AF1-256 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:13
Flemingsburg-Spurlock 138 kV
48.0 MW Capacity / 80.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF1-256 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the EKPC zone — Fleming County, Kentucky. The installed facilities will have a total capability of 80.0 MW with 48.0 MW of this output being recognized by PJM as Capacity.
Project Information | |
---|---|
Queue Number | AF1-256 |
Project Name | Flemingsburg-Spurlock 138 kV |
Developer Name | Fleming Solar, LLC |
State | Kentucky |
County | Fleming |
Transmission Owner | EKPC |
MFO | 80.0 MW |
MWE | 80.0 MW |
MWC | 48.0 MW |
Fuel Type | Solar |
Basecase Study Year | 2023 |
Point of Interconnection
AF1-256 will interconnect on the EKPC transmission system tapping the Flemingsburg – Spurlock 138 kV line.
Summer Peak Analysis
The Queue Project was evaluated as a 80.0 MW (Capacity 48.0 MW) injection in the EKPC area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Summer Peak Analysis | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
DAY/EKPC |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
342838 to 253077 ckt 1 |
DEOK_P2-2_C1 SILVER GROVE 345 BUS
CONTINGENCY 'DEOK_P2-2_C1 SILVER GROVE 345 BUS' OPEN BRANCH FROM BUS 249571 TO BUS 249573 CKT 1 /*08REDBK1 345.0 - 08SGROVE 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 249577 CKT 1 /*08SGROVE 345.0 - 08ZIMER 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 250097 CKT 1 /*08SGROVE 345.0 - 08SGROVE 138.0 END |
Bus | AC | 119.12 % | 121.37 % | 1532.0 | B | 1859.39 | 33.72 | |
EKPC |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line
342091 to 341923 ckt 1 |
EKPC_P4-6_SPUR N39-92T
CONTINGENCY 'EKPC_P4-6_SPUR N39-92T' OPEN BRANCH FROM BUS 342622 TO BUS 342625 CKT 1 /*4MAYSVIL I T 138.0 - 4MAYSVIL IND 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342634 CKT 1 /*4MAYSVIL I T 138.0 - 4PLUMVILLE 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342664 CKT 1 /*4MAYSVIL I T 138.0 - 4SPURLOCK 138.0 OPEN BRANCH FROM BUS 945910 TO BUS 342664 CKT 1 /*AF1-256 TAP 138.0 - 4SPURLOCK 138.0 END |
Breaker | AC | 123.37 % | 152.0 % | 63.0 | B | 95.76 | 18.69 | |
AEP |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line
246946 to 243019 ckt 1 |
DAY_P4_L34553-1
CONTINGENCY 'DAY_P4_L34553-1' OPEN LINE FROM BUS 253077 TO BUS 253076 CKT 1 /*09STUART 345.0 - 09STUART 138.0 OPEN LINE FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Breaker | AC | 121.05 % | 123.21 % | 185.0 | B | 227.94 | 4.71 | |
DAY/EKPC |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
342838 to 253077 ckt 1 |
DEOK_P2-3_C2 816_SILVERGROVE
CONTINGENCY 'DEOK_P2-3_C2 816_SILVERGROVE' OPEN BRANCH FROM BUS 249571 TO BUS 249573 CKT 1 /*08REDBK1 345.0 - 08SGROVE 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 249577 CKT 1 /*08SGROVE 345.0 - 08ZIMER 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 250097 CKT 1 /*08SGROVE 345.0 - 08SGROVE 138.0 OPEN BRANCH FROM BUS 249988 TO BUS 250097 CKT 1 /*08BKJ135 138.0 - 08SGROVE 138.0 OPEN BRANCH FROM BUS 250042 TO BUS 250097 CKT 1 /*08HANDS1 138.0 - 08SGROVE 138.0 OPEN BRANCH FROM BUS 250052 TO BUS 250097 CKT 1 /*08KYUNIV 138.0 - 08SGROVE 138.0 OPEN BRANCH FROM BUS 250053 TO BUS 250097 CKT 1 /*08LAFARG 138.0 - 08SGROVE 138.0 END |
Breaker | AC | 119.29 % | 121.54 % | 1532.0 | B | 1861.99 | 33.75 | |
DAY/EKPC |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
342838 to 253077 ckt 1 |
DEOK_P2-3_C2 1493_RED BANK
CONTINGENCY 'DEOK_P2-3_C2 1493_RED BANK' OPEN BRANCH FROM BUS 249571 TO BUS 249573 CKT 1 /*08REDBK1 345.0 - 08SGROVE 345.0 OPEN BRANCH FROM BUS 249571 TO BUS 250092 CKT 1 /*08REDBK1 345.0 - 08REDBK1 138.0 OPEN BRANCH FROM BUS 249573 TO BUS 249577 CKT 1 /*08SGROVE 345.0 - 08ZIMER 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 250097 CKT 1 /*08SGROVE 345.0 - 08SGROVE 138.0 END |
Breaker | AC | 119.24 % | 121.49 % | 1532.0 | B | 1861.23 | 33.72 | |
DAY/EKPC |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
342838 to 253077 ckt 1 |
DEOK_P2-3_C2 1487_RED BANK
CONTINGENCY 'DEOK_P2-3_C2 1487_RED BANK' OPEN BRANCH FROM BUS 249571 TO BUS 249573 CKT 1 /*08REDBK1 345.0 - 08SGROVE 345.0 OPEN BRANCH FROM BUS 249571 TO BUS 250093 CKT 1 /*08REDBK1 345.0 - 08REDBK2 138.0 OPEN BRANCH FROM BUS 249573 TO BUS 249577 CKT 1 /*08SGROVE 345.0 - 08ZIMER 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 250097 CKT 1 /*08SGROVE 345.0 - 08SGROVE 138.0 END |
Breaker | AC | 119.19 % | 121.44 % | 1532.0 | B | 1860.46 | 33.72 | |
DAY/EKPC |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
342838 to 253077 ckt 1 |
DEOK_P2-3_C2 1441_ZIMMER
CONTINGENCY 'DEOK_P2-3_C2 1441_ZIMMER' OPEN BRANCH FROM BUS 249571 TO BUS 249573 CKT 1 /*08REDBK1 345.0 - 08SGROVE 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 249577 CKT 1 /*08SGROVE 345.0 - 08ZIMER 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 250097 CKT 1 /*08SGROVE 345.0 - 08SGROVE 138.0 END |
Breaker | AC | 119.12 % | 121.37 % | 1532.0 | B | 1859.39 | 33.72 | |
EKPC/LGEE |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line
342649 to 324302 ckt 1 |
EKPC_P4-6_SPUR N39-92T
CONTINGENCY 'EKPC_P4-6_SPUR N39-92T' OPEN BRANCH FROM BUS 342622 TO BUS 342625 CKT 1 /*4MAYSVIL I T 138.0 - 4MAYSVIL IND 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342634 CKT 1 /*4MAYSVIL I T 138.0 - 4PLUMVILLE 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342664 CKT 1 /*4MAYSVIL I T 138.0 - 4SPURLOCK 138.0 OPEN BRANCH FROM BUS 945910 TO BUS 342664 CKT 1 /*AF1-256 TAP 138.0 - 4SPURLOCK 138.0 END |
Breaker | AC | 85.39 % | 107.38 % | 191.0 | B | 205.1 | 42.33 | |
EKPC |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line
342589 to 342571 ckt 1 |
EKPC_P4-6_SPUR N39-92T
CONTINGENCY 'EKPC_P4-6_SPUR N39-92T' OPEN BRANCH FROM BUS 342622 TO BUS 342625 CKT 1 /*4MAYSVIL I T 138.0 - 4MAYSVIL IND 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342634 CKT 1 /*4MAYSVIL I T 138.0 - 4PLUMVILLE 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342664 CKT 1 /*4MAYSVIL I T 138.0 - 4SPURLOCK 138.0 OPEN BRANCH FROM BUS 945910 TO BUS 342664 CKT 1 /*AF1-256 TAP 138.0 - 4SPURLOCK 138.0 END |
Breaker | AC | 83.34 % | 101.69 % | 255.0 | B | 259.31 | 47.24 | |
EKPC |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line
342571 to 342649 ckt 1 |
EKPC_P4-6_SPUR N39-92T
CONTINGENCY 'EKPC_P4-6_SPUR N39-92T' OPEN BRANCH FROM BUS 342622 TO BUS 342625 CKT 1 /*4MAYSVIL I T 138.0 - 4MAYSVIL IND 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342634 CKT 1 /*4MAYSVIL I T 138.0 - 4PLUMVILLE 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342664 CKT 1 /*4MAYSVIL I T 138.0 - 4SPURLOCK 138.0 OPEN BRANCH FROM BUS 945910 TO BUS 342664 CKT 1 /*AF1-256 TAP 138.0 - 4SPURLOCK 138.0 END |
Breaker | AC | 83.33 % | 101.67 % | 255.0 | B | 259.26 | 47.24 | |
DAY/EKPC |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
342838 to 253077 ckt 1 |
Base Case | Single | AC | 118.09 % | 119.64 % | 1240.0 | A | 1483.54 | 18.74 | |
DAY/EKPC |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
342838 to 253077 ckt 1 |
DEOK_P1-3_B3 SILVER GROVE 345/138 TB23*
CONTINGENCY 'DEOK_P1-3_B3 SILVER GROVE 345 OPEN BRANCH FROM BUS 249571 TO BUS 249573 CKT 1 /*08REDBK1 345.0 - 08SGROVE 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 249577 CKT 1 /*08SGROVE 345.0 - 08ZIMER 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 250097 CKT 1 /*08SGROVE 345.0 - 08SGROVE 138.0 END |
Single | AC | 113.09 % | 114.45 % | 1532.0 | B | 1753.37 | 20.23 | |
DAY/EKPC |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
342838 to 253077 ckt 1 |
PORT UNION-ZIMMER 4544
CONTINGENCY 'PORT UNION-ZIMMER 4544' OPEN BRANCH FROM BUS 249570 TO BUS 249577 CKT 1 /*08P.UNON 345.0 - 08ZIMER 345.0 END |
Single | AC | 106.35 % | 107.68 % | 1532.0 | B | 1649.66 | 19.67 | |
AEP |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line
246946 to 243019 ckt 1 |
DAY_P734541 34553
CONTINGENCY 'DAY_P734541 34553' OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1 /*08MELDAL 345.0 - 7SPURLOCK 345.0 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Tower | AC | 160.16 % | 163.52 % | 185.0 | B | 302.51 | 7.32 | |
DAY/EKPC |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line
342838 to 253077 ckt 1 |
DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER
CONTINGENCY 'DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER' OPEN BRANCH FROM BUS 249571 TO BUS 249573 CKT 1 /*08REDBK1 345.0 - 08SGROVE 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 249577 CKT 1 /*08SGROVE 345.0 - 08ZIMER 345.0 OPEN BRANCH FROM BUS 249573 TO BUS 250097 CKT 1 /*08SGROVE 345.0 - 08SGROVE 138.0 OPEN BRANCH FROM BUS 249989 TO BUS 250080 CKT 1 /*08BKJ246 138.0 - 08NWTWN2 138.0 OPEN BRANCH FROM BUS 250079 TO BUS 250080 CKT Z1 /*08NWTWN1 138.0 - 08NWTWN2 138.0 OPEN BRANCH FROM BUS 250079 TO BUS 250092 CKT 1 /*08NWTWN1 138.0 - 08REDBK1 138.0 END |
Tower | AC | 119.06 % | 121.3 % | 1532.0 | B | 1858.32 | 33.73 | |
DEO&K/EKPC |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line
342559 to 250054 ckt 1 |
DAY_P734541 34553
CONTINGENCY 'DAY_P734541 34553' OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1 /*08MELDAL 345.0 - 7SPURLOCK 345.0 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Tower | AC | 117.6 % | 120.58 % | 284.0 | B | 342.45 | 8.87 | |
AEP/LGEE |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line
324267 to 246800 ckt 1 |
DAY_P734541 34553
CONTINGENCY 'DAY_P734541 34553' OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1 /*08MELDAL 345.0 - 7SPURLOCK 345.0 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Tower | AC | 111.02 % | 114.38 % | 185.0 | B | 211.6 | 7.32 | |
DEO&K |
08LONGBR-08MTZION 138.0 kV Ckt 1 line
250054 to 250077 ckt 1 |
DAY_P734541 34553
CONTINGENCY 'DAY_P734541 34553' OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1 /*08MELDAL 345.0 - 7SPURLOCK 345.0 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Tower | AC | 110.56 % | 113.55 % | 284.0 | B | 322.48 | 8.87 | |
AEP |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line
246800 to 247034 ckt 1 |
DAY_P734541 34553
CONTINGENCY 'DAY_P734541 34553' OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1 /*08MELDAL 345.0 - 7SPURLOCK 345.0 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Tower | AC | 108.29 % | 111.65 % | 185.0 | B | 206.55 | 7.32 | |
AEP |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line
247034 to 246946 ckt 1 |
DAY_P734541 34553
CONTINGENCY 'DAY_P734541 34553' OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1 /*08MELDAL 345.0 - 7SPURLOCK 345.0 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Tower | AC | 107.14 % | 110.5 % | 185.0 | B | 204.42 | 7.32 | |
EKPC/LGEE |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line
342661 to 324267 ckt 1 |
DAY_P734541 34553
CONTINGENCY 'DAY_P734541 34553' OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1 /*08MELDAL 345.0 - 7SPURLOCK 345.0 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Tower | AC | 106.58 % | 109.1 % | 281.0 | B | 306.57 | 7.48 | |
EKPC |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line
342091 to 341923 ckt 1 |
DAY_P734541 34553
CONTINGENCY 'DAY_P734541 34553' OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1 /*08MELDAL 345.0 - 7SPURLOCK 345.0 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Tower | AC | 101.94 % | 108.03 % | 63.0 | B | 68.06 | 4.52 | |
EKPC |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line
342664 to 342661 ckt 1 |
DAY_P734541 34553
CONTINGENCY 'DAY_P734541 34553' OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1 /*08MELDAL 345.0 - 7SPURLOCK 345.0 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Tower | AC | 102.91 % | 105.35 % | 291.0 | B | 306.57 | 7.48 | |
EKPC/LGEE |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line
342544 to 324275 ckt 1 |
DAY_P734541 34553
CONTINGENCY 'DAY_P734541 34553' OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1 /*08MELDAL 345.0 - 7SPURLOCK 345.0 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Tower | AC | 103.44 % | 105.24 % | 203.0 | B | 213.64 | 4.29 | |
DEO&K |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line
250077 to 249991 ckt 1 |
DAY_P734541 34553
CONTINGENCY 'DAY_P734541 34553' OPEN BRANCH FROM BUS 249581 TO BUS 342838 CKT 1 /*08MELDAL 345.0 - 7SPURLOCK 345.0 OPEN BRANCH FROM BUS 253077 TO BUS 342838 CKT 1 /*09STUART 345.0 - 7SPURLOCK 345.0 END |
Tower | AC | 101.21 % | 104.06 % | 298.0 | B | 310.1 | 8.87 |
Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 936381 | AD2-048 C | Adder | 12.72 MW | 10.81 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 936382 | AD2-048 E | Adder | 6.34 MW | 5.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 942411 | AE2-254 C O1 | Adder | 5.05 MW | 4.29 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 942412 | AE2-254 E O1 | Adder | 3.37 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 942591 | AE2-275 C O1 | Adder | 15.89 MW | 13.51 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 942592 | AE2-275 E O1 | Adder | 5.98 MW | 5.08 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 942891 | AE2-308 C O1 | Adder | 26.63 MW | 22.63 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 942892 | AE2-308 E O1 | Adder | 9.68 MW | 8.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 943111 | AE2-339 C | 50/50 | 7.45 MW | 7.45 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 943112 | AE2-339 E | 50/50 | 3.67 MW | 3.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 943701 | AF1-038 C | Adder | 3.78 MW | 3.21 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 943702 | AF1-038 E | Adder | 2.52 MW | 2.14 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 943821 | AF1-050 C | Adder | 3.36 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 943822 | AF1-050 E | Adder | 2.24 MW | 1.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 944151 | AF1-083 C O1 | Adder | 3.53 MW | 3.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 944152 | AF1-083 E O1 | Adder | 2.35 MW | 2.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 944511 | AF1-116 C | Adder | 8.44 MW | 7.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 944512 | AF1-116 E | Adder | 5.63 MW | 4.79 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 945681 | AF1-233 C | 50/50 | 63.06 MW | 63.06 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 945682 | AF1-233 E | 50/50 | 31.15 MW | 31.15 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 945911 | AF1-256 C | 50/50 | 20.23 MW | 20.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 945912 | AF1-256 E | 50/50 | 13.49 MW | 13.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 251968 | 08ZIMRHP | 50/50 | 51.25 MW | 51.25 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 251969 | 08ZIMRLP | 50/50 | 28.06 MW | 28.06 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 251970 | 08MELDL1 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 251971 | 08MELDL2 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 251972 | 08MELDL3 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 342942 | 1JKCT 10G | 50/50 | 3.82 MW | 3.82 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 342957 | 1SPURLK1G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 342960 | 1SPURLK2G | 50/50 | 50.12 MW | 50.12 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 342963 | 1SPURLK3G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 342966 | 1SPURLK4G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 939131 | AE1-143 C | Adder | 7.53 MW | 6.4 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 939132 | AE1-143 E | Adder | 3.73 MW | 3.17 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 940531 | AE2-038 C O1 | 50/50 | 21.94 MW | 21.94 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 940532 | AE2-038 E O1 | 50/50 | 10.87 MW | 10.87 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 941411 | AE2-138 C | 50/50 | 63.18 MW | 63.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 941412 | AE2-138 E | 50/50 | 23.37 MW | 23.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 941981 | AE2-210 C O1 | 50/50 | 21.77 MW | 21.77 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 941982 | AE2-210 E O1 | 50/50 | 8.19 MW | 8.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 938921 | AE1-120 | Adder | -5.77 MW | -4.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 925981 | AC1-074 C O1 | 50/50 | 15.73 MW | 15.73 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 925982 | AC1-074 E O1 | 50/50 | 6.74 MW | 6.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 926061 | AC1-085 C | Adder | -29.85 MW | -25.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 932551 | AC2-075 C | 50/50 | 3.74 MW | 3.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 932552 | AC2-075 E | 50/50 | 1.88 MW | 1.88 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 926951 | AC1-182 | 50/50 | 1.22 MW | 1.22 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 936571 | AD2-072 C O1 | Adder | 10.05 MW | 8.54 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 936572 | AD2-072 E O1 | Adder | 4.93 MW | 4.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 939141 | AE2-000C C | 50/50 | 27.39 MW | 27.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 939142 | AE2-000C E | 50/50 | 13.61 MW | 13.61 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | 943772 | AF1-045 BAT | Adder | 5.5 MW | 4.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.67 MW | 4.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 24.76 MW | 24.76 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.74 MW | 0.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.26 MW | 5.26 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 8.64 MW | 8.64 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 7.65 MW | 7.65 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 38.99 MW | 38.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.33 MW | 1.33 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.27 MW | 3.27 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.99 MW | 2.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-2_C1 SILVER GROVE 345 BUS | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.16 MW | 10.16 MW |
Details for 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945681 | AF1-233 C | 50/50 | 35.18 MW | 35.18 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945682 | AF1-233 E | 50/50 | 17.38 MW | 17.38 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945911 | AF1-256 C | 50/50 | 11.21 MW | 11.21 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945912 | AF1-256 E | 50/50 | 7.47 MW | 7.47 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940531 | AE2-038 C O1 | 50/50 | 15.96 MW | 15.96 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940532 | AE2-038 E O1 | 50/50 | 7.91 MW | 7.91 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939141 | AE2-000C C | 50/50 | 19.93 MW | 19.93 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939142 | AE2-000C E | 50/50 | 9.9 MW | 9.9 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.05 MW | 0.05 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.04 MW | 0.04 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.05 MW | 0.05 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.12 MW | 0.12 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.07 MW | 0.07 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.06 MW | 0.06 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.01 MW | 0.01 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.02 MW | 0.02 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.33 MW | 0.33 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.08 MW | 0.08 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.04 MW | 0.04 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.28 MW | 0.28 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.19 MW | 0.19 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
Details for 05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 936381 | AD2-048 C | Adder | 2.71 MW | 2.31 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 936382 | AD2-048 E | Adder | 1.35 MW | 1.15 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 945681 | AF1-233 C | Adder | 8.92 MW | 7.58 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 945682 | AF1-233 E | Adder | 4.41 MW | 3.75 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 945911 | AF1-256 C | Adder | 2.83 MW | 2.4 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 945912 | AF1-256 E | Adder | 1.88 MW | 1.6 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 940531 | AE2-038 C O1 | Adder | 3.32 MW | 2.82 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 940532 | AE2-038 E O1 | Adder | 1.64 MW | 1.4 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 926101 | AC1-089 C O1 | 50/50 | 39.87 MW | 39.87 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 926102 | AC1-089 E O1 | 50/50 | 65.05 MW | 65.05 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 939141 | AE2-000C C | Adder | 4.14 MW | 3.52 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 939142 | AE2-000C E | Adder | 2.06 MW | 1.75 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 251831 | Z1-080 BAT | Adder | 0.61 MW | 0.52 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | 918803 | AA1-099 BAT | Adder | 0.4 MW | 0.34 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.69 MW | 0.69 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 3.39 MW | 3.39 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.68 MW | 0.68 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.77 MW | 0.77 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.04 MW | 1.04 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 5.26 MW | 5.26 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.12 MW | 0.12 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.89 MW | 0.89 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.45 MW | 0.45 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P4_L34553-1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.94 MW | 1.94 MW |
Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 936381 | AD2-048 C | Adder | 12.75 MW | 10.84 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 936382 | AD2-048 E | Adder | 6.36 MW | 5.41 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 942411 | AE2-254 C O1 | Adder | 5.06 MW | 4.3 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 942412 | AE2-254 E O1 | Adder | 3.37 MW | 2.87 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 942591 | AE2-275 C O1 | Adder | 15.91 MW | 13.52 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 942592 | AE2-275 E O1 | Adder | 5.98 MW | 5.08 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 942891 | AE2-308 C O1 | Adder | 26.66 MW | 22.66 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 942892 | AE2-308 E O1 | Adder | 9.69 MW | 8.24 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 943111 | AE2-339 C | 50/50 | 7.46 MW | 7.46 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 943112 | AE2-339 E | 50/50 | 3.67 MW | 3.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 943701 | AF1-038 C | Adder | 3.79 MW | 3.22 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 943702 | AF1-038 E | Adder | 2.53 MW | 2.15 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 943821 | AF1-050 C | Adder | 3.37 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 943822 | AF1-050 E | Adder | 2.24 MW | 1.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 944151 | AF1-083 C O1 | Adder | 3.54 MW | 3.01 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 944152 | AF1-083 E O1 | Adder | 2.36 MW | 2.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 944511 | AF1-116 C | Adder | 8.46 MW | 7.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 944512 | AF1-116 E | Adder | 5.64 MW | 4.79 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 945681 | AF1-233 C | 50/50 | 63.1 MW | 63.1 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 945682 | AF1-233 E | 50/50 | 31.17 MW | 31.17 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 945911 | AF1-256 C | 50/50 | 20.25 MW | 20.25 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 945912 | AF1-256 E | 50/50 | 13.5 MW | 13.5 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 251968 | 08ZIMRHP | 50/50 | 51.23 MW | 51.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 251969 | 08ZIMRLP | 50/50 | 28.06 MW | 28.06 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 251970 | 08MELDL1 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 251971 | 08MELDL2 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 251972 | 08MELDL3 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 342942 | 1JKCT 10G | 50/50 | 3.82 MW | 3.82 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 342957 | 1SPURLK1G | 50/50 | 26.36 MW | 26.36 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 342960 | 1SPURLK2G | 50/50 | 50.12 MW | 50.12 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 342963 | 1SPURLK3G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 342966 | 1SPURLK4G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 939131 | AE1-143 C | Adder | 7.54 MW | 6.41 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 939132 | AE1-143 E | Adder | 3.74 MW | 3.17 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 940531 | AE2-038 C O1 | 50/50 | 21.95 MW | 21.95 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 940532 | AE2-038 E O1 | 50/50 | 10.87 MW | 10.87 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 941411 | AE2-138 C | 50/50 | 63.23 MW | 63.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 941412 | AE2-138 E | 50/50 | 23.39 MW | 23.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 941981 | AE2-210 C O1 | 50/50 | 21.79 MW | 21.79 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 941982 | AE2-210 E O1 | 50/50 | 8.2 MW | 8.2 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 938921 | AE1-120 | Adder | -5.78 MW | -4.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 925981 | AC1-074 C O1 | 50/50 | 15.78 MW | 15.78 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 925982 | AC1-074 E O1 | 50/50 | 6.76 MW | 6.76 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 926061 | AC1-085 C | Adder | -29.86 MW | -25.38 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 932551 | AC2-075 C | 50/50 | 3.75 MW | 3.75 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 932552 | AC2-075 E | 50/50 | 1.89 MW | 1.89 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 926951 | AC1-182 | 50/50 | 1.22 MW | 1.22 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 936571 | AD2-072 C O1 | Adder | 10.07 MW | 8.56 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 936572 | AD2-072 E O1 | Adder | 4.94 MW | 4.2 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 939141 | AE2-000C C | 50/50 | 27.41 MW | 27.41 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 939142 | AE2-000C E | 50/50 | 13.62 MW | 13.62 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | 943772 | AF1-045 BAT | Adder | 5.51 MW | 4.69 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.68 MW | 4.68 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 24.82 MW | 24.82 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.74 MW | 0.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.27 MW | 5.27 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 8.64 MW | 8.64 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 7.68 MW | 7.68 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 39.09 MW | 39.09 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.33 MW | 1.33 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.34 MW | 3.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.0 MW | 3.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 816_SILVERGROVE | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.21 MW | 10.21 MW |
Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 936381 | AD2-048 C | Adder | 12.71 MW | 10.81 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 936382 | AD2-048 E | Adder | 6.34 MW | 5.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 942411 | AE2-254 C O1 | Adder | 5.05 MW | 4.29 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 942412 | AE2-254 E O1 | Adder | 3.37 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 942591 | AE2-275 C O1 | Adder | 15.89 MW | 13.5 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 942592 | AE2-275 E O1 | Adder | 5.98 MW | 5.08 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 942891 | AE2-308 C O1 | Adder | 26.63 MW | 22.63 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 942892 | AE2-308 E O1 | Adder | 9.68 MW | 8.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 943111 | AE2-339 C | 50/50 | 7.45 MW | 7.45 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 943112 | AE2-339 E | 50/50 | 3.67 MW | 3.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 943701 | AF1-038 C | Adder | 3.78 MW | 3.21 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 943702 | AF1-038 E | Adder | 2.52 MW | 2.14 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 943821 | AF1-050 C | Adder | 3.36 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 943822 | AF1-050 E | Adder | 2.24 MW | 1.9 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 944151 | AF1-083 C O1 | Adder | 3.53 MW | 3.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 944152 | AF1-083 E O1 | Adder | 2.35 MW | 2.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 944511 | AF1-116 C | Adder | 8.44 MW | 7.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 944512 | AF1-116 E | Adder | 5.63 MW | 4.78 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 945681 | AF1-233 C | 50/50 | 63.06 MW | 63.06 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 945682 | AF1-233 E | 50/50 | 31.15 MW | 31.15 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 945911 | AF1-256 C | 50/50 | 20.23 MW | 20.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 945912 | AF1-256 E | 50/50 | 13.49 MW | 13.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 251968 | 08ZIMRHP | 50/50 | 51.26 MW | 51.26 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 251969 | 08ZIMRLP | 50/50 | 28.07 MW | 28.07 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 251970 | 08MELDL1 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 251971 | 08MELDL2 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 251972 | 08MELDL3 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 342942 | 1JKCT 10G | 50/50 | 3.82 MW | 3.82 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 342957 | 1SPURLK1G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 342960 | 1SPURLK2G | 50/50 | 50.12 MW | 50.12 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 342963 | 1SPURLK3G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 342966 | 1SPURLK4G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 939131 | AE1-143 C | Adder | 7.53 MW | 6.4 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 939132 | AE1-143 E | Adder | 3.73 MW | 3.17 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 940531 | AE2-038 C O1 | 50/50 | 21.94 MW | 21.94 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 940532 | AE2-038 E O1 | 50/50 | 10.87 MW | 10.87 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 941411 | AE2-138 C | 50/50 | 63.18 MW | 63.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 941412 | AE2-138 E | 50/50 | 23.37 MW | 23.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 941981 | AE2-210 C O1 | 50/50 | 21.77 MW | 21.77 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 941982 | AE2-210 E O1 | 50/50 | 8.19 MW | 8.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 938921 | AE1-120 | Adder | -5.77 MW | -4.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 925981 | AC1-074 C O1 | 50/50 | 15.73 MW | 15.73 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 925982 | AC1-074 E O1 | 50/50 | 6.74 MW | 6.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 926061 | AC1-085 C | Adder | -29.85 MW | -25.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 932551 | AC2-075 C | 50/50 | 3.74 MW | 3.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 932552 | AC2-075 E | 50/50 | 1.88 MW | 1.88 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 926951 | AC1-182 | 50/50 | 1.22 MW | 1.22 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 936571 | AD2-072 C O1 | Adder | 10.05 MW | 8.54 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 936572 | AD2-072 E O1 | Adder | 4.93 MW | 4.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 939141 | AE2-000C C | 50/50 | 27.39 MW | 27.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 939142 | AE2-000C E | 50/50 | 13.61 MW | 13.61 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | 943772 | AF1-045 BAT | Adder | 5.5 MW | 4.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.67 MW | 4.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 24.76 MW | 24.76 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.74 MW | 0.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.26 MW | 5.26 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 8.64 MW | 8.64 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 7.65 MW | 7.65 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 38.99 MW | 38.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.33 MW | 1.33 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.27 MW | 3.27 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.99 MW | 2.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1493_RED BANK | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.17 MW | 10.17 MW |
Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 936381 | AD2-048 C | Adder | 12.71 MW | 10.81 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 936382 | AD2-048 E | Adder | 6.34 MW | 5.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 942411 | AE2-254 C O1 | Adder | 5.05 MW | 4.29 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 942412 | AE2-254 E O1 | Adder | 3.37 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 942591 | AE2-275 C O1 | Adder | 15.89 MW | 13.5 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 942592 | AE2-275 E O1 | Adder | 5.98 MW | 5.08 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 942891 | AE2-308 C O1 | Adder | 26.63 MW | 22.63 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 942892 | AE2-308 E O1 | Adder | 9.68 MW | 8.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 943111 | AE2-339 C | 50/50 | 7.45 MW | 7.45 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 943112 | AE2-339 E | 50/50 | 3.67 MW | 3.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 943701 | AF1-038 C | Adder | 3.78 MW | 3.21 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 943702 | AF1-038 E | Adder | 2.52 MW | 2.14 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 943821 | AF1-050 C | Adder | 3.36 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 943822 | AF1-050 E | Adder | 2.24 MW | 1.9 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 944151 | AF1-083 C O1 | Adder | 3.53 MW | 3.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 944152 | AF1-083 E O1 | Adder | 2.35 MW | 2.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 944511 | AF1-116 C | Adder | 8.44 MW | 7.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 944512 | AF1-116 E | Adder | 5.63 MW | 4.78 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 945681 | AF1-233 C | 50/50 | 63.06 MW | 63.06 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 945682 | AF1-233 E | 50/50 | 31.15 MW | 31.15 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 945911 | AF1-256 C | 50/50 | 20.23 MW | 20.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 945912 | AF1-256 E | 50/50 | 13.49 MW | 13.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 251968 | 08ZIMRHP | 50/50 | 51.25 MW | 51.25 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 251969 | 08ZIMRLP | 50/50 | 28.07 MW | 28.07 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 251970 | 08MELDL1 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 251971 | 08MELDL2 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 251972 | 08MELDL3 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 342942 | 1JKCT 10G | 50/50 | 3.82 MW | 3.82 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 342957 | 1SPURLK1G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 342960 | 1SPURLK2G | 50/50 | 50.12 MW | 50.12 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 342963 | 1SPURLK3G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 342966 | 1SPURLK4G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 939131 | AE1-143 C | Adder | 7.53 MW | 6.4 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 939132 | AE1-143 E | Adder | 3.73 MW | 3.17 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 940531 | AE2-038 C O1 | 50/50 | 21.94 MW | 21.94 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 940532 | AE2-038 E O1 | 50/50 | 10.87 MW | 10.87 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 941411 | AE2-138 C | 50/50 | 63.18 MW | 63.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 941412 | AE2-138 E | 50/50 | 23.37 MW | 23.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 941981 | AE2-210 C O1 | 50/50 | 21.77 MW | 21.77 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 941982 | AE2-210 E O1 | 50/50 | 8.19 MW | 8.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 938921 | AE1-120 | Adder | -5.77 MW | -4.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 925981 | AC1-074 C O1 | 50/50 | 15.73 MW | 15.73 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 925982 | AC1-074 E O1 | 50/50 | 6.74 MW | 6.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 926061 | AC1-085 C | Adder | -29.85 MW | -25.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 932551 | AC2-075 C | 50/50 | 3.74 MW | 3.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 932552 | AC2-075 E | 50/50 | 1.88 MW | 1.88 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 926951 | AC1-182 | 50/50 | 1.22 MW | 1.22 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 936571 | AD2-072 C O1 | Adder | 10.05 MW | 8.54 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 936572 | AD2-072 E O1 | Adder | 4.93 MW | 4.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 939141 | AE2-000C C | 50/50 | 27.39 MW | 27.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 939142 | AE2-000C E | 50/50 | 13.61 MW | 13.61 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | 943772 | AF1-045 BAT | Adder | 5.5 MW | 4.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.67 MW | 4.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 24.76 MW | 24.76 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.74 MW | 0.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.26 MW | 5.26 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 8.64 MW | 8.64 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 7.65 MW | 7.65 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 38.99 MW | 38.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.33 MW | 1.33 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.27 MW | 3.27 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.99 MW | 2.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1487_RED BANK | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.17 MW | 10.17 MW |
Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 936381 | AD2-048 C | Adder | 12.72 MW | 10.81 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 936382 | AD2-048 E | Adder | 6.34 MW | 5.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 942411 | AE2-254 C O1 | Adder | 5.05 MW | 4.29 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 942412 | AE2-254 E O1 | Adder | 3.37 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 942591 | AE2-275 C O1 | Adder | 15.89 MW | 13.51 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 942592 | AE2-275 E O1 | Adder | 5.98 MW | 5.08 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 942891 | AE2-308 C O1 | Adder | 26.63 MW | 22.63 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 942892 | AE2-308 E O1 | Adder | 9.68 MW | 8.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 943111 | AE2-339 C | 50/50 | 7.45 MW | 7.45 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 943112 | AE2-339 E | 50/50 | 3.67 MW | 3.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 943701 | AF1-038 C | Adder | 3.78 MW | 3.21 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 943702 | AF1-038 E | Adder | 2.52 MW | 2.14 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 943821 | AF1-050 C | Adder | 3.36 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 943822 | AF1-050 E | Adder | 2.24 MW | 1.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 944151 | AF1-083 C O1 | Adder | 3.53 MW | 3.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 944152 | AF1-083 E O1 | Adder | 2.35 MW | 2.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 944511 | AF1-116 C | Adder | 8.44 MW | 7.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 944512 | AF1-116 E | Adder | 5.63 MW | 4.79 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 945681 | AF1-233 C | 50/50 | 63.06 MW | 63.06 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 945682 | AF1-233 E | 50/50 | 31.15 MW | 31.15 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 945911 | AF1-256 C | 50/50 | 20.23 MW | 20.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 945912 | AF1-256 E | 50/50 | 13.49 MW | 13.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 251968 | 08ZIMRHP | 50/50 | 51.25 MW | 51.25 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 251969 | 08ZIMRLP | 50/50 | 28.06 MW | 28.06 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 251970 | 08MELDL1 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 251971 | 08MELDL2 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 251972 | 08MELDL3 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 342942 | 1JKCT 10G | 50/50 | 3.82 MW | 3.82 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 342957 | 1SPURLK1G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 342960 | 1SPURLK2G | 50/50 | 50.12 MW | 50.12 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 342963 | 1SPURLK3G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 342966 | 1SPURLK4G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 939131 | AE1-143 C | Adder | 7.53 MW | 6.4 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 939132 | AE1-143 E | Adder | 3.73 MW | 3.17 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 940531 | AE2-038 C O1 | 50/50 | 21.94 MW | 21.94 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 940532 | AE2-038 E O1 | 50/50 | 10.87 MW | 10.87 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 941411 | AE2-138 C | 50/50 | 63.18 MW | 63.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 941412 | AE2-138 E | 50/50 | 23.37 MW | 23.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 941981 | AE2-210 C O1 | 50/50 | 21.77 MW | 21.77 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 941982 | AE2-210 E O1 | 50/50 | 8.19 MW | 8.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 938921 | AE1-120 | Adder | -5.77 MW | -4.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 925981 | AC1-074 C O1 | 50/50 | 15.73 MW | 15.73 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 925982 | AC1-074 E O1 | 50/50 | 6.74 MW | 6.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 926061 | AC1-085 C | Adder | -29.85 MW | -25.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 932551 | AC2-075 C | 50/50 | 3.74 MW | 3.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 932552 | AC2-075 E | 50/50 | 1.88 MW | 1.88 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 926951 | AC1-182 | 50/50 | 1.22 MW | 1.22 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 936571 | AD2-072 C O1 | Adder | 10.05 MW | 8.54 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 936572 | AD2-072 E O1 | Adder | 4.93 MW | 4.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 939141 | AE2-000C C | 50/50 | 27.39 MW | 27.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 939142 | AE2-000C E | 50/50 | 13.61 MW | 13.61 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | 943772 | AF1-045 BAT | Adder | 5.5 MW | 4.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.67 MW | 4.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 24.76 MW | 24.76 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.74 MW | 0.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.26 MW | 5.26 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 8.64 MW | 8.64 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 7.65 MW | 7.65 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 38.99 MW | 38.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.33 MW | 1.33 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.27 MW | 3.27 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.99 MW | 2.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P2-3_C2 1441_ZIMMER | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.16 MW | 10.16 MW |
Details for 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945681 | AF1-233 C | 50/50 | 79.69 MW | 79.69 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945682 | AF1-233 E | 50/50 | 39.37 MW | 39.37 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945911 | AF1-256 C | 50/50 | 25.4 MW | 25.4 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945912 | AF1-256 E | 50/50 | 16.93 MW | 16.93 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940531 | AE2-038 C O1 | 50/50 | 25.62 MW | 25.62 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940532 | AE2-038 E O1 | 50/50 | 12.69 MW | 12.69 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939141 | AE2-000C C | 50/50 | 31.98 MW | 31.98 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939142 | AE2-000C E | 50/50 | 15.9 MW | 15.9 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.12 MW | 0.12 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.05 MW | 0.05 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.09 MW | 0.09 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.24 MW | 0.24 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.22 MW | 0.22 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.02 MW | 0.02 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.03 MW | 0.03 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.43 MW | 0.43 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.07 MW | 0.07 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.35 MW | 0.35 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.42 MW | 0.42 MW |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
Details for 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 936381 | AD2-048 C | Adder | 2.69 MW | 2.29 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 936382 | AD2-048 E | Adder | 1.34 MW | 1.14 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945681 | AF1-233 C | 50/50 | 88.93 MW | 88.93 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945682 | AF1-233 E | 50/50 | 43.93 MW | 43.93 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945911 | AF1-256 C | 50/50 | 28.34 MW | 28.34 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945912 | AF1-256 E | 50/50 | 18.89 MW | 18.89 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940531 | AE2-038 C O1 | 50/50 | 28.41 MW | 28.41 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940532 | AE2-038 E O1 | 50/50 | 14.07 MW | 14.07 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939141 | AE2-000C C | 50/50 | 35.48 MW | 35.48 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939142 | AE2-000C E | 50/50 | 17.63 MW | 17.63 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.08 MW | 0.08 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.35 MW | 0.35 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.04 MW | 0.04 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.11 MW | 0.11 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.4 MW | 0.4 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.02 MW | 0.02 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.47 MW | 0.47 MW |
Details for 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 936381 | AD2-048 C | Adder | 2.69 MW | 2.29 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 936382 | AD2-048 E | Adder | 1.34 MW | 1.14 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945681 | AF1-233 C | 50/50 | 88.93 MW | 88.93 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945682 | AF1-233 E | 50/50 | 43.93 MW | 43.93 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945911 | AF1-256 C | 50/50 | 28.34 MW | 28.34 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945912 | AF1-256 E | 50/50 | 18.89 MW | 18.89 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940531 | AE2-038 C O1 | 50/50 | 28.41 MW | 28.41 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940532 | AE2-038 E O1 | 50/50 | 14.07 MW | 14.07 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939141 | AE2-000C C | 50/50 | 35.48 MW | 35.48 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939142 | AE2-000C E | 50/50 | 17.63 MW | 17.63 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.08 MW | 0.08 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.35 MW | 0.35 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.04 MW | 0.04 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.11 MW | 0.11 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.4 MW | 0.4 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.02 MW | 0.02 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.47 MW | 0.47 MW |
Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 936381 | AD2-048 C | 80/20 | 11.99 MW | 11.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 942411 | AE2-254 C O1 | 80/20 | 4.81 MW | 4.81 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 942591 | AE2-275 C O1 | 80/20 | 14.92 MW | 14.92 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 942891 | AE2-308 C O1 | 80/20 | 25.02 MW | 25.02 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 943111 | AE2-339 C | 80/20 | 6.99 MW | 6.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 943701 | AF1-038 C | Adder | 3.65 MW | 3.1 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 943821 | AF1-050 C | Adder | 3.28 MW | 2.79 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 944151 | AF1-083 C O1 | Adder | 3.43 MW | 2.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 944511 | AF1-116 C | Adder | 8.16 MW | 6.94 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 945681 | AF1-233 C | 80/20 | 58.41 MW | 58.41 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 945911 | AF1-256 C | 80/20 | 18.74 MW | 18.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 251968 | 08ZIMRHP | 80/20 | 33.94 MW | 33.94 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 251969 | 08ZIMRLP | 80/20 | 18.59 MW | 18.59 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 251970 | 08MELDL1 | 80/20 | 1.94 MW | 1.94 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 251971 | 08MELDL2 | 80/20 | 1.94 MW | 1.94 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 251972 | 08MELDL3 | 80/20 | 1.94 MW | 1.94 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342903 | 1COOPER2 G | 80/20 | 4.78 MW | 4.78 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342918 | 1JKCT 1G | 80/20 | 4.88 MW | 4.88 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342921 | 1JKCT 2G | 80/20 | 3.45 MW | 3.45 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342924 | 1JKCT 3G | 80/20 | 4.88 MW | 4.88 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342927 | 1JKCT 4G | 80/20 | 3.24 MW | 3.24 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342930 | 1JKCT 5G | 80/20 | 3.22 MW | 3.22 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342933 | 1JKCT 6G | 80/20 | 3.24 MW | 3.24 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342936 | 1JKCT 7G | 80/20 | 3.24 MW | 3.24 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342939 | 1JKCT 9G | 80/20 | 3.57 MW | 3.57 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342942 | 1JKCT 10G | 80/20 | 3.57 MW | 3.57 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342945 | 1LAUREL 1G | 80/20 | 1.63 MW | 1.63 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342957 | 1SPURLK1G | 80/20 | 24.36 MW | 24.36 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342960 | 1SPURLK2G | 80/20 | 46.23 MW | 46.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342963 | 1SPURLK3G | 80/20 | 24.29 MW | 24.29 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 342966 | 1SPURLK4G | 80/20 | 24.29 MW | 24.29 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 939131 | AE1-143 C | Adder | 7.28 MW | 6.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 940531 | AE2-038 C O1 | 80/20 | 20.33 MW | 20.33 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 941411 | AE2-138 C | 80/20 | 58.86 MW | 58.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 941981 | AE2-210 C O1 | 80/20 | 20.28 MW | 20.28 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 938921 | AE1-120 | Adder | -6.13 MW | -5.21 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 925981 | AC1-074 C O1 | 80/20 | 14.86 MW | 14.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 926061 | AC1-085 C | Adder | -32.18 MW | -27.36 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 932551 | AC2-075 C | 80/20 | 3.53 MW | 3.53 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 926951 | AC1-182 | 80/20 | 0.81 MW | 0.81 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 936571 | AD2-072 C O1 | 80/20 | 9.65 MW | 9.65 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | 939141 | AE2-000C C | 80/20 | 25.39 MW | 25.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.48 MW | 0.48 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.77 MW | 4.77 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 26.52 MW | 26.52 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.73 MW | 0.73 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.3 MW | 5.3 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 7.59 MW | 7.59 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 39.47 MW | 39.47 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.16 MW | 2.16 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.44 MW | 3.44 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o Base Case | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 13.8 MW | 13.8 MW |
Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 936381 | AD2-048 C | 80/20 | 12.71 MW | 12.71 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 942411 | AE2-254 C O1 | 80/20 | 5.05 MW | 5.05 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 942591 | AE2-275 C O1 | 80/20 | 15.89 MW | 15.89 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 942891 | AE2-308 C O1 | 80/20 | 26.63 MW | 26.63 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 943111 | AE2-339 C | 80/20 | 7.45 MW | 7.45 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 943701 | AF1-038 C | Adder | 3.78 MW | 3.21 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 943821 | AF1-050 C | Adder | 3.36 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 944151 | AF1-083 C O1 | Adder | 3.53 MW | 3.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 944511 | AF1-116 C | Adder | 8.44 MW | 7.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 945681 | AF1-233 C | 80/20 | 63.06 MW | 63.06 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 945911 | AF1-256 C | 80/20 | 20.23 MW | 20.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 251968 | 08ZIMRHP | 80/20 | 51.25 MW | 51.25 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 251969 | 08ZIMRLP | 80/20 | 28.06 MW | 28.06 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 251970 | 08MELDL1 | 80/20 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 251971 | 08MELDL2 | 80/20 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 251972 | 08MELDL3 | 80/20 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342903 | 1COOPER2 G | 80/20 | 4.99 MW | 4.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342918 | 1JKCT 1G | 80/20 | 5.21 MW | 5.21 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342921 | 1JKCT 2G | 80/20 | 3.68 MW | 3.68 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342924 | 1JKCT 3G | 80/20 | 5.21 MW | 5.21 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342927 | 1JKCT 4G | 80/20 | 3.46 MW | 3.46 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342930 | 1JKCT 5G | 80/20 | 3.44 MW | 3.44 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342933 | 1JKCT 6G | 80/20 | 3.46 MW | 3.46 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342936 | 1JKCT 7G | 80/20 | 3.46 MW | 3.46 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342939 | 1JKCT 9G | 80/20 | 3.82 MW | 3.82 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342942 | 1JKCT 10G | 80/20 | 3.82 MW | 3.82 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342945 | 1LAUREL 1G | 80/20 | 1.71 MW | 1.71 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342957 | 1SPURLK1G | 80/20 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342960 | 1SPURLK2G | 80/20 | 50.12 MW | 50.12 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342963 | 1SPURLK3G | 80/20 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 342966 | 1SPURLK4G | 80/20 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 939131 | AE1-143 C | Adder | 7.53 MW | 6.4 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 940531 | AE2-038 C O1 | 80/20 | 21.94 MW | 21.94 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 941411 | AE2-138 C | 80/20 | 63.18 MW | 63.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 941981 | AE2-210 C O1 | 80/20 | 21.77 MW | 21.77 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 938921 | AE1-120 | Adder | -5.77 MW | -4.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 925981 | AC1-074 C O1 | 80/20 | 15.73 MW | 15.73 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 926061 | AC1-085 C | Adder | -29.85 MW | -25.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 932551 | AC2-075 C | 80/20 | 3.74 MW | 3.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 926951 | AC1-182 | 80/20 | 1.22 MW | 1.22 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 936571 | AD2-072 C O1 | 80/20 | 10.05 MW | 10.05 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | 939141 | AE2-000C C | 80/20 | 27.39 MW | 27.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.67 MW | 4.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 24.76 MW | 24.76 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.74 MW | 0.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.26 MW | 5.26 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 7.65 MW | 7.65 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 38.99 MW | 38.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.27 MW | 3.27 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.99 MW | 2.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P1-3_B3 SILVER GROVE 345/138 TB23* | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.16 MW | 10.16 MW |
Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 936381 | AD2-048 C | 80/20 | 12.52 MW | 12.52 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 942411 | AE2-254 C O1 | 80/20 | 5.0 MW | 5.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 942591 | AE2-275 C O1 | 80/20 | 15.58 MW | 15.58 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 942891 | AE2-308 C O1 | 80/20 | 26.12 MW | 26.12 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 943111 | AE2-339 C | 80/20 | 7.3 MW | 7.3 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 943701 | AF1-038 C | Adder | 3.77 MW | 3.21 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 943821 | AF1-050 C | Adder | 3.38 MW | 2.87 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 944151 | AF1-083 C O1 | Adder | 3.53 MW | 3.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 944511 | AF1-116 C | Adder | 8.43 MW | 7.17 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 945681 | AF1-233 C | 80/20 | 61.3 MW | 61.3 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 945911 | AF1-256 C | 80/20 | 19.67 MW | 19.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 251968 | 08ZIMRHP | 80/20 | 44.96 MW | 44.96 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 251969 | 08ZIMRLP | 80/20 | 24.62 MW | 24.62 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 251970 | 08MELDL1 | 80/20 | 2.35 MW | 2.35 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 251971 | 08MELDL2 | 80/20 | 2.35 MW | 2.35 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 251972 | 08MELDL3 | 80/20 | 2.36 MW | 2.36 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342903 | 1COOPER2 G | 80/20 | 4.96 MW | 4.96 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342918 | 1JKCT 1G | 80/20 | 5.1 MW | 5.1 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342921 | 1JKCT 2G | 80/20 | 3.61 MW | 3.61 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342924 | 1JKCT 3G | 80/20 | 5.1 MW | 5.1 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342927 | 1JKCT 4G | 80/20 | 3.38 MW | 3.38 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342930 | 1JKCT 5G | 80/20 | 3.37 MW | 3.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342933 | 1JKCT 6G | 80/20 | 3.38 MW | 3.38 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342936 | 1JKCT 7G | 80/20 | 3.38 MW | 3.38 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342939 | 1JKCT 9G | 80/20 | 3.74 MW | 3.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342942 | 1JKCT 10G | 80/20 | 3.74 MW | 3.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342945 | 1LAUREL 1G | 80/20 | 1.69 MW | 1.69 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342957 | 1SPURLK1G | 80/20 | 25.58 MW | 25.58 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342960 | 1SPURLK2G | 80/20 | 48.57 MW | 48.57 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342963 | 1SPURLK3G | 80/20 | 25.52 MW | 25.52 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 342966 | 1SPURLK4G | 80/20 | 25.52 MW | 25.52 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 939131 | AE1-143 C | Adder | 7.52 MW | 6.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 940531 | AE2-038 C O1 | 80/20 | 21.34 MW | 21.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 941411 | AE2-138 C | 80/20 | 61.64 MW | 61.64 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 941981 | AE2-210 C O1 | 80/20 | 21.24 MW | 21.24 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 938921 | AE1-120 | Adder | -6.2 MW | -5.27 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 925981 | AC1-074 C O1 | 80/20 | 15.52 MW | 15.52 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 926061 | AC1-085 C | Adder | -31.28 MW | -26.59 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 932551 | AC2-075 C | 80/20 | 3.69 MW | 3.69 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 926951 | AC1-182 | 80/20 | 1.07 MW | 1.07 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 936571 | AD2-072 C O1 | 80/20 | 9.99 MW | 9.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | 939141 | AE2-000C C | 80/20 | 26.64 MW | 26.64 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.43 MW | 0.43 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.82 MW | 4.82 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.5 MW | 0.5 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 26.18 MW | 26.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.75 MW | 0.75 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.38 MW | 5.38 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 7.8 MW | 7.8 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 40.01 MW | 40.01 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 4.33 MW | 4.33 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.28 MW | 3.28 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o PORT UNION-ZIMMER 4544 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.21 MW | 12.21 MW |
Details for 05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936381 | AD2-048 C | Adder | 3.64 MW | 3.1 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936382 | AD2-048 E | Adder | 1.82 MW | 1.55 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943111 | AE2-339 C | Adder | 1.35 MW | 1.15 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943112 | AE2-339 E | Adder | 0.67 MW | 0.57 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945681 | AF1-233 C | Adder | 13.79 MW | 11.72 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945682 | AF1-233 E | Adder | 6.81 MW | 5.79 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945911 | AF1-256 C | Adder | 4.39 MW | 3.73 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945912 | AF1-256 E | Adder | 2.93 MW | 2.49 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940531 | AE2-038 C O1 | Adder | 5.01 MW | 4.26 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940532 | AE2-038 E O1 | Adder | 2.48 MW | 2.11 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941411 | AE2-138 C | Adder | 10.52 MW | 8.95 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941412 | AE2-138 E | Adder | 3.89 MW | 3.31 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941981 | AE2-210 C O1 | Adder | 3.63 MW | 3.08 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941982 | AE2-210 E O1 | Adder | 1.36 MW | 1.16 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925981 | AC1-074 C O1 | Adder | 3.14 MW | 2.67 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925982 | AC1-074 E O1 | Adder | 1.35 MW | 1.14 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 926101 | AC1-089 C O1 | 50/50 | 40.27 MW | 40.27 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 926102 | AC1-089 E O1 | 50/50 | 65.71 MW | 65.71 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932551 | AC2-075 C | Adder | 0.75 MW | 0.63 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932552 | AC2-075 E | Adder | 0.38 MW | 0.32 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939141 | AE2-000C C | Adder | 6.25 MW | 5.32 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939142 | AE2-000C E | Adder | 3.11 MW | 2.64 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 251831 | Z1-080 BAT | Adder | 0.61 MW | 0.52 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 918803 | AA1-099 BAT | Adder | 0.41 MW | 0.35 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.93 MW | 0.93 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 4.52 MW | 4.52 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.02 MW | 1.02 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.85 MW | 0.85 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.82 MW | 1.82 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.61 MW | 7.61 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.13 MW | 0.13 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 1.92 MW | 1.92 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.53 MW | 0.53 MW |
05WLDCAT-05HILLSB 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.88 MW | 1.88 MW |
Details for 7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 936381 | AD2-048 C | Adder | 12.72 MW | 10.81 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 936382 | AD2-048 E | Adder | 6.34 MW | 5.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 942411 | AE2-254 C O1 | Adder | 5.05 MW | 4.29 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 942412 | AE2-254 E O1 | Adder | 3.37 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 942591 | AE2-275 C O1 | Adder | 15.89 MW | 13.51 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 942592 | AE2-275 E O1 | Adder | 5.98 MW | 5.08 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 942891 | AE2-308 C O1 | Adder | 26.63 MW | 22.64 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 942892 | AE2-308 E O1 | Adder | 9.68 MW | 8.23 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 943111 | AE2-339 C | 50/50 | 7.45 MW | 7.45 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 943112 | AE2-339 E | 50/50 | 3.67 MW | 3.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 943701 | AF1-038 C | Adder | 3.78 MW | 3.21 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 943702 | AF1-038 E | Adder | 2.52 MW | 2.14 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 943821 | AF1-050 C | Adder | 3.36 MW | 2.86 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 943822 | AF1-050 E | Adder | 2.24 MW | 1.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 944151 | AF1-083 C O1 | Adder | 3.53 MW | 3.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 944152 | AF1-083 E O1 | Adder | 2.35 MW | 2.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 944511 | AF1-116 C | Adder | 8.44 MW | 7.18 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 944512 | AF1-116 E | Adder | 5.63 MW | 4.79 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 945681 | AF1-233 C | 50/50 | 63.06 MW | 63.06 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 945682 | AF1-233 E | 50/50 | 31.16 MW | 31.16 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 945911 | AF1-256 C | 50/50 | 20.24 MW | 20.24 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 945912 | AF1-256 E | 50/50 | 13.49 MW | 13.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 251968 | 08ZIMRHP | 50/50 | 51.27 MW | 51.27 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 251969 | 08ZIMRLP | 50/50 | 28.07 MW | 28.07 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 251970 | 08MELDL1 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 251971 | 08MELDL2 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 251972 | 08MELDL3 | 50/50 | 2.6 MW | 2.6 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 342942 | 1JKCT 10G | 50/50 | 3.82 MW | 3.82 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 342957 | 1SPURLK1G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 342960 | 1SPURLK2G | 50/50 | 50.12 MW | 50.12 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 342963 | 1SPURLK3G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 342966 | 1SPURLK4G | 50/50 | 26.34 MW | 26.34 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 939131 | AE1-143 C | Adder | 7.53 MW | 6.4 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 939132 | AE1-143 E | Adder | 3.73 MW | 3.17 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 940531 | AE2-038 C O1 | 50/50 | 21.94 MW | 21.94 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 940532 | AE2-038 E O1 | 50/50 | 10.87 MW | 10.87 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 941411 | AE2-138 C | 50/50 | 63.19 MW | 63.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 941412 | AE2-138 E | 50/50 | 23.37 MW | 23.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 941981 | AE2-210 C O1 | 50/50 | 21.77 MW | 21.77 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 941982 | AE2-210 E O1 | 50/50 | 8.19 MW | 8.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 938921 | AE1-120 | Adder | -5.77 MW | -4.91 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 925981 | AC1-074 C O1 | 50/50 | 15.73 MW | 15.73 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 925982 | AC1-074 E O1 | 50/50 | 6.74 MW | 6.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 926061 | AC1-085 C | Adder | -29.84 MW | -25.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 932551 | AC2-075 C | 50/50 | 3.74 MW | 3.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 932552 | AC2-075 E | 50/50 | 1.88 MW | 1.88 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 926951 | AC1-182 | 50/50 | 1.22 MW | 1.22 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 936571 | AD2-072 C O1 | Adder | 10.05 MW | 8.54 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 936572 | AD2-072 E O1 | Adder | 4.93 MW | 4.19 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 939141 | AE2-000C C | 50/50 | 27.39 MW | 27.39 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 939142 | AE2-000C E | 50/50 | 13.62 MW | 13.62 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | 943772 | AF1-045 BAT | Adder | 5.5 MW | 4.68 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.67 MW | 4.67 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 24.77 MW | 24.77 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.74 MW | 0.74 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.26 MW | 5.26 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 8.64 MW | 8.64 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 7.65 MW | 7.65 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 39.0 MW | 39.0 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.33 MW | 1.33 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.26 MW | 3.26 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.99 MW | 2.99 MW |
7SPURLOCK-09STUART 345.0 kV Ckt 1 line l/o DEOK_P7-1_C5 CIRCUIT1883&4545REDBANKSILGRVZIMMER | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.18 MW | 10.18 MW |
Details for 4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936381 | AD2-048 C | 50/50 | 6.08 MW | 6.08 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936382 | AD2-048 E | 50/50 | 3.03 MW | 3.03 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942411 | AE2-254 C O1 | Adder | 1.66 MW | 1.41 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942412 | AE2-254 E O1 | Adder | 1.11 MW | 0.94 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942591 | AE2-275 C O1 | Adder | 4.74 MW | 4.03 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942592 | AE2-275 E O1 | Adder | 1.78 MW | 1.51 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942891 | AE2-308 C O1 | Adder | 8.15 MW | 6.93 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942892 | AE2-308 E O1 | Adder | 2.96 MW | 2.52 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943111 | AE2-339 C | Adder | 2.47 MW | 2.1 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943112 | AE2-339 E | Adder | 1.22 MW | 1.03 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945681 | AF1-233 C | 50/50 | 16.61 MW | 16.61 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945682 | AF1-233 E | 50/50 | 8.2 MW | 8.2 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945911 | AF1-256 C | 50/50 | 5.32 MW | 5.32 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945912 | AF1-256 E | 50/50 | 3.55 MW | 3.55 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342957 | 1SPURLK1G | 50/50 | 6.72 MW | 6.72 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342960 | 1SPURLK2G | 50/50 | 10.55 MW | 10.55 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342963 | 1SPURLK3G | 50/50 | 5.55 MW | 5.55 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342966 | 1SPURLK4G | 50/50 | 5.55 MW | 5.55 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940531 | AE2-038 C O1 | 50/50 | 5.87 MW | 5.87 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940532 | AE2-038 E O1 | 50/50 | 2.91 MW | 2.91 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941411 | AE2-138 C | Adder | 16.76 MW | 14.24 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941412 | AE2-138 E | Adder | 6.2 MW | 5.27 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941981 | AE2-210 C O1 | Adder | 5.77 MW | 4.91 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941982 | AE2-210 E O1 | Adder | 2.17 MW | 1.85 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925981 | AC1-074 C O1 | 50/50 | 9.26 MW | 9.26 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925982 | AC1-074 E O1 | 50/50 | 3.97 MW | 3.97 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932551 | AC2-075 C | 50/50 | 2.2 MW | 2.2 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932552 | AC2-075 E | 50/50 | 1.11 MW | 1.11 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936571 | AD2-072 C O1 | Adder | 3.47 MW | 2.95 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936572 | AD2-072 E O1 | Adder | 1.7 MW | 1.45 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939141 | AE2-000C C | 50/50 | 7.33 MW | 7.33 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939142 | AE2-000C E | 50/50 | 3.64 MW | 3.64 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.71 MW | 1.71 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.28 MW | 0.28 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.31 MW | 6.31 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.62 MW | 1.62 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.62 MW | 0.62 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 3.35 MW | 3.35 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.78 MW | 12.78 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.1 MW | 0.1 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.78 MW | 3.78 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.58 MW | 0.58 MW |
4BOONE CO-08LONGBR 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.85 MW | 0.85 MW |
Details for 4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936381 | AD2-048 C | Adder | 3.64 MW | 3.1 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936382 | AD2-048 E | Adder | 1.82 MW | 1.55 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943111 | AE2-339 C | Adder | 1.35 MW | 1.15 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943112 | AE2-339 E | Adder | 0.67 MW | 0.57 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945681 | AF1-233 C | Adder | 13.79 MW | 11.72 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945682 | AF1-233 E | Adder | 6.81 MW | 5.79 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945911 | AF1-256 C | Adder | 4.39 MW | 3.73 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945912 | AF1-256 E | Adder | 2.93 MW | 2.49 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940531 | AE2-038 C O1 | Adder | 5.01 MW | 4.26 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940532 | AE2-038 E O1 | Adder | 2.48 MW | 2.11 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941411 | AE2-138 C | Adder | 10.52 MW | 8.95 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941412 | AE2-138 E | Adder | 3.89 MW | 3.31 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941981 | AE2-210 C O1 | Adder | 3.63 MW | 3.08 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941982 | AE2-210 E O1 | Adder | 1.36 MW | 1.16 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925981 | AC1-074 C O1 | Adder | 3.14 MW | 2.67 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925982 | AC1-074 E O1 | Adder | 1.35 MW | 1.14 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932551 | AC2-075 C | Adder | 0.75 MW | 0.63 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932552 | AC2-075 E | Adder | 0.38 MW | 0.32 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939141 | AE2-000C C | Adder | 6.25 MW | 5.32 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939142 | AE2-000C E | Adder | 3.11 MW | 2.64 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 251831 | Z1-080 BAT | Adder | 0.61 MW | 0.52 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 918803 | AA1-099 BAT | Adder | 0.41 MW | 0.35 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.93 MW | 0.93 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 4.52 MW | 4.52 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.02 MW | 1.02 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.85 MW | 0.85 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.82 MW | 1.82 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.61 MW | 7.61 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.13 MW | 0.13 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 1.92 MW | 1.92 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.53 MW | 0.53 MW |
4KENTON-05SARDINIA 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.88 MW | 1.88 MW |
Details for 08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936381 | AD2-048 C | 50/50 | 6.08 MW | 6.08 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936382 | AD2-048 E | 50/50 | 3.03 MW | 3.03 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942411 | AE2-254 C O1 | Adder | 1.66 MW | 1.41 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942412 | AE2-254 E O1 | Adder | 1.11 MW | 0.94 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942591 | AE2-275 C O1 | Adder | 4.74 MW | 4.03 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942592 | AE2-275 E O1 | Adder | 1.78 MW | 1.51 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942891 | AE2-308 C O1 | Adder | 8.15 MW | 6.93 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942892 | AE2-308 E O1 | Adder | 2.96 MW | 2.52 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943111 | AE2-339 C | Adder | 2.47 MW | 2.1 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943112 | AE2-339 E | Adder | 1.22 MW | 1.03 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945681 | AF1-233 C | 50/50 | 16.61 MW | 16.61 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945682 | AF1-233 E | 50/50 | 8.2 MW | 8.2 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945911 | AF1-256 C | 50/50 | 5.32 MW | 5.32 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945912 | AF1-256 E | 50/50 | 3.55 MW | 3.55 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342957 | 1SPURLK1G | 50/50 | 6.72 MW | 6.72 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342960 | 1SPURLK2G | 50/50 | 10.55 MW | 10.55 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342963 | 1SPURLK3G | 50/50 | 5.55 MW | 5.55 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342966 | 1SPURLK4G | 50/50 | 5.55 MW | 5.55 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940531 | AE2-038 C O1 | 50/50 | 5.87 MW | 5.87 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940532 | AE2-038 E O1 | 50/50 | 2.91 MW | 2.91 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941411 | AE2-138 C | Adder | 16.76 MW | 14.24 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941412 | AE2-138 E | Adder | 6.2 MW | 5.27 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941981 | AE2-210 C O1 | Adder | 5.77 MW | 4.91 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941982 | AE2-210 E O1 | Adder | 2.17 MW | 1.85 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925981 | AC1-074 C O1 | 50/50 | 9.26 MW | 9.26 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925982 | AC1-074 E O1 | 50/50 | 3.97 MW | 3.97 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932551 | AC2-075 C | 50/50 | 2.2 MW | 2.2 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932552 | AC2-075 E | 50/50 | 1.11 MW | 1.11 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936571 | AD2-072 C O1 | Adder | 3.47 MW | 2.95 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936572 | AD2-072 E O1 | Adder | 1.7 MW | 1.45 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939141 | AE2-000C C | 50/50 | 7.33 MW | 7.33 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939142 | AE2-000C E | 50/50 | 3.64 MW | 3.64 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.71 MW | 1.71 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.28 MW | 0.28 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.31 MW | 6.31 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.62 MW | 1.62 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.62 MW | 0.62 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 3.35 MW | 3.35 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.78 MW | 12.78 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.1 MW | 0.1 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.78 MW | 3.78 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.58 MW | 0.58 MW |
08LONGBR-08MTZION 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.85 MW | 0.85 MW |
Details for 05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936381 | AD2-048 C | Adder | 3.64 MW | 3.1 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936382 | AD2-048 E | Adder | 1.82 MW | 1.55 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943111 | AE2-339 C | Adder | 1.35 MW | 1.15 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943112 | AE2-339 E | Adder | 0.67 MW | 0.57 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945681 | AF1-233 C | Adder | 13.79 MW | 11.72 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945682 | AF1-233 E | Adder | 6.81 MW | 5.79 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945911 | AF1-256 C | Adder | 4.39 MW | 3.73 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945912 | AF1-256 E | Adder | 2.93 MW | 2.49 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940531 | AE2-038 C O1 | Adder | 5.01 MW | 4.26 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940532 | AE2-038 E O1 | Adder | 2.48 MW | 2.11 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941411 | AE2-138 C | Adder | 10.52 MW | 8.95 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941412 | AE2-138 E | Adder | 3.89 MW | 3.31 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941981 | AE2-210 C O1 | Adder | 3.63 MW | 3.08 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941982 | AE2-210 E O1 | Adder | 1.36 MW | 1.16 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925981 | AC1-074 C O1 | Adder | 3.14 MW | 2.67 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925982 | AC1-074 E O1 | Adder | 1.35 MW | 1.14 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932551 | AC2-075 C | Adder | 0.75 MW | 0.63 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932552 | AC2-075 E | Adder | 0.38 MW | 0.32 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939141 | AE2-000C C | Adder | 6.25 MW | 5.32 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939142 | AE2-000C E | Adder | 3.11 MW | 2.64 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 251831 | Z1-080 BAT | Adder | 0.61 MW | 0.52 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 918803 | AA1-099 BAT | Adder | 0.41 MW | 0.35 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.93 MW | 0.93 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 4.52 MW | 4.52 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.02 MW | 1.02 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.85 MW | 0.85 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.82 MW | 1.82 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.61 MW | 7.61 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.13 MW | 0.13 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 1.92 MW | 1.92 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.53 MW | 0.53 MW |
05SARDINIA-05EMERSS 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.88 MW | 1.88 MW |
Details for 05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936381 | AD2-048 C | Adder | 3.64 MW | 3.1 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936382 | AD2-048 E | Adder | 1.82 MW | 1.55 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943111 | AE2-339 C | Adder | 1.35 MW | 1.15 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943112 | AE2-339 E | Adder | 0.67 MW | 0.57 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945681 | AF1-233 C | Adder | 13.79 MW | 11.72 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945682 | AF1-233 E | Adder | 6.81 MW | 5.79 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945911 | AF1-256 C | Adder | 4.39 MW | 3.73 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945912 | AF1-256 E | Adder | 2.93 MW | 2.49 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940531 | AE2-038 C O1 | Adder | 5.01 MW | 4.26 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940532 | AE2-038 E O1 | Adder | 2.48 MW | 2.11 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941411 | AE2-138 C | Adder | 10.52 MW | 8.95 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941412 | AE2-138 E | Adder | 3.89 MW | 3.31 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941981 | AE2-210 C O1 | Adder | 3.63 MW | 3.08 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941982 | AE2-210 E O1 | Adder | 1.36 MW | 1.16 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925981 | AC1-074 C O1 | Adder | 3.14 MW | 2.67 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925982 | AC1-074 E O1 | Adder | 1.35 MW | 1.14 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932551 | AC2-075 C | Adder | 0.75 MW | 0.63 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932552 | AC2-075 E | Adder | 0.38 MW | 0.32 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939141 | AE2-000C C | Adder | 6.25 MW | 5.32 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939142 | AE2-000C E | Adder | 3.11 MW | 2.64 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 251831 | Z1-080 BAT | Adder | 0.61 MW | 0.52 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 918803 | AA1-099 BAT | Adder | 0.41 MW | 0.35 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.93 MW | 0.93 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 4.52 MW | 4.52 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.02 MW | 1.02 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.85 MW | 0.85 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.82 MW | 1.82 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.61 MW | 7.61 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.13 MW | 0.13 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 1.92 MW | 1.92 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.53 MW | 0.53 MW |
05EMERSS-05WLDCAT 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.88 MW | 1.88 MW |
Details for 4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943111 | AE2-339 C | Adder | 1.34 MW | 1.14 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943112 | AE2-339 E | Adder | 0.66 MW | 0.56 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945681 | AF1-233 C | Adder | 13.66 MW | 11.61 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945682 | AF1-233 E | Adder | 6.75 MW | 5.74 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945911 | AF1-256 C | Adder | 4.49 MW | 3.82 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945912 | AF1-256 E | Adder | 2.99 MW | 2.54 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342957 | 1SPURLK1G | 50/50 | 8.46 MW | 8.46 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342960 | 1SPURLK2G | 50/50 | 12.3 MW | 12.3 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342963 | 1SPURLK3G | 50/50 | 6.46 MW | 6.46 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342966 | 1SPURLK4G | 50/50 | 6.46 MW | 6.46 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940531 | AE2-038 C O1 | Adder | 4.13 MW | 3.51 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940532 | AE2-038 E O1 | Adder | 2.05 MW | 1.74 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941411 | AE2-138 C | Adder | 13.12 MW | 11.15 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941412 | AE2-138 E | Adder | 4.85 MW | 4.12 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941981 | AE2-210 C O1 | Adder | 4.52 MW | 3.84 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941982 | AE2-210 E O1 | Adder | 1.7 MW | 1.45 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925981 | AC1-074 C O1 | Adder | 2.88 MW | 2.45 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925982 | AC1-074 E O1 | Adder | 1.23 MW | 1.05 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932551 | AC2-075 C | Adder | 0.68 MW | 0.58 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932552 | AC2-075 E | Adder | 0.34 MW | 0.29 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939141 | AE2-000C C | Adder | 5.16 MW | 4.38 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939142 | AE2-000C E | Adder | 2.56 MW | 2.18 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.33 MW | 0.33 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 2.15 MW | 2.15 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.89 MW | 0.89 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.95 MW | 0.95 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.93 MW | 3.93 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.14 MW | 0.14 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 1.08 MW | 1.08 MW |
4SPUR-KENT-R-4KENTON 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.18 MW | 0.18 MW |
Details for 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945681 | AF1-233 C | Adder | 8.66 MW | 7.36 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945682 | AF1-233 E | Adder | 4.28 MW | 3.64 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945911 | AF1-256 C | Adder | 2.71 MW | 2.3 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945912 | AF1-256 E | Adder | 1.81 MW | 1.54 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940531 | AE2-038 C O1 | Adder | 5.2 MW | 4.42 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940532 | AE2-038 E O1 | Adder | 2.57 MW | 2.19 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939141 | AE2-000C C | Adder | 6.49 MW | 5.51 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939142 | AE2-000C E | Adder | 3.22 MW | 2.74 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.03 MW | 0.03 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.01 MW | 0.01 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.03 MW | 0.03 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.04 MW | 0.04 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.12 MW | 0.12 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.01 MW | 0.01 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.01 MW | 0.01 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.1 MW | 0.1 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.14 MW | 0.14 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.02 MW | 0.02 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.02 MW | 0.02 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.16 MW | 0.16 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.08 MW | 0.08 MW |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o DAY_P734541 34553 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
Details for 4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943111 | AE2-339 C | Adder | 1.34 MW | 1.14 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943112 | AE2-339 E | Adder | 0.66 MW | 0.56 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945681 | AF1-233 C | Adder | 13.66 MW | 11.61 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945682 | AF1-233 E | Adder | 6.75 MW | 5.74 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945911 | AF1-256 C | Adder | 4.49 MW | 3.82 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945912 | AF1-256 E | Adder | 2.99 MW | 2.54 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342957 | 1SPURLK1G | 50/50 | 8.46 MW | 8.46 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342960 | 1SPURLK2G | 50/50 | 12.3 MW | 12.3 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342963 | 1SPURLK3G | 50/50 | 6.46 MW | 6.46 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342966 | 1SPURLK4G | 50/50 | 6.46 MW | 6.46 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940531 | AE2-038 C O1 | Adder | 4.13 MW | 3.51 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940532 | AE2-038 E O1 | Adder | 2.05 MW | 1.74 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941411 | AE2-138 C | Adder | 13.12 MW | 11.15 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941412 | AE2-138 E | Adder | 4.85 MW | 4.12 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941981 | AE2-210 C O1 | Adder | 4.52 MW | 3.84 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941982 | AE2-210 E O1 | Adder | 1.7 MW | 1.45 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925981 | AC1-074 C O1 | Adder | 2.88 MW | 2.45 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925982 | AC1-074 E O1 | Adder | 1.23 MW | 1.05 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932551 | AC2-075 C | Adder | 0.68 MW | 0.58 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932552 | AC2-075 E | Adder | 0.34 MW | 0.29 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939141 | AE2-000C C | Adder | 5.16 MW | 4.38 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939142 | AE2-000C E | Adder | 2.56 MW | 2.18 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.33 MW | 0.33 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 2.15 MW | 2.15 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.89 MW | 0.89 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.95 MW | 0.95 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.93 MW | 3.93 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.14 MW | 0.14 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 1.08 MW | 1.08 MW |
4SPURLOCK-4SPUR-KENT-R 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.18 MW | 0.18 MW |
Details for 4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942891 | AE2-308 C O1 | Adder | 6.62 MW | 5.63 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942892 | AE2-308 E O1 | Adder | 2.41 MW | 2.05 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943111 | AE2-339 C | 50/50 | 4.8 MW | 4.8 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943112 | AE2-339 E | 50/50 | 2.36 MW | 2.36 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945681 | AF1-233 C | Adder | 8.03 MW | 6.83 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945682 | AF1-233 E | Adder | 3.97 MW | 3.37 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945911 | AF1-256 C | Adder | 2.58 MW | 2.19 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945912 | AF1-256 E | Adder | 1.72 MW | 1.46 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940531 | AE2-038 C O1 | Adder | 2.8 MW | 2.38 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940532 | AE2-038 E O1 | Adder | 1.38 MW | 1.18 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941411 | AE2-138 C | Adder | 17.13 MW | 14.56 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941412 | AE2-138 E | Adder | 6.33 MW | 5.38 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941981 | AE2-210 C O1 | Adder | 5.9 MW | 5.02 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941982 | AE2-210 E O1 | Adder | 2.22 MW | 1.89 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925981 | AC1-074 C O1 | Adder | 5.23 MW | 4.44 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925982 | AC1-074 E O1 | Adder | 2.24 MW | 1.9 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932551 | AC2-075 C | Adder | 1.24 MW | 1.05 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932552 | AC2-075 E | Adder | 0.62 MW | 0.53 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939141 | AE2-000C C | Adder | 3.49 MW | 2.97 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939142 | AE2-000C E | Adder | 1.74 MW | 1.48 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.27 MW | 0.27 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.01 MW | 0.01 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.55 MW | 0.55 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.23 MW | 0.23 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.05 MW | 0.05 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.07 MW | 0.07 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.16 MW | 0.16 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.04 MW | 0.04 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.2 MW | 1.2 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
4AVON-R-4LOUDON AVE 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
Details for 08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936381 | AD2-048 C | 50/50 | 6.08 MW | 6.08 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936382 | AD2-048 E | 50/50 | 3.03 MW | 3.03 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942411 | AE2-254 C O1 | Adder | 1.66 MW | 1.41 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942412 | AE2-254 E O1 | Adder | 1.11 MW | 0.94 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942591 | AE2-275 C O1 | Adder | 4.74 MW | 4.03 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942592 | AE2-275 E O1 | Adder | 1.78 MW | 1.51 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942891 | AE2-308 C O1 | Adder | 8.15 MW | 6.93 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 942892 | AE2-308 E O1 | Adder | 2.96 MW | 2.52 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943111 | AE2-339 C | Adder | 2.47 MW | 2.1 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 943112 | AE2-339 E | Adder | 1.22 MW | 1.03 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945681 | AF1-233 C | 50/50 | 16.61 MW | 16.61 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945682 | AF1-233 E | 50/50 | 8.2 MW | 8.2 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945911 | AF1-256 C | 50/50 | 5.32 MW | 5.32 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 945912 | AF1-256 E | 50/50 | 3.55 MW | 3.55 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342957 | 1SPURLK1G | 50/50 | 6.72 MW | 6.72 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342960 | 1SPURLK2G | 50/50 | 10.55 MW | 10.55 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342963 | 1SPURLK3G | 50/50 | 5.55 MW | 5.55 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 342966 | 1SPURLK4G | 50/50 | 5.55 MW | 5.55 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940531 | AE2-038 C O1 | 50/50 | 5.87 MW | 5.87 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 940532 | AE2-038 E O1 | 50/50 | 2.91 MW | 2.91 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941411 | AE2-138 C | Adder | 16.76 MW | 14.24 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941412 | AE2-138 E | Adder | 6.2 MW | 5.27 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941981 | AE2-210 C O1 | Adder | 5.77 MW | 4.91 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 941982 | AE2-210 E O1 | Adder | 2.17 MW | 1.85 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925981 | AC1-074 C O1 | 50/50 | 9.26 MW | 9.26 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 925982 | AC1-074 E O1 | 50/50 | 3.97 MW | 3.97 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932551 | AC2-075 C | 50/50 | 2.2 MW | 2.2 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 932552 | AC2-075 E | 50/50 | 1.11 MW | 1.11 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936571 | AD2-072 C O1 | Adder | 3.47 MW | 2.95 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 936572 | AD2-072 E O1 | Adder | 1.7 MW | 1.45 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939141 | AE2-000C C | 50/50 | 7.33 MW | 7.33 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | 939142 | AE2-000C E | 50/50 | 3.64 MW | 3.64 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.71 MW | 1.71 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.28 MW | 0.28 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.31 MW | 6.31 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.62 MW | 1.62 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.62 MW | 0.62 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 3.35 MW | 3.35 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.78 MW | 12.78 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.1 MW | 0.1 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.78 MW | 3.78 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.58 MW | 0.58 MW |
08MTZION-08BUFTN1 138.0 kV Ckt 1 line l/o DAY_P734541 34553 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.85 MW | 0.85 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
System Reinforcements | |||
---|---|---|---|
RTEP ID | Title | Total Cost | |
n5472 | A Sag Study will be required on the 10 miles ofACSR ~ 477 ~ 26/7 ~ HA [...] n time would be 24 to 36 months after signing an interconnection agreement. | $186,000 | |
n5857 | Rebuild / reconductor 10 miles of ACSR ~ 477 ~ 26/7 ~ HAWK- Conductor Section 1. Estimated cost: $15 million. | $15,040,000 | |
n6461 | A Sag Study will be required on the 24 miles ofACSR ~ 477 ~ 26/7 ~ HA [...] n time would be 24 to 36 months after signing an interconnection agreement. | $96,000 | |
n8066 | Rebuild the line and Substation Bus Conductor on the Buffington terminal at Mt. Zion, Replace equipment at Buffington | $5,264,470 | |
n6460.1 | Increase the EKPC-owned 3.7 miles of conductor MOT to 275 degrees F. | $400,000 | |
n6463.2 | Upgrade bus and jumpers associated with Boone 138 kV bus using 2-500 MCM 37 CU conductor or equivalent | $170,000 | |
n6463.1 | Increase MOT of Boone-Longbranch 138kV line section 954 MCM conductor to 275F (~2.25 miles) | $200,000 | |
(TBD) | Line is 100% owned by EKPC. No DEOK upgrade required. | $0 | |
n5780.2 | Reconductor Stuart substation conductor with twin bundle 1033 Curlew ACCR conductor Reconductor Stuart Substation conductor with a bundled 795 hi-temperature conductor. | $250,000 | |
n5780.3 | Replace the 1500A interconnection metering CTs with 2000A equipment. | $150,000 | |
n5780.4 | Replace the 3000A wave trap with 3600A equipment. | $170,000 | |
n5780.5 | A second new 345kV transmission line between Stuart and Spurlock. Accordin [...] EKPC will need to provide the estimates of this line on the Kentucky side. | $21,590,000 | |
n5780 | Reconductor Stuart-Spurlock line with twin bundle 1033 Curlew ACCR conductor. | $17,000,000 | |
n5780.1 | Replace Stuart substation riser conductor with 2500AAC (parallel) | $100,000 | |
n6480.1 | Rebuild the Plumville-Murphysville 69 kV line section using 795 MCM ACSR conductor at 212 degrees F (9.9 miles) | $8,140,000 | |
n6480.2 | Replace the 4/0 copper bus and jumpers at the Murphysville substation using 750 MCM copper or equivalent | $120,000 | |
n6480.3 | Replace the 4/0 copper bus and jumpers at the Plumville substation using 750 MCM copper or equivalent | $120,000 | |
n6480.4 | Replace the 600A disconnect switches N34-613 and N34-615 at the Plumville substation with 1200A equipment | $100,000 | |
n6480.5 | Change the Zone 3 relay setting at Murphysville associated with the line protection to at least 108 MVA LTE rating. | $0 | |
n6480 | Increase the maximum operating temperature of the 266 MCM ACSR conductor in the Murphysville-Plumville 69 kV line section to 266 degrees F (9.9 miles) | $650,000 | |
n6828 | Increase the maximum operating temperature of the 795 MCM ACSR conductor in the Goddard-Cranston 138 kV line section to 275 degrees F (12.7 miles) | $1,150,000 | |
n6829 | Increase the maximum operating temperature of the 795 MCM ACSR conductor in the Cranston-Rowan County 138 kV line section to 275 degrees F (7.5 miles) | $680,000 | |
b2827 | Upgrade Spurlock-KU Kenton 138kv series reactor from 1200A at 5% impedance to 1600A at 6.5% impedance. | $0 | |
n7617 | Increase the maximum operating temperature of the 795 MCM ACSR conductor in the Spurlock-Kenton 138 kV line section to 275 degrees F (4.4 miles) | $400,000 | |
(TBD) | LGEE violation (non PJM area). EKPC emergency rating is 281 MVA. The extern [...] Owner, LGEE, will not evaluate this violation until the facility study phase. | $0 | |
n6827 | Replace the 800A wave trap at Rodburn substation with 1200A equipment. | $90,000 | |
(TBD) | LGEE violation (non PJM area). EKPC emergency rating at 255 MVA The extern [...] Owner, LGEE, will not evaluate this violation until the facility study phase. | $0 | |
n8402.1 | Replace the 1200A wave trap at Spurlock substation with 2000A equipment. | $110,000 |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF1-256 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.