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 85.68 % | 100.11 % | 199.0 | B | 199.22 | 30.81 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 102952
CONTINGENCY 'DVP_P4-2: 102952' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314572 CKT 1 /*3METCATP 115.0 - 3EMPORIA 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314588 CKT 1 /*3METCATP 115.0 - 3METCALF 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 314863 CKT 1 /*3EMPORIA 115.0 - 3EMPOR_1 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 925170 CKT 1 /*3EMPORIA 115.0 - AB2-174 TAP 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 OPEN BUS 314570 /*3METCATP 115.0 OPEN BUS 314572 /*3EMPORIA 115.0 OPEN BUS 314588 /*3METCALF 115.0 OPEN BUS 314863 /*3EMPOR_1 115.0 END |
Breaker | AC | 101.92 % | 106.32 % | 288.6 | C | 306.84 | 13.59 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 7152
CONTINGENCY 'DVP_P4-2: 7152' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314516 TO BUS 314676 CKT 1 /*3BRUNWICK_1 115.0 - 3BRUNWICK 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BRANCH FROM BUS 314565 TO BUS 314693 CKT 1 /*3CLUBHSE71 115.0 - 3FRMAN D 115.0 OPEN BRANCH FROM BUS 314565 TO BUS 314850 CKT 1 /*3CLUBHSE71 115.0 - 3CLUBHSE71_1 115.0 OPEN BRANCH FROM BUS 314675 TO BUS 314676 CKT 1 /*3BRODNAX 115.0 - 3BRUNWICK 115.0 OPEN BRANCH FROM BUS 314676 TO BUS 314704 CKT 1 /*3BRUNWICK 115.0 - 3LAWRENC 115.0 OPEN BRANCH FROM BUS 314693 TO BUS 314704 CKT 1 /*3FRMAN D 115.0 - 3LAWRENC 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314516 /*3BRUNWICK_1 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 OPEN BUS 314565 /*3CLUBHSE71 115.0 OPEN BUS 314676 /*3BRUNWICK 115.0 OPEN BUS 314693 /*3FRMAN D 115.0 OPEN BUS 314704 /*3LAWRENC 115.0 OPEN BUS 314782 /*2BRUNWICK 69.0 OPEN BUS 314785 /*2DANLTWN 69.0 OPEN BUS 314786 /*2GASBURG 69.0 OPEN BUS 314787 /*2BRUNWICK2 69.0 OPEN BUS 314850 /*3CLUBHSE71_1 115.0 OPEN BUS 314872 /*2BRUNSWICKDP 69.0 END |
Breaker | AC | 97.57 % | 101.97 % | 288.6 | C | 294.29 | 13.59 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 14852
CONTINGENCY 'DVP_P4-2: 14852' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 END |
Breaker | AC | 96.96 % | 101.36 % | 288.6 | C | 292.52 | 13.59 | |
| DVP |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line
314563 to 940480 ckt 1 |
DVP_P4-2: 246T247
CONTINGENCY 'DVP_P4-2: 246T247' OPEN BRANCH FROM BUS 313713 TO BUS 314648 CKT 1 /*6SWAMP 230.0 - 6SUNBURY 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 OPEN BUS 314648 /*6SUNBURY 230.0 END |
Breaker | AC | 98.67 % | 100.5 % | 830.0 | C | 834.15 | 17.83 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
DVP_P1-2: LN 1012-A
CONTINGENCY 'DVP_P1-2: LN 1012-A' OPEN BRANCH FROM BUS 314679 TO BUS 314681 CKT 1 /*3CENTRAL 115.0 - 3CHASCTY 115.0 OPEN BRANCH FROM BUS 314679 TO BUS 314722 CKT 1 /*3CENTRAL 115.0 - 3TWITTYS 115.0 OPEN BUS 314679 /*3CENTRAL 115.0 END |
Single | AC | 73.17 % | 119.91 % | 205.86 | B | 246.85 | 100.0 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
DVP_P1-2: LN 154-A
CONTINGENCY 'DVP_P1-2: LN 154-A' OPEN BRANCH FROM BUS 959310 TO BUS 314722 CKT 1 /*AF2-222 TAP 115.0 - 3TWITTYS 115.0 END |
Single | AC | 72.15 % | 118.89 % | 205.86 | B | 244.75 | 100.0 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
314679 3CENTRAL 115 314681 3CHASCTY 115 1
CONTINGENCY '314679 3CENTRAL 115 314681 3CHASCTY 115 1' OPEN BRANCH FROM BUS 314679 TO BUS 314681 CKT 1 /*3CENTRAL 115.0 - 3CHASCTY 115.0 END |
Single | AC | 71.9 % | 118.64 % | 205.86 | B | 244.23 | 100.0 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 314936 CKT 1 /*AF1-246 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 119.42 % | 125.4 % | 559.3 | B | 701.36 | 33.36 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A
CONTINGENCY '314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A' OPEN BRANCH FROM BUS 314906 TO BUS 945810 CKT 1 /*8CLOVER 500.0 - AF1-246 TAP 500.0 END |
Single | AC | 101.4 % | 107.39 % | 559.3 | B | 600.63 | 33.36 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 314936 CKT 1 /*AF1-246 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 118.1 % | 123.94 % | 571.52 | B | 708.34 | 33.35 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A
CONTINGENCY '314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A' OPEN BRANCH FROM BUS 314906 TO BUS 945810 CKT 1 /*8CLOVER 500.0 - AF1-246 TAP 500.0 END |
Single | AC | 100.41 % | 106.28 % | 571.52 | B | 607.41 | 33.35 | |
| DVP |
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
314697 to 927250 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 314936 CKT 1 /*AF1-246 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 122.47 % | 125.82 % | 674.92 | B | 849.18 | 23.0 | |
| DVP |
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
314697 to 927250 ckt 1 |
314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A
CONTINGENCY '314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A' OPEN BRANCH FROM BUS 314906 TO BUS 945810 CKT 1 /*8CLOVER 500.0 - AF1-246 TAP 500.0 END |
Single | AC | 96.68 % | 100.01 % | 674.92 | B | 674.99 | 23.0 | |
| CPLE/DVP |
AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line
927250 to 304070 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 314936 CKT 1 /*AF1-246 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 124.4 % | 127.53 % | 718.0 | B | 915.67 | 23.0 | |
| CPLE/DVP |
AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line
927250 to 304070 ckt 1 |
314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A
CONTINGENCY '314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A' OPEN BRANCH FROM BUS 314906 TO BUS 945810 CKT 1 /*8CLOVER 500.0 - AF1-246 TAP 500.0 END |
Single | AC | 100.29 % | 103.43 % | 718.0 | B | 742.63 | 23.0 | |
| CPLE/DVP |
AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line
927250 to 304070 ckt 1 |
DVP_P1-2: LN 556-A
CONTINGENCY 'DVP_P1-2: LN 556-A' OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 1 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 2 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 3 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314906 TO BUS 945810 CKT 1 /*8CLOVER 500.0 - AF1-246 TAP 500.0 OPEN BUS 314906 /*8CLOVER 500.0 OPEN BUS 314915 /*8CLOVER_STC 500.0 END |
Single | AC | 99.9 % | 103.02 % | 718.0 | B | 739.68 | 23.0 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 5254
CONTINGENCY 'DVP_P1-2: LN 5254' OPEN BRANCH FROM BUS 314563 TO BUS 924510 CKT 1 /*6CLUBHSE 230.0 - AB2-100 TAP 230.0 END |
Single | AC | 100.48 % | 105.89 % | 182.64 | B | 193.4 | 9.82 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 END |
Single | AC | 113.27 % | 116.25 % | 661.76 | B | 769.3 | 20.14 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
DVP_P1-2: LN 2027-B
CONTINGENCY 'DVP_P1-2: LN 2027-B' OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 933500 TO BUS 314333 CKT 1 /*AC2-165 TAP 230.0 - 6POWHATN 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 END |
Single | AC | 113.26 % | 116.23 % | 661.76 | B | 769.16 | 20.14 | |
| DVP |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line
940480 to 314435 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Single | AC | 102.07 % | 103.41 % | 678.68 | B | 701.82 | 10.56 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 END |
Single | AC | 109.48 % | 112.45 % | 661.76 | B | 744.15 | 20.14 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 2027-B
CONTINGENCY 'DVP_P1-2: LN 2027-B' OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 933500 TO BUS 314333 CKT 1 /*AC2-165 TAP 230.0 - 6POWHATN 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 END |
Single | AC | 109.46 % | 112.43 % | 661.76 | B | 744.02 | 20.14 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P1-2: LN 2027-B
CONTINGENCY 'DVP_P1-2: LN 2027-B' OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 933500 TO BUS 314333 CKT 1 /*AC2-165 TAP 230.0 - 6POWHATN 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 END |
Single | AC | 116.09 % | 119.33 % | 661.76 | B | 789.68 | 21.98 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 END |
Single | AC | 116.07 % | 119.31 % | 661.76 | B | 789.55 | 21.98 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 END |
Single | AC | 113.34 % | 116.33 % | 661.76 | B | 769.83 | 20.14 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 2027-B
CONTINGENCY 'DVP_P1-2: LN 2027-B' OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 933500 TO BUS 314333 CKT 1 /*AC2-165 TAP 230.0 - 6POWHATN 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 END |
Single | AC | 113.33 % | 116.32 % | 661.76 | B | 769.76 | 20.14 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P1-2: LN 2027-B
CONTINGENCY 'DVP_P1-2: LN 2027-B' OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 933500 TO BUS 314333 CKT 1 /*AC2-165 TAP 230.0 - 6POWHATN 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 END |
Single | AC | 113.79 % | 117.03 % | 661.76 | B | 774.46 | 21.98 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 END |
Single | AC | 113.77 % | 117.01 % | 661.76 | B | 774.33 | 21.98 | |
| DVP |
6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer
314747 to 314744 ckt 1 |
DVP_P1-2: LN 2193
CONTINGENCY 'DVP_P1-2: LN 2193' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 END |
Single | AC | 104.2 % | 107.72 % | 269.78 | B | 290.61 | 9.76 | |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 315159 | 1KERR 2 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 315160 | 1KERR 3 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 315161 | 1KERR 4 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 315162 | 1KERR 5 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 942461 | AE2-259 C O1 | Adder | 4.45 MW | 3.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 942462 | AE2-259 E O1 | Adder | 2.97 MW | 2.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 943901 | AF1-058 C | Adder | 0.67 MW | 0.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 943902 | AF1-058 E | Adder | 0.44 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 958801 | AF2-171 C | 50/50 | 10.84 MW | 10.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 958802 | AF2-171 E | 50/50 | 7.23 MW | 7.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 959311 | AF2-222 C | 50/50 | 14.93 MW | 14.93 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 959312 | AF2-222 E | 50/50 | 10.01 MW | 10.01 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 960061 | AF2-297 C | Adder | 2.67 MW | 2.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 960062 | AF2-297 E | Adder | 1.78 MW | 1.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 315163 | 1KERR 6 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 315164 | 1KERR 7 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 924162 | AB2-060 E OP | 50/50 | 4.92 MW | 4.92 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 924301 | AB2-077 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 924302 | AB2-077 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 924311 | AB2-078 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 924312 | AB2-078 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 924321 | AB2-079 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 924322 | AB2-079 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 938371 | AE1-056 C | Adder | 4.17 MW | 3.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 938372 | AE1-056 E | Adder | 2.28 MW | 1.94 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 940661 | AE2-053 O1 | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 946301 | AF1-294 C | Adder | 2.94 MW | 2.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 946302 | AF1-294 E | Adder | 1.96 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 958211 | AF2-115 C | Adder | 1.79 MW | 1.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 958212 | AF2-115 E | Adder | 1.19 MW | 1.01 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 924021 | AB2-043 C O1 | 50/50 | 0.64 MW | 0.64 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 924022 | AB2-043 E O1 | 50/50 | 3.29 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 924161 | AB2-060 C OP | 50/50 | 1.81 MW | 1.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 925781 | AC1-054 C O1 | 50/50 | 15.55 MW | 15.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 925782 | AC1-054 E O1 | 50/50 | 7.16 MW | 7.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 926271 | AC1-105 C O1 | Adder | 2.87 MW | 2.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 926272 | AC1-105 E O1 | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 936261 | AD2-033 C | 50/50 | 12.6 MW | 12.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 936262 | AD2-033 E | 50/50 | 8.4 MW | 8.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 939181 | AE1-148 C O1 | 50/50 | 17.2 MW | 17.2 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 939182 | AE1-148 E O1 | 50/50 | 11.47 MW | 11.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 940241 | AE2-006 | 50/50 | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 925611 | AC1-036 C | 50/50 | 0.88 MW | 0.88 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | 925612 | AC1-036 E | 50/50 | 1.44 MW | 1.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.22 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.08 MW | 0.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.13 MW | 0.13 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.24 MW | 0.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.65 MW | 0.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.42 MW | 0.42 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 315159 | 1KERR 2 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 315160 | 1KERR 3 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 315161 | 1KERR 4 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 315162 | 1KERR 5 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 927261 | AC1-222 C | Adder | 1.17 MW | 1.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 927262 | AC1-222 E | Adder | 1.12 MW | 0.95 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 934311 | AD1-055 C | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 934312 | AD1-055 E | Adder | 0.21 MW | 0.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 942461 | AE2-259 C O1 | Adder | 4.45 MW | 3.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 942462 | AE2-259 E O1 | Adder | 2.97 MW | 2.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 943901 | AF1-058 C | Adder | 0.67 MW | 0.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 943902 | AF1-058 E | Adder | 0.44 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 958801 | AF2-171 C | 50/50 | 10.84 MW | 10.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 958802 | AF2-171 E | 50/50 | 7.23 MW | 7.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 959311 | AF2-222 C | 50/50 | 14.93 MW | 14.93 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 959312 | AF2-222 E | 50/50 | 10.01 MW | 10.01 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 960061 | AF2-297 C | Adder | 2.67 MW | 2.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 960062 | AF2-297 E | Adder | 1.78 MW | 1.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 315163 | 1KERR 6 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 315164 | 1KERR 7 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 924162 | AB2-060 E OP | 50/50 | 4.92 MW | 4.92 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 924301 | AB2-077 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 924302 | AB2-077 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 924311 | AB2-078 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 924312 | AB2-078 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 924321 | AB2-079 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 924322 | AB2-079 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 938371 | AE1-056 C | Adder | 4.17 MW | 3.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 938372 | AE1-056 E | Adder | 2.28 MW | 1.94 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 940661 | AE2-053 O1 | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 946301 | AF1-294 C | Adder | 2.94 MW | 2.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 946302 | AF1-294 E | Adder | 1.96 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 958211 | AF2-115 C | Adder | 1.79 MW | 1.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 958212 | AF2-115 E | Adder | 1.19 MW | 1.01 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 924021 | AB2-043 C O1 | 50/50 | 0.64 MW | 0.64 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 924022 | AB2-043 E O1 | 50/50 | 3.29 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 924161 | AB2-060 C OP | 50/50 | 1.81 MW | 1.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 926271 | AC1-105 C O1 | Adder | 2.87 MW | 2.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 926272 | AC1-105 E O1 | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 936261 | AD2-033 C | 50/50 | 12.6 MW | 12.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 936262 | AD2-033 E | 50/50 | 8.4 MW | 8.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 939181 | AE1-148 C O1 | 50/50 | 17.2 MW | 17.2 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 939182 | AE1-148 E O1 | 50/50 | 11.47 MW | 11.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 940241 | AE2-006 | 50/50 | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 925611 | AC1-036 C | 50/50 | 0.88 MW | 0.88 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | 925612 | AC1-036 E | 50/50 | 1.44 MW | 1.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.22 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.08 MW | 0.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.13 MW | 0.13 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.24 MW | 0.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.65 MW | 0.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90-B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.42 MW | 0.42 MW |
| Details for 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940241 | AE2-006 | 50/50 | 2.9 MW | 2.9 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 5.7 MW | 5.7 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| Details for 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940241 | AE2-006 | 50/50 | 2.9 MW | 2.9 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 5.7 MW | 5.7 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| Details for 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 940241 | AE2-006 | 50/50 | 2.9 MW | 2.9 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925611 | AC1-036 C | 50/50 | 5.7 MW | 5.7 MW |
| 3CENTRAL-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 0.31 MW | 0.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.23 MW | 1.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 22.15 MW | 22.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 49.83 MW | 49.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 55.37 MW | 55.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 37.1 MW | 37.1 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 14.17 MW | 14.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 21.48 MW | 21.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 11.74 MW | 11.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 13.62 MW | 13.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 9.08 MW | 9.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 8.3 MW | 8.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 5.54 MW | 5.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 924161 | AB2-060 C OP | 50/50 | 5.23 MW | 5.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 936261 | AD2-033 C | 50/50 | 43.19 MW | 43.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 936262 | AD2-033 E | 50/50 | 28.79 MW | 28.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 940241 | AE2-006 | 50/50 | 1.61 MW | 1.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 3.16 MW | 3.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 5.15 MW | 5.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 925831 | AC1-062 | 50/50 | 0.18 MW | 0.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| Details for 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314541 | 3WATKINS | Adder | 0.23 MW | 0.19 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.06 MW | 0.06 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314704 | 3LAWRENC | 50/50 | 0.22 MW | 0.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 4.02 MW | 3.41 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 4.02 MW | 3.41 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315136 | 1ROSEMG1 | 50/50 | 1.45 MW | 1.45 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315137 | 1ROSEMS1 | 50/50 | 0.9 MW | 0.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315138 | 1ROSEMG2 | 50/50 | 0.68 MW | 0.68 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315139 | 1GASTONA | 50/50 | 2.16 MW | 2.16 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 2.07 MW | 1.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.31 MW | 0.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 2.08 MW | 1.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.76 MW | 1.49 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.22 MW | 3.59 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.3 MW | 0.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 3.08 MW | 2.62 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.83 MW | 1.56 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 1.03 MW | 0.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.61 MW | 0.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927251 | AC1-221 C | Adder | 0.92 MW | 0.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927252 | AC1-221 E | Adder | 0.92 MW | 0.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927261 | AC1-222 C | Adder | 1.46 MW | 1.24 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927262 | AC1-222 E | Adder | 1.39 MW | 1.18 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934311 | AD1-055 C | Adder | 1.01 MW | 0.86 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 5.74 MW | 4.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 3.07 MW | 2.61 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934341 | AD1-058 C | Adder | 2.31 MW | 1.96 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934342 | AD1-058 E | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934521 | AD1-076 C | Adder | 17.72 MW | 15.06 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934522 | AD1-076 E | Adder | 9.02 MW | 7.67 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934991 | AD1-131 C | Adder | 0.76 MW | 0.64 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934992 | AD1-131 E | Adder | 0.5 MW | 0.43 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 3.62 MW | 3.08 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 2.41 MW | 2.05 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936161 | AD2-022 C O1 | Adder | 3.27 MW | 2.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936162 | AD2-022 E O1 | Adder | 1.96 MW | 1.67 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936171 | AD2-023 C O1 | Adder | 1.91 MW | 1.62 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936172 | AD2-023 E O1 | Adder | 1.04 MW | 0.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 1.02 MW | 0.87 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.48 MW | 0.41 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | 50/50 | 19.47 MW | 19.47 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | 50/50 | 12.98 MW | 12.98 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.6 MW | 0.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.26 MW | 0.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.81 MW | 0.69 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.54 MW | 0.46 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | 50/50 | 7.08 MW | 7.08 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | 50/50 | 2.75 MW | 2.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.44 MW | 1.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 3.65 MW | 3.1 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 5.04 MW | 4.28 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958801 | AF2-171 C | Adder | 4.9 MW | 4.16 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958802 | AF2-171 E | Adder | 3.26 MW | 2.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959311 | AF2-222 C | Adder | 6.21 MW | 5.28 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959312 | AF2-222 E | Adder | 4.16 MW | 3.54 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 3.23 MW | 2.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 2.15 MW | 1.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 2.03 MW | 2.03 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.35 MW | 1.35 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315294 | 1DOMTR10 | Adder | 3.78 MW | 3.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.12 MW | 0.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.53 MW | 0.45 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.29 MW | 0.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922922 | AB1-081 C OP | Adder | 4.48 MW | 3.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.92 MW | 1.63 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | 50/50 | 9.5 MW | 9.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | 50/50 | 4.07 MW | 4.07 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | 50/50 | 0.75 MW | 0.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | 50/50 | 5.22 MW | 5.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.72 MW | 2.31 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.88 MW | 1.6 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 2.16 MW | 1.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 3.42 MW | 2.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.58 MW | 2.19 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 4.39 MW | 3.73 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 2.16 MW | 1.84 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932761 | AC2-100 C | Adder | 2.12 MW | 1.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932762 | AC2-100 E | Adder | 1.03 MW | 0.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.44 MW | 0.37 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 2.24 MW | 1.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.96 MW | 0.81 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.53 MW | 1.3 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | 50/50 | 21.68 MW | 21.68 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | 50/50 | 9.71 MW | 9.71 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 1.21 MW | 1.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.81 MW | 0.81 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 26.06 MW | 22.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 17.38 MW | 14.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 7.06 MW | 6.0 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.55 MW | 3.02 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 3.53 MW | 3.0 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.56 MW | 1.33 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 17.97 MW | 17.97 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 12.11 MW | 12.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 15.04 MW | 15.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.5 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.81 MW | -2.38 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -4.05 MW | -3.44 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315103 | 1BRUNSWICKG2 | 50/50 | 4.71 MW | 4.71 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315104 | 1BRUNSWICKG3 | 50/50 | 4.71 MW | 4.71 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315105 | 1BRUNSWICKS1 | 50/50 | 9.78 MW | 9.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315141 | 1GASTONB | 50/50 | 2.16 MW | 2.16 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.29 MW | 1.29 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938221 | AE1-035 C | Adder | 0.9 MW | 0.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 3.7 MW | 3.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920672 | AA2-174 E OP | Adder | 0.24 MW | 0.2 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923911 | AB2-031 C O1 | 50/50 | 1.59 MW | 1.59 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923912 | AB2-031 E O1 | 50/50 | 0.78 MW | 0.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 1.25 MW | 1.07 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924501 | AB2-099 C | Adder | 0.25 MW | 0.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924502 | AB2-099 E | Adder | 0.11 MW | 0.09 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924512 | AB2-100 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925172 | AB2-174 E O1 | 50/50 | 4.68 MW | 4.68 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925781 | AC1-054 C O1 | Adder | 3.66 MW | 3.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925782 | AC1-054 E O1 | Adder | 1.69 MW | 1.43 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 C | 50/50 | 13.99 MW | 13.99 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926072 | AC1-086 E | 50/50 | 6.37 MW | 6.37 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926271 | AC1-105 C O1 | Adder | 2.34 MW | 1.99 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926272 | AC1-105 E O1 | Adder | 1.16 MW | 0.99 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927021 | AC1-189 C | Adder | 3.89 MW | 3.3 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927022 | AC1-189 E | Adder | 1.94 MW | 1.65 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927141 | AC1-208 C | Adder | 4.75 MW | 4.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927142 | AC1-208 E | Adder | 2.11 MW | 1.79 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934611 | AD1-087 C O1 | Adder | 3.49 MW | 2.97 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934612 | AD1-087 E O1 | Adder | 1.64 MW | 1.39 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936261 | AD2-033 C | Adder | 5.1 MW | 4.33 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936262 | AD2-033 E | Adder | 3.4 MW | 2.89 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C O1 | Adder | 4.14 MW | 3.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E O1 | Adder | 2.76 MW | 2.35 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940241 | AE2-006 | Adder | 0.18 MW | 0.16 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923572 | AB1-173 C OP | 50/50 | 1.6 MW | 1.6 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923582 | AB1-173AC OP | 50/50 | 1.6 MW | 1.6 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923583 | AB1-173AE OP | 50/50 | 0.75 MW | 0.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925611 | AC1-036 C | Adder | 0.36 MW | 0.31 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925612 | AC1-036 E | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C O1 | Adder | 3.92 MW | 3.33 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E O1 | Adder | 2.1 MW | 1.79 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314947 | 8GREENSVILLE | 50/50 | 28.73 MW | 28.73 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924511 | AB2-100 C | 50/50 | 1.84 MW | 1.84 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925171 | AB2-174 C O1 | 50/50 | 0.9 MW | 0.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939411 | AE1-173 C | Adder | 36.98 MW | 31.44 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939412 | AE1-173 E | Adder | 24.66 MW | 20.96 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 O1 | 50/50 | 3.27 MW | 3.27 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918561 | AA1-072 C | Adder | 0.16 MW | 0.14 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918562 | AA1-072 E | Adder | 0.08 MW | 0.06 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933981 | AD1-022 C | Adder | 3.03 MW | 2.57 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933982 | AD1-022 E | Adder | 1.65 MW | 1.4 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.78 MW | 1.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.36 MW | 0.36 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.69 MW | 0.69 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.82 MW | 3.82 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.69 MW | 14.69 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.52 MW | 0.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.09 MW | 3.09 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 7.38 MW | 7.38 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 26.01 MW | 26.01 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 17.24 MW | 17.24 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.15 MW | 1.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.87 MW | 0.87 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.21 MW | 2.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.6 MW | 2.6 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 13.7 MW | 13.7 MW |
| Details for 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314541 | 3WATKINS | Adder | 0.23 MW | 0.19 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.06 MW | 0.06 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314704 | 3LAWRENC | 50/50 | 0.22 MW | 0.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 4.02 MW | 3.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 4.02 MW | 3.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315136 | 1ROSEMG1 | 50/50 | 1.45 MW | 1.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315137 | 1ROSEMS1 | 50/50 | 0.9 MW | 0.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315138 | 1ROSEMG2 | 50/50 | 0.68 MW | 0.68 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315139 | 1GASTONA | 50/50 | 2.16 MW | 2.16 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 2.07 MW | 1.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.31 MW | 0.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 2.08 MW | 1.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.76 MW | 1.49 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.22 MW | 3.59 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.3 MW | 0.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 3.08 MW | 2.62 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.83 MW | 1.56 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 1.03 MW | 0.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.61 MW | 0.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927251 | AC1-221 C | Adder | 0.92 MW | 0.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927252 | AC1-221 E | Adder | 0.92 MW | 0.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927261 | AC1-222 C | Adder | 1.46 MW | 1.24 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927262 | AC1-222 E | Adder | 1.39 MW | 1.18 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934311 | AD1-055 C | Adder | 1.01 MW | 0.86 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 5.74 MW | 4.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 3.07 MW | 2.61 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934341 | AD1-058 C | Adder | 2.31 MW | 1.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934342 | AD1-058 E | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934521 | AD1-076 C | Adder | 17.72 MW | 15.06 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934522 | AD1-076 E | Adder | 9.02 MW | 7.67 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934991 | AD1-131 C | Adder | 0.76 MW | 0.64 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934992 | AD1-131 E | Adder | 0.5 MW | 0.43 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 3.62 MW | 3.08 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 2.41 MW | 2.05 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936161 | AD2-022 C O1 | Adder | 3.27 MW | 2.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936162 | AD2-022 E O1 | Adder | 1.96 MW | 1.67 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936171 | AD2-023 C O1 | Adder | 1.91 MW | 1.62 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936172 | AD2-023 E O1 | Adder | 1.04 MW | 0.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 1.02 MW | 0.87 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.48 MW | 0.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | 50/50 | 19.47 MW | 19.47 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | 50/50 | 12.98 MW | 12.98 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.6 MW | 0.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.26 MW | 0.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.81 MW | 0.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.54 MW | 0.46 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | 50/50 | 7.08 MW | 7.08 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | 50/50 | 2.75 MW | 2.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.44 MW | 1.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 3.65 MW | 3.1 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 5.04 MW | 4.28 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958801 | AF2-171 C | Adder | 4.9 MW | 4.16 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958802 | AF2-171 E | Adder | 3.26 MW | 2.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959311 | AF2-222 C | Adder | 6.21 MW | 5.28 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959312 | AF2-222 E | Adder | 4.16 MW | 3.54 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 3.23 MW | 2.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 2.15 MW | 1.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 2.03 MW | 2.03 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.35 MW | 1.35 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315294 | 1DOMTR10 | Adder | 3.78 MW | 3.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.12 MW | 0.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.53 MW | 0.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.29 MW | 0.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922922 | AB1-081 C OP | Adder | 4.48 MW | 3.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.92 MW | 1.63 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | 50/50 | 9.5 MW | 9.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | 50/50 | 4.07 MW | 4.07 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | 50/50 | 0.75 MW | 0.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | 50/50 | 5.22 MW | 5.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.72 MW | 2.31 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.88 MW | 1.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 2.16 MW | 1.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 3.42 MW | 2.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.58 MW | 2.19 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 4.39 MW | 3.73 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 2.16 MW | 1.84 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932761 | AC2-100 C | Adder | 2.12 MW | 1.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932762 | AC2-100 E | Adder | 1.03 MW | 0.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.44 MW | 0.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 2.24 MW | 1.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.96 MW | 0.81 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.53 MW | 1.3 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | 50/50 | 21.68 MW | 21.68 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | 50/50 | 9.71 MW | 9.71 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 1.21 MW | 1.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.81 MW | 0.81 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 26.06 MW | 22.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 17.38 MW | 14.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 7.06 MW | 6.0 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.55 MW | 3.02 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 3.53 MW | 3.0 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.56 MW | 1.33 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 17.97 MW | 17.97 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 12.11 MW | 12.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 15.04 MW | 15.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.5 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.81 MW | -2.38 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -4.05 MW | -3.44 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315103 | 1BRUNSWICKG2 | 50/50 | 4.71 MW | 4.71 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315104 | 1BRUNSWICKG3 | 50/50 | 4.71 MW | 4.71 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315105 | 1BRUNSWICKS1 | 50/50 | 9.78 MW | 9.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315141 | 1GASTONB | 50/50 | 2.16 MW | 2.16 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.29 MW | 1.29 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938221 | AE1-035 C | Adder | 0.9 MW | 0.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 3.7 MW | 3.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920672 | AA2-174 E OP | Adder | 0.24 MW | 0.2 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923911 | AB2-031 C O1 | 50/50 | 1.59 MW | 1.59 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923912 | AB2-031 E O1 | 50/50 | 0.78 MW | 0.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 1.25 MW | 1.07 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924501 | AB2-099 C | Adder | 0.25 MW | 0.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924502 | AB2-099 E | Adder | 0.11 MW | 0.09 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924512 | AB2-100 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925172 | AB2-174 E O1 | 50/50 | 4.68 MW | 4.68 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925781 | AC1-054 C O1 | Adder | 3.66 MW | 3.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925782 | AC1-054 E O1 | Adder | 1.69 MW | 1.43 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 C | 50/50 | 13.99 MW | 13.99 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926072 | AC1-086 E | 50/50 | 6.37 MW | 6.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926271 | AC1-105 C O1 | Adder | 2.34 MW | 1.99 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926272 | AC1-105 E O1 | Adder | 1.16 MW | 0.99 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927021 | AC1-189 C | Adder | 3.89 MW | 3.3 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927022 | AC1-189 E | Adder | 1.94 MW | 1.65 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927141 | AC1-208 C | Adder | 4.75 MW | 4.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927142 | AC1-208 E | Adder | 2.11 MW | 1.79 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934611 | AD1-087 C O1 | Adder | 3.49 MW | 2.97 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934612 | AD1-087 E O1 | Adder | 1.64 MW | 1.39 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936261 | AD2-033 C | Adder | 5.1 MW | 4.33 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936262 | AD2-033 E | Adder | 3.4 MW | 2.89 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C O1 | Adder | 4.14 MW | 3.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E O1 | Adder | 2.76 MW | 2.35 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940241 | AE2-006 | Adder | 0.18 MW | 0.16 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923572 | AB1-173 C OP | 50/50 | 1.6 MW | 1.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923582 | AB1-173AC OP | 50/50 | 1.6 MW | 1.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923583 | AB1-173AE OP | 50/50 | 0.75 MW | 0.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925611 | AC1-036 C | Adder | 0.36 MW | 0.31 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925612 | AC1-036 E | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C O1 | Adder | 3.92 MW | 3.33 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E O1 | Adder | 2.1 MW | 1.79 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314947 | 8GREENSVILLE | 50/50 | 28.73 MW | 28.73 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924511 | AB2-100 C | 50/50 | 1.84 MW | 1.84 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925171 | AB2-174 C O1 | 50/50 | 0.9 MW | 0.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939411 | AE1-173 C | Adder | 36.98 MW | 31.44 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939412 | AE1-173 E | Adder | 24.66 MW | 20.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 O1 | 50/50 | 3.27 MW | 3.27 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918561 | AA1-072 C | Adder | 0.16 MW | 0.14 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918562 | AA1-072 E | Adder | 0.08 MW | 0.06 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933981 | AD1-022 C | Adder | 3.03 MW | 2.57 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933982 | AD1-022 E | Adder | 1.65 MW | 1.4 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.78 MW | 1.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.36 MW | 0.36 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.69 MW | 0.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.82 MW | 3.82 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.69 MW | 14.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.52 MW | 0.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.09 MW | 3.09 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 7.38 MW | 7.38 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 26.01 MW | 26.01 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 17.24 MW | 17.24 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.15 MW | 1.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.87 MW | 0.87 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.21 MW | 2.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.6 MW | 2.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 13.7 MW | 13.7 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 0.9 MW | 0.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 22.64 MW | 22.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 22.42 MW | 22.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | Adder | 1.68 MW | 1.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | Adder | 1.68 MW | 1.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | Adder | 4.08 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | Adder | 3.88 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | Adder | 2.83 MW | 2.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | Adder | 0.73 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | Adder | 4.22 MW | 3.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | Adder | 1.07 MW | 0.91 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | Adder | 1.38 MW | 1.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | Adder | 0.92 MW | 0.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.07 MW | 12.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.05 MW | 8.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 3.77 MW | 3.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.77 MW | 1.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 30.5 MW | 30.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 20.33 MW | 20.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 8.33 MW | 7.08 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 5.56 MW | 4.72 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | Adder | 2.3 MW | 1.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | Adder | 1.53 MW | 1.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 12.41 MW | 12.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 17.14 MW | 17.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 36.08 MW | 36.08 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 24.06 MW | 24.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 33.39 MW | 33.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 22.37 MW | 22.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | Adder | 6.13 MW | 5.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | Adder | 3.87 MW | 3.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | Adder | 1.89 MW | 1.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 16.72 MW | 16.72 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 9.14 MW | 9.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | Adder | 3.5 MW | 2.97 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 5.74 MW | 5.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.67 MW | 2.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 9.93 MW | 9.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 6.62 MW | 6.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 88.64 MW | 88.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 59.09 MW | 59.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958501 | AF2-144 C | Adder | -0.91 MW | -0.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924021 | AB2-043 C O1 | 50/50 | 0.75 MW | 0.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 3.87 MW | 3.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924161 | AB2-060 C OP | 50/50 | 2.21 MW | 2.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925781 | AC1-054 C O1 | Adder | 6.1 MW | 5.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925782 | AC1-054 E O1 | Adder | 2.81 MW | 2.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925991 | AC1-075 C | Adder | 4.98 MW | 4.23 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925992 | AC1-075 E | Adder | 2.82 MW | 2.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926021 | AC1-080 C | Adder | 1.66 MW | 1.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926022 | AC1-080 E | Adder | 0.94 MW | 0.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926271 | AC1-105 C O1 | 50/50 | 6.79 MW | 6.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926272 | AC1-105 E O1 | 50/50 | 3.38 MW | 3.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934611 | AD1-087 C O1 | 50/50 | 12.88 MW | 12.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934612 | AD1-087 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936261 | AD2-033 C | 50/50 | 23.84 MW | 23.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936262 | AD2-033 E | 50/50 | 15.89 MW | 15.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C O1 | Adder | 9.44 MW | 8.03 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E O1 | Adder | 6.29 MW | 5.35 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940241 | AE2-006 | 50/50 | 0.94 MW | 0.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C O1 | Adder | 6.69 MW | 5.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E O1 | Adder | 4.46 MW | 3.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 1.84 MW | 1.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 3.0 MW | 3.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925831 | AC1-062 | 50/50 | 0.13 MW | 0.13 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934621 | AD1-088 C | 50/50 | 35.3 MW | 35.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934622 | AD1-088 E | 50/50 | 16.61 MW | 16.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 12.98 MW | 11.03 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958503 | AF2-144 BAT | Adder | 1.05 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | Adder | 9.07 MW | 7.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.56 MW | 0.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.52 MW | 3.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.42 MW | 12.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 5.45 MW | 5.45 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.6 MW | 23.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.69 MW | 14.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.85 MW | 0.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.79 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.83 MW | 1.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.4 MW | 2.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 11.16 MW | 11.16 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 313853 | 3PONTONDP | 50/50 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 314429 | 3JTRSVLE | 50/50 | 0.9 MW | 0.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 315153 | 1CLOVER1 | 50/50 | 22.64 MW | 22.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 315154 | 1CLOVER2 | 50/50 | 22.42 MW | 22.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 927251 | AC1-221 C | Adder | 1.68 MW | 1.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 927252 | AC1-221 E | Adder | 1.68 MW | 1.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 927261 | AC1-222 C | Adder | 4.08 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 927262 | AC1-222 E | Adder | 3.88 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934311 | AD1-055 C | Adder | 2.83 MW | 2.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934312 | AD1-055 E | Adder | 0.73 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934341 | AD1-058 C | Adder | 4.22 MW | 3.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934342 | AD1-058 E | Adder | 1.07 MW | 0.91 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934991 | AD1-131 C | Adder | 1.38 MW | 1.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934992 | AD1-131 E | Adder | 0.92 MW | 0.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 935171 | AD1-152 C O1 | 50/50 | 12.07 MW | 12.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 935172 | AD1-152 E O1 | 50/50 | 8.05 MW | 8.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 937481 | AD2-202 C O1 | 50/50 | 3.77 MW | 3.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 937482 | AD2-202 E O1 | 50/50 | 1.77 MW | 1.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942461 | AE2-259 C O1 | 50/50 | 30.5 MW | 30.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942462 | AE2-259 E O1 | 50/50 | 20.33 MW | 20.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942761 | AE2-292 C O1 | Adder | 8.33 MW | 7.08 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942762 | AE2-292 E O1 | Adder | 5.56 MW | 4.72 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 943901 | AF1-058 C | Adder | 2.3 MW | 1.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 943902 | AF1-058 E | Adder | 1.53 MW | 1.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 945811 | AF1-246 C O1 | 50/50 | 12.41 MW | 12.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 945812 | AF1-246 E O1 | 50/50 | 17.14 MW | 17.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 958801 | AF2-171 C | 50/50 | 36.08 MW | 36.08 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 958802 | AF2-171 E | 50/50 | 24.06 MW | 24.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 959311 | AF2-222 C | 50/50 | 33.39 MW | 33.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 959312 | AF2-222 E | 50/50 | 22.37 MW | 22.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 960061 | AF2-297 C | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 960062 | AF2-297 E | Adder | 6.13 MW | 5.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924162 | AB2-060 E OP | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924301 | AB2-077 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924311 | AB2-078 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924321 | AB2-079 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 932761 | AC2-100 C | Adder | 3.87 MW | 3.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 932762 | AC2-100 E | Adder | 1.89 MW | 1.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 938371 | AE1-056 C | 50/50 | 16.72 MW | 16.72 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 938372 | AE1-056 E | 50/50 | 9.14 MW | 9.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 940661 | AE2-053 O1 | Adder | 3.5 MW | 2.97 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 941791 | AE2-182 C | 50/50 | 5.74 MW | 5.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 941792 | AE2-182 E | 50/50 | 2.67 MW | 2.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 946301 | AF1-294 C | 50/50 | 9.93 MW | 9.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 946302 | AF1-294 E | 50/50 | 6.62 MW | 6.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 957481 | AF2-042 C | 50/50 | 88.64 MW | 88.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 957482 | AF2-042 E | 50/50 | 59.09 MW | 59.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 958211 | AF2-115 C | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 958212 | AF2-115 E | 50/50 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 958501 | AF2-144 C | Adder | -0.91 MW | -0.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924021 | AB2-043 C O1 | 50/50 | 0.75 MW | 0.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924022 | AB2-043 E O1 | 50/50 | 3.87 MW | 3.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924161 | AB2-060 C OP | 50/50 | 2.21 MW | 2.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925781 | AC1-054 C O1 | Adder | 6.1 MW | 5.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925782 | AC1-054 E O1 | Adder | 2.81 MW | 2.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925991 | AC1-075 C | Adder | 4.98 MW | 4.23 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925992 | AC1-075 E | Adder | 2.82 MW | 2.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 926021 | AC1-080 C | Adder | 1.66 MW | 1.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 926022 | AC1-080 E | Adder | 0.94 MW | 0.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 926271 | AC1-105 C O1 | 50/50 | 6.79 MW | 6.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 926272 | AC1-105 E O1 | 50/50 | 3.38 MW | 3.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934611 | AD1-087 C O1 | 50/50 | 12.88 MW | 12.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934612 | AD1-087 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 936261 | AD2-033 C | 50/50 | 23.84 MW | 23.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 936262 | AD2-033 E | 50/50 | 15.89 MW | 15.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 939181 | AE1-148 C O1 | Adder | 9.44 MW | 8.03 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 939182 | AE1-148 E O1 | Adder | 6.29 MW | 5.35 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 940241 | AE2-006 | 50/50 | 0.94 MW | 0.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942751 | AE2-291 C O1 | Adder | 6.69 MW | 5.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942752 | AE2-291 E O1 | Adder | 4.46 MW | 3.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925611 | AC1-036 C | 50/50 | 1.84 MW | 1.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925612 | AC1-036 E | 50/50 | 3.0 MW | 3.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925831 | AC1-062 | 50/50 | 0.13 MW | 0.13 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934621 | AD1-088 C | 50/50 | 35.3 MW | 35.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934622 | AD1-088 E | 50/50 | 16.61 MW | 16.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 946293 | AF1-293 BAT | Adder | 12.98 MW | 11.03 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 958503 | AF2-144 BAT | Adder | 1.05 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 961063 | AF2-397 BAT | Adder | 9.07 MW | 7.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.56 MW | 0.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.52 MW | 3.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.42 MW | 12.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 5.45 MW | 5.45 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.6 MW | 23.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.69 MW | 14.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.85 MW | 0.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.79 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.83 MW | 1.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.4 MW | 2.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 11.16 MW | 11.16 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 0.9 MW | 0.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 22.64 MW | 22.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 22.41 MW | 22.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | Adder | 1.68 MW | 1.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | Adder | 1.68 MW | 1.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | Adder | 4.08 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | Adder | 3.88 MW | 3.3 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | Adder | 2.83 MW | 2.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | Adder | 0.73 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | Adder | 4.22 MW | 3.58 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | Adder | 1.07 MW | 0.91 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | Adder | 1.38 MW | 1.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | Adder | 0.92 MW | 0.78 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.07 MW | 12.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.05 MW | 8.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 3.77 MW | 3.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.77 MW | 1.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 30.5 MW | 30.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 20.33 MW | 20.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 8.33 MW | 7.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 5.55 MW | 4.72 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | Adder | 2.3 MW | 1.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | Adder | 1.53 MW | 1.3 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 12.41 MW | 12.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 17.13 MW | 17.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 36.08 MW | 36.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 24.05 MW | 24.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 33.38 MW | 33.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 22.37 MW | 22.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | Adder | 9.2 MW | 7.82 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | Adder | 6.13 MW | 5.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | Adder | 3.87 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | Adder | 1.89 MW | 1.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 16.72 MW | 16.72 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 9.13 MW | 9.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | Adder | 3.5 MW | 2.97 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 5.73 MW | 5.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.67 MW | 2.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 9.92 MW | 9.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 6.62 MW | 6.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 88.62 MW | 88.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 59.08 MW | 59.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 4.03 MW | 4.03 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924032 | AB2-045 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314677 | 6BUCKING | 50/50 | 1.64 MW | 1.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924021 | AB2-043 C O1 | 50/50 | 0.75 MW | 0.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 3.87 MW | 3.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924161 | AB2-060 C OP | 50/50 | 2.21 MW | 2.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925781 | AC1-054 C O1 | Adder | 6.1 MW | 5.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925782 | AC1-054 E O1 | Adder | 2.81 MW | 2.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925991 | AC1-075 C | Adder | 4.98 MW | 4.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925992 | AC1-075 E | Adder | 2.82 MW | 2.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926021 | AC1-080 C | Adder | 1.66 MW | 1.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926022 | AC1-080 E | Adder | 0.94 MW | 0.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926271 | AC1-105 C O1 | 50/50 | 6.79 MW | 6.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926272 | AC1-105 E O1 | 50/50 | 3.38 MW | 3.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934611 | AD1-087 C O1 | 50/50 | 12.87 MW | 12.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934612 | AD1-087 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936261 | AD2-033 C | 50/50 | 23.83 MW | 23.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936262 | AD2-033 E | 50/50 | 15.89 MW | 15.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C O1 | Adder | 9.44 MW | 8.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E O1 | Adder | 6.29 MW | 5.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940241 | AE2-006 | 50/50 | 0.94 MW | 0.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C O1 | Adder | 6.69 MW | 5.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E O1 | Adder | 4.46 MW | 3.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 3.0 MW | 3.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925831 | AC1-062 | 50/50 | 0.13 MW | 0.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934621 | AD1-088 C | 50/50 | 35.3 MW | 35.3 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934622 | AD1-088 E | 50/50 | 16.61 MW | 16.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 12.98 MW | 11.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | Adder | 9.07 MW | 7.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.56 MW | 0.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.52 MW | 3.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.36 MW | 12.36 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.64 MW | 2.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 5.5 MW | 5.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.56 MW | 23.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.63 MW | 14.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.86 MW | 0.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.79 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.82 MW | 1.82 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.4 MW | 2.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 11.07 MW | 11.07 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 313853 | 3PONTONDP | 50/50 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 314429 | 3JTRSVLE | 50/50 | 0.9 MW | 0.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 315153 | 1CLOVER1 | 50/50 | 22.64 MW | 22.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 315154 | 1CLOVER2 | 50/50 | 22.41 MW | 22.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 927251 | AC1-221 C | Adder | 1.68 MW | 1.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 927252 | AC1-221 E | Adder | 1.68 MW | 1.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 927261 | AC1-222 C | Adder | 4.08 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 927262 | AC1-222 E | Adder | 3.88 MW | 3.3 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934311 | AD1-055 C | Adder | 2.83 MW | 2.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934312 | AD1-055 E | Adder | 0.73 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934341 | AD1-058 C | Adder | 4.22 MW | 3.58 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934342 | AD1-058 E | Adder | 1.07 MW | 0.91 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934991 | AD1-131 C | Adder | 1.38 MW | 1.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934992 | AD1-131 E | Adder | 0.92 MW | 0.78 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 935171 | AD1-152 C O1 | 50/50 | 12.07 MW | 12.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 935172 | AD1-152 E O1 | 50/50 | 8.05 MW | 8.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 937481 | AD2-202 C O1 | 50/50 | 3.77 MW | 3.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 937482 | AD2-202 E O1 | 50/50 | 1.77 MW | 1.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942461 | AE2-259 C O1 | 50/50 | 30.5 MW | 30.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942462 | AE2-259 E O1 | 50/50 | 20.33 MW | 20.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942761 | AE2-292 C O1 | Adder | 8.33 MW | 7.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942762 | AE2-292 E O1 | Adder | 5.55 MW | 4.72 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 943901 | AF1-058 C | Adder | 2.3 MW | 1.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 943902 | AF1-058 E | Adder | 1.53 MW | 1.3 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 945811 | AF1-246 C O1 | 50/50 | 12.41 MW | 12.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 945812 | AF1-246 E O1 | 50/50 | 17.13 MW | 17.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 958801 | AF2-171 C | 50/50 | 36.08 MW | 36.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 958802 | AF2-171 E | 50/50 | 24.05 MW | 24.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 959311 | AF2-222 C | 50/50 | 33.38 MW | 33.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 959312 | AF2-222 E | 50/50 | 22.37 MW | 22.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 960061 | AF2-297 C | Adder | 9.2 MW | 7.82 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 960062 | AF2-297 E | Adder | 6.13 MW | 5.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924162 | AB2-060 E OP | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924301 | AB2-077 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924311 | AB2-078 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924321 | AB2-079 C O1 | 50/50 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 932761 | AC2-100 C | Adder | 3.87 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 932762 | AC2-100 E | Adder | 1.89 MW | 1.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 938371 | AE1-056 C | 50/50 | 16.72 MW | 16.72 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 938372 | AE1-056 E | 50/50 | 9.13 MW | 9.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 940661 | AE2-053 O1 | Adder | 3.5 MW | 2.97 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 941791 | AE2-182 C | 50/50 | 5.73 MW | 5.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 941792 | AE2-182 E | 50/50 | 2.67 MW | 2.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 946301 | AF1-294 C | 50/50 | 9.92 MW | 9.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 946302 | AF1-294 E | 50/50 | 6.62 MW | 6.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 957481 | AF2-042 C | 50/50 | 88.62 MW | 88.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 957482 | AF2-042 E | 50/50 | 59.08 MW | 59.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 958211 | AF2-115 C | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 958212 | AF2-115 E | 50/50 | 4.03 MW | 4.03 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924032 | AB2-045 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 314677 | 6BUCKING | 50/50 | 1.64 MW | 1.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924021 | AB2-043 C O1 | 50/50 | 0.75 MW | 0.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924022 | AB2-043 E O1 | 50/50 | 3.87 MW | 3.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 924161 | AB2-060 C OP | 50/50 | 2.21 MW | 2.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925781 | AC1-054 C O1 | Adder | 6.1 MW | 5.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925782 | AC1-054 E O1 | Adder | 2.81 MW | 2.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925991 | AC1-075 C | Adder | 4.98 MW | 4.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925992 | AC1-075 E | Adder | 2.82 MW | 2.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 926021 | AC1-080 C | Adder | 1.66 MW | 1.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 926022 | AC1-080 E | Adder | 0.94 MW | 0.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 926271 | AC1-105 C O1 | 50/50 | 6.79 MW | 6.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 926272 | AC1-105 E O1 | 50/50 | 3.38 MW | 3.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934611 | AD1-087 C O1 | 50/50 | 12.87 MW | 12.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934612 | AD1-087 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 936261 | AD2-033 C | 50/50 | 23.83 MW | 23.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 936262 | AD2-033 E | 50/50 | 15.89 MW | 15.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 939181 | AE1-148 C O1 | Adder | 9.44 MW | 8.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 939182 | AE1-148 E O1 | Adder | 6.29 MW | 5.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 940241 | AE2-006 | 50/50 | 0.94 MW | 0.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942751 | AE2-291 C O1 | Adder | 6.69 MW | 5.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 942752 | AE2-291 E O1 | Adder | 4.46 MW | 3.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925611 | AC1-036 C | 50/50 | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925612 | AC1-036 E | 50/50 | 3.0 MW | 3.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 925831 | AC1-062 | 50/50 | 0.13 MW | 0.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934621 | AD1-088 C | 50/50 | 35.3 MW | 35.3 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 934622 | AD1-088 E | 50/50 | 16.61 MW | 16.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 946293 | AF1-293 BAT | Adder | 12.98 MW | 11.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | 961063 | AF2-397 BAT | Adder | 9.07 MW | 7.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.56 MW | 0.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.52 MW | 3.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.36 MW | 12.36 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.64 MW | 2.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 5.5 MW | 5.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.56 MW | 23.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.63 MW | 14.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.86 MW | 0.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.79 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.82 MW | 1.82 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.4 MW | 2.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591-A | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 11.07 MW | 11.07 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 0.25 MW | 0.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 0.99 MW | 0.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 17.84 MW | 17.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 40.13 MW | 40.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 44.59 MW | 44.59 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 29.88 MW | 29.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 11.42 MW | 11.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 17.3 MW | 17.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 9.45 MW | 9.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 10.97 MW | 10.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 7.31 MW | 7.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 6.69 MW | 6.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 4.46 MW | 4.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 924161 | AB2-060 C OP | 50/50 | 4.21 MW | 4.21 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 936261 | AD2-033 C | 50/50 | 34.78 MW | 34.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 936262 | AD2-033 E | 50/50 | 23.19 MW | 23.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 940241 | AE2-006 | 50/50 | 1.29 MW | 1.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 4.15 MW | 4.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 925831 | AC1-062 | 50/50 | 0.15 MW | 0.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.11 MW | 0.11 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| Details for 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940241 | AE2-006 | 50/50 | 2.9 MW | 2.9 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 5.7 MW | 5.7 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| Details for 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940241 | AE2-006 | 50/50 | 2.9 MW | 2.9 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 5.7 MW | 5.7 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| Details for AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| Details for AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315158 | 1KERR 1 | 50/50 | 0.72 MW | 0.72 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315159 | 1KERR 2 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315162 | 1KERR 5 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 918492 | AA1-063AE OP | Adder | 1.52 MW | 1.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 919692 | AA2-053 E OP | Adder | 1.51 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 11.09 MW | 11.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 7.39 MW | 7.39 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 16.63 MW | 16.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 11.09 MW | 11.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 18.48 MW | 18.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 12.38 MW | 12.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 960081 | AF2-299 C | Adder | 0.95 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 960082 | AF2-299 E | Adder | 0.63 MW | 0.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923573 | AB1-173 E OP | Adder | 0.43 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923991 | AB2-040 C O1 | Adder | 3.01 MW | 2.56 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923992 | AB2-040 E O1 | Adder | 2.47 MW | 2.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | Adder | 4.73 MW | 4.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 7.17 MW | 7.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 3.92 MW | 3.92 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 5.17 MW | 5.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946281 | AF1-292 C | Adder | 0.57 MW | 0.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946282 | AF1-292 E | Adder | 0.38 MW | 0.32 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | Adder | 4.54 MW | 3.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | Adder | 3.03 MW | 2.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | Adder | 2.77 MW | 2.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | Adder | 1.85 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 920672 | AA2-174 E OP | Adder | 0.17 MW | 0.15 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923911 | AB2-031 C O1 | Adder | 0.92 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923912 | AB2-031 E O1 | Adder | 0.45 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924021 | AB2-043 C O1 | 50/50 | 0.61 MW | 0.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 3.12 MW | 3.12 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924161 | AB2-060 C OP | 50/50 | 1.74 MW | 1.74 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925172 | AB2-174 E O1 | Adder | 2.55 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925781 | AC1-054 C O1 | 50/50 | 10.08 MW | 10.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925782 | AC1-054 E O1 | 50/50 | 4.64 MW | 4.64 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 926271 | AC1-105 C O1 | Adder | 2.59 MW | 2.2 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 926272 | AC1-105 E O1 | Adder | 1.29 MW | 1.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936261 | AD2-033 C | Adder | 14.41 MW | 12.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936262 | AD2-033 E | Adder | 9.61 MW | 8.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C O1 | 50/50 | 13.97 MW | 13.97 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E O1 | 50/50 | 9.31 MW | 9.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940241 | AE2-006 | 50/50 | 0.54 MW | 0.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923572 | AB1-173 C OP | Adder | 0.92 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923582 | AB1-173AC OP | Adder | 0.92 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923583 | AB1-173AE OP | Adder | 0.43 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.05 MW | 1.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 1.72 MW | 1.72 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.47 MW | 0.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.18 MW | 0.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.48 MW | 0.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.23 MW | 0.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.27 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.09 MW | 0.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.14 MW | 0.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.25 MW | 0.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.71 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.23 MW | 0.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315158 | 1KERR 1 | 50/50 | 0.72 MW | 0.72 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315160 | 1KERR 3 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 918492 | AA1-063AE OP | Adder | 1.51 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 919692 | AA2-053 E OP | Adder | 1.5 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 11.07 MW | 11.07 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 7.38 MW | 7.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 16.6 MW | 16.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 11.07 MW | 11.07 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 18.45 MW | 18.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 12.36 MW | 12.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 960081 | AF2-299 C | Adder | 0.95 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 960082 | AF2-299 E | Adder | 0.63 MW | 0.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315163 | 1KERR 6 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315164 | 1KERR 7 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923573 | AB1-173 E OP | Adder | 0.43 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923991 | AB2-040 C O1 | Adder | 3.01 MW | 2.56 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923992 | AB2-040 E O1 | Adder | 2.46 MW | 2.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | Adder | 4.72 MW | 4.01 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 7.16 MW | 7.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 3.91 MW | 3.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 5.17 MW | 5.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946281 | AF1-292 C | Adder | 0.56 MW | 0.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946282 | AF1-292 E | Adder | 0.38 MW | 0.32 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | Adder | 4.54 MW | 3.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | Adder | 3.02 MW | 2.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | Adder | 2.77 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | Adder | 1.84 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 920672 | AA2-174 E OP | Adder | 0.17 MW | 0.15 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923911 | AB2-031 C O1 | Adder | 0.92 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923912 | AB2-031 E O1 | Adder | 0.45 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924021 | AB2-043 C O1 | 50/50 | 0.6 MW | 0.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 3.12 MW | 3.12 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925172 | AB2-174 E O1 | Adder | 2.54 MW | 2.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925781 | AC1-054 C O1 | 50/50 | 10.07 MW | 10.07 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925782 | AC1-054 E O1 | 50/50 | 4.64 MW | 4.64 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 926271 | AC1-105 C O1 | Adder | 2.57 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 926272 | AC1-105 E O1 | Adder | 1.28 MW | 1.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936261 | AD2-033 C | Adder | 14.39 MW | 12.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936262 | AD2-033 E | Adder | 9.59 MW | 8.15 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C O1 | 50/50 | 13.96 MW | 13.96 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E O1 | 50/50 | 9.3 MW | 9.3 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940241 | AE2-006 | 50/50 | 0.54 MW | 0.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923572 | AB1-173 C OP | Adder | 0.92 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923582 | AB1-173AC OP | Adder | 0.92 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923583 | AB1-173AE OP | Adder | 0.43 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.05 MW | 1.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 1.72 MW | 1.72 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.48 MW | 0.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.19 MW | 0.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.49 MW | 0.49 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.23 MW | 0.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.09 MW | 0.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.39 MW | 0.39 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.14 MW | 0.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.26 MW | 0.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.71 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.23 MW | 0.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315159 | 1KERR 2 | 50/50 | 2.56 MW | 2.56 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315160 | 1KERR 3 | 50/50 | 2.56 MW | 2.56 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315161 | 1KERR 4 | 50/50 | 2.56 MW | 2.56 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315162 | 1KERR 5 | 50/50 | 2.56 MW | 2.56 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942461 | AE2-259 C O1 | Adder | 4.5 MW | 3.83 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942462 | AE2-259 E O1 | Adder | 3.0 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 943901 | AF1-058 C | Adder | 0.67 MW | 0.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 943902 | AF1-058 E | Adder | 0.45 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958801 | AF2-171 C | 50/50 | 10.97 MW | 10.97 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958802 | AF2-171 E | 50/50 | 7.31 MW | 7.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959311 | AF2-222 C | 50/50 | 15.11 MW | 15.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959312 | AF2-222 E | 50/50 | 10.12 MW | 10.12 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 960061 | AF2-297 C | Adder | 2.7 MW | 2.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 960062 | AF2-297 E | Adder | 1.8 MW | 1.53 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315163 | 1KERR 6 | 50/50 | 2.56 MW | 2.56 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315164 | 1KERR 7 | 50/50 | 2.56 MW | 2.56 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924162 | AB2-060 E OP | 50/50 | 4.98 MW | 4.98 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924301 | AB2-077 C O1 | 50/50 | 2.4 MW | 2.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924302 | AB2-077 E O1 | 50/50 | 1.6 MW | 1.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924311 | AB2-078 C O1 | 50/50 | 2.4 MW | 2.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924312 | AB2-078 E O1 | 50/50 | 1.6 MW | 1.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924321 | AB2-079 C O1 | 50/50 | 2.4 MW | 2.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924322 | AB2-079 E O1 | 50/50 | 1.6 MW | 1.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938371 | AE1-056 C | Adder | 4.22 MW | 3.59 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938372 | AE1-056 E | Adder | 2.31 MW | 1.96 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 940661 | AE2-053 O1 | 50/50 | 6.41 MW | 6.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946301 | AF1-294 C | Adder | 2.97 MW | 2.53 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946302 | AF1-294 E | Adder | 1.98 MW | 1.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958211 | AF2-115 C | Adder | 1.81 MW | 1.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958212 | AF2-115 E | Adder | 1.21 MW | 1.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924021 | AB2-043 C O1 | 50/50 | 0.65 MW | 0.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924022 | AB2-043 E O1 | 50/50 | 3.33 MW | 3.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924161 | AB2-060 C OP | 50/50 | 1.83 MW | 1.83 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925781 | AC1-054 C O1 | 50/50 | 15.62 MW | 15.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925782 | AC1-054 E O1 | 50/50 | 7.2 MW | 7.2 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 926271 | AC1-105 C O1 | Adder | 2.9 MW | 2.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 926272 | AC1-105 E O1 | Adder | 1.44 MW | 1.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936261 | AD2-033 C | 50/50 | 12.75 MW | 12.75 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936262 | AD2-033 E | 50/50 | 8.5 MW | 8.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939181 | AE1-148 C O1 | 50/50 | 17.29 MW | 17.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939182 | AE1-148 E O1 | 50/50 | 11.53 MW | 11.53 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 940241 | AE2-006 | 50/50 | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925611 | AC1-036 C | 50/50 | 0.89 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925612 | AC1-036 E | 50/50 | 1.45 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.18 MW | 0.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.49 MW | 0.49 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.23 MW | 1.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.08 MW | 0.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.39 MW | 0.39 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.14 MW | 0.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.24 MW | 0.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.66 MW | 0.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.43 MW | 0.43 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315158 | 1KERR 1 | 50/50 | 0.72 MW | 0.72 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315159 | 1KERR 2 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315160 | 1KERR 3 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315161 | 1KERR 4 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315162 | 1KERR 5 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 918492 | AA1-063AE OP | Adder | 1.51 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 919692 | AA2-053 E OP | Adder | 1.5 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958801 | AF2-171 C | 50/50 | 16.6 MW | 16.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958802 | AF2-171 E | 50/50 | 11.07 MW | 11.07 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 959311 | AF2-222 C | 50/50 | 18.45 MW | 18.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 959312 | AF2-222 E | 50/50 | 12.36 MW | 12.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 960081 | AF2-299 C | Adder | 0.95 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 960082 | AF2-299 E | Adder | 0.63 MW | 0.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315163 | 1KERR 6 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315164 | 1KERR 7 | 50/50 | 2.02 MW | 2.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 923573 | AB1-173 E OP | Adder | 0.43 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 923991 | AB2-040 C O1 | Adder | 3.01 MW | 2.56 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 923992 | AB2-040 E O1 | Adder | 2.46 MW | 2.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924162 | AB2-060 E OP | Adder | 4.72 MW | 4.01 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 938371 | AE1-056 C | 50/50 | 7.16 MW | 7.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 938372 | AE1-056 E | 50/50 | 3.91 MW | 3.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 940661 | AE2-053 O1 | 50/50 | 5.17 MW | 5.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 946281 | AF1-292 C | Adder | 0.56 MW | 0.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 946282 | AF1-292 E | Adder | 0.38 MW | 0.32 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 946301 | AF1-294 C | Adder | 4.54 MW | 3.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 946302 | AF1-294 E | Adder | 3.02 MW | 2.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958211 | AF2-115 C | Adder | 2.77 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958212 | AF2-115 E | Adder | 1.84 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 920672 | AA2-174 E OP | Adder | 0.17 MW | 0.15 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 923911 | AB2-031 C O1 | Adder | 0.92 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 923912 | AB2-031 E O1 | Adder | 0.45 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924021 | AB2-043 C O1 | 50/50 | 0.6 MW | 0.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924022 | AB2-043 E O1 | 50/50 | 3.12 MW | 3.12 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925172 | AB2-174 E O1 | Adder | 2.54 MW | 2.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925781 | AC1-054 C O1 | 50/50 | 10.07 MW | 10.07 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925782 | AC1-054 E O1 | 50/50 | 4.64 MW | 4.64 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 926271 | AC1-105 C O1 | Adder | 2.57 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 926272 | AC1-105 E O1 | Adder | 1.28 MW | 1.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 936261 | AD2-033 C | Adder | 14.39 MW | 12.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 936262 | AD2-033 E | Adder | 9.59 MW | 8.15 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 939181 | AE1-148 C O1 | 50/50 | 13.96 MW | 13.96 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 939182 | AE1-148 E O1 | 50/50 | 9.3 MW | 9.3 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 940241 | AE2-006 | 50/50 | 0.54 MW | 0.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 923572 | AB1-173 C OP | Adder | 0.92 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 923582 | AB1-173AC OP | Adder | 0.92 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 923583 | AB1-173AE OP | Adder | 0.43 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925611 | AC1-036 C | 50/50 | 1.05 MW | 1.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925612 | AC1-036 E | 50/50 | 1.72 MW | 1.72 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.48 MW | 0.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.19 MW | 0.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.49 MW | 0.49 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.23 MW | 0.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.09 MW | 0.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.39 MW | 0.39 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.14 MW | 0.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.26 MW | 0.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.71 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.23 MW | 0.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315126 | 1ROARAP2 | 50/50 | 3.94 MW | 3.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315128 | 1ROARAP4 | 50/50 | 3.76 MW | 3.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315160 | 1KERR 3 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315161 | 1KERR 4 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315162 | 1KERR 5 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919692 | AA2-053 E OP | 50/50 | 8.61 MW | 8.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919702 | AA2-057 E OP | Adder | 2.28 MW | 1.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920042 | AA2-088 E OP | 50/50 | 13.29 MW | 13.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920592 | AA2-165 E | Adder | 0.39 MW | 0.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926201 | AC1-098 C | Adder | 5.7 MW | 4.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926202 | AC1-098 E | Adder | 3.4 MW | 2.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926211 | AC1-099 C | Adder | 1.91 MW | 1.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926212 | AC1-099 E | Adder | 1.12 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943171 | AE2-346 C | Adder | 0.79 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959311 | AF2-222 C | Adder | 8.14 MW | 6.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959312 | AF2-222 E | Adder | 5.45 MW | 4.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315163 | 1KERR 6 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315164 | 1KERR 7 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315606 | 3AA2-053SOLA | 50/50 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 917332 | Z2-043 E | Adder | 0.69 MW | 0.59 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923573 | AB1-173 E OP | 50/50 | 2.84 MW | 2.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923991 | AB2-040 C O1 | 50/50 | 19.86 MW | 19.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923992 | AB2-040 E O1 | 50/50 | 16.25 MW | 16.25 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924162 | AB2-060 E OP | Adder | 2.69 MW | 2.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924301 | AB2-077 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924302 | AB2-077 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924311 | AB2-078 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924312 | AB2-078 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924321 | AB2-079 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924322 | AB2-079 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932631 | AC2-084 C | Adder | 8.13 MW | 6.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932632 | AC2-084 E | Adder | 4.0 MW | 3.4 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 940661 | AE2-053 O1 | Adder | 3.14 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957521 | AF2-046 C | Adder | 16.0 MW | 13.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957522 | AF2-046 E | Adder | 8.05 MW | 6.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314539 | 3UNCAMP | Adder | 1.75 MW | 1.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315607 | 3AA1-063SOLA | 50/50 | 3.19 MW | 3.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315608 | 3AA2-088SOLA | 50/50 | 1.41 MW | 1.41 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920671 | AA2-174 C OP | 50/50 | 0.16 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920672 | AA2-174 E OP | 50/50 | 0.99 MW | 0.99 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923911 | AB2-031 C O1 | 50/50 | 6.05 MW | 6.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923912 | AB2-031 E O1 | 50/50 | 2.98 MW | 2.98 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924022 | AB2-043 E O1 | Adder | 1.8 MW | 1.53 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924501 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924502 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925172 | AB2-174 E O1 | 50/50 | 17.15 MW | 17.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925781 | AC1-054 C O1 | 50/50 | 10.69 MW | 10.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925782 | AC1-054 E O1 | 50/50 | 4.92 MW | 4.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927141 | AC1-208 C | 50/50 | 11.27 MW | 11.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927142 | AC1-208 E | 50/50 | 5.01 MW | 5.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936261 | AD2-033 C | Adder | 6.88 MW | 5.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936262 | AD2-033 E | Adder | 4.58 MW | 3.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939181 | AE1-148 C O1 | Adder | 8.48 MW | 7.2 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939182 | AE1-148 E O1 | Adder | 5.65 MW | 4.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 940241 | AE2-006 | Adder | 0.24 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923572 | AB1-173 C OP | 50/50 | 6.09 MW | 6.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923582 | AB1-173AC OP | 50/50 | 6.09 MW | 6.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923583 | AB1-173AE OP | 50/50 | 2.84 MW | 2.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925611 | AC1-036 C | Adder | 0.48 MW | 0.41 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925612 | AC1-036 E | Adder | 0.78 MW | 0.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 907092 | X1-038 E | Adder | 4.38 MW | 3.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925171 | AB2-174 C O1 | 50/50 | 3.29 MW | 3.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938771 | AE1-103 C O1 | Adder | 2.1 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938772 | AE1-103 E O1 | Adder | 2.9 MW | 2.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 918561 | AA1-072 C | Adder | 0.21 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 918562 | AA1-072 E | Adder | 0.1 MW | 0.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.86 MW | 0.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.23 MW | 1.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 1.02 MW | 1.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.84 MW | 0.84 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314572 | 3EMPORIA | 50/50 | 0.2 MW | 0.2 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315126 | 1ROARAP2 | 50/50 | 3.94 MW | 3.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315128 | 1ROARAP4 | 50/50 | 3.76 MW | 3.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315160 | 1KERR 3 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315161 | 1KERR 4 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315162 | 1KERR 5 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 919692 | AA2-053 E OP | 50/50 | 8.61 MW | 8.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 919702 | AA2-057 E OP | Adder | 2.28 MW | 1.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 920042 | AA2-088 E OP | 50/50 | 13.29 MW | 13.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 920592 | AA2-165 E | Adder | 0.39 MW | 0.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926201 | AC1-098 C | Adder | 5.7 MW | 4.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926202 | AC1-098 E | Adder | 3.4 MW | 2.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926211 | AC1-099 C | Adder | 1.91 MW | 1.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926212 | AC1-099 E | Adder | 1.12 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 943171 | AE2-346 C | Adder | 0.79 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 959311 | AF2-222 C | Adder | 8.14 MW | 6.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 959312 | AF2-222 E | Adder | 5.45 MW | 4.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315163 | 1KERR 6 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315164 | 1KERR 7 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315606 | 3AA2-053SOLA | 50/50 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 917332 | Z2-043 E | Adder | 0.69 MW | 0.59 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923573 | AB1-173 E OP | 50/50 | 2.84 MW | 2.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923991 | AB2-040 C O1 | 50/50 | 19.86 MW | 19.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923992 | AB2-040 E O1 | 50/50 | 16.25 MW | 16.25 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924162 | AB2-060 E OP | Adder | 2.69 MW | 2.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924301 | AB2-077 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924302 | AB2-077 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924311 | AB2-078 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924312 | AB2-078 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924321 | AB2-079 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924322 | AB2-079 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 932631 | AC2-084 C | Adder | 8.13 MW | 6.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 932632 | AC2-084 E | Adder | 4.0 MW | 3.4 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 940661 | AE2-053 O1 | Adder | 3.14 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 957521 | AF2-046 C | Adder | 16.0 MW | 13.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 957522 | AF2-046 E | Adder | 8.05 MW | 6.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314539 | 3UNCAMP | Adder | 1.75 MW | 1.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315607 | 3AA1-063SOLA | 50/50 | 3.19 MW | 3.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315608 | 3AA2-088SOLA | 50/50 | 1.41 MW | 1.41 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 920671 | AA2-174 C OP | 50/50 | 0.16 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 920672 | AA2-174 E OP | 50/50 | 0.99 MW | 0.99 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923911 | AB2-031 C O1 | 50/50 | 6.05 MW | 6.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923912 | AB2-031 E O1 | 50/50 | 2.98 MW | 2.98 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924022 | AB2-043 E O1 | Adder | 1.8 MW | 1.53 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924501 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924502 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925172 | AB2-174 E O1 | 50/50 | 17.15 MW | 17.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925781 | AC1-054 C O1 | 50/50 | 10.69 MW | 10.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925782 | AC1-054 E O1 | 50/50 | 4.92 MW | 4.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 927141 | AC1-208 C | 50/50 | 11.27 MW | 11.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 927142 | AC1-208 E | 50/50 | 5.01 MW | 5.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 936261 | AD2-033 C | Adder | 6.88 MW | 5.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 936262 | AD2-033 E | Adder | 4.58 MW | 3.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 939181 | AE1-148 C O1 | Adder | 8.48 MW | 7.2 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 939182 | AE1-148 E O1 | Adder | 5.65 MW | 4.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 940241 | AE2-006 | Adder | 0.24 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923572 | AB1-173 C OP | 50/50 | 6.09 MW | 6.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923582 | AB1-173AC OP | 50/50 | 6.09 MW | 6.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923583 | AB1-173AE OP | 50/50 | 2.84 MW | 2.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925611 | AC1-036 C | Adder | 0.48 MW | 0.41 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925612 | AC1-036 E | Adder | 0.78 MW | 0.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 907092 | X1-038 E | Adder | 4.38 MW | 3.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925171 | AB2-174 C O1 | 50/50 | 3.29 MW | 3.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 938771 | AE1-103 C O1 | Adder | 2.1 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 938772 | AE1-103 E O1 | Adder | 2.9 MW | 2.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 918561 | AA1-072 C | Adder | 0.21 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 918562 | AA1-072 E | Adder | 0.1 MW | 0.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.86 MW | 0.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.23 MW | 1.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 1.02 MW | 1.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.84 MW | 0.84 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314572 | 3EMPORIA | 50/50 | 0.2 MW | 0.2 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315126 | 1ROARAP2 | 50/50 | 3.94 MW | 3.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315128 | 1ROARAP4 | 50/50 | 3.76 MW | 3.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315160 | 1KERR 3 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315161 | 1KERR 4 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315162 | 1KERR 5 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 919692 | AA2-053 E OP | 50/50 | 8.61 MW | 8.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 919702 | AA2-057 E OP | Adder | 2.28 MW | 1.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920042 | AA2-088 E OP | 50/50 | 13.29 MW | 13.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920592 | AA2-165 E | Adder | 0.39 MW | 0.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926201 | AC1-098 C | Adder | 5.7 MW | 4.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926202 | AC1-098 E | Adder | 3.4 MW | 2.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926211 | AC1-099 C | Adder | 1.91 MW | 1.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926212 | AC1-099 E | Adder | 1.12 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 943171 | AE2-346 C | Adder | 0.79 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 959311 | AF2-222 C | Adder | 8.14 MW | 6.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 959312 | AF2-222 E | Adder | 5.45 MW | 4.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315163 | 1KERR 6 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315164 | 1KERR 7 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315606 | 3AA2-053SOLA | 50/50 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 917332 | Z2-043 E | Adder | 0.69 MW | 0.59 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923573 | AB1-173 E OP | 50/50 | 2.84 MW | 2.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923991 | AB2-040 C O1 | 50/50 | 19.86 MW | 19.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923992 | AB2-040 E O1 | 50/50 | 16.25 MW | 16.25 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924162 | AB2-060 E OP | Adder | 2.69 MW | 2.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924301 | AB2-077 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924302 | AB2-077 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924311 | AB2-078 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924312 | AB2-078 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924321 | AB2-079 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924322 | AB2-079 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 932631 | AC2-084 C | Adder | 8.13 MW | 6.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 932632 | AC2-084 E | Adder | 4.0 MW | 3.4 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 940661 | AE2-053 O1 | Adder | 3.14 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 957521 | AF2-046 C | Adder | 16.0 MW | 13.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 957522 | AF2-046 E | Adder | 8.05 MW | 6.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314539 | 3UNCAMP | Adder | 1.75 MW | 1.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315607 | 3AA1-063SOLA | 50/50 | 3.19 MW | 3.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315608 | 3AA2-088SOLA | 50/50 | 1.41 MW | 1.41 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920671 | AA2-174 C OP | 50/50 | 0.16 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920672 | AA2-174 E OP | 50/50 | 0.99 MW | 0.99 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923911 | AB2-031 C O1 | 50/50 | 6.05 MW | 6.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923912 | AB2-031 E O1 | 50/50 | 2.98 MW | 2.98 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924022 | AB2-043 E O1 | Adder | 1.8 MW | 1.53 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924501 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924502 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925172 | AB2-174 E O1 | 50/50 | 17.15 MW | 17.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925781 | AC1-054 C O1 | 50/50 | 10.69 MW | 10.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925782 | AC1-054 E O1 | 50/50 | 4.92 MW | 4.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 927141 | AC1-208 C | 50/50 | 11.27 MW | 11.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 927142 | AC1-208 E | 50/50 | 5.01 MW | 5.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 936261 | AD2-033 C | Adder | 6.88 MW | 5.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 936262 | AD2-033 E | Adder | 4.58 MW | 3.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 939181 | AE1-148 C O1 | Adder | 8.47 MW | 7.2 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 939182 | AE1-148 E O1 | Adder | 5.65 MW | 4.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 940241 | AE2-006 | Adder | 0.24 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923572 | AB1-173 C OP | 50/50 | 6.09 MW | 6.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923582 | AB1-173AC OP | 50/50 | 6.09 MW | 6.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923583 | AB1-173AE OP | 50/50 | 2.84 MW | 2.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925611 | AC1-036 C | Adder | 0.48 MW | 0.41 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925612 | AC1-036 E | Adder | 0.78 MW | 0.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 907092 | X1-038 E | Adder | 4.38 MW | 3.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925171 | AB2-174 C O1 | 50/50 | 3.29 MW | 3.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 938771 | AE1-103 C O1 | Adder | 2.1 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 938772 | AE1-103 E O1 | Adder | 2.9 MW | 2.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 918561 | AA1-072 C | Adder | 0.21 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 918562 | AA1-072 E | Adder | 0.1 MW | 0.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.85 MW | 0.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.96 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 1.01 MW | 1.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.83 MW | 0.83 MW |
| Details for 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314541 | 3WATKINS | Adder | 0.46 MW | 0.39 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314572 | 3EMPORIA | 50/50 | 0.18 MW | 0.18 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314704 | 3LAWRENC | 50/50 | 0.67 MW | 0.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315126 | 1ROARAP2 | 50/50 | 2.46 MW | 2.46 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315131 | 1EDGECMA | Adder | 9.28 MW | 7.88 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315132 | 1EDGECMB | Adder | 9.28 MW | 7.88 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315136 | 1ROSEMG1 | 50/50 | 4.44 MW | 4.44 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315137 | 1ROSEMS1 | 50/50 | 2.75 MW | 2.75 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315138 | 1ROSEMG2 | 50/50 | 2.08 MW | 2.08 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315139 | 1GASTONA | 50/50 | 6.78 MW | 6.78 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918492 | AA1-063AE OP | Adder | 5.76 MW | 4.9 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918532 | AA1-067 E | Adder | 0.78 MW | 0.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 919692 | AA2-053 E OP | Adder | 6.09 MW | 5.17 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 919702 | AA2-057 E OP | Adder | 4.4 MW | 3.74 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920042 | AA2-088 E OP | Adder | 10.41 MW | 8.85 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920592 | AA2-165 E | Adder | 0.74 MW | 0.63 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926201 | AC1-098 C | Adder | 8.36 MW | 7.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926202 | AC1-098 E | Adder | 4.98 MW | 4.23 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926211 | AC1-099 C | Adder | 2.8 MW | 2.38 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926212 | AC1-099 E | Adder | 1.64 MW | 1.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 934331 | AD1-057 C O1 | Adder | 15.75 MW | 13.39 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 934332 | AD1-057 E O1 | Adder | 8.42 MW | 7.16 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 934521 | AD1-076 C | Adder | 48.94 MW | 41.6 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 934522 | AD1-076 E | Adder | 24.92 MW | 21.18 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 943171 | AE2-346 C | Adder | 1.78 MW | 1.51 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 943172 | AE2-346 E | Adder | 0.76 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 944141 | AF1-082 | Adder | 3.29 MW | 2.8 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 959311 | AF2-222 C | Adder | 10.68 MW | 9.08 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 959312 | AF2-222 E | Adder | 7.16 MW | 6.08 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 960081 | AF2-299 C | 50/50 | 6.55 MW | 6.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 960082 | AF2-299 E | 50/50 | 4.37 MW | 4.37 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315294 | 1DOMTR10 | Adder | 10.18 MW | 8.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 900672 | V4-068 E | Adder | 0.34 MW | 0.28 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 917332 | Z2-043 E | Adder | 1.54 MW | 1.31 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 917342 | Z2-044 E | Adder | 0.7 MW | 0.59 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 922922 | AB1-081 C OP | Adder | 10.25 MW | 8.71 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 922923 | AB1-081 E OP | Adder | 4.39 MW | 3.73 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923262 | AB1-132 C OP | 50/50 | 29.81 MW | 29.81 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923263 | AB1-132 E OP | 50/50 | 12.78 MW | 12.78 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923573 | AB1-173 E OP | 50/50 | 2.32 MW | 2.32 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923991 | AB2-040 C O1 | 50/50 | 16.22 MW | 16.22 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923992 | AB2-040 E O1 | 50/50 | 13.27 MW | 13.27 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924152 | AB2-059 E OP | Adder | 6.22 MW | 5.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924162 | AB2-060 E OP | Adder | 3.6 MW | 3.06 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924301 | AB2-077 C O1 | Adder | 1.69 MW | 1.44 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924302 | AB2-077 E O1 | Adder | 1.13 MW | 0.96 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924311 | AB2-078 C O1 | Adder | 1.69 MW | 1.44 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924312 | AB2-078 E O1 | Adder | 1.13 MW | 0.96 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924321 | AB2-079 C O1 | Adder | 1.69 MW | 1.44 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924322 | AB2-079 E O1 | Adder | 1.13 MW | 0.96 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925122 | AB2-169 E | Adder | 5.67 MW | 4.82 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925591 | AC1-034 C | Adder | 7.82 MW | 6.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925592 | AC1-034 E | Adder | 5.9 MW | 5.02 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 932631 | AC2-084 C | Adder | 11.91 MW | 10.13 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 932632 | AC2-084 E | Adder | 5.87 MW | 4.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 938222 | AE1-035 E | Adder | 1.41 MW | 1.2 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 940491 | AE2-034 C | Adder | 5.34 MW | 4.54 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 940492 | AE2-034 E | Adder | 2.29 MW | 1.95 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 940571 | AE2-044 C | Adder | 5.12 MW | 4.36 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 940572 | AE2-044 E | Adder | 2.2 MW | 1.87 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 940661 | AE2-053 O1 | Adder | 3.08 MW | 2.62 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 946281 | AF1-292 C | 50/50 | 3.9 MW | 3.9 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 946282 | AF1-292 E | 50/50 | 2.6 MW | 2.6 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957521 | AF2-046 C | Adder | 19.35 MW | 16.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957522 | AF2-046 E | Adder | 9.74 MW | 8.28 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957531 | AF2-047 C | Adder | 12.7 MW | 10.79 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957532 | AF2-047 E | Adder | 6.39 MW | 5.43 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957861 | AF2-080 C | Adder | 8.58 MW | 7.3 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957862 | AF2-080 E | Adder | 3.81 MW | 3.23 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315141 | 1GASTONB | 50/50 | 6.78 MW | 6.78 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 938221 | AE1-035 C | Adder | 2.9 MW | 2.46 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 917512 | Z2-088 E OP1 | Adder | 8.88 MW | 7.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920672 | AA2-174 E OP | Adder | 0.7 MW | 0.6 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923911 | AB2-031 C O1 | 50/50 | 4.94 MW | 4.94 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923912 | AB2-031 E O1 | 50/50 | 2.43 MW | 2.43 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924022 | AB2-043 E O1 | Adder | 2.41 MW | 2.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924501 | AB2-099 C | Adder | 0.74 MW | 0.63 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924502 | AB2-099 E | Adder | 0.32 MW | 0.27 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924512 | AB2-100 E | 50/50 | 17.75 MW | 17.75 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925172 | AB2-174 E O1 | 50/50 | 14.72 MW | 14.72 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925781 | AC1-054 C O1 | Adder | 8.38 MW | 7.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925782 | AC1-054 E O1 | Adder | 3.86 MW | 3.28 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926071 | AC1-086 C | 50/50 | 43.9 MW | 43.9 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926072 | AC1-086 E | 50/50 | 19.98 MW | 19.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927021 | AC1-189 C | Adder | 9.45 MW | 8.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927022 | AC1-189 E | Adder | 4.71 MW | 4.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927141 | AC1-208 C | Adder | 12.71 MW | 10.8 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927142 | AC1-208 E | Adder | 5.64 MW | 4.8 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 936261 | AD2-033 C | Adder | 9.08 MW | 7.72 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 936262 | AD2-033 E | Adder | 6.05 MW | 5.14 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 939181 | AE1-148 C O1 | Adder | 8.32 MW | 7.08 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 939182 | AE1-148 E O1 | Adder | 5.55 MW | 4.72 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 940241 | AE2-006 | Adder | 0.32 MW | 0.27 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923572 | AB1-173 C OP | 50/50 | 4.98 MW | 4.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923582 | AB1-173AC OP | 50/50 | 4.98 MW | 4.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923583 | AB1-173AE OP | 50/50 | 2.32 MW | 2.32 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925611 | AC1-036 C | Adder | 0.63 MW | 0.54 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925612 | AC1-036 E | Adder | 1.03 MW | 0.88 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 960331 | AF2-324 C O1 | Adder | 9.05 MW | 7.7 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 960332 | AF2-324 E O1 | Adder | 4.86 MW | 4.13 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920692 | AA2-178 E | Adder | 3.05 MW | 2.6 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924511 | AB2-100 C | 50/50 | 6.25 MW | 6.25 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925171 | AB2-174 C O1 | 50/50 | 2.82 MW | 2.82 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918561 | AA1-072 C | Adder | 0.46 MW | 0.39 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918562 | AA1-072 E | Adder | 0.22 MW | 0.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 933981 | AD1-022 C | Adder | 8.77 MW | 7.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 933982 | AD1-022 E | Adder | 4.77 MW | 4.06 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918512 | AA1-065 E OP | Adder | 5.71 MW | 4.86 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 940542 | AE2-040 BAT | Adder | 4.66 MW | 3.96 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 946012 | AF1-266 BAT | Adder | 24.54 MW | 20.86 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.61 MW | 0.61 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.77 MW | 3.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.91 MW | 12.91 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.69 MW | 2.69 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 5.56 MW | 5.56 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.39 MW | 23.39 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 15.06 MW | 15.06 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.87 MW | 0.87 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.73 MW | 0.73 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.97 MW | 1.97 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.57 MW | 2.57 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.37 MW | 12.37 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-A | 942461 | AE2-259 C O1 | 80/20 | 60.0 MW | 60.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-A | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-A | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-A | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-A | 940241 | AE2-006 | 80/20 | 2.9 MW | 2.9 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-A | 925611 | AC1-036 C | 80/20 | 5.7 MW | 5.7 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 942461 | AE2-259 C O1 | 80/20 | 60.0 MW | 60.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o 314679 3CENTRAL 115 314681 3CHASCTY 115 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o 314679 3CENTRAL 115 314681 3CHASCTY 115 1 | 942461 | AE2-259 C O1 | 80/20 | 60.0 MW | 60.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o 314679 3CENTRAL 115 314681 3CHASCTY 115 1 | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o 314679 3CENTRAL 115 314681 3CHASCTY 115 1 | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o 314679 3CENTRAL 115 314681 3CHASCTY 115 1 | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o 314679 3CENTRAL 115 314681 3CHASCTY 115 1 | 940241 | AE2-006 | 80/20 | 2.9 MW | 2.9 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o 314679 3CENTRAL 115 314681 3CHASCTY 115 1 | 925611 | AC1-036 C | 80/20 | 5.7 MW | 5.7 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313853 | 3PONTONDP | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.9 MW | 0.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314572 | 3EMPORIA | 80/20 | 0.03 MW | 0.03 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315126 | 1ROARAP2 | 80/20 | 0.57 MW | 0.57 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 22.59 MW | 22.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 22.37 MW | 22.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.42 MW | 0.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.67 MW | 1.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 4.06 MW | 4.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.82 MW | 2.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 4.18 MW | 4.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.37 MW | 1.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 4.22 MW | 4.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.46 MW | 2.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 3.76 MW | 3.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 30.49 MW | 30.49 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 8.29 MW | 8.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 2.29 MW | 2.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 12.38 MW | 12.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 36.06 MW | 36.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 33.36 MW | 33.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 9.16 MW | 9.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960081 | AF2-299 C | 80/20 | 1.03 MW | 1.03 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923991 | AB2-040 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.84 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 16.71 MW | 16.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.49 MW | 3.49 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 5.73 MW | 5.73 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 9.92 MW | 9.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 88.44 MW | 88.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | Adder | -0.9 MW | -0.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923911 | AB2-031 C O1 | 80/20 | 0.9 MW | 0.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924021 | AB2-043 C O1 | 80/20 | 0.75 MW | 0.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924161 | AB2-060 C OP | 80/20 | 2.21 MW | 2.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925781 | AC1-054 C O1 | 80/20 | 6.09 MW | 6.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925991 | AC1-075 C | 80/20 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926021 | AC1-080 C | 80/20 | 1.66 MW | 1.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926271 | AC1-105 C O1 | 80/20 | 6.77 MW | 6.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934611 | AD1-087 C O1 | 80/20 | 12.85 MW | 12.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936261 | AD2-033 C | 80/20 | 23.81 MW | 23.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C O1 | 80/20 | 9.42 MW | 9.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940241 | AE2-006 | 80/20 | 0.93 MW | 0.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C O1 | 80/20 | 6.66 MW | 6.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923572 | AB1-173 C OP | 80/20 | 0.9 MW | 0.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923582 | AB1-173AC OP | 80/20 | 0.9 MW | 0.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 1.84 MW | 1.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925171 | AB2-174 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925831 | AC1-062 | 80/20 | 0.13 MW | 0.13 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934621 | AD1-088 C | 80/20 | 35.28 MW | 35.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.44 MW | 3.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.07 MW | 12.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.38 MW | 0.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.0 MW | 23.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.29 MW | 14.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.77 MW | 0.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.78 MW | 1.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.34 MW | 2.34 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.83 MW | 10.83 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 313853 | 3PONTONDP | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314429 | 3JTRSVLE | 80/20 | 0.9 MW | 0.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314572 | 3EMPORIA | 80/20 | 0.03 MW | 0.03 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315126 | 1ROARAP2 | 80/20 | 0.57 MW | 0.57 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315153 | 1CLOVER1 | 80/20 | 22.59 MW | 22.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315154 | 1CLOVER2 | 80/20 | 22.37 MW | 22.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315158 | 1KERR 1 | 80/20 | 0.42 MW | 0.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315159 | 1KERR 2 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315160 | 1KERR 3 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315161 | 1KERR 4 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315162 | 1KERR 5 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 927251 | AC1-221 C | 80/20 | 1.67 MW | 1.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 927261 | AC1-222 C | 80/20 | 4.06 MW | 4.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934311 | AD1-055 C | 80/20 | 2.82 MW | 2.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934341 | AD1-058 C | 80/20 | 4.18 MW | 4.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934991 | AD1-131 C | 80/20 | 1.37 MW | 1.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 935171 | AD1-152 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 936161 | AD2-022 C O1 | 80/20 | 4.22 MW | 4.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 936171 | AD2-023 C O1 | 80/20 | 2.46 MW | 2.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 937481 | AD2-202 C O1 | 80/20 | 3.76 MW | 3.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942461 | AE2-259 C O1 | 80/20 | 30.49 MW | 30.49 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942761 | AE2-292 C O1 | 80/20 | 8.29 MW | 8.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 943901 | AF1-058 C | 80/20 | 2.29 MW | 2.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 958801 | AF2-171 C | 80/20 | 36.06 MW | 36.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 959311 | AF2-222 C | 80/20 | 33.36 MW | 33.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 960061 | AF2-297 C | 80/20 | 9.16 MW | 9.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 960081 | AF2-299 C | 80/20 | 1.03 MW | 1.03 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315163 | 1KERR 6 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315164 | 1KERR 7 | 80/20 | 1.17 MW | 1.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315266 | 1PLYWOOD A | 80/20 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 923991 | AB2-040 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924301 | AB2-077 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924311 | AB2-078 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924321 | AB2-079 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 932761 | AC2-100 C | 80/20 | 3.84 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 938371 | AE1-056 C | 80/20 | 16.71 MW | 16.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 940661 | AE2-053 O1 | 80/20 | 3.49 MW | 3.49 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 941791 | AE2-182 C | 80/20 | 5.73 MW | 5.73 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 946301 | AF1-294 C | 80/20 | 9.92 MW | 9.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 958211 | AF2-115 C | 80/20 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 958501 | AF2-144 C | Adder | -0.9 MW | -0.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 923911 | AB2-031 C O1 | 80/20 | 0.9 MW | 0.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924021 | AB2-043 C O1 | 80/20 | 0.75 MW | 0.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924161 | AB2-060 C OP | 80/20 | 2.21 MW | 2.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925781 | AC1-054 C O1 | 80/20 | 6.09 MW | 6.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925991 | AC1-075 C | 80/20 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 926021 | AC1-080 C | 80/20 | 1.66 MW | 1.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 926271 | AC1-105 C O1 | 80/20 | 6.77 MW | 6.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934611 | AD1-087 C O1 | 80/20 | 12.85 MW | 12.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 936261 | AD2-033 C | 80/20 | 23.81 MW | 23.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 939181 | AE1-148 C O1 | 80/20 | 9.42 MW | 9.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 940241 | AE2-006 | 80/20 | 0.93 MW | 0.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942751 | AE2-291 C O1 | 80/20 | 6.66 MW | 6.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 923572 | AB1-173 C OP | 80/20 | 0.9 MW | 0.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 923582 | AB1-173AC OP | 80/20 | 0.9 MW | 0.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925611 | AC1-036 C | 80/20 | 1.84 MW | 1.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925171 | AB2-174 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925831 | AC1-062 | 80/20 | 0.13 MW | 0.13 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934621 | AD1-088 C | 80/20 | 35.28 MW | 35.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.44 MW | 3.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.07 MW | 12.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.38 MW | 0.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.0 MW | 23.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.29 MW | 14.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.77 MW | 0.77 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.78 MW | 1.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.34 MW | 2.34 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.83 MW | 10.83 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313853 | 3PONTONDP | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.9 MW | 0.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314572 | 3EMPORIA | 80/20 | 0.03 MW | 0.03 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315126 | 1ROARAP2 | 80/20 | 0.57 MW | 0.57 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 22.59 MW | 22.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 22.36 MW | 22.36 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.42 MW | 0.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.67 MW | 1.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 4.06 MW | 4.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.82 MW | 2.82 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 4.18 MW | 4.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.37 MW | 1.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.03 MW | 12.03 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.46 MW | 2.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 3.76 MW | 3.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 30.48 MW | 30.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 8.28 MW | 8.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 2.29 MW | 2.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 12.38 MW | 12.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 36.05 MW | 36.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 33.35 MW | 33.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 9.16 MW | 9.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960081 | AF2-299 C | 80/20 | 1.03 MW | 1.03 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923991 | AB2-040 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.83 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 16.71 MW | 16.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.49 MW | 3.49 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 5.73 MW | 5.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 9.92 MW | 9.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 88.42 MW | 88.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 1.64 MW | 1.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923911 | AB2-031 C O1 | 80/20 | 0.9 MW | 0.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924021 | AB2-043 C O1 | 80/20 | 0.75 MW | 0.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924161 | AB2-060 C OP | 80/20 | 2.21 MW | 2.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925781 | AC1-054 C O1 | 80/20 | 6.08 MW | 6.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925991 | AC1-075 C | 80/20 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926021 | AC1-080 C | 80/20 | 1.66 MW | 1.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926271 | AC1-105 C O1 | 80/20 | 6.76 MW | 6.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934611 | AD1-087 C O1 | 80/20 | 12.84 MW | 12.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936261 | AD2-033 C | 80/20 | 23.8 MW | 23.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C O1 | 80/20 | 9.41 MW | 9.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940241 | AE2-006 | 80/20 | 0.93 MW | 0.93 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C O1 | 80/20 | 6.65 MW | 6.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923572 | AB1-173 C OP | 80/20 | 0.9 MW | 0.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923582 | AB1-173AC OP | 80/20 | 0.9 MW | 0.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925171 | AB2-174 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925831 | AC1-062 | 80/20 | 0.13 MW | 0.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934621 | AD1-088 C | 80/20 | 35.27 MW | 35.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.54 MW | 0.54 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.43 MW | 3.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.02 MW | 12.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.38 MW | 0.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.57 MW | 2.57 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 22.96 MW | 22.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.23 MW | 14.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.77 MW | 0.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.77 MW | 1.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.34 MW | 2.34 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.75 MW | 10.75 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 313853 | 3PONTONDP | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314429 | 3JTRSVLE | 80/20 | 0.9 MW | 0.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314572 | 3EMPORIA | 80/20 | 0.03 MW | 0.03 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315126 | 1ROARAP2 | 80/20 | 0.57 MW | 0.57 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315153 | 1CLOVER1 | 80/20 | 22.59 MW | 22.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315154 | 1CLOVER2 | 80/20 | 22.36 MW | 22.36 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315158 | 1KERR 1 | 80/20 | 0.42 MW | 0.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315159 | 1KERR 2 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315160 | 1KERR 3 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315161 | 1KERR 4 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315162 | 1KERR 5 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 927251 | AC1-221 C | 80/20 | 1.67 MW | 1.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 927261 | AC1-222 C | 80/20 | 4.06 MW | 4.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934311 | AD1-055 C | 80/20 | 2.82 MW | 2.82 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934341 | AD1-058 C | 80/20 | 4.18 MW | 4.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934991 | AD1-131 C | 80/20 | 1.37 MW | 1.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 935171 | AD1-152 C O1 | 80/20 | 12.03 MW | 12.03 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 936161 | AD2-022 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 936171 | AD2-023 C O1 | 80/20 | 2.46 MW | 2.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 937481 | AD2-202 C O1 | 80/20 | 3.76 MW | 3.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942461 | AE2-259 C O1 | 80/20 | 30.48 MW | 30.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942761 | AE2-292 C O1 | 80/20 | 8.28 MW | 8.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 943901 | AF1-058 C | 80/20 | 2.29 MW | 2.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 958801 | AF2-171 C | 80/20 | 36.05 MW | 36.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 959311 | AF2-222 C | 80/20 | 33.35 MW | 33.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 960061 | AF2-297 C | 80/20 | 9.16 MW | 9.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 960081 | AF2-299 C | 80/20 | 1.03 MW | 1.03 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315163 | 1KERR 6 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315164 | 1KERR 7 | 80/20 | 1.17 MW | 1.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315266 | 1PLYWOOD A | 80/20 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 923991 | AB2-040 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924301 | AB2-077 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924311 | AB2-078 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924321 | AB2-079 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 932761 | AC2-100 C | 80/20 | 3.83 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 938371 | AE1-056 C | 80/20 | 16.71 MW | 16.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 940661 | AE2-053 O1 | 80/20 | 3.49 MW | 3.49 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 941791 | AE2-182 C | 80/20 | 5.73 MW | 5.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 946301 | AF1-294 C | 80/20 | 9.92 MW | 9.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 958211 | AF2-115 C | 80/20 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314677 | 6BUCKING | 80/20 | 1.64 MW | 1.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 958501 | AF2-144 C | Adder | -0.9 MW | -0.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 923911 | AB2-031 C O1 | 80/20 | 0.9 MW | 0.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924021 | AB2-043 C O1 | 80/20 | 0.75 MW | 0.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924161 | AB2-060 C OP | 80/20 | 2.21 MW | 2.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925781 | AC1-054 C O1 | 80/20 | 6.08 MW | 6.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925991 | AC1-075 C | 80/20 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 926021 | AC1-080 C | 80/20 | 1.66 MW | 1.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 926271 | AC1-105 C O1 | 80/20 | 6.76 MW | 6.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934611 | AD1-087 C O1 | 80/20 | 12.84 MW | 12.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 936261 | AD2-033 C | 80/20 | 23.8 MW | 23.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 939181 | AE1-148 C O1 | 80/20 | 9.41 MW | 9.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 940241 | AE2-006 | 80/20 | 0.93 MW | 0.93 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942751 | AE2-291 C O1 | 80/20 | 6.65 MW | 6.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 923572 | AB1-173 C OP | 80/20 | 0.9 MW | 0.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 923582 | AB1-173AC OP | 80/20 | 0.9 MW | 0.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925611 | AC1-036 C | 80/20 | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925171 | AB2-174 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925831 | AC1-062 | 80/20 | 0.13 MW | 0.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934621 | AD1-088 C | 80/20 | 35.27 MW | 35.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.54 MW | 0.54 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.43 MW | 3.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.02 MW | 12.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.38 MW | 0.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.57 MW | 2.57 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 22.96 MW | 22.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.23 MW | 14.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.77 MW | 0.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.77 MW | 1.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.34 MW | 2.34 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.75 MW | 10.75 MW |
| Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313853 | 3PONTONDP | 80/20 | 0.13 MW | 0.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 39.63 MW | 39.63 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 39.24 MW | 39.24 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 1.14 MW | 1.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.37 MW | 0.37 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 10.13 MW | 10.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 7.03 MW | 7.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 26.75 MW | 26.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 14.38 MW | 14.38 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 3.98 MW | 3.98 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 19.55 MW | 19.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 5.75 MW | 5.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 21.73 MW | 21.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 21.04 MW | 21.04 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 23.0 MW | 23.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 22.98 MW | 22.98 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.89 MW | 0.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 3.36 MW | 3.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 9.13 MW | 9.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.21 MW | 6.21 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 3.9 MW | 3.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 3.62 MW | 3.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 3.62 MW | 3.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.29 MW | 9.29 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 5.75 MW | 5.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.45 MW | 2.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 155.18 MW | 155.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 3.51 MW | 3.51 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 6.96 MW | 6.96 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 2.89 MW | 2.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 2.89 MW | 2.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 5.95 MW | 5.95 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924021 | AB2-043 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924161 | AB2-060 C OP | 80/20 | 2.12 MW | 2.12 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925781 | AC1-054 C O1 | 80/20 | 5.01 MW | 5.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925991 | AC1-075 C | 80/20 | 11.97 MW | 11.97 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926021 | AC1-080 C | 80/20 | 4.0 MW | 4.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926271 | AC1-105 C O1 | 80/20 | 14.51 MW | 14.51 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926641 | AC1-145 C | 80/20 | 1.91 MW | 1.91 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934611 | AD1-087 C O1 | 80/20 | 22.64 MW | 22.64 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936261 | AD2-033 C | 80/20 | 17.83 MW | 17.83 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C | 80/20 | 7.17 MW | 7.17 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C O1 | 80/20 | 8.51 MW | 8.51 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940241 | AE2-006 | 80/20 | 0.67 MW | 0.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C O1 | 80/20 | 15.7 MW | 15.7 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 1.31 MW | 1.31 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925831 | AC1-062 | 80/20 | 0.08 MW | 0.08 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934621 | AD1-088 C | 80/20 | 23.99 MW | 23.99 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 920291 | AA2-127 | 80/20 | 0.6 MW | 0.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.1 MW | 0.1 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.5 MW | 0.5 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.32 MW | 1.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.76 MW | 0.76 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.47 MW | 4.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | LTF | 5.14 MW | 5.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.3 MW | 0.3 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.47 MW | 1.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.48 MW | 0.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.83 MW | 0.83 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.43 MW | 1.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.31 MW | 2.31 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.73 MW | 0.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 313853 | 3PONTONDP | 80/20 | 0.13 MW | 0.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315153 | 1CLOVER1 | 80/20 | 39.63 MW | 39.63 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315154 | 1CLOVER2 | 80/20 | 39.24 MW | 39.24 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315156 | 1HALLBR1 | 80/20 | 1.14 MW | 1.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315158 | 1KERR 1 | 80/20 | 0.37 MW | 0.37 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315159 | 1KERR 2 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315160 | 1KERR 3 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315161 | 1KERR 4 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315162 | 1KERR 5 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 927261 | AC1-222 C | 80/20 | 10.13 MW | 10.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934311 | AD1-055 C | 80/20 | 7.03 MW | 7.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 935171 | AD1-152 C O1 | 80/20 | 26.75 MW | 26.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 937481 | AD2-202 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942461 | AE2-259 C O1 | 80/20 | 14.38 MW | 14.38 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942671 | AE2-283 C | 80/20 | 3.98 MW | 3.98 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942761 | AE2-292 C O1 | 80/20 | 19.55 MW | 19.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 943901 | AF1-058 C | 80/20 | 5.75 MW | 5.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 958801 | AF2-171 C | 80/20 | 21.04 MW | 21.04 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 959311 | AF2-222 C | 80/20 | 23.0 MW | 23.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 960061 | AF2-297 C | 80/20 | 22.98 MW | 22.98 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 960111 | AF2-302 C | 80/20 | 0.89 MW | 0.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315163 | 1KERR 6 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315164 | 1KERR 7 | 80/20 | 1.03 MW | 1.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315266 | 1PLYWOOD A | 80/20 | 3.36 MW | 3.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924301 | AB2-077 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924311 | AB2-078 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924321 | AB2-079 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925661 | AC1-042 C | 80/20 | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 938371 | AE1-056 C | 80/20 | 9.13 MW | 9.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 940661 | AE2-053 O1 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 941011 | AE2-092 C | 80/20 | 6.21 MW | 6.21 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 941791 | AE2-182 C | 80/20 | 3.9 MW | 3.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 941801 | AE2-185 C | 80/20 | 3.62 MW | 3.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 941821 | AE2-187 C | 80/20 | 3.62 MW | 3.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 946291 | AF1-293 C O1 | 80/20 | 9.29 MW | 9.29 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 946301 | AF1-294 C | 80/20 | 5.75 MW | 5.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 946591 | AF1-323 C | 80/20 | 2.45 MW | 2.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 958211 | AF2-115 C | 80/20 | 3.51 MW | 3.51 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 933501 | AC2-165 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 961061 | AF2-397 C | 80/20 | 6.96 MW | 6.96 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315191 | 1BEARGRDN G1 | 80/20 | 2.89 MW | 2.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315192 | 1BEARGRDN G2 | 80/20 | 2.89 MW | 2.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315193 | 1BEARGRDN S1 | 80/20 | 5.95 MW | 5.95 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924021 | AB2-043 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924161 | AB2-060 C OP | 80/20 | 2.12 MW | 2.12 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925781 | AC1-054 C O1 | 80/20 | 5.01 MW | 5.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925991 | AC1-075 C | 80/20 | 11.97 MW | 11.97 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 926021 | AC1-080 C | 80/20 | 4.0 MW | 4.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 926271 | AC1-105 C O1 | 80/20 | 14.51 MW | 14.51 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 926641 | AC1-145 C | 80/20 | 1.91 MW | 1.91 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934611 | AD1-087 C O1 | 80/20 | 22.64 MW | 22.64 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 936261 | AD2-033 C | 80/20 | 17.83 MW | 17.83 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 938821 | AE1-108 C | 80/20 | 7.17 MW | 7.17 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 939181 | AE1-148 C O1 | 80/20 | 8.51 MW | 8.51 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 940241 | AE2-006 | 80/20 | 0.67 MW | 0.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942751 | AE2-291 C O1 | 80/20 | 15.7 MW | 15.7 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925611 | AC1-036 C | 80/20 | 1.31 MW | 1.31 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925831 | AC1-062 | 80/20 | 0.08 MW | 0.08 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934621 | AD1-088 C | 80/20 | 23.99 MW | 23.99 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 920291 | AA2-127 | 80/20 | 0.6 MW | 0.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.1 MW | 0.1 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.5 MW | 0.5 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.32 MW | 1.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.76 MW | 0.76 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.47 MW | 4.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | LTF | 5.14 MW | 5.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.3 MW | 0.3 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.47 MW | 1.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.48 MW | 0.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.83 MW | 0.83 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.43 MW | 1.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.31 MW | 2.31 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.73 MW | 0.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| Details for AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313853 | 3PONTONDP | 80/20 | 0.13 MW | 0.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 39.63 MW | 39.63 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 39.24 MW | 39.24 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 1.14 MW | 1.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.37 MW | 0.37 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 11.71 MW | 11.71 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 10.13 MW | 10.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 7.03 MW | 7.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 29.37 MW | 29.37 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 9.63 MW | 9.63 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 26.75 MW | 26.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 14.38 MW | 14.38 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 3.98 MW | 3.98 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 19.55 MW | 19.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 5.75 MW | 5.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 21.73 MW | 21.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 21.04 MW | 21.04 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 23.0 MW | 23.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 22.98 MW | 22.98 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.89 MW | 0.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 3.36 MW | 3.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 26.96 MW | 26.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 9.13 MW | 9.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.21 MW | 6.21 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 3.9 MW | 3.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 3.62 MW | 3.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 3.62 MW | 3.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.29 MW | 9.29 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 5.75 MW | 5.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.45 MW | 2.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 155.18 MW | 155.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 3.51 MW | 3.51 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 6.96 MW | 6.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 2.89 MW | 2.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 2.89 MW | 2.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 5.95 MW | 5.95 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924021 | AB2-043 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924161 | AB2-060 C OP | 80/20 | 2.12 MW | 2.12 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925781 | AC1-054 C O1 | 80/20 | 5.01 MW | 5.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925991 | AC1-075 C | 80/20 | 11.97 MW | 11.97 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926021 | AC1-080 C | 80/20 | 4.0 MW | 4.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926271 | AC1-105 C O1 | 80/20 | 14.51 MW | 14.51 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926641 | AC1-145 C | 80/20 | 1.91 MW | 1.91 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934611 | AD1-087 C O1 | 80/20 | 22.64 MW | 22.64 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936261 | AD2-033 C | 80/20 | 17.83 MW | 17.83 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C | 80/20 | 7.17 MW | 7.17 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C O1 | 80/20 | 8.51 MW | 8.51 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940241 | AE2-006 | 80/20 | 0.67 MW | 0.67 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C O1 | 80/20 | 15.7 MW | 15.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 1.31 MW | 1.31 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925831 | AC1-062 | 80/20 | 0.08 MW | 0.08 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934621 | AD1-088 C | 80/20 | 23.99 MW | 23.99 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 920291 | AA2-127 | 80/20 | 0.6 MW | 0.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.1 MW | 0.1 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.5 MW | 0.5 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.32 MW | 1.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.76 MW | 0.76 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.47 MW | 4.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | LTF | 5.14 MW | 5.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.3 MW | 0.3 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.47 MW | 1.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.48 MW | 0.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.83 MW | 0.83 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.43 MW | 1.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.31 MW | 2.31 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.73 MW | 0.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| Details for AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 313853 | 3PONTONDP | 80/20 | 0.13 MW | 0.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315153 | 1CLOVER1 | 80/20 | 39.63 MW | 39.63 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315154 | 1CLOVER2 | 80/20 | 39.24 MW | 39.24 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315156 | 1HALLBR1 | 80/20 | 1.14 MW | 1.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315158 | 1KERR 1 | 80/20 | 0.37 MW | 0.37 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315159 | 1KERR 2 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315160 | 1KERR 3 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315161 | 1KERR 4 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315162 | 1KERR 5 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 927251 | AC1-221 C | 80/20 | 11.71 MW | 11.71 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 927261 | AC1-222 C | 80/20 | 10.13 MW | 10.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934311 | AD1-055 C | 80/20 | 7.03 MW | 7.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934341 | AD1-058 C | 80/20 | 29.37 MW | 29.37 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934991 | AD1-131 C | 80/20 | 9.63 MW | 9.63 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 935171 | AD1-152 C O1 | 80/20 | 26.75 MW | 26.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 937481 | AD2-202 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942461 | AE2-259 C O1 | 80/20 | 14.38 MW | 14.38 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942671 | AE2-283 C | 80/20 | 3.98 MW | 3.98 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942761 | AE2-292 C O1 | 80/20 | 19.55 MW | 19.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 943901 | AF1-058 C | 80/20 | 5.75 MW | 5.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 958801 | AF2-171 C | 80/20 | 21.04 MW | 21.04 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 959311 | AF2-222 C | 80/20 | 23.0 MW | 23.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 960061 | AF2-297 C | 80/20 | 22.98 MW | 22.98 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 960111 | AF2-302 C | 80/20 | 0.89 MW | 0.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315163 | 1KERR 6 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315164 | 1KERR 7 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315266 | 1PLYWOOD A | 80/20 | 3.36 MW | 3.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924301 | AB2-077 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924311 | AB2-078 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924321 | AB2-079 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925661 | AC1-042 C | 80/20 | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 932761 | AC2-100 C | 80/20 | 26.96 MW | 26.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 938371 | AE1-056 C | 80/20 | 9.13 MW | 9.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 940661 | AE2-053 O1 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 941011 | AE2-092 C | 80/20 | 6.21 MW | 6.21 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 941791 | AE2-182 C | 80/20 | 3.9 MW | 3.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 941801 | AE2-185 C | 80/20 | 3.62 MW | 3.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 941821 | AE2-187 C | 80/20 | 3.62 MW | 3.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 946291 | AF1-293 C O1 | 80/20 | 9.29 MW | 9.29 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 946301 | AF1-294 C | 80/20 | 5.75 MW | 5.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 946591 | AF1-323 C | 80/20 | 2.45 MW | 2.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 958211 | AF2-115 C | 80/20 | 3.51 MW | 3.51 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 933501 | AC2-165 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 961061 | AF2-397 C | 80/20 | 6.96 MW | 6.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315191 | 1BEARGRDN G1 | 80/20 | 2.89 MW | 2.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315192 | 1BEARGRDN G2 | 80/20 | 2.89 MW | 2.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 315193 | 1BEARGRDN S1 | 80/20 | 5.95 MW | 5.95 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924021 | AB2-043 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 924161 | AB2-060 C OP | 80/20 | 2.12 MW | 2.12 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925781 | AC1-054 C O1 | 80/20 | 5.01 MW | 5.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925991 | AC1-075 C | 80/20 | 11.97 MW | 11.97 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 926021 | AC1-080 C | 80/20 | 4.0 MW | 4.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 926271 | AC1-105 C O1 | 80/20 | 14.51 MW | 14.51 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 926641 | AC1-145 C | 80/20 | 1.91 MW | 1.91 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934611 | AD1-087 C O1 | 80/20 | 22.64 MW | 22.64 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 936261 | AD2-033 C | 80/20 | 17.83 MW | 17.83 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 938821 | AE1-108 C | 80/20 | 7.17 MW | 7.17 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 939181 | AE1-148 C O1 | 80/20 | 8.51 MW | 8.51 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 940241 | AE2-006 | 80/20 | 0.67 MW | 0.67 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 942751 | AE2-291 C O1 | 80/20 | 15.7 MW | 15.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925611 | AC1-036 C | 80/20 | 1.31 MW | 1.31 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 925831 | AC1-062 | 80/20 | 0.08 MW | 0.08 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 934621 | AD1-088 C | 80/20 | 23.99 MW | 23.99 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | 920291 | AA2-127 | 80/20 | 0.6 MW | 0.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.1 MW | 0.1 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.5 MW | 0.5 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.32 MW | 1.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.76 MW | 0.76 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.47 MW | 4.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | LTF | 5.14 MW | 5.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.3 MW | 0.3 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.47 MW | 1.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.48 MW | 0.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.83 MW | 0.83 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.43 MW | 1.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.31 MW | 2.31 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.73 MW | 0.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1-A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| Details for AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 313853 | 3PONTONDP | 80/20 | 0.13 MW | 0.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315153 | 1CLOVER1 | 80/20 | 39.63 MW | 39.63 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315154 | 1CLOVER2 | 80/20 | 39.24 MW | 39.24 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315156 | 1HALLBR1 | 80/20 | 1.14 MW | 1.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315158 | 1KERR 1 | 80/20 | 0.37 MW | 0.37 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315159 | 1KERR 2 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315160 | 1KERR 3 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315161 | 1KERR 4 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315162 | 1KERR 5 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 927251 | AC1-221 C | 80/20 | 11.71 MW | 11.71 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 927261 | AC1-222 C | 80/20 | 10.13 MW | 10.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934311 | AD1-055 C | 80/20 | 7.03 MW | 7.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934341 | AD1-058 C | 80/20 | 29.37 MW | 29.37 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934991 | AD1-131 C | 80/20 | 9.63 MW | 9.63 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 935171 | AD1-152 C O1 | 80/20 | 26.75 MW | 26.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 937481 | AD2-202 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 942461 | AE2-259 C O1 | 80/20 | 14.38 MW | 14.38 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 942671 | AE2-283 C | 80/20 | 3.98 MW | 3.98 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 942761 | AE2-292 C O1 | 80/20 | 19.55 MW | 19.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 943901 | AF1-058 C | 80/20 | 5.75 MW | 5.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 958801 | AF2-171 C | 80/20 | 21.04 MW | 21.04 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 959311 | AF2-222 C | 80/20 | 23.0 MW | 23.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 960061 | AF2-297 C | 80/20 | 22.98 MW | 22.98 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 960111 | AF2-302 C | 80/20 | 0.89 MW | 0.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315163 | 1KERR 6 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315164 | 1KERR 7 | 80/20 | 1.03 MW | 1.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315266 | 1PLYWOOD A | 80/20 | 3.36 MW | 3.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 924301 | AB2-077 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 924311 | AB2-078 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 924321 | AB2-079 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 925661 | AC1-042 C | 80/20 | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 932761 | AC2-100 C | 80/20 | 26.96 MW | 26.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 938371 | AE1-056 C | 80/20 | 9.13 MW | 9.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 940661 | AE2-053 O1 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 941011 | AE2-092 C | 80/20 | 6.21 MW | 6.21 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 941791 | AE2-182 C | 80/20 | 3.9 MW | 3.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 941801 | AE2-185 C | 80/20 | 3.62 MW | 3.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 941821 | AE2-187 C | 80/20 | 3.62 MW | 3.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 946291 | AF1-293 C O1 | 80/20 | 9.29 MW | 9.29 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 946301 | AF1-294 C | 80/20 | 5.75 MW | 5.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 946591 | AF1-323 C | 80/20 | 2.45 MW | 2.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 958211 | AF2-115 C | 80/20 | 3.51 MW | 3.51 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 933501 | AC2-165 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 961061 | AF2-397 C | 80/20 | 6.96 MW | 6.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315191 | 1BEARGRDN G1 | 80/20 | 2.89 MW | 2.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315192 | 1BEARGRDN G2 | 80/20 | 2.89 MW | 2.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315193 | 1BEARGRDN S1 | 80/20 | 5.95 MW | 5.95 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 924021 | AB2-043 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 924161 | AB2-060 C OP | 80/20 | 2.12 MW | 2.12 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 925781 | AC1-054 C O1 | 80/20 | 5.01 MW | 5.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 925991 | AC1-075 C | 80/20 | 11.97 MW | 11.97 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 926021 | AC1-080 C | 80/20 | 4.0 MW | 4.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 926271 | AC1-105 C O1 | 80/20 | 14.51 MW | 14.51 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 926641 | AC1-145 C | 80/20 | 1.91 MW | 1.91 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934611 | AD1-087 C O1 | 80/20 | 22.64 MW | 22.64 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 936261 | AD2-033 C | 80/20 | 17.83 MW | 17.83 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 938821 | AE1-108 C | 80/20 | 7.17 MW | 7.17 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 939181 | AE1-148 C O1 | 80/20 | 8.51 MW | 8.51 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 940241 | AE2-006 | 80/20 | 0.67 MW | 0.67 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 942751 | AE2-291 C O1 | 80/20 | 15.7 MW | 15.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 925611 | AC1-036 C | 80/20 | 1.31 MW | 1.31 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 925831 | AC1-062 | 80/20 | 0.08 MW | 0.08 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934621 | AD1-088 C | 80/20 | 23.99 MW | 23.99 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 920291 | AA2-127 | 80/20 | 0.6 MW | 0.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.1 MW | 0.1 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.5 MW | 0.5 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.32 MW | 1.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.76 MW | 0.76 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.47 MW | 4.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | LTF | 5.14 MW | 5.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.3 MW | 0.3 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.47 MW | 1.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.48 MW | 0.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.83 MW | 0.83 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.43 MW | 1.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.31 MW | 2.31 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.73 MW | 0.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 314572 | 3EMPORIA | 80/20 | 0.21 MW | 0.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 314704 | 3LAWRENC | 80/20 | 0.8 MW | 0.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315126 | 1ROARAP2 | 80/20 | 1.32 MW | 1.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315128 | 1ROARAP4 | 80/20 | 1.26 MW | 1.26 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315136 | 1ROSEMG1 | 80/20 | 1.03 MW | 1.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315137 | 1ROSEMS1 | 80/20 | 0.64 MW | 0.64 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315138 | 1ROSEMG2 | 80/20 | 0.48 MW | 0.48 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315139 | 1GASTONA | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315158 | 1KERR 1 | 80/20 | 0.29 MW | 0.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315159 | 1KERR 2 | 80/20 | 0.81 MW | 0.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315160 | 1KERR 3 | 80/20 | 0.81 MW | 0.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315161 | 1KERR 4 | 80/20 | 0.81 MW | 0.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315162 | 1KERR 5 | 80/20 | 0.81 MW | 0.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 926201 | AC1-098 C | 80/20 | 3.14 MW | 3.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 926211 | AC1-099 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 943171 | AE2-346 C | Adder | 0.55 MW | 0.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 958801 | AF2-171 C | 80/20 | 7.04 MW | 7.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 959311 | AF2-222 C | 80/20 | 9.82 MW | 9.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 960081 | AF2-299 C | 80/20 | 8.12 MW | 8.12 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315163 | 1KERR 6 | 80/20 | 0.81 MW | 0.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315164 | 1KERR 7 | 80/20 | 0.81 MW | 0.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315606 | 3AA2-053SOLA | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 923262 | AB1-132 C OP | 80/20 | 6.85 MW | 6.85 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 923991 | AB2-040 C O1 | 80/20 | 16.27 MW | 16.27 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 924301 | AB2-077 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 924311 | AB2-078 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 924321 | AB2-079 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 932631 | AC2-084 C | 80/20 | 4.47 MW | 4.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 938371 | AE1-056 C | Adder | 2.69 MW | 2.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 940661 | AE2-053 O1 | 80/20 | 2.3 MW | 2.3 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 946281 | AF1-292 C | 80/20 | 4.84 MW | 4.84 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 946301 | AF1-294 C | Adder | 1.9 MW | 1.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 957521 | AF2-046 C | Adder | 7.49 MW | 6.37 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 958211 | AF2-115 C | Adder | 1.16 MW | 0.99 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315141 | 1GASTONB | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315607 | 3AA1-063SOLA | 80/20 | 1.1 MW | 1.1 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 315608 | 3AA2-088SOLA | 80/20 | 0.53 MW | 0.53 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 920671 | AA2-174 C OP | 80/20 | 0.06 MW | 0.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 923911 | AB2-031 C O1 | 80/20 | 4.95 MW | 4.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 924021 | AB2-043 C O1 | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 924161 | AB2-060 C OP | 80/20 | 1.21 MW | 1.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 924501 | AB2-099 C | Adder | 0.23 MW | 0.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 925781 | AC1-054 C O1 | 80/20 | 5.41 MW | 5.41 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 926071 | AC1-086 C | 80/20 | 10.08 MW | 10.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 927141 | AC1-208 C | 80/20 | 5.3 MW | 5.3 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 936261 | AD2-033 C | 80/20 | 8.31 MW | 8.31 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 939181 | AE1-148 C O1 | 80/20 | 6.22 MW | 6.22 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 940241 | AE2-006 | 80/20 | 0.29 MW | 0.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 923572 | AB1-173 C OP | 80/20 | 4.99 MW | 4.99 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 923582 | AB1-173AC OP | 80/20 | 4.99 MW | 4.99 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 925611 | AC1-036 C | 80/20 | 0.58 MW | 0.58 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 924511 | AB2-100 C | 80/20 | 0.95 MW | 0.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 925171 | AB2-174 C O1 | 80/20 | 3.04 MW | 3.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | 918561 | AA1-072 C | Adder | 0.15 MW | 0.12 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.22 MW | 0.22 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.22 MW | 1.22 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 4.53 MW | 4.53 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 7.83 MW | 7.83 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 5254 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.44 MW | 4.44 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313853 | 3PONTONDP | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.55 MW | 0.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.02 MW | 0.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.4 MW | 7.4 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.33 MW | 7.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.24 MW | 0.24 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.62 MW | 0.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.23 MW | 1.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.96 MW | 18.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.71 MW | 4.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 22.09 MW | 22.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 20.14 MW | 20.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.0 MW | 4.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.77 MW | 0.77 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.17 MW | 4.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.7 MW | 0.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.29 MW | 10.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.03 MW | 2.03 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 29.19 MW | 29.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 3.25 MW | 3.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.46 MW | 0.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 47.05 MW | 47.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.08 MW | 6.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.47 MW | 11.47 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.34 MW | 23.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 6.06 MW | 6.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 32.16 MW | 32.16 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.82 MW | 49.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.08 MW | 1.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.18 MW | 15.18 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.18 MW | 15.18 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 31.24 MW | 31.24 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924021 | AB2-043 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924161 | AB2-060 C OP | 80/20 | 1.28 MW | 1.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925781 | AC1-054 C O1 | 80/20 | 3.66 MW | 3.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925991 | AC1-075 C | 80/20 | 2.57 MW | 2.57 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926021 | AC1-080 C | 80/20 | 0.86 MW | 0.86 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926271 | AC1-105 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934611 | AD1-087 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936261 | AD2-033 C | 80/20 | 14.26 MW | 14.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C | 80/20 | 34.98 MW | 34.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C O1 | 80/20 | 5.48 MW | 5.48 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940241 | AE2-006 | 80/20 | 0.56 MW | 0.56 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C O1 | 80/20 | 3.78 MW | 3.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 1.1 MW | 1.1 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925171 | AB2-174 C O1 | 80/20 | 0.36 MW | 0.36 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925831 | AC1-062 | 80/20 | 0.08 MW | 0.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934621 | AD1-088 C | 80/20 | 20.0 MW | 20.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 920291 | AA2-127 | 80/20 | 3.15 MW | 3.15 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.25 MW | 0.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.18 MW | 2.18 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.55 MW | 6.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.5 MW | 1.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 14.52 MW | 14.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 8.1 MW | 8.1 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.55 MW | 0.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.87 MW | 0.87 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.49 MW | 1.49 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.43 MW | 4.43 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 313853 | 3PONTONDP | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314429 | 3JTRSVLE | 80/20 | 0.55 MW | 0.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314572 | 3EMPORIA | 80/20 | 0.02 MW | 0.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315153 | 1CLOVER1 | 80/20 | 7.4 MW | 7.4 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315154 | 1CLOVER2 | 80/20 | 7.33 MW | 7.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315158 | 1KERR 1 | 80/20 | 0.24 MW | 0.24 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315159 | 1KERR 2 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315160 | 1KERR 3 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315161 | 1KERR 4 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315162 | 1KERR 5 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934991 | AD1-131 C | 80/20 | 0.62 MW | 0.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 935171 | AD1-152 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 937481 | AD2-202 C O1 | 80/20 | 1.23 MW | 1.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942461 | AE2-259 C O1 | 80/20 | 18.96 MW | 18.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942761 | AE2-292 C O1 | 80/20 | 4.71 MW | 4.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 945811 | AF1-246 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958801 | AF2-171 C | 80/20 | 22.09 MW | 22.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 959311 | AF2-222 C | 80/20 | 20.14 MW | 20.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960061 | AF2-297 C | 80/20 | 4.0 MW | 4.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960081 | AF2-299 C | 80/20 | 0.77 MW | 0.77 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960111 | AF2-302 C | 80/20 | 4.17 MW | 4.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315163 | 1KERR 6 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315164 | 1KERR 7 | 80/20 | 0.68 MW | 0.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315266 | 1PLYWOOD A | 80/20 | 0.7 MW | 0.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924301 | AB2-077 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924311 | AB2-078 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924321 | AB2-079 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 938371 | AE1-056 C | 80/20 | 10.29 MW | 10.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 940661 | AE2-053 O1 | 80/20 | 2.03 MW | 2.03 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 941011 | AE2-092 C | 80/20 | 29.19 MW | 29.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 941791 | AE2-182 C | 80/20 | 3.25 MW | 3.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946281 | AF1-292 C | 80/20 | 0.46 MW | 0.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946291 | AF1-293 C O1 | 80/20 | 47.05 MW | 47.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946301 | AF1-294 C | 80/20 | 6.08 MW | 6.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946591 | AF1-323 C | 80/20 | 11.47 MW | 11.47 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 957481 | AF2-042 C | 80/20 | 23.34 MW | 23.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958131 | AF2-107 C | 80/20 | 6.06 MW | 6.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958211 | AF2-115 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 933501 | AC2-165 C | 80/20 | 32.16 MW | 32.16 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 961061 | AF2-397 C | 80/20 | 49.82 MW | 49.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314677 | 6BUCKING | 80/20 | 1.08 MW | 1.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315191 | 1BEARGRDN G1 | 80/20 | 15.18 MW | 15.18 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315192 | 1BEARGRDN G2 | 80/20 | 15.18 MW | 15.18 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315193 | 1BEARGRDN S1 | 80/20 | 31.24 MW | 31.24 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924021 | AB2-043 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924161 | AB2-060 C OP | 80/20 | 1.28 MW | 1.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925781 | AC1-054 C O1 | 80/20 | 3.66 MW | 3.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925991 | AC1-075 C | 80/20 | 2.57 MW | 2.57 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 926021 | AC1-080 C | 80/20 | 0.86 MW | 0.86 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 926271 | AC1-105 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934611 | AD1-087 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 936261 | AD2-033 C | 80/20 | 14.26 MW | 14.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 938821 | AE1-108 C | 80/20 | 34.98 MW | 34.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 939181 | AE1-148 C O1 | 80/20 | 5.48 MW | 5.48 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 940241 | AE2-006 | 80/20 | 0.56 MW | 0.56 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942751 | AE2-291 C O1 | 80/20 | 3.78 MW | 3.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925611 | AC1-036 C | 80/20 | 1.1 MW | 1.1 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925171 | AB2-174 C O1 | 80/20 | 0.36 MW | 0.36 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925831 | AC1-062 | 80/20 | 0.08 MW | 0.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934621 | AD1-088 C | 80/20 | 20.0 MW | 20.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 920291 | AA2-127 | 80/20 | 3.15 MW | 3.15 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.25 MW | 0.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.18 MW | 2.18 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.55 MW | 6.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.5 MW | 1.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 14.52 MW | 14.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 8.1 MW | 8.1 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.55 MW | 0.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.87 MW | 0.87 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.49 MW | 1.49 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.43 MW | 4.43 MW |
| Details for AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 0.18 MW | 0.18 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.59 MW | 0.59 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.28 MW | 0.28 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.66 MW | 0.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 2.42 MW | 2.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 2.31 MW | 2.31 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 9.05 MW | 9.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 9.05 MW | 9.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.38 MW | 4.38 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.72 MW | 2.72 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.05 MW | 2.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.68 MW | 6.68 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.18 MW | 0.18 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 8.14 MW | 8.14 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.73 MW | 2.73 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.47 MW | 15.47 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | Adder | 42.84 MW | 36.41 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.72 MW | 1.72 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 959311 | AF2-222 C | Adder | 10.56 MW | 8.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 6.51 MW | 6.51 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | Adder | 9.11 MW | 7.74 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 2.42 MW | 2.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 10.0 MW | 10.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 29.41 MW | 29.41 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 16.07 MW | 16.07 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924301 | AB2-077 C O1 | Adder | 1.67 MW | 1.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924311 | AB2-078 C O1 | Adder | 1.67 MW | 1.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924321 | AB2-079 C O1 | Adder | 1.67 MW | 1.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.63 MW | 7.63 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 11.61 MW | 11.61 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | Adder | 4.36 MW | 3.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 5.0 MW | 5.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 3.04 MW | 3.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 3.88 MW | 3.88 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 18.88 MW | 18.88 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | Adder | 10.36 MW | 8.8 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 8.25 MW | 8.25 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940481 | AE2-033 C | 80/20 | 63.97 MW | 63.97 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946011 | AF1-266 | 80/20 | 53.55 MW | 53.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.68 MW | 6.68 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 2.09 MW | 2.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 1.09 MW | 1.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 2.76 MW | 2.76 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314574 | 6EVERETS | 80/20 | 0.3 MW | 0.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315612 | 3AA2-057SOLA | 80/20 | 1.56 MW | 1.56 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920671 | AA2-174 C OP | 80/20 | 0.11 MW | 0.11 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923911 | AB2-031 C O1 | 80/20 | 4.89 MW | 4.89 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924021 | AB2-043 C O1 | 80/20 | 0.46 MW | 0.46 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924151 | AB2-059 C OP | 80/20 | 2.05 MW | 2.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924501 | AB2-099 C | 80/20 | 0.72 MW | 0.72 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925781 | AC1-054 C O1 | 80/20 | 8.26 MW | 8.26 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926071 | AC1-086 C | 80/20 | 43.3 MW | 43.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927021 | AC1-189 C | 80/20 | 9.09 MW | 9.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927141 | AC1-208 C | 80/20 | 12.44 MW | 12.44 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 936261 | AD2-033 C | Adder | 8.98 MW | 7.63 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C O1 | 80/20 | 8.21 MW | 8.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940241 | AE2-006 | Adder | 0.32 MW | 0.27 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923572 | AB1-173 C OP | 80/20 | 4.93 MW | 4.93 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923582 | AB1-173AC OP | 80/20 | 4.93 MW | 4.93 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925611 | AC1-036 C | Adder | 0.62 MW | 0.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C O1 | 80/20 | 8.83 MW | 8.83 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924511 | AB2-100 C | 80/20 | 6.22 MW | 6.22 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925171 | AB2-174 C O1 | 80/20 | 2.8 MW | 2.8 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 918561 | AA1-072 C | 80/20 | 0.45 MW | 0.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.9 MW | 7.9 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.92 MW | 1.92 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.54 MW | 12.54 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.38 MW | 0.38 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.62 MW | 2.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 22.71 MW | 22.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.64 MW | 14.64 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.71 MW | 0.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.91 MW | 1.91 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.49 MW | 2.49 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.04 MW | 12.04 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313853 | 3PONTONDP | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.55 MW | 0.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.02 MW | 0.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.4 MW | 7.4 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.33 MW | 7.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.24 MW | 0.24 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.62 MW | 0.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.23 MW | 1.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.96 MW | 18.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.71 MW | 4.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 22.09 MW | 22.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 20.14 MW | 20.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.0 MW | 4.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.77 MW | 0.77 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.17 MW | 4.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.7 MW | 0.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.29 MW | 10.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.03 MW | 2.03 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 29.19 MW | 29.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 3.25 MW | 3.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.46 MW | 0.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 47.05 MW | 47.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.08 MW | 6.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.47 MW | 11.47 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.34 MW | 23.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 6.06 MW | 6.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 32.16 MW | 32.16 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.82 MW | 49.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.08 MW | 1.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.18 MW | 15.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.18 MW | 15.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 31.24 MW | 31.24 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924021 | AB2-043 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924161 | AB2-060 C OP | 80/20 | 1.28 MW | 1.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925781 | AC1-054 C O1 | 80/20 | 3.66 MW | 3.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925991 | AC1-075 C | 80/20 | 2.57 MW | 2.57 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926021 | AC1-080 C | 80/20 | 0.86 MW | 0.86 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926271 | AC1-105 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934611 | AD1-087 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936261 | AD2-033 C | 80/20 | 14.26 MW | 14.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C | 80/20 | 34.98 MW | 34.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C O1 | 80/20 | 5.48 MW | 5.48 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940241 | AE2-006 | 80/20 | 0.56 MW | 0.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C O1 | 80/20 | 3.78 MW | 3.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 1.1 MW | 1.1 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925171 | AB2-174 C O1 | 80/20 | 0.36 MW | 0.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925831 | AC1-062 | 80/20 | 0.08 MW | 0.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934621 | AD1-088 C | 80/20 | 20.0 MW | 20.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 920291 | AA2-127 | 80/20 | 3.15 MW | 3.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.25 MW | 0.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.18 MW | 2.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.55 MW | 6.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.5 MW | 1.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 14.52 MW | 14.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 8.1 MW | 8.1 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.55 MW | 0.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.87 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.49 MW | 1.49 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.43 MW | 4.43 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 313853 | 3PONTONDP | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314429 | 3JTRSVLE | 80/20 | 0.55 MW | 0.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314572 | 3EMPORIA | 80/20 | 0.02 MW | 0.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315153 | 1CLOVER1 | 80/20 | 7.4 MW | 7.4 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315154 | 1CLOVER2 | 80/20 | 7.33 MW | 7.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315158 | 1KERR 1 | 80/20 | 0.24 MW | 0.24 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315159 | 1KERR 2 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315160 | 1KERR 3 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315161 | 1KERR 4 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315162 | 1KERR 5 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934991 | AD1-131 C | 80/20 | 0.62 MW | 0.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 935171 | AD1-152 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 937481 | AD2-202 C O1 | 80/20 | 1.23 MW | 1.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942461 | AE2-259 C O1 | 80/20 | 18.96 MW | 18.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942761 | AE2-292 C O1 | 80/20 | 4.71 MW | 4.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 945811 | AF1-246 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958801 | AF2-171 C | 80/20 | 22.09 MW | 22.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 959311 | AF2-222 C | 80/20 | 20.14 MW | 20.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960061 | AF2-297 C | 80/20 | 4.0 MW | 4.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960081 | AF2-299 C | 80/20 | 0.77 MW | 0.77 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960111 | AF2-302 C | 80/20 | 4.17 MW | 4.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315163 | 1KERR 6 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315164 | 1KERR 7 | 80/20 | 0.68 MW | 0.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315266 | 1PLYWOOD A | 80/20 | 0.7 MW | 0.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924301 | AB2-077 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924311 | AB2-078 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924321 | AB2-079 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 938371 | AE1-056 C | 80/20 | 10.29 MW | 10.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 940661 | AE2-053 O1 | 80/20 | 2.03 MW | 2.03 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 941011 | AE2-092 C | 80/20 | 29.19 MW | 29.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 941791 | AE2-182 C | 80/20 | 3.25 MW | 3.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946281 | AF1-292 C | 80/20 | 0.46 MW | 0.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946291 | AF1-293 C O1 | 80/20 | 47.05 MW | 47.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946301 | AF1-294 C | 80/20 | 6.08 MW | 6.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946591 | AF1-323 C | 80/20 | 11.47 MW | 11.47 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 957481 | AF2-042 C | 80/20 | 23.34 MW | 23.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958131 | AF2-107 C | 80/20 | 6.06 MW | 6.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958211 | AF2-115 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 933501 | AC2-165 C | 80/20 | 32.16 MW | 32.16 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 961061 | AF2-397 C | 80/20 | 49.82 MW | 49.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314677 | 6BUCKING | 80/20 | 1.08 MW | 1.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315191 | 1BEARGRDN G1 | 80/20 | 15.18 MW | 15.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315192 | 1BEARGRDN G2 | 80/20 | 15.18 MW | 15.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315193 | 1BEARGRDN S1 | 80/20 | 31.24 MW | 31.24 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924021 | AB2-043 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924161 | AB2-060 C OP | 80/20 | 1.28 MW | 1.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925781 | AC1-054 C O1 | 80/20 | 3.66 MW | 3.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925991 | AC1-075 C | 80/20 | 2.57 MW | 2.57 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 926021 | AC1-080 C | 80/20 | 0.86 MW | 0.86 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 926271 | AC1-105 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934611 | AD1-087 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 936261 | AD2-033 C | 80/20 | 14.26 MW | 14.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 938821 | AE1-108 C | 80/20 | 34.98 MW | 34.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 939181 | AE1-148 C O1 | 80/20 | 5.48 MW | 5.48 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 940241 | AE2-006 | 80/20 | 0.56 MW | 0.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942751 | AE2-291 C O1 | 80/20 | 3.78 MW | 3.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925611 | AC1-036 C | 80/20 | 1.1 MW | 1.1 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925171 | AB2-174 C O1 | 80/20 | 0.36 MW | 0.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925831 | AC1-062 | 80/20 | 0.08 MW | 0.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934621 | AD1-088 C | 80/20 | 20.0 MW | 20.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 920291 | AA2-127 | 80/20 | 3.15 MW | 3.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.25 MW | 0.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.18 MW | 2.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.55 MW | 6.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.5 MW | 1.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 14.52 MW | 14.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 8.1 MW | 8.1 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.55 MW | 0.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.87 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.49 MW | 1.49 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.43 MW | 4.43 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 313853 | 3PONTONDP | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314429 | 3JTRSVLE | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314572 | 3EMPORIA | 80/20 | 0.02 MW | 0.02 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315126 | 1ROARAP2 | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315153 | 1CLOVER1 | 80/20 | 8.08 MW | 8.08 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315154 | 1CLOVER2 | 80/20 | 8.0 MW | 8.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315159 | 1KERR 2 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315160 | 1KERR 3 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315161 | 1KERR 4 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315162 | 1KERR 5 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 927261 | AC1-222 C | 80/20 | 1.88 MW | 1.88 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934311 | AD1-055 C | 80/20 | 1.3 MW | 1.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934341 | AD1-058 C | 80/20 | 2.0 MW | 2.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934991 | AD1-131 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 935171 | AD1-152 C O1 | 80/20 | 4.54 MW | 4.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 937481 | AD2-202 C O1 | 80/20 | 1.35 MW | 1.35 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942461 | AE2-259 C O1 | 80/20 | 20.78 MW | 20.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942761 | AE2-292 C O1 | 80/20 | 4.12 MW | 4.12 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 943901 | AF1-058 C | 80/20 | 1.05 MW | 1.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 945811 | AF1-246 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958801 | AF2-171 C | 80/20 | 24.15 MW | 24.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 959311 | AF2-222 C | 80/20 | 21.98 MW | 21.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960061 | AF2-297 C | 80/20 | 4.2 MW | 4.2 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960111 | AF2-302 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315163 | 1KERR 6 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315164 | 1KERR 7 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315266 | 1PLYWOOD A | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 923991 | AB2-040 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924301 | AB2-077 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924311 | AB2-078 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924321 | AB2-079 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 932761 | AC2-100 C | 80/20 | 1.83 MW | 1.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 938371 | AE1-056 C | 80/20 | 11.26 MW | 11.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 940661 | AE2-053 O1 | 80/20 | 2.2 MW | 2.2 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 941791 | AE2-182 C | 80/20 | 3.56 MW | 3.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946291 | AF1-293 C O1 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946301 | AF1-294 C | 80/20 | 6.65 MW | 6.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946591 | AF1-323 C | 80/20 | 3.73 MW | 3.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 957481 | AF2-042 C | 80/20 | 25.57 MW | 25.57 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958131 | AF2-107 C | 80/20 | 2.03 MW | 2.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958211 | AF2-115 C | 80/20 | 4.05 MW | 4.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 933501 | AC2-165 C | 80/20 | 35.32 MW | 35.32 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314677 | 6BUCKING | 80/20 | 1.18 MW | 1.18 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315191 | 1BEARGRDN G1 | 80/20 | 16.67 MW | 16.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315192 | 1BEARGRDN G2 | 80/20 | 16.67 MW | 16.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315193 | 1BEARGRDN S1 | 80/20 | 34.31 MW | 34.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 923911 | AB2-031 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924021 | AB2-043 C O1 | 80/20 | 0.47 MW | 0.47 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924161 | AB2-060 C OP | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925781 | AC1-054 C O1 | 80/20 | 3.96 MW | 3.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925991 | AC1-075 C | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 926021 | AC1-080 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 926271 | AC1-105 C O1 | 80/20 | 3.38 MW | 3.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934611 | AD1-087 C O1 | 80/20 | 4.6 MW | 4.6 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 936261 | AD2-033 C | 80/20 | 15.54 MW | 15.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 938821 | AE1-108 C | 80/20 | 11.34 MW | 11.34 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 939181 | AE1-148 C O1 | 80/20 | 5.93 MW | 5.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 940241 | AE2-006 | 80/20 | 0.61 MW | 0.61 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942751 | AE2-291 C O1 | 80/20 | 3.31 MW | 3.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 923572 | AB1-173 C OP | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 923582 | AB1-173AC OP | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925611 | AC1-036 C | 80/20 | 1.21 MW | 1.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925171 | AB2-174 C O1 | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925831 | AC1-062 | 80/20 | 0.09 MW | 0.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934621 | AD1-088 C | 80/20 | 21.93 MW | 21.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 920291 | AA2-127 | 80/20 | 3.46 MW | 3.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.13 MW | 0.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.25 MW | 2.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 5.05 MW | 5.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.24 MW | 1.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 14.37 MW | 14.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 6.52 MW | 6.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.58 MW | 0.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.53 MW | 1.53 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 2.09 MW | 2.09 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313853 | 3PONTONDP | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.02 MW | 0.02 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 8.08 MW | 8.08 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 8.0 MW | 8.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.88 MW | 1.88 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.3 MW | 1.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 2.0 MW | 2.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.54 MW | 4.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.35 MW | 1.35 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 20.78 MW | 20.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.12 MW | 4.12 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.05 MW | 1.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 24.15 MW | 24.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 21.98 MW | 21.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.2 MW | 4.2 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.83 MW | 1.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 11.26 MW | 11.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.2 MW | 2.2 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 3.56 MW | 3.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.65 MW | 6.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.73 MW | 3.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 25.57 MW | 25.57 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 2.03 MW | 2.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 4.05 MW | 4.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 35.32 MW | 35.32 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.18 MW | 1.18 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 16.67 MW | 16.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 16.67 MW | 16.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 34.31 MW | 34.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923911 | AB2-031 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924021 | AB2-043 C O1 | 80/20 | 0.47 MW | 0.47 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924161 | AB2-060 C OP | 80/20 | 1.39 MW | 1.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925781 | AC1-054 C O1 | 80/20 | 3.96 MW | 3.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925991 | AC1-075 C | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926021 | AC1-080 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926271 | AC1-105 C O1 | 80/20 | 3.38 MW | 3.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934611 | AD1-087 C O1 | 80/20 | 4.6 MW | 4.6 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936261 | AD2-033 C | 80/20 | 15.54 MW | 15.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C | 80/20 | 11.34 MW | 11.34 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C O1 | 80/20 | 5.93 MW | 5.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940241 | AE2-006 | 80/20 | 0.61 MW | 0.61 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C O1 | 80/20 | 3.31 MW | 3.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923572 | AB1-173 C OP | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923582 | AB1-173AC OP | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 1.21 MW | 1.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925171 | AB2-174 C O1 | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925831 | AC1-062 | 80/20 | 0.09 MW | 0.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934621 | AD1-088 C | 80/20 | 21.93 MW | 21.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 920291 | AA2-127 | 80/20 | 3.46 MW | 3.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.13 MW | 0.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.25 MW | 2.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 5.04 MW | 5.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.24 MW | 1.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 14.36 MW | 14.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.58 MW | 0.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.53 MW | 1.53 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 2.08 MW | 2.08 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313853 | 3PONTONDP | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.55 MW | 0.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.02 MW | 0.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.4 MW | 7.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.33 MW | 7.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.24 MW | 0.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.62 MW | 0.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.96 MW | 18.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.71 MW | 4.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 22.09 MW | 22.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 20.14 MW | 20.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.0 MW | 4.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.77 MW | 0.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.17 MW | 4.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.7 MW | 0.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.29 MW | 10.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.03 MW | 2.03 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 29.19 MW | 29.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 3.25 MW | 3.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.46 MW | 0.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 47.05 MW | 47.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.08 MW | 6.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.47 MW | 11.47 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.34 MW | 23.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 6.06 MW | 6.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 32.16 MW | 32.16 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.08 MW | 1.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.18 MW | 15.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.18 MW | 15.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 31.24 MW | 31.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924021 | AB2-043 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924161 | AB2-060 C OP | 80/20 | 1.28 MW | 1.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925781 | AC1-054 C O1 | 80/20 | 3.66 MW | 3.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925991 | AC1-075 C | 80/20 | 2.57 MW | 2.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926021 | AC1-080 C | 80/20 | 0.86 MW | 0.86 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926271 | AC1-105 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934611 | AD1-087 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936261 | AD2-033 C | 80/20 | 14.26 MW | 14.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C | 80/20 | 34.98 MW | 34.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C O1 | 80/20 | 5.48 MW | 5.48 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940241 | AE2-006 | 80/20 | 0.56 MW | 0.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C O1 | 80/20 | 3.78 MW | 3.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 1.1 MW | 1.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925171 | AB2-174 C O1 | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925831 | AC1-062 | 80/20 | 0.08 MW | 0.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934621 | AD1-088 C | 80/20 | 20.0 MW | 20.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 920291 | AA2-127 | 80/20 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.55 MW | 6.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.5 MW | 1.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 14.52 MW | 14.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 8.1 MW | 8.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.55 MW | 0.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.87 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.43 MW | 4.43 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 313853 | 3PONTONDP | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314429 | 3JTRSVLE | 80/20 | 0.55 MW | 0.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314572 | 3EMPORIA | 80/20 | 0.02 MW | 0.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315153 | 1CLOVER1 | 80/20 | 7.4 MW | 7.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315154 | 1CLOVER2 | 80/20 | 7.33 MW | 7.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315158 | 1KERR 1 | 80/20 | 0.24 MW | 0.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315159 | 1KERR 2 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315160 | 1KERR 3 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315161 | 1KERR 4 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315162 | 1KERR 5 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934991 | AD1-131 C | 80/20 | 0.62 MW | 0.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 935171 | AD1-152 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 937481 | AD2-202 C O1 | 80/20 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942461 | AE2-259 C O1 | 80/20 | 18.96 MW | 18.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942761 | AE2-292 C O1 | 80/20 | 4.71 MW | 4.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 945811 | AF1-246 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958801 | AF2-171 C | 80/20 | 22.09 MW | 22.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 959311 | AF2-222 C | 80/20 | 20.14 MW | 20.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960061 | AF2-297 C | 80/20 | 4.0 MW | 4.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960081 | AF2-299 C | 80/20 | 0.77 MW | 0.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960111 | AF2-302 C | 80/20 | 4.17 MW | 4.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315163 | 1KERR 6 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315164 | 1KERR 7 | 80/20 | 0.68 MW | 0.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315266 | 1PLYWOOD A | 80/20 | 0.7 MW | 0.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924301 | AB2-077 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924311 | AB2-078 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924321 | AB2-079 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 938371 | AE1-056 C | 80/20 | 10.29 MW | 10.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 940661 | AE2-053 O1 | 80/20 | 2.03 MW | 2.03 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 941011 | AE2-092 C | 80/20 | 29.19 MW | 29.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 941791 | AE2-182 C | 80/20 | 3.25 MW | 3.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946281 | AF1-292 C | 80/20 | 0.46 MW | 0.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946291 | AF1-293 C O1 | 80/20 | 47.05 MW | 47.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946301 | AF1-294 C | 80/20 | 6.08 MW | 6.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946591 | AF1-323 C | 80/20 | 11.47 MW | 11.47 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 957481 | AF2-042 C | 80/20 | 23.34 MW | 23.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958131 | AF2-107 C | 80/20 | 6.06 MW | 6.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958211 | AF2-115 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 933501 | AC2-165 C | 80/20 | 32.16 MW | 32.16 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314677 | 6BUCKING | 80/20 | 1.08 MW | 1.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315191 | 1BEARGRDN G1 | 80/20 | 15.18 MW | 15.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315192 | 1BEARGRDN G2 | 80/20 | 15.18 MW | 15.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315193 | 1BEARGRDN S1 | 80/20 | 31.24 MW | 31.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924021 | AB2-043 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924161 | AB2-060 C OP | 80/20 | 1.28 MW | 1.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925781 | AC1-054 C O1 | 80/20 | 3.66 MW | 3.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925991 | AC1-075 C | 80/20 | 2.57 MW | 2.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 926021 | AC1-080 C | 80/20 | 0.86 MW | 0.86 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 926271 | AC1-105 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934611 | AD1-087 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 936261 | AD2-033 C | 80/20 | 14.26 MW | 14.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 938821 | AE1-108 C | 80/20 | 34.98 MW | 34.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 939181 | AE1-148 C O1 | 80/20 | 5.48 MW | 5.48 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 940241 | AE2-006 | 80/20 | 0.56 MW | 0.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942751 | AE2-291 C O1 | 80/20 | 3.78 MW | 3.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925611 | AC1-036 C | 80/20 | 1.1 MW | 1.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925171 | AB2-174 C O1 | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925831 | AC1-062 | 80/20 | 0.08 MW | 0.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934621 | AD1-088 C | 80/20 | 20.0 MW | 20.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 920291 | AA2-127 | 80/20 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.55 MW | 6.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.5 MW | 1.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 14.52 MW | 14.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 8.1 MW | 8.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.55 MW | 0.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.87 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.43 MW | 4.43 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 313853 | 3PONTONDP | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314429 | 3JTRSVLE | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314572 | 3EMPORIA | 80/20 | 0.02 MW | 0.02 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315126 | 1ROARAP2 | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315153 | 1CLOVER1 | 80/20 | 8.08 MW | 8.08 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315154 | 1CLOVER2 | 80/20 | 8.0 MW | 8.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315159 | 1KERR 2 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315160 | 1KERR 3 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315161 | 1KERR 4 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315162 | 1KERR 5 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 927261 | AC1-222 C | 80/20 | 1.88 MW | 1.88 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934311 | AD1-055 C | 80/20 | 1.3 MW | 1.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934341 | AD1-058 C | 80/20 | 2.0 MW | 2.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934991 | AD1-131 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 935171 | AD1-152 C O1 | 80/20 | 4.54 MW | 4.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 937481 | AD2-202 C O1 | 80/20 | 1.35 MW | 1.35 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942461 | AE2-259 C O1 | 80/20 | 20.78 MW | 20.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942761 | AE2-292 C O1 | 80/20 | 4.12 MW | 4.12 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 943901 | AF1-058 C | 80/20 | 1.05 MW | 1.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 945811 | AF1-246 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958801 | AF2-171 C | 80/20 | 24.15 MW | 24.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 959311 | AF2-222 C | 80/20 | 21.98 MW | 21.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960061 | AF2-297 C | 80/20 | 4.2 MW | 4.2 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 960111 | AF2-302 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315163 | 1KERR 6 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315164 | 1KERR 7 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315266 | 1PLYWOOD A | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 923991 | AB2-040 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924301 | AB2-077 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924311 | AB2-078 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924321 | AB2-079 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 932761 | AC2-100 C | 80/20 | 1.83 MW | 1.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 938371 | AE1-056 C | 80/20 | 11.26 MW | 11.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 940661 | AE2-053 O1 | 80/20 | 2.2 MW | 2.2 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 941791 | AE2-182 C | 80/20 | 3.56 MW | 3.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946291 | AF1-293 C O1 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946301 | AF1-294 C | 80/20 | 6.65 MW | 6.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 946591 | AF1-323 C | 80/20 | 3.73 MW | 3.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 957481 | AF2-042 C | 80/20 | 25.57 MW | 25.57 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958131 | AF2-107 C | 80/20 | 2.03 MW | 2.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 958211 | AF2-115 C | 80/20 | 4.05 MW | 4.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 933501 | AC2-165 C | 80/20 | 35.32 MW | 35.32 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 314677 | 6BUCKING | 80/20 | 1.18 MW | 1.18 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315191 | 1BEARGRDN G1 | 80/20 | 16.67 MW | 16.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315192 | 1BEARGRDN G2 | 80/20 | 16.67 MW | 16.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 315193 | 1BEARGRDN S1 | 80/20 | 34.31 MW | 34.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 923911 | AB2-031 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924021 | AB2-043 C O1 | 80/20 | 0.47 MW | 0.47 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 924161 | AB2-060 C OP | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925781 | AC1-054 C O1 | 80/20 | 3.96 MW | 3.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925991 | AC1-075 C | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 926021 | AC1-080 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 926271 | AC1-105 C O1 | 80/20 | 3.38 MW | 3.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934611 | AD1-087 C O1 | 80/20 | 4.6 MW | 4.6 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 936261 | AD2-033 C | 80/20 | 15.54 MW | 15.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 938821 | AE1-108 C | 80/20 | 11.34 MW | 11.34 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 939181 | AE1-148 C O1 | 80/20 | 5.93 MW | 5.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 940241 | AE2-006 | 80/20 | 0.61 MW | 0.61 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 942751 | AE2-291 C O1 | 80/20 | 3.31 MW | 3.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 923572 | AB1-173 C OP | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 923582 | AB1-173AC OP | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925611 | AC1-036 C | 80/20 | 1.21 MW | 1.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925171 | AB2-174 C O1 | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 925831 | AC1-062 | 80/20 | 0.09 MW | 0.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 934621 | AD1-088 C | 80/20 | 21.93 MW | 21.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | 920291 | AA2-127 | 80/20 | 3.46 MW | 3.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.13 MW | 0.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.25 MW | 2.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 5.05 MW | 5.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.24 MW | 1.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 14.37 MW | 14.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 6.52 MW | 6.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.58 MW | 0.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.53 MW | 1.53 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027-B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 2.09 MW | 2.09 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313853 | 3PONTONDP | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.02 MW | 0.02 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 8.08 MW | 8.08 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 8.0 MW | 8.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.88 MW | 1.88 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.3 MW | 1.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 2.0 MW | 2.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.54 MW | 4.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.35 MW | 1.35 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 20.78 MW | 20.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.12 MW | 4.12 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.05 MW | 1.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 24.15 MW | 24.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 21.98 MW | 21.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.2 MW | 4.2 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.83 MW | 1.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 11.26 MW | 11.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.2 MW | 2.2 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 3.56 MW | 3.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.65 MW | 6.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.73 MW | 3.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 25.57 MW | 25.57 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 2.03 MW | 2.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 4.05 MW | 4.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 35.32 MW | 35.32 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.18 MW | 1.18 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 16.67 MW | 16.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 16.67 MW | 16.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 34.31 MW | 34.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923911 | AB2-031 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924021 | AB2-043 C O1 | 80/20 | 0.47 MW | 0.47 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924161 | AB2-060 C OP | 80/20 | 1.39 MW | 1.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925781 | AC1-054 C O1 | 80/20 | 3.96 MW | 3.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925991 | AC1-075 C | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926021 | AC1-080 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926271 | AC1-105 C O1 | 80/20 | 3.38 MW | 3.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934611 | AD1-087 C O1 | 80/20 | 4.6 MW | 4.6 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936261 | AD2-033 C | 80/20 | 15.54 MW | 15.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C | 80/20 | 11.34 MW | 11.34 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C O1 | 80/20 | 5.93 MW | 5.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940241 | AE2-006 | 80/20 | 0.61 MW | 0.61 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C O1 | 80/20 | 3.31 MW | 3.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923572 | AB1-173 C OP | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923582 | AB1-173AC OP | 80/20 | 0.74 MW | 0.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 1.21 MW | 1.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925171 | AB2-174 C O1 | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925831 | AC1-062 | 80/20 | 0.09 MW | 0.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934621 | AD1-088 C | 80/20 | 21.93 MW | 21.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 920291 | AA2-127 | 80/20 | 3.46 MW | 3.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.13 MW | 0.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.25 MW | 2.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 5.04 MW | 5.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.24 MW | 1.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 14.36 MW | 14.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.58 MW | 0.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.53 MW | 1.53 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 2.08 MW | 2.08 MW |
| Details for 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 313853 | 3PONTONDP | 80/20 | 0.07 MW | 0.07 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314429 | 3JTRSVLE | 80/20 | 0.26 MW | 0.26 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315153 | 1CLOVER1 | 80/20 | 4.12 MW | 4.12 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315154 | 1CLOVER2 | 80/20 | 4.08 MW | 4.08 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 937481 | AD2-202 C O1 | 80/20 | 0.69 MW | 0.69 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 942461 | AE2-259 C O1 | 80/20 | 8.99 MW | 8.99 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958801 | AF2-171 C | 80/20 | 10.59 MW | 10.59 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 959311 | AF2-222 C | 80/20 | 9.76 MW | 9.76 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924301 | AB2-077 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924311 | AB2-078 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924321 | AB2-079 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 938371 | AE1-056 C | 80/20 | 4.91 MW | 4.91 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 940661 | AE2-053 O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941791 | AE2-182 C | 80/20 | 1.56 MW | 1.56 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 946301 | AF1-294 C | 80/20 | 2.91 MW | 2.91 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958211 | AF2-115 C | 80/20 | 1.78 MW | 1.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 933501 | AC2-165 C | 80/20 | 9.04 MW | 9.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314333 | 6POWHATN | 80/20 | 0.33 MW | 0.33 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314677 | 6BUCKING | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958501 | AF2-144 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315191 | 1BEARGRDN G1 | 80/20 | 7.02 MW | 7.02 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315192 | 1BEARGRDN G2 | 80/20 | 7.02 MW | 7.02 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315193 | 1BEARGRDN S1 | 80/20 | 14.44 MW | 14.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 938561 | AE1-075 C | 80/20 | 1.64 MW | 1.64 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 957911 | AF2-085 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924021 | AB2-043 C O1 | 80/20 | 0.22 MW | 0.22 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924161 | AB2-060 C OP | 80/20 | 0.64 MW | 0.64 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 934611 | AD1-087 C O1 | 80/20 | 2.35 MW | 2.35 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 936261 | AD2-033 C | 80/20 | 6.95 MW | 6.95 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 939181 | AE1-148 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 940241 | AE2-006 | 80/20 | 0.27 MW | 0.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 925611 | AC1-036 C | 80/20 | 0.54 MW | 0.54 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 925831 | AC1-062 | 80/20 | 0.04 MW | 0.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 934621 | AD1-088 C | 80/20 | 9.62 MW | 9.62 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 920291 | AA2-127 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.15 MW | 1.15 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.01 MW | 0.01 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.18 MW | 0.18 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.09 MW | 0.09 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.57 MW | 0.57 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.06 MW | 0.06 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.12 MW | 0.12 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 6.17 MW | 6.17 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.22 MW | 0.22 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.34 MW | 0.34 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.64 MW | 0.64 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
Light Load Analysis
The Queue Project was evaluated as a 167.0 MW (Capacity 100.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n6852 | Add an additional 2 miles single circuit 230 kV line from Fork Union to Bremo parallel to existing line. Add a breaker at Fork Union 230 kV and Bremo 230 kV | $3,500,000 | |
| n6113 | Add additional 230/115 kV transformer at Carolina substation. | $6,000,000 | |
| (TBD) | Rebuild 8.5 miles of 115 kV Line 1012 from Chase City to Central to a single circuit 230 kV line with 2-636 ACSR. Will need a CPCN for this project. | $12,750,000 | |
| n7766 | Rebuild 115 kV Line #1012 From AD2-063 Tap-AG1-181 Tap-Central-Twitty's Creek-AF2-222 Tap-Madsonav | $24,835,000 | |
| n6114 | Add additional 230/115 kV transformer at Clubhouse substation. Cost changed during facility study phase. | $13,653,448 | |
| n7185 | Reconductor 115 kV line #84 from Willis Mountain to Farmville. | $2,876,000 | |
| n6246 | Add additional 230/115 kV transformer (#3) for Circuit 1 at Farmville substation | $6,000,000 | |
| n7550 | Add additional 230/115 kV transformer (#4) for Circuit 2 at Farmville substation. | $6,000,000 | |
| (TBD) | Reconductor 20 miles with single 795 ACSS-TW per phase, replace breaker, disconnect switches, wave trap, line switch | $60,000,000 | |
| s2614 | For DEV portion, rebuild 4.7 miles of 115 kV Line 45 from Kerr Dam to GW King Tap with 768 ACSS. | $6,123,000 | |
| n5873 | Rebuild 0.16 miles of Line 2028 from Bremo to Bremo Dist with 2-636 ACSR. | $500,000 | |
| n6219 | Rebuild 15.51 miles of 230 kV Line 298 from Buckingham to Bremo with 2-636 ACSR. | $23,265,000 | |
| n6245 | Rebuild 12.76 miles of 230 kV Line 298 from Buckingham to Farmville with 2-768.2 ACSS 250 C. Replace Line Lead, Line Switch, Relay (CT), Wave trap at Farmville terminal | $19,710,000 | |
| b3694.8 | Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. | $15,365,000 | |
| n6379 | Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-636 ACSR. | $16,175,000 | |
| n6872 | Rebuild 14.28 miles of 230 kV Line 238 from Clubhouse to AE2-033 Tap with 2-795 150C ACSR. | $21,420,000 | |
| n7567 | Rebuild 1.63 miles of 230 kV Line 2028 from Fork Union to Bremo Dist with 2-795 ACSR (26/7) 150 C | $2,445,000 | |
| n6185.2 | Rebuild 17.42 miles of 230 kV Line 2028 from Fork Union to Mount Eagle with 2-636 ACSR. | $26,130,000 | |
| (TBD) | Dominion Rating Update | $0 | |
| (TBD) | Reconductor 5 miles with double 795 ACSS-TW per phase, replace disconnect switches | $22,500,000 | |
| n6452 | Rebuild 2.47 miles of 230 kV Line 238 from AE2-033 TAP to Sapony with 2-795 150C ACSR. | $3,705,000 | |
| (TBD) | Upgrade is not needed in Dominion End. Need to coordinate with Duke. | $0 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF2-222 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.